ADOPTS WITH AMENDMENTS:

International Building Code 2009 (IBC 2009)

Heads up: There are no amended sections in this chapter.

3101.1 Scope

AMENDMENT
This section has been amended at the state or city level.
The provisions of this chapter shall govern special building construction including membrane structures, temporary structures, pedestrian walkways and tunnels, automatic vehicular gates, awnings and canopies, marquees, signs, and towers and antennas. Referenced in this chapter are the International Fire Code (IFC) and the International Mechanical Code 2009 (IMC). When referenced, the requirements within these codes shall be used to the extent as described in section 101.4.
The provisions of this section shall apply to air-supported, air-inflated, membrane-covered cable and membrane-covered frame structures, collectively known as membrane structures, erected for a period of 180 days or longer. Those erected for a shorter period of time shall comply with the International Fire Code. Membrane structures covering water storage facilities, water clarifiers, water treatment plants, sewage treatment plants, greenhouses and similar facilities not used for human occupancy are required to meet only the requirements of Sections 3102.3.1 and 3102.7. Membrane structures erected on a building, balcony, deck or other structure for any period of time shall comply with this section.

The following words and terms shall, for the purposes of this section and as used elsewhere in this code, have the meanings shown herein.

  1. AIR-INFLATED STRUCTURE. A structure that uses air-pressurized membrane beams, arches or other elements to enclose space. Occupants of such a structure do not occupy the pressurized area used to support the structure.
  2. AIR-SUPPORTED STRUCTURE. A building wherein the shape of the structure is attained by air pressure and occupants of the structure are within the elevated pressure area. Air-supported structures are of two basic types:
    1. Double skin. Similar to a single skin, but with an attached liner that is separated from the outer skin and provides an airspace which serves for insulation, acoustic, aesthetic or similar purposes.
    2. Single skin. Where there is only the single outer skin and the air pressure is directly against that skin.
  3. CABLE-RESTRAINED, AIR-SUPPORTED STRUCTURE. A structure in which the uplift is resisted by cables or webbings which are anchored to either foundations or dead men. Reinforcing cable or webbing is attached by various methods to the membrane or is an integral part of the membrane. This is not a cable-supported structure.
  4. MEMBRANE-COVERED CABLE STRUCTURE. A nonpressurized structure in which a mast and cable system provides support and tension to the membrane weather barrier and the membrane imparts stability to the structure.
  5. MEMBRANE-COVERED FRAME STRUCTURE. A nonpressurized building wherein the structure is composed of a rigid framework to support a tensioned membrane which provides the weather barrier.
  6. NONCOMBUSTIBLE MEMBRANE STRUCTURE. A membrane structure in which the membrane and all component parts of the structure are noncombustible.
Noncombustible membrane structures shall be classified as Type IIB construction. Noncombustible frame or cable-supported structures covered by an approved membrane in accordance with Section 3102.3.1 shall be classified as Type IIB construction. Heavy timber frame-supported structures covered by an approved membrane in accordance with Section 3102.3.1 shall be classified as Type IV construction. Other membrane structures shall be classified as Type V construction.
Exception: Plastic less than 30 feet (9144 mm) above any floor used in greenhouses, where occupancy by the general public is not authorized, and for aquaculture pond covers is not required to meet the fire propagation performance criteria of NFPA 701.
Membranes and interior liners shall be either noncombustible as set forth in Section 703.4 or meet the fire propagation performance criteria of NFPA 701 and the manufacturer's test protocol.
Exception: Plastic less than 20 mil (0.5 mm) in thickness used in greenhouses, where occupancy by the general public is not authorized, and for aquaculture pond covers is not required to meet the fire propagation performance criteria of NFPA 701.
The area of a membrane structure shall not exceed the limitations set forth in Table 503, except as provided in Section 506.
Membrane structures shall not exceed one story nor shall such structures exceed the height limitations in feet set forth in Table 503.
Exception: Noncombustible membrane structures serving as roofs only.
Membrane structures shall be permitted to be utilized as specified in this section as a portion of buildings of other types of construction. Height and area limits shall be as specified for the type of construction and occupancy of the building.
A noncombustible membrane shall be permitted for use as the roof or as a skylight of any building or atrium of a building of any type of construction provided it is at least 20 feet (6096 mm) above any floor, balcony or gallery.
A membrane meeting the fire propagation performance criteria of NFPA 701 shall be permitted to be used as the roof or as a skylight on buildings of Types IIB, III, IV and V construction, provided it is at least 20 feet (6096 mm) above any floor, balcony or gallery.
The structure shall be designed and constructed to sustain dead loads; loads due to tension or inflation; live loads including wind, snow or flood and seismic loads and in accordance with Chapter 16.
Air-supported and air-inflated structures shall be provided with primary and auxiliary inflation systems to meet the minimum requirements of Sections 3102.8.1 through 3102.8.3.
This inflation system shall consist of one or more blowers and shall include provisions for automatic control to maintain the required inflation pressures. The system shall be so designed as to prevent overpressurization of the system.
In addition to the primary inflation system, in buildings exceeding 1,500 square feet (140 m2) in area, an auxiliary inflation system shall be provided with sufficient capacity to maintain the inflation of the structure in case of primary system failure. The auxiliary inflation system shall operate automatically when there is a loss of internal pressure and when the primary blower system becomes inoperative.
Blower equipment shall meet all of the following requirements:
  1. Blowers shall be powered by continuous-rated motors at the maximum power required for any flow condition as required by the structural design.
  2. Blowers shall be provided with inlet screens, belt guards and other protective devices as required by the building official to provide protection from injury.
  3. Blowers shall be housed within a weather-protecting structure.
  4. Blowers shall be equipped with backdraft check dampers to minimize air loss when inoperative.
  5. Blower inlets shall be located to provide protection from air contamination. The location of inlets shall be approved.

3102.8.2 Standby Power

ILLUSTRATION
Wherever an auxiliary inflation system is required, an approved standby power-generating system shall be provided. The system shall be equipped with a suitable means for automatically starting the generator set upon failure of the normal electrical service and for automatic transfer and operation of all of the required electrical functions at full power within 60 seconds of such service failure. Standby power shall be capable of operating independently for a minimum of 4 hours.
A system capable of supporting the membrane in the event of deflation shall be provided for in air-supported and air-inflated structures having an occupant load of 50 or more or where covering a swimming pool regardless of occupant load. The support system shall be capable of maintaining membrane structures used as a roof for Type I construction not less than 20 feet (6096 mm) above floor or seating areas. The support system shall be capable of maintaining other membranes at least 7 feet (2134 mm) above the floor, seating area or surface of the water.
The provisions of this section shall apply to structures erected for a period of less than 180 days. Tents and other membrane structures erected for a period of less than 180 days shall comply with the International Fire Code. Those erected for a longer period of time shall comply with applicable sections of this code.
Temporary structures that cover an area in excess of 120 square feet (11.16 m2), including connecting areas or spaces with a common means of egress or entrance which are used or intended to be used for the gathering together of 10 or more persons, shall not be erected, operated or maintained for any purpose without obtaining a permit from the building official.
A permit application and construction documents shall be submitted for each installation of a temporary structure. The construction documents shall include a site plan indicating the location of the temporary structure and information delineating the means of egress and the occupant load.
Temporary structures shall be located in accordance with the requirements of Table 602 based on the fire-resistance rating of the exterior walls for the proposed type of construction.

3103.4 Means of Egress

ILLUSTRATION
Temporary structures shall conform to the means of egress requirements of Chapter 10 and shall have a maximum exit access travel distance of 100 feet (30 480 mm).

3104.1 General

AMENDMENT
This section has been amended at the state or city level.
This section shall apply to connections between buildings such as pedestrian walkways or tunnels, located at, above or below grade level, that are used as a means of travel by persons. The pedestrian walkway shall not contribute to the building area or the number of stories or height of connected buildings. Pedestrian walkways and tunnels shall also conform to applicable requirements of 521 CMR.

Connected buildings shall be considered to be separate structures.

Exceptions:
  1. Buildings on the same lot in accordance with Section 503.1.2.
  2. For purposes of calculating the number of Type B units required by Chapter 11, structurally connected buildings and buildings with multiple wings shall be considered one structure.
The pedestrian walkway shall be of noncombustible construction.
Exceptions:
  1. Combustible construction shall be permitted where connected buildings are of combustible construction.
  2. Fire-retardant-treated wood, in accordance with Section 603.1, Item 25.3, shall be permitted for the roof construction of the pedestrian walkway where connected buildings are a minimum of Type I or II construction.

3104.4 Contents

AMENDMENT
This section has been amended at the state or city level.
Only materials and decorations conforming to Chapter 8 and 527 CMR, and approved by the building official in consultation with the fire official, shall be located in the pedestrian walkway.
Walkways shall be separated from the interior of the building by not less than 2-hour fire barriers constructed in accordance with Section 707 or horizontal assemblies constructed in accordance with Section 712, or both. This protection shall extend vertically from a point 10 feet (3048 mm) above the walkway roof surface or the connected building roof line, whichever is lower, down to a point 10 feet (3048 mm) below the walkway and horizontally 10 feet (3048 mm) from each side of the pedestrian walkway. Openings within the l0-foot (3048 mm) horizontal extension of the protected walls beyond the walkway shall be equipped with devices providing a 3/4-hour fire protection rating in accordance with Section 715.
Exception: The walls separating the pedestrian walkway from a connected building and the openings within the 10- foot (3048 mm) horizontal extension of the protected walls beyond the walkway are not required to have a fire-resistance rating by this section where any of the following conditions exist:

  1. The distance between the connected buildings is more than 10 feet (3048 mm). The pedestrian walkway and connected buildings, except for open parking garages, are equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1. The wall is capable of resisting the passage of smoke or is constructed of a tempered, wired or laminated glass wall and doors subject to the following:

    1. The wall or glass separating the interior of the building from the pedestrian walkway shall be protected by an automatic sprinkler system in accordance with Section 903.3.1.1 and the sprinkler system shall completely wet the entire surface of interior sides of the wall or glass when actuated;
    2. The glass shall be in a gasketed frame and installed in such a manner that the framing system will deflect without breaking (loading) the glass before the sprinkler operates; and
    3. Obstructions shall not be installed between the sprinkler heads and the wall or glass.
  2. The distance between the connected buildings is more than 10 feet (3048 mm) and both sidewalls of the pedestrian walkway are at least 50 percent open with the open area uniformly distributed to prevent the accumulation of smoke and toxic gases.
  3. Buildings are on the same lot in accordance with Section 503.1.2.
  4. Where exterior walls of connected buildings are required by Section 705 to have a fire-resistance rating greater than 2 hours, the walkway shall be equipped throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.1.
The previous exception shall apply to pedestrian walkways having a maximum height above grade of three stories or 40 feet (12 192 mm), or five stories or 55 feet (16 764 mm) where sprinklered.
Access shall be provided at all times to a pedestrian walkway that serves as a required exit.
The unobstructed width of pedestrian walkways shall not be less than 36 inches (914 mm). The total width shall not exceed 30 feet (9144 mm).
The length of exit access travel shall not exceed 200 feet (60 960 mm).
Exceptions:
  1. Exit access travel distance on a pedestrian walkway equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 shall not exceed 250 feet (76 200 mm).
  2. Exit access travel distance on a pedestrian walkway constructed with both sides at least 50 percent open shall not exceed 300 feet (91 440 mm).
  3. Exit access travel distance on a pedestrian walkway constructed with both sides at least 50 percent open, and equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1, shall not exceed 400 feet (122 m).
Separation between the tunneled walkway and the building to which it is connected shall not be less than 2-hour fire-resistant construction and openings therein shall be protected in accordance with Table 715.4.
Awnings or canopies shall comply with the requirements of this section and other applicable sections of this code.

The following term shall, for the purposes of this section and as used elsewhere in this code, have the meaning shown herein.

RETRACTABLE AWNING. A retractable awning is a cover with a frame that retracts against a building or other structure to which it is entirely supported.

Awnings and canopies shall be designed and constructed to withstand wind or other lateral loads and live loads as required by Chapter 16 with due allowance for shape, open construction and similar features that relieve the pressures or loads. Structural members shall be protected to prevent deterioration. Awnings shall have frames of noncombustible material, fire-retardant-treated wood, wood of Type IV size, or 1-hour construction with combustible or noncombustible covers and shall be either fixed, retractable, folding or collapsible.
Canopies shall be constructed of a rigid framework with an approved covering that meets the fire propagation performance criteria of NFPA 701 or has a flame spread index not greater than 25 when tested in accordance with ASTM E 84 or UL 723.
Marquees shall comply with this section and other applicable sections of this code.
The maximum height or thickness of a marquee measured vertically from its lowest to its highest point shall not exceed 3 feet (914 mm) where the marquee projects more than two-thirds of the distance from the property line to the curb line, and shall not exceed 9 feet (2743 mm) where the marquee is less than two-thirds of the distance from the property line to the curb line.
Where the roof or any part thereof is a skylight, the skylight shall comply with the requirements of Chapter 24. Every roof and skylight of a marquee shall be sloped to downspouts that shall conduct any drainage from the marquee in such a manner so as not to spill over the sidewalk.
Every marquee shall be so located as not to interfere with the operation of any exterior standpipe, and such that the marquee does not obstruct the clear passage of stairways or exit discharge from the building or the installation or maintenance of street lighting.
A marquee shall be supported entirely from the building and constructed of noncombustible materials. Marquees shall be designed as required in Chapter 16. Structural members shall be protected to prevent deterioration.
Signs shall be designed, constructed and maintained in accordance with this code.
Towers shall be designed and constructed in accordance with the provisions of TIA-222.
Exception: Single free-standing poles used to support antennas not greater than 75 feet (22 860 mm), measured from the top of the pole to grade, shall not be required to be noncombustible.
Towers shall be located such that guy wires and other accessories shall not cross or encroach upon any street or other public space, or over above-ground electric utility lines, or encroach upon any privately owned property without the written consent of the owner of the encroached-upon property, space or above-ground electric utility lines. Towers shall be equipped with climbing and working facilities in compliance with TIA-222. Access to the tower sites shall be limited as required by applicable OSHA, FCC and EPA regulations.

3108.3 Grounding

AMENDMENT
This section has been amended at the state or city level.
Towers shall be permanently and effectively grounded per the requirements of 527 CMR 12.00: 2008 Massachusetts Electrical Code (Amendments).

3109.1 General

AMENDMENT
This section has been amended at the state or city level.
Swimming pools shall comply with the requirements of this section and other applicable sections of this code.
See also the following for applicable requirements:
  1. M.G.L. c. 140, § 206 for enclosures to public and semi-public outdoor in-ground swimming pools;
  2. 521 CMR 19.00: Recreational Facilities;
  3. 105 CMR 430.000: Minimum Standards for Recreational Camps for Children (State Sanitary Code: Chapter IV) and 105 CMR 435.00: Minimum Standards for Swimming Pools (State Sanitary Code: Chapter V);
  4. 527 CMR 12.00: 2008 Massachusetts Electrical Code (Amendments) for the installation of electrical wiring and electrical devices
  5. 248 CMR for the installation of gas-fired pool heaters

The following word and term shall, for the purposes of this section and as used elsewhere in this code, have the meaning shown herein.

SWIMMING POOLS. Any structure intended for swimming, recreational bathing or wading that contains water over 24 inches (610 mm) deep. This includes in-ground, above-ground and on-ground pools; hot tubs; spas and fixed-in-place wading pools.

3109.3 Public Swimming Pools

AMENDMENT
This section has been amended at the state or city level.
Residential swimming pools shall comply with Sections 3109.4.1 through 3109.4.3.
Exception: A swimming pool with a power safety cover or a spa with a safety cover complying with ASTM F 1346.
The top of the barrier shall be at least 48 inches (1219 mm) above grade measured on the side of the barrier that faces away from the swimming pool. The maximum vertical clearance between grade and the bottom of the barrier shall be 2 inches (51 mm) measured on the side of the barrier that faces away from the swimming pool. Where the top of the pool structure is above grade, the barrier is authorized to be at ground level or mounted on top of the pool structure, and the maximum vertical clearance between the top of the pool structure and the bottom of the barrier shall be 4 inches (102 mm).
Openings in the barrier shall not allow passage of a 4-inch-diameter (102 mm) sphere.
Solid barriers which do not have openings shall not contain indentations or protrusions except for normal construction tolerances and tooled masonry joints.
Where the barrier is composed of horizontal and vertical members and the distance between the tops of the horizontal members is less than 45 inches (1143 mm), the horizontal members shall be located on the swimming pool side of the fence. Spacing between vertical members shall not exceed 13/4 inches (44 mm) in width. Where there are decorative cutouts within vertical members, spacing within the cutouts shall not exceed 13/4 inches (44 mm) in width.
Where the barrier is composed of horizontal and vertical members and the distance between the tops of the horizontal members is 45 inches (1143 mm) or more, spacing between vertical members shall not exceed 4 inches (102 mm). Where there are decorative cutouts within vertical members, spacing within the cutouts shall not exceed 13/4 inches (44 mm) in width.
Maximum mesh size for chain link fences shall be a 21/4 inch square (57 mm square) unless the fence is provided with slats fastened at the top or the bottom which reduce the openings to no more than 13/4 inches (44 mm).
Where the barrier is composed of diagonal members, the maximum opening formed by the diagonal members shall be no more than 13/4 inches (44 mm).
Access doors or gates shall comply with the requirements of Sections 3109.4.1.1 through 3109.4.1.6 and shall be equipped to accommodate a locking device. Pedestrian access doors or gates shall open outward away from the pool and shall be self-closing and have a self-latching device. Doors or gates other than pedestrian access doors or gates shall have a self-latching device. Release mechanisms shall be in accordance with Sections 1008.1.9 and 1109.12. Where the release mechanism of the self-latching device is located less than 54 inches (1372 mm) from the bottom of the door or gate, the release mechanism shall be located on the pool side of the door or gate at least 3 inches (76 mm) below the top of the door or gate, and the door or gate and barrier shall have no opening greater than 1/2 inch (12.7 mm) within 18 inches (457 mm) of the release mechanism.
Where a wall of a dwelling serves as part of the barrier, one of the following shall apply:
  1. Doors with direct access to the pool through that wall shall be equipped with an alarm that produces an audible warning when the door and/or its screen, if present, are opened. The alarm shall be listed and labeled in accordance with UL 2017. In dwellings not required to be Accessible units, Type A units or Type B units, the deactivation switch shall be located 54 inches (1372 mm) or more above the threshold of the door. In dwellings required to be Accessible units, Type A units or Type B units, the deactivation switch(es) shall be located at 54 inches (1372 mm) maximum and 48 inches (1219 mm) minimum above the threshold of the door.
  2. The pool shall be equipped with a power safety cover that complies with ASTM F 1346.
  3. Other means of protection, such as self-closing doors with self-latching devices, which are approved, shall be accepted so long as the degree of protection afforded is not less than the protection afforded by Section 3109.4.1.8, Item 1 or 2.
Where an aboveground pool structure is used as a barrier or where the barrier is mounted on top of the pool structure, and the means of access is a ladder or steps, then the ladder or steps either shall be capable of being secured, locked or removed to prevent access, or the ladder or steps shall be surrounded by a barrier which meets the requirements of Sections 3109.4.1.1 through 3109.4.1.8. When the ladder or steps are secured, locked or removed, any opening created shall not allow the passage of a 4-inch-diameter (102 mm) sphere.
Walls surrounding indoor swimming pools shall not be required to comply with Section 3109.4.1.8.
Barriers shall be located so as to prohibit permanent structures, equipment or similar objects from being used to climb the barriers.
Suction outlets shall be designed and installed in accordance with ANSI/APSP-7.
Automatic vehicular gates shall comply with the requirements of this section and other applicable sections of this code.

The following word and term shall, for the purposes of this section and as used elsewhere in this code, have the meaning shown herein.

VEHICULAR GATE. A gate that is intended for use at a vehicular entrance or exit to a facility, building or portion thereof, and that is not intended for use by pedestrian traffic.

Vehicular gates intended for automation shall be designed, constructed and installed to comply with the requirements of ASTM F 2200.
Vehicular gate openers, when provided, shall be listed in accordance with UL 325.

Section 3111 Temporary Overnight Shelters

AMENDMENT
This section has been amended at the state or city level.

3111.1 Scope and Purpose

AMENDMENT
This section has been amended at the state or city level.
The purpose of section 3111 is to establish reasonable standards for the use of facilities designed for other purposes to be safely occupied temporarily as places of overnight accommodation. In this regard, the State Building Code is not intended to serve as a barrier to those seeking to assist individuals in need, but instead to offer a means to ensure that a reasonable degree of life safety is provided.

3111.2 Temporary Overnight Shelters - Defined

AMENDMENT
This section has been amended at the state or city level.
For purposes of section 3111, a temporary overnight shelter shall be defined as any building, facility, or space therein designed and used primarily as a church or house of worship for religions services or instruction or related activities which is owned or operated by a religions organization and qualified for exemption under 26 U.S.C. section 501(c)(3) of the Internal Revenue Code. The primary use of the building, facility, or space therein is for religious services or instruction but may, on occasion, provide temporary overnight accommodation to a limited number of individuals for a limited period of time as provided for. Other groups organizations wishing to offer overnight accommodations in buildings designed and constructed for other purposes shall file an applicaöon for change of use in accordance with section 105.

Temporary overnight shelters, as addressed in section 3111, shall be classified as R-1 Use. Express administrative and technical requirements found in section 3111 shall override more general requirements found elsewhere in this code.

3111.3 Approval and Temporary Certificate of Occupancy

AMENDMENT
This section has been amended at the state or city level.
In order to operate a temporary overnight shelter, a temporary certificate of occupancy must first be issued by the building official. Application for a certificate shall be made as follows:
  1. The application must contain information demonstrating that the structure meets the following requirements:
    1. It has been issued a valid certificate of occupancy for its current use.
    2. It is or will be equipped with a functioning sprinkler system or is suitably protected by a hard-wired smoke and/or heat detection and alarm system, and a carbon monoxide detection system. Until January 1, 2013, battery operated detectors may be approved by the municipal building official and fire chief depending upon the location and in conformance with the Board of Fire Prevention Regulations 527 CMR 31.00: Carbon Monoxide Alarms for carbon monoxide (CO) requirements. Commencing January 1, 2013 the facility must be protected with fire protection systems in accordance with section 3111.6, Table 3111.6 and sections 3111.7 through 3111.14.
    3. It contains adequate means of egress relative to the number of approved overnight occupants.
    4. It contains adequate emergency lighting and egress signage.
    5. It contains the necessary facilities in accordance with the applicable guidelines promulgated by the Massachusetts Department of Public Health.
    6. Attestation that the structure meets the requirements of the Architectural Access Board's regulations at 521 CMR.
    7. Attestation that the location is equipped with a hard-wired land line phone for use in the event of an emergency.
  2. The application must include the following:
    1. Zoning approval (if applicable).
    2. A plot plan (internet accessed satellite maps may be sufficient if properly labeled).
    3. A plan for compliance with the applicable guidelines promulgated by the Massachusetts Department of Public Health.
    4. A fire safety and evacuation plan. The plan shall include, but not be limited to:
      1. The identification of the anticipated nightly occupant load.
      2. A diagram of the bed and personal space layout.
      3. The identification of exits and aisles leading thereto.
      4. Outline of procedures for accounting for employees and occupants after evacuation.
      5. Outline of procedures for the evacuation of occupants with special needs.
      6. At time of activation, the Head of the Fire Department shall be provided with the identification of the preferred and any alternative person responsible for reporting fires and other emergencies to the fire department.
      7. At time of activation, the Head of the Fire Department shall be provided with a plan for assignment of personnel responsible for oversight of evacuation.
      8. A plan for training of employees relative to emergency evacuation.
    5. Identification of an on-site individual responsible for ensuring compliance with section 3111.
  3. Upon receipt of a completed application, the building official shall forward the application to the municipal fire chief and health official for their review. A site visit shall then be undertaken collectively by the building official, fire official, health official, building owner, and the applicant, or their respective designees. Said officials shall assess the suitability of the structure for issuance of a temporary certificate of occupancy and ensure the accuracy and efficiency of the documentation submitted in accordance with section 3111.3 items 1. and 2. Promptly after the site visit is completed, the building official shall either approve the application and issue the temporary certificate of occupancy, or deny the application, or approve the application and issue the temporary certificate of occupancy with conditions. The building official may condition the issuance of a certificate upon anything that he determines is necessary to ensure the safety of the occupants of the shelter and consistent with section 3111.1. Prior to taking action, the building official shall review the application with the fire chief and health official. The building official shall consider any recommendations made by the fire chief or health official with due regard for their concerns. However, the building official shall not issue any temporary certificate over the objection of the Head of the Fire Department or the local Board of Health.
  4. Temporary certificates of occupancy shall not be issued for a period to exceed one year. Applications for renewal shall be reviewed in accordance with section 3111.3 items 1. through 3.
  5. If issued, the temporary certificate shall reflect the name of the organization it was issued to, the name of the party responsible for the operation of the shelter, the address, of the shelter, the issuance date, the expiration date, any conditions of issuance ordered pursuant to section 3111.3 item 3., and the maximum allowed occupant load.
  6. A temporary certificate of occupancy may be revoked by the building official at any time for a violation of any provision of section 3111, any violation of the General Laws, or for any reason necessary to ensure the safety of the occupants of the structure. The terms of issuance of the certificate may similarly be modified. Any such action may be appealed to the Building Code Appeals Board in accordance with M.G.L. c. 143, § 100.

3111.4 Sbelter Operation

AMENDMENT
This section has been amended at the state or city level.
  1. The party responsible for the operation of the temporary overnight shelter must notify the municipal building official and fire chief in writing at least 48 hours prior to each period of operation. The notification must include a statement as to the anticipated number of days the shelter will be in operation and an estimate as to the number of individuals who will be in occupancy per night. Notification shall similarly be made within 24 hours after use of the shelter has ended.
  2. The temporary certificate of occupancy issued pursuant to section 3111.3 shall be conspicuously posted at the main entrance to the shelter.
  3. A document shall be posted, in a location approved by the municipal building official and the head of the fire department, containing an accurate number and names of occupants on a nightly basis and a copy of the evacuation plan referenced section 3111.3 item 2.d. Such document shall also contain the names of all workers and volunteers who are overseeing or assisting in the usage on a nightly basis. The shelter shall be set up and operated in accordance with the documentation submitted pursuant to section 3111.3 item 2. and any conditions mandated under Section 3111.3 item 3.

3111.5 Access by Public Officials

AMENDMENT
This section has been amended at the state or city level.
Access to the shelter for purposes of ensuring compliance with Section 3111 shall be granted upon request by the building official, fire chief, health official, police chief or their respective designees.

3111.6 Limitations of Use

AMENDMENT
This section has been amended at the state or city level.
Use shall be limited as described in this section and Table 3111.6.
  1. A temporary overnight shelter identified with a 'P' in table 3111.6 and where smoke and CO detection is battery-operated and not interconnected, may operate year-round for the following periods only:
    1. not more then 52 days during a calendar year,
    2. not more than seven consecutive days
    Note: Commencing January 1, 2013, all temporary overnight shelters shall be equipped with operational, interconnected, monitored smoke and carbon monoxide detection and notification alarm systems as required by chapter 9.

    Where the subject church/house of worship proper possesses a NFPA 13 fire sprinkler system throughout the building per the governing edition of NFPA 13 in effect when such system was installed, the temporary overnight shelter can be located anywhere in the church/house of worship, providing all other requirements of section 3111, inclusive are met. If the church/house of worship does not have an NFPA 13 fire sprinkler system installed throughout the building then the location of the temporary overnight shelter must conform to the requirements set forth in Table 3111.6 (partial fire sprinklering of the temporary overnight shelter is required under certain circumstances addressed in Table 3111.6).
  2. Alternatively, a temporary overnight shelter identified with a 'P' in Table 3111.6 may operate year-round for the following periods only:
    1. not more than 52 days during a calendar year,
    2. not more than 14 consecutive days.
    In order to achieve compliance with this section a temporary overnight shelter shall be equipped with an interconnected, monitored smoke and carbon monoxide detection and notification alarm system as required by Chapter 9.
  3. A temporary overnight shelter identified with a 'PS' in Table 3111.6 may operate year-round for the following periods only:
    1. not more than 104 days during a calendar year,
    2. not more than 30 consecutive days.
    Note: In order to achieve compliance with this section a temporary overnight shelter shall be equipped with a full NFPA 13 sprinkler system, interconnected and monitored smoke and carbon monoxide detection and notification alarm system as required by Chapter 9.
  4. The operating period limitations set forth in section 3111.6 may be exceeded in the event that a state of emergency is declared by the Governor in accordance with St. 1950, c. 639 or due to an emergency deemed detrimental to the public health pursuant to M.G.L. c. 17, § 2A.
TABLE 3111.6
Use Limitations for Temporary Overnight Shelters
Location in Building Building Constriction Type
IA IB IIA IIB IIIA IIIB IV VA VB
Basement
(without direct access to outside)
PS PS PS PS NP NP PS NP NP
Basement
(with direct access to outside)
P P P P P P P P PS
1st Floor P P P P P P P P P
2nd Floor P P P P P P P P P
3rd Floor P P P P PS PS PS PS PS
4th Floor and above PS PS PS PS PS PS PS PS NP
P = Permitted, see section 3111.6. PS = Permitted with sprinklers, see section 3111.6. NP = Not Permitted.
Subject to the provisions of section 3111.3, through January 1, 2013, a temporary overnight shelter may install and utilize battery only operated smoke and carbon monoxide detectors, and, off-premise supervision (monitoring) of these life safety devices is not required.
All temporary overnight shelters are required to install and have operational, an interconnected, monitored smoke and carbon monoxide detection and notification alarm system no later than January 1, 2013 as required in chapter 9.

3111.9 Monitoring Requirement

AMENDMENT
This section has been amended at the state or city level.
Off premise monitoring of the interconnected smoke and carbon monoxide detection and notification alarm system is required and shall conform to the requirements in chapter 9 and NFPA 72 and NFPA 720, as applicable.

3111.10 General Installation Requirements and Alarm Signal Precedence

AMENDMENT
This section has been amended at the state or city level.
Installation requirements for the interconnected, monitored smoke and carbon monoxide detection and notification alarm systems shall be in accordance with this code; 527 CMR 31.00: Carbon Monoxide Alarms; the smoke alarm/detector and carbon monoxide alarm/detector manufacturers' requirements; NFPA 72 and NFPA 720, all as applicable. For alarm signal precedence, see section 916.5.

3111.11 Location of Fire and CO Detection and Occupant Notification Appliances-Pre and Post 2012

AMENDMENT
This section has been amended at the state or city level.
Buildings, facilities or spaces therein intended used as a temporary overnight shelters as defined in section 3111.2 shall incorporate, as applicable, smoke and carbon monoxide detection and notification alarm systems in:
  1. All shelter sleeping areas;
  2. All egress routes directly serving the shelter areas;
  3. All common areas directly associated with the shelter areas.

3111.12 Listing

AMENDMENT
This section has been amended at the state or city level.
Smoke detectors/alarms shall be listed to UL 268; carbon monoxide detectors/alarms shall be listed to IAS/CSA 6.19 or UL 2075 as applicable.
Exception: Prior January 1, 2013, smoke alarms listed to UL 217 are allowed and battery-powered CO alarms, listed to UL-2034 are allowed.

3111.13 Power Source

AMENDMENT
This section has been amended at the state or city level.
The primary and secondary power sources for the low voltage or wireless, interconnected, monitored smoke detection system shall conform to the applicable requirements of NFPA 72; primary and secondary power requirements for CO detectors shall conform to the applicable requirements of NFPA 720.
Exception: Prior to January 1, 2013, smoke alarms listed to UL 217 are allowed and battery-powered CO alarms, listed to applicable sections of UL-2034 are allowed.

3111.14 Fire Sprinkler Locations When Utilized

AMENDMENT
This section has been amended at the state or city level.
Where fire sprinklers are intended employed, as a minimum, such fire sprinkler system(s), complying w/applicable portions of NFPA 13, shall protect:
  1. All shelter sleeping areas;
  2. All egress routes directly serving the shelter areas;
  3. All common areas directly associated with the shelter areas

3112 Temporary Emergency Use

AMENDMENT
This section has been amended at the state or city level.

3112.1 General

AMENDMENT
This section has been amended at the state or city level.
Except as noted herein, the provisions of section 3116 shall apply to temporary emergency uses.

3112.1.1 Permit Required

AMENDMENT
This section has been amended at the state or city level.
Temporary emergency uses shall not be operated or maintained for any purpose without first obtaining a permit from the municipal official having jurisdiction.

3112.2 Construction Documents

AMENDMENT
This section has been amended at the state or city level.
A written request for the Temporary Emergency Use change, identifying the address-specific property is required.

3112.3 Certification

AMENDMENT
This section has been amended at the state or city level.
A temporary emergency use shall be so identified by a special certificate of use and occupancy as established for such purpose (see the Department of Public Safety website www.mass.gov/dps for an example of this special certificate of use and occupancy) by the municipal or state building official in consultation with other appropriate municipal and state officials in accordance with procedures established for such purposes.

3112.4 Means of Egress

AMENDMENT
This section has been amended at the state or city level.
All temporary emergency uses shall conform to the means of egress requirements of Chapter 10 to the degree practicable.
UpCodes Premium
Leverage the most sophisticated code compliance platform.
TRY FREE FOR TWO WEEKS VISIT PRICING