ADOPTS WITH AMENDMENTS:

International Building Code 2018 (IBC 2018)

Heads up: There are no amended sections in this chapter.

Chapter 33 Safeguards During Construction

AMENDMENT
This section has been amended at the state or city level.
CALIFORNIA BUILDING CODE — MATRIX ADOPTION TABLE
CHAPTER 33 — SAFEGUARDS DURING CONSTRUCTION

(Matrix Adoption Tables are nonregulatory, intended only as an aid to the code user. See Chapter 1 for state agency authority and building applications.)
Adopting agency BSC BSC-
CG
SFM HCD DSA OSHPD BSCC DPH AGR DWR CEC CA SL SLC
1 2 1/AC AC SS SS/CC 1 1R 2 3 4 5
Adopt entire chapter X X X X X X X X X X
Adopt entire chapter as
amended (amended
sections listed below)
Adopt only those sections
that are listed below
X X X
Chapter / Section
3301 X X
3302 X X
3303 X X
3304 X X
3304.1.5 X
3305 X X
3306 X X
3306.2 X
3307 X X
3308 X X
3310
The state agency does not adopt sections identified with the following symbol:
The Office of the State Fire Marshal's adoption of this chapter or individual sections is applicable to structures regulated by other state agencies pursuant to Section 1.11.



User note:
About this chapter: While the balance of the chapters in this code specify how a building is to be designed and constructed in order to be in compliance with the code, Chapter 33 looks to the actual construction process. Parameters are provided for demolition and for protecting adjacent property during demolition and construction. Issues such as how to provide egress while the building is growing, the timing of standpipe and sprinkler installation, and protection of pedestrians are addressed.

Code development reminder: Code change proposals to sections preceded by the designation [BS] will be considered by the IBC—Structural Code Development Committee during the 2019 (Group B) Code Development Cycle. See explanation on page ix.


3301.1 Scope

AMENDMENT
This section has been amended at the state or city level.
The provisions of this division shall govern safety during construction and the protection of adjacent public and private properties.

This section shall not be construed to waive the requirements of the General Safety Orders of the Department of Industrial Relations of the State of California, or the provisions of California Civil Code Section 832 concerning the rights of coterminous owners as to excavations.

See Division 70, Article 1, Chapter IX of the LAMC for all grading, excavation and fill requirements.

Construction equipment and materials shall be stored and placed so as not to endanger the public, the workers or adjoining property for the duration of the construction project.

Required exits, existing structural elements, fire protection devices and sanitary safeguards shall be maintained at all times during alterations, repairs or additions to any building or structure.

Exceptions:

  1. Where such required elements or devices are being altered or repaired, adequate substitute provisions shall be made.
  2. Maintenance of such elements and devices is not required where the existing building is not occupied.
Waste materials shall be removed in a manner that prevents injury or damage to persons, adjoining properties and public rights-of-way.

3302.3 Fire Safety During Construction

AMENDMENT
This section has been amended at the state or city level.
Fire safety during construction shall comply with the applicable requirements of this code and the applicable provisions of Chapter 33 of the California Fire Code.
Construction documents and a schedule for demolition shall be submitted where required by the building official. Where such information is required, work shall not be done until such construction documents or schedule, or both, are approved.
The work of demolishing any building shall not be commenced until pedestrian protection is in place as required by this chapter.
A horizontal exit shall not be destroyed unless and until a substitute means of egress has been provided and approved.
Where a structure has been demolished or removed, the vacant lot shall be filled and maintained to the existing grade or in accordance with the ordinances of the jurisdiction having authority.
Provision shall be made to prevent the accumulation of water or damage to any foundations on the premises or the adjoining property.
Service utility connections shall be discontinued and capped in accordance with the approved rules and the requirements of the applicable governing authority.

3303.7 Fire Safety During Demolition

AMENDMENT
This section has been amended at the state or city level.
Fire safety during demolition shall comply with the applicable requirements of this code and the applicable provisions of Chapter 33 of the California Fire Code.
Excavation and fill for buildings and structures shall be constructed or protected so as not to endanger life or property. Stumps and roots shall be removed from the soil to a depth of not less than 12 inches (305 mm) below the surface of the ground in the area to be occupied by the building. Wood forms that have been used in placing concrete, if within the ground or between foundation sills and the ground, shall be removed before a building is occupied or used for any purpose. Before completion, loose or casual wood shall be removed from direct contact with the ground under the building.
Slopes for permanent fill shall be not steeper than one unit vertical in two units horizontal (50-percent slope). Cut slopes for permanent excavations shall be not steeper than one unit vertical in two units horizontal (50-percent slope). Deviation from the foregoing limitations for cut slopes shall be permitted only upon the presentation of a soil investigation report acceptable to the building official.
Fill or other surcharge loads shall not be placed adjacent to any building or structure unless such building or structure is capable of withstanding the additional loads caused by the fill or surcharge. Existing footings or foundations that can be affected by any excavation shall be underpinned adequately or otherwise protected against settlement and shall be protected against lateral movement.
For footings on adjacent slopes, see Chapter 18.

3304.1.4 Fill Supporting Foundations

AMENDMENT
This section has been amended at the state or city level.
Fill to be used to support the foundations of any building or structure shall comply with CBC Section 1804.6 and Division 70, Article 1, Chapter IX of the LAMC. Special inspections of compacted fill shall be in accordance with CBC Section 1705.6.

3304.1.5 [HCD 1] Storm Water Drainage and Retention During Construction

AMENDMENT
This section has been amended at the state or city level.
Projects which disturb less than one acre of soil and are not part of a larger common plan of development which in total disturbs one acre or more, shall manage storm water drainage during contsruction in accordance with the California Green Building Standards Code (CALGreen), Chapter 4, Division 4.1.

Section 3305 Sanitary Toilet Facilities During Construction

AMENDMENT
This section has been amended at the state or city level.

3305.1 Toilet Facilities Required

AMENDMENT
This section has been amended at the state or city level.
No person shall commence or proceed with the erection, construction, alteration, repair, raising, adding to, removal or demolition of any building or structure unless adequate, suitable, sanitary toilet facilities under the control of that person are provided for the use of any person employed or working upon the building or structure. The toilet facilities shall be located upon or within a reasonable distance of the lot, premises, or site upon which the work is being done. In no case shall the line of travel to any toilet facility exceed 500 feet (152.4 m).

3305.2 Toilet Standards

AMENDMENT
This section has been amended at the state or city level.
Every toilet shall be of the water-flush type and connected to a public sewer or a private sewage disposal system built in accordance with the provisions of the Plumbing Code. All toilet structures shall be completely enclosed on four sides and the top, and the door shall be self-closing; the toilet floor shall be smooth, and screened ventilation shall be provided for the toilet compartment. Where workers are employed during the night hours, the toilet building shall be provided with artificial light. In lieu of flush water closets, approved chemical toilets, which meet the requirements of Chapter III of the Los Angeles Municipal Code, may be provided.

[BS] 3306.1 Protection Required

AMENDMENT
This section has been amended at the state or city level.
Pedestrians shall be protected during construction, remodeling and demolition activities as required by Division 33, Article 1, Chapter IX of the Los Angeles Municipal Code and CBC Table 3306.1. Signs shall be provided to direct pedestrian traffic.

Nothing contained in this section shall be construed to grant permission to use, construct or place a canopy over any street or public place without first obtaining the necessary permits from the Department of Public Works.

[BS] 3306.2 Walkways

AMENDMENT
This section has been amended at the state or city level.
A walkway shall be provided for pedestrian travel in front of every construction and demolition site unless the applicable governing authority authorizes the sidewalk to be fenced or closed. A walkway shall be provided for pedestrian travel that leads from a building entrance or exit of an occupied structure to a public way.Walkways shall be of sufficient width to accommodate the pedestrian traffic, but shall be not less than 4 feet (1219 mm) in width. Walkways shall be provided with a durable walking surface. Walkways shall be accessible in accordance with Chapter 11A or 11B as applicable, and shall be designed to support all imposed loads, and the design live load shall be not less than 150 pounds per square foot (psf) (7.2 kN/m2).
Pedestrian traffic shall be protected by a directional barricade where the walkway extends into the street. The directional barricade shall be of sufficient size and construction to direct vehicular traffic away from the pedestrian path.
Construction railings shall be not less than 42 inches (1067 mm) in height and shall be sufficient to direct pedestrians around construction areas.
Barriers shall be not less than 8 feet (2438 mm) in height and shall be placed on the side of the walkway nearest the construction. Barriers shall extend the entire length of the construction site. Openings in such barriers shall be protected by doors that are normally kept closed.

Barriers shall be designed to resist loads required in Chapter 16 unless constructed as follows:

  1. Barriers shall be provided with 2-inch by 4-inch (51 mm by 102 mm) top and bottom plates.
  2. The barrier material shall be boards not less than 3/4-inch (19.1 mm) thick or wood structural panels not less than 1/4-inch (6.4 mm) thick.
  3. Wood structural use panels shall be bonded with an adhesive identical to that for exterior wood structural use panels.
  4. Wood structural use panels 1/4 inch (6.4 mm) or 5/16 inch (23.8 mm) in thickness shall have studs spaced not more than 2 feet (610 mm) on center.
  5. Wood structural use panels 3/8 inch (9.5 mm) or 1/2 inch (12.7 mm) in thickness shall have studs spaced not more than 4 feet (1219 mm) on center provided that a 2-inch by 4-inch (51 mm by 102 mm) stiffener is placed horizontally at mid-height where the stud spacing is greater than 2 feet (610 mm) on center.
  6. Wood structural use panels 5/8 inch (15.9 mm) or thicker shall not span over 8 feet (2438 mm).

Covered walkways shall have a clear height of not less than 8 feet (2438 mm) as measured from the floor surface to the canopy overhead. Adequate lighting shall be provided at all times. Covered walkways shall be designed to support all imposed loads. The design live load shall be not less than 150 psf (7.2 kN/m2) for the entire structure.

Exception: Roofs and supporting structures of covered walkways for new, light-frame construction not exceeding two stories above grade plane are permitted to be designed for a live load of 75 psf (3.6kN/m2) or the loads imposed on them, whichever is greater. In lieu of such designs, the roof and supporting structure of a covered walkway are permitted to be constructed as follows:

  1. Footings shall be continuous 2-inch by 6-inch (51 mm by 152 mm) members.
  2. Posts not less than 4 inches by 6 inches (102 mm by 152 mm) shall be provided on both sides of the roof and spaced not more than 12 feet (3658 mm) on center.
  3. Stringers not less than 4 inches by 12 inches (102 mm by 305 mm) shall be placed on edge upon the posts.
  4. Joists resting on the stringers shall be not less than 2 inches by 8 inches (51 mm by 203 mm) and shall be spaced not more than 2 feet (610 mm) on center.
  5. The deck shall be planks not less than 2 inches (51 mm) thick or wood structural panels with an exterior exposure durability classification not less than 23/32 inch (18.3 mm) thick nailed to the joists.
  6. Each post shall be knee braced to joists and stringers by members not less than 2 inches by 4 inches (51 mm by 102 mm); 4 feet (1219 mm) in length.
  7. A curb that is not less than 2 inches by 4 inches (51 mm by 102 mm) shall be set on edge along the outside edge of the deck.
Pedestrian protection required by this chapter shall be maintained in place and kept in good order for the entire length of time pedestrians are subject to being endangered. The owner or the owner's authorized agent, on completion of the construction activity, shall immediately remove walkways, debris and other obstructions and leave such public property in as good a condition as it was before such work was commenced.
Every excavation on a site located 5 feet (1524 mm) or less from the street lot line shall be enclosed with a barrier not less than 6 feet (1829 mm) in height. Where located more than 5 feet (1524 mm) from the street lot line, a barrier shall be erected where required by the building official. Barriers shall be of adequate strength to resist wind pressure as specified in Chapter 16.

[BS] 3307.1 Protection Required

AMENDMENT
This section has been amended at the state or city level.
Adjoining public and private property shall be protected from damage during construction, remodeling and demolition work. Protection must be provided for footings, foundations, party walls, chimneys, skylights and roofs. Provisions shall be made to control water runoff and erosion during construction or demolition activities.

For excavations, adjacent property shall be protected as set forth in Section 832 of the Civil Code of California.

Prior to the issuance of any permit, which authorizes an excavation where the excavation is to be of a greater depth than are the walls or foundation of any adjoining building or structure and located closer to the property line than the depth of the excavation, the owner of the site shall provide the Department of Building and Safety with evidence that the adjacent property owner or owners have been given a 30-day written notice of the intent to excavate. This notice shall state the depth to which the excavation is intended to be made and when the excavation will commence. This notice shall be by certified mail, return receipt requested.

3307.2 Underpinning

AMENDMENT
This section has been amended at the state or city level.

3307.2.1 General

AMENDMENT
This section has been amended at the state or city level.
In constructing underpinning, all portions of the structure shall be supported so that no structural material is stressed beyond the yield point.

3307.2.2 Closure

AMENDMENT
This section has been amended at the state or city level.
All spaces between the existing footing and the underpinning shall be packed full of mortar conforming to the provisions of CBC Section 2103 and having no slump when tested by the method specified in ASTM C 143.

3307.3 Temporary Excavations and Shoring

AMENDMENT
This section has been amended at the state or city level.

3307.3.1 General

AMENDMENT
This section has been amended at the state or city level.
Excavations shall not remove the lateral support from a public way, from an adjacent property or from an existing structure. For the purpose of this section, the lateral support shall be considered to have been removed when any of the following conditions exist:
  1. The excavation exposes any adverse geological formations, which would affect the lateral support of a public way, an adjacent property or an adjacent structure.
  2. The excavation extends below a plane extending downward at an angle of 45 degrees from the edge of the public way or an adjacent property.
    EXCEPTION: Normal footing excavations not exceeding two feet in depth will not be construed as removing lateral support.
  3. The excavation extends below a plane extending downward at an angle of 45 degrees from the bottom of a footing of an existing structure.

3307.3.2 Removal of Lateral Support

AMENDMENT
This section has been amended at the state or city level.
Approval of the Department of Public Works shall be obtained prior to the issuance of a permit for any excavation that would remove the lateral support from a public way.

The slopes of excavations adjacent to an existing structure, an adjacent property or public way may exceed one horizontal to one vertical where either:
  1. A soil report recommending that the slope may be in excess of one to one has been approved by the Department and the Department of Public Works when the excavation is adjacent to a public way.

    When justified by the soils engineer, the Department may approve the use of the proposed building and/or shoring to support an adjacent structure on an adjoining property in lieu of underpinning, provided:
    1. Evidence is submitted that the adjoining property owner has been notified in advance of the proposed excavation in compliance with Section 832 of the Civil Code of California.
    2. The owner of the site records a sworn affidavit with the Office of the County Recorder, which will inform future owners of the site that the lateral support of a portion of the building footings on the adjoining property is provided by the subterranean walls of the building on the site.
  2. Underpinning is designed to support adjacent structures, temporary shoring is designed to support the excavation, and plans are approved and permits are issued by the Department.

    Temporary shoring shall be designed for an earth pressure recommended by a soils engineer and approved by the Department, equivalent to that exerted by a fluid weighing not less than 24 pounds (11 kg) per cubic foot plus all surcharge loads.

    Soils bearing values shall be those specified in Division 18, Article 1, Chapter IX of the LAMC or those recommended by a soils engineer and approved by the Department.

    The design of the required temporary shoring and necessary underpinning shall include a sequence of construction and installation.

    Allowable stresses used in the design of temporary shoring may be increased 33-1/3% for structural and reinforcing steel and 25% for wood. No increase will be permitted for concrete. Other values shall be those prescribed by this Code.
The temporary use of streets or public property for the storage or handling of materials or of equipment required for construction or demolition, and the protection provided to the public shall comply with the provisions of the applicable governing authority and this chapter.
Construction materials and equipment shall not be placed or stored so as to obstruct access to fire hydrants, standpipes, fire or police alarm boxes, catch basins or manholes, nor shall such material or equipment be located within 20 feet (6096 mm) of a street intersection, or placed so as to obstruct normal observations of traffic signals or to hinder the use of public transit loading platforms.
Building materials, fences, sheds or any obstruction of any kind shall not be placed so as to obstruct free approach to any fire hydrant, fire department connection, utility pole, manhole, fire alarm box or catch basin, or so as to interfere with the passage of water in the gutter. Protection against damage shall be provided to such utility fixtures during the progress of the work, but sight of them shall not be obstructed.

Structures under construction, alteration or demolition shall be provided with not fewer than one approved portable fire extinguisher in accordance with Section 906 and sized for not less than ordinary hazard as follows:

  1. At each stairway on all floor levels where combustible materials have accumulated.
  2. In every storage and construction shed.
  3. Additional portable fire extinguishers shall be provided where special hazards exist, such as the storage and use of flammable and combustible liquids.

[F] 3309.2 Fire Hazards

AMENDMENT
This section has been amended at the state or city level.
The provisions of this code and the California Fire Code shall be strictly observed to safeguard against all fire hazards attendant upon construction operations.
Where building construction exceeds 40 feet (12 192 mm) in height above the lowest level of fire department vehicle access, a temporary or permanent stairway shall be provided. As construction progresses, such stairway shall be extended to within one floor of the highest point of construction having secured decking or flooring.

Means of egress and required accessible means of egress shall be maintained at all times during construction, demolition, remodeling or alterations and additions to any building.

Exception: Existing means of egress need not be maintained where approved temporary means of egress systems and facilities are provided.

In buildings required to have standpipes by Section 905.3.1, not fewer than one standpipe shall be provided for use during construction. Such standpipes shall be installed prior to construction exceeding 40 feet (12 192 mm) in height above the lowest level of fire department vehicle access. Such standpipes shall be provided with fire department hose connections at locations adjacent to stairways complying with Section 3310.1. As construction progresses, such standpipes shall be extended to within one floor of the highest point of construction having secured decking or flooring.
Where a building is being demolished and a standpipe exists within such a building, such standpipe shall be maintained in an operable condition so as to be available for use by the fire department. Such standpipe shall be demolished with the building but shall not be demolished more than one floor below the floor being demolished.

Standpipes shall be installed in accordance with the provisions of Chapter 9.

Exception: Standpipes shall be either temporary or permanent in nature, and with or without a water supply, provided that such standpipes conform to the requirements of Section 905 as to capacity, outlets and materials.

In buildings where an automatic sprinkler system is required by this code, it shall be unlawful to occupy any portion of a building or structure until the automatic sprinkler system installation has been tested and approved, except as provided in Section 111.3.
Operation of sprinkler control valves shall be permitted only by properly authorized personnel and shall be accompanied by notification of duly designated parties. When the sprinkler protection is being regularly turned off and on to facilitate connection of newly completed segments, the sprinkler control valves shall be checked at the end of each work period to ascertain that protection is in service.
An approved water supply for fire protection, either temporary or permanent, shall be made available as soon as combustible material arrives on the site.
Where required by the fire code official, a fire watch shall be provided during nonworking hours for construction that exceeds 40 feet (12 192 mm) in height above the lowest adjacent grade.
UpCodes Premium
Leverage the most sophisticated code compliance platform.
TRY FREE FOR TWO WEEKS VISIT PRICING