ADOPTS WITH AMENDMENTS:

International Existing Building Code 2009 (IEBC 2009)

Heads up: There are no amended sections in this chapter.

Part 1 — Scope and Application

101.1 Title

AMENDMENT
This section has been amended at the state or city level.
These regulations shall be known as the Existing Building Code of Massachusetts, hereinafter referred to as "this code."

101.2 Scope

AMENDMENT
This section has been amended at the state or city level.
The provisions of this code shall apply to the repair, alteration, change of occupancy, addition, and relocation of existing buildings. See Table 101.2 below which includes, but is not limited to, applicable laws and specific use of other regulations.

TABLE 101.2
APPLICABLE LAWS AND REGULATIONS
Unless directed otherwise in this code, reference to: Shall mean to use the requirements found in:
International Plumbing Code 248 CMR: Board of Plumbers and Gas Fitters Regulations
International Property Maintenance Code 780 CMR 1.00: Scope and Administration
International Fire Code (IFC) Reference to sections of the International Fire Code (IFC) for fire prevention requirements shall be considered reference to 527 CMR: Board of Fire Prevention Regulations. The fire official enforces the provisions of 527 CMR.
Reference to sections of the International Fire Code (IFC) 2009 Edition for building code requirements are adopted, except that retroactive requirements of the IFC are not adopted. The building official enforces 780 CMR and all adopted IFC requirements. Also see MGL c. 148, § 9.


International Electrical Code 527 CMR 12.00: Massachusetts Electrical Code (Amendments)
International Energy Conservation Code (IECC) 780 CMR 13 and 51 (IECC with MA amendments)
International Mechanical Code (IMC) Reference to the IMC shall apply to all mechanical systems except for that which is defined as sheet metal work by M.G.L. c. 112, § 237. The provisions of 271 CMR shall apply to all sheet metal work as defined by M.G.L. c.112, § 237. Note: 527 CMR may cover certain fire protection requirements of the IMC.
International Fuel Gas Code 248 CMR: Board of Plumbers and Gas Fitters Regulations
International Residential Code (IRC) 780 CMR 51.00: Residential Volume (IRC 2009 Edition with MA amendments).
International Building Code (IBC) or 780 CMR 780 CMR Base Volume a.k.a. IBC with MA amendments.
Construction in flood areas 780 CMR: Appendix G: Flood-resistant Construction
Accessibility 521 CMR: Architectural Access Board Regulations
Elevators and lifts 524 CMR: Board of Elevator Regulations
Sprinkler Systems This code (780 CMR 34.00) or if applicable M.G.L. c. 148, § 26A, 26A1/2 , 26G, 26G1/2 , 26H or 26I, or M.G.L. c. 272 §§ 86 through 86d
Other requirements Refer to:
for Carbon Monoxide Protection in all R-Uses 780 CMR 9.00: Fire Protection Systems
for A-2 Nightclubs Use 780 CMR 1.00, 3.00, 9.00 and 10.00
The intent of this code is to provide flexibility to permit the use of alternative approaches to achieve compliance with minimum requirements to safeguard the public health, safety and welfare insofar as they are affected by the repair, alteration, change of occupancy, addition and relocation of existing buildings.
This code shall apply to the repair, alteration, change of occupancy, addition and relocation of all existing buildings, regardless of occupancy, subject to the criteria of Sections 101.4.1 and 101.4.2.
A building or portion of a building that has not been previously occupied or used for its intended purpose in accordance with the laws in existence at the time of its completion shall comply with the provisions of the International Building Code or International Residential Code, as applicable, for new construction or with any current permit for such occupancy.
The legal occupancy of any building existing on the date of adoption of this code shall be permitted to continue without change, except as is specifically covered in this code, the International Fire Code, or the International Property Maintenance Code, or as is deemed necessary by the code official for the general safety and welfare of the occupants and the public.

The repair, alteration, change of occupancy, addition or relocation of all existing buildings shall comply with one of the methods listed in Sections 101.5.1 through 101.5.3 as selected by the applicant. Application of a method shall be the sole basis for assessing the compliance of work performed under a single permit unless otherwise approved by the code official. Sections 101.5.1 through 101.5.3 shall not be applied in combination with each other. Where this code requires consideration of the seismic-force-resisting system of an existing building subject to repair, alteration, change of occupancy, addition or relocation of existing buildings, the seismic evaluation and design shall be based on Section 101.5.4 regardless of which compliance method is used.

Exception: Subject to the approval of the code official, alterations complying with the laws in existence at the time the building or the affected portion of the building was built shall be considered in compliance with the provisions of this code unless the building is undergoing more than a limited structural alteration as defined in Section 807.5.3. New structural members added as part of the alteration shall comply with the International Building Code. Alterations of existing buildings in flood hazard areas shall comply with Section 601.3.

101.5.0 Compliance Alternatives

AMENDMENT
This section has been amended at the state or city level.
Where compliance with the provisions of the code for new construction, required by this code, is impractical because of construction difficulties or regulatory conflicts, compliance alternatives may be accepted by the building official. The building official may accept these compliance alternatives, archaic materials and assemblies in Resource A of this code, or others proposed. If the compliance alternative involves fire protection systems the building official shall consult with the fire official.

101.5.0.1 Submittals

AMENDMENT
This section has been amended at the state or city level.
The application for a permit shall be in accordance with 780 CMR 1.00: Scope and Administration and identify all items of non- or partial compliance with the requirements of this code, and compliance alternatives, if any are proposed, for approval by the building official. The building official shall respond to the acceptability of any proposed compliance alternatives within 30 days of the filing of the permit application. Where proposed compliance alternatives are, in the opinion of the building official, unacceptable, or where issues of non-compliance remain, the permit applicant shall have the remedies prescribed by 780 CMR, section 113.

101.5.1 Prescriptive Compliance Method

AMENDMENT
This section has been amended at the state or city level.
Repairs, alterations, additions and changes of occupancy complying with Chapter 3 of this code shall be considered in compliance with the provisions of this code.
Repairs, alterations, additions, changes in occupancy and relocated buildings complying with the applicable requirements of Chapters 4 through 12 of this code shall be considered in compliance with the provisions of this code.
Repairs, alterations, additions, changes in occupancy and relocated buildings complying with Chapter 13 of this code shall be considered in compliance with the provisions of this code.
The seismic evaluation and design shall be based on the procedures specified in the International Building Code, ASCE 31 or ASCE 41. The procedures contained in Appendix A of this code shall be permitted to be used as specified in Section 101.5.4.2.

101.5.4.0 Investigation and Evaluation

AMENDMENT
This section has been amended at the state or city level.
For any proposed work regulated by this code and subject to 780 CMR, section 107, as a condition of the issuance of a permit the building owner shall cause the existing building (or portion thereof) to be investigated and evaluated in accordance with the provisions of this code. The investigation and evaluation shall be in sufficient detail to ascertain the effects of the proposed work on at least these systems: structural, means of egress, fire protection, energy conservation, lighting, hazardous materials, and ventilation for the space under consideration and, where necessary, the entire building or structure and its foundation if impacted by the proposed work. The results of the investigation and evaluation, along with any proposed compliance alternatives, shall be submitted to the building official in written report form.

101.5.4.1 Compliance With IBC Level Seismic Forces

AMENDMENT
This section has been amended at the state or city level.
Where compliance with the seismic design provisions of the International Building Code is required, the procedures shall be in accordance with one of the following:
  1. The International Building Code 2009 with Massachusetts Amendments using 100% of the prescribed forces. For existing buildings with seismic force resisting systems found in Table 101.5.4.1.0, the values of R, Ω0, and Cd from this table shall be used in the analysis. For seismic force resisting systems not found in Table 101.5.4.1.0, the values of R, Ω0, and Cd used for analysis in accordance with Chapter 16 of the International Building Code 2009 with Massachusetts Amendments, (780 CMR 16.00) shall be those specified for structural systems classified as "Ordinary" in accordance with Table 12.2-1 of ASCE 7, unless it can be demonstrated that the structural system satisfies the proportioning and detailing requirements for systems classified as "Intermediate" or "Special".
  2. Compliance with ASCE 41 using both the BSE-1 and BSE-2 earthquake hazard levels and the corresponding performance levels shown in Table 101.5.4.1.

TABLE 101.5.4.1
PERFORMANCE CRITERIA FOR IBC LEVEL SEISMIC FORCES

OCCUPANCY CATEGORY
(Based on IBC Table 1604.5)

PERFORMANCE LEVEL FOR USE WITH ASCE 41 BSE-1 EARTHQUAKE HAZARD LEVEL

PERFORMANCE LEVEL FOR USE WITH ASCE 41 BSE-2 EARTHQUAKE HAZARD LEVEL

I

Life safety (LS)

Collapse prevention (CP)

II

Life safety (LS)

Collapse prevention (CP)

III

Note a, Note b

Note a

IV

Immediate occupancy (IO)

Life safety (LS)

  1. Acceptable criteria for Occupancy Category III shall be taken as 80 percent of the acceptance criteria specified for Occupancy Category IV performance levels.
  2. For Occupancy Category III, the ASCE 31 screening phase checklists shall be based on the life safety performance level.

101.5.4.1.0

AMENDMENT
This section has been amended at the state or city level.

101.5.4.2 Compliance With Reduced IBC Level Seismic Forces

AMENDMENT
This section has been amended at the state or city level.
Where seismic evaluation and design is permitted to meet reduced International Building Code seismic force levels, the procedures used shall be in accordance with one of the following:
  1. The International Building Code using 75 percent of the prescribed forces. Values of R, Ωo,and Cd used for analysis shall be as specified in Section 101.5.4.1 of this code.
    Exceptions:
    1. 780 CMR using 50% of prescribed forces when directed here by section 807.4.3
    2. 780 CMR using either
      1. 50 % of prescribed forces when directed here by section 1003.3.1 and when the vertical addition increases the building area less than or equal to 30% or,
      2. 75% of prescribed forces when directed here by section 1003.3.1 and when the vertical addition increases the building area more than 30% but less than 50%.
  2. Structures or portions of structures that comply with the requirements of the applicable chapter in Appendix A as specified in Items 2.1 through 2.5 shall be deemed to comply with this section.
    1. The seismic evaluation and design of unreinforced masonry bearing wall buildings in Occupancy Category I or II are permitted to be based on the procedures specified in Appendix Chapter A1.
    2. Seismic evaluation and design of the wall anchorage system in reinforced concrete and reinforced masonry wall buildings with flexible diaphragms in Occupancy Category I or II are permitted to be based on the procedures specified in Chapter A2.
    3. Seismic evaluation and design of cripple walls and sill plate anchorage in residential buildings of light-frame wood construction in Occupancy Category I or II are permitted to be based on the procedures specified in Chapter A3.
    4. Seismic evaluation and design of soft, weak, or open-front wall conditions in multiunit residential buildings of wood construction in Occupancy Category I or II are permitted to be based on the procedures specified in Chapter A4.
    5. Seismic evaluation and design of concrete buildings and concrete with masonry infill buildings in all occupancy categories are permitted to be based on the procedures specified in Chapter A5.
  3. Compliance with ASCE 31 based on the applicable performance level as shown in Table 101.5.4.2. It shall be permitted to use the BSE-1 earthquake hazard level as defined in ASCE 41 and subject to the limitations in Item 4 below.
  4. Compliance with ASCE 41 using the BSE-1 Earthquake Hazard Level and the performance level shown in Table 101.5.4.2. The design spectral response acceleration parameters SXS and SX1 specified in ASCE 41 shall not be taken less than 75 percent of the respective design spectral response acceleration parameters SDS and SD1 defined by the International Building Code.
TABLE 101.5.4.2
PERFORMANCE CRITERIA FOR REDUCED IBC
LEVEL SEISMIC FORCES
OCCUPANCY CATEGORY
(Based on IBC Table 1604.5)
PERFORMANCE LEVEL FOR USE WITH ASCE 31 PERFORMANCE LEVEL FOR USE WITH ASCE 41 BSE-1 EARTHQUAKE HAZARD LEVEL

I

Life safety (LS)

Life safety (LS)

II

Life safety (LS)

Life safety (LS)

III

Note a

Note a

IV

Immediate
occupancy (IO)

Immediate
occupancy (IO)

  1. Performance levels for Occupancy Category III shall be taken as halfway between the performance levels specified for Occupancy Categories II and IV.
All construction work covered in this code, including any related demolition, shall comply with the requirements of Chapter 14.
The code official is authorized to require rehabilitation and retrofit of buildings, structures or individual structural members in accordance with the appendices of this code if such appendices have been individually adopted.
Repairs or alterations mandated by any property, housing, or fire safety maintenance code or mandated by any licensing rule or ordinance adopted pursuant to law shall conform only to the requirements of that code, rule, or ordinance and shall not be required to conform to this code unless the code requiring such repair or alteration so provides.

101.9 Cumulative Effects of Alterations, Additions, or Changes of Occupancy on Structural Elements

AMENDMENT
This section has been amended at the state or city level.
As noted in several sections of this code, evaluation of structural elements and their connections shall consider the cumulative effects of alterations, additions, or changes of occupancy since original construction.
Exception: When structural work:
  1. does not involve more than 2% of the total tributary area of horizontal framing members of any existing framed floor or roof and,
  2. does not alter shear walls above the foundation and,
  3. does not alter columns or diagonal braces and,
  4. does not create an opening in any framed floor or roof that has an area more than 2% of the framed floor or roof and,
  5. does not alter any floor or roof diaphragm and its connections such that in-plane shear resistance is reduced by more than 5% and,
  6. does not remove or reconfigure lateral load resisting frames, or foundations supporting them.

101.10 Masonry Walls

AMENDMENT
This section has been amended at the state or city level.
For alterations to buildings with masonry walls, all masonry walls shall comply with the provisions of Appendix A1 as modified by Massachusetts Amendments, where any of the following conditions exist:
  1. the work area exceeds 50% of the aggregate area of the building, or
  2. an occupancy increase of more than 25% and to a total of 100 or more, or
  3. a change of occupancy to a relative hazard category of 1 or 2 per Table 912.5, or educational occupancies K to 12, or
  4. a Level 2 Alteration, as defined by section 404, to an Occupancy Category IV per ASCE 7.
Where there is a conflict between a general requirement and a specific requirement, the specific requirement shall be applicable. Where in any specific case different sections of this code specify different materials, methods of construction or other requirements, the most restrictive shall govern.

102.2 Other Laws

AMENDMENT
This section has been amended at the state or city level.

102.2 Other Laws and Specialty Codes

AMENDMENT
This section has been amended at the state or city level.
The provisions of this code shall not be deemed to nullify any provisions of local, state, or federal law, or the regulations pursuant to specialty codes listed in section 101.4 of the International Building Code 2009 with Massachusetts Amendments (780 CMR 101.4).

102.2.1 Fire Protection Systems

AMENDMENT
This section has been amended at the state or city level.
Notwithstanding other provisions of this code, the requirements of this section are applicable in existing buildings. In case of conflict, between regulations of 780 CMR, the more restrictive requirement applies.

102.2.1.1 Major Alterations

AMENDMENT
This section has been amended at the state or city level.
When existing buildings or portionsthereof undergo additions or alterations, M.G.L. c. 148, § 26G may apply with respect to automatic sprinkler requirements. The requirements of this statute are enforced by the fire official. Applicability of these requirements can be found at the Department of Fire Services web site www.mass.gov/dfs.

102.2.1.2 Other Cases Where Required

AMENDMENT
This section has been amended at the state or city level.
Fire protection systems are required for the following cases:
  1. Carbon monoxide alarms are required and shall be selected and installed in accordance with the applicable requirements of 527 CMR and/or 248 CMR and Chapter 9 of the International Building Code 2009 with Massachusetts Amendments (780 CMR 9.00).
  2. Existing buildings or portions thereof when changed in use to an A-2 Nightclub occupancy shall be protected with an automatic fire suppression system. Where the A-2 Nightclub occupancy is created in a mixed use building, the A-2 Nightclub occupancy, including all ingress and egress portions shall require automatic fire suppression when the occupant load is 50 or greater; additionally in such mixed use, the A-2 Nightclub occupancy shall be separated from adjacent uses by one hour horizontal and vertical fire separation assemblies in accordance with the applicable provisions of Chapter 7 of the International Building Code 2009 with Massachusetts Amendments (780 CMR 7.00).
  3. Notwithstanding the provisions of this code, automatic fire suppression systems are required in municipalities which have adopted the provisions of M.G.L. c. 148, § 26H or I; also see M.G.L. c. 143, § 97A, and M.G.L. c. 148, § 26G1/2 relative to statutory prospective and retroactive sprinkler requirements for A-2 nightclubs and similar uses.

102.2.1.3 Change in Commodity or Storage Arrangement

AMENDMENT
This section has been amended at the state or city level.
Existing buildings, or portions thereof, in which there is a change in occupancy classification, commodity classification, or storage arrangement, as defined by NFPA 13, requires an evaluation of the existing sprinkler system for compliance with NFPA 13 and NFPA 25.

In enforcing the provisions of this section the building official may require or accept engineering or other evaluations of the fire protection systems in order to identify possible noncompliant conditions and acceptable solutions. If the evaluation determines that alterations are necessary, the building official shall order the abatement of such conditions.

102.2.2 Existing Hazardous Conditions

AMENDMENT
This section has been amended at the state or city level.
This section shall apply to all existing buildings.

102.2.2.1 Existing Non Conforming Means of Egress

AMENDMENT
This section has been amended at the state or city level.
The following conditions shall be corrected in all existing buildings:
  1. Less than the number of means of egress serving every space and/or story, required byChapter 10 of the International Building Code 2009 with Massachusetts Amendments (780 CMR 10.00);
  2. Any required means of egress component which is not of sufficient width to provide adequate exit capacityin accordance with section 1005.1 of the International Building Code 2009 with Massachusetts Amendments (780 CMR 1005.1);
  3. Any means of egress which is not so arranged as to provide safe and adequate means of egress, including exit signage and emergency lighting in accordance with Chapter 10 of the International Building Code 2009 with Massachusetts Amendments (780 CMR 10.00); or
  4. Where the occupant load of an existing Group A-2 Nightclub use is 50 or greater, the main entrance/exit door shall be a minimum 72 inches (nominal) width. This main entrance/exit door shall consist of a pair of side-hinged swinging type doors without a center mullion and shall be equipped with panic hardware (see Chapter 10 of the International Building Code 2009 with Massachusetts Amendments (780 CMR 10.00). As an alternative, or where construction, regulations or other conditions exist which would preclude the installation of said main entrance/exit door and associated exit access, the ownershall cause the existing means of egress system to be evaluated by a registered design professional. Such evaluation shall determine whether the existing means of egress is sufficient to accommodate the occupant load orwhether the existing means of egress requires improvement to accommodate safely the occupant load. If the existing means of egress is insufficient to accommodate the occupant load, such inadequate means of egress will, as a minimum, be deemed in violation of this code. Calculation methodologies based on alternative approaches to life safety may be utilized in order to effect said egress evaluation.
If not corrected, the building official shall cite each deficiency in writing as a violation. Said citation shall order the abatement of the non conformance and shall include such a time element as the building official deems necessary for the protection of the occupants thereof, or as otherwise provided for by statute.

102.2.2.2 Exit Order for Hazardous Means of Egress

AMENDMENT
This section has been amended at the state or city level.
In any existing building or structure not provided with exit facilities as herein prescribed and in which the exits are deemed hazardous or dangerous to life and limb, the building official shall declare such building dangerous and unsafe in accordance with the provisions of section 116 of the International Building Code 2009 with Massachusetts Amendments (780 CMR 116). Any person served with any such order shall have the remedy prescribed in section 116 of the International Building Code 2009 with Massachusetts Amendments (780 CMR 116).

102.2.2.3 Fire Escapes

AMENDMENT
This section has been amended at the state or city level.
Fire escapes shall be permitted in accordance with section 305.

102.2.2.4 Testing and Certification of Egress Structures

AMENDMENT
This section has been amended at the state or city level.
All exterior bridges, steel or wooden stairways, fire escapes and egress balconies and their structural anchorage shall be examined and/or tested, and certified for structural adequacy and safety every five years, by a registered design professional, or others qualified and acceptable to the building official; said professional or others shall then submit an affidavit to the building official.

102.2.2.5 Unsafe Lighting and/or Ventilation

AMENDMENT
This section has been amended at the state or city level.
In any existing building, or portion thereof, in which (a) the lighting or ventilation do not meet the applicable provisions in Chapter 12 of the International Building Code 2009 with Massachusetts Amendments (780 CMR 12.00), and (b) which, in the opinion of the building official, are dangerous, or hazardous, to the health and safety of the occupants, the building official shall order the abatement of such conditions to render the building or structure occupiable or habitable as applicable for the posted use and occupant load.

In enforcing the provisions of this section the building official may require or accept engineering or other evaluations of the lighting and/or ventilation systems in order to evaluate possible dangerous or hazardous conditions and acceptable solutions.

Where full compliance with 780 CMR for new construction is not practical for structural and/or other technical reasons, the building official may accept compliance alternatives, or engineering or other evaluations which adequately address the building or structure livability for the posted use and occupant load.
References to chapter or section numbers or to provisions not specifically identified by number shall be construed to refer to such chapter, section, or provision of this code.

The codes and standards referenced in this code shall be considered part of the requirements of this code to the prescribed extent of each such reference. Where differences occur between provisions of this code and referenced codes and standards, the provisions of this code shall govern.

Exception: Where enforcement of a code provision would violate the conditions of the listing of the equipment or appliance, the conditions of the listing shall govern.
In the event that any part or provision of this code is held to be illegal or void, this shall not have the effect of making void or illegal any of the other parts or provisions.

Part 2 — Administration and Enforcement

The Department of Building Safety is hereby created, and the official in charge thereof shall be known as the code official.
The code official shall be appointed by the chief appointing authority of the jurisdiction.
In accordance with the prescribed procedures of this jurisdiction and with the concurrence of the appointing authority, the code official shall have the authority to appoint a deputy code official, the related technical officers, inspectors, plan examiners, and other employees. Such employees shall have powers as delegated by the code official.
The code official is hereby authorized and directed to enforce the provisions of this code. The code official shall have the authority to render interpretations of this code and to adopt policies and procedures in order to clarify the application of its provisions. Such interpretations, policies, and procedures shall be in compliance with the intent and purpose of this code. Such policies and procedures shall not have the effect of waiving requirements specifically provided for in this code.
The code official shall receive applications, review construction documents, and issue permits for the repair, alteration, addition, demolition, change of occupancy, and relocation of buildings; inspect the premises for which such permits have been issued; and enforce compliance with the provisions of this code.

When requested by the permit applicant or the code official, the code official shall meet with the permit applicant prior to the application for a construction permit to discuss plans for the proposed work or change of occupancy in order to establish the specific applicability of the provisions of this code.

Exception: Repairs and Level 1 alterations.
The code official is authorized to require an existing building to be investigated and evaluated by a registered design professional based on the circumstances agreed upon at the preliminary meeting. The design professional shall notify the code official if any potential nonconformance with the provisions of this code is identified.
The code official shall issue all necessary notices or orders to ensure compliance with this code.
The code official shall make all of the required inspections, or the code official shall have the authority to accept reports of inspection by approved agencies or individuals. Reports of such inspections shall be in writing and be certified by a responsible officer of such approved agency or by the responsible individual. The code official is authorized to engage such expert opinion as deemed necessary to report upon unusual technical issues that arise, subject to the approval of the appointing authority.
The code official shall carry proper identification when inspecting structures or premises in the performance of duties under this code.
Where it is necessary to make an inspection to enforce the provisions of this code, or where the code official has reasonable cause to believe that there exists in a structure or upon a premises a condition which is contrary to or in violation of this code which makes the structure or premises unsafe, dangerous, or hazardous, the code official is authorized to enter the structure or premises at reasonable times to inspect or to perform the duties imposed by this code, provided that if such structure or premises be occupied that credentials be presented to the occupant and entry requested. If such structure or premises be unoccupied, the code official shall first make a reasonable effort to locate the owner or other person having charge or control of the structure or premises and request entry. If entry is refused, the code official shall have recourse to the remedies provided by law to secure entry.
The code official shall keep official records of applications received, permits and certificates issued, fees collected, reports of inspections, and notices and orders issued. Such records shall be retained in the official records for the period required for retention of public records.
The code official, member of the Board of Appeals, or employee charged with the enforcement of this code, while acting for the jurisdiction in good faith and without malice in the discharge of the duties required by this code or other pertinent law or ordinance, shall not thereby be rendered liable personally and is hereby relieved from personal liability for any damage accruing to persons or property as a result of any act or by reason of an act or omission in the discharge of official duties. Any suit instituted against an officer or employee because of an act performed by that officer or employee in the lawful discharge of duties and under the provisions of this code shall be defended by legal representative of the jurisdiction until the final termination of the proceedings. The code official or any subordinate shall not be liable for cost in any action, suit, or proceeding that is instituted in pursuance of the provisions of this code.
Materials, equipment, and devices approved by the code official shall be constructed and installed in accordance with such approval.
The use of used materials that meet the requirements of this code for new materials is permitted. Used equipment and devices shall be permitted to be reused subject to the approval of the code official.
Wherever there are practical difficulties involved in carrying out the provisions of this code, the code official shall have the authority to grant modifications for individual cases upon application of the owner or owner's representative, provided the code official shall first find that special individual reason makes the strict letter of this code impractical and the modification is in compliance with the intent and purpose of this code, and that such modification does not lessen health, accessibility, life and fire safety, or structural requirements. The details of action granting modifications shall be recorded and entered in the files of the Department of Building Safety.

For existing buildings located in flood hazard areas for which repairs, alterations and additions constitute substantial improvement, the code official shall not grant modifications to provisions related to flood resistance unless a determination is made that:

  1. The applicant has presented good and sufficient cause that the unique characteristics of the size, configuration or topography of the site render compliance with the flood-resistant construction provisions inappropriate.
  2. Failure to grant the modification would result in exceptional hardship.
  3. The granting of the modification will not result in increased flood heights, additional threats to public safety, extraordinary public expense nor create nuisances, cause fraud on or victimization of the public or conflict with existing laws or ordinances.
  4. The modification is the minimum necessary to afford relief, considering the flood hazard.
  5. A written notice will be provided to the applicant specifying, if applicable, the difference between the design flood elevation and the elevation to which the building is to be built, stating that the cost of flood insurance will be commensurate with the increased risk resulting from the reduced floor elevation and that construction below the design flood elevation increases risks to life and property.
The provisions of this code are not intended to prevent the installation of any material or to prohibit any design or method of construction not specifically prescribed by this code, provided that any such alternative has been approved. An alternative material, design, or method of construction shall be approved where the code official finds that the proposed design is satisfactory and complies with the intent of the provisions of this code, and that the material, method, or work offered is, for the purpose intended, at least the equivalent of that prescribed in this code in quality, strength, effectiveness, fire resistance, durability, and safety.
Supporting data, where necessary to assist in the approval of materials or assemblies not specifically provided for in this code, shall consist of valid research reports from approved sources.
Whenever there is insufficient evidence of compliance with the provisions of this code or evidence that a material or method does not conform to the requirements of this code, or in order to substantiate claims for alternative materials or methods, the code official shall have the authority to require tests as evidence of compliance to be made at no expense to the jurisdiction. Test methods shall be as specified in this code or by other recognized test standards. In the absence of recognized and accepted test methods, the code official shall approve the testing procedures. Tests shall be performed by an approved agency. Reports of such tests shall be retained by the code official for the period required for retention.
Any owner or authorized agent who intends to repair, add to, alter, relocate, demolish, or change the occupancy of a building or to repair, install, add, alter, remove, convert, or replace any electrical, gas, mechanical, or plumbing system, the installation of which is regulated by this code, or to cause any such work to be done, shall first make application to the code official and obtain the required permit.
In lieu of an individual permit for each alteration to an already approved electrical, gas, mechanical, or plumbing installation, the code official is authorized to issue an annual permit upon application therefor to any person, firm, or corporation regularly employing one or more qualified trade persons in the building, structure, or on the premises owned or operated by the applicant for the permit.
The person to whom an annual permit is issued shall keep a detailed record of alterations made under such annual permit. The code official shall have access to such records at all times, or such records shall be filed with the code official as designated.

Exemptions from permit requirements of this code shall not be deemed to grant authorization for any work to be done in any manner in violation of the provisions of this code or any other laws or ordinances of this jurisdiction. Permits shall not be required for the following:

Building:

  1. Sidewalks and driveways not more than 30 inches (762 mm) above grade and not over any basement or story below and that are not part of an accessible route.
  2. Painting, papering, tiling, carpeting, cabinets, counter tops, and similar finish work.
  3. Temporary motion picture, television, and theater stage sets and scenery.
  4. Shade cloth structures constructed for nursery or agricultural purposes, and not including service systems.
  5. Window awnings supported by an exterior wall of Group R-3 or Group U occupancies.
  6. Movable cases, counters, and partitions not over 69 inches (1753 mm) in height.

Electrical:

Repairs and maintenance: Minor repair work, including the replacement of lamps or the connection of approved portable electrical equipment to approved permanently installed receptacles.

Radio and television transmitting stations: The provisions of this code shall not apply to electrical equipment used for radio and television transmissions, but do apply to equipment and wiring for power supply, the installations of towers, and antennas.

Temporary testing systems: A permit shall not be required for the installation of any temporary system required for the testing or servicing of electrical equipment or apparatus.

Gas:

  1. Portable heating appliance.
  2. Replacement of any minor part that does not alter approval of equipment or make such equipment unsafe.

Mechanical:

  1. Portable heating appliance.
  2. Portable ventilation equipment.
  3. Portable cooling unit.
  4. Steam, hot, or chilled water piping within any heating or cooling equipment regulated by this code.
  5. Replacement of any part that does not alter its approval or make it unsafe.
  6. Portable evaporative cooler.
  7. Self-contained refrigeration system containing 10 pounds (4.54 kg) or less of refrigerant and actuated by motors of 1 horsepower (746 W) or less.

Plumbing:

  1. The stopping of leaks in drains, water, soil, waste, or vent pipe; provided, however, that if any concealed trap, drainpipe, water, soil, waste, or vent pipe becomes defective and it becomes necessary to remove and replace the same with new material, such work shall be considered as new work, and a permit shall be obtained and inspection made as provided in this code.
  2. The clearing of stoppages or the repairing of leaks in pipes, valves, or fixtures, and the removal and reinstallation of water closets, provided such repairs do not involve or require the replacement or rearrangement of valves, pipes, or fixtures.
Where equipment replacements and repairs must be performed in an emergency situation, the permit application shall be submitted within the next working business day to the code official.
Application or notice to the code official is not required for ordinary repairs to structures and items listed in Section 105.2. Such repairs shall not include the cutting away of any wall, partition, or portion thereof, the removal or cutting of any structural beam or load-bearing support, or the removal or change of any required means of egress or rearrangement of parts of a structure affecting the egress requirements; nor shall ordinary repairs include addition to, alteration of, replacement, or relocation of any standpipe, water supply, sewer, drainage, drain leader, gas, soil, waste, vent, or similar piping, electric wiring, or mechanical or other work affecting public health or general safety.
A permit shall not be required for the installation, alteration, or repair of generation, transmission, distribution, or metering or other related equipment that is under the ownership and control of public service agencies by established right.

To obtain a permit, the applicant shall first file an application therefor in writing on a form furnished by the Department of Building Safety for that purpose. Such application shall:

  1. Identify and describe the work in accordance with Chapter 3 to be covered by the permit for which application is made.
  2. Describe the land on which the proposed work is to be done by legal description, street address, or similar description that will readily identify and definitely locate the proposed building or work.
  3. Indicate the use and occupancy for which the proposed work is intended.
  4. Be accompanied by construction documents and other information as required in Section 106.3.
  5. State the valuation of the proposed work.
  6. Be signed by the applicant or the applicant's authorized agent.
  7. Give such other data and information as required by the code official.
The code official shall examine or cause to be examined applications for permits and amendments thereto within a reasonable time after filing. If the application or the construction documents do not conform to the requirements of pertinent laws, the code official shall reject such application in writing, stating the reasons therefor. If the code official is satisfied that the proposed work conforms to the requirements of this code and laws and ordinances applicable thereto, the code official shall issue a permit therefor as soon as practicable.
An application for a permit for any proposed work shall be deemed to have been abandoned 180 days after the date of filing, unless such application has been pursued in good faith or a permit has been issued; except that the code official is authorized to grant one or more extensions of time for additional periods not exceeding 90 days each. The extension shall be requested in writing and justifiable cause demonstrated.
The issuance or granting of a permit shall not be construed to be a permit for, or an approval of, any violation of any of the provisions of this code or of any other ordinance of the jurisdiction. Permits presuming to give authority to violate or cancel the provisions of this code or other ordinances of the jurisdiction shall not be valid. The issuance of a permit based on construction documents and other data shall not prevent the code official from requiring the correction of errors in the construction documents and other data. The code official is also authorized to prevent occupancy or use of a structure where in violation of this code or of any other ordinances of this jurisdiction.
Every permit issued shall become invalid unless the work on the site authorized by such permit is commenced within 180 days after its issuance, or if the work authorized on the site by such permit is suspended or abandoned for a period of 180 days after the time the work is commenced. The code official is authorized to grant, in writing, one or more extensions of time for periods not more than 180 days each. The extension shall be requested in writing and justifiable cause demonstrated.
The code official is author- ized to suspend or revoke a permit issued under the provisions of this code wherever the permit is issued in error or on the basis of incorrect, inaccurate, or incomplete information or in violation of any ordinance or regulation or any of the provisions of this code.
The building permit or copy shall be kept on the site of the work until the completion of the project.

Submittal documents consisting of construction documents, special inspection and structural observation programs, investigation and evaluation reports, and other data shall be submitted in two or more sets with each application for a permit. The construction documents shall be prepared by a registered design professional where required by the statutes of the jurisdiction in which the project is to be constructed. Where special conditions exist, the code official is authorized to require additional construction documents to be prepared by a registered design professional.

Exception: The code official is authorized to waive the submission of construction documents and other data not required to be prepared by a registered design professional if it is found that the nature of the work applied for is such that reviewing of construction documents is not necessary to obtain compliance with this code.
Construction documents shall be in accordance with Sections 106.2.1 through 106.2.5.
Construction documents shall be dimensioned and drawn upon suitable material. Electronic media documents are permitted to be submitted when approved by the code official. Construction documents shall be of sufficient clarity to indicate the location, nature and extent of the work proposed and show in detail that it will conform to the provisions of this code and relevant laws, ordinances, rules and regulations, as determined by the code official. The work areas shall be shown.
Shop drawings for the fire protection system(s) shall be submitted to indicate conformance with this code and the construction documents and shall be approved prior to the start of system installation. Shop drawings shall contain all information as required by the referenced installation standards in Chapter 9 of the International Building Code.
The construction documents for Alterations—Level 2, Alterations—Level 3, additions and changes of occupancy shall show in sufficient detail the location, construction, size and character of all portions of the means of egress in compliance with the provisions of this code. The construction documents shall designate the number of occupants to be accommodated in every work area of every floor and in all affected rooms and spaces.

Construction documents for all work affecting the exterior wall envelope shall describe the exterior wall envelope in sufficient detail to determine compliance with this code. The construction documents shall provide details of the exterior wall envelope as required, including windows, doors, flashing, intersections with dissimilar materials, corners, end details, control joints, intersections at roof, eaves, or parapets, means of drainage, water-resistive membrane, and details around openings.

The construction documents shall include manufacturer's installation instructions that provide supporting documentation that the proposed penetration and opening details described in the construction documents maintain the wind and weather resistance of the exterior wall envelope. The supporting documentation shall fully describe the exterior wall system which was tested, where applicable, as well as the test procedure used.

The construction documents submitted with the application for permit shall be accompanied by a site plan showing to scale the size and location of new construction and existing structures on the site, distances from lot lines, the established street grades, and the proposed finished grades; and it shall be drawn in accordance with an accurate boundary line survey. In the case of demolition, the site plan shall show construction to be demolished and the location and size of existing structures and construction that are to remain on the site or plot. The code official is authorized to waive or modify the requirement for a site plan when the application for permit is for alteration, repair or change of occupancy.
The code official shall examine or cause to be examined the submittal documents and shall ascertain by such examinations whether the construction or occupancy indicated and described is in accordance with the requirements of this code and other pertinent laws or ordinances.
When the code official issues a permit, the construction documents shall be approved in writing or by stamp as "Reviewed for Code Compliance." One set of construction documents so reviewed shall be retained by the code official. The other set shall be returned to the applicant, shall be kept at the site of work, and shall be open to inspection by the code official or a duly authorized representative.
This code shall not require changes in the construction documents, construction or designated occupancy of a structure for which a lawful permit has been issued and the construction of which has been pursued in good faith within 180 days after the effective date of this code and has not been abandoned.
The code official is authorized to issue a permit for the construction of foundations or any other part of a building before the construction documents for the whole building or structure have been submitted, provided that adequate information and detailed statements have been filed complying with pertinent requirements of this code. The holder of such permit for the foundation or other parts of a building shall proceed at the holder's own risk with the building operation and without assurance that a permit for the entire structure will be granted.

For the purposes of this section, deferred submittals are defined as those portions of the design that are not submitted at the time of the application and that are to be submitted to the code official within a specified period.

Deferral of any submittal items shall have the prior approval of the code official. The registered design professional in responsible charge shall list the deferred submittals on the construction documents for review by the code official.

Submittal documents for deferred submittal items shall be submitted to the registered design professional in responsible charge who shall review them and forward them to the code official with a notation indicating that the deferred submittal documents have been reviewed and that they have been found to be in general conformance to the design of the building. The deferred submittal items shall not be installed until their deferred submittal documents have been approved by the code official.

Work shall be installed in accordance with the reviewed construction documents, and any changes made during construction that are not in compliance with the approved construction documents shall be resubmitted for approval as an amended set of construction documents.
One set of approved construction documents shall be retained by the code official for a period of not less than the period required for retention of public records.
When it is required that documents be prepared by a registered design professional, the code official shall be authorized to require the owner to engage and designate on the building permit application a registered design professional who shall act as the registered design professional in responsible charge. If the circumstances require, the owner shall designate a substitute registered design professional in responsible charge who shall perform the duties required of the original registered design professional in responsible charge. The code official shall be notified in writing by the owner if the registered design professional in responsible charge is changed or is unable to continue to perform the duties. The registered design professional in responsible charge shall be responsible for reviewing and coordinating submittal documents prepared by others, including phased and deferred submittal items, for compatibility with the design of the building. Where structural observation is required, the inspection program shall name the individual or firms who are to perform structural observation and describe the stages of construction at which structural observation is to occur.
The code official is authorized to issue a permit for temporary uses. Such permits shall be limited as to time of service but shall not be permitted for more than 180 days. The code official is authorized to grant extensions for demonstrated cause.
Temporary uses shall conform to the structural strength, fire safety, means of egress, accessibility, light, ventilation and sanitary requirements of this code as necessary to ensure the public health, safety and general welfare.
The code official is authorized to give permission to temporarily supply and use power in part of an electric installation before such installation has been fully completed and the final certificate of completion has been issued. The part covered by the temporary certificate shall comply with the requirements specified for temporary lighting, heat or power in NFPA 70.
The code official is authorized to terminate such permit for a temporary use and to order the temporary use to be discontinued.
A permit shall not be valid until the fees prescribed by law have been paid. Nor shall an amendment to a permit be released until the additional fee, if any, has been paid.
On buildings, electrical, gas, mechanical, and plumbing systems or alterations requiring a permit, a fee for each permit shall be paid as required in accordance with the schedule as established by the applicable governing authority.
The applicant for a permit shall provide an estimated permit value at time of application. Permit valuations shall include total value of work including materials and labor for which the permit is being issued, such as electrical, gas, mechanical, plumbing equipment, and permanent systems. If, in the opinion of the code official, the valuation is underestimated on the application, the permit shall be denied unless the applicant can show detailed estimates to meet the approval of the code official. Final building permit valuation shall be set by the code official.
Any person who commences any work before obtaining the necessary permits shall be subject to an additional fee established by the code official that shall be in addition to the required permit fees.
The payment of the fee for the construction, alteration, removal, or demolition of work done in connection to or concurrently with the work authorized by a building permit shall not relieve the applicant or holder of the permit from the payment of other fees that are prescribed by law.
The code official is authorized to establish a refund policy.
Construction or work for which a permit is required shall be subject to inspection by the code official, and such construction or work shall remain accessible and exposed for inspection purposes until approved. Approval as a result of an inspection shall not be construed to be an approval of a violation of the provisions of this code or of other ordinances of the jurisdiction. Inspections presuming to give authority to violate or cancel the provisions of this code or of other ordinances of the jurisdiction shall not be valid. It shall be the duty of the permit applicant to cause the work to remain accessible and exposed for inspection purposes. Neither the code official nor the jurisdiction shall be liable for expense entailed in the removal or replacement of any material required to allow inspection.
Before issuing a permit, the code official is authorized to examine or cause to be examined buildings and sites for which an application has been filed.
The code official, upon notification, shall make the inspections set forth in Sections 109.3.1 through 109.3.9.
Footing and foundation inspections shall be made after excavations for footings are complete and any required reinforcing steel is in place. For concrete foundations, any required forms shall be in place prior to inspection. Materials for the foundation shall be on the job, except where concrete is ready-mixed in accordance with ASTM C 94, the concrete need not be on the job.
Concrete slab and under-floor inspections shall be made after in-slab or under-floor reinforcing steel and building service equipment, conduit, piping accessories, and other ancillary equipment items are in place but before any concrete is placed or floor sheathing installed, including the sub floor.
For additions and substantial improvements to existing buildings in flood hazard areas, upon placement of the lowest floor, including basement, and prior to further vertical construction, the elevation documentation required in the International Building Code shall be submitted to the code official.
Framing inspections shall be made after the roof deck or sheathing, all framing, fire blocking, and bracing are in place and pipes, chimneys, and vents to be concealed are complete and the rough electrical, plumbing, heating wires, pipes, and ducts are approved.

Lath and gypsum board inspections shall be made after lathing and gypsum board, interior and exterior, is in place but before any plastering is applied or before gypsum board joints and fasteners are taped and finished.

Exception: Gypsum board that is not part of a fire-resistance-rated assembly or a shear assembly.
Protection of joints and penetrations in fire-resistance-rated assemblies, smoke barriers and smoke partitions shall not be concealed from view until inspected and approved.
In addition to the inspections specified above, the code official is authorized to make or require other inspections of any construction work to ascertain compliance with the provisions of this code and other laws that are enforced by the Department of Building Safety.
Special inspections shall be required in accordance with the International Building Code.
The final inspection shall be made after all work required by the building permit is completed.
The code official is authorized to accept reports of approved inspection agencies, provided such agencies satisfy the requirements as to qualifications and reliability.
It shall be the duty of the holder of the building permit or their duly authorized agent to notify the code official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for any inspections of such work that are required by this code.
Work shall not be done beyond the point indicated in each successive inspection without first obtaining the approval of the code official. The code official, upon notification, shall make the requested inspections and shall either indicate the portion of the construction that is satisfactory as completed or shall notify the permit holder or an agent of the permit holder wherein the same fails to comply with this code. Any portions that do not comply shall be corrected and such portion shall not be covered or concealed until authorized by the code official.
No altered area of a building and no relocated building shall be used or occupied, and no change in the existing occupancy classification of a building or portion thereof shall be made until the code official has issued a certificate of occupancy therefor as provided herein. Issuance of a certificate of occupancy shall not be construed as an approval of a violation of the provisions of this code or of other ordinances of the jurisdiction.

After the code official inspects the building and finds no violations of the provisions of this code or other laws that are enforced by the Department of Building Safety, the code official shall issue a certificate of occupancy that shall contain the following:

  1. The building permit number.
  2. The address of the structure.
  3. The name and address of the owner.
  4. A description of that portion of the structure for which the certificate is issued.
  5. A statement that the described portion of the structure has been inspected for compliance with the requirements of this code for the occupancy and division of occupancy and the use for which the proposed occupancy is classified.
  6. The name of the code official.
  7. The edition of the code under which the permit was issued.
  8. The use and occupancy in accordance with the provisions of the International Building Code.
  9. The type of construction as defined in the International Building Code.
  10. The design occupant load and any impact the alteration has on the design occupant load of the area not within the scope of the work.
  11. If fire protection systems are provided, whether the fire protection systems are required.
  12. Any special stipulations and conditions of the building permit.
The code official is authorized to issue a temporary certificate of occupancy before the completion of the entire work covered by the permit, provided that such portion or portions shall be occupied safely. The code official shall set a time period during which the temporary certificate of occupancy is valid.
The code official is authorized to, in writing, suspend or revoke a certificate of occupancy or completion issued under the provisions of this code wherever the certificate is issued in error or on the basis of incorrect information supplied, or where it is determined that the building or structure or portion thereof is in violation of any ordinance or regulation or any of the provisions of this code.
No person shall make connections from a utility, source of energy, fuel, or power to any building or system that is regulated by this code for which a permit is required, until approved by the code official.
The code official shall have the authority to authorize the temporary connection of the building or system to the utility source of energy, fuel, or power.
The code official shall have the authority to authorize disconnection of utility service to the building, structure or system regulated by this code and the referenced codes and standards in case of emergency where necessary to eliminate an immediate hazard to life or property or when such utility connection has been made without the approval required by Section 111.1 or 111.2. The code official shall notify the serving utility and, wherever possible, the owner and occupant of the building, structure or service system of the decision to disconnect prior to taking such action. If not notified prior to disconnecting, the owner or occupant of the building, structure or service system shall be notified in writing, as soon as practical thereafter.
In order to hear and decide appeals of orders, decisions, or determinations made by the code official relative to the application and interpretation of this code, there shall be and is hereby created a board of appeals. The board of appeals shall be appointed by the governing body and shall hold office at its pleasure. The board shall adopt rules of procedure for conducting its business.
An application for appeal shall be based on a claim that the true intent of this code or the rules legally adopted thereunder have been incorrectly interpreted, the provisions of this code do not fully apply, or an equally good or better form of construction is proposed. The board shall have no authority to waive requirements of this code.
The board of appeals shall consist of members who are qualified by experience and training to pass on matters pertaining to building construction and are not employees of the jurisdiction.
It shall be unlawful for any person, firm, or corporation to repair, alter, extend, add, move, remove, demolish, or change the occupancy of any building or equipment regulated by this code or cause same to be done in conflict with or in violation of any of the provisions of this code.
The code official is authorized to serve a notice of violation or order on the person responsible for the repair, alteration, extension, addition, moving, removal, demolition, or change in the occupancy of a building in violation of the provisions of this code or in violation of a permit or certificate issued under the provisions of this code. Such order shall direct the discontinuance of the illegal action or condition and the abatement of the violation.
If the notice of violation is not complied with promptly, the code official is authorized to request the legal counsel of the jurisdiction to institute the appropriate proceeding at law or in equity to restrain, correct, or abate such violation or to require the removal or termination of the unlawful occupancy of the building or structure in violation of the provisions of this code or of the order or direction made pursuant thereto.
Any person who violates a provision of this code or fails to comply with any of the requirements thereof or who repairs or alters or changes the occupancy of a building or structure in violation of the approved construction documents or directive of the code official or of a permit or certificate issued under the provisions of this code shall be subject to penalties as prescribed by law.
Whenever the code official finds any work regulated by this code being performed in a manner contrary to the provisions of this code or in a dangerous or unsafe manner, the code official is authorized to issue a stop work order.
The stop work order shall be in writing and shall be given to the owner of the property involved or to the owner's agent, or to the person doing the work. Upon issuance of a stop work order, the cited work shall immediately cease. The stop work order shall state the reason for the order and the conditions under which the cited work will be permitted to resume.
Any person who shall continue any work after having been served with a stop work order, except such work as that person is directed to perform to remove a violation or unsafe condition, shall be subject to penalties as prescribed by law.
Buildings, structures or equipment that are or hereafter become unsafe, shall be taken down, removed or made safe as the code official deems necessary and as provided for in this code.
The code official shall cause a report to be filed on an unsafe condition. The report shall state the occupancy of the structure and the nature of the unsafe condition.
If an unsafe condition is found, the code official shall serve on the owner, agent, or person in control of the structure a written notice that describes the condition deemed unsafe and specifies the required repairs or improvements to be made to abate the unsafe condition, or that requires the unsafe building to be demolished within a stipulated time. Such notice shall require the person thus notified to declare immediately to the code official acceptance or rejection of the terms of the order.
Such notice shall be deemed properly served if a copy thereof is delivered to the owner personally; sent by certified or registered mail addressed to the owner at the last known address with the return receipt requested; or delivered in any other manner as prescribed by local law. If the certified or registered letter is returned showing that the letter was not delivered, a copy thereof shall be posted in a conspicuous place in or about the structure affected by such notice. Service of such notice in the foregoing manner upon the owner's agent or upon the person responsible for the structure shall constitute service of notice upon the owner.
The building or equipment determined to be unsafe by the code official is permitted to be restored to a safe condition. To the extent that repairs, alterations, or additions are made or a change of occupancy occurs during the restoration of the building, such repairs, alterations, additions, or change of occupancy shall comply with the requirements of this code.
When, in the opinion of the code official, there is imminent danger of failure or collapse of a building that endangers life, or when any building or part of a building has fallen and life is endangered by the occupation of the building, or when there is actual or potential danger to the building occupants or those in the proximity of any structure because of explosives, explosive fumes or vapors, or the presence of toxic fumes, gases, or materials, or operation of defective or dangerous equipment, the code official is hereby authorized and empowered to order and require the occupants to vacate the premises forthwith. The code official shall cause to be posted at each entrance to such structure a notice reading as follows: "This Structure Is Unsafe and Its Occupancy Has Been Prohibited by the Code Official." It shall be unlawful for any person to enter such structure except for the purpose of securing the structure, making the required repairs, removing the hazardous condition, or of demolishing the same.
Notwithstanding other provisions of this code, whenever, in the opinion of the code official, there is imminent danger due to an unsafe condition, the code official shall order the necessary work to be done, including the boarding up of openings, to render such structure temporarily safe whether or not the legal procedure herein described has been instituted; and shall cause such other action to be taken as the code official deems necessary to meet such emergency.
When necessary for public safety, the code official shall temporarily close structures and close or order the authority having jurisdiction to close sidewalks, streets, public ways, and places adjacent to unsafe structures, and prohibit the same from being utilized.
For the purposes of this section, the code official shall employ the necessary labor and materials to perform the required work as expeditiously as possible.
Costs incurred in the performance of emergency work shall be paid by the jurisdiction. The legal counsel of the jurisdiction shall institute appropriate action against the owner of the premises where the unsafe structure is or was located for the recovery of such costs.
Any person ordered to take emergency measures shall comply with such order forthwith. Any affected person shall thereafter, upon petition directed to the appeals board, be afforded a hearing as described in this code.
The code official shall order the owner of any premises upon which is located any structure that in the code official's judgment is so old, dilapidated, or has become so out of repair as to be dangerous, unsafe, insanitary, or otherwise unfit for human habitation or occupancy, and such that it is unreasonable to repair the structure, to demolish and remove such structure; or if such structure is capable of being made safe by repairs, to repair and make safe and sanitary or to demolish and remove at the owner's option; or where there has been a cessation of normal construction of any structure for a period of more than two years, to demolish and remove such structure.
All notices and orders shall comply with Section 113.
If the owner of a premises fails to comply with a demolition order within the time prescribed, the code official shall cause the structure to be demolished and removed, either through an available public agency or by contract or arrangement with private persons, and the cost of such demolition and removal shall be charged against the real estate upon which the structure is located and shall be a lien upon such real estate.
When any structure has been ordered demolished and removed, the governing body or other designated officer under said contract or arrangement aforesaid shall have the right to sell the salvage and valuable materials at the highest price obtainable. The net proceeds of such sale, after deducting the expenses of such demolition and removal, shall be promptly remitted with a report of such sale or transaction, including the items of expense and the amounts deducted, for the person who is entitled thereto, subject to any order of a court. If such a surplus does not remain to be turned over, the report shall so state.
UpCodes Premium
Leverage the most sophisticated code compliance platform.
TRY FREE FOR TWO WEEKS VISIT PRICING