ADOPTS WITH AMENDMENTS:

International Building Code 2015 (IBC 2015)

Heads up: There are no amended sections in this chapter.
The provisions of this chapter shall govern special building construction including membrane structures, temporary structures, pedestrian walkways and tunnels, automatic vehicular gates, awnings and canopies, marquees, signs, and towers and antennas.
The provisions of Sections 3102.1 through 3102.8 shall apply to air-supported, air-inflated, membranecovered cable, membrane-covered frame and tensile membrane structures, collectively known as membrane structures, erected for a period of 180 days or longer. Those erected for a shorter period of time shall comply with the International Fire Code. Membrane structures covering water storage facilities, water clarifiers, water treatment plants, sewage treatment plants, greenhouses and similar facilities not used for human occupancy are required to meet only the requirements of Sections 3102.3.1 and 3102.7. Membrane structures erected on a building, balcony, deck or other structure for any period of time shall comply with this section.
Tensile membrane structures, including permanent and temporary structures, shall be designed and constructed in accordance with ASCE 55. The provisions in Sections 3102.3 through 3102.6 shall apply.
Noncombustible membrane structures shall be classified as Type IIB construction. Noncombustible frame or cable-supported structures covered by an approved membrane in accordance with Section 3102.3.1 shall be classified as Type IIB construction. Heavy timber frame-supported structures covered by an approved membrane in accordance with Section 3102.3.1 shall be classified as Type IV construction. Other membrane structures shall be classified as Type V construction.
Exception: Plastic less than 30 feet (9144 mm) above any floor used in greenhouses, where occupancy by the general public is not authorized, and for aquaculture pond covers is not required to meet the fire propagation performance criteria of Test Method 1 or Test Method 2, as appropriate, of NFPA 701.
Membranes and interior liners shall be either noncombustible as set forth in Section 703.5 or meet the fire propagation performance criteria of Test Method 1 or Test Method 2, as appropriate, of NFPA 701 and the manufacturer's test protocol.
Exception: Plastic less than 20 mil (0.5 mm) in thickness used in greenhouses, where occupancy by the general public is not authorized, and for aquaculture pond covers is not required to meet the fire propagation performance criteria of Test Method 1 or Test Method 2, as appropriate, of NFPA 701.
The area of a membrane structure shall not exceed the limitations specified in Section 506.
Membrane structures shall not exceed one story nor shall such structures exceed the height limitations in feet specified in Section 504.3.
Exception: Noncombustible membrane structures serving as roofs only.
Membrane structures shall be permitted to be utilized as specified in this section as a portion of buildings of other types of construction. Height and area limits shall be as specified for the type of construction and occupancy of the building.
A noncombustible membrane shall be permitted for use as the roof or as a skylight of any building or atrium of a building of any type of construction provided the membrane is not less than 20 feet (6096 mm) above any floor, balcony or gallery.
A membrane meeting the fire propagation performance criteria of Test Method 1 or Test Method 2, as appropriate, of NFPA 701 shall be permitted to be used as the roof or as a skylight on buildings of Type IIB, III, IV and V construction, provided the membrane is not less than 20 feet (6096 mm) above any floor, balcony or gallery.
The structure shall be designed and constructed to sustain dead loads; loads due to tension or inflation; live loads including wind, snow or flood and seismic loads and in accordance with Chapter 16.
For membrane-covered frame structures, the membrane shall not be considered to provide lateral restraint in the calculation of the capacities of the frame members.
Air-supported and air-inflated structures shall be provided with primary and auxiliary inflation systems to meet the minimum requirements of Sections 3102.8.1 through 3102.8.3.
This inflation system shall consist of one or more blowers and shall include provisions for automatic control to maintain the required inflation pressures. The system shall be so designed as to prevent overpressurization of the system.
In addition to the primary inflation system, in buildings larger than 1,500 square feet (140 m2) in area, an auxiliary inflation system shall be provided with sufficient capacity to maintain the inflation of the structure in case of primary system failure. The auxiliary inflation system shall operate automatically when there is a loss of internal pressure and when the primary blower system becomes inoperative.
Blower equipment shall meet all of the following requirements:
  1. Blowers shall be powered by continuous-rated motors at the maximum power required for any flow condition as required by the structural design.
  2. Blowers shall be provided with inlet screens, belt guards and other protective devices as required by the building official to provide protection from injury.
  3. Blowers shall be housed within a weather-protecting structure.
  4. Blowers shall be equipped with backdraft check dampers to minimize air loss when inoperative.
  5. Blower inlets shall be located to provide protection from air contamination. The location of inlets shall be approved.
Wherever an auxiliary inflation system is required, an approved standby power-generating system shall be provided. The system shall be equipped with a suitable means for automatically starting the generator set upon failure of the normal electrical service and for automatic transfer and operation of all of the required electrical functions at full power within 60 seconds of such service failure. Standby power shall be capable of operating independently for not less than 4 hours.
A system capable of supporting the membrane in the event of deflation shall be provided for in air-supported and air-inflated structures having an occupant load of 50 or more or where covering a swimming pool regardless of occupant load. The support system shall be capable of maintaining membrane structures used as a roof for Type I construction not less than 20 feet (6096 mm) above floor or seating areas. The support system shall be capable of maintaining other membranes not less than 7 feet (2134 mm) above the floor, seating area or surface of the water.
The provisions of Sections 3103.1 through 3103.4 shall apply to structures erected for a period of less than 180 days. Tents and other membrane structures erected for a period of less than 180 days shall comply with the International Fire Code. Those erected for a longer period of time shall comply with applicable sections of this code.
Temporary structures and uses shall conform to the structural strength, fire safety, means of egress, accessibility, light, ventilation, and sanitary requirements of this code as necessary to ensure public health, safety, and general welfare.
Temporary structures that cover an area greater than 120 square feet (11.16 m2), including connecting areas or spaces with a common means of egress or entrance that are used or intended to be used for the gathering together of 10 or more persons, shall not be erected, operated or maintained for any purpose without obtaining a permit from the building official.
A permit application and construction documents shall be submitted for each installation of a temporary structure. The construction documents shall include a site plan indicating the location of the temporary structure and information delineating the means of egress and the occupant load.
Temporary structures shall be located in accordance with the requirements of Table 602 based on the fire-resistance rating of the exterior walls for the proposed type of construction.

3103.4 Means of Egress

ILLUSTRATION
Temporary structures shall conform to the means of egress requirements of Chapter 10 and shall have an exit access travel distance of 100 feet (30 480 mm) or less.
This section shall apply to connections between buildings such as pedestrian walkways or tunnels, located at, above or below grade level, that are used as a means of travel by persons. The pedestrian walkway shall not contribute to the building area or the number of stories or height of connected buildings.
Pedestrian walkways shall be designed and constructed in accordance with Sections 3104.2 through 3104.9. Tunnels shall be designed and constructed in accordance with Sections 3104.2 and 3104.10.
Buildings connected by pedestrian walkways or tunnels shall be considered to be separate structures.
Exceptions:
  1. Buildings that are on the same lot and considered as portions of a single building in accordance with Section 503.1.2.
  2. For purposes of calculating the number of Type B units required by Chapter 11, structurally connected buildings and buildings with multiple wings shall be considered one structure.
The pedestrian walkway shall be of noncombustible construction.
Exceptions:
  1. Combustible construction shall be permitted where connected buildings are of combustible construction.
  2. Fire-retardant-treated wood, in accordance with Section 603.1, Item 1.3, shall be permitted for the roof construction of the pedestrian walkway where connected buildings are a minimum of Type I or II construction.

3104.4 Contents

AMENDMENT
This section has been amended at the state or city level.
Only materials and decorations conforming to 780 CMR 8.00: Interior Finishes and 527 CMR: Board of Fire Prevention Regulations and approved by the building official in consultation with the fire official shall be located in the pedestrian walkway.
The connection of a pedestrian walkway to a building shall comply with Section 3104.5.1, 3104.5.2, 3104.5.3 or 3104.5.4.
Exception: Buildings that are on the same lot and considered as portions of a single building in accordance with Section 503.1.2.

3104.5.1 Fire Barriers

ILLUSTRATION
Pedestrian walkways shall be separated from the interior of the building by not less than 2- hour fire barriers constructed in accordance with Section 707 and Sections 3104.5.1.1 through 3104.5.1.3.
Exterior walls of buildings connected to pedestrian walkways shall be 2-hour fire-resistance-rated. This protection shall extend not less than 10 feet (3048 mm) in every direction surrounding the perimeter of the pedestrian walkway.
Openings in exterior walls required to be fire-resistance-rated in accordance with Section 3104.5.1.1 shall be equipped with opening protectives providing a not less than 3/4-hour fire protection rating in accordance with Section 716.
The fire barrier shall be supported by construction as required by Section 707.5.1.
The wall separating the pedestrian walkway and the building shall comply with Section 3104.5.2.1 or 3104.5.2.2 where:
  1. The distance between the connected buildings is more than 10 feet (3048 mm).
  2. The pedestrian walkway and connected buildings are equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1, and the roof of the walkway is not more than 55 feet (16 764 mm) above grade connecting to the fifth, or lower, story above grade plane, of each building.
Exception: Open parking garages need not be equipped with an automatic sprinkler system.
The wall shall be capable of resisting the passage of smoke.
The wall shall be constructed of a tempered, wired or laminated glass wall and doors or glass separating the interior of the building from the pedestrian walkway. The glass shall be protected by an automatic sprinkler system in accordance with Section 903.3.1.1 that, when actuated, shall completely wet the entire surface of interior sides of the wall or glass. Obstructions shall not be installed between the sprinkler heads and the wall or glass. The glass shall be in a gasketed frame and installed in such a manner that the framing system will deflect without breaking (loading) the glass before the sprinkler operates.
Where the distance between the connected buildings is more than 10 feet (3048 mm), the walls at the intersection of the pedestrian walkway and each building need not be fire-resistance-rated provided both sidewalls of the pedestrian walkway are not less than 50 percent open with the open area uniformly distributed to prevent the accumulation of smoke and toxic gases. The roof of the walkway shall be located not more than 40 feet (12 160 mm) above grade plane, and the walkway shall only be permitted to connect to the third or lower story of each building.
Exception: Where the pedestrian walkway is protected with a sprinkler system in accordance with Section 903.3.1.1, the roof of the walkway shall be located not more than 55 feet (16 764 mm) above grade plane and the walkway shall only be permitted to connect to the fifth or lower story of each building.
Where exterior walls of connected buildings are required by Section 705 to have a fire-resistance rating greater than 2 hours, the walls at the intersection of the pedestrian walkway and each building need not be fire-resistance-rated provided:
  1. The pedestrian walkway is equipped throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.1.
  2. The roof of the walkway is not located more than 55 feet (16 764 mm) above grade plane and the walkway connects to the fifth, or lower, story above grade plane of each building.
Access shall be provided at all times to a pedestrian walkway that serves as a required exit.
The unobstructed width of pedestrian walkways shall be not less than 36 inches (914 mm). The total width shall be not greater than 30 feet (9144 mm).

3104.9 Exit Access Travel

ILLUSTRATION
The length of exit access travel shall be 200 feet (60 960 mm) or less.
Exceptions:
  1. Exit access travel distance on a pedestrian walkway equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 shall be 250 feet (76 200 mm) or less.
  2. Exit access travel distance on a pedestrian walkway constructed with both sides not less than 50 percent open shall be 300 feet (91 440 mm) or less.
  3. Exit access travel distance on a pedestrian walkway constructed with both sides not less than 50 percent open, and equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1, shall be 400 feet (122 m) or less.
Separation between the tunneled walkway and the building to which it is connected shall be not less than 2-hour fire-resistant construction and openings therein shall be protected in accordance with Table 716.5.
Awnings and canopies shall comply with the requirements of Sections 3105.2 through 3105.4 and other applicable sections of this code.
The following term is defined in Chapter 2:

RETRACTABLE AWNING.
Awnings and canopies shall be designed and constructed to withstand wind or other lateral loads and live loads as required by Chapter 16 with due allowance for shape, open construction and similar features that relieve the pressures or loads. Structural members shall be protected to prevent deterioration. Awnings shall have frames of noncombustible material, fire-retardant-treated wood, wood of Type IV size, or 1-hour construction with combustible or noncombustible covers and shall be either fixed, retractable, folding or collapsible.
Awnings and canopies shall be provided with an approved covering that meets the fire propagation performance criteria of Test Method 1 or Test Method 2, as appropriate, of NFPA 701 or has a flame spread index not greater than 25 when tested in accordance with ASTM E84 or UL 723.
Exception: The fire propagation performance and flame spread index requirements shall not apply to awnings installed on detached one- and two-family dwellings.
Marquees shall comply with Sections 3106.2 through 3106.5 and other applicable sections of this code.
The height or thickness of a marquee measured vertically from its lowest to its highest point shall be not greater than 3 feet (914 mm) where the marquee projects more than two-thirds of the distance from the lot line to the curb line, and shall be not greater than 9 feet (2743 mm) where the marquee is less than two-thirds of the distance from the lot line to the curb line.
Where the roof or any part thereof is a skylight, the skylight shall comply with the requirements of Chapter 24. Every roof and skylight of a marquee shall be sloped to downspouts that shall conduct any drainage from the marquee in such a manner so as not to spill over the sidewalk.
Every marquee shall be so located as not to interfere with the operation of any exterior standpipe, and such that the marquee does not obstruct the clear passage of stairways or exit discharge from the building or the installation or maintenance of street lighting.
A marquee shall be supported entirely from the building and constructed of noncombustible materials. Marquees shall be designed as required in Chapter 16. Structural members shall be protected to prevent deterioration.
Signs shall be designed, constructed and maintained in accordance with this code.
Towers shall be designed and constructed in accordance with the provisions of TIA-222. Towers shall be designed for seismic loads; exceptions related to seismic design listed in Section 2.7.3 of TIA-222 shall not apply. In Section 2.6.6.2 of TIA 222, the horizontal extent of Topographic Category 2, escarpments, shall be 16 times the height of the escarpment.
Exception: Single free-standing poles used to support antennas not greater than 75 feet (22 860 mm), measured from the top of the pole to grade, shall not be required to be noncombustible.
Towers shall be located such that guy wires and other accessories shall not cross or encroach upon any street or other public space, or over above-ground electric utility lines, or encroach upon any privately owned property without the written consent of the owner of the encroached-upon property, space or aboveground electric utility lines. Towers shall be equipped with climbing and working facilities in compliance with TIA-222. Access to the tower sites shall be limited as required by applicable OSHA, FCC and EPA regulations.

3109.1 General

AMENDMENT
This section has been amended at the state or city level.
Swimming pools shall comply with the requirements of sections 3109.2 through 3109.5 and other applicable sections of 780 CMR.
See also:
  1. 521 CMR 19.00: Recreational Facilities;
  2. 105 CMR 430.00: Minimum Standards for Recreational Camps for Children (State Sanitary Code: Chapter IV) and 105 CMR 435.00: Minimum Standards for Swimming Pools (State Sanitary Code: Chapter V).
Automatic vehicular gates shall comply with the requirements of Sections 3110.2 through 3110.4 and other applicable sections of this code.
The following term is defined in Chapter 2:

VEHICULAR GATE.
Vehicular gates intended for automation shall be designed, constructed and installed to comply with the requirements of ASTM F2200.
Vehicular gate openers, where provided, shall be listed in accordance with UL 325.
Photovoltaic panels and modules shall comply with the requirements of this code and the International Fire Code.
Photovoltaic panels and modules installed on a roof or as an integral part of a roof assembly shall comply with the requirements of Chapter 15 and the International Fire Code.

Section 3112 Temporary Overnight Shelters

AMENDMENT
This section has been amended at the state or city level.

3112.1 Scope and Purpose

AMENDMENT
This section has been amended at the state or city level.
The purpose of section 3112 is to establish reasonable standards for the use of facilities designed for other purposes to be safely occupied temporarily as places of overnight accommodation. In this regard, 780 CMR is not intended to serve as a barrier to those seeking to assist individuals in need, but instead to offer a means to ensure that a reasonable degree of life safety is provided.

3112.2 Temporary Overnight Shelters - Defined

AMENDMENT
This section has been amended at the state or city level.
For purposes of section 3112, a temporary overnight shelter shall be defined as any building, facility, or space therein designed and used primarily as a church or house of worship for religious services or instruction or related activities which is owned or operated by a religious organization and qualified for exemption under 26 U.S.C. § 501(c)(3) (the Internal Revenue Code). The primary use of the building, facility, or space therein is for religious services or instruction but may, on occasion, provide temporary overnight accommodation to a limited number of individuals for a limited period of time as provided for section 3112. Other groups or organizations wishing to offer overnight accommodations in buildings designed and constructed for other purposes shall file an application for change of use in accordance with section 105.

Temporary overnight shelters, as addressed in section 3112, shall be classified as R-1 Use. Express administrative and technical requirements found in section 3112 shall override more general requirements found elsewhere in 780 CMR.

3112.3 Approval and Temporary Certificate of Occupancy

AMENDMENT
This section has been amended at the state or city level.
In order to operate a temporary overnight shelter, a temporary certificate of occupancy shall first be issued by the building official. Application for a certificate shall be made as follows:
  1. The application shall contain information demonstrating that the structure meets the following requirements:
    1. It has been issued a valid certificate of occupancy for its current use.
    2. It is or will be equipped with a functioning sprinkler system or is suitably protected by a hard-wired smoke and/or heat detection and alarm system, and a carbon monoxide detection system in accordance with section 3112.6, Table 3112.6; and sections 3112.7 through 3112.14.
    3. It contains adequate means of egress relative to the number of approved overnight occupants.
    4. It contains adequate emergency lighting and egress signage.
    5. It contains the necessary facilities in accordance with the applicable guidelines promulgated by the Massachusetts Department of Public Health.
    6. Attestation that the structure meets the requirements of 521 CMR: Architectural Access Board.
    7. Attestation that the location is equipped with a hard-wired land line phone or voice over internet protocol ("VOIP") device for use in the event of an emergency.
  2. The application shall include the following:
    1. Zoning approval (if applicable).
    2. A plot plan (internet accessed satellite maps may be sufficient if properly labeled).
    3. A plan for compliance with the applicable guidelines promulgated by the Massachusetts Department of Public Health.
    4. A fire safety and evacuation plan. The plan shall include, but not be limited to:
      1. The identification of the anticipated nightly occupant load.
      2. A diagram of the bed and personal space layout.
      3. The identification of exits and aisles leading thereto.
      4. Outline of procedures for accounting for employees and occupants after evacuation.
      5. Outline of procedures for the evacuation of occupants with special needs.
      6. At time of activation, the head of the fire department shall be provided with the identification of the preferred and any alternative person responsible for reporting fires and other emergencies to the fire department.
      7. At time of activation, the head of the fire department shall be provided with a plan for assignment of personnel responsible for oversight of evacuation.
      8. A plan for training of employees relative to emergency evacuation.
    5. Identification of an on-site individual responsible for ensuring compliance with section 3112.
  3. Upon receipt of a completed application, the building official shall forward the application to the municipal fire chief and health official for their review. A site visit shall then be undertaken collectively by the building official, fire official, health official, the owner, and the applicant, or their respective designees. Said officials shall assess the suitability of the structure for issuance of a temporary certificate of occupancy and ensure the accuracy and efficiency of the documentation submitted in accordance with section 3112.3 items 1. and 2. Promptly after the site visit is completed, the building official shall either approve the application and issue the temporary certificate of occupancy, or deny the application, or approve the application and issue the temporary certificate of occupancy with conditions. The building official may condition the issuance of a certificate upon anything that he or she determines is necessary to ensure the safety of the occupants of the shelter and consistent with section 3112.1. Prior to taking action, the building official shall review the application with the fire chief and health official. The building official shall consider any recommendations made by the fire chief or health official with due regard for their concerns. However, the building official shall not issue any temporary certificate over the objection of the head of the fire department or the local board of health.
  4. Temporary certificates of occupancy shall not be issued for a period to exceed one year. Applications for renewal shall be reviewed in accordance with section 3112.3 items 1. through 3.
  5. If issued, the temporary certificate shall reflect the name of the organization it was issued to, the name of the party responsible for the operation of the shelter, the address, the issuance date, the expiration date, any conditions of issuance ordered pursuant to section 3112.3 item 3., and the maximum allowed occupant load.
  6. A temporary certificate of occupancy may be revoked by the building official at any time for a violation of any provision of section 3112, any violation of the applicable General Laws, or for any reason necessary to ensure the safety of the occupants of the structure. The terms of issuance of the certificate may similarly be modified. Any such action may be appealed to the Building Code Appeals Board in accordance with M.G.L. c. 143, § 100.

3112.4 Shelter Operation

AMENDMENT
This section has been amended at the state or city level.
  1. The party responsible for the operation of the temporary overnight shelter shall notify the municipal building official and fire chief in writing at least 48 hours prior to each period of operation. The notification shall include a statement as to the anticipated number of days the shelter will be in operation and an estimate as to the number of individuals who will be in occupancy per night. Notification shall similarly be made within 24 hours after use of the shelter has ended. The temporary certificate of occupancy issued pursuant to section 3112.3 shall be conspicuously posted at the main entrance to the shelter.
  2. A document shall be posted, in a location approved by the municipal building official and the head of the fire department, containing an accurate number and names of occupants on a nightly basis and a copy of the evacuation plan referenced section 3112.3 item 2.d. Such document shall also contain the names of all workers and volunteers who are overseeing or assisting in the usage on a nightly basis. The shelter shall be set up and operated in accordance with the documentation submitted pursuant to section 3112.3 item 2. and any conditions mandated under section 3112.3 item 3.

3112.5 Access by Public Officials

AMENDMENT
This section has been amended at the state or city level.
Access to the shelter for purposes of ensuring compliance with section 3112 shall be granted upon request by the building official, fire chief, health official, police chief or their respective designees.

3112.6 Limitations of Use

AMENDMENT
This section has been amended at the state or city level.
Use shall be limited as described in this section and Table 3112.6.
  1. A temporary overnight shelter identified with a "P" in Table 3112.6 equipped with an interconnected, monitored smoke and carbon monoxide detection and notification system as required by 780 CMR 9.00 may operate year-round for the following periods only:
    1. not more than 52 days during a calendar year;
    2. not more than seven consecutive days.
    Where the subject church/house of worship proper possesses a NFPA 13 fire sprinkler system throughout the building pursuant to the governing edition of NFPA 13 in effect when such system was installed, the temporary overnight shelter can be located anywhere in the church/house of worship, providing all other requirements of section 3112 inclusive are met. If the church/house of worship does not have an NFPA 13 fire sprinkler system installed throughout the building then the location of the temporary overnight shelter shall conform to the requirements set forth in Table 3112.6 (partial fire sprinklering of the temporary overnight shelter is required under certain circumstances addressed in Table 3112.6).

    TABLE 3112.6 LIMITATIONS OF USE
    Use Limitations for Temporary Overnight Shelters
    Location in Building Building Construction Type
    IA IB IIA IIB IIIA IIIB IV VA VB
    Basement
    (without direct access to outside)
    PS PS PS PS NP NP PS NP NP
    Basement
    (with direct access to outside)
    P P P P P P P P PS
    1st Floor P P P P P P P P P
    2nd Floor P P P P P P P P P
    3rd Floor P P P P PS PS PS PS PS
    4th Floor and above PS PS PS PS PS PS PS PS NP

    P= Permitted, see section 3112.6. PS= Permitted with sprinklers, see section 3112.6. NP = Not Permitted.
  2. Alternatively, a temporary overnight shelter identified with a "P" in Table 3112.6 may operate year-round for the following periods only:
    1. not more than 52 days during a calendar year,
    2. not more than 14 consecutive days.
    Note: In order to achieve compliance with section 3112 a temporary overnight shelter shall be equipped with an interconnected, monitored smoke and carbon monoxide detection and notification alarm system as required by 780 CMR 9.00: Fire Protection Systems.
  3. A temporary overnight shelter identified with a "PS" in Table 3112.6 may operate year-round for the following periods only:
    1. not more than 104 days during a calendar year,
    2. not more than 30 consecutive days.
    Note: In order to achieve compliance with section 3112, a temporary overnight shelter shall be equipped with a full NFPA 13 sprinkler system, interconnected and monitored smoke and carbon monoxide detection and notification alarm system as required by 780 CMR 9.00: Fire Protetion Systems.
  4. The operating period limitations set forth in section 3112.6 may be exceeded in the event that a state of emergency is declared by the governor in accordance with St. 1950, c. 639 or due to an emergency deemed detrimental to the public health pursuant to M.G.L. c. 17, § 2A.

3112.7 Reserved

AMENDMENT
This section has been amended at the state or city level.

3112.8 Fire and CO Detection, Occupant Notification and Life Safety System Supervision

AMENDMENT
This section has been amended at the state or city level.
All temporary overnight shelters are required to install and have operational, an interconnected, monitored smoke and carbon monoxide detection and notification alarm system.

3112.9 Monitoring Requirements

AMENDMENT
This section has been amended at the state or city level.
Off-premise monitoring of the interconnected smoke and carbon monoxide detection and notification alarm system is required and shall conform to the requirements in 780 CMR 9.00: Fire Protection Systems and NFPA 72 and NFPA 720, as applicable.

3112.10 General Installation Requirements and Alarm Signal Precedence

AMENDMENT
This section has been amended at the state or city level.
Installation requirements for the interconnected, monitored smoke and carbon monoxide detection and notification alarm systems shall be in accordance with 780 CMR; 527 CMR: Board of Fire Prevention Regulations; the smoke alarm/detector and carbon monoxide alarm/detector manufacturers' requirements; NFPA 72 and NFPA 720, all as applicable. For alarm signal precedence, see section 916.5.

3112.11 Location of Fire and CO Detection and Occupant Notification Appliances

AMENDMENT
This section has been amended at the state or city level.
Buildings, facilities or spaces therein intended used as a temporary overnight shelters as defined in section 3112.2 shall incorporate, as applicable, smoke and carbon monoxide detection and notification alarm systems in:
  1. All shelter sleeping areas;
  2. All egress routes directly serving the shelter areas; and
  3. All common areas directly associated with the shelter areas.

3112.12 Listing

AMENDMENT
This section has been amended at the state or city level.
Smoke detectors/alarms shall be listed to UL 268; carbon monoxide detectors/alarms shall be listed to IAS/CSA 6.19 or UL 2075 as applicable.

3112.13 Power Source

AMENDMENT
This section has been amended at the state or city level.
The primary and secondary power sources for the low voltage or wireless, interconnected, monitored smoke detection system shall conform to the applicable requirements of NFPA 72; primary and secondary power requirements for CO detectors shall conform to the applicable requirements of NFPA 720.

3112.14 Fire Sprinkler Locations When Utilized

AMENDMENT
This section has been amended at the state or city level.
Where fire sprinklers are intended to be employed, as a minimum, such fire sprinkler system(s), complying w/applicable portions of NFPA 13, shall protect:
  1. All shelter sleeping areas;
  2. All egress routes directly serving the shelter areas; and
  3. All common areas directly associated with the shelter areas.

Section 3113 Temporary Emergency Use

AMENDMENT
This section has been amended at the state or city level.

3113.1 General

AMENDMENT
This section has been amended at the state or city level.
Except as noted herein, the provisions of section 3113 shall apply to temporary emergency uses.

3113.1.1 Permit Required

AMENDMENT
This section has been amended at the state or city level.
Temporary emergency uses shall not be operated or maintained for any purpose without first obtaining a permit from the municipal official having jurisdiction.

3113.2 Construction Documents

AMENDMENT
This section has been amended at the state or city level.
A written request for the temporary emergency use change, identifying the address-specific property is required.

3113.3 Certification

AMENDMENT
This section has been amended at the state or city level.
A temporary emergency use shall be so identified by a special certificate of use and occupancy as established for such purpose by the municipal or state building official in consultation with other appropriate municipal and state officials in accordance with procedures established for such purposes. See the Division of Professional Licensure website http://www.mass.gov/ocabr/government/ocaagencies/dpl-lp/opsi/ for an example of this special certificate of use and occupancy.

3113.4 Means of Egress

AMENDMENT
This section has been amended at the state or city level.
All temporary emergency uses shall conform to the means of egress requirements of 780 CMR 10.00: Means of Egress to the degree practicable.
UpCodes Premium
Leverage the most sophisticated code compliance platform.
TRY FREE FOR TWO WEEKS VISIT PRICING