ADOPTS WITH AMENDMENTS:

International Building Code 2009 (IBC 2009)

Heads up: There are no amended sections in this chapter.

The provisions contained in this appendix are not mandatory unless specifically referenced in the adopting ordinance.

The provisions of this appendix shall apply exclusively to agricultural buildings. Such buildings shall be classified as Group U and shall include the following uses:

  1. Livestock shelters or buildings, including shade structures and milking barns.
  2. Poultry buildings or shelters.
  3. Barns.
  4. Storage of equipment and machinery used exclusively in agriculture.
  5. Horticultural structures, including detached production greenhouses and crop protection shelters.
  6. Sheds.
  7. Grain silos.
  8. Stables.

C101.2 Occupancy Thresholds

AMENDMENT
This section has been amended at the state or city level.
Buildings that exceed an occupancy load of 100, that would otherwise be classified as Group U Agricultural, shall be classified per their intended use.

Exception. Riding arenas shall have an occupancy load limit of 100

C101.3 H-Use

AMENDMENT
This section has been amended at the state or city level.
Agricultural buildings used to store commercial fertilizers, herbicides, or pesticides shall comply with 527 CMR, 780 CMR, and M.G.L. c. 132B with its associated regulations, as applicable.

C102.1 General

AMENDMENT
This section has been amended at the state or city level.
Buildings classified as Group U Agricultural shall not exceed the area or height limits specified in Table C102.1.

TABLE C102.1—BASIC ALLOWABLE AREA FOR A GROUP U,
ONE STORY IN HEIGHT AND MAXIMUM HEIGHT OF SUCH OCCUPANCY
I II III and IV V
A B A B III A and IV III B A B
ALLOWABLE AREA (square feet)a
Unlimited 60,000 27,100 18,000 27,100 18,000 21,100 12,000
MAXIMUM HEIGHT IN STORIES
Unlimited 12 4 2 4 2 3 2
MAXIMUM HEIGHT IN FEET
Unlimited 160 65 55 65 55 50 40
For SI: 1 square foot = 0.0929 m2.
  1. See Section C102 for unlimited area under certain conditions.
  2. Greenhouses that comply with snow-load requirements are exempt from the area requirements set forth in C102.
The area of a one-story Group U agricultural building shall not be limited if the building is surrounded and adjoined by public ways or yards not less than 60 feet (18 288 mm) in width.

C102.3 Two-Story Unlimited Area

AMENDMENT
This section has been amended at the state or city level.
Mixed occupancies shall be protected in accordance with Section 508.

Exits shall be provided in accordance with Chapters 10 and 11.

Exceptions:

  1. The maximum travel distance from any point in the building to an approved exit shall not exceed 300 feet (91 440 mm).
  2. One exit is required for each 15,000 square feet (1393.5 m2) of area or fraction thereof.
UpCodes Premium
Leverage the most sophisticated code compliance platform.
TRY FREE FOR TWO WEEKS VISIT PRICING