ADOPTS WITH AMENDMENTS:

International Residential Code 2015 (IRC 2015)

Part I — Administrative

Part II — Definitions

Part III — Building Planning and Construction

Part IV — Energy Conservation

Part V — Mechanical

Part VI — Fuel Gas

Part VII — Plumbing

Part VIII — Electrical

Part IX — Referenced Standards

Heads up: There are no amended sections in this chapter.

Appendix J Existing Buildings and Structures

AMENDMENT
This section has been amended at the state or city level.
(Adopted as modified herein)

AJ101.1 General

AMENDMENT
This section has been amended at the state or city level.
The purpose of Appendix J is to encourage the continued use or reuse of legally existing buildings and structures. The provisions of Appendix J are intended to permit work in existing buildings that is consistent with the purpose of 780 CMR 51.00. Compliance with these provisions shall be deemed to meet the requirements of 780 CMR 51.00.

Features of existing construction which do not meet the requirements of 780 CMR 51.00 for new construction shall be presumed to have met the regulations, codes or laws in effect at the time of construction or alteration and, if so, shall be deemed to be existing nonconforming. Unless stated otherwise, nothing in Appendix J shall require the upgrading or replacement of any existing nonconforming feature or component of an existing building, provided the feature, component or system is in serviceable condition. Components or features of an existing building which, in the opinion of the building official, are dangerous, unsafe, damaged, significantly deteriorated or which otherwise present a threat to occupants or to public safety shall be remediated in accordance with 780 CMR 51.00.

Any new building system or portion thereof shall conform to 780 CMR 51.00 for new construction to the fullest extent practicable. However, individual components of an existing building system may be repaired or replaced without requiring that system to comply fully with 780 CMR 51.00 unless specifically required by Appendix J.

For compliance of work governed by other codes, including the specialized codes, see section R101.4.
For purposes of this appendix, work in existing buildings shall be classified into the categories of repair, renovation, alteration and reconstruction. Specific requirements are established for each category of work in these provisions.
Work of more than one category shall be part of a single work project. Related work permitted within a 12-month period shall be considered to be a single work project. Where a project includes one category of work in one building area and another category of work in a separate and unrelated area of the building, each project area shall comply with the requirements of the respective category of work. Where a project with more than one category of work is performed in the same area or in related areas of the building, the project shall comply with the requirements of the more stringent category of work.

AJ102.1 General

AMENDMENT
This section has been amended at the state or city level.
Regardless of the category of work being performed, the work shall not cause the structure to become unsafe or adversely affect the performance of the building; shall not cause a system regulated by 780 CMR 51.00: Massachusetts Residential Code to become unsafe, hazardous, insanitary or overloaded; and unless expressly permitted by these provisions, shall not make the building any less compliant with 780 CMR 51.00: Massachusetts Residential Code or to any previously approved alternative arrangements than it was before the work was undertaken.
Repairs shall conform to the requirements of Section AJ301. Renovations shall conform to the requirements of Section AJ401. Alterations shall conform to the requirements of Section AJ501 and the requirements for renovations. Reconstructions shall conform to the requirements of Section AJ601 and the requirements for alterations and renovations.

AJ102.3 Smoke Detectors

AMENDMENT
This section has been amended at the state or city level.

AJ102.3 Smoke, Carbon Monoxide and Heat Protection

AMENDMENT
This section has been amended at the state or city level.
Smoke, carbon monoxide and heat protection shall be provided when required by this section and designed, located and installed in accordance with the provisions for new construction. See sections R314, R314.5, and R315.

AJ102.3.1 Adding or Creating One or More Sleeping Rooms

AMENDMENT
This section has been amended at the state or city level.
  1. Single-family Dwelling. When one or more sleeping rooms are added or created to an existing dwelling, the entire dwelling shall be provided with smoke, heat and carbon monoxide protection.
  2. Two-family Dwelling. When one or more sleeping rooms are added or created to one dwelling unit that unit shall be provided with smoke, heat and carbon monoxide protection detectors. When sleeping rooms are added or created to both units the entire building shall be provided with smoke, heat and carbon monoxide protection.
  3. Townhouses Dwelling Unit. When one or more sleeping rooms are added or created to an existing dwelling unit, the entire unit shall be provided with smoke, heat, and carbon monoxide protection.

AJ102.3.2 Complete Reconstruction

AMENDMENT
This section has been amended at the state or city level.
If a dwelling or townhouse building undergoes reconstruction such that more than 50% of walls and ceilings are open to framing, then the entire existing building shall be provided with smoke, heat and carbon monoxide protection.

AJ102.3.3 Adding an Attached Garage

AMENDMENT
This section has been amended at the state or city level.
If a garage is created under or attached to an existing dwelling unit, a heat detector shall be provided in the garage in accordance with R314.8.
Regardless of the category of work, where an existing window, including the sash and glazed portion, or safety glazing is replaced, the replacement window or safety glazing shall comply with the requirements of Sections AJ102.4.1 through AJ102.4.4, as applicable.
Replacement windows shall comply with the requirements of Chapter 11.
Replacement glazing in hazardous locations shall comply with the safety glazing requirements of Section R308.
Where windows are required to provide emergency escape and rescue openings, replacement windows shall be exempt from the maximum sill height requirements of Section R310.2.2 and the requirements of Sections R310.2.1 and R310.2.3 provided that the replacement window meets the following conditions:
  1. The replacement window is the manufacturer's largest standard size window that will fit within the existing frame or existing rough opening. The replacement window shall be permitted to be of the same operating style as the existing window or a style that provides for an equal or greater window opening area than the existing window.
  2. The replacement window is not part of a change of occupancy.
  3. Window opening control devices complying with ASTM F 2090 shall be permitted for use on windows required to provide emergency escape and rescue openings.
Where window fall prevention devices complying with ASTM F 2090 are not provided, window opening control devices complying with ASTM F 2090 shall be installed where an existing window is replaced and where all of the following apply to the replacement window:
  1. The window is operable.
  2. The window replacement includes replacement of the sash and the frame.
  3. The top of the sill of the window opening is at a height less than 24 inches (610 mm) above the finished floor.
  4. The window will permit openings that will allow passage of a 4-inch-diameter (102 mm) sphere where the window is in its largest opened position.
  5. The vertical distance from the top of the sill of the window opening to the finished grade or other surface below, on the exterior of the building, is greater than 72 inches (1829 mm).
The window opening control device, after operation to release the control device allowing the window to fully open, shall not reduce the minimum net clear opening area of the window unit.
Work performed in existing buildings located in a flood hazard area as established by Table R301.2(1) shall be subject to the provisions of Section R105.3.1.1.
Work performed in accordance with the International Existing Building Code shall be deemed to comply with the provisions of this appendix. These provisions are not intended to prevent the use of any alternative material, alternative design or alternative method of construction not specifically prescribed herein, provided that any alternative has been deemed to be equivalent and its use authorized by the building official.
Where compliance with these provisions or with this code as required by these provisions is technically infeasible or would impose disproportionate costs because of construction or dimensional difficulties, the building official shall have the authority to accept alternatives. These alternatives include materials, design features and operational features.

AJ102.7.1 Documentation of Compliance Alternatives

AMENDMENT
This section has been amended at the state or city level.
The building official shall ensure that the BBRS is provided with information regarding any and all compliance alternatives accepted by the building official within two weeks of acceptance.
Buildings or systems in compliance with the requirements of this code for new construction shall not be required to comply with any more restrictive requirement of these provisions.
Elements, components and systems of existing buildings with features that exceed the requirements of this code for new construction, and are not otherwise required as part of approved alternative arrangements or deemed by the building official to be required to balance other building elements not complying with this code for new construction, shall not be prevented by these provisions from being modified as long as they remain in compliance with the applicable requirements for new construction.

AJ102.10 Unlined Chimneys

AMENDMENT
This section has been amended at the state or city level.
Where new HVAC appliances are connected to an unlined chimney, the chimney lining requirements of 248 CMR: Board of State Examiners of Plumbers and Gas Fitters or 527 CMR: Board of Fire Prevention Regulations, as applicable, and those of the appliance manufacturer, shall be satisfied. If the appliance is a solid fuel-burning appliance, the chimney shall be relined to satisfy requirements both of the code for new construction and those of the manufacturer, as applicable.

AJ102.11 Latent Conditions

AMENDMENT
This section has been amended at the state or city level.
When latent conditions are observed and which are determined by the licensed construction supervisor, the owner or the building official to be dangerous or unsafe, or when a component or system is determined to be unserviceable, said conditions shall be corrected in accordance with applicable provisions of 780 CMR 51.00: Massachusetts Residential Code. A building permit shall be obtained or the building permit shall be amended in accordance with the provisions of section R105 in order to reflect the necessary required work and the approval shall be obtained from the building official prior to commencement of the corrections.

EXCEPTION: If the public safety so warrants, corrective actions are permitted to be made prior to amending the building permit application, providing that the building official is notified in writing within 24 hours of actions taken pursuant to this exception. This exception shall not be construed as to authorize constructive approval nor set aside the requirements to amend the permit application, nor shall the authority of the building official to enforce 780 CMR 51.00: Massachusetts Residential Code be abridged. Such corrective actions shall be documented by the construction supervisor or the owner and submitted to the building official within 48 hours of the completion of the action under this exception. Such corrective work shall not be concealed until the building official has inspected and approved the work.

AJ102.12 Energy Efficiency

AMENDMENT
This section has been amended at the state or city level.

AJ102.13 Roofing and Reroofing

AMENDMENT
This section has been amended at the state or city level.
See Chapter 9 of 780 CMR 51.00: Massachusetts Residential Code generally and section R907.

AJ102.14 Accessibility for Persons With Disabilities

AMENDMENT
This section has been amended at the state or city level.
Accessibility requirements shall be in accordance with 521 CMR.

AJ103.1 General

AMENDMENT
This section has been amended at the state or city level.
If a building permit is required at the request of the prospective permit applicant, the building official or his or her legal designee may meet with the prospective applicant to discuss plans for any proposed work under these provisions prior to the application for the permit. The purpose of this preliminary meeting is for the building official to gain an understanding of the prospective applicant's intentions for the proposed work, and to determine, together with the prospective applicant, the specific applicability of these provisions.
The building official shall have the authority to require an existing building to be investigated and evaluated by a registered design professional in the case of proposed reconstruction of any portion of a building. The evaluation shall determine the existence of any potential nonconformities to these provisions, and shall provide a basis for determining the impact of the proposed changes on the performance of the building. The evaluation shall use the following sources of information, as applicable:

1. Available documentation of the existing building.

1.1. Field surveys.

1.2. Tests (nondestructive and destructive).

1.3. Laboratory analysis.

Exception: Detached one- or two-family dwellings that are not irregular buildings under Section R301.2.2.2.5 and are not undergoing an extensive reconstruction shall not be required to be evaluated.
The work area shall be clearly identified on the permits issued under these provisions.
For purposes of this appendix, the terms used are defined as follows.

ALTERATION. The reconfiguration of any space; the addition or elimination of any door or window; the reconfiguration or extension of any system; or the installation of any additional equipment.

CATEGORIES OF WORK. The nature and extent of construction work undertaken in an existing building. The categories of work covered in this appendix, listed in increasing order of stringency of requirements, are repair, renovation, alteration and reconstruction.

DANGEROUS. Where the stresses in any member; the condition of the building, or any of its components or elements or attachments; or other condition that results in an overload exceeding 150 percent of the stress allowed for the member or material in this code.

EQUIPMENT OR FIXTURE. Any plumbing, heating, electrical, ventilating, air-conditioning, refrigerating and fire protection equipment; and elevators, dumb waiters, boilers, pressure vessels, and other mechanical facilities or installations that are related to building services.

LOAD-BEARING ELEMENT. Any column, girder, beam, joist, truss, rafter, wall, floor or roof sheathing that supports any vertical load in addition to its own weight, or any lateral load.

MATERIALS AND METHODS REQUIREMENTS. Those requirements in this code that specify material standards; details of installation and connection; joints; penetrations; and continuity of any element, component or system in the building. The required quantity, fire resistance, flame spread, acoustic or thermal performance, or other performance attribute is specifically excluded from materials and methods requirements.

RECONSTRUCTION. The reconfiguration of a space that affects an exit, a renovation or alteration where the work area is not permitted to be occupied because existing means-of-egress and fire protection systems, or their equivalent, are not in place or continuously maintained; or there are extensive alterations as defined in Section AJ501.3.

REHABILITATION. Any repair, renovation, alteration or reconstruction work undertaken in an existing building.

RENOVATION. The change, strengthening or addition of load-bearing elements; or the refinishing, replacement, bracing, strengthening, upgrading or extensive repair of existing materials, elements, components, equipment or fixtures. Renovation does not involve reconfiguration of spaces. Interior and exterior painting are not considered refinishing for purposes of this definition, and are not renovation.

REPAIR. The patching, restoration or minor replacement of materials, elements, components, equipment or fixtures for the purposes of maintaining those materials, elements, components, equipment or fixtures in good or sound condition.

WORK AREA. That portion of a building affected by any renovation, alteration or reconstruction work as initially intended by the owner and indicated as such in the permit. Work area excludes other portions of the building where incidental work entailed by the intended work must be performed, and portions of the building where work not initially intended by the owner is specifically required by these provisions for a renovation, alteration or reconstruction.
Except as otherwise required herein, work shall be done using like materials or materials permitted by this code for new construction.
Hazardous materials no longer permitted, such as asbestos and lead-based paint, shall not be used.

AJ301.1.2 Plumbing Materials and Supplies

AMENDMENT
This section has been amended at the state or city level.

AJ301.2 Water Closets

AMENDMENT
This section has been amended at the state or city level.

AJ301.3 Electrical

AMENDMENT
This section has been amended at the state or city level.
The work shall comply with the materials and methods requirements of this code.
Minor reductions in the clear opening dimensions of replacement doors and windows that result from the use of different materials shall be allowed, whether or not they are permitted by this code.

AJ401.2.1 Emergency Escape and Rescue Windows

AMENDMENT
This section has been amended at the state or city level.
For one- and two-family dwellings and townhouses of no more than three stories in height, all emergency escape windows from sleeping rooms shall have a net clear opening of 3.3 ft2 (0.307 m2). The minimum net clear opening shall be 20 inches by 24 inches (508 mm by 610 mm) in either direction except that windows in sleeping rooms of existing dwellings which do not conform to these requirements may be replaced without conforming to these dimensional requirements, provided that the windows do not significantly reduce the existing opening size.

EXCEPTION: Replacement windows utilized as emergency escape and rescue windows, other than double-hung windows, shall generally conform to the requirements of this section without conforming to the cited dimensional requirements, provided that such replacement windows do not significantly reduce the existing opening size.
Wood paneling and textile wall coverings used as an interior finish shall comply with the flame spread requirements of Section R302.9.

AJ401.4 Structural

AMENDMENT
This section has been amended at the state or city level.
Unreinforced masonry townhouse buildings shall have parapet bracing and wall anchors installed at the roofline whenever a reroofing permit is issued if required by 780 CMR 34.00: Existing Structures. Such parapet bracing and wall anchors shall be of an approved design. Where renovations may decrease the structural performance of the existing building, such proposed activities shall be evaluated by a registered design professional for adequacy, prior to such actual structural renovation.

AJ501.1 Newly Constructed Elements

AMENDMENT
This section has been amended at the state or city level.
Additions, newly constructed elements, components and systems shall comply with the requirements of 780 CMR 51.00: Massachusetts Residential Code.

EXCEPTIONS:
  1. Operable windows may be added without requiring compliance with the light and ventilation requirements of section R303.
  2. Newly installed electrical equipment shall comply with the requirements of section AJ501.5.
The work shall not increase the extent of noncompliance with the requirements of Section AJ601, or create nonconformity to those requirements that did not previously exist.
Where the total area of all of the work areas included in an alteration exceeds 50 percent of the area of the dwelling unit, the work shall be considered to be a reconstruction and shall comply with the requirements of these provisions for reconstruction work.

Exception: Work areas in which the alteration work is exclusively plumbing, mechanical or electrical shall not be included in the computation of the total area of all work areas.

AJ501.4 Structural

AMENDMENT
This section has been amended at the state or city level.
The minimum design loads for the structure shall be the loads applicable at the time the building was constructed, provided that a dangerous condition is not created. Structural elements that are uncovered during the course of the alteration and that are found to be unsound or dangerous shall be made to comply with the applicable requirements of 780 CMR 51.00. Where alterations may decrease the structural performance of the existing building, such proposed activities shall be evaluated by a registered design professional for adequacy, prior to such actual structural alterations.

AJ501.5 Electrical Equipment and Wiring

AMENDMENT
This section has been amended at the state or city level.
See 527 CMR 12.00: Massachusetts Electrical Code (Amendments).
Newly installed electrical equipment and wiring relating to work done in any work area shall comply with the materials and methods requirements of Chapters 34 through 43.

Exception: Electrical equipment and wiring in newly installed partitions and ceilings shall comply with the applicable requirements of Chapters 34 through 43.
Service to the dwelling unit shall be not less than 100 ampere, three-wire capacity and service equipment shall be dead front having no live parts exposed that could allow accidental contact. Type "S" fuses shall be installed where fused equipment is used.

Exception: Existing service of 60 ampere, three-wire capacity, and feeders of 30 ampere or larger two- or three-wire capacity shall be accepted if adequate for the electrical load being served.
Where the work area includes any of the following areas within a dwelling unit, the requirements of Sections AJ501.5.3.1 through AJ501.5.3.5 shall apply.
Enclosed areas other than closets, kitchens, basements, garages, hallways, laundry areas and bathrooms shall have not less than two duplex receptacle outlets, or one duplex receptacle outlet and one ceiling- or wall-type lighting outlet.
Kitchen areas shall have not less than two duplex receptacle outlets. Laundry areas shall have not less than one duplex receptacle outlet located near the laundry equipment and installed on an independent circuit.
Ground-fault circuit-interruption shall be provided on newly installed receptacle outlets if required by Chapters 34 through 43.
Not less than one lighting outlet shall be provided in every bathroom, hallway, stairway, attached garage and detached garage with electric power to illuminate outdoor entrances and exits, and in utility rooms and basements where these spaces are used for storage or contain equipment requiring service.
Clearance for electrical service equipment shall be provided in accordance with Chapters 34 through 43.
Reconfigured spaces intended for occupancy and spaces converted to habitable or occupiable space in any work area shall be provided with ventilation in accordance with Section R303.
Habitable spaces created in existing basements shall have ceiling heights of not less than 6 feet, 8 inches (2032 mm), except that the ceiling height at obstructions shall be not less than 6 feet 4 inches (1930 mm) from the basement floor. Existing finished ceiling heights in nonhabitable spaces in basements shall not be reduced.
Existing basement stairs and handrails not otherwise being altered or modified shall be permitted to maintain their current clear width at, above and below existing handrails.
Headroom height on existing basement stairs being altered or modified shall not be reduced below the existing stairway finished headroom. Existing basement stairs not otherwise being altered shall be permitted to maintain the current finished headroom.
Landings serving existing basement stairs being altered or modified shall not be reduced below the existing stairway landing depth and width. Existing basement stairs not otherwise being altered shall be permitted to maintain the current landing depth and width.
Stairways within the work area shall be provided with illumination in accordance with Section R303.6.
Every required exit stairway that has four or more risers, is part of the means of egress for any work area, and is not provided with at least one handrail, or in which the existing handrails are judged to be in danger of collapsing, shall be provided with handrails designed and installed in accordance with Section R311 for the full length of the run of steps on not less than one side.
Every open portion of a stair, landing or balcony that is more than 30 inches (762 mm) above the floor or grade below, is part of the egress path for any work area, and does not have guards, or in which the existing guards are judged to be in danger of collapsing, shall be provided with guards designed and installed in accordance with Section R312.
The interior finish of walls and ceilings in any work area shall comply with the requirements of Section R302.9. Existing interior finish materials that do not comply with those requirements shall be removed or shall be treated with an approved fire-retardant coating in accordance with the manufacturer's instructions to secure compliance with the requirements of this section.
Where the work area is in an attached dwelling unit, walls separating dwelling units that are not continuous from the foundation to the underside of the roof sheathing shall be constructed to provide a continuous fire separation using construction materials consistent with the existing wall or complying with the requirements for new structures. Performance of work shall be required only on the side of the wall of the dwelling unit that is part of the work area.
Habitable spaces created in existing basements shall have ceiling heights of not less than 6 feet, 8 inches (2032 mm), except that the ceiling height at obstructions shall be not less than 6 feet 4 inches (1930 mm) from the basement floor. Existing finished ceiling heights in nonhabitable spaces in basements shall not be reduced.

AJ601.5 Structural

AMENDMENT
This section has been amended at the state or city level.
Where reconstruction may decrease the structural performance of the existing building, such proposed activities shall be evaluated by a registered design professional for adequacy, prior to such actual structural reconstruction.

Section AJ701 Historic Buildings

AMENDMENT
This section has been amended at the state or city level.

AJ701.1 General

AMENDMENT
This section has been amended at the state or city level.
For historic building requirements, see 780 CMR 34.00: Existing Building Code.
UpCodes Premium
Leverage the most sophisticated code compliance platform.
TRY FREE FOR TWO WEEKS VISIT PRICING