- Allowable stress design in accordance with Sections 2304, 2305 and 2306.
- Load and resistance factor design in accordance with Sections 2304, 2305 and 2307.
- Conventional light-frame construction in accordance with Sections 2304 and 2308.
Exception: Buildings designed in accordance with the provisions of the AF&PA WFCM shall be deemed to meet the requirements of the provisions of Section 2308.
- The design and construction of log structures shall be in accordance with the provisions of ICC 400.
The following words and terms shall, for the purposes of this chapter, have the meanings shown herein.
ACCREDITATION BODY. An approved, third-party organization that is independent of the grading and inspection agencies, and the lumber mills, and that initially accredits and subsequently monitors, on a continuing basis, the competency and performance of a grading or inspection agency related to carrying out specific tasks.
BRACED WALL LINE. A series of braced wall panels in a single story that meets the requirements of Section 2308.3 or 2308.12.4.
BRACED WALL PANEL. A section of wall braced in accordance with Section 2308.9.3 or 2308.12.4.
COLLECTOR. A horizontal diaphragm element parallel and in line with the applied force that collects and transfers diaphragm shear forces to the vertical elements of the lateral-force-resisting system and/or distributes forces within the diaphragm.
CONVENTIONAL LIGHT-FRAME CONSTRUCTION. A type of construction whose primary structural elements are formed by a system of repetitive wood-framing members. See Section 2308 for conventional light-frame construction provisions.
CRIPPLE WALL. A framed stud wall extending from the top of the foundation to the underside of floor framing for the lowest occupied floor level.
DIAPHRAGM, UNBLOCKED. A diaphragm that has edge nailing at supporting members only. Blocking between supporting structural members at panel edges is not included. Diaphragm panels are field nailed to supporting members.
DRAG STRUT. See "Collector."
FIBERBOARD. A fibrous, homogeneous panel made from lignocellulosic fibers (usually wood or cane) and having a density of less than 31 pounds per cubic foot (pcf) (497 kg/m3) but more than 10 pcf (160 kg/m3).
GLUED BUILT-UP MEMBER. A structural element, the section of which is composed of built-up lumber, wood structural panels or wood structural panels in combination with lumber, all parts bonded together with structural adhesives.
GRADE (LUMBER). The classification of lumber in regard to strength and utility in accordance with American Softwood Lumber Standard DOC PS 20 and the grading rules of an approved lumber rules-writing agency.
HARDBOARD. A fibrous-felted, homogeneous panel made from lignocellulosic fibers consolidated under heat and pressure in a hot press to a density not less than 31 pcf (497 kg/m3).
NAILING, BOUNDARY. A special nailing pattern required by design at the boundaries of diaphragms.
NAILING, EDGE. A special nailing pattern required by design at the edges of each panel within the assembly of a diaphragm or shear wall.
NAILING, FIELD. Nailing required between the sheathing panels and framing members at locations other than boundary nailing and edge nailing.
NATIVE LUMBER. Native lumber is wood processed in the Commonwealth of Massachusetts by a mill registered in accordance with 780 CMR 110.R4. Such wood may be ungraded but is stamped or certified in accordance with 780 CMR 110.R4.
NATURALLY DURABLE WOOD. The heartwood of the following species with the exception that an occasional piece with corner sapwood is permitted if 90 percent or more of the width of each side on which it occurs is heartwood.
Decay resistant. Redwood, cedar, black locust and black walnut.
Termite resistant. Redwood, Alaska yellow-cedar, Eastern redcedar and both heartwood and all sapwood of Western redcedar.
NOMINAL SIZE (LUMBER). The commercial size designation of width and depth, in standard sawn lumber and glued-laminated lumber grades; somewhat larger than the standard net size of dressed lumber, in accordance with DOC PS 20 for sawn lumber and with the AF&PA NDS for glued-laminated lumber.
PARTICLEBOARD. A generic term for a panel primarily composed of cellulosic materials (usually wood), generally in the form of discrete pieces or particles, as distinguished from fibers. The cellulosic material is combined with synthetic resin or other suitable bonding system by a process in which the interparticle bond is created by the bonding system under heat and pressure.
PREFABRICATED WOOD I-JOIST. Structural member manufactured using sawn or structural composite lumber flanges and wood structural panel webs bonded together with exterior exposure adhesives, which forms an "I" cross-sectional shape.
SHEAR WALL. A wall designed to resist lateral forces parallel to the plane of a wall.
Shear wall, perforated. A wood structural panel sheathed wall with openings, that has not been specifically designed and detailed for force transfer around openings.
Shear wall segment, perforated. A section of shear wall with full-height sheathing that meets the height-to-width ratio limits of Section 4.3.4 of AF&PA SDPWS.
STRUCTURAL COMPOSITE LUMBER. Structural member manufactured using wood elements bonded together with exterior adhesives. Examples of structural composite lumber are:
Laminated veneer lumber (LVL). A composite of wood veneer sheet elements with wood fibers primarily oriented along the length of the member.
Parallel strand lumber (PSL). A composite of wood strand elements with wood fibers primarily oriented along the length of the member.
STRUCTURAL GLUED-LAMINATED TIMBER. An engineered, stress-rated product of a timber laminating plant, comprised of assemblies of specially selected and prepared wood laminations in which the grain of all laminations is approximately parallel longitudinally and the laminations are bonded with adhesives.
SUBDIAPHRAGM. A portion of a larger wood diaphragm designed to anchor and transfer local forces to primary diaphragm struts and the main diaphragm.
TIE-DOWN (HOLD-DOWN). A device used to resist uplift of the chords of shear walls.
TREATED WOOD. Wood and wood-based materials that use vacuum-pressure impregnation processes to enhance fire retardant or preservative properties.
Fire-retardant-treated wood. Pressure-treated lumber and plywood that exhibit reduced surface-burning characteristics and resist propagation of fire.
Preservative-treated wood. Pressure-treated wood products that exhibit reduced susceptibility to damage by fungi, insects or marine borers.
WOOD SHEAR PANEL. A wood floor, roof or wall component sheathed to act as a shear wall or diaphragm.
WOOD STRUCTURAL PANEL. A panel manufactured from veneers, wood strands or wafers or a combination of veneer and wood strands or wafers bonded together with waterproof synthetic resins or other suitable bonding systems. Examples of wood structural panels are:
Composite panels. A wood structural panel that is comprised of wood veneer and reconstituted wood-based material and bonded together with waterproof adhesive;
Oriented strand board (OSB). A mat-formed wood structural panel comprised of thin rectangular wood strands arranged in cross-aligned layers with surface layers normally arranged in the long panel direction and bonded with waterproof adhesive; or
Plywood. A wood structural panel comprised of plies of wood veneer arranged in cross-aligned layers. The plies are bonded with waterproof adhesive that cures on application of heat and pressure.
Sawn lumber used for load-supporting purposes, including end-jointed or edge-glued lumber, machine stress-rated or machine-evaluated lumber, shall be identified by the grade mark of a lumber grading or inspection agency that has been approved by an accreditation body that complies with DOC PS 20 or equivalent. Grading practices and identification shall comply with rules published by an agency approved in accordance with the procedures of DOC PS 20 or equivalent procedures. In lieu of a grade mark on the material, a certificate of inspection as to species and grade issued by a lumber grading or inspection agency meeting the requirements of this section is permitted to be accepted for precut, remanufactured or rough-sawn lumber and for sizes larger than 3 inches (76 mm) nominal thickness.
Approved end-jointed lumber is permitted to be used interchangeably with solid-sawn members of the same species and grade.
Wood required by Section 2304.11 to be preservative treated shall bear the quality mark of an inspection agency that maintains continuing supervision, testing and inspection over the quality of the preservative-treated wood. Inspection agencies for preservative-treated wood shall be listed by an accreditation body that complies with the requirements of the American Lumber Standards Treated Wood Program, or equivalent. The quality mark shall be on a stamp or label affixed to the preservative-treated wood, and shall include the following information:
- Identification of treating manufacturer.
- Type of preservative used.
- Minimum preservative retention (pcf).
- End use for which the product is treated.
- AWPA standard to which the product was treated.
- Identity of the accredited inspection agency.
When native lumber is used, it shall be subject to the following requirements:
- Sizing Criteria: For lumber, sized in accordance with the DOC PS-20, figures for maximum fiber stress and modulus of elasticity for framing grade No. 2 shall be used in establishing span and spacing characteristics for all structural members.
- Stress Criteria: Lumber which is sized in excess of the dimensions established by the DOC PS-20 for the given nominal size referenced shall be allowed to have a maximum fiber stress increase above that provided in section 2303.1.12 item 1 in proportion to the increased bearing capacity of the cross section as provided in Table 2303.1.12.
- The identification mark of an approved agency in accordance with Section 1703.5.
- Identification of the treating manufacturer.
- The name of the fire-retardant treatment.
- The species of wood treated.
- Flame spread and smoke-developed index.
- Method of drying after treatment.
- Conformance with appropriate standards in accordance with Sections 2303.2.5 through 2303.2.8.
- For fire-retardant-treated wood exposed to weather, damp or wet locations, include the words "No increase in the listed classification when subjected to the Standard Rain Test" (ASTM D 2898).
- Slope or depth, span and spacing;
- Location of all joints and support locations;
- Number of plies if greater than one;
- Required bearing widths;
- Design loads as applicable, including:
- Other lateral loads, including drag strut loads;
- Adjustments to wood member and metal connector plate design value for conditions of use;
- Maximum reaction force and direction, including maximum uplift reaction forces where applicable;
- Metal-connector-plate type, size and thickness or gage, and the dimensioned location of each metal connector plate except where symmetrically located relative to the joint interface;
- Size, species and grade for each wood member;
- Truss-to-truss connections and truss field assembly requirements;
- Calculated span-to-deflection ratio and maximum vertical and horizontal deflection for live and total load as applicable;
- Maximum axial tension and compression forces in the truss members; and
- Required permanent individual truss member restraint location and the method and details of restraint/bracing to be used in accordance with Section 2303.4.1.2.
Where permanent restraint of truss members is required on the truss design drawings, it shall be accomplished by one of the following methods:
- Permanent individual truss member restraint/bracing shall be installed using standard industry lateral restraint/bracing details in accordance with generally accepted engineering practice. Locations for lateral restraint shall be identified on the truss design drawing.
- The trusses shall be designed so that the buckling of any individual truss member is resisted internally by the individual truss through suitable means (i.e., buckling reinforcement by T-reinforcement or L-reinforcement, proprietary reinforcement, etc.). The buckling reinforcement of individual members of the trusses shall be installed as shown on the truss design drawing or on supplemental truss member buckling reinforcement details provided by the truss designer.
- A project-specific permanent individual truss member restraint/bracing design shall be permitted to be specified by any registered design professional.
Where required by the registered design professional, the building official or the statutes of the jurisdiction in which the project is to be constructed, each individual truss design drawing shall bear the seal and signature of the truss designer.
- Where a cover sheet and truss index sheet are combined into a single sheet and attached to the set of truss design drawings, the single cover/truss index sheet is the only document required to be signed and sealed by the truss designer.
- When a cover sheet and a truss index sheet are separately provided and attached to the set of truss design drawings, the cover sheet and the truss index sheet are the only documents required to be signed and sealed by the truss designer.
SHEATHING TYPE | MINIMUM THICKNESS | MAXIMUM WALL STUD SPACING |
Wood boards | 5/8 inch | 24 inches on center |
Fiberboard | 1/2 inch | 16 inches on center |
Wood structural panel | In accordance with Tables 2308.9.3(2) and 2308.9.3(3) | — |
M-S "Exterior Glue" and M-2 "Exterior Glue" Particleboard | In accordance with Tables 2306.5 and 2308.9.3(4) | — |
Gypsum sheathing | 1/2 inch | 16 inches on center |
Gypsum wallboard | 1/2 inch | 24 inches on center |
Reinforced cement mortar | 1 inch | 24 inches on center |
MINIMUM NAIL | MINIMUM WOOD STRUCTURAL PANEL SPAN RATING | MINIMUM NOMINAL PANEL THICKNESS (inches) | MAXIMUM WALL STUD SPACING (inches) | PANEL NAIL SPACING | MAXIMUM WIND SPEED (MPH) | ||||
Size | Penetration (inches) | Edges (inches o.c.) |
Field (inches o.c.) |
Wind exposure category | |||||
B | C | D | |||||||
6d common (2.0" × 0.113") | 1.5 | 24/0 | 3/8 | 16 | 6 | 12 | 110 | 90 | 85 |
24/16 | 7/16 | 16 | 6 | 12 | 110 | 100 | 90 | ||
6 | 150 | 125 | 110 | ||||||
8d common (2.5" × 0.131") | 1.75 | 24/16 | 7/16 | 16 | 6 | 12 | 130 | 110 | 105 |
6 | 150 | 125 | 110 | ||||||
24 | 6 | 12 | 110 | 90 | 85 | ||||
6 | 110 | 90 | 85 |
- Panel strength axis shall be parallel or perpendicular to supports. Three-ply plywood sheathing with studs spaced more than 16 inches on center shall be applied with panel strength axis perpendicular to supports.
- The table is based on wind pressures acting toward and away from building surfaces in accordance with Section 6.4.2.2 of ASCE 7. Lateral requirements shall be in accordance with Section 2305 or 2308.
- Wood structural panels with span ratings of wall-16 or wall-24 shall be permitted as an alternative to panels with a 24/0 span rating. Plywood siding rated 16 o.c. or 24 o.c. shall be permitted as an alternative to panels with a 24/16 span rating. Wall-16 and plywood siding 16 o.c. shall be used with studs spaced a maximum of 16 inches o.c.
SPAN (inches) | MINIMUM NET THICKNESS (inches) OF LUMBER PLACED | |||
Perpendicular to supports | Diagonally to supports | |||
Surfaced dryc | Surfaced unseasoned | Surfaced dryc | Surfaced unseasoned | |
Floors | ||||
24 | 3/4 | 25/32 | 3/4 | 25/32 |
16 | 5/8 | 11/16 | 5/8 | 11/16 |
Roofs | ||||
24 | 5/8 | 11/16 | 3/4 | 25/32 |
SOLID FLOOR OR ROOF SHEATHING | SPACED ROOF SHEATHING | GRADING RULES |
Utility | Standard | NLGA, WCLIB, WWPA |
4 common or utility | 3 common or standard | NLGA, WCLIB, WWPA, NSLB or NELMA |
No. 3 | No. 2 | SPIB |
Merchantable | Construction common | RIS |
SHEATHING GRADES | ROOFc | FLOORd | ||||
Panel span rating roof/floor span | Panel thickness (inches) |
Maximum span (inches) | Loade (psf) | Maximum span (inches) | ||
With edge supportf | Without edge support | Total load | Live load | |||
16/0 | 3/8 | 16 | 16 | 40 | 30 | 0 |
20/0 | 3/8 | 20 | 20 | 40 | 30 | 0 |
24/0 | 3/8, 7/16, 1/2 | 24 | 20g | 40 | 30 | 0 |
24/16 | 7/16, 1/2 | 24 | 24 | 50 | 40 | 16 |
32/16 | 15/32, 1/2, 5/8 | 32 | 28 | 40 | 30 | 16h |
40/20 | 19/32, 5/8, 3/4, 7/8 | 40 | 32 | 40 | 30 | 20h,i |
48/24 | 23/32, 3/4, 7/8 | 48 | 36 | 45 | 35 | 24 |
54/32 | 7/8, 1 | 54 | 40 | 45 | 35 | 32 |
60/32 | 7/8, 11/8 | 60 | 48 | 45 | 35 | 32 |
SINGLE FLOOR GRADES | ROOFc | FLOORd | ||||
Panel span rating | Panel thickness (inches) | Maximum span (inches) | Loade (psf) | Maximum span (inches) | ||
With edge supportf | Without edge support | Total load | Live load | |||
16 o.c. | 1/2, 19/32, 5/8 | 24 | 24 | 50 | 40 | 16h |
20 o.c. | 19/32, 5/8, 3/4 | 32 | 32 | 40 | 30 | 20h,i |
24 o.c. | 23/32, 3/4 | 48 | 36 | 35 | 25 | 24 |
32 o.c. | 7/8, 1 | 48 | 40 | 50 | 40 | 32 |
48 o.c. | 13/32, 11/8 | 60 | 48 | 50 | 40 | 48 |
- Applies to panels 24 inches or wider.
- Floor and roof sheathing conforming with this table shall be deemed to meet the design criteria of Section 2304.7.
- Uniform load deflection limitations 1/180 of span under live load plus dead load, 1/240 under live load only.
- Panel edges shall have approved tongue-and-groove joints or shall be supported with blocking unless 1/4-inch minimum thickness underlayment or 11/2 inches of approved cellular or lightweight concrete is placed over the subfloor, or finish floor is 3/4-inch wood strip. Allowable uniform load based on deflection of 1/360 of span is 100 pounds per square foot except the span rating of 48 inches on center is based on a total load of 65 pounds per square foot.
- Allowable load at maximum span.
- Tongue-and-groove edges, panel edge clips (one midway between each support, except two equally spaced between supports 48 inches on center), lumber blocking or other. Only lumber blocking shall satisfy blocked diaphragm requirements.
- For 1/2-inch panel, maximum span shall be 24 inches.
- Span is permitted to be 24 inches on center where 3/4-inch wood strip flooring is installed at right angles to joist.
- Span is permitted to be 24 inches on center for floors where 11/2 inches of cellular or lightweight concrete is applied over the panels.
IDENTIFICATION | MAXIMUM SPACING OF JOISTS (inches) | ||||
16 | 20 | 24 | 32 | 48 | |
Species groupc | Thickness (inches) | ||||
1 | 1/2 | 5/8 | 3/4 | — | — |
2, 3 | 5/8 | 3/4 | 7/8 | — | — |
4 | 3/4 | 7/8 | 1 | — | — |
Single floor span ratingd | 16 o.c. | 20 o.c. | 24 o.c. | 32 o.c. | 48 o.c. |
- Spans limited to value shown because of possible effects of concentrated loads. Allowable uniform loads based on deflection of 1/360 of span is 100 pounds per square foot except allowable total uniform load for 11/8-inch wood structural panels over joists spaced 48 inches on center is 65 pounds per square foot. Panel edges shall have approved tongue-and-groove joints or shall be supported with blocking, unless 1/4-inch minimum thickness underlayment or 11/2 inches of approved cellular or lightweight concrete is placed over the subfloor, or finish floor is 3/4-inch wood strip.
- Floor panels conforming with this table shall be deemed to meet the design criteria of Section 2304.7.
- Applicable to all grades of sanded exterior-type plywood. See DOC PS 1 for plywood species groups.
- Applicable to Underlayment grade, C-C (Plugged) plywood, and Single Floor grade wood structural panels.
PANEL GRADE | THICKNESS (inch) | MAXIMUM SPAN (inches) | LOAD AT MAXIMUM SPAN (psf) | |
Live | Total | |||
Structural I sheathing | 7/16 | 24 | 20 | 30 |
15/32 | 24 | 35c | 45c | |
1/2 | 24 | 40c | 50c | |
19/32, 5/8 | 24 | 70 | 80 | |
23/32, 3/4 | 24 | 90 | 100 | |
Sheathing, other grades covered in DOC PS 1 or DOC PS 2 | 7/16 | 16 | 40 | 50 |
15/32 | 24 | 20 | 25 | |
1/2 | 24 | 25 | 30 | |
19/32 | 24 | 40c | 50c | |
5/8 | 24 | 45c | 55c | |
23/32, 3/4 | 24 | 60c | 65c |
- Roof sheathing conforming with this table shall be deemed to meet the design criteria of Section 2304.7.
- Uniform load deflection limitations 1/180 of span under live load plus dead load, 1/240 under live load only. Edges shall be blocked with lumber or other approved type of edge supports.
- For composite and four-ply plywood structural panel, load shall be reduced by 15 pounds per square foot.
Structural floor sheathing shall be designed in accordance with the general provisions of this code and the special provisions in this section.
Floor sheathing conforming to the provisions of Table 2304.7(1), 2304.7(2), 2304.7(3) or 2304.7(4) shall be deemed to meet the requirements of this section.
Structural roof sheathing shall be designed in accordance with the general provisions of this code and the special provisions in this section.
Roof sheathing conforming to the provisions of Table 2304.7(1), 2304.7(2), 2304.7(3) or 2304.7(5) shall be deemed to meet the requirements of this section. Wood structural panel roof sheathing shall be bonded by exterior glue.
The decking shall extend across a minimum of three spans. End joints of pieces within 6 inches (152 mm) of the end joints of the adjacent pieces in either direction shall be separated by at least two intervening courses. In the end bays, each piece shall bear on at least one support. Where an end joint occurs in an end bay, the next piece in the same course shall continue over the first inner support for at least 24 inches (610 mm). The details of the controlled random pattern shall be as specified for each decking material in Section 2304.8.3.3, 2304.8.4.3 or 2304.8.5.3.
Decking that cantilevers beyond a support for a horizontal distance greater than 18 inches (457 mm), 24 inches (610 mm) or 36 inches (914 mm) for 2-inch (51 mm), 3-inch (76 mm) and 4-inch (102 mm) nominal thickness decking, respectively, shall comply with the following:
- The maximum cantilevered length shall be 30 percent of the length of the first adjacent interior span.
- A structural fascia shall be fastened to each decking piece to maintain a continuous, straight line.
- There shall be no end joints in the decking between the cantilevered end of the decking and the centerline of the first adjacent interior span.
The length of nails connecting laminations shall not be less than two and one-half times the net thickness of each lamination. Where decking supports are 48 inches (1219 mm) on center (o.c.) or less, side nails shall be installed not more than 30 inches (762 mm) o.c. alternating between top and bottom edges, and staggered one-third of the spacing in adjacent laminations. Where supports are spaced more than 48 inches (1219 mm) o.c., side nails shall be installed not more than 18 inches (457 mm) o.c. alternating between top and bottom edges and staggered one-third of the spacing in adjacent laminations. Two side nails shall be installed at each end of butt-jointed pieces.
Laminations shall be toenailed to supports with 20d or larger common nails. Where the supports are 48 inches (1219 mm) o.c. or less, alternate laminations shall be toenailed to alternate supports; where supports are spaced more than 48 inches (1219 mm) o.c., alternate laminations shall be toenailed to every support.
Connections for wood members shall be designed in accordance with the appropriate methodology in Section 2301.2. The number and size of fasteners connecting wood members shall not be less than that set forth in Table 2304.9.1.
CONNECTION
|
FASTENINGa, m
|
LOCATION
|
1. Joist to sill or girder | 3 - 8d common (21/2" × 0.131") 3 - 3" × 0.131" nails 3 - 3" 14 gage staples |
toenail |
2. Bridging to joist | 2 - 8d common (21/2" × 0.131") 2 - 3" × 0.131" nails 2 - 3" 14 gage staples |
toenail each end |
3. 1" × 6" subfloor or less to each joist | 2 - 8d common (21/2" × 0.131") | face nail |
4. Wider than 1" × 6" subfloor to each joist | 3 - 8d common (21/2" × 0.131") | face nail |
5. 2" subfloor to joist or girder | 2 - 16d common (31/2" × 0.162") | blind and face nail |
6. Sole plate to joist or blocking | 16d (31/2" × 0.135") at 16" o.c. 3" × 0.131" nails at 8" o.c. 3" 14 gage staples at 12" o.c. |
typical face nail |
Sole plate to joist or blocking at braced wall panel |
3 - 16d (31/2" × 0.135") at 16" o.c. 4 - 3" × 0.131" nails at 16" o.c. 4 - 3" 14 gage staples at 16" o.c. |
braced wall panels |
7. Top plate to stud | 2 - 16d common (31/2" × 0.162") 3 - 3" × 0.131" nails 3 - 3" 14 gage staples |
end nail |
8. Stud to sole plate | 4 - 8d common (21/2" × 0.131") 4 - 3" × 0.131" nails 3 - 3" 14 gage staples |
toenail |
2 - 16d common (31/2" × 0.162") 3 - 3" × 0.131" nails 3 - 3" 14 gage staples |
end nail | |
9. Double studs | 16d (31/2" × 0.135") at 24" o.c. 3" × 0.131" nail at 8" o.c. 3" 14 gage staple at 8" o.c. |
face nail |
10. Double top plates | 16d (31/2" × 0.135") at 16" o.c. 3" × 0.131" nail at 12" o.c. 3" 14 gage staple at 12" o.c. |
typical face nail |
Double top plates | 8 - 16d common (31/2" × 0.162") 12 - 3" × 0.131" nails 12 - 3" 14 gage staples |
lap splice |
11. Blocking between joists or rafters to top plate | 3 - 8d common (21/2" × 0.131") 3 - 3" × 0.131" nails 3 - 3" 14 gage staples |
toenail |
12. Rim joist to top plate | 8d (21/2" × 0.131") at 6" o.c. 3" × 0.131" nail at 6" o.c. 3" 14 gage staple at 6" o.c. |
toenail |
13. Top plates, laps and intersections | 2 - 16d common (31/2" × 0.162") 3 - 3" × 0.131" nails 3 - 3" 14 gage staples |
face nail |
14. Continuous header, two pieces | 16d common (31/2" × 0.162") | 16" o.c. along edge |
15. Ceiling joists to plate | 3 - 8d common (21/2" × 0.131") 5 - 3" × 0.131" nails 5 - 3" 14 gage staples |
toenail |
16. Continuous header to stud | 4 - 8d common (21/2" × 0.131") | toenail |
17. Ceiling joists, laps over partitions (see Section 2308.10.4.1, Table 2308.10.4.1) |
3 - 16d common (31/2" × 0.162") minimum, TABLE 2308.10.4.1 4 - 3" × 0.131" nails 4 - 3" 14 gage staples |
face nail |
18. Ceiling joists to parallel rafters (see Section 2308.10.4.1, Table 2308.10.4.1) |
3 - 16d common (31/2" × 0.162") minimum, TABLE 2308.10.4.1 4 - 3" × 0.131" nails 4 - 3" 14 gage staples |
face nail |
19. Rafter to plate (see Section 2308.10.1, Table 2308.10.1) |
3 - 8d common (21/2" × 0.131") 3 - 3" × 0.131" nails 3 - 3" 14 gage staples |
toenail |
20. 1" diagonal brace to each stud and plate | 2 - 8d common (21/2" × 0.131") 2 - 3" × 0.131" nails 3 - 3" 14 gage staples |
face nail |
21. 1" × 8" sheathing to each bearing | 3 - 8d common (21/2" × 0.131") | face nail |
22. Wider than 1" × 8" sheathing to each bearing | 3 - 8d common (21/2" × 0.131") | face nail |
23. Built-up corner studs | 16d common (31/2" × 0.162") 3" × 0.131" nails 3" 14 gage staples |
24" o.c. 16" o.c. 16" o.c. |
24. Built-up girder and beams | 20d common (4" × 0.192") 32" o.c. 3" × 0.131" nail at 24" o.c. 3" 14 gage staple at 24" o.c. |
face nail at top and bottom staggered on opposite sides |
2 - 20d common (4" × 0.192") 3 - 3" × 0.131" nails 3 - 3" 14 gage staples |
face nail at ends and at each splice | |
25. 2" planks | 16d common (31/2" × 0.162") | at each bearing |
26. Collar tie to rafter | 3 - 10d common (3" × 0.148") 4 - 3" × 0.131" nails 4 - 3" 14 gage staples |
face nail |
27. Jack rafter to hip | 3 - 10d common (3" × 0.148") 4 - 3" × 0.131" nails 4 - 3" 14 gage staples |
toenail |
2 - 16d common (31/2" × 0.162") 3 - 3" × 0.131" nails 3 - 3" 14 gage staples |
face nail | |
28. Roof rafter to 2-by ridge beam | 2 - 16d common (31/2" × 0.162") 3 - 3" × 0.131" nails 3 - 3" 14 gage staples |
toenail |
2 -16d common (31/2" × 0.162") 3 - 3" × 0.131" nails 3 - 3" 14 gage staples |
face nail | |
29. Joist to band joist | 3 - 16d common (31/2" × 0.162") 4 - 3" × 0.131" nails 4 - 3" 14 gage staples |
face nail |
CONNECTION | FASTENINGa, m | LOCATION | |
30. Ledger strip | 3 - 16d common (31/2" × 0.162") 4 - 3" × 0.131" nails 4 - 3" 14 gage staples |
face nail at each joist | |
31. Wood structural panels and particleboardb Subfloor, roof and wall sheathing (to framing) |
1/2" and less | 6dc, l | |
2 3/8" × 0.113" nailn | |||
13/4" 16 gageo | |||
19/32" to 3/4" | 8dd or 6de | ||
23/8" × 0.113" nailp | |||
2" 16 gage staplep | |||
7/8" to 1" | 8dc | ||
11/8" to 11/4" | 10dd or 8de | ||
Single floor (combination subfloor-underlayment to framing) |
3/4" and less | 6de | |
7/8" to 1" | 8de | ||
11/8" to 11/4" | 10dd or 8de | ||
32. Panel siding (to framing) | 1/2" or less 5/8" |
6df 8df |
|
33. Fiberboard sheathingg | 1/2" | No. 11 gage roofing nailh | |
6d common nail (2" × 0.113") | |||
No. 16 gage staplei | |||
25/32" | No. 11 gage roofing nailh | ||
8d common nail (21/2" × 0.131") | |||
No. 16 gage staplei | |||
34. Interior paneling | 1/4" 3/8" | 4dj 6dk |
- Common or box nails are permitted to be used except where otherwise stated.
- Nails spaced at 6 inches on center at edges, 12 inches at intermediate supports except 6 inches at supports where spans are 48 inches or more. For nailing of wood structural panel and particleboard diaphragms and shear walls, refer to Section 2305. Nails for wall sheathing are permitted to be common, box or casing.
- Common or deformed shank (6d - 2" × 0.113"; 8d - 21/2" × 0.131"; 10d - 3" × 0.148").
- Common (6d - 2" × 0.113"; 8d - 21/2" × 0.131"; 10d - 3" × 0.148").
- Deformed shank (6d - 2" × 0.113"; 8d - 21/2" × 0.131"; 10d - 3" × 0.148").
- Corrosion-resistant siding (6d - 17/8" × 0.106"; 8d - 23/8" × 0.128") or casing (6d - 2" × 0.099"; 8d - 21/2" × 0.113") nail.
- Fasteners spaced 3 inches on center at exterior edges and 6 inches on center at intermediate supports, when used as structural sheathing. Spacing shall be 6 inches on center on the edges and 12 inches on center at intermediate supports for nonstructural applications.
- Corrosion-resistant roofing nails with 7/16-inch-diameter head and 11/2-inch length for 1/2-inch sheathing and 13/4-inch length for 25/32-inch sheathing.
- Corrosion-resistant staples with nominal 7/16-inch crown or 1-inch crown and 11/4-inch length for 1/2-inch sheathing and 11/2-inch length for 25/32-inch sheathing. Panel supports at 16 inches (20 inches if strength axis in the long direction of the panel, unless otherwise marked).
- Casing (11/2" × 0.080") or finish (11/2" × 0.072") nails spaced 6 inches on panel edges, 12 inches at intermediate supports.
- Panel supports at 24 inches. Casing or finish nails spaced 6 inches on panel edges, 12 inches at intermediate supports.
- For roof sheathing applications, 8d nails (21/2" × 0.113") are the minimum required for wood structural panels.
- Staples shall have a minimum crown width of 7/16 inch.
- For roof sheathing applications, fasteners spaced 4 inches on center at edges, 8 inches at intermediate supports.
- Fasteners spaced 4 inches on center at edges, 8 inches at intermediate supports for subfloor and wall sheathing and 3 inches on center at edges, 6 inches at intermediate supports for roof sheathing.
- Fasteners spaced 4 inches on center at edges, 8 inches at intermediate supports.
Fasteners in contact with preservative-treated wood shall be of hot-dipped zinc-coated galvanized steel, stainless steel, silicon bronze or copper. Fasteners other than nails, timber rivets, wood screws and lag screws shall be permitted to be of mechanically deposited zinc-coated steel with coating weights in accordance with ASTM B 695, Class 55 minimum. Connectors that are used in exterior applications and in contact with preservative-treated wood shall have coating types and weights in accordance with the treated wood or connector manufacturer's recommendations. In the absence of manufacturer's recommendations, a minimum of ASTM A 653, type G185 zinc-coated galvanized steel, or equivalent, shall be used.
- Posts or columns that are either exposed to the weather or located in basements or cellars, supported by concrete piers or metal pedestals projected at least 1 inch (25 mm) above the slab or deck and 6 inches (152 mm) above exposed earth, and are separated therefrom by an impervious moisture barrier.
- Posts or columns in enclosed crawl spaces or unexcavated areas located within the periphery of the building, supported by a concrete pier or metal pedestal at a height greater than 8 inches (203 mm) from exposed ground, and are separated therefrom by an impervious moisture barrier.
Wood used in contact with the ground (exposed earth) in the locations specified in Sections 2304.11.4.1 and 2304.11.4.2 shall be naturally durable (species for both decay and termite resistance) or preservative treated using water-borne preservatives in accordance with AWPA U1 (Commodity Specifications A or F) for soil or fresh water use.
Naturally durable or preservative-treated wood shall be utilized for those portions of wood members that form the structural supports of buildings, balconies, porches or similar permanent building appurtenances where such members are exposed to the weather without adequate protection from a roof, eave, overhang or other covering to prevent moisture or water accumulation on the surface or at joints between members.
Wood members supporting concrete, masonry or similar materials shall be checked for the effects of long-term loading using the provisions of the AF&PA NDS. The total deflection, including the effects of long-term loading, shall be limited in accordance with Section 1604.3.1 for these supported materials.
The deflection (Δ) of a blocked wood structural panel diaphragm uniformly fastened throughout with staples is permitted to be calculated by using the following equation. If not uniformly fastened, the constant 0.188 (For SI: 1/1627) in the third term shall be modified accordingly.
(Equation 23-1)
where:
A = Area of chord cross section, in square inches (mm2).
b = Diaphragm width, in feet (mm).
E = Elastic modulus of chords, in pounds per square inch (N/mm2).
en = Staple deformation, in inches (mm) [see Table 2305.2(1)].
Gt = Panel rigidity through the thickness, in pounds per inch (N/mm) of panel width or depth [see Table 2305.2(2)].
L = Diaphragm length, in feet (mm).
v = Maximum shear due to design loads in the direction under consideration, in pounds per linear foot (plf) (N/mm).
Δ = The calculated deflection, in inches (mm).
∑ (ΔcX) = Sum of individual chord-splice slip values on both sides of the diaphragm, each multiplied by its distance to the nearest support.
LOAD PER FASTENERb (pounds) | FASTENER DESIGNATIONS |
14-Ga staple x 2 inches long | |
60 | 0.011 |
80 | 0.018 |
100 | 0.028 |
120 | 0.04 |
140 | 0.053 |
160 | 0.068 |
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound = 4.448 N.
- Increase en values 20 percent for plywood grades other than Structural I.
- Load per fastener = maximum shear per foot divided by the number of fasteners per foot at interior panel edges.
- Decrease en values 50 percent for seasoned lumber (moisture content < 19 percent).
PANEL TYPE | SPAN RATING | VALUES OF Gt (lb/in. panel depth or width) | |||||||
OTHER | STRUCTURAL I | ||||||||
3-ply Plywood | 4-ply Plywood | 5-ply Plywooda | OSB | 3-ply Plywood |
4-ply Plywood |
5-ply Plywooda | OSB | ||
Sheathing | 24/0 | 25,000 | 32,500 | 37,500 | 77,500 | 32,500 | 42,500 | 41,500 | 77,500 |
24/16 | 27,000 | 35,000 | 40,500 | 83,500 | 35,000 | 45,500 | 44,500 | 83,500 | |
32/16 | 27,000 | 35,000 | 40,500 | 83,500 | 35,000 | 45,500 | 44,500 | 83,500 | |
40/20 | 28,500 | 37,000 | 43,000 | 88,500 | 37,000 | 48,000 | 47,500 | 88,500 | |
48/24 | 31,000 | 40,500 | 46,500 | 96,000 | 40,500 | 52,500 | 51,000 | 96,000 | |
Single Floor | 16 o.c. | 27,000 | 35,000 | 40,500 | 83,500 | 35,000 | 45,500 | 44,500 | 83,500 |
20 o.c. | 28,000 | 36,500 | 42,000 | 87,000 | 36,500 | 47,500 | 46,000 | 87,000 | |
24 o.c. | 30,000 | 39,000 | 45,000 | 93,000 | 39,000 | 50,500 | 49,500 | 93,000 | |
32 o.c. | 36,000 | 47,000 | 54,000 | 110,000 | 47,000 | 61,000 | 59,500 | 110,000 | |
48 o.c. | 50,500 | 65,500 | 76,000 | 155,000 | 65,500 | 85,000 | 83,500 | 155,000 |
OTHER | STRUCTURAL I | |||||||
Thickness (in.) | A-A, A-C | Marine | All Other Grades | A-A, A-C | Marine | All Other Grades | ||
Sanded Plywood | 1/4 | 24,000 | 31,000 | 24,000 | 31,000 | 31,000 | 31,000 | |
11/32 | 25,500 | 33,000 | 25,500 | 33,000 | 33,000 | 33,000 | ||
3/8 | 26,000 | 34,000 | 26,000 | 34,000 | 34,000 | 34,000 | ||
15/32 | 38,000 | 49,500 | 38,000 | 49,500 | 49,500 | 49,500 | ||
1/2 | 38,500 | 50,000 | 38,500 | 50,000 | 50,000 | 50,000 | ||
19/32 | 49,000 | 63,500 | 49,000 | 63,500 | 63,500 | 63,500 | ||
5/8 | 49,500 | 64,500 | 49,500 | 64,500 | 64,500 | 64,500 | ||
23/32 | 50,500 | 65,500 | 50,500 | 65,500 | 65,500 | 65,500 | ||
3/4 | 51,000 | 66,500 | 51,000 | 66,500 | 66,500 | 66,500 | ||
7/8 | 52,500 | 68,500 | 52,500 | 68,500 | 68,500 | 68,500 | ||
1 | 73,500 | 95,500 | 73,500 | 95,500 | 95,500 | 95,500 | ||
11/8 | 75,000 | 97,500 | 75,000 | 97,500 | 97,500 | 97,500 |
The deflection (Δ) of a blocked wood structural panel shear wall uniformly fastened throughout with staples is permitted to be calculated by the use of the following equation:
(Equation 23-2)
where:
A = Area of boundary element cross section in square inches (mm2) (vertical member at shear wall boundary).
b = Wall width, in feet (mm).
da = Vertical elongation of overturning anchorage (including fastener slip, device elongation, anchor rod elongation, etc.) at the design shear load (v).
E = Elastic modulus of boundary element (vertical member at shear wall boundary), in pounds per square inch (N/mm2).
en = Staple deformation, in inches (mm) [see Table 2305.2(1)].
Gt = Panel rigidity through the thickness, in pounds per inch (N/mm) of panel width or depth [see Table 2305.2(2)].
h = Wall height, in feet (mm).
v = Maximum shear due to design loads at the top of the wall, in pounds per linear foot (N/mm).
Δ = The calculated deflection, in inches (mm).
The structural analysis and construction of wood elements in structures using allowable stress design shall be in accordance with the following applicable standards:
American Forest & Paper Association.
- NDS National Design Specification for Wood Construction
- SDPWS Special Design Provisions for Wind and Seismic
American Institute of Timber Construction.
- AITC 104 Typical Construction Details
- AITC 110 Standard Appearance Grades for Structural Glued Laminated Timber
- AITC 113 Standard for Dimensions of Structural Glued Laminated Timber
- AITC 117 Standard Specifications for Structural Glued Laminated Timber of Softwood Species
- AITC 119 Standard Specifications for Structural Glued Laminated Timber of Hardwood Species
- ANSI/AITC A190.1 Structural Glued Laminated Timber
- AITC 200 Inspection Manual
American Society of Agricultural and Biological Engineers.
- ASABE EP 484.2 Diaphragm Design of Metal-clad, Post- Frame Rectangular Buildings
- ASABE EP 486.1 Shallow Post Foundation Design
- ASABE 559 Design Requirements and Bending Properties for Mechanically Laminated Columns
APA—The Engineered Wood Association.
- Panel Design Specification
- Plywood Design Specification Supplement 1 -
Design & Fabrication of Plywood Curved Panel - Plywood Design Specification Supplement 2 -
Design & Fabrication of Glued Plywood-lumber Beams - Plywood Design Specification Supplement 3 -
Design & Fabrication of Plywood Stressed-skin Panels - Plywood Design Specification Supplement 4 -
Design & Fabrication of Plywood Sandwich Panels - Plywood Design Specification Supplement 5 -
Design & Fabrication of All-plywood Beams - EWS T300 Glulam Connection Details
- EWS S560 Field Notching and Drilling of Glued Laminated Timber Beams
- EWS S475 Glued Laminated Beam Design Tables
- EWS X450 Glulam in Residential Construction
- EWS X440 Product and Application Guide: Glulam
- EWS R540 Builders Tips: Proper Storage and Handling of Glulam Beams
Truss Plate Institute, Inc.
- TPI 1 National Design Standard for Metal Plate Connected Wood Truss Construction
The allowable unit stresses for preservative-treated wood need no adjustment for treatment, but are subject to other adjustments.
The allowable unit stresses for fire-retardant-treated wood, including fastener values, shall be developed from an approved method of investigation that considers the effects of anticipated temperature and humidity to which the fire-retardant-treated wood will be subjected, the type of treatment and the redrying process. Other adjustments are applicable except that the impact load duration shall not apply.
The capacity of lumber decking arranged according to the patterns described in Section 2304.8.2 shall be the lesser of the capacities determined for flexure and deflection according to the formulas in Table 2306.1.4.
PATTERN | ALLOWABLE AREA LOADa,b | |
Flexure | Deflection | |
Simple span |
|
|
Two-span continuous |
|
|
Combination simple- and two-span continuous |
|
|
Cantilevered pieces intermixed |
|
|
Controlled random layup | ||
Mechanically laminated decking |
|
|
2-inch decking |
|
|
3-inch and 4-inch decking |
|
|
- σb = Allowable total uniform load limited by bending.
σΔ = Allowable total uniform load limited by deflection. - d = Actual decking thickness.
l = Span of decking.
Fb' = Allowable bending stress adjusted by applicable factors.
E' = Modulus of elasticity adjusted by applicable factors.
PANEL GRADE |
COMMON NAIL SIZE OR STAPLEf LENGTH AND GAGE | MINIMUM FASTENER PENETRATION IN FRAMING (inches) |
MINIMUM NOMINAL PANEL THICKNESS (inch) | MINIMUM NOMINAL WIDTH OF FRAMING MEMBERS AT ADJOINING PANEL EDGES AND BOUNDARIESg (inches) |
BLOCKED DIAPHRAGMS | UNBLOCKED DIAPHRAGMS | ||||
Fastener spacing (inches) at diaphragm boundaries (all cases) at continuous panel edges parallel to load (Cases 3, 4), and at all panel edges (Cases 5, 6)b |
Fasteners spaced 6" max. at supported edgesb | |||||||||
6 | 4 | 21/2c | 2c | Case 1 (No unblocked edges or continuous joints parallel to load) |
All other configurations (Cases 2, 3, 4, 5 and 6) |
|||||
Fastener spacing (inches) at other panel edges (Cases 1, 2, 3 and 4)b |
||||||||||
6 | 6 | 4 | 3 | |||||||
Structural I grades | 8d (21/2" × 0.131") | 13/8 | 3/8 | 2 | 270 | 360 | 530 | 600 | 240 | 180 |
3 | 300 | 400 | 600 | 675 | 265 | 200 | ||||
11/2 16 Gage | 1 | 2 | 175 | 235 | 350 | 400 | 155 | 115 | ||
3 | 200 | 265 | 395 | 450 | 175 | 130 | ||||
10dd (3" × 0.148") | 11/2 | 15/32 | 2 | 320 | 425 | 640 | 730 | 285 | 215 | |
3 | 360 | 480 | 720 | 820 | 320 | 240 | ||||
11/2 16 Gage | 1 | 2 | 175 | 235 | 350 | 400 | 155 | 120 | ||
3 | 200 | 265 | 395 | 450 | 175 | 130 | ||||
Sheathing, single floor and other grades covered in DOC PS 1 and PS 2 | 6de (2" × 0.113") | 11/4 | 3/8 | 2 | 185 | 250 | 375 | 420 | 165 | 125 |
8d (21/2"× 0.131") | 13/8 | 3 | 210 | 280 | 420 | 475 | 185 | 140 | ||
2 | 240 | 320 | 480 | 545 | 215 | 160 | ||||
3 | 270 | 360 | 540 | 610 | 240 | 180 | ||||
11/2 16 Gage | 1 | 2 | 160 | 210 | 315 | 360 | 140 | 105 | ||
3 | 180 | 235 | 355 | 400 | 160 | 120 | ||||
8d (21/2"× 0.131") | 13/8 | 7/16 | 2 | 255 | 340 | 505 | 575 | 230 | 170 | |
3 | 285 | 380 | 570 | 645 | 255 | 190 | ||||
11/2 16 Gage | 1 | 2 | 165 | 225 | 335 | 380 | 150 | 110 | ||
3 | 190 | 250 | 375 | 425 | 165 | 125 | ||||
8d (21/2" × 0.131") | 13/8 | 15/32 | 2 | 270 | 360 | 530 | 600 | 240 | 180 | |
3 | 300 | 400 | 600 | 675 | 265 | 200 | ||||
10dd (3" × 0.148") | 11/2 | 2 | 290 | 385 | 575 | 655 | 255 | 190 | ||
3 | 325 | 430 | 650 | 735 | 290 | 215 | ||||
11/2 16 Gage | 1 | 2 | 160 | 210 | 315 | 360 | 140 | 105 | ||
3 | 180 | 235 | 355 | 405 | 160 | 120 | ||||
10dd (3" × 0.148") | 11/2 | 19/32 | 2 | 320 | 425 | 640 | 730 | 285 | 215 | |
3 | 360 | 480 | 720 | 820 | 320 | 240 | ||||
13/4 16 Gage | 1 | 2 | 175 | 235 | 350 | 400 | 155 | 115 | ||
3 | 200 | 265 | 395 | 450 | 175 | 130 |
- For framing of other species: (1) Find specific gravity for species of lumber in AF&PA NDS. (2) For staples find shear value from table above for Structural I panels (regardless of actual grade) and multiply value by 0.82 for species with specific gravity of 0.42 or greater, or 0.65 for all other species. (3) For nails find shear value from table above for nail size for actual grade and multiply value by the following adjustment factor: Specific Gravity Adjustment Factor = [1-(0.5 - SG)], where SG = Specific Gravity of the framing lumber. This adjustment factor shall not be greater than 1.
- Space fasteners maximum 12 inches o.c. along intermediate framing members (6 inches o.c. where supports are spaced 48 inches o.c.).
- Framing at adjoining panel edges shall be 3 inches nominal or wider, and nails at all panel edges shall be staggered where panel edge nailing is specified at 21/2 inches o.c. or less.
- Framing at adjoining panel edges shall be 3 inches nominal or wider, and nails at all panel edges shall be staggered where both of the following conditions are met: (1) 10d nails having penetration into framing of more than 11/2 inches and (2) panel edge nailing is specified at 3 inches o.c. or less.
- 8d is recommended minimum for roofs due to negative pressures of high winds.
- Staples shall have a minimum crown width of 7/16 inch and shall be installed with their crowns parallel to the long dimension of the framing members.
- The minimum nominal width of framing members not located at boundaries or adjoining panel edges shall be 2 inches.
- For shear loads of normal or permanent load duration as defined by the AF&PA NDS, the values in the table above shall be multiplied by 0.63 or 0.56, respectively.
PANEL GRADEc |
COMMON NAIL SIZE OR STAPLEf GAGE | MINIMUM FASTENER PENETRATION IN FRAMING (inches) |
MINIMUM NOMINAL PANEL THICKNESS (inch) |
MINIMUM NOMINAL WIDTH OF FRAMING MEMBER AT ADJOINING PANEL EDGES AND BOUNDARIESe | LINES OF FASTENERS | BLOCKED DIAPHRAGMS | |||||
Cases 1 and 2d | |||||||||||
Fastener Spacing Per Line at Boundaries (inches) |
|||||||||||
4 | 21/2 | 2 | |||||||||
Fastener Spacing Per Line at Other Panel Edges (inches) | |||||||||||
6 | 4 | 4 | 3 | 3 | 2 | ||||||
Structural I grades | 10d common nails |
11/2 | 15/32 | 3 4 4 |
2 2 3 |
605 700 875 |
815 915 1,220 |
875 1,005 1,285 |
1,150 1,290 1,395 |
— — — | — — — |
19/32 | 3 4 4 |
2 2 3 |
670 780 965 |
880 990 1,320 |
965 1,110 1,405 |
1,255 1,440 1,790 |
— — — | — — — | |||
23/32 | 3 4 4 |
2 2 3 |
730 855 1,050 |
955 1,070 1,430 |
1,050 1,210 1,525 |
1,365 1,565 1,800 |
— — — | — — — | |||
14 gage staples | 2 | 15/32 | 3 4 |
2 3 |
600 860 |
600 900 |
860 1,160 |
960 1,295 |
1,060 1,295 |
1,200 1,400 |
|
19/32 | 3 4 |
2 3 |
600 875 |
600 900 |
875 1,175 |
960 1,440 |
1,075 1,475 |
1,200 1,795 |
|||
Sheathing single floor and other grades covered in DOC PS 1 and PS 2 | 10d common nails |
11/2 | 15/32 | 3 4 4 |
2 2 3 |
525 605 765 |
725 815 1,085 |
765 875 1,130 |
1,010 1,105 1,195 |
— — — | — — — |
19/32 | 3 4 4 |
2 2 3 |
650 755 935 |
860 965 1,290 |
935 1,080 1,365 |
1,225 1,370 1,485 |
— — — | — — — | |||
23/32 | 3 4 4 |
2 2 3 |
710 825 1,020 |
935 1,050 1,400 |
1,020 1,175 1,480 |
1,335 1,445 1,565 |
— — — | — — — | |||
14 gage staples |
2 | 15/32 | 3 4 |
2 3 |
540 735 |
540 810 |
735 1,005 |
865 1,105 |
915 1,105 |
1,080 1,195 |
|
19/32 | 3 4 |
2 3 |
600 865 |
600 900 |
865 1,130 |
960 1,430 |
1,065 1,370 |
1,200 1,485 |
|||
23/32 | 4 | 3 | 865 | 900 | 1,130 | 1,490 | 1,430 | 1,545 |
- For framing of other species: (1) Find specific gravity for species of framing lumber in AF&PA NDS. (2) For staples, find shear value from table above for Structural I panels (regardless of actual grade) and multiply value by 0.82 for species with specific gravity of 0.42 or greater, or 0.65 for all other species. (3) For nails, find shear value from table above for nail size of actual grade and multiply value by the following adjustment factor: Specific Gravity Adjustment Factor = [ 1- (0.5 - SG)], where SG = Specific gravity of the framing lumber. This adjustment factor shall not be greater than 1.
- Fastening along intermediate framing members: Space fasteners a maximum of 12 inches on center, except 6 inches on center for spans greater than 32 inches.
- Panels conforming to PS 1 or PS 2.
- This table gives shear values for Cases 1 and 2 as shown in Table 2306.2.1(1). The values shown are applicable to Cases 3, 4, 5 and 6 as shown in Table 2306.2.1(1), providing fasteners at all continuous panel edges are spaced in accordance with the boundary fastener spacing.
- The minimum nominal depth of framing members shall be 3 inches nominal. The minimum nominal width of framing members not located at boundaries or adjoining panel edges shall be 2 inches.
- Staples shall have a minimum crown width of 7/16 inch, and shall be installed with their crowns parallel to the long dimension of the framing members.
- High load diaphragms shall be subject to special inspection in accordance with Section 1704.6.1.
- For shear loads of normal or permanent load duration as defined by the AF&PA NDS, the values in the table above shall be multiplied by 0.63 or 0.56, respectively.
PANEL GRADE | MINIMUM NOMINAL PANEL THICKNESS (inch) | MINIMUM FASTENER PENETRATION IN FRAMING (inches) | PANELS APPLIED DIRECT TO FRAMING | PANELS APPLIED OVER 1/2" OR 5/8" GYPSUM SHEATHING | ||||||||
NAIL (common or galvanized box) or staple sizek | Fastener spacing at panel edges (inches) | NAIL (common or galvanized box) or staple sizek | Fastener spacing at panel edges (inches) | |||||||||
6 | 4 | 3 | 2e | 6 | 4 | 3 | 2e | |||||
Structural I sheathing | 3/8 | 13/8 | 8d (21/2" × 0.131" common, 21/2" × 0.113" galvanized box) |
230d | 360d | 460d | 610d | 10d (3" × 0.148" common, 3" × 0.128" galvanized box) |
280 | 430 | 550f | 730 |
1 | 11/2 16 Gage | 155 | 235 | 315 | 400 | 2 16 Gage | 155 | 235 | 310 | 400 | ||
7/16 | 13/8 | 8d (21/2" × 0.131" common, 21/2" × 0.113" galvanized box) |
255d | 395d | 505d | 670d | 10d (3" × 0.148" common, 3" × 0.128" galvanized box) |
280 | 430 | 550f | 730 | |
1 | 11/2 16 Gage | 170 | 260 | 345 | 440 | 2 16 Gage | 155 | 235 | 310 | 400 | ||
15/32 | 13/8 | 8d (21/2" × 0.131" common, 21/2" × 0.113" galvanized box) |
280 | 430 | 550 | 730 | 10d (3" × 0.148" common, 3" × 0.128" galvanized box) |
280 | 430 | 550f | 730 | |
1 | 11/2 16 Gage | 185 | 280 | 375 | 475 | 2 16 Gage | 155 | 235 | 300 | 400 | ||
11/2 | 10d (3" × 0.148" common, 3" × 0.128" galvanized box) |
340 | 510 | 665f | 870 | — | — | — | — | — | ||
Sheathing, plywood siding e, g except Group 5 Species | 5/16c or 1/4c | 11/4 | 6d (2" × 0.113" common, 2" × 0.099" galvanized box) |
180 | 270 | 350 | 450 | 8d (21/2" × 0.131" common, 21/2" × 0.113" galvanized box) |
180 | 270 | 350 | 450 |
1 | 11/2 16 Gage | 145 | 220 | 295 | 375 | 2 16 Gage | 110 | 165 | 220 | 285 | ||
3/8 | 11/4 | 6d (2" × 0.113" common, 2" × 0.099" galvanized box) | 200 | 300 | 390 | 510 | 8d (2 1/2" × 0.131" common, 2 1/2" × 0.113" galvanized box) |
200 | 300 | 390 | 510 | |
13/8 | 8d (2 1/2" × 0.131" common, 2 1/2" × 0.113" galvanized box) |
220d | 320d | 410d | 530d | 10d (3" × 0.148" common, 3" × 0.128" galvanized box) |
260 | 380 | 490f | 640 | ||
1 | 1 1/2 16 Gage | 140 | 210 | 280 | 360 | 2 16 Gage | 140 | 210 | 280 | 360 | ||
7/16 | 13/8 | 8d (2 1/2" × 0.131" common, 2 1/2" × 0.113" galvanized box) |
240d | 350d | 450d | 585d | 10d (3" × 0.148" common, 3" × 0.128" galvanized box) |
260 | 380 | 490f | 640 | |
1 | 1 1/2 16 Gage | 155 | 230 | 310 | 395 | 2 16 Gage | 140 | 210 | 280 | 360 | ||
15/32 | 13/8 | 8d (2 1/2" × 0.131" common, 2 1/2" × 0.113" galvanized box) |
260 | 380 | 490 | 640 | 10d (3" × 0.148" common, 3" × 0.128" galvanized box) |
260 | 380 | 490f | 640 | |
11/2 | 10d (3" × 0.148" common, 3" × 0.128" galvanized box) |
310 | 460 | 600f | 770 | - | - | - | - | - | ||
1 | 1 1/2 16 Gage | 170 | 255 | 335 | 430 | 2 16 Gage | 140 | 210 | 280 | 360 | ||
19/32 | 11/2 | 10d (3" × 0.148" common, 3" × 0.128" galvanized box) |
340 | 510 | 665f | 870 | - | - | - | - | - | |
1 | 1 3/4 16 Gage | 185 | 280 | 375 | 475 | - | - | - | - | - | ||
Nail Size (galvanized casing) | Nail Size (galvanized casing) | |||||||||||
5/16c | 11/4 | 6d (2" × 0.099") | 140 | 210 | 275 | 360 | 8d (2 1/2" × 0.113") | 140 | 210 | 275 | 360 | |
3/8c | 13/8 | 8d (2 1/2" × 0.113") | 160 | 240 | 310 | 410 | 10d (3" × 0.128") | 160 | 240 | 310f | 410 |
- For framing of other species: (1) Find specific gravity for species of lumber in AF&PA NDS. (2) For staples find shear value from table above for Structural I panels (regardless of actual grade) and multiply value by 0.82 for species with specific gravity of 0.42 or greater, or 0.65 for all other species. (3) For nails find shear value from table above for nail size for actual grade and multiply value by the following adjustment factor: Specific Gravity Adjustment Factor = [1-(0.5 - SG)], where SG = Specific Gravity of the framing lumber. This adjustment factor shall not be greater than 1.
- Panel edges backed with 2-inch nominal or wider framing. Install panels either horizontally or vertically. Space fasteners maximum 6 inches on center along intermediate framing members for 3/8-inch and 7/16-inch panels installed on studs spaced 24 inches on center. For other conditions and panel thickness, space fasteners maximum 12 inches on center on intermediate supports.
- 3/8-inch panel thickness or siding with a span rating of 16 inches on center is the minimum recommended where applied directly to framing as exterior siding. For grooved panel siding, the nominal panel thickness is the thickness of the panel measured at the point of nailing.
- Allowable shear values are permitted to be increased to values shown for 15/32-inch sheathing with same nailing provided (a) studs are spaced a maximum of 16 inches on center, or (b) panels are applied with long dimension across studs.
- Framing at adjoining panel edges shall be 3 inches nominal or wider, and nails at all panel edges shall be staggered where panel edge nailing is specified at 2 inches on center or less.
- Framing at adjoining panel edges shall be 3 inches nominal or wider, and nails at all panel edges shall be staggered where both of the following conditions are met: (1) 10d (3" × 0.148") nails having penetration into framing of more than 11/2 inches and (2) panel edge nailing is specified at 3 inches on center or less.
- Values apply to all-veneer plywood. Thickness at point of fastening on panel edges governs shear values.
- Where panels are applied on both faces of a wall and nail spacing is less than 6 inches o.c. on either side, panel joints shall be offset to fall on different framing members. Or framing shall be 3-inch nominal or thicker at adjoining panel edges and nails at all panel edges shall be staggered.
- In Seismic Design Category D, E or F, where shear design values exceed 350 pounds per linear foot, all framing members receiving edge nailing from abutting panels shall not be less than a single 3-inch nominal member, or two 2-inch nominal members fastened together in accordance with Section 2306.1 to transfer the design shear value between framing members. Wood structural panel joint and sill plate nailing shall be staggered at all panel edges. See Sections 4.3.6.1 and 4.3.6.4.3 of AF&PA SDPWS for sill plate size and anchorage requirements.
- Galvanized nails shall be hot dipped or tumbled.
- Staples shall have a minimum crown width of 7/16 inch and shall be installed with their crowns parallel to the long dimension of the framing members.
- For shear loads of normal or permanent load duration as defined by the AF&PA NDS, the values in the table above shall be multiplied by 0.63 or 0.56, respectively.
PANEL GRADE | MINIMUM NOMINAL PANEL THICKNESS (inch) | MINIMUM NAIL PENETRATION IN FRAMING (inches) |
PANELS APPLIED DIRECT TO FRAMING | ||||
Nail size (common or galvanized box) | Allowable shear (pounds per foot) nail spacing at panel edges (inches)a | ||||||
6 | 4 | 3 | 2 | ||||
M-S "Exterior Glue" and M-2 "Exterior Glue" | 3/8 | 11/2 | 6d | 120 | 180 | 230 | 300 |
3/8 | 11/2 | 8d | 130 | 190 | 240 | 315 | |
1/2 | 140 | 210 | 270 | 350 | |||
1/2 | 15/8 | 10d | 185 | 275 | 360 | 460 | |
5/8 | 200 | 305 | 395 | 520 |
- Values are not permitted in Seismic Design Category D, E or F.
- Galvanized nails shall be hot-dipped or tumbled.
THICKNESS AND GRADE | FASTENER SIZE | ALLOWABLE SHEAR VALUE (pounds per linear foot) NAIL SPACING AT PANEL EDGES (inches)a |
||
4 | 3 | 2 | ||
1/2" or 25/32" Structural | No. 11 gage galvanized roofing nail 11/2" long for 1/2", 13/4" long for 25/32" with 3/8" head |
170 | 230 | 260 |
No. 16 gage galvanized staple, 7/16" crownf | 150 | 200 | 225 | |
No. 16 gage galvanized staple, 1" crownf | 220 | 290 | 325 |
- Fiberboard sheathing shall not be used to brace concrete or masonry walls.
- Panel edges shall be backed with 2-inch or wider framing of Douglas fir-larch or Southern pine. For framing of other species: (1) Find specific gravity for species of framing lumber in AF&PA NDS. (2) For staples, multiply the shear value from the table above by 0.82 for species with specific gravity of 0.42 or greater, or 0.65 for all other species. (3) For nails, multiply the shear value from the table above by the following adjustment factor: specific gravity adjustment factor = [1-(0.5-SG)], where SG = Specific gravity of the framing lumber.
- Values shown are for fiberboard sheathing on one side only with long panel dimension either parallel or perpendicular to studs.
- Fastener shall be spaced 6 inches on center along intermediate framing members.
- Values are not permitted in Seismic Design Category D, E or F.
- Staple length shall not be less than 11/2 inches for 25/32-inch sheathing or 11/4 inches for 1/2-inch sheathing.
TYPE OF MATERIAL | THICKNESS OF MATERIAL | WALL CONSTRUCTION | FASTENER SPACINGb MAXIMUM (inches) | SHEAR VALUEa, e (plf) | MINIMUM FASTENER SIZEc, d, j, k |
1. Expanded metal or woven wire lath and portland cement plaster |
7/8" | Unblocked | 6 | 180 | No. 11 gage 11/2" long, 7/16" head No. 16 gage galv. staple, 7/8" legs |
2. Gypsum lath, plain or perforated with vertical joints staggered |
3/8" lath and 1/2" plaster | Unblocked | 5 | 180 | No. 13 gage galv. 11/8" long, 19/64" head, plasterboard nail |
3. Gypsum lath, plain or perforated |
3/8'' lath and 1/2''plaster | Unblocked | 5 | 100 | No. 16 gage galv. staple 11/8''long, 0.120'' nail min. 3/8'' head, 11/4'' long |
4. Gypsum sheathing |
1/2" x 2' x 8' | Unblocked | 4 | 75 | No. 11 gage, 1 3/4" long, 7/16" head, diamond-point, galvanized 16 Ga. Galv. Stable, 1 3/4" long |
1/2" x 4' | Blocked d Unblocked |
4 7 |
175 100 |
||
5/8" x 4' | Blocked | 4" edge/ 7" field | 200 | 6d galvanized 0.120" Nail, min. 3/8" head, 1 3/4" long |
|
1/2" | Unblockedf | 7 | 75 | 5d cooler (15/8" × 0.086") or wallboard 0.120" nail, min. 3/8 " head, 11/2 " long No. 16 gage galv. staple, 11/2" long | |
Unblockedf | 4 | 110 | |||
Unblocked | 7 | 100 | |||
Unblocked | 4 | 125 | |||
Blockedg | 7 | 125 | |||
Blockedg | 4 | 150 | |||
Unblocked | 8/12h | 60 | No. 6—11/4" screwsi | ||
Blockedg | 4/16h | 160 | |||
Blockedf, g | 4/12h | 155 | |||
Blockedg | 8/12h | 70 | |||
Blockedg | 6/12h | 90 | |||
5/8" | Unblockedf | 7 | 115 | 6d cooler (17/8" × 0.092") or wallboard 0.120" nail, min. 3/8" head, 13/4" long No. 16 gage galv. staple, 11/2" legs, 15/8" long |
|
4 | 145 | ||||
Blockedg | 7 | 145 | |||
4 | 175 | ||||
Blockedg Two-ply |
Base ply: 9 Face ply: 7 | 250 | Base ply-6d cooler (17/8" × 0.092") or wallboard 13/4" × 0.120" nail, min. 3/8" head 15/8" 16 gage galv. staple Face ply-8d cooler (23/8" × 0.113") or wallboard 0.120" nail, min. 3/8" head, 23/8" long No. 15 gage galv. staple, 21/4" long | ||
Unblocked | 8/12h | 70 | No. 6—11/4" screwsi | ||
Blockedg | 8/12h | 90 |
- These shear walls shall not be used to resist loads imposed by masonry or concrete walls (see Section 4.1.5 of AF & PA SDPWS). Values shown are for short-term loading due to wind or seismic loading. Walls resisting seismic loads shall be subject to the limitations in Section 12.2.1 of ASCE 7. Values shown shall be reduced 25 percent for normal loading.
- Applies to fastening at studs, top and bottom plates and blocking.
- Alternate fasteners are permitted to be used if their dimensions are not less than the specified dimensions. Drywall screws are permitted to substitute for the 5d (15/8" × 0.086"), and 6d (17/8" × 0.092")(cooler) nails listed above, and No. 6 11/4 inch Type S or W screws for 6d (17/8" × 0.092) (cooler) nails.
- For properties of cooler nails, see ASTM C 514.
- Except as noted, shear values are based on a maximum framing spacing of 16 inches on center.
- Maximum framing spacing of 24 inches on center.
- All edges are blocked, and edge fastening is provided at all supports and all panel edges.
- First number denotes fastener spacing at the edges; second number denotes fastener spacing at intermediate framing members.
- Screws are Type W or S.
- Staples shall have a minimum crown width of 7/16 inch, measured outside the legs, and shall be installed with their crowns parallel to the long dimension of the framing members.
- Staples for the attachment of gypsum lath and woven-wire lath shall have a minimum crown width of 3/4 inch, measured outside the legs.
- Buildings shall be limited to a maximum of three stories above grade plane. For the purposes of this section, for buildings in Seismic Design Category D or E as determined in Section 1613, cripple stud walls shall be considered to be a story.
Exception: Solid blocked cripple walls not exceeding 14 inches (356 mm) in height need not be considered a story. - Maximum floor-to-floor height shall not exceed 11 feet, 7 inches (3531 mm). Bearing wall height shall not exceed a stud height of 10 feet (3048 mm).
- Loads as determined in Chapter 16 shall not exceed the following:
- Average dead loads shall not exceed 15 psf (718 N/m2) for combined roof and ceiling, exterior walls, floors and partitions.
Exceptions:- Subject to the limitations of Sections 2308.11.2 and 2308.12.2, stone or masonry veneer up to the lesser of 5 inches (127 mm) thick or 50 psf (2395 N/m2) and installed in accordance with Chapter 14 is permitted to a height of 30 feet (9144 mm) above a noncombustible foundation, with an additional 8 feet (2438 mm) permitted for gable ends.
- Concrete or masonry fireplaces, heaters and chimneys shall be permitted in accordance with the provisions of this code.
- Live loads shall not exceed 40 psf (1916 N/m2) for floors.
- Ground snow loads shall not exceed 50 psf (2395 N/m2).
- Average dead loads shall not exceed 15 psf (718 N/m2) for combined roof and ceiling, exterior walls, floors and partitions.
- Wind speeds shall not exceed 100 miles per hour (mph) (44 m/s) (3-second gust).
Exception: Wind speeds shall not exceed 110 mph (48.4 m/s) (3-second gust) for buildings in Exposure Category B that are not located in a hurricane-prone region. - Roof trusses and rafters shall not span more than 40 feet (12 192 mm) between points of vertical support.
- The use of the provisions for conventional light-frame construction in this section shall not be permitted for Occupancy Category IV buildings assigned to Seismic Design Category B, C, D, E or F, as determined in Section 1613.
- Conventional light-frame construction is limited in irregular structures in Seismic Design Category D or E, as specified in Section 2308.12.6.
Buildings of conventional light-frame construction in Seismic Design Category B or C, as determined in Section 1613, shall comply with the additional requirements in Section 2308.11.
Buildings of conventional light-frame construction in Seismic Design Category D or E, as determined in Section 1613, shall comply with the additional requirements in Section 2308.12.
Braced wall line top plates shall be fastened to joists, rafters or full-depth blocking above in accordance with Table 2304.9.1, Items 11, 12, 15 or 19 as applicable based on the orientation of the joists or rafters to the braced wall line. Braced wall line bottom plates shall be connected to joists or blocking below in accordance with Table 2304.9.1, Item 6, or to foundations in accordance with Section 2308.3.3. At exterior gable end walls, braced wall panel sheathing in the top story shall be extended and fastened to roof framing where the spacing between parallel exterior braced wall lines is greater than 50 feet (15 240 mm).
Girders for single-story construction or girders supporting loads from a single floor shall not be less than 4 inches by 6 inches (102 mm by 152 mm) for spans 6 feet (1829 mm) or less, provided that girders are spaced not more than 8 feet (2438 mm) o.c. Spans for built-up 2-inch (51 mm) girders shall be in accordance with Table 2308.9.5 or 2308.9.6. Other girders shall be designed to support the loads specified in this code. Girder end joints shall occur over supports.
Where a girder is spliced over a support, an adequate tie shall be provided. The ends of beams or girders supported on masonry or concrete shall not have less than 3 inches (76 mm) of bearing.
JOIST SPACING |
SPECIES AND GRADE |
DEAD LOAD = 10 psf |
DEAD LOAD = 20 psf |
||||||
2x6 |
2x8 |
2x10 |
2x12 |
2x6 |
2x8 |
2x10 |
2x12 |
||
Maximum floor joist spans |
|||||||||
(ft. - in.) |
(ft. - in.) |
(ft. - in.) |
(ft. - in.) |
(ft. - in.) |
(ft. - in.) |
(ft. - in.) |
(ft. - in.) |
||
12 |
Douglas Fir-Larch SS |
12-6 |
16-6 |
21-0 |
25-7 |
12-6 |
16-6 |
21-0 |
25-7 |
Douglas Fir-Larch #1 |
12-0 |
15-10 |
20-3 |
24-8 |
12-0 |
15-7 |
19-0 |
22-0 |
|
Douglas Fir-Larch #2 |
11-10 |
15-7 |
19-10 |
23-0 |
11-6 |
14-7 |
17-9 |
20-7 |
|
Douglas Fir-Larch #3 |
9-8 |
12-4 |
15-0 |
17-5 |
8-8 |
11-0 |
13-5 |
15-7 |
|
Hem-Fir SS |
11-10 |
15-7 |
19-10 |
24-2 |
11-10 |
15-7 |
19-10 |
24-2 |
|
Hem-Fir #1 |
11-7 |
15-3 |
19-5 |
23-7 |
11-7 |
15-2 |
18-6 |
21-6 |
|
Hem-Fir #2 |
11-0 |
14-6 |
18-6 |
22-6 |
11-0 |
14-4 |
17-6 |
20-4 |
|
Hem-Fir #3 |
9-8 |
12-4 |
15-0 |
17-5 |
8-8 |
11-0 |
13-5 |
15-7 |
|
Southern Pine SS |
12-3 |
16-2 |
20-8 |
25-1 |
12-3 |
16-2 |
20-8 |
25-1 |
|
Southern Pine #1 |
12-0 |
15-10 |
20-3 |
24-8 |
12-0 |
15-10 |
20-3 |
24-8 |
|
Southern Pine #2 |
11-10 |
15-7 |
19-10 |
24-2 |
11-10 |
15-7 |
18-7 |
21-9 |
|
Southern Pine #3 |
10-5 |
13-3 |
15-8 |
18-8 |
9-4 |
11-11 |
14-0 |
16-8 |
|
Spruce-Pine-Fir SS |
11-7 |
15-3 |
19-5 |
23-7 |
11-7 |
15-3 |
19-5 |
23-7 |
|
Spruce-Pine-Fir #1 |
11-3 |
14-11 |
19-0 |
23-0 |
11-3 |
14-7 |
17-9 |
20-7 |
|
Spruce-Pine-Fir #2 |
11-3 |
14-11 |
19-0 |
23-0 |
11-3 |
14-7 |
17-9 |
20-7 |
|
Spruce-Pine-Fir #3 |
9-8 |
12-4 |
15-0 |
17-5 |
8-8 |
11-0 |
13-5 |
15-7 |
|
16 |
Douglas Fir-Larch SS |
11-4 |
15-0 |
19-1 |
23-3 |
11-4 |
15-0 |
19-1 |
23-0 |
Douglas Fir-Larch #1 |
10-11 |
14-5 |
18-5 |
21-4 |
10-8 |
13-6 |
16-5 |
19-1 |
|
Douglas Fir-Larch #2 |
10-9 |
14-1 |
17-2 |
19-11 |
9-11 |
12-7 |
15-5 |
17-10 |
|
Douglas Fir-Larch #3 |
8-5 |
10-8 |
13-0 |
15-1 |
7-6 |
9-6 |
11-8 |
13-6 |
|
Hem-Fir SS |
10-9 |
14-2 |
18-0 |
21-11 |
10-9 |
14-2 |
18-0 |
21-11 |
|
Hem-Fir #1 |
10-6 |
13-10 |
17-8 |
20-9 |
10-4 |
13-1 |
16-0 |
18-7 |
|
Hem-Fir #2 |
10-0 |
13-2 |
16-10 |
19-8 |
9-10 |
12-5 |
15-2 |
17-7 |
|
Hem-Fir #3 |
8-5 |
10-8 |
13-0 |
15-1 |
7-6 |
9-6 |
11-8 |
13-6 |
|
Southern Pine SS |
11-2 |
14-8 |
18-9 |
22-10 |
11-2 |
14-8 |
18-9 |
22-10 |
|
Southern Pine #1 |
10-11 |
14-5 |
18-5 |
22-5 |
10-11 |
14-5 |
17-11 |
21-4 |
|
Southern Pine #2 |
10-9 |
14-2 |
18-0 |
21-1 |
10-5 |
13-6 |
16-1 |
18-10 |
|
Southern Pine #3 |
9-0 |
11-6 |
13-7 |
16-2 |
8-1 |
10-3 |
12-2 |
14-6 |
|
Spruce-Pine-Fir SS |
10-6 |
13-10 |
17-8 |
21-6 |
10-6 |
13-10 |
17-8 |
21-4 |
|
Spruce-Pine-Fir #1 |
10-3 |
13-6 |
17-2 |
19-11 |
9-11 |
12-7 |
15-5 |
17-10 |
|
Spruce-Pine-Fir #2 |
10-3 |
13-6 |
17-2 |
19-11 |
9-11 |
12-7 |
15-5 |
17-10 |
|
Spruce-Pine-Fir #3 |
8-5 |
10-8 |
13-0 |
15-1 |
7-6 |
9-6 |
11-8 |
13-6 |
|
19.2 |
Douglas Fir-Larch SS |
10-8 |
14-1 |
18-0 |
21-10 |
10-8 |
14-1 |
18-0 |
21-0 |
Douglas Fir-Larch #1 |
10-4 |
13-7 |
16-9 |
19-6 |
9-8 |
12-4 |
15-0 |
17-5 |
|
Douglas Fir-Larch #2 |
10-1 |
12-10 |
15-8 |
18-3 |
9-1 |
11-6 |
14-1 |
16-3 |
|
Douglas Fir-Larch #3 |
7-8 |
9-9 |
11-10 |
13-9 |
6-10 |
8-8 |
10-7 |
12-4 |
|
Hem-Fir SS |
10-1 |
13-4 |
17-0 |
20-8 |
10-1 |
13-4 |
17-0 |
20-7 |
|
Hem-Fir #1 |
9-10 |
13-0 |
16-4 |
19-0 |
9-6 |
12-0 |
14-8 |
17-0 |
|
Hem-Fir #2 |
9-5 |
12-5 |
15-6 |
17-1 |
8-11 |
11-4 |
13-10 |
16-1 |
|
Hem-Fir #3 |
7-8 |
9-9 |
11-10 |
13-9 |
6-10 |
8-8 |
10-7 |
12-4 |
|
Southern Pine SS |
10-6 |
13-10 |
17-8 |
21-6 |
10-6 |
13-10 |
17-8 |
21-6 |
|
Southern Pine #1 |
10-4 |
13-7 |
17-4 |
21-1 |
10-4 |
13-7 |
16-4 |
19-6 |
|
Southern Pine #2 |
10-1 |
13-4 |
16-5 |
19-3 |
9-6 |
12-4 |
14-8 |
17-2 |
|
Southern Pine #3 |
8-3 |
10-6 |
12-5 |
14-9 |
7-4 |
9-5 |
11-1 |
13-2 |
|
Spruce-Pine-Fir SS |
9-10 |
13-0 |
16-7 |
20-2 |
9-10 |
13-0 |
16-7 |
19-6 |
|
Spruce-Pine-Fir #1 |
9-8 |
12-9 |
15-8 |
18-3 |
9-1 |
11-6 |
14-1 |
16-3 |
|
Spruce-Pine-Fir #2 |
9-8 |
12-9 |
15-8 |
18-3 |
9-1 |
11-6 |
14-1 |
16-3 |
|
Spruce-Pine-Fir #3 |
7-8 |
9-9 |
11-10 |
13-9 |
6-10 |
8-8 |
10-7 |
12-4 |
|
24 |
Douglas Fir-Larch SS |
9-11 |
13-1 |
16-8 |
20-3 |
9-11 |
13-1 |
16-2 |
18-9 |
Douglas Fir-Larch #1 |
9-7 |
12-4 |
15-0 |
17-5 |
8-8 |
11-0 |
13-5 |
15-7 |
|
Douglas Fir-Larch #2 |
9-1 |
11-6 |
14-1 |
16-3 |
8-1 |
10-3 |
12-7 |
14-7 |
|
Douglas Fir-Larch #3 |
6-10 |
8-8 |
10-7 |
12-4 |
6-2 |
7-9 |
9-6 |
11-0 |
|
Hem-Fir SS |
9-4 |
12-4 |
15-9 |
19-2 |
9-4 |
12-4 |
15-9 |
18-5 |
|
Hem-Fir #1 |
9-2 |
12-0 |
14-8 |
17-0 |
8-6 |
10-9 |
13-1 |
15-2 |
|
Hem-Fir #2 |
8-9 |
11-4 |
13-10 |
16-1 |
8-0 |
10-2 |
12-5 |
14-4 |
|
Hem-Fir #3 |
6-10 |
8-8 |
10-7 |
12-4 |
6-2 |
7-9 |
9-6 |
11-0 |
|
Southern Pine SS |
9-9 |
12-10 |
16-5 |
19-11 |
9-9 |
12-10 |
16-5 |
19-11 |
|
Southern Pine #1 |
9-7 |
12-7 |
16-1 |
19-6 |
9-7 |
12-4 |
14-7 |
17-5 |
|
Southern Pine #2 |
9-4 |
12-4 |
14-8 |
17-2 |
8-6 |
11-0 |
13-1 |
15-5 |
|
Southern Pine #3 |
7-4 |
9-5 |
11-1 |
13-2 |
6-7 |
8-5 |
9-11 |
11-10 |
|
Spruce-Pine-Fir SS |
9-2 |
12-1 |
15-5 |
18-9 |
9-2 |
12-1 |
15-0 |
17-5 |
|
Spruce-Pine-Fir #1 |
8-11 |
11-6 |
14-1 |
16-3 |
8-1 |
10-3 |
12-7 |
14-7 |
|
Spruce-Pine-Fir #2 |
8-11 |
11-6 |
14-1 |
16-3 |
8-1 |
10-3 |
12-7 |
14-7 |
|
Spruce-Pine-Fir #3 |
6-10 |
8-8 |
10-7 |
12-4 |
6-2 |
7-9 |
9-6 |
11-0 |
Check sources for availability of lumber in lengths greater than 20 feet.
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square foot = 47.8 N/m2.
JOIST SPACING |
SPECIES AND GRADE |
DEAD LOAD = 10 psf |
DEAD LOAD = 20 psf |
||||||
2x6 |
2x8 |
2x10 |
2x12 |
2x6 |
2x8 |
2x10 |
2x12 |
||
Maximum floor joist spans |
|||||||||
(ft. - in.) |
(ft. - in.) |
(ft. - in.) |
(ft. - in.) |
(ft. - in.) |
(ft. - in.) |
(ft. - in.) |
(ft. - in.) |
||
12 |
Douglas Fir-Larch SS |
11-4 |
15-0 |
19-1 |
23-3 |
11-4 |
15-0 |
19-1 |
23-3 |
Douglas Fir-Larch #1 |
10-11 |
14-5 |
18-5 |
22-0 |
10-11 |
14-2 |
17-4 |
20-1 |
|
Douglas Fir-Larch #2 |
10-9 |
14-2 |
17-9 |
20-7 |
10-6 |
13-3 |
16-3 |
18-10 |
|
Douglas Fir-Larch #3 |
8-8 |
11-0 |
13-5 |
15-7 |
7-11 |
10-0 |
12-3 |
14-3 |
|
Hem-Fir SS |
10-9 |
14-2 |
18-0 |
21-11 |
10-9 |
14-2 |
18-0 |
21-11 |
|
Hem-Fir #1 |
10-6 |
13-10 |
17-8 |
21-6 |
10-6 |
13-10 |
16-11 |
19-7 |
|
Hem-Fir #2 |
10-0 |
13-2 |
16-10 |
20-4 |
10-0 |
13-1 |
16-0 |
18-6 |
|
Hem-Fir #3 |
8-8 |
11-0 |
13-5 |
15-7 |
7-11 |
10-0 |
12-3 |
14-3 |
|
Southern Pine SS |
11-2 |
14-8 |
18-9 |
22-10 |
11-2 |
14-8 |
18-9 |
22-10 |
|
Southern Pine #1 |
10-11 |
14-5 |
18-5 |
22-5 |
10-11 |
14-5 |
18-5 |
22-5 |
|
Southern Pine #2 |
10-9 |
14-2 |
18-0 |
21-9 |
10-9 |
14-2 |
16-11 |
19-10 |
|
Southern Pine #3 |
9-4 |
11-11 |
14-0 |
16-8 |
8-6 |
10-10 |
12-10 |
15-3 |
|
Spruce-Pine-Fir SS |
10-6 |
13-10 |
17-8 |
21-6 |
10-6 |
13-10 |
17-8 |
21-6 |
|
Spruce-Pine-Fir #1 |
10-3 |
13-6 |
17-3 |
20-7 |
10-3 |
13-3 |
16-3 |
18-10 |
|
Spruce-Pine-Fir #2 |
10-3 |
13-6 |
17-3 |
20-7 |
10-3 |
13-3 |
16-3 |
18-10 |
|
Spruce-Pine-Fir #3 |
8-8 |
11-0 |
13-5 |
15-7 |
7-11 |
10-0 |
12-3 |
14-3 |
|
16 |
Douglas Fir-Larch SS |
10-4 |
13-7 |
17-4 |
21-1 |
10-4 |
13-7 |
17-4 |
21-0 |
Douglas Fir-Larch #1 |
9-11 |
13-1 |
16-5 |
19-1 |
9-8 |
12-4 |
15-0 |
17-5 |
|
Douglas Fir-Larch #2 |
9-9 |
12-7 |
15-5 |
17-10 |
9-1 |
11-6 |
14-1 |
16-3 |
|
Douglas Fir-Larch #3 |
7-6 |
9-6 |
11-8 |
13-6 |
6-10 |
8-8 |
10-7 |
12-4 |
|
Hem-Fir SS |
9-9 |
12-10 |
16-5 |
19-11 |
9-9 |
12-10 |
16-5 |
19-11 |
|
Hem-Fir #1 |
9-6 |
12-7 |
16-0 |
18-7 |
9-6 |
12-0 |
14-8 |
17-0 |
|
Hem-Fir #2 |
9-1 |
12-0 |
15-2 |
17-7 |
8-11 |
11-4 |
13-10 |
16-1 |
|
Hem-Fir #3 |
7-6 |
9-6 |
11-8 |
13-6 |
6-10 |
8-8 |
10-7 |
12-4 |
|
Southern Pine SS |
10-2 |
13-4 |
17-0 |
20-9 |
10-2 |
13-4 |
17-0 |
20-9 |
|
Southern Pine #1 |
9-11 |
13-1 |
16-9 |
20-4 |
9-11 |
13-1 |
16-4 |
19-6 |
|
Southern Pine #2 |
9-9 |
12-10 |
16-1 |
18-10 |
9-6 |
12-4 |
14-8 |
17-2 |
|
Southern Pine #3 |
8-1 |
10-3 |
12-2 |
14-6 |
7-4 |
9-5 |
11-1 |
13-2 |
|
Spruce-Pine-Fir SS |
9-6 |
12-7 |
16-0 |
19-6 |
9-6 |
12-7 |
16-0 |
19-6 |
|
Spruce-Pine-Fir #1 |
9-4 |
12-3 |
15-5 |
17-10 |
9-1 |
11-6 |
14-1 |
16-3 |
|
Spruce-Pine-Fir #2 |
9-4 |
12-3 |
15-5 |
17-10 |
9-1 |
11-6 |
14-1 |
16-3 |
|
Spruce-Pine-Fir #3 |
7-6 |
9-6 |
11-8 |
13-6 |
6-10 |
8-8 |
10-7 |
12-4 |
|
19.2 |
Douglas Fir-Larch SS |
9-8 |
12-10 |
16-4 |
19-10 |
9-8 |
12-10 |
16-4 |
19-2 |
Douglas Fir-Larch #1 |
9-4 |
12-4 |
15-0 |
17-5 |
8-10 |
11-3 |
13-8 |
15-11 |
|
Douglas Fir-Larch #2 |
9-1 |
11-6 |
14-1 |
16-3 |
8-3 |
10-6 |
12-10 |
14-10 |
|
Douglas Fir-Larch #3 |
6-10 |
8-8 |
10-7 |
12-4 |
6-3 |
7-11 |
9-8 |
11-3 |
|
Hem-Fir SS |
9-2 |
12-1 |
15-5 |
18-9 |
9-2 |
12-1 |
15-5 |
18-9 |
|
Hem-Fir #1 |
9-0 |
11-10 |
14-8 |
17-0 |
8-8 |
10-11 |
13-4 |
15-6 |
|
Hem-Fir #2 |
8-7 |
11-3 |
13-10 |
16-1 |
8-2 |
10-4 |
12-8 |
14-8 |
|
Hem-Fir #3 |
6-10 |
8-8 |
10-7 |
12-4 |
6-3 |
7-11 |
9-8 |
11-3 |
|
Southern Pine SS |
9-6 |
12-7 |
16-0 |
19-6 |
9-6 |
12-7 |
16-0 |
19-6 |
|
Southern Pine #1 |
9-4 |
12-4 |
15-9 |
19-2 |
9-4 |
12-4 |
14-11 |
17-9 |
|
Southern Pine #2 |
9-2 |
12 -1 |
14-8 |
17-2 |
8-8 |
11-3 |
13-5 |
15-8 |
|
Southern Pine #3 |
7-4 |
9-5 |
11-1 |
13-2 |
6-9 |
8-7 |
10-1 |
12-1 |
|
Spruce-Pine-Fir SS |
9-0 |
11-10 |
15-1 |
18-4 |
9-0 |
11-10 |
15-1 |
17-9 |
|
Spruce-Pine-Fir #1 |
8-9 |
11-6 |
14-1 |
16-3 |
8-3 |
10-6 |
12-10 |
14-10 |
|
Spruce-Pine-Fir #2 |
8-9 |
11-6 |
14-1 |
16-3 |
8-3 |
10-6 |
12-10 |
14-10 |
|
Spruce-Pine-Fir #3 |
6-10 |
8-8 |
10-7 |
12-4 |
6-3 |
7-11 |
9-8 |
11-3 |
|
24 |
Douglas Fir-Larch SS |
9-0 |
11-11 |
15-2 |
18-5 |
9-0 |
11-11 |
14-9 |
17-1 |
Douglas Fir-Larch #1 |
8-8 |
11-0 |
13-5 |
15-7 |
7-11 |
10-0 |
12-3 |
14-3 |
|
Douglas Fir-Larch #2 |
8-1 |
10-3 |
12-7 |
14-7 |
7-5 |
9-5 |
11-6 |
13-4 |
|
Douglas Fir-Larch #3 |
6-2 |
7-9 |
9-6 |
11-0 |
5-7 |
7-1 |
8-8 |
10-1 |
|
Hem-Fir SS |
8-6 |
11-3 |
14-4 |
17-5 |
8-6 |
11-3 |
14-4 |
16-10a |
|
Hem-Fir #1 |
8-4 |
10-9 |
13-1 |
15-2 |
7-9 |
9-9 |
11-11 |
13-10 |
|
Hem-Fir #2 |
7-11 |
10-2 |
12-5 |
14-4 |
7-4 |
9-3 |
11-4 |
13-1 |
|
Hem-Fir #3 |
6-2 |
7-9 |
9-6 |
11-0 |
5-7 |
7-1 |
8-8 |
10-1 |
|
Southern Pine SS |
8-10 |
11-8 |
14-11 |
18-1 |
8-10 |
11-8 |
14-11 |
18-1 |
|
Southern Pine #1 |
8-8 |
11-5 |
14-7 |
17-5 |
8-8 |
11-3 |
13-4 |
15-11 |
|
Southern Pine #2 |
8-6 |
11-0 |
13-1 |
15-5 |
7-9 |
10-0 |
12-0 |
14-0 |
|
Southern Pine #3 |
6-7 |
8-5 |
9-11 |
11-10 |
6-0 |
7-8 |
9-1 |
10-9 |
|
Spruce-Pine-Fir SS |
8-4 |
11-0 |
14-0 |
17-0 |
8-4 |
11-0 |
13-8 |
15-11 |
|
Spruce-Pine-Fir #1 |
8-1 |
10-3 |
12-7 |
14-7 |
7-5 |
9-5 |
11-6 |
13-4 |
|
Spruce-Pine-Fir #2 |
8-1 |
10-3 |
12-7 |
14-7 |
7-5 |
9-5 |
11-6 |
13-4 |
|
Spruce-Pine-Fir #3 |
6-2 |
7-9 |
9-6 |
11-0 |
5-7 |
7-1 |
8-8 |
10-1 |
Check sources for availability of lumber in lengths greater than 20 feet.
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square foot = 47.8 N/m2.
- End bearing length shall be increased to 2 inches.
Joists shall be supported laterally at the ends and at each support by solid blocking except where the ends of the joists are nailed to a header, band or rim joist or to an adjoining stud or by other means. Solid blocking shall not be less than 2 inches (51mm) in thickness and the full depth of the joist. Notches on the ends of joists shall not exceed one-fourth the joist depth. Holes bored in joists shall not be within 2 inches (51 mm) of the top or bottom of the joist, and the diameter of any such hole shall not exceed one-third the depth of the joist. Notches in the top or bottom of joists shall not exceed one-sixth the depth and shall not be located in the middle third of the span.
Joist framing from opposite sides of a beam, girder or partition shall be lapped at least 3 inches (76 mm) or the opposing joists shall be tied together in an approved manner.
Joists framing into the side of a wood girder shall be supported by framing anchors or on ledger strips not less than 2 inches by 2 inches (51 mm by 51 mm).
STUD SIZE |
BEARING WALLS |
NONBEARING WALLS |
||||
Laterally unsupported |
Supporting roof |
Supporting one floor, roof |
Supporting two floors, roof |
Laterally unsupported |
Spacing |
|
Spacing |
||||||
2 × 3b |
— |
— |
— |
— |
10 |
16 |
2 × 4 |
10 |
24 |
16 |
— |
14 |
24 |
3 × 4 |
10 |
24 |
24 |
16 |
14 |
24 |
2 × 5 |
10 |
24 |
24 |
— |
16 |
24 |
2 × 6 |
10 |
24 |
24 |
16 |
20 |
24 |
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm.
- Listed heights are distances between points of lateral support placed perpendicular to the plane of the wall. Increases in unsupported height are permitted where justified by an analysis.
- Shall not be used in exterior walls.
- Nominal 1-inch by 4-inch (25 mm by 102 mm) continuous diagonal braces let into top and bottom plates and intervening studs, placed at an angle not more than 60 degrees (1.0 rad) or less than 45 degrees (0.79 rad) from the horizontal and attached to the framing in conformance with Table 2304.9.1.
- Wood boards of 5/8 inch (15.9 mm) net minimum thickness applied diagonally on studs spaced not over 24 inches (610 mm) o.c.
- Wood structural panel sheathing with a thickness not less than 3/8 inch (9.5 mm) for 16-inch (406 mm) or 24-inch (610 mm) stud spacing in accordance with Tables 2308.9.3(2) and 2308.9.3(3).
- Fiberboard sheathing panels not less than 1/2 inch (12.7 mm) thick applied vertically or horizontally on studs spaced not over 16 inches (406 mm) o.c. where installed with fasteners in accordance with Section 2306.6 and Table 2306.6.
- Gypsum board [sheathing 1/2-inch-thick (12.7 mm) by 4-feet-wide (1219 mm) wallboard or veneer base] on studs spaced not over 24 inches (610 mm) o.c. and nailed at 7 inches (178 mm) o.c. with nails as required by Table 2306.7.
- Particleboard wall sheathing panels where installed in accordance with Table 2308.9.3(4).
- Portland cement plaster on studs spaced 16 inches (406 mm) o.c. installed in accordance with Section 2510.
- Hardboard panel siding where installed in accordance with Section 2303.1.6 and Table 2308.9.3(5).
For Method 5, each panel must be at least 96 inches (2438 mm) in length where applied to one face of a panel and 48 inches (1219 mm) where applied to both faces. All vertical joints of panel sheathing shall occur over studs and adjacent panel joints shall be nailed to common framing members. Horizontal joints shall occur over blocking or other framing equal in size to the studding except where waived by the installation requirements for the specific sheathing materials. Sole plates shall be nailed to the floor framing and top plates shall be connected to the framing above in accordance with Section 2308.3.2. Where joists are perpendicular to braced wall lines above, blocking shall be provided under and in line with the braced wall panels.
SEISMIC DESIGN CATEGORY | CONDITION | CONSTRUCTION METHODSb, c | BRACED PANEL LOCATION AND LENGTHd | |||||||
1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | |||
A and B | One story, top of two or three story | X | X | X | X | X | X | X | X | Located in accordance with Section 2308.9.3 and not more than 25 feet on center. |
First story of two story or second story of three story | X | X | X | X | X | X | X | X | ||
First story of three story | 3/4 | X | X | X | Xe | X | X | X | ||
C | One story or top of two story | — | X | X | X | X | X | X | X | Located in accordance with Section 2308.9.3 and not more than 25 feet on center. |
First story of two story | — | X | X | X | Xe | X | X | X | Located in accordance with Section 2308.9.3 and not more than 25 feet on center, but total length shall not be less than 25% of building lengthf. |
- This table specifies minimum requirements for braced panels that form interior or exterior braced wall lines.
- See Section 2308.9.3 for full description.
- See Sections 2308.9.3.1 and 2308.9.3.2 for alternative braced panel requirements.
- Building length is the dimension parallel to the braced wall length.
- Gypsum wallboard applied to framing supports that are spaced at 16 inches on center.
- The required lengths shall be doubled for gypsum board applied to only one face of a braced wall panel.
MINIMUM THICKNESSa (inch) |
MINIMUM NUMBER OF PLIES | STUD SPACING (inches) Plywood siding applied directly to studs or over sheathing |
3/8 | 3 | 16b |
1/2 | 4 | 24 |
- Thickness of grooved panels is measured at bottom of grooves.
- Spans are permitted to be 24 inches if plywood siding applied with face grain perpendicular to studs or over one of the following: (1) 1-inch board sheathing, (2) 7/16 -inch wood structural panel sheathing or (3) 3/8-inch wood structural panel sheathing with strength axis (which is the long direction of the panel unless otherwise marked) of sheathing perpendicular to studs.
MINIMUM THICKNESS (inch) |
PANEL SPAN RATING | STUD SPACING (inches) | ||
Siding nailed to studs | Nailable sheathing | |||
Sheathing parallel to studs | Sheathing perpendicular to studs | |||
3/8, 15/32, 1/2 | 16/0, 20/0, 24/0, 32/16 Wall—24" o.c. |
24 | 16 | 24 |
7/16, 15/32, 1/2 | 24/0, 24/16, 32/16 Wall—24" o.c. |
24 | 24a | 24 |
GRADE | THICKNESS (inch) |
STUD SPACING (inches) | |
Siding nailed to studs |
Sheathing under coverings specified in Section 2308.9.3 parallel or perpendicular to studs |
||
M-S "Exterior Glue" and M-2"Exterior Glue" |
3/8 | 16 | — |
1/2 | 16 | 16 |
SIDING | MINIMUM NOMINAL THICKNESS (inch) |
2 × 4 FRAMING MAXIMUM SPACING |
NAIL SIZEa, b, d |
NAIL SPACING | |
General | Bracing panelsc | ||||
1. Lap siding | |||||
Direct to studs | 3/8 | 16" o.c. | 8d | 16" o.c. | Not applicable |
Over sheathing | 3/8 | 16" o.c. | 10d | 16" o.c. | Not applicable |
2. Square edge panel siding | |||||
Direct to studs | 3/8 | 24" o.c. | 6d | 6" o.c. edges; 12" o.c. at intermediate supports |
4" o.c. edges; 8" o.c. at intermediate supports |
Over sheathing | 3/8 | 24" o.c. | 8d | 6" o.c. edges; 12" o.c. at intermediate supports |
4" o.c. edges; 8" o.c. at intermediate supports |
3. Shiplap edge panel siding | |||||
Direct to studs | 3/8 | 16" o.c. | 6d | 6" o.c. edges; 12" o.c. at intermediate supports |
4" o.c. edges; 8" o.c. at intermediate supports |
Over sheathing | 3/8 | 16" o.c. | 8d | 6" o.c. edges; 12" o.c. at intermediate supports |
4" o.c. edges; 8" o.c. at intermediate supports |
- Nails shall be corrosion resistant.
- Minimum acceptable nail dimensions:
Panel Siding
(inch)Lap Siding
(inch)Shank diameter 0.092 0.099 Head diameter 0.225 0.240 - Where used to comply with Section 2308.9.3.
- Nail length must accommodate the sheathing and penetrate framing 11/2 inches.
SEISMIC DESIGN CATEGORY | MAXIMUM WALL SPACING (feet) | REQUIRED BRACING LENGTH, b |
A, B and C | 35'-0" | TABLE 2308.9.3(1) and Section 2308.9.3 |
D and E | 25'-0" | TABLE 2308.12.4 |
BASIC COMPONENTS OF THE LATERAL BRACING SYSTEM
- In one-story buildings, each panel shall have a length of not less than 2 feet 8 inches (813 mm) and a height of not more than 10 feet (3048 mm). Each panel shall be sheathed on one face with 3/8-inch-minimum-thickness (9.5 mm) wood structural panel sheathing nailed with 8d common or galvanized box nails in accordance with Table 2304.9.1 and blocked at wood structural panel edges. Two anchor bolts installed in accordance with Section 2308.6 shall be provided in each panel. Anchor bolts shall be placed at each panel outside quarter points. Each panel end stud shall have a tie-down device fastened to the foundation, capable of providing an approved uplift capacity of not less than 1,800 pounds (8006 N). The tie-down device shall be installed in accordance with the manufacturer's recommendations. The panels shall be supported directly on a foundation or on floor framing supported directly on a foundation that is continuous across the entire length of the braced wall line. This foundation shall be reinforced with not less than one No. 4 bar top and bottom.
Where the continuous foundation is required to have a depth greater than 12 inches (305 mm), a minimum 12-inch by 12-inch (305 mm by 305 mm) continuous footing or turned down slab edge is permitted at door openings in the braced wall line. This continuous footing or turned down slab edge shall be reinforced with not less than one No. 4 bar top and bottom. This reinforcement shall be lapped 15 inches (381 mm) with the reinforcement required in the continuous foundation located directly under the braced wall line. - In the first story of two-story buildings, each wall panel shall be braced in accordance with Section 2308.9.3.1, Item 1, except that the wood structural panel sheathing shall be provided on both faces, three anchor bolts shall be placed at one-quarter points, and tie-down device uplift capacity shall not be less than 3,000 pounds (13 344 N).
- In one-story buildings, each panel shall have a length of not less than 16 inches (406 mm) and a height of not more than 10 feet (3048 mm). Each panel shall be sheathed on one face with a single layer of 3/8 inch (9.5 mm) minimum thickness wood structural panel sheathing nailed with 8d common or galvanized box nails in accordance with Figure 2308.9.3.2. The wood structural panel sheathing shall extend up over the solid sawn or glued-laminated header and shall be nailed in accordance with Figure 2308.9.3.2. A built-up header consisting of at least two 2 × 12s and fastened in accordance with Item 24 of Table 2304.9.1 shall be permitted to be used. A spacer, if used, shall be placed on the side of the built-up beam opposite the wood structural panel sheathing. The header shall extend between the inside faces of the first full-length outer studs of each panel. The clear span of the header between the inner studs of each panel shall be not less than 6 feet (1829 mm) and not more than 18 feet (5486 mm) in length. A strap with an uplift capacity of not less than 1,000 pounds (4,400 N) shall fasten the header to the inner studs opposite the sheathing. One anchor bolt not less than 5/8 inch (15.9 mm) diameter and installed in accordance with Section 2308.6 shall be provided in the center of each sill plate. The studs at each end of the panel shall have a tie-down device fastened to the foundation with an uplift capacity of not less than 4,200 pounds (18 480 N).
Where a panel is located on one side of the opening, the header shall extend between the inside face of the first full-length stud of the panel and the bearing studs at the other end of the opening. A strap with an uplift capacity of not less than 1,000 pounds (4400 N) shall fasten the header to the bearing studs. The bearing studs shall also have a tie-down device fastened to the foundation with an uplift capacity of not less than 1,000 pounds (4400 N).
The tie-down devices shall be an embedded strap type, installed in accordance with the manufacturer's recommendations. The panels shall be supported directly on a foundation that is continuous across the entire length of the braced wall line. This foundation shall be reinforced with not less than one No. 4 bar top and bottom.
Where the continuous foundation is required to have a depth greater than 12 inches (305 mm), a minimum 12-inch by 12-inch (305 mm by 305 mm) continuous footing or turned down slab edge is permitted at door openings in the braced wall line. This continuous footing or turned down slab edge shall be reinforced with not less than one No. 4 bar top and bottom. This reinforcement shall be lapped not less than 15 inches (381 mm) with the reinforcement required in the continuous foundation located directly under the braced wall line. - In the first story of two-story buildings, each wall panel shall be braced in accordance with Item 1 above, except that each panel shall have a length of not less than 24 inches (610 mm).
ALTERNATE BRACED WALL PANEL ADJACENT TO A DOOR OR WINDOW OPENING
HEADERS SUPPORTING |
SIZE | GROUND SNOW LOAD (psf)e | |||||||||||
30 | 50 | ||||||||||||
Building widthc (feet) | |||||||||||||
20 | 28 | 36 | 20 | 28 | 36 | ||||||||
Span | NJd | Span | NJd | Span | NJd | Span | NJd | Span | NJd | Span | NJd | ||
Roof & Ceiling | 2-2 × 4 | 3-6 | 1 | 3-2 | 1 | 2-10 | 1 | 3-2 | 1 | 2-9 | 1 | 2-6 | 1 |
2-2 × 6 | 5-5 | 1 | 4-8 | 1 | 4-2 | 1 | 4-8 | 1 | 4-1 | 1 | 3-8 | 2 | |
2-2 × 8 | 6-10 | 1 | 5-11 | 2 | 5-4 | 2 | 5-11 | 2 | 5-2 | 2 | 4-7 | 2 | |
2-2 × 10 | 8-5 | 2 | 7-3 | 2 | 6-6 | 2 | 7-3 | 2 | 6-3 | 2 | 5-7 | 2 | |
2-2 × 12 | 9-9 | 2 | 8-5 | 2 | 7-6 | 2 | 8-5 | 2 | 7-3 | 2 | 6-6 | 2 | |
3-2 × 8 | 8-4 | 1 | 7-5 | 1 | 6-8 | 1 | 7-5 | 1 | 6-5 | 2 | 5-9 | 2 | |
3-2 × 10 | 10-6 | 1 | 9-1 | 2 | 8-2 | 2 | 9-1 | 2 | 7-10 | 2 | 7-0 | 2 | |
3-2 × 12 | 12-2 | 2 | 10-7 | 2 | 9-5 | 2 | 10-7 | 2 | 9-2 | 2 | 8-2 | 2 | |
4-2 × 8 | 9-2 | 1 | 8-4 | 1 | 7-8 | 1 | 8-4 | 1 | 7-5 | 1 | 6-8 | 1 | |
4-2 × 10 | 11-8 | 1 | 10-6 | 1 | 9-5 | 2 | 10-6 | 1 | 9-1 | 2 | 8-2 | 2 | |
4-2 × 12 | 14-1 | 1 | 12-2 | 2 | 10-11 | 2 | 12-2 | 2 | 10-7 | 2 | 9-5 | 2 | |
Roof, Ceiling & 1 Center-Bearing Floor |
2-2 × 4 | 3-1 | 1 | 2-9 | 1 | 2-5 | 1 | 2-9 | 1 | 2-5 | 1 | 2-2 | 1 |
2-2 × 6 | 4-6 | 1 | 4-0 | 1 | 3-7 | 2 | 4-1 | 1 | 3-7 | 2 | 3-3 | 2 | |
2-2 × 8 | 5-9 | 2 | 5-0 | 2 | 4-6 | 2 | 5-2 | 2 | 4-6 | 2 | 4-1 | 2 | |
2-2 × 10 | 7-0 | 2 | 6-2 | 2 | 5-6 | 2 | 6-4 | 2 | 5-6 | 2 | 5-0 | 2 | |
2-2 × 12 | 8-1 | 2 | 7-1 | 2 | 6-5 | 2 | 7-4 | 2 | 6-5 | 2 | 5-9 | 3 | |
3-2 × 8 | 7-2 | 1 | 6-3 | 2 | 5-8 | 2 | 6-5 | 2 | 5-8 | 2 | 5-1 | 2 | |
3-2 × 10 | 8-9 | 2 | 7-8 | 2 | 6-11 | 2 | 7-11 | 2 | 6-11 | 2 | 6-3 | 2 | |
3-2 × 12 | 10-2 | 2 | 8-11 | 2 | 8-0 | 2 | 9-2 | 2 | 8-0 | 2 | 7-3 | 2 | |
4-2 × 8 | 8-1 | 1 | 7-3 | 1 | 6-7 | 1 | 7-5 | 1 | 6-6 | 1 | 5-11 | 2 | |
4-2 × 10 | 10-1 | 1 | 8-10 | 2 | 8-0 | 2 | 9-1 | 2 | 8-0 | 2 | 7-2 | 2 | |
4-2 × 12 | 11-9 | 2 | 10-3 | 2 | 9-3 | 2 | 10-7 | 2 | 9-3 | 2 | 8-4 | 2 | |
Roof, Ceiling & 1 Clear Span Floor |
2-2 × 4 | 2-8 | 1 | 2-4 | 1 | 2-1 | 1 | 2-7 | 1 | 2-3 | 1 | 2-0 | 1 |
2-2 × 6 | 3-11 | 1 | 3-5 | 2 | 3-0 | 2 | 3-10 | 2 | 3-4 | 2 | 3-0 | 2 | |
2-2 × 8 | 5-0 | 2 | 4-4 | 2 | 3-10 | 2 | 4-10 | 2 | 4-2 | 2 | 3-9 | 2 | |
2-2 × 10 | 6-1 | 2 | 5-3 | 2 | 4-8 | 2 | 5-11 | 2 | 5-1 | 2 | 4-7 | 3 | |
2-2 × 12 | 7-1 | 2 | 6-1 | 3 | 5-5 | 3 | 6-10 | 2 | 5-11 | 3 | 5-4 | 3 | |
3-2 × 8 | 6-3 | 2 | 5-5 | 2 | 4-10 | 2 | 6-1 | 2 | 5-3 | 2 | 4-8 | 2 | |
3-2 × 10 | 7-7 | 2 | 6-7 | 2 | 5-11 | 2 | 7-5 | 2 | 6-5 | 2 | 5-9 | 2 | |
3-2 × 12 | 8-10 | 2 | 7-8 | 2 | 6-10 | 2 | 8-7 | 2 | 7-5 | 2 | 6-8 | 2 | |
4-2 × 8 | 7-2 | 1 | 6-3 | 2 | 5-7 | 2 | 7-0 | 1 | 6-1 | 2 | 5-5 | 2 | |
4-2 × 10 | 8-9 | 2 | 7-7 | 2 | 6-10 | 2 | 8-7 | 2 | 7-5 | 2 | 6-7 | 2 | |
4-2 × 12 | 10-2 | 2 | 8-10 | 2 | 7-11 | 2 | 9-11 | 2 | 8-7 | 2 | 7-8 | 2 | |
Roof, Ceiling & 2 Center-Bearing Floors |
2-2 × 4 | 2-7 | 1 | 2-3 | 1 | 2-0 | 1 | 2-6 | 1 | 2-2 | 1 | 1-11 | 1 |
2-2 × 6 | 3-9 | 2 | 3-3 | 2 | 2-11 | 2 | 3-8 | 2 | 3-2 | 2 | 2-10 | 2 | |
2-2 × 8 | 4-9 | 2 | 4-2 | 2 | 3-9 | 2 | 4-7 | 2 | 4-0 | 2 | 3-8 | 2 | |
2-2 × 10 | 5-9 | 2 | 5-1 | 2 | 4-7 | 3 | 5-8 | 2 | 4-11 | 2 | 4-5 | 3 | |
2-2 × 12 | 6-8 | 2 | 5-10 | 3 | 5-3 | 3 | 6-6 | 2 | 5-9 | 3 | 5-2 | 3 | |
3-2 × 8 | 5-11 | 2 | 5-2 | 2 | 4-8 | 2 | 5-9 | 2 | 5-1 | 2 | 4-7 | 2 | |
3-2 × 10 | 7-3 | 2 | 6-4 | 2 | 5-8 | 2 | 7-1 | 2 | 6-2 | 2 | 5-7 | 2 | |
3-2 × 12 | 8-5 | 2 | 7-4 | 2 | 6-7 | 2 | 8-2 | 2 | 7-2 | 2 | 6-5 | 3 | |
4-2 × 8 | 6-10 | 1 | 6-0 | 2 | 5-5 | 2 | 6-8 | 1 | 5-10 | 2 | 5-3 | 2 | |
4-2 × 10 | 8-4 | 2 | 7-4 | 2 | 6-7 | 2 | 8-2 | 2 | 7-2 | 2 | 6-5 | 2 | |
4-2 × 12 | 9-8 | 2 | 8-6 | 2 | 7-8 | 2 | 9-5 | 2 | 8-3 | 2 | 7-5 | 2 | |
Roof, Ceiling & 2 Clear Span Floors |
2-2 × 4 | 2-1 | 1 | 1-8 | 1 | 1-6 | 2 | 2-0 | 1 | 1-8 | 1 | 1-5 | 2 |
2-2 × 6 | 3-1 | 2 | 2-8 | 2 | 2-4 | 2 | 3-0 | 2 | 2-7 | 2 | 2-3 | 2 | |
2-2 × 8 | 3-10 | 2 | 3-4 | 2 | 3-0 | 3 | 3-10 | 2 | 3-4 | 2 | 2-11 | 3 | |
2-2 × 10 | 4-9 | 2 | 4-1 | 3 | 3-8 | 3 | 4-8 | 2 | 4-0 | 3 | 3-7 | 3 | |
2-2 × 12 | 5-6 | 3 | 4-9 | 3 | 4-3 | 3 | 5-5 | 3 | 4-8 | 3 | 4-2 | 3 | |
3-2 × 8 | 4-10 | 2 | 4-2 | 2 | 3-9 | 2 | 4-9 | 2 | 4-1 | 2 | 3-8 | 2 | |
3-2 × 10 | 5-11 | 2 | 5-1 | 2 | 4-7 | 3 | 5-10 | 2 | 5-0 | 2 | 4-6 | 3 | |
3-2 × 12 | 6-10 | 2 | 5-11 | 3 | 5-4 | 3 | 6-9 | 2 | 5-10 | 3 | 5-3 | 3 | |
4-2 × 8 | 5-7 | 2 | 4-10 | 2 | 4-4 | 2 | 5-6 | 2 | 4-9 | 2 | 4-3 | 2 | |
4-2 × 10 | 6-10 | 2 | 5-11 | 2 | 5-3 | 2 | 6-9 | 2 | 5-10 | 2 | 5-2 | 2 | |
4-2 × 12 | 7-11 | 2 | 6-10 | 2 | 6-2 | 3 | 7-9 | 2 | 6-9 | 2 | 6-0 | 3 |
- Spans are given in feet and inches (ft-in).
- Tabulated values are for No. 2 grade lumber.
- Building width is measured perpendicular to the ridge. For widths between those shown, spans are permitted to be interpolated.
- NJ - Number of jack studs required to support each end. Where the number of required jack studs equals one, the header is permitted to be supported by an approved framing anchor attached to the full-height wall stud and to the header.
- Use 30 pounds per square foot ground snow load for cases in which ground snow load is less than 30 pounds per square foot and the roof live load is equal to or less than 20 pounds per square foot.
HEADERS AND GIRDERS SUPPORTING |
SIZE | BUILDING WIDTHc (feet) | |||||
20 | 28 | 36 | |||||
Span | NJd | Span | NJd | Span | NJd | ||
One Floor Only | 2-2 × 4 | 3-1 | 1 | 2-8 | 1 | 2-5 | 1 |
2-2 × 6 | 4-6 | 1 | 3-11 | 1 | 3-6 | 1 | |
2-2 × 8 | 5-9 | 1 | 5-0 | 2 | 4-5 | 2 | |
2-2 ×10 | 7-0 | 2 | 6-1 | 2 | 5-5 | 2 | |
2-2 ×12 | 8-1 | 2 | 7-0 | 2 | 6-3 | 2 | |
3-2 × 8 | 7-2 | 1 | 6-3 | 1 | 5-7 | 2 | |
3-2 ×10 | 8-9 | 1 | 7-7 | 2 | 6-9 | 2 | |
3-2 ×12 | 10-2 | 2 | 8-10 | 2 | 7-10 | 2 | |
4-2 × 8 | 9-0 | 1 | 7-8 | 1 | 6-9 | 1 | |
4-2 ×10 | 10-1 | 1 | 8-9 | 1 | 7-10 | 2 | |
4-2 ×12 | 11-9 | 1 | 10-2 | 2 | 9-1 | 2 | |
Two Floors | 2-2 × 4 | 2-2 | 1 | 1-10 | 1 | 1-7 | 1 |
2-2 × 6 | 3-2 | 2 | 2-9 | 2 | 2-5 | 2 | |
2-2 × 8 | 4-1 | 2 | 3-6 | 2 | 3-2 | 2 | |
2-2 ×10 | 4-11 | 2 | 4-3 | 2 | 3-10 | 3 | |
2-2 ×12 | 5-9 | 2 | 5-0 | 3 | 4-5 | 3 | |
3-2 × 8 | 5-1 | 2 | 4-5 | 2 | 3-11 | 2 | |
3-2 ×10 | 6-2 | 2 | 5-4 | 2 | 4-10 | 2 | |
3-2 ×12 | 7-2 | 2 | 6-3 | 2 | 5-7 | 3 | |
4-2 × 8 | 6-1 | 1 | 5-3 | 2 | 4-8 | 2 | |
4-2 ×10 | 7-2 | 2 | 6-2 | 2 | 5-6 | 2 | |
4-2 ×12 | 8-4 | 2 | 7-2 | 2 | 6-5 | 2 |
- Spans are given in feet and inches (ft-in).
- Tabulated values are for No. 2 grade lumber.
- Building width is measured perpendicular to the ridge. For widths between those shown, spans are permitted to be interpolated.
- NJ - Number of jack studs required to support each end. Where the number of required jack studs equals one, the headers are permitted to be supported by an approved framing anchor attached to the full-height wall stud and to the header.
A hole not greater in diameter than 40 percent of the stud width is permitted to be bored in any wood stud. Bored holes not greater than 60 percent of the width of the stud are permitted in nonbearing partitions or in any wall where each bored stud is doubled, provided not more than two such successive doubled studs are so bored.
In no case shall the edge of the bored hole be nearer than 5/8 inch (15.9 mm) to the edge of the stud.
Bored holes shall not be located at the same section of stud as a cut or notch.
BASIC WIND SPEED (3-second gust) |
ROOF SPAN (feet) | OVERHANGS (pounds/feet)d |
||||||
12 | 20 | 24 | 28 | 32 | 36 | 40 | ||
85 | -72 | -120 | -145 | -169 | -193 | -217 | -241 | -38.55 |
90 | -91 | -151 | -181 | -212 | -242 | -272 | -302 | -43.22 |
100 | -131 | -281 | -262 | -305 | -349 | -393 | -436 | -53.36 |
110 | -175 | -292 | -351 | -409 | -467 | -526 | -584 | -64.56 |
- The uplift connection requirements are based on a 30-foot mean roof height located in Exposure B. For Exposure C or D and for other mean roof heights, multiply the above loads by the adjustment coefficients below.
Mean Roof Height (feet) EXPOSURE 15 20 25 30 35 40 45 50 55 60 B 1.00 1.00 1.00 1.00 1.05 1.09 1.12 1.16 1.19 1.22 C 1.21 1.29 1.35 1.40 1.45 1.49 1.53 1.56 1.59 1.62 D 1.47 1.55 1.61 1.66 1.70 1.74 1.78 1.81 1.84 1.87 - The uplift connection requirements are based on the framing being spaced 24 inches on center. Multiply by 0.67 for framing spaced 16 inches on center and multiply by 0.5 for framing spaced 12 inches on center.
- The uplift connection requirements include an allowance for 10 pounds of dead load.
- The uplift connection requirements do not account for the effects of overhangs. The magnitude of the above loads shall be increased by adding the overhang loads found in the table. The overhang loads are also based on framing spaced 24 inches on center. The overhang loads given shall be multiplied by the overhang projection and added to the roof uplift value in the table.
- The uplift connection requirements are based upon wind loading on end zones as defined in Figure 6-2 of ASCE 7. Connection loads for connections located a distance of 20 percent of the least horizontal dimension of the building from the corner of the building are permitted to be reduced by multiplying the table connection value by 0.7 and multiplying the overhang load by 0.8.
- For wall-to-wall and wall-to-foundation connections, the capacity of the uplift connector is permitted to be reduced by 100 pounds for each full wall above. (For example, if a 500-pound rated connector is used on the roof framing, a 400-pound rated connector is permitted at the next floor level down).
- Interpolation is permitted for intermediate values of basic wind speeds and roof spans.
- The rated capacity of approved tie-down devices is permitted to include up to a 60-percent increase for wind effects where allowed by material specifications.
CEILING JOIST SPACING (inches) |
SPECIES AND GRADE | DEAD LOAD = 5 pounds per square foot | ||||
2 × 4 | 2 × 6 | 2 × 8 | 2 × 10 | |||
Maximum ceiling joist spans | ||||||
(ft. - in.) | (ft. - in.) | (ft. - in.) | (ft. - in.) | |||
12 | Douglas Fir-Larch | SS | 13-2 | 20-8 | Note a | Note a |
Douglas Fir-Larch | #1 | 12-8 | 19-11 | Note a | Note a | |
Douglas Fir-Larch | #2 | 12-5 | 19-6 | 25-8 | Note a | |
Douglas Fir-Larch | #3 | 10-10 | 15-10 | 20-1 | 24-6 | |
Hem-Fir | SS | 12-5 | 19-6 | 25-8 | Note a | |
Hem-Fir | #1 | 12-2 | 19-1 | 25-2 | Note a | |
Hem-Fir | #2 | 11-7 | 18-2 | 24-0 | Note a | |
Hem-Fir | #3 | 10-10 | 15-10 | 20-1 | 24-6 | |
Southern Pine | SS | 12-11 | 20-3 | Note a | Note a | |
Southern Pine | #1 | 12-8 | 19-11 | Note a | Note a | |
Southern Pine | #2 | 12-5 | 19-6 | 25-8 | Note a | |
Southern Pine | #3 | 11-6 | 17-0 | 21-8 | 25-7 | |
Spruce-Pine-Fir | SS | 12-2 | 19-1 | 25-2 | Note a | |
Spruce-Pine-Fir | #1 | 11-10 | 18-8 | 24-7 | Note a | |
Spruce-Pine-Fir | #2 | 11-10 | 18-8 | 24-7 | Note a | |
Spruce-Pine-Fir | #3 | 10-10 | 15-10 | 20-1 | 24-6 | |
16 | Douglas Fir-Larch | SS | 11-11 | 18-9 | 24-8 | Note a |
Douglas Fir-Larch | #1 | 11-6 | 18-1 | 23-10 | Note a | |
Douglas Fir-Larch | #2 | 11-3 | 17-8 | 23-0 | Note a | |
Douglas Fir-Larch | #3 | 9-5 | 13-9 | 17-5 | 21-3 | |
Hem-Fir | SS | 11-3 | 17-8 | 23-4 | Note a | |
Hem-Fir | #1 | 11-0 | 17-4 | 22-10 | Note a | |
Hem-Fir | #2 | 10-6 | 16-6 | 21-9 | Note a | |
Hem-Fir | #3 | 9-5 | 13-9 | 17-5 | 21-3 | |
Southern Pine | SS | 11-9 | 18-5 | 24-3 | Note a | |
Southern Pine | #1 | 11-6 | 18-1 | 23-1 | Note a | |
Southern Pine | #2 | 11-3 | 17-8 | 23-4 | Note a | |
Southern Pine | #3 | 10-0 | 14-9 | 18-9 | 22-2 | |
Spruce-Pine-Fir | SS | 11-0 | 17-4 | 22-10 | Note a | |
Spruce-Pine-Fir | #1 | 10-9 | 16-11 | 22-4 | Note a | |
Spruce-Pine-Fir | #2 | 10-9 | 16-11 | 22-4 | Note a | |
Spruce-Pine-Fir | #3 | 9-5 | 13-9 | 17-5 | 21-3 | |
19.2 | Douglas Fir-Larch | SS | 11-3 | 17-8 | 23-3 | Note a |
Douglas Fir-Larch | #1 | 10-10 | 17-0 | 22-5 | Note a | |
Douglas Fir-Larch | #2 | 10-7 | 16-7 | 21-0 | 25-8 | |
Douglas Fir-Larch | #3 | 8-7 | 12-6 | 15-10 | 19-5 | |
Hem-Fir | SS | 10-7 | 16-8 | 21-11 | Note a | |
Hem-Fir | #1 | 10-4 | 16-4 | 21-6 | Note a | |
Hem-Fir | #2 | 9-11 | 15-7 | 20-6 | 25-3 | |
Hem-Fir | #3 | 8-7 | 12-6 | 15-10 | 19-5 | |
Southern Pine | SS | 11-0 | 17-4 | 22-10 | Note a | |
Southern Pine | #1 | 10-10 | 17-0 | 22-5 | Note a | |
Southern Pine | #2 | 10-7 | 16-8 | 21-11 | Note a | |
Southern Pine | #3 | 9-1 | 13-6 | 17-2 | 20-3 | |
Spruce-Pine-Fir | SS | 10-4 | 16-4 | 21-6 | Note a | |
Spruce-Pine-Fir | #1 | 10-2 | 15-11 | 21-0 | 25-8 | |
Spruce-Pine-Fir | #2 | 10-2 | 15-11 | 21-0 | 25-8 | |
Spruce-Pine-Fir | #3 | 8-7 | 12-6 | 15-10 | 19-5 | |
24 | Douglas Fir-Larch | SS | 10-5 | 16-4 | 21-7 | Note a |
Douglas Fir-Larch | #1 | 10-0 | 15-9 | 20-1 | 24-6 | |
Douglas Fir-Larch | #2 | 9-10 | 14-10 | 18-9 | 22-11 | |
Douglas Fir-Larch | #3 | 7-8 | 11-2 | 14-2 | 17-4 | |
Hem-Fir | SS | 9-10 | 15-6 | 20-5 | Note a | |
Hem-Fir | #1 | 9-8 | 15-2 | 19-7 | 23-11 | |
Hem-Fir | #2 | 9-2 | 14-5 | 18-6 | 22-7 | |
Hem-Fir | #3 | 7-8 | 11-2 | 14-2 | 17-4 | |
Southern Pine | SS | 10-3 | 16-1 | 21-2 | Note a | |
Southern Pine | #1 | 10-0 | 15-9 | 20-10 | Note a | |
Southern Pine | #2 | 9-10 | 15-6 | 20-1 | 23-11 | |
Southern Pine | #3 | 8-2 | 12-0 | 15-4 | 18-1 | |
Spruce-Pine-Fir | SS | 9-8 | 15-2 | 19-11 | 25-5 | |
Spruce-Pine-Fir | #1 | 9-5 | 14-9 | 18-9 | 22-11 | |
Spruce-Pine-Fir | #2 | 9-5 | 14-9 | 18-9 | 22-11 | |
Spruce-Pine-Fir | #3 | 7-8 | 11-2 | 14-2 | 17-4 |
- Span exceeds 26 feet in length. Check sources for availability of lumber in lengths greater than 20 feet.
CEILING JOIST SPACING (inches) |
SPECIES AND GRADE | DEAD LOAD = 10 pounds per square foot | ||||
2 × 4 | 2 × 6 | 2 × 8 | 2 × 10 | |||
Maximum ceiling joist spans | ||||||
(ft. - in.) | (ft. - in.) | (ft. - in.) | (ft. - in.) | |||
12 | Douglas Fir-Larch | SS | 10-5 | 16-4 | 21-7 | Note a |
Douglas Fir-Larch | #1 | 10-0 | 15-9 | 20-1 | 24-6 | |
Douglas Fir-Larch | #2 | 9-10 | 14-10 | 18-9 | 22-11 | |
Douglas Fir-Larch | #3 | 7-8 | 11-2 | 14-2 | 17-4 | |
Hem-Fir | SS | 9-10 | 15-6 | 20-5 | Note a | |
Hem-Fir | #1 | 9-8 | 15-2 | 19-7 | 23-11 | |
Hem-Fir | #2 | 9-2 | 14-5 | 18-6 | 22-7 | |
Hem-Fir | #3 | 7-8 | 11-2 | 14-2 | 17-4 | |
Southern Pine | SS | 10-3 | 16-1 | 21-2 | Note a | |
Southern Pine | #1 | 10-0 | 15-9 | 20-10 | Note a | |
Southern Pine | #2 | 9-10 | 15-6 | 20-1 | 23-11 | |
Southern Pine | #3 | 8-2 | 12-0 | 15-4 | 18-1 | |
Spruce-Pine-Fir | SS | 9-8 | 15-2 | 19-11 | 25-5 | |
Spruce-Pine-Fir | #1 | 9-5 | 14-9 | 18-9 | 22-11 | |
Spruce-Pine-Fir | #2 | 9-5 | 14-9 | 18-9 | 22-11 | |
Spruce-Pine-Fir | #3 | 7-8 | 11-2 | 14-2 | 17-4 | |
16 | Douglas Fir-Larch | SS | 9-6 | 14-11 | 19-7 | 25-0 |
Douglas Fir-Larch | #1 | 9-1 | 13-9 | 17-5 | 21-3 | |
Douglas Fir-Larch | #2 | 8-9 | 12-10 | 16-3 | 19-10 | |
Douglas Fir-Larch | #3 | 6-8 | 9-8 | 12-4 | 15-0 | |
Hem-Fir | SS | 8-11 | 14-1 | 18-6 | 23-8 | |
Hem-Fir | #1 | 8-9 | 13-5 | 16-10 | 20-8 | |
Hem-Fir | #2 | 8-4 | 12-8 | 16-0 | 19-7 | |
Hem-Fir | #3 | 6-8 | 9-8 | 12-4 | 15-0 | |
Southern Pine | SS | 9-4 | 14-7 | 19-3 | 24-7 | |
Southern Pine | #1 | 9-1 | 14-4 | 18-11 | 23-1 | |
Southern Pine | #2 | 8-11 | 13-6 | 17-5 | 20-9 | |
Southern Pine | #3 | 7-1 | 10-5 | 13-3 | 15-8 | |
Spruce-Pine-Fir | SS | 8-9 | 13-9 | 18-1 | 23-1 | |
Spruce-Pine-Fir | #1 | 8-7 | 12-10 | 16-3 | 19-10 | |
Spruce-Pine-Fir | #2 | 8-7 | 12-10 | 16-3 | 19-10 | |
Spruce-Pine-Fir | #3 | 6-8 | 9-8 | 12-4 | 15-0 | |
19.2 | Douglas Fir-Larch | SS | 8-11 | 14-0 | 18-5 | 23-4 |
Douglas Fir-Larch | #1 | 8-7 | 12-6 | 15-10 | 19-5 | |
Douglas Fir-Larch | #2 | 8-0 | 11-9 | 14-10 | 18-2 | |
Douglas Fir-Larch | #3 | 6-1 | 8-10 | 11-3 | 13-8 | |
Hem-Fir | SS | 8-5 | 13-3 | 17-5 | 22-3 | |
Hem-Fir | #1 | 8-3 | 12-3 | 15-6 | 18-11 | |
Hem-Fir | #2 | 7-10 | 11-7 | 14-8 | 17-10 | |
Hem-Fir | #3 | 6-1 | 8-10 | 11-3 | 13-8 | |
Southern Pine | SS | 8-9 | 13-9 | 18-1 | 23-1 | |
Southern Pine | #1 | 8-7 | 13-6 | 17-9 | 21-1 | |
Southern Pine | #2 | 8-5 | 12-3 | 15-10 | 18-11 | |
Southern Pine | #3 | 6-5 | 9-6 | 12-1 | 14-4 | |
Spruce-Pine-Fir | SS | 8-3 | 12-11 | 17-1 | 21-8 | |
Spruce-Pine-Fir | #1 | 8-0 | 11-9 | 14-10 | 18-2 | |
Spruce-Pine-Fir | #2 | 8-0 | 11-9 | 14-10 | 18-2 | |
Spruce-Pine-Fir | #3 | 6-1 | 8-10 | 11-3 | 13-8 | |
24 | Douglas Fir-Larch | SS | 8-3 | 13-0 | 17-1 | 20-11 |
Douglas Fir-Larch | #1 | 7-8 | 11-2 | 14-2 | 17-4 | |
Douglas Fir-Larch | #2 | 7-2 | 10-6 | 13-3 | 16-3 | |
Douglas Fir-Larch | #3 | 5-5 | 7-11 | 10-0 | 12-3 | |
Hem-Fir | SS | 7-10 | 12-3 | 16-2 | 20-6 | |
Hem-Fir | #1 | 7-6 | 10-11 | 13-10 | 16-11 | |
Hem-Fir | #2 | 7-1 | 10-4 | 13-1 | 16-0 | |
Hem-Fir | #3 | 5-5 | 7-11 | 10-0 | 12-3 | |
Southern Pine | SS | 8-1 | 12-9 | 16-10 | 21-6 | |
Southern Pine | #1 | 8-0 | 12-6 | 15-10 | 18-10 | |
Southern Pine | #2 | 7-8 | 11-0 | 14-2 | 16-11 | |
Southern Pine | #3 | 5-9 | 8-6 | 10-10 | 12-10 | |
Spruce-Pine-Fir | SS | 7-8 | 12-0 | 15-10 | 19-5 | |
Spruce-Pine-Fir | #1 | 7-2 | 10-6 | 13-3 | 16-3 | |
Spruce-Pine-Fir | #2 | 7-2 | 10-6 | 13-3 | 16-3 | |
Spruce-Pine-Fir | #3 | 5-5 | 7-11 | 10-0 | 12-3 |
- Span exceeds 26 feet in length. Check sources for availability of lumber in lengths greater than 20 feet.
RAFTER SPACING (inches) |
SPECIES AND GRADE | DEAD LOAD = 10 pounds per square foot | DEAD LOAD = 20 pounds per square foot | |||||||||
2 × 4 | 2 × 6 | 2 × 8 | 2 × 10 | 2 × 12 | 2 × 4 | 2 × 6 | 2 × 8 | 2 × 10 | 2 × 12 | |||
Maximum rafter spans | ||||||||||||
(ft. - in.) | (ft. - in.) | (ft. - in.) | (ft. - in.) | (ft. - in.) | (ft. - in.) | (ft. - in.) | (ft. - in.) | (ft. - in.) | (ft. - in.) | |||
12 | Douglas Fir-Larch | SS | 11-6 | 18-0 | 23-9 | Note a | Note a | 11-6 | 18-0 | 23-5 | Note a | Note a |
Douglas Fir-Larch | #1 | 11-1 | 17-4 | 22-5 | Note a | Note a | 10-6 | 15-4 | 19-5 | 23-9 | Note a | |
Douglas Fir-Larch | #2 | 10-10 | 16-7 | 21-0 | 25-8 | Note a | 9-10 | 14-4 | 18-2 | 22-3 | 25-9 | |
Douglas Fir-Larch | #3 | 8-7 | 12-6 | 15-10 | 19-5 | 22-6 | 7-5 | 10-10 | 13-9 | 16-9 | 19-6 | |
Hem-Fir | SS | 10-10 | 17-0 | 22-5 | Note a | Note a | 10-10 | 17-0 | 22-5 | Note a | Note a | |
Hem-Fir | #1 | 10-7 | 16-8 | 21-10 | Note a | Note a | 10-3 | 14-11 | 18-11 | 23-2 | Note a | |
Hem-Fir | #2 | 10-1 | 15-11 | 20-8 | 25-3 | Note a | 9-8 | 14-2 | 17-11 | 21-11 | 25-5 | |
Hem-Fir | #3 | 8-7 | 12-6 | 15-10 | 19-5 | 22-6 | 7-5 | 10-10 | 13-9 | 16-9 | 19-6 | |
Southern Pine | SS | 11-3 | 17-8 | 23-4 | Note a | Note a | 11-3 | 17-8 | 23-4 | Note a | Note a | |
Southern Pine | #1 | 11-1 | 17-4 | 22-11 | Note a | Note a | 11-1 | 17-3 | 21-9 | 25-10 | Note a | |
Southern Pine | #2 | 10-10 | 17-0 | 22-5 | Note a | Note a | 10-6 | 15-1 | 19-5 | 23-2 | Note a | |
Southern Pine | #3 | 9-1 | 13-6 | 17-2 | 20-3 | 24-1 | 7-11 | 11-8 | 14-10 | 17-6 | 20-11 | |
Spruce-Pine-Fir | SS | 10-7 | 16-8 | 21-11 | Note a | Note a | 10-7 | 16-8 | 21-9 | Note a | Note a | |
Spruce-Pine-Fir | #1 | 10-4 | 16-3 | 21-0 | 25-8 | Note a | 9-10 | 14-4 | 18-2 | 22-3 | 25-9 | |
Spruce-Pine-Fir | #2 | 10-4 | 16-3 | 21-0 | 25-8 | Note a | 9-10 | 14-4 | 18-2 | 22-3 | 25-9 | |
Spruce-Pine-Fir | #3 | 8-7 | 12-6 | 15-10 | 19-5 | 22-6 | 7-5 | 10-10 | 13-9 | 16-9 | 19-6 | |
16 | Douglas Fir-Larch | SS | 10-5 | 16-4 | 21-7 | Note a | Note a | 10-5 | 16-0 | 20-3 | 24-9 | Note a |
Douglas Fir-Larch | #1 | 10-0 | 15-4 | 19-5 | 23-9 | Note a | 9-1 | 13-3 | 16-10 | 20-7 | 23-10 | |
Douglas Fir-Larch | #2 | 9-10 | 14-4 | 18-2 | 22-3 | 25-9 | 8-6 | 12-5 | 15-9 | 19-3 | 22-4 | |
Douglas Fir-Larch | #3 | 7-5 | 10-10 | 13-9 | 16-9 | 19-6 | 6-5 | 9-5 | 11-11 | 14-6 | 16-10 | |
Hem-Fir | SS | 9-10 | 15-6 | 20-5 | Note a | Note a | 9-10 | 15-6 | 19-11 | 24-4 | Note a | |
Hem-Fir | #1 | 9-8 | 14-11 | 18-11 | 23-2 | Note a | 8-10 | 12-11 | 16-5 | 20-0 | 23-3 | |
Hem-Fir | #2 | 9-2 | 14-2 | 17-11 | 21-11 | 25-5 | 8-5 | 12-3 | 15-6 | 18-11 | 22-0 | |
Hem-Fir | #3 | 7-5 | 10-10 | 13-9 | 16-9 | 19-6 | 6-5 | 9-5 | 11-11 | 14-6 | 16-10 | |
Southern Pine | SS | 10-3 | 16-1 | 21-2 | Note a | Note a | 10-3 | 16-1 | 21-2 | Note a | Note a | |
Southern Pine | #1 | 10-0 | 15-9 | 20-10 | 25-10 | Note a | 10-0 | 15-0 | 18-10 | 22-4 | Note a | |
Southern Pine | #2 | 9-10 | 15-1 | 19-5 | 23-2 | Note a | 9-1 | 13-0 | 16-10 | 20-1 | 23-7 | |
Southern Pine | #3 | 7-11 | 11-8 | 14-10 | 17-6 | 20-11 | 6-10 | 10-1 | 12-10 | 15-2 | 18-1 | |
Spruce-Pine-Fir | SS | 9-8 | 15-2 | 19-11 | 25-5 | Note a | 9-8 | 14-10 | 18-10 | 23-0 | Note a | |
Spruce-Pine-Fir | #1 | 9-5 | 14-4 | 18-2 | 22-3 | 25-9 | 8-6 | 12-5 | 15-9 | 19-3 | 22-4 | |
Spruce-Pine-Fir | #2 | 9-5 | 14-4 | 18-2 | 22-3 | 25-9 | 8-6 | 12-5 | 15-9 | 19-3 | 22-4 | |
Spruce-Pine-Fir | #3 | 7-5 | 10-10 | 13-9 | 16-9 | 19-6 | 6-5 | 9-5 | 11-11 | 14-6 | 16-10 | |
19.2 | Douglas Fir-Larch | SS | 9-10 | 15-5 | 20-4 | 25-11 | Note a | 9-10 | 14-7 | 18-6 | 22-7 | Note a |
Douglas Fir-Larch | #1 | 9-5 | 14-0 | 17-9 | 21-8 | 25-2 | 8-4 | 12-2 | 15-4 | 18-9 | 21-9 | |
Douglas Fir-Larch | #2 | 8-11 | 13-1 | 16-7 | 20-3 | 23-6 | 7-9 | 11-4 | 14-4 | 17-7 | 20-4 | |
Douglas Fir-Larch | #3 | 6-9 | 9-11 | 12-7 | 15-4 | 17-9 | 5-10 | 8-7 | 10-10 | 13-3 | 15-5 | |
Hem-Fir | SS | 9-3 | 14-7 | 19-2 | 24-6 | Note a | 9-3 | 14-4 | 18-2 | 22-3 | 25-9 | |
Hem-Fir | #1 | 9-1 | 13-8 | 17-4 | 21-1 | 24-6 | 8-1 | 11-10 | 15-0 | 18-4 | 21-3 | |
Hem-Fir | #2 | 8-8 | 12-11 | 16-4 | 20-0 | 23-2 | 7-8 | 11-2 | 14-2 | 17-4 | 20-1 | |
Hem-Fir | #3 | 6-9 | 9-11 | 12-7 | 15-4 | 17-9 | 5-10 | 8-7 | 10-10 | 13-3 | 15-5 | |
Southern Pine | SS | 9-8 | 15-2 | 19-11 | 25-5 | Note a | 9-8 | 15-2 | 19-11 | 25-5 | Note a | |
Southern Pine | #1 | 9-5 | 14-10 | 19-7 | 23-7 | Note a | 9-3 | 13-8 | 17-2 | 20-5 | 24-4 | |
Southern Pine | #2 | 9-3 | 13-9 | 17-9 | 21-2 | 24-10 | 8-4 | 11-11 | 15-4 | 18-4 | 21-6 | |
Southern Pine | #3 | 7-3 | 10-8 | 13-7 | 16-0 | 19-1 | 6-3 | 9-3 | 11-9 | 13-10 | 16-6 | |
Spruce-Pine-Fir | SS | 9-1 | 14-3 | 18-9 | 23-11 | Note a | 9-1 | 13-7 | 17-2 | 21-0 | 24-4 | |
Spruce-Pine-Fir | #1 | 8-10 | 13-1 | 16-7 | 20-3 | 23-6 | 7-9 | 11-4 | 14-4 | 17-7 | 20-4 | |
Spruce-Pine-Fir | #2 | 8-10 | 13-1 | 16-7 | 20-3 | 23-6 | 7-9 | 11-4 | 14-4 | 17-7 | 20-4 | |
Spruce-Pine-Fir | #3 | 6-9 | 9-11 | 12-7 | 15-4 | 17-9 | 5-10 | 8-7 | 10-10 | 13-3 | 15-5 | |
24 | Douglas Fir-Larch | SS | 9-1 | 14-4 | 18-10 | 23-4 | Note a | 8-11 | 13-1 | 16-7 | 20-3 | 23-5 |
Douglas Fir-Larch | #1 | 8-7 | 12-6 | 15-10 | 19-5 | 22-6 | 7-5 | 10-10 | 13-9 | 16-9 | 19-6 | |
Douglas Fir-Larch | #2 | 8-0 | 11-9 | 14-10 | 18-2 | 21-0 | 6-11 | 10-2 | 12-10 | 15-8 | 18-3 | |
Douglas Fir-Larch | #3 | 6-1 | 8-10 | 11-3 | 13-8 | 15-11 | 5-3 | 7-8 | 9-9 | 11-10 | 13-9 | |
Hem-Fir | SS | 8-7 | 13-6 | 17-10 | 22-9 | Note a | 8-7 | 12-10 | 16-3 | 19-10 | 23-0 | |
Hem-Fir | #1 | 8-4 | 12-3 | 15-6 | 18-11 | 21-11 | 7-3 | 10-7 | 13-5 | 16-4 | 19-0 | |
Hem-Fir | #2 | 7-11 | 11-7 | 14-8 | 17-10 | 20-9 | 6-10 | 10-0 | 12-8 | 15-6 | 17-11 | |
Hem-Fir | #3 | 6-1 | 8-10 | 11-3 | 13-8 | 15-11 | 5-3 | 7-8 | 9-9 | 11-10 | 13-9 | |
Southern Pine | SS | 8-11 | 14-1 | 18-6 | 23-8 | Note a | 8-11 | 14-1 | 18-6 | 22-11 | Note a | |
Southern Pine | #1 | 8-9 | 13-9 | 17-9 | 21-1 | 25-2 | 8-3 | 12-3 | 15-4 | 18-3 | 21-9 | |
Southern Pine | #2 | 8-7 | 12-3 | 15-10 | 18-11 | 22-2 | 7-5 | 10-8 | 13-9 | 16-5 | 19-3 | |
Southern Pine | #3 | 6-5 | 9-6 | 12-1 | 14-4 | 17-1 | 5-7 | 8-3 | 10-6 | 12-5 | 14-9 | |
Spruce-Pine-Fir | SS | 8-5 | 13-3 | 17-5 | 21-8 | 25-2 | 8-4 | 12-2 | 15-4 | 18-9 | 21-9 | |
Spruce-Pine-Fir | #1 | 8-0 | 11-9 | 14-10 | 18-2 | 21-0 | 6-11 | 10-2 | 12-10 | 15-8 | 18-3 | |
Spruce-Pine-Fir | #2 | 8-0 | 11-9 | 14-10 | 18-2 | 21-0 | 6-11 | 10-2 | 12-10 | 15-8 | 18-3 | |
Spruce-Pine-Fir | #3 | 6-1 | 8-10 | 11-3 | 13-8 | 15-11 | 5-3 | 7-8 | 9-9 | 11-10 | 13-9 |
- Span exceeds 26 feet in length. Check sources for availability of lumber in lengths greater than 20 feet.
RAFTER SPACING (inches) |
SPECIES AND GRADE | DEAD LOAD = 10 pounds per square foot | DEAD LOAD = 20 pounds per square foot | |||||||||
2 × 4 | 2 × 6 | 2 × 8 | 2 × 10 | 2 × 12 | 2 × 4 | 2 × 6 | 2 × 8 | 2 × 10 | 2 × 12 | |||
Maximum rafter spans | ||||||||||||
(ft. - in.) | (ft. - in.) | (ft. - in.) | (ft. - in.) | (ft. - in.) | (ft. - in.) | (ft. - in.) | (ft. - in.) | (ft. - in.) | (ft. - in.) | |||
12 | Douglas Fir-Larch | SS | 10-5 | 16-4 | 21-7 | Note a | Note a | 10-5 | 16-4 | 21-7 | Note a | Note a |
Douglas Fir-Larch | #1 | 10-0 | 15-9 | 20-10 | Note a | Note a | 10-0 | 15-4 | 19-5 | 23-9 | Note a | |
Douglas Fir-Larch | #2 | 9-10 | 15-6 | 20-5 | 25-8 | Note a | 9-10 | 14-4 | 18-2 | 22-3 | 25-9 | |
Douglas Fir-Larch | #3 | 8-7 | 12-6 | 15-10 | 19-5 | 22-6 | 7-5 | 10-10 | 13-9 | 16-9 | 19-6 | |
Hem-Fir | SS | 9-10 | 15-6 | 20-5 | Note a | Note a | 9-10 | 15-6 | 20-5 | Note a | Note a | |
Hem-Fir | #1 | 9-8 | 15-2 | 19-11 | 25-5 | Note a | 9-8 | 14-11 | 18-11 | 23-2 | Note a | |
Hem-Fir | #2 | 9-2 | 14-5 | 19-0 | 24-3 | Note a | 9-2 | 14-2 | 17-11 | 21-11 | 25-5 | |
Hem-Fir | #3 | 8-7 | 12-6 | 15-10 | 19-5 | 22-6 | 7-5 | 10-10 | 13-9 | 16-9 | 19-6 | |
Southern Pine | SS | 10-3 | 16-1 | 21-2 | Note a | Note a | 10-3 | 16-1 | 21-2 | Note a | Note a | |
Southern Pine | #1 | 10-0 | 15-9 | 20-10 | Note a | Note a | 10-0 | 15-9 | 20-10 | 25-10 | Note a | |
Southern Pine | #2 | 9-10 | 15-6 | 20-5 | Note a | Note a | 9-10 | 15-1 | 19-5 | 23-2 | Note a | |
Southern Pine | #3 | 9-1 | 13-6 | 17-2 | 20-3 | 24-1 | 7-11 | 11-8 | 14-10 | 17-6 | 20-11 | |
Spruce-Pine-Fir | SS | 9-8 | 15-2 | 19-11 | 25-5 | Note a | 9-8 | 15-2 | 19-11 | 25-5 | Note a | |
Spruce-Pine-Fir | #1 | 9-5 | 14-9 | 19-6 | 24-10 | Note a | 9-5 | 14-4 | 18-2 | 22-3 | 25-9 | |
Spruce-Pine-Fir | #2 | 9-5 | 14-9 | 19-6 | 24-10 | Note a | 9-5 | 14-4 | 18-2 | 22-3 | 25-9 | |
Spruce-Pine-Fir | #3 | 8-7 | 12-6 | 15-10 | 19-5 | 22-6 | 7-5 | 10-10 | 13-9 | 16-9 | 19-6 | |
16 | Douglas Fir-Larch | SS | 9-6 | 14-11 | 19-7 | 25-0 | Note a | 9-6 | 14-11 | 19-7 | 24-9 | Note a |
Douglas Fir-Larch | #1 | 9-1 | 14-4 | 18-11 | 23-9 | Note a | 9-1 | 13-3 | 16-10 | 20-7 | 23-10 | |
Douglas Fir-Larch | #2 | 8-11 | 14-1 | 18-2 | 22-3 | 25-9 | 8-6 | 12-5 | 15-9 | 19-3 | 22-4 | |
Douglas Fir-Larch | #3 | 7-5 | 10-10 | 13-9 | 16-9 | 19-6 | 6-5 | 9-5 | 11-11 | 14-6 | 16-10 | |
Hem-Fir | SS | 8-11 | 14-1 | 18-6 | 23-8 | Note a | 8-11 | 14-1 | 18-6 | 23-8 | Note a | |
Hem-Fir | #1 | 8-9 | 13-9 | 18-1 | 23-1 | Note a | 8-9 | 12-11 | 16-5 | 20-0 | 23-3 | |
Hem-Fir | #2 | 8-4 | 13-1 | 17-3 | 21-11 | 25-5 | 8-4 | 12-3 | 15-6 | 18-11 | 22-0 | |
Hem-Fir | #3 | 7-5 | 10-10 | 13-9 | 16-9 | 19-6 | 6-5 | 9-5 | 11-11 | 14-6 | 16-10 | |
Southern Pine | SS | 9-4 | 14-7 | 19-3 | 24-7 | Note a | 9-4 | 14-7 | 19-3 | 24-7 | Note a | |
Southern Pine | #1 | 9-1 | 14-4 | 18-11 | 24-1 | Note a | 9-1 | 14-4 | 18-10 | 22-4 | Note a | |
Southern Pine | #2 | 8-11 | 14-1 | 18-6 | 23-2 | Note a | 8-11 | 13-0 | 16-10 | 20-1 | 23-7 | |
Southern Pine | #3 | 7-11 | 11-8 | 14-10 | 17-6 | 20-11 | 6-10 | 10-1 | 12-10 | 15-2 | 18-1 | |
Spruce-Pine-Fir | SS | 8-9 | 13-9 | 18-1 | 23-1 | Note a | 8-9 | 13-9 | 18-1 | 23-0 | Note a | |
Spruce-Pine-Fir | #1 | 8-7 | 13-5 | 17-9 | 22-3 | 25-9 | 8-6 | 12-5 | 15-9 | 19-3 | 22-4 | |
Spruce-Pine-Fir | #2 | 8-7 | 13-5 | 17-9 | 22-3 | 25-9 | 8-6 | 12-5 | 15-9 | 19-3 | 22-4 | |
Spruce-Pine-Fir | #3 | 7-5 | 10-10 | 13-9 | 16-9 | 19-6 | 6-5 | 9-5 | 11-11 | 14-6 | 16-10 | |
19.2 | Douglas Fir-Larch | SS | 8-11 | 14-0 | 18-5 | 23-7 | Note a | 8-11 | 14-0 | 18-5 | 22-7 | Note a |
Douglas Fir-Larch | #1 | 8-7 | 13-6 | 17-9 | 21-8 | 25-2 | 8-4 | 12-2 | 15-4 | 18-9 | 21-9 | |
Douglas Fir-Larch | #2 | 8-5 | 13-1 | 16-7 | 20-3 | 23-6 | 7-9 | 11-4 | 14-4 | 17-7 | 20-4 | |
Douglas Fir-Larch | #3 | 6-9 | 9-11 | 12-7 | 15-4 | 17-9 | 5-10 | 8-7 | 10-10 | 13-3 | 15-5 | |
Hem-Fir | SS | 8-5 | 13-3 | 17-5 | 22-3 | Note a | 8-5 | 13-3 | 17-5 | 22-3 | 25-9 | |
Hem-Fir | #1 | 8-3 | 12-11 | 17-1 | 21-1 | 24-6 | 8-1 | 11-10 | 15-0 | 18-4 | 21-3 | |
Hem-Fir | #2 | 7-10 | 12-4 | 16-3 | 20-0 | 23-2 | 7-8 | 11-2 | 14-2 | 17-4 | 20-1 | |
Hem-Fir | #3 | 6-9 | 9-11 | 12-7 | 15-4 | 17-9 | 5-10 | 8-7 | 10-10 | 13-3 | 15-5 | |
Southern Pine | SS | 8-9 | 13-9 | 18-1 | 23-1 | Note a | 8-9 | 13-9 | 18-1 | 23-1 | Note a | |
Southern Pine | #1 | 8-7 | 13-6 | 17-9 | 22-8 | Note a | 8-7 | 13-6 | 17-2 | 20-5 | 24-4 | |
Southern Pine | #2 | 8-5 | 13-3 | 17-5 | 21-2 | 24-10 | 8-4 | 11-11 | 15-4 | 18-4 | 21-6 | |
Southern Pine | #3 | 7-3 | 10-8 | 13-7 | 16-0 | 19-1 | 6-3 | 9-3 | 11-9 | 13-10 | 16-6 | |
Spruce-Pine-Fir | SS | 8-3 | 12-11 | 17-1 | 21-9 | Note a | 8-3 | 12-11 | 17-1 | 21-0 | 24-4 | |
Spruce-Pine-Fir | #1 | 8-1 | 12-8 | 16-7 | 20-3 | 23-6 | 7-9 | 11-4 | 14-4 | 17-7 | 20-4 | |
Spruce-Pine-Fir | #2 | 8-1 | 12-8 | 16-7 | 20-3 | 23-6 | 7-9 | 11-4 | 14-4 | 17-7 | 20-4 | |
Spruce-Pine-Fir | #3 | 6-9 | 9-11 | 12-7 | 15-4 | 17-9 | 5-10 | 8-7 | 10-10 | 13-3 | 15-5 | |
24 | Douglas Fir-Larch | SS | 8-3 | 13-0 | 17-2 | 21-10 | Note a | 8-3 | 13-0 | 16-7 | 20-3 | 23-5 |
Douglas Fir-Larch | #1 | 8-0 | 12-6 | 15-10 | 19-5 | 22-6 | 7-5 | 10-10 | 13-9 | 16-9 | 19-6 | |
Douglas Fir-Larch | #2 | 7-10 | 11-9 | 14-10 | 18-2 | 21-0 | 6-11 | 10-2 | 12-10 | 15-8 | 18-3 | |
Douglas Fir-Larch | #3 | 6-1 | 8-10 | 11-3 | 13-8 | 15-11 | 5-3 | 7-8 | 9-9 | 11-10 | 13-9 | |
Hem-Fir | SS | 7-10 | 12-3 | 16-2 | 20-8 | 25-1 | 7-10 | 12-3 | 16-2 | 19-10 | 23-0 | |
Hem-Fir | #1 | 7-8 | 12-0 | 15-6 | 18-11 | 21-11 | 7-3 | 10-7 | 13-5 | 16-4 | 19-0 | |
Hem-Fir | #2 | 7-3 | 11-5 | 14-8 | 17-10 | 20-9 | 6-10 | 10-0 | 12-8 | 15-6 | 17-11 | |
Hem-Fir | #3 | 6-1 | 8-10 | 11-3 | 13-8 | 15-11 | 5-3 | 7-8 | 9-9 | 11-10 | 13-9 | |
Southern Pine | SS | 8-1 | 12-9 | 16-10 | 21-6 | Note a | 8-1 | 12-9 | 16-10 | 21-6 | Note a | |
Southern Pine | #1 | 8-0 | 12-6 | 16-6 | 21-1 | 25-2 | 8-0 | 12-3 | 15-4 | 18-3 | 21-9 | |
Southern Pine | #2 | 7-10 | 12-3 | 15-10 | 18-11 | 22-2 | 7-5 | 10-8 | 13-9 | 16-5 | 19-3 | |
Southern Pine | #3 | 6-5 | 9-6 | 12-1 | 14-4 | 17-1 | 5-7 | 8-3 | 10-6 | 12-5 | 14-9 | |
Spruce-Pine-Fir | SS | 7-8 | 12-0 | 15-10 | 20-2 | 24-7 | 7-8 | 12-0 | 15-4 | 18-9 | 21-9 | |
Spruce-Pine-Fir | #1 | 7-6 | 11-9 | 14-10 | 18-2 | 21-0 | 6-11 | 10-2 | 12-10 | 15-8 | 18-3 | |
Spruce-Pine-Fir | #2 | 7-6 | 11-9 | 14-10 | 18-2 | 21-0 | 6-11 | 10-2 | 12-10 | 15-8 | 18-3 | |
Spruce-Pine-Fir | #3 | 6-1 | 8-10 | 11-3 | 13-8 | 15-11 | 5-3 | 7-8 | 9-9 | 11-10 | 13-9 |
- Span exceeds 26 feet in length. Check sources for availability of lumber in lengths greater than 20 feet.
RAFTER SPACING (inches) |
SPECIES AND GRADE | DEAD LOAD = 10 pounds per square foot | DEAD LOAD = 20 pounds per square foot | |||||||||
2 × 4 | 2 × 6 | 2 × 8 | 2 × 10 | 2 × 12 | 2 × 4 | 2 × 6 | 2 × 8 | 2 × 10 | 2 × 12 | |||
Maximum rafter spans | ||||||||||||
(ft. - in.) | (ft. - in.) | (ft. - in.) | (ft. - in.) | (ft. - in.) | (ft. - in.) | (ft. - in.) | (ft. - in.) | (ft. - in.) | (ft. - in.) | |||
12 | Douglas Fir-Larch | SS | 10-0 | 15-9 | 20-9 | Note a | Note a | 10-0 | 15-9 | 20-1 | 24-6 | Note a |
Douglas Fir-Larch | #1 | 9-8 | 14-9 | 18-8 | 22-9 | Note a | 9-0 | 13-2 | 16-8 | 20-4 | 23-7 | |
Douglas Fir-Larch | #2 | 9-5 | 13-9 | 17-5 | 21-4 | 24-8 | 8-5 | 12-4 | 15-7 | 19-1 | 22-1 | |
Douglas Fir-Larch | #3 | 7-1 | 10-5 | 13-2 | 16-1 | 18-8 | 6-4 | 9-4 | 11-9 | 14-5 | 16-8 | |
Hem-Fir | SS | 9-6 | 14-10 | 19-7 | 25-0 | Note a | 9-6 | 14-10 | 19-7 | 24-1 | Note a | |
Hem-Fir | #1 | 9-3 | 14-4 | 18-2 | 22-2 | 25-9 | 8-9 | 12-10 | 16-3 | 19-10 | 23-0 | |
Hem-Fir | #2 | 8-10 | 13-7 | 17-2 | 21-0 | 24-4 | 8-4 | 12-2 | 15-4 | 18-9 | 21-9 | |
Hem-Fir | #3 | 7-1 | 10-5 | 13-2 | 16-1 | 18-8 | 6-4 | 9-4 | 11-9 | 14-5 | 16-8 | |
Southern Pine | SS | 9-10 | 15-6 | 20-5 | Note a | Note a | 9-10 | 15-6 | 20-5 | Note a | Note a | |
Southern Pine | #1 | 9-8 | 15-2 | 20-0 | 24-9 | Note a | 9-8 | 14-10 | 18-8 | 22-2 | Note a | |
Southern Pine | #2 | 9-6 | 14-5 | 18-8 | 22-3 | Note a | 9-0 | 12-11 | 16-8 | 19-11 | 23-4 | |
Southern Pine | #3 | 7-7 | 11-2 | 14-3 | 16-10 | 20-0 | 6-9 | 10-0 | 12-9 | 15-1 | 17-11 | |
Spruce-Pine-Fir | SS | 9-3 | 14-7 | 19-2 | 24-6 | Note a | 9-3 | 14-7 | 18-8 | 22-9 | Note a | |
Spruce-Pine-Fir | #1 | 9-1 | 13-9 | 17-5 | 21-4 | 24-8 | 8-5 | 12-4 | 15-7 | 19-1 | 22-1 | |
Spruce-Pine-Fir | #2 | 9-1 | 13-9 | 17-5 | 21-4 | 24-8 | 8-5 | 12-4 | 15-7 | 19-1 | 22-1 | |
Spruce-Pine-Fir | #3 | 7-1 | 10-5 | 13-2 | 16-1 | 18-8 | 6-4 | 9-4 | 11-9 | 14-5 | 16-8 | |
16 | Douglas Fir-Larch | SS | 9-1 | 14-4 | 18-10 | 23-9 | Note a | 9-1 | 13-9 | 17-5 | 21-3 | 24-8 |
Douglas Fir-Larch | #1 | 8-9 | 12-9 | 16-2 | 19-9 | 22-10 | 7-10 | 11-5 | 14-5 | 17-8 | 20-5 | |
Douglas Fir-Larch | #2 | 8-2 | 11-11 | 15-1 | 18-5 | 21-5 | 7-3 | 10-8 | 13-6 | 16-6 | 19-2 | |
Douglas Fir-Larch | #3 | 6-2 | 9-0 | 11-5 | 13-11 | 16-2 | 5-6 | 8-1 | 10-3 | 12-6 | 14-6 | |
Hem-Fir | SS | 8-7 | 13-6 | 17-10 | 22-9 | Note a | 8-7 | 13-6 | 17-1 | 20-10 | 24-2 | |
Hem-Fir | #1 | 8-5 | 12-5 | 15-9 | 19-3 | 22-3 | 7-7 | 11-1 | 14-1 | 17-2 | 19-11 | |
Hem-Fir | #2 | 8-0 | 11-9 | 14-11 | 18-2 | 21-1 | 7-2 | 10-6 | 13-4 | 16-3 | 18-10 | |
Hem-Fir | #3 | 6-2 | 9-0 | 11-5 | 13-11 | 16-2 | 5-6 | 8-1 | 10-3 | 12-6 | 14-6 | |
Southern Pine | SS | 8-11 | 14-1 | 18-6 | 23-8 | Note a | 8-11 | 14-1 | 18-6 | 23-8 | Note a | |
Southern Pine | #1 | 8-9 | 13-9 | 18-1 | 21-5 | 25-7 | 8-8 | 12-10 | 16-2 | 19-2 | 22-10 | |
Southern Pine | #2 | 8-7 | 12-6 | 16-2 | 19-3 | 22-7 | 7-10 | 11-2 | 14-5 | 17-3 | 20-2 | |
Southern Pine | #3 | 6-7 | 9-8 | 12-4 | 14-7 | 17-4 | 5-10 | 8-8 | 11-0 | 13-0 | 15-6 | |
Spruce-Pine-Fir | SS | 8-5 | 13-3 | 17-5 | 22-1 | 25-7 | 8-5 | 12-9 | 16-2 | 19-9 | 22-10 | |
Spruce-Pine-Fir | #1 | 8-2 | 11-11 | 15-1 | 18-5 | 21-5 | 7-3 | 10-8 | 13-6 | 16-6 | 19-2 | |
Spruce-Pine-Fir | #2 | 8-2 | 11-11 | 15-1 | 18-5 | 21-5 | 7-3 | 10-8 | 13-6 | 16-6 | 19-2 | |
Spruce-Pine-Fir | #3 | 6-2 | 9-0 | 11-5 | 13-11 | 16-2 | 5-6 | 8-1 | 10-3 | 12-6 | 14-6 | |
19.2 | Douglas Fir-Larch | SS | 8-7 | 13-6 | 17-9 | 21-8 | 25-2 | 8-7 | 12-6 | 15-10 | 19-5 | 22-6 |
Douglas Fir-Larch | #1 | 7-11 | 11-8 | 14-9 | 18-0 | 20-11 | 7-1 | 10-5 | 13-2 | 16-1 | 18-8 | |
Douglas Fir-Larch | #2 | 7-5 | 10-11 | 13-9 | 16-10 | 19-6 | 6-8 | 9-9 | 12-4 | 15-1 | 17-6 | |
Douglas Fir-Larch | #3 | 5-7 | 8-3 | 10-5 | 12-9 | 14-9 | 5-0 | 7-4 | 9-4 | 11-5 | 13-2 | |
Hem-Fir | SS | 8-1 | 12-9 | 16-9 | 21-4 | 24-8 | 8-1 | 12-4 | 15-7 | 19-1 | 22-1 | |
Hem-Fir | #1 | 7-9 | 11-4 | 14-4 | 17-7 | 20-4 | 6-11 | 10-2 | 12-10 | 15-8 | 18-2 | |
Hem-Fir | #2 | 7-4 | 10-9 | 13-7 | 16-7 | 19-3 | 6-7 | 9-7 | 12-2 | 14-10 | 17-3 | |
Hem-Fir | #3 | 5-7 | 8-3 | 10-5 | 12-9 | 14-9 | 5-0 | 7-4 | 9-4 | 11-5 | 13-2 | |
Southern Pine | SS | 8-5 | 13-3 | 17-5 | 22-3 | Note a | 8-5 | 13-3 | 17-5 | 22-0 | 25-9 | |
Southern Pine | #1 | 8-3 | 13-0 | 16-6 | 19-7 | 23-4 | 7-11 | 11-9 | 14-9 | 17-6 | 20-11 | |
Southern Pine | #2 | 7-11 | 11-5 | 14-9 | 17-7 | 20-7 | 7-1 | 10-2 | 13-2 | 15-9 | 18-5 | |
Southern Pine | #3 | 6-0 | 8-10 | 11-3 | 13-4 | 15-10 | 5-4 | 7-11 | 10-1 | 11-11 | 14-2 | |
Spruce-Pine-Fir | SS | 7-11 | 12-5 | 16-5 | 20-2 | 23-4 | 7-11 | 11-8 | 14-9 | 18-0 | 20-11 | |
Spruce-Pine-Fir | #1 | 7-5 | 10-11 | 13-9 | 16-10 | 19-6 | 6-8 | 9-9 | 12-4 | 15-1 | 17-6 | |
Spruce-Pine-Fir | #2 | 7-5 | 10-11 | 13-9 | 16-10 | 19-6 | 6-8 | 9-9 | 12-4 | 15-1 | 17-6 | |
Spruce-Pine-Fir | #3 | 5-7 | 8-3 | 10-5 | 12-9 | 14-9 | 5-0 | 7-4 | 9-4 | 11-5 | 13-2 | |
24 | Douglas Fir-Larch | SS | 7-11 | 12-6 | 15-10 | 19-5 | 22-6 | 7-8 | 11-3 | 14-2 | 17-4 | 20-1 |
Douglas Fir-Larch | #1 | 7-1 | 10-5 | 13-2 | 16-1 | 18-8 | 6-4 | 9-4 | 11-9 | 14-5 | 16-8 | |
Douglas Fir-Larch | #2 | 6-8 | 9-9 | 12-4 | 15-1 | 17-6 | 5-11 | 8-8 | 11-0 | 13-6 | 15-7 | |
Douglas Fir-Larch | #3 | 5-0 | 7-4 | 9-4 | 11-5 | 13-2 | 4-6 | 6-7 | 8-4 | 10-2 | 11-10 | |
Hem-Fir | SS | 7-6 | 11-10 | 15-7 | 19-1 | 22-1 | 7-6 | 11-0 | 13-11 | 17-0 | 19-9 | |
Hem-Fir | #1 | 6-11 | 10-2 | 12-10 | 15-8 | 18-2 | 6-2 | 9-1 | 11-6 | 14-0 | 16-3 | |
Hem-Fir | #2 | 6-7 | 9-7 | 12-2 | 14-10 | 17-3 | 5-10 | 8-7 | 10-10 | 13-3 | 15-5 | |
Hem-Fir | #3 | 5-0 | 7-4 | 9-4 | 11-5 | 13-2 | 4-6 | 6-7 | 8-4 | 10-2 | 11-10 | |
Southern Pine | SS | 7-10 | 12-3 | 16-2 | 20-8 | 25-1 | 7-10 | 12-3 | 16-2 | 19-8 | 23-0 | |
Southern Pine | #1 | 7-8 | 11-9 | 14-9 | 17-6 | 20-11 | 7-1 | 10-6 | 13-2 | 15-8 | 18-8 | |
Southern Pine | #2 | 7-1 | 10-2 | 13-2 | 15-9 | 18-5 | 6-4 | 9-2 | 11-9 | 14-1 | 16-6 | |
Southern Pine | #3 | 5-4 | 7-11 | 10-1 | 11-11 | 14-2 | 4-9 | 7-1 | 9-0 | 10-8 | 12-8 | |
Spruce-Pine-Fir | SS | 7-4 | 11-7 | 14-9 | 18-0 | 20-11 | 7-1 | 10-5 | 13-2 | 16-1 | 18-8 | |
Spruce-Pine-Fir | #1 | 6-8 | 9-9 | 12-4 | 15-1 | 17-6 | 5-11 | 8-8 | 11-0 | 13-6 | 15-7 | |
Spruce-Pine-Fir | #2 | 6-8 | 9-9 | 12-4 | 15-1 | 17-6 | 5-11 | 8-8 | 11-0 | 13-6 | 15-7 | |
Spruce-Pine-Fir | #3 | 5-0 | 7-4 | 9-4 | 11-5 | 13-2 | 4-6 | 6-7 | 8-4 | 10-2 | 11-10 |
- Span exceeds 26 feet in length. Check sources for availability of lumber in lengths greater than 20 feet.
RAFTER SPACING (inches) |
SPECIES AND GRADE | DEAD LOAD = 10 pounds per square foot | DEAD LOAD = 20 pounds per square foot | |||||||||
2 × 4 | 2 × 6 | 2 × 8 | 2 × 10 | 2 × 12 | 2 × 4 | 2 × 6 | 2 × 8 | 2 × 10 | 2 × 12 | |||
Maximum rafter spans | ||||||||||||
(ft. - in.) | (ft. - in.) | (ft. - in.) | (ft. - in.) | (ft. - in.) | (ft. - in.) | (ft. - in.) | (ft. - in.) | (ft. - in.) | (ft. - in.) | |||
12 | Douglas Fir-Larch | SS | 8-5 | 13-3 | 17-6 | 22-4 | 26-0 | 8-5 | 13-3 | 17-0 | 20-9 | 24-10 |
Douglas Fir-Larch | #1 | 8-2 | 12-0 | 15-3 | 18-7 | 21-7 | 7-7 | 11-2 | 14-1 | 17-3 | 20-0 | |
Douglas Fir-Larch | #2 | 7-8 | 11-3 | 14-3 | 17-5 | 20-2 | 7-1 | 10-5 | 13-2 | 16-1 | 18-8 | |
Douglas Fir-Larch | #3 | 5-10 | 8-6 | 10-9 | 13-2 | 15-3 | 5-5 | 7-10 | 10-0 | 12-2 | 14-1 | |
Hem-Fir | SS | 8-0 | 12-6 | 16-6 | 21-1 | 25-6 | 8-0 | 12-6 | 16-6 | 20-4 | 23-7 | |
Hem-Fir | #1 | 7-10 | 11-9 | 14-10 | 18-1 | 21-0 | 7-5 | 10-10 | 13-9 | 16-9 | 19-5 | |
Hem-Fir | #2 | 7-5 | 11-1 | 14-0 | 17-2 | 19-11 | 7-0 | 10-3 | 13-0 | 15-10 | 18-5 | |
Hem-Fir | #3 | 5-10 | 8-6 | 10-9 | 13-2 | 15-3 | 5-5 | 7-10 | 10-0 | 12-2 | 14-1 | |
Southern Pine | SS | 8-4 | 13-0 | 17-2 | 21-11 | Note a | 8-4 | 13-0 | 17-2 | 21-11 | Note a | |
Southern Pine | #1 | 8-2 | 12-10 | 16-10 | 20-3 | 24-1 | 8-2 | 12-6 | 15-9 | 18-9 | 22-4 | |
Southern Pine | #2 | 8-0 | 11-9 | 15-3 | 18-2 | 21-3 | 7-7 | 10-11 | 14-1 | 16-10 | 19-9 | |
Southern Pine | #3 | 6-2 | 9-2 | 11-8 | 13-9 | 16-4 | 5-9 | 8-5 | 10-9 | 12-9 | 15-2 | |
Spruce-Pine-Fir | SS | 7-10 | 12-3 | 16-2 | 20-8 | 24-1 | 7-10 | 12-3 | 15-9 | 19-3 | 22-4 | |
Spruce-Pine-Fir | #1 | 7-8 | 11-3 | 14-3 | 17-5 | 20-2 | 7-1 | 10-5 | 13-2 | 16-1 | 18-8 | |
Spruce-Pine-Fir | #2 | 7-8 | 11-3 | 14-3 | 17-5 | 20-2 | 7-1 | 10-5 | 13-2 | 16-1 | 18-8 | |
Spruce-Pine-Fir | #3 | 5-10 | 8-6 | 10-9 | 13-2 | 15-3 | 5-5 | 7-10 | 10-0 | 12-2 | 14-1 | |
16 | Douglas Fir-Larch | SS | 7-8 | 12-1 | 15-10 | 19-5 | 22-6 | 7-8 | 11-7 | 14-8 | 17-11 | 20-10 |
Douglas Fir-Larch | #1 | 7-1 | 10-5 | 13-2 | 16-1 | 18-8 | 6-7 | 9-8 | 12-2 | 14-11 | 17-3 | |
Douglas Fir-Larch | #2 | 6-8 | 9-9 | 12-4 | 15-1 | 17-6 | 6-2 | 9-0 | 11-5 | 13-11 | 16-2 | |
Douglas Fir-Larch | #3 | 5-0 | 7-4 | 9-4 | 11-5 | 13-2 | 4-8 | 6-10 | 8-8 | 10-6 | 12-3 | |
Hem-Fir | SS | 7-3 | 11-5 | 15-0 | 19-1 | 22-1 | 7-3 | 11-5 | 14-5 | 17-8 | 20-5 | |
Hem-Fir | #1 | 6-11 | 10-2 | 12-10 | 15-8 | 18-2 | 6-5 | 9-5 | 11-11 | 14-6 | 16-10 | |
Hem-Fir | #2 | 6-7 | 9-7 | 12-2 | 14-10 | 17-3 | 6-1 | 8-11 | 11-3 | 13-9 | 15-11 | |
Hem-Fir | #3 | 5-0 | 7-4 | 9-4 | 11-5 | 13-2 | 4-8 | 6-10 | 8-8 | 10-6 | 12-3 | |
Southern Pine | SS | 7-6 | 11-10 | 15-7 | 19-11 | 24-3 | 7-6 | 11-10 | 15-7 | 19-11 | 23-10 | |
Southern Pine | #1 | 7-5 | 11-7 | 14-9 | 17-6 | 20-11 | 7-4 | 10-10 | 13-8 | 16-2 | 19-4 | |
Southern Pine | #2 | 7-1 | 10-2 | 13-2 | 15-9 | 18-5 | 6-7 | 9-5 | 12-2 | 14-7 | 17-1 | |
Southern Pine | #3 | 5-4 | 7-11 | 10-1 | 11-11 | 14-2 | 4-11 | 7-4 | 9-4 | 11-0 | 13-1 | |
Spruce-Pine-Fir | SS | 7-1 | 11-2 | 14-8 | 18-0 | 20-11 | 7-1 | 10-9 | 13-8 | 16-8 | 19-4 | |
Spruce-Pine-Fir | #1 | 6-8 | 9-9 | 12-4 | 15-1 | 17-6 | 6-2 | 9-0 | 11-5 | 13-11 | 16-2 | |
Spruce-Pine-Fir | #2 | 6-8 | 9-9 | 12-4 | 15-1 | 17-6 | 6-2 | 9-0 | 11-5 | 13-11 | 16-2 | |
Spruce-Pine-Fir | #3 | 5-0 | 7-4 | 9-4 | 11-5 | 13-2 | 4-8 | 6-10 | 8-8 | 10-6 | 12-3 | |
19.2 | Douglas Fir-Larch | SS | 7-3 | 11-4 | 14-6 | 17-8 | 20-6 | 7-3 | 10-7 | 13-5 | 16-5 | 19-0 |
Douglas Fir-Larch | #1 | 6-6 | 9-6 | 12-0 | 14-8 | 17-1 | 6-0 | 8-10 | 11-2 | 13-7 | 15-9 | |
Douglas Fir-Larch | #2 | 6-1 | 8-11 | 11-3 | 13-9 | 15-11 | 5-7 | 8-3 | 10-5 | 12-9 | 14-9 | |
Douglas Fir-Larch | #3 | 4-7 | 6-9 | 8-6 | 10-5 | 12-1 | 4-3 | 6-3 | 7-11 | 9-7 | 11-2 | |
Hem-Fir | SS | 6-10 | 10-9 | 14-2 | 17-5 | 20-2 | 6-10 | 10-5 | 13-2 | 16-1 | 18-8 | |
Hem-Fir | #1 | 6-4 | 9-3 | 11-9 | 14-4 | 16-7 | 5-10 | 8-7 | 10-10 | 13-3 | 15-5 | |
Hem-Fir | #2 | 6-0 | 8-9 | 11-1 | 13-7 | 15-9 | 5-7 | 8-1 | 10-3 | 12-7 | 14-7 | |
Hem-Fir | #3 | 4-7 | 6-9 | 8-6 | 10-5 | 12-1 | 4-3 | 6-3 | 7-11 | 9-7 | 11-2 | |
Southern Pine | SS | 7-1 | 11-2 | 14-8 | 18-9 | 22-10 | 7-1 | 11-2 | 14-8 | 18-7 | 21-9 | |
Southern Pine | #1 | 7-0 | 10-8 | 13-5 | 16-0 | 19-1 | 6-8 | 9-11 | 12-5 | 14-10 | 17-8 | |
Southern Pine | #2 | 6-6 | 9-4 | 12-0 | 14-4 | 16-10 | 6-0 | 8-8 | 11-2 | 13-4 | 15-7 | |
Southern Pine | #3 | 4-11 | 7-3 | 9-2 | 10-10 | 12-11 | 4-6 | 6-8 | 8-6 | 10-1 | 12-0 | |
Spruce-Pine-Fir | SS | 6-8 | 10-6 | 13-5 | 16-5 | 19-1 | 6-8 | 9-10 | 12-5 | 15-3 | 17-8 | |
Spruce-Pine-Fir | #1 | 6-1 | 8-11 | 11-3 | 13-9 | 15-11 | 5-7 | 8-3 | 10-5 | 12-9 | 14-9 | |
Spruce-Pine-Fir | #2 | 6-1 | 8-11 | 11-3 | 13-9 | 15-11 | 5-7 | 8-3 | 10-5 | 12-9 | 14-9 | |
Spruce-Pine-Fir | #3 | 4-7 | 6-9 | 8-6 | 10-5 | 12-1 | 4-3 | 6-3 | 7-11 | 9-7 | 11-2 | |
24 | Douglas Fir-Larch | SS | 6-8 | 10-3 | 13-0 | 15-10 | 18-4 | 6-6 | 9-6 | 12-0 | 14-8 | 17-0 |
Douglas Fir-Larch | #1 | 5-10 | 8-6 | 10-9 | 13-2 | 15-3 | 5-5 | 7-10 | 10-0 | 12-2 | 14-1 | |
Douglas Fir-Larch | #2 | 5-5 | 7-11 | 10-1 | 12-4 | 14-3 | 5-0 | 7-4 | 9-4 | 11-5 | 13-2 | |
Douglas Fir-Larch | #3 | 4-1 | 6-0 | 7-7 | 9-4 | 10-9 | 3-10 | 5-7 | 7-1 | 8-7 | 10-0 | |
Hem-Fir | SS | 6-4 | 9-11 | 12-9 | 15-7 | 18-0 | 6-4 | 9-4 | 11-9 | 14-5 | 16-8 | |
Hem-Fir | #1 | 5-8 | 8-3 | 10-6 | 12-10 | 14-10 | 5-3 | 7-8 | 9-9 | 11-10 | 13-9 | |
Hem-Fir | #2 | 5-4 | 7-10 | 9-11 | 12-1 | 14-1 | 4-11 | 7-3 | 9-2 | 11-3 | 13-0 | |
Hem-Fir | #3 | 4-1 | 6-0 | 7-7 | 9-4 | 10-9 | 3-10 | 5-7 | 7-1 | 8-7 | 10-0 | |
Southern Pine | SS | 6-7 | 10-4 | 13-8 | 17-5 | 21-0 | 6-7 | 10-4 | 13-8 | 16-7 | 19-5 | |
Southern Pine | #1 | 6-5 | 9-7 | 12-0 | 14-4 | 17-1 | 6-0 | 8-10 | 11-2 | 13-3 | 15-9 | |
Southern Pine | #2 | 5-10 | 8-4 | 10-9 | 12-10 | 15-1 | 5-5 | 7-9 | 10-0 | 11-11 | 13-11 | |
Southern Pine | #3 | 4-4 | 6-5 | 8-3 | 9-9 | 11-7 | 4-1 | 6-0 | 7-7 | 9-0 | 10-8 | |
Spruce-Pine-Fir | SS | 6-2 | 9-6 | 12-0 | 14-8 | 17-1 | 6-0 | 8-10 | 11-2 | 13-7 | 15-9 | |
Spruce-Pine-Fir | #1 | 5-5 | 7-11 | 10-1 | 12-4 | 14-3 | 5-0 | 7-4 | 9-4 | 11-5 | 13-2 | |
Spruce-Pine-Fir | #2 | 5-5 | 7-11 | 10-1 | 12-4 | 14-3 | 5-0 | 7-4 | 9-4 | 11-5 | 13-2 | |
Spruce-Pine-Fir | #3 | 4-1 | 6-0 | 7-7 | 9-4 | 10-9 | 3-10 | 5-7 | 7-1 | 8-7 | 10-0 |
- Span exceeds 26 feet in length. Check sources for availability of lumber in lengths greater than 20 feet.
RAFTER SPACING (inches) |
SPECIES AND GRADE | DEAD LOAD = 10 pounds per square foot | DEAD LOAD = 20 pounds per square foot | |||||||||
2 × 4 | 2 × 6 | 2 × 8 | 2 × 10 | 2 × 12 | 2 × 4 | 2 × 6 | 2 × 8 | 2 × 10 | 2 × 12 | |||
Maximum rafter spans | ||||||||||||
(ft. - in.) | (ft. - in.) | (ft. - in.) | (ft. - in.) | (ft. - in.) | (ft. - in.) | (ft. - in.) | (ft. - in.) | (ft. - in.) | (ft. - in.) | |||
12 | Douglas Fir-Larch | SS | 9-1 | 14-4 | 18-10 | 24-1 | Note a | 9-1 | 14-4 | 18-10 | 24-1 | Note a |
Douglas Fir-Larch | #1 | 8-9 | 13-9 | 18-2 | 22-9 | Note a | 8-9 | 13-2 | 16-8 | 20-4 | 23-7 | |
Douglas Fir-Larch | #2 | 8-7 | 13-6 | 17-5 | 21-4 | 24-8 | 8-5 | 12-4 | 15-7 | 19-1 | 22-1 | |
Douglas Fir-Larch | #3 | 7-1 | 10-5 | 13-2 | 16-1 | 18-8 | 6-4 | 9-4 | 11-9 | 14-5 | 16-8 | |
Hem-Fir | SS | 8-7 | 13-6 | 17-10 | 22-9 | Note a | 8-7 | 13-6 | 17-10 | 22-9 | Note a | |
Hem-Fir | #1 | 8-5 | 13-3 | 17-5 | 22-2 | 25-9 | 8-5 | 12-10 | 16-3 | 19-10 | 23-0 | |
Hem-Fir | #2 | 8-0 | 12-7 | 16-7 | 21-0 | 24-4 | 8-0 | 12-2 | 15-4 | 18-9 | 21-9 | |
Hem-Fir | #3 | 7-1 | 10-5 | 13-2 | 16-1 | 18-8 | 6-4 | 9-4 | 11-9 | 14-5 | 16-8 | |
Southern Pine | SS | 8-11 | 14-1 | 18-6 | 23-8 | Note a | 8-11 | 14-1 | 18-6 | 23-8 | Note a | |
Southern Pine | #1 | 8-9 | 13-9 | 18-2 | 23-2 | Note a | 8-9 | 13-9 | 18-2 | 22-2 | Note a | |
Southern Pine | #2 | 8-7 | 13-6 | 17-10 | 22-3 | Note a | 8-7 | 12-11 | 16-8 | 19-11 | 23-4 | |
Southern Pine | #3 | 7-7 | 11-2 | 14-3 | 16-10 | 20-0 | 6-9 | 10-0 | 12-9 | 15-1 | 17-11 | |
Spruce-Pine-Fir | SS | 8-5 | 13-3 | 17-5 | 22-3 | Note a | 8-5 | 13-3 | 17-5 | 22-3 | Note a | |
Spruce-Pine-Fir | #1 | 8-3 | 12-11 | 17-0 | 21-4 | 24-8 | 8-3 | 12-4 | 15-7 | 19-1 | 22-1 | |
Spruce-Pine-Fir | #2 | 8-3 | 12-11 | 17-0 | 21-4 | 24-8 | 8-3 | 12-4 | 15-7 | 19-1 | 22-1 | |
Spruce-Pine-Fir | #3 | 7-1 | 10-5 | 13-2 | 16-1 | 18-8 | 6-4 | 9-4 | 11-9 | 14-5 | 16-8 | |
16 | Douglas Fir-Larch | SS | 8-3 | 13-0 | 17-2 | 21-10 | Note a | 8-3 | 13-0 | 17-2 | 21-3 | 24-8 |
Douglas Fir-Larch | #1 | 8-0 | 12-6 | 16-2 | 19-9 | 22-10 | 7-10 | 11-5 | 14-5 | 17-8 | 20-5 | |
Douglas Fir-Larch | #2 | 7-10 | 11-11 | 15-1 | 18-5 | 21-5 | 7-3 | 10-8 | 13-6 | 16-6 | 19-2 | |
Douglas Fir-Larch | #3 | 6-2 | 9-0 | 11-5 | 13-11 | 16-2 | 5-6 | 8-1 | 10-3 | 12-6 | 14-6 | |
Hem-Fir | SS | 7-10 | 12-3 | 16-2 | 20-8 | 25-1 | 7-10 | 12-3 | 16-2 | 20-8 | 24-2 | |
Hem-Fir | #1 | 7-8 | 12-0 | 15-9 | 19-3 | 22-3 | 7-7 | 11-1 | 14-1 | 17-2 | 19-11 | |
Hem-Fir | #2 | 7-3 | 11-5 | 14-11 | 18-2 | 21-1 | 7-2 | 10-6 | 13-4 | 16-3 | 18-10 | |
Hem-Fir | #3 | 6-2 | 9-0 | 11-5 | 13-11 | 16-2 | 5-6 | 8-1 | 10-3 | 12-6 | 14-6 | |
Southern Pine | SS | 8-1 | 12-9 | 16-10 | 21-6 | Note a | 8-1 | 12-9 | 16-10 | 21-6 | Note a | |
Southern Pine | #1 | 8-0 | 12-6 | 16-6 | 21-1 | 25-7 | 8-0 | 12-6 | 16-2 | 19-2 | 22-10 | |
Southern Pine | #2 | 7-10 | 12-3 | 16-2 | 19-3 | 22-7 | 7-10 | 11-2 | 14-5 | 17-3 | 20-2 | |
Southern Pine | #3 | 6-7 | 9-8 | 12-4 | 14-7 | 17-4 | 5-10 | 8-8 | 11-0 | 13-0 | 15-6 | |
Spruce-Pine-Fir | SS | 7-8 | 12-0 | 15-10 | 20-2 | 24-7 | 7-8 | 12-0 | 15-10 | 19-9 | 22-10 | |
Spruce-Pine-Fir | #1 | 7-6 | 11-9 | 15-1 | 18-5 | 21-5 | 7-3 | 10-8 | 13-6 | 16-6 | 19-2 | |
Spruce-Pine-Fir | #2 | 7-6 | 11-9 | 15-1 | 18-5 | 21-5 | 7-3 | 10-8 | 13-6 | 16-6 | 19-2 | |
Spruce-Pine-Fir | #3 | 6-2 | 9-0 | 11-5 | 13-11 | 16-2 | 5-6 | 8-1 | 10-3 | 12-6 | 14-6 | |
19.2 | Douglas Fir-Larch | SS | 7-9 | 12-3 | 16-1 | 20-7 | 25-0 | 7-9 | 12-3 | 15-10 | 19-5 | 22-6 |
Douglas Fir-Larch | #1 | 7-6 | 11-8 | 14-9 | 18-0 | 20-11 | 7-1 | 10-5 | 13-2 | 16-1 | 18-8 | |
Douglas Fir-Larch | #2 | 7-4 | 10-11 | 13-9 | 16-10 | 19-6 | 6-8 | 9-9 | 12-4 | 15-1 | 17-6 | |
Douglas Fir-Larch | #3 | 5-7 | 8-3 | 10-5 | 12-9 | 14-9 | 5-0 | 7-4 | 9-4 | 11-5 | 13-2 | |
Hem-Fir | SS | 7-4 | 11-7 | 15-3 | 19-5 | 23-7 | 7-4 | 11-7 | 15-3 | 19-1 | 22-1 | |
Hem-Fir | #1 | 7-2 | 11-4 | 14-4 | 17-7 | 20-4 | 6-11 | 10-2 | 12-10 | 15-8 | 18-2 | |
Hem-Fir | #2 | 6-10 | 10-9 | 13-7 | 16-7 | 19-3 | 6-7 | 9-7 | 12-2 | 14-10 | 17-3 | |
Hem-Fir | #3 | 5-7 | 8-3 | 10-5 | 12-9 | 14-9 | 5-0 | 7-4 | 9-4 | 11-5 | 13-2 | |
Southern Pine | SS | 7-8 | 12-0 | 15-10 | 20-2 | 24-7 | 7-8 | 12-0 | 15-10 | 20-2 | 24-7 | |
Southern Pine | #1 | 7-6 | 11-9 | 15-6 | 19-7 | 23-4 | 7-6 | 11-9 | 14-9 | 17-6 | 20-11 | |
Southern Pine | #2 | 7-4 | 11-5 | 14-9 | 17-7 | 20-7 | 7-1 | 10-2 | 13-2 | 15-9 | 18-5 | |
Southern Pine | #3 | 6-0 | 8-10 | 11-3 | 13-4 | 15-10 | 5-4 | 7-11 | 10-1 | 11-11 | 14-2 | |
Spruce-Pine-Fir | SS | 7-2 | 11-4 | 14-11 | 19-0 | 23-1 | 7-2 | 11-4 | 14-9 | 18-0 | 20-11 | |
Spruce-Pine-Fir | #1 | 7-0 | 10-11 | 13-9 | 16-10 | 19-6 | 6-8 | 9-9 | 12-4 | 15-1 | 17-6 | |
Spruce-Pine-Fir | #2 | 7-0 | 10-11 | 13-9 | 16-10 | 19-6 | 6-8 | 9-9 | 12-4 | 15-1 | 17-6 | |
Spruce-Pine-Fir | #3 | 5-7 | 8-3 | 10-5 | 12-9 | 14-9 | 5-0 | 7-4 | 9-4 | 11-5 | 13-2 | |
24 | Douglas Fir-Larch | SS | 7-3 | 11-4 | 15-0 | 19-1 | 22-6 | 7-3 | 11-3 | 14-2 | 17-4 | 20-1 |
Douglas Fir-Larch | #1 | 7-0 | 10-5 | 13-2 | 16-1 | 18-8 | 6-4 | 9-4 | 11-9 | 14-5 | 16-8 | |
Douglas Fir-Larch | #2 | 6-8 | 9-9 | 12-4 | 15-1 | 17-6 | 5-11 | 8-8 | 11-0 | 13-6 | 15-7 | |
Douglas Fir-Larch | #3 | 5-0 | 7-4 | 9-4 | 11-5 | 13-2 | 4-6 | 6-7 | 8-4 | 10-2 | 11-10 | |
Hem-Fir | SS | 6-10 | 10-9 | 14-2 | 18-0 | 21-11 | 6-10 | 10-9 | 13-11 | 17-0 | 19-9 | |
Hem-Fir | #1 | 6-8 | 10-2 | 12-10 | 15-8 | 18-2 | 6-2 | 9-1 | 11-6 | 14-0 | 16-3 | |
Hem-Fir | #2 | 6-4 | 9-7 | 12-2 | 14-10 | 17-3 | 5-10 | 8-7 | 10-10 | 13-3 | 15-5 | |
Hem-Fir | #3 | 5-0 | 7-4 | 9-4 | 11-5 | 13-2 | 4-6 | 6-7 | 8-4 | 10-2 | 11-10 | |
Southern Pine | SS | 7-1 | 11-2 | 14-8 | 18-9 | 22-10 | 7-1 | 11-2 | 14-8 | 18-9 | 22-10 | |
Southern Pine | #1 | 7-0 | 10-11 | 14-5 | 17-6 | 20-11 | 7-0 | 10-6 | 13-2 | 15-8 | 18-8 | |
Southern Pine | #2 | 6-10 | 10-2 | 13-2 | 15-9 | 18-5 | 6-4 | 9-2 | 11-9 | 14-1 | 16-6 | |
Southern Pine | #3 | 5-4 | 7-11 | 10-1 | 11-11 | 14-2 | 4-9 | 7-1 | 9-0 | 10-8 | 12-8 | |
Spruce-Pine-Fir | SS | 6-8 | 10-6 | 13-10 | 17-8 | 20-11 | 6-8 | 10-5 | 13-2 | 16-1 | 18-8 | |
Spruce-Pine-Fir | #1 | 6-6 | 9-9 | 12-4 | 15-1 | 17-6 | 5-11 | 8-8 | 11-0 | 13-6 | 15-7 | |
Spruce-Pine-Fir | #2 | 6-6 | 9-9 | 12-4 | 15-1 | 17-6 | 5-11 | 8-8 | 11-0 | 13-6 | 15-7 | |
Spruce-Pine-Fir | #3 | 5-0 | 7-4 | 9-4 | 11-5 | 13-2 | 4-6 | 6-7 | 8-4 | 10-2 | 11-10 |
- Span exceeds 26 feet in length. Check sources for availability of lumber in lengths greater than 20 feet.
RAFTER SPACING (inches) |
SPECIES AND GRADE | DEAD LOAD = 10 pounds per square foot | DEAD LOAD = 20 pounds per square foot | |||||||||
2 × 4 | 2 × 6 | 2 × 8 | 2 × 10 | 2 × 12 | 2 × 4 | 2 × 6 | 2 × 8 | 2 × 10 | 2 × 12 | |||
Maximum rafter spans | ||||||||||||
(ft. - in.) | (ft. - in.) | (ft. - in.) | (ft. - in.) | (ft. - in.) | (ft. - in.) | (ft. - in.) | (ft. - in.) | (ft. - in.) | (ft. - in.) | |||
12 | Douglas Fir-Larch | SS | 7-8 | 12-1 | 15-11 | 20-3 | 24-8 | 7-8 | 12-1 | 15-11 | 20-3 | 24-0 |
Douglas Fir-Larch | #1 | 7-5 | 11-7 | 15-3 | 18-7 | 21-7 | 7-5 | 11-2 | 14-1 | 17-3 | 20-0 | |
Douglas Fir-Larch | #2 | 7-3 | 11-3 | 14-3 | 17-5 | 20-2 | 7-1 | 10-5 | 13-2 | 16-1 | 18-8 | |
Douglas Fir-Larch | #3 | 5-10 | 8-6 | 10-9 | 13-2 | 15-3 | 5-5 | 7-10 | 10-0 | 12-2 | 14-1 | |
Hem-Fir | SS | 7-3 | 11-5 | 15-0 | 19-2 | 23-4 | 7-3 | 11-5 | 15-0 | 19-2 | 23-4 | |
Hem-Fir | #1 | 7-1 | 11-2 | 14-8 | 18-1 | 21-0 | 7-1 | 10-10 | 13-9 | 16-9 | 19-5 | |
Hem-Fir | #2 | 6-9 | 10-8 | 14-0 | 17-2 | 19-11 | 6-9 | 10-3 | 13-0 | 15-10 | 18-5 | |
Hem-Fir | #3 | 5-10 | 8-6 | 10-9 | 13-2 | 15-3 | 5-5 | 7-10 | 10-0 | 12-2 | 14-1 | |
Southern Pine | SS | 7-6 | 11-0 | 15-7 | 19-11 | 24-3 | 7-6 | 11-10 | 15-7 | 19-11 | 24-3 | |
Southern Pine | #1 | 7-5 | 11-7 | 15-4 | 19-7 | 23-9 | 7-5 | 11-7 | 15-4 | 18-9 | 22-4 | |
Southern Pine | #2 | 7-3 | 11-5 | 15-0 | 18-2 | 21-3 | 7-3 | 10-11 | 14-1 | 16-10 | 19-9 | |
Southern Pine | #3 | 6-2 | 9-2 | 11-8 | 13-9 | 16-4 | 5-9 | 8-5 | 10-9 | 12-9 | 15-2 | |
Spruce-Pine-Fir | SS | 7-1 | 11-2 | 14-8 | 18-9 | 22-10 | 7-1 | 11-2 | 14-8 | 18-9 | 22-4 | |
Spruce-Pine-Fir | #1 | 6-11 | 10-11 | 14-3 | 17-5 | 20-2 | 6-11 | 10-5 | 13-2 | 16-1 | 18-8 | |
Spruce-Pine-Fir | #2 | 6-11 | 10-11 | 14-3 | 17-5 | 20-2 | 6-11 | 10-5 | 13-2 | 16-1 | 18-8 | |
Spruce-Pine-Fir | #3 | 5-10 | 8-6 | 10-9 | 13-2 | 15-3 | 5-5 | 7-10 | 10-0 | 12-2 | 14-1 | |
16 | Douglas Fir-Larch | SS | 7-0 | 11-0 | 14-5 | 18-5 | 22-5 | 7-0 | 11-0 | 14-5 | 17-11 | 20-10 |
Douglas Fir-Larch | #1 | 6-9 | 10-5 | 13-2 | 16-1 | 18-8 | 6-7 | 9-8 | 12-2 | 14-11 | 17-3 | |
Douglas Fir-Larch | #2 | 6-7 | 9-9 | 12-4 | 15-1 | 17-6 | 6-2 | 9-0 | 11-5 | 13-11 | 16-2 | |
Douglas Fir-Larch | #3 | 5-0 | 7-4 | 9-4 | 11-5 | 13-2 | 4-8 | 6-10 | 8-8 | 10-6 | 12-3 | |
Hem-Fir | SS | 6-7 | 10-4 | 13-8 | 17-5 | 21-2 | 6-7 | 10-4 | 13-8 | 17-5 | 20-5 | |
Hem-Fir | #1 | 6-5 | 10-2 | 12-10 | 15-8 | 18-2 | 6-5 | 9-5 | 11-11 | 14-6 | 16-10 | |
Hem-Fir | #2 | 6-2 | 9-7 | 12-2 | 14-10 | 17-3 | 6-1 | 8-11 | 11-3 | 13-9 | 15-11 | |
Hem-Fir | #3 | 5-0 | 7-4 | 9-4 | 11-5 | 13-2 | 4-8 | 6-10 | 8-8 | 10-6 | 12-3 | |
Southern Pine | SS | 6-10 | 10-9 | 14-2 | 18-1 | 22-0 | 6-10 | 10-9 | 14-2 | 18-1 | 22-0 | |
Southern Pine | #1 | 6-9 | 10-7 | 13-11 | 17-6 | 20-11 | 6-9 | 10-7 | 13-8 | 16-2 | 19-4 | |
Southern Pine | #2 | 6-7 | 10-2 | 13-2 | 15-9 | 18-5 | 6-7 | 9-5 | 12-2 | 14-7 | 17-1 | |
Southern Pine | #3 | 5-4 | 7-11 | 10-1 | 11-11 | 14-2 | 4-11 | 7-4 | 9-4 | 11-0 | 13-1 | |
Spruce-Pine-Fir | SS | 6-5 | 10-2 | 13-4 | 17-0 | 20-9 | 6-5 | 10-2 | 13-4 | 16-8 | 19-4 | |
Spruce-Pine-Fir | #1 | 6-4 | 9-9 | 12-4 | 15-1 | 17-6 | 6-2 | 9-0 | 11-5 | 13-11 | 16-2 | |
Spruce-Pine-Fir | #2 | 6-4 | 9-9 | 12-4 | 15-1 | 17-6 | 6-2 | 9-0 | 11-5 | 13-11 | 16-2 | |
Spruce-Pine-Fir | #3 | 5-0 | 7-4 | 9-4 | 11-5 | 13-2 | 4-8 | 6-10 | 8-8 | 10-6 | 12-3 | |
19.2 | Douglas Fir-Larch | SS | 6-7 | 10-4 | 13-7 | 17-4 | 20-6 | 6-7 | 10-4 | 13-5 | 16-5 | 19-0 |
Douglas Fir-Larch | #1 | 6-4 | 9-6 | 12-0 | 14-8 | 17-1 | 6-0 | 8-10 | 11-2 | 13-7 | 15-9 | |
Douglas Fir-Larch | #2 | 6-1 | 8-11 | 11-3 | 13-9 | 15-11 | 5-7 | 8-3 | 10-5 | 12-9 | 14-9 | |
Douglas Fir-Larch | #3 | 4-7 | 6-9 | 8-6 | 10-5 | 12-1 | 4-3 | 6-3 | 7-11 | 9-7 | 11-2 | |
Hem-Fir | SS | 6-2 | 9-9 | 12-10 | 16-5 | 19-11 | 6-2 | 9-9 | 12-10 | 16-1 | 18-8 | |
Hem-Fir | #1 | 6-1 | 9-3 | 11-9 | 14-4 | 16-7 | 5-10 | 8-7 | 10-10 | 13-3 | 15-5 | |
Hem-Fir | #2 | 5-9 | 8-9 | 11-1 | 13-7 | 15-9 | 5-7 | 8-1 | 10-3 | 12-7 | 14-7 | |
Hem-Fir | #3 | 4-7 | 6-9 | 8-6 | 10-5 | 12-1 | 4-3 | 6-3 | 7-11 | 9-7 | 11-2 | |
Southern Pine | SS | 6-5 | 10-2 | 13-4 | 17-0 | 20-9 | 6-5 | 10-2 | 13-4 | 17-0 | 20-9 | |
Southern Pine | #1 | 6-4 | 9-11 | 13-1 | 16-0 | 19-1 | 6-4 | 9-11 | 12-5 | 14-10 | 17-8 | |
Southern Pine | #2 | 6-2 | 9-4 | 12-0 | 14-4 | 16-10 | 6-0 | 8-8 | 11-2 | 13-4 | 15-7 | |
Southern Pine | #3 | 4-11 | 7-3 | 9-2 | 10-10 | 12-11 | 4-6 | 6-8 | 8-6 | 10-1 | 12-0 | |
Spruce-Pine-Fir | SS | 6-1 | 9-6 | 12-7 | 16-0 | 19-1 | 6-1 | 9-6 | 12-5 | 15-3 | 17-8 | |
Spruce-Pine-Fir | #1 | 5-11 | 8-11 | 11-3 | 13-9 | 15-11 | 5-7 | 8-3 | 10-5 | 12-9 | 14-9 | |
Spruce-Pine-Fir | #2 | 5-11 | 8-11 | 11-3 | 13-9 | 15-11 | 5-7 | 8-3 | 10-5 | 12-9 | 14-9 | |
Spruce-Pine-Fir | #3 | 4-7 | 6-9 | 8-6 | 10-5 | 12-1 | 4-3 | 6-3 | 7-11 | 9-7 | 11-2 | |
24 | Douglas Fir-Larch | SS | 6-1 | 9-7 | 12-7 | 15-10 | 18-4 | 6-1 | 9-6 | 12-0 | 14-8 | 17-0 |
Douglas Fir-Larch | #1 | 5-10 | 8-6 | 10-9 | 13-2 | 15-3 | 5-5 | 7-10 | 10-0 | 12-2 | 14-1 | |
Douglas Fir-Larch | #2 | 5-5 | 7-11 | 10-1 | 12-4 | 14-3 | 5-0 | 7-4 | 9-4 | 11-5 | 13-2 | |
Douglas Fir-Larch | #3 | 4-1 | 6-0 | 7-7 | 9-4 | 10-9 | 3-10 | 5-7 | 7-1 | 8-7 | 10-0 | |
Hem-Fir | SS | 5-9 | 9-1 | 11-11 | 15-12 | 18-0 | 5-9 | 9-1 | 11-9 | 14-5 | 16-8 | |
Hem-Fir | #1 | 5-8 | 8-3 | 10-6 | 12-10 | 14-10 | 5-3 | 7-8 | 9-9 | 11-10 | 13-9 | |
Hem-Fir | #2 | 5-4 | 7-10 | 9-11 | 12-1 | 14-1 | 4-11 | 7-3 | 9-2 | 11-3 | 13-0 | |
Hem-Fir | #3 | 4-1 | 6-0 | 7-7 | 9-4 | 10-9 | 3-10 | 5-7 | 7-1 | 8-7 | 10-0 | |
Southern Pine | SS | 6-0 | 9-5 | 12-5 | 15-10 | 19-3 | 6-0 | 9-5 | 12-5 | 15-10 | 19-3 | |
Southern Pine | #1 | 5-10 | 9-3 | 12-0 | 14-4 | 17-1 | 5-10 | 8-10 | 11-2 | 13-3 | 15-9 | |
Southern Pine | #2 | 5-9 | 8-4 | 10-9 | 12-10 | 15-1 | 5-5 | 7-9 | 10-0 | 11-11 | 13-11 | |
Southern Pine | #3 | 4-4 | 6-5 | 8-3 | 9-9 | 11-7 | 4-1 | 6-0 | 7-7 | 9-0 | 10-8 | |
Spruce-Pine-Fir | SS | 5-8 | 8-10 | 11-8 | 14-8 | 17-1 | 5-8 | 8-10 | 11-2 | 13-7 | 15-9 | |
Spruce-Pine-Fir | #1 | 5-5 | 7-11 | 10-1 | 12-4 | 14-3 | 5-0 | 7-4 | 9-4 | 11-5 | 13-2 | |
Spruce-Pine-Fir | #2 | 5-5 | 7-11 | 10-1 | 12-4 | 14-3 | 5-0 | 7-4 | 9-4 | 11-5 | 13-2 | |
Spruce-Pine-Fir | #3 | 4-1 | 6-0 | 7-7 | 9-4 | 10-9 | 3-10 | 5-7 | 7-1 | 8-7 | 10-0 |
Where ceiling joists are not parallel to rafters, an equivalent rafter tie shall be installed in a manner to provide a continuous tie across the building, at a spacing of not more than 4 feet (1219 mm) o.c. The connections shall be in accordance with Tables 2308.10.4.1 and 2304.9.1, or connections of equivalent capacities shall be provided. Where ceiling joists or rafter ties are not provided at the top of the rafter support walls, the ridge formed by these rafters shall also be supported by a girder conforming to Section 2308.4.
Rafter ties shall be spaced not more than 4 feet (1219 mm) o.c. Rafter tie connections shall be based on the equivalent rafter spacing in Table 2308.10.4.1. Where rafter ties are spaced at 32 inches (813 mm) o.c., the number of 16d common nails shall be two times the number specified for rafters spaced 16 inches (406 mm) o.c., with a minimum of four 16d common nails where no snow loads are indicated. Where rafter ties are spaced at 48 inches (1219 mm) o.c., the number of 16d common nails shall be two times the number specified for rafters spaced 24 inches (610 mm) o.c., with a minimum of six 16d common nails where no snow loads are indicated. Rafter/ceiling joist connections and rafter/tie connections shall be of sufficient size and number to prevent splitting from nailing.
RAFTER SLOPE |
TIE SPACING (inches) |
NO SNOW LOAD | GROUND SNOW LOAD (pound per square foot) |
||||||||||
30 pounds per square foot |
50 pounds per square foot |
||||||||||||
Roof span (feet) | |||||||||||||
12 | 20 | 28 | 36 | 12 | 20 | 28 | 36 | 12 | 20 | 28 | 36 | ||
Required number of 16d common (31/2" x 0.162") nailsa, b per connectionc, d, e, f |
|||||||||||||
3:12 | 12 | 4 | 6 | 8 | 10 | 4 | 6 | 8 | 11 | 5 | 8 | 12 | 15 |
16 | 5 | 7 | 10 | 13 | 5 | 8 | 11 | 14 | 6 | 11 | 15 | 20 | |
24 | 7 | 11 | 15 | 19 | 7 | 11 | 16 | 21 | 9 | 16 | 23 | 30 | |
32 | 10 | 14 | 19 | 25 | 10 | 16 | 22 | 28 | 12 | 27 | 30 | 40 | |
48 | 14 | 21 | 29 | 37 | 14 | 32 | 36 | 42 | 18 | 32 | 46 | 60 | |
4:12 | 12 | 3 | 4 | 5 | 6 | 3 | 5 | 6 | 8 | 4 | 6 | 9 | 11 |
16 | 3 | 5 | 7 | 8 | 4 | 6 | 8 | 11 | 5 | 8 | 12 | 15 | |
24 | 4 | 7 | 10 | 12 | 5 | 9 | 12 | 16 | 7 | 12 | 17 | 22 | |
32 | 6 | 9 | 13 | 16 | 8 | 12 | 16 | 22 | 10 | 16 | 24 | 30 | |
48 | 8 | 14 | 19 | 24 | 10 | 18 | 24 | 32 | 14 | 24 | 34 | 44 | |
5:12 | 12 | 3 | 3 | 4 | 5 | 3 | 4 | 5 | 7 | 3 | 5 | 7 | 9 |
16 | 3 | 4 | 5 | 7 | 3 | 5 | 7 | 9 | 4 | 7 | 9 | 12 | |
24 | 4 | 6 | 8 | 10 | 4 | 7 | 10 | 13 | 6 | 10 | 14 | 18 | |
32 | 5 | 8 | 10 | 13 | 6 | 10 | 14 | 18 | 8 | 14 | 18 | 24 | |
48 | 7 | 11 | 15 | 20 | 8 | 14 | 20 | 26 | 12 | 20 | 28 | 36 | |
7:12 | 12 | 3 | 3 | 3 | 4 | 3 | 3 | 4 | 5 | 3 | 4 | 5 | 7 |
16 | 3 | 3 | 4 | 5 | 3 | 4 | 5 | 6 | 3 | 5 | 7 | 9 | |
24 | 3 | 4 | 6 | 7 | 3 | 5 | 7 | 9 | 4 | 7 | 10 | 13 | |
32 | 4 | 6 | 8 | 10 | 4 | 8 | 10 | 12 | 6 | 10 | 14 | 18 | |
48 | 5 | 8 | 11 | 14 | 6 | 10 | 14 | 18 | 9 | 14 | 20 | 26 | |
9:12 | 12 | 3 | 3 | 3 | 3 | 3 | 3 | 3 | 4 | 3 | 3 | 4 | 5 |
16 | 3 | 3 | 3 | 4 | 3 | 3 | 4 | 5 | 3 | 4 | 5 | 7 | |
24 | 3 | 3 | 5 | 6 | 3 | 4 | 6 | 7 | 3 | 6 | 8 | 10 | |
32 | 3 | 4 | 6 | 8 | 4 | 6 | 8 | 10 | 5 | 8 | 10 | 14 | |
48 | 4 | 6 | 9 | 11 | 5 | 8 | 12 | 14 | 7 | 12 | 16 | 20 | |
12:12 | 12 | 3 | 3 | 3 | 3 | 3 | 3 | 3 | 3 | 3 | 3 | 3 | 4 |
16 | 3 | 3 | 3 | 3 | 3 | 3 | 3 | 4 | 3 | 3 | 4 | 5 | |
24 | 3 | 3 | 3 | 4 | 3 | 3 | 4 | 6 | 3 | 4 | 6 | 8 | |
32 | 3 | 3 | 4 | 5 | 3 | 5 | 6 | 8 | 4 | 6 | 8 | 10 | |
48 | 3 | 4 | 6 | 7 | 4 | 7 | 8 | 12 | 6 | 8 | 12 | 16 |
- 40d box (5" × 0.162") or l6d sinker (31/4" × 0.148") nails are permitted to be substituted for 16d common (31/2" × 0.16") nails.
- Nailing requirements are permitted to be reduced 25 percent if nails are clinched.
- Rafter tie heel joint connections are not required where the ridge is supported by a load-bearing wall, header or ridge beam.
- When intermediate support of the rafter is provided by vertical struts or purlins to a load-bearing wall, the tabulated heel joint connection requirements are permitted to be reduced proportionally to the reduction in span.
- Equivalent nailing patterns are required for ceiling joist to ceiling joist lap splices.
- Connected members shall be of sufficient size to prevent splitting due to nailing.
- For snow loads less than 30 pounds per square foot, the required number of nails is permitted to be reduced by multiplying by the ratio of actual snow load plus 10 divided by 40, but not less than the number required for no snow load.
Notching at the ends of rafters or ceiling joists shall not exceed one-fourth the depth. Notches in the top or bottom of the rafter or ceiling joist shall not exceed one-sixth the depth and shall not be located in the middle one-third of the span, except that a notch not exceeding one-third of the depth is permitted in the top of the rafter or ceiling joist not further from the face of the support than the depth of the member.
Holes bored in rafters or ceiling joists shall not be within 2 inches (51 mm) of the top and bottom and their diameter shall not exceed one-third the depth of the member.
In lieu of such design, 2-inch (51 mm) tongue-and- groove planking is permitted in accordance with Table 2308.10.9. Joints in such planking are permitted to be randomly spaced, provided the system is applied to not less than three continuous spans, planks are center matched and end matched or splined, each plank bears on at least one support, and joints are separated by at least 24 inches (610 mm) in adjacent pieces.
SPANa (feet) |
LIVE LOAD (pound per square foot) | DEFLECTION LIMIT | BENDING STRESS (f) (pound per square inch) |
MODULUS OF ELASTICITY (E) (pound per square inch) |
---|---|---|---|---|
Roofs | ||||
4 | 20 | 1/240 | 160 | 170,000 |
1/360 | 256,000 | |||
30 | 1/240 | 210 | 256,000 | |
1/360 | 384,000 | |||
40 | 1/240 | 270 | 340,000 | |
1/360 | 512,000 | |||
4.5 | 20 | 1/240 | 200 | 242,000 |
1/360 | 305,000 | |||
30 | 1/240 | 270 | 363,000 | |
1/360 | 405,000 | |||
40 | 1/240 | 350 | 484,000 | |
1/360 | 725,000 | |||
5.0 | 20 | 1/240 | 250 | 332,000 |
1/360 | 500,000 | |||
30 | 1/240 | 330 | 495,000 | |
1/360 | 742,000 | |||
40 | 1/240 | 420 | 660,000 | |
1/360 | 1,000,000 | |||
5.5 | 20 | 1/240 | 300 | 442,000 |
1/360 | 660,000 | |||
30 | 1/240 | 400 | 662,000 | |
1/360 | 998,000 | |||
40 | 1/240 | 500 | 884,000 | |
1/360 | 1,330,000 | |||
6.0 | 20 | 1/240 | 360 | 575,000 |
1/360 | 862,000 | |||
30 | 1/240 | 480 | 862,000 | |
1/360 | 1,295,000 | |||
40 | 1/240 | 600 | 1,150,000 | |
1/360 | 1,730,000 | |||
6.5 | 20 | 1/240 | 420 | 595,000 |
1/360 | 892,000 | |||
30 | 1/240 | 560 | 892,000 | |
1/360 | 1,340,000 | |||
40 | 1/240 | 700 | 1,190,000 | |
1/360 | 1,730,000 | |||
7.0 | 20 | 1/240 | 490 | 910,000 |
1/360 | 1,360,000 | |||
30 | 1/240 | 650 | 1,370,000 | |
1/360 | 2,000,000 | |||
40 | 1/240 | 810 | 1,820,000 | |
1/360 | 2,725,000 | |||
7.5 | 20 | 1/240 | 560 | 1,125,000 |
1/360 | 1,685,000 | |||
30 | 1/240 | 750 | 1,685,000 | |
1/360 | 2,530,000 | |||
40 | 1/240 | 930 | 2,250,000 | |
1/360 | 3,380,000 | |||
8.0 | 20 | 1/240 | 640 | 1,360,000 |
1/360 | 2,040,000 | |||
30 | 1/240 | 850 | 2,040,000 | |
1/360 | 3,060,000 | |||
Floors | ||||
4 | 40 | 1/360 | 840 | 1,000,000 |
4.5 | 950 | 1,300,000 | ||
5.0 | 1,060 | 1,600,000 |
- Spans are based on simple beam action with 10 pounds per square foot dead load and provisions for a 300-pound concentrated load on a 12-inch width of decking. Random layup is permitted in accordance with the provisions of Section 2308.10.9. Lumber thickness is 11/2 inches nominal.
- Stone and masonry veneer is permitted to be used in the first two stories above grade plane or the first three stories above grade plane where the lowest story has concrete or masonry walls in Seismic Design Category B, provided that structural use panel wall bracing is used and the length of bracing provided is one- and one-half times the required length as determined in Table 2308.9.3(1).
- Stone and masonry veneer is permitted to be used in the first story above grade plane or the first two stories above grade plane where the lowest story has concrete or masonry walls in Seismic Design Category B or C.
- Stone and masonry veneer is permitted to be used in both stories of buildings with two stories above grade plane in Seismic Design Categories B and C, provided the following criteria are met:
- Type of brace per Section 2308.9.3 shall be Method 3 and the allowable shear capacity in accordance with Table 2306.3 shall be a minimum of 350 plf (5108 N/m).
- Braced wall panels in the second story shall be located in accordance with Section 2308.9.3 and not more than 25 feet (7620 mm) on center, and the total length of braced wall panels shall be not less than 25 percent of the braced wall line length. Braced wall panels in the first story shall be located in accordance with Section 2308.9.3 and not more than 25 feet (7620 mm) on center, and the total length of braced wall panels shall be not less than 45 percent of the braced wall line length.
- Hold-down connectors shall be provided at the ends of each braced wall panel for the second story to first story connection with an allowable design of 2,000 pounds (8896 N). Hold-down connectors shall be provided at the ends of each braced wall panel for the first story to foundation connection with an allowable capactiy of 3,900 pounds (17 347 N). In all cases, the hold-down connector force shall be transferred to the foundation.
- Cripple walls shall not be permitted.
- Where the bottom of the footing is stepped and the lowest floor framing rests directly on a sill bolted to the footings, the sill shall be anchored as required in Section 2308.3.3.
- Where the lowest floor framing rests directly on a sill bolted to a footing not less than 8 feet (2438 mm) in length along a line of bracing, the line shall be considered to be braced. The double plate of the cripple stud wall beyond the segment of footing extending to the lowest framed floor shall be spliced to the sill plate with metal ties, one on each side of the sill and plate. The metal ties shall not be less than 0.058 inch [1.47 mm (16 galvanized gage)] by 11/2 inches (38 mm) wide by 48 inches (1219 mm) with eight 16d common nails on each side of the splice location (see Figure 2308.11.3.2). The metal tie shall have a minimum yield of 33,000 pounds per square inch (psi) (227 MPa).
- Where cripple walls occur between the top of the footing and the lowest floor framing, the bracing requirements for a story shall apply.
STEPPED FOOTING CONNECTION DETAILS
- Blocking shall be provided beyond headers.
- Metal ties not less than 0.058 inch [1.47 mm (16 galvanized gage)] by 11/2 inches (38 mm) wide with eight 16d common nails on each side of the header-joist intersection shall be provided (see Figure 2308.11.3.3). The metal ties shall have a minimum yield of 33,000 psi (227 MPa).
OPENINGS IN HORIZONTAL DIAPHRAGMS
- Type of brace in accordance with Section 2308.9.3 shall be Method 3 and the allowable shear capacity in accordance with Table 2306.3 shall be a minimum of 350 plf (5108 N/m).
- The bracing of the first story shall be located at each end and at least every 25 feet (7620 mm) o.c. but not less than 45 percent of the braced wall line.
- Hold-down connectors shall be provided at the ends of braced walls for the first floor to foundation with an allowable capacity of 2,100 pounds (9341 N).
- Cripple walls shall not be permitted.
Cripple walls having a stud height exceeding 14 inches (356 mm) shall be considered a story for the purpose of this section and shall be braced as required for braced wall lines in accordance with Table 2308.12.4. Where interior braced wall lines occur without a continuous foundation below, the length of parallel exterior cripple wall bracing shall be one and one-half times the lengths required by Table 2308.12.4. Where the cripple wall sheathing type used is Type S-W and this additional length of bracing cannot be provided, the capacity of Type S-W sheathing shall be increased by reducing the spacing of fasteners along the perimeter of each piece of sheathing to 4 inches (102 mm) o.c.
CONDITION | SHEATHING TYPEb | SDS < 0.50 | 0.50 ≤ SDS < 0.75 | 0.75 ≤ SDS ≤ 1.00 | SDS > 1.00 |
One story | G-Pc | 10 feet 8 inches | 14 feet 8 inches | 18 feet 8 inches | 25 feet 0 inches |
S-W | 5 feet 4 inches | 8 feet 0 inches | 9 feet 4 inches | 12 feet 0 inches |
- Minimum length of panel bracing of one face of the wall for S-W sheathing or both faces of the wall for G-P sheathing; h/w ratio shall not exceed 2:1. For S-W panel bracing of the same material on two faces of the wall, the minimum length is permitted to be one-half the tabulated value but the h/w ratio shall not exceed 2:1 and design for uplift is required.
- G-P = gypsum board, fiberboard, particleboard, lath and plaster or gypsum sheathing boards; S-W = wood structural panels and diagonal wood sheathing.
- Nailing as specified below shall occur at all panel edges at studs, at top and bottom plates and, where occurring, at blocking:
For 1/2-inch gypsum board, 5d (0.113 inch diameter) cooler nails at 7 inches on center;
For 5/8-inch gypsum board, No. 11 gage (0.120 inch diameter) at 7 inches on center;
For gypsum sheathing board, 13/4 inches long by 7/16-inch head, diamond point galvanized nails at 4 inches on center;
For gypsum lath, No. 13 gage (0.092 inch) by 11/8 inches long, 19/64-inch head, plasterboard at 5 inches on center;
For Portland cement plaster, No. 11 gage (0.120 inch) by 11/2 inches long, 7/16- inch head at 6 inches on center;
For fiberboard and particleboard, No. 11 gage (0.120 inch) by 11/2 inches long, 7/16-inch head, galvanized nails at 3 inches on center.
- Where exterior braced wall panels are not in one plane vertically from the foundation to the uppermost story in which they are required, the structure shall be considered to be irregular [see Figure 2308.12.6(1)].
Exception: Floors with cantilevers or setbacks not exceeding four times the nominal depth of the floor joists [see Figure 2308.12.6(2)] are permitted to support braced wall panels provided:
- Floor joists are 2 inches by 10 inches (51 mm by 254 mm) or larger and spaced not more than 16 inches (406 mm) o.c.
- The ratio of the back span to the cantilever is at least 2:1.
- Floor joists at ends of braced wall panels are doubled.
- A continuous rim joist is connected to the ends of cantilevered joists. The rim joist is permitted to be spliced using a metal tie not less than 0.058 inch (1.47 mm) (16 galvanized gage) and 11/2 inches (38 mm) wide fastened with six 16d common nails on each side. The metal tie shall have a minimum yield of 33,000 psi (227 MPa).
- Joists at setbacks or the end of cantilevered joists shall not carry gravity loads from more than a single story having uniform wall and roof loads, nor carry the reactions from headers having a span of 8 feet (2438 mm) or more.
- Where a section of floor or roof is not laterally supported by braced wall lines on all edges, the structure shall be considered to be irregular [see Figure 2308.12.6(3)].
Exception: Portions of roofs or floors that do not support braced wall panels above are permitted to extend up to 6 feet (1829 mm) beyond a braced wall line [see Figure 2308.12.6(4)].
- Where the end of a required braced wall panel extends more than 1 foot (305 mm) over an opening in the wall below, the structure shall be considered to be irregular. This requirement is applicable to braced wall panels offset in plane and to braced wall panels offset out of plane as permitted by the exception to Item 1 above in this section [see Figure 2308.12.6(5)].
Exception: Braced wall panels are permitted to extend over an opening not more than 8 feet (2438 mm) in width where the header is a 4-inch by 12-inch (102 mm by 305 mm) or larger member.
- Where portions of a floor level are vertically offset such that the framing members on either side of the offset cannot be lapped or tied together in an approved manner, the structure shall be considered to be irregular [see Figure 2308.12.6(6)].
Exception: Framing supported directly by foundations need not be lapped or tied directly together.
- Where braced wall lines are not perpendicular to each other, the structure shall be considered to be irregular [see Figure 2308.12.6(7)].
- Where openings in floor and roof diaphragms having a maximum dimension greater than 50 percent of the distance between lines of bracing or an area greater than 25 percent of the area between orthogonal pairs of braced wall lines are present, the structure shall be considered to be irregular [see Figure 2308.12.6(8)].
BRACED WALL PANELS OUT OF PLANE
BRACED WALL PANELS SUPPORTED BY CANTILEVER OR SET BACK
FLOOR OR ROOF NOT SUPPORTED ON ALL EDGES
ROOF OR FLOOR EXTENSION BEYOND BRACED WALL LINE
BRACED WALL PANEL EXTENSION OVER OPENING
PORTIONS OF FLOOR LEVEL OFFSET VERTICALLY
BRACED WALL LINES NOT PERPENDICULAR
OPENING LIMITATIONS FOR FLOOR AND ROOF DIAPHRAGMS