Adopting agency | BSC | BSC-CG | SFM | HCD | DSA | OSHPD | BSCC | DPH | AGR | DWR | CEC | CA | SL | SLC | |||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
1 | 2 | 1/AC | AC | SS | SS/CC | 1 | 1R | 2 | 3 | 4 | 5 | ||||||||||||
Adopt entire chapter | |||||||||||||||||||||||
Adopt entire chapter as amended (amended sections listed below) | X | X | X | X | X | X | |||||||||||||||||
Adopt only those sections that are listed below | |||||||||||||||||||||||
Chapter / Section | |||||||||||||||||||||||
1701.1.1 | X | X | X | ||||||||||||||||||||
1701.1.2 | X | X | X | ||||||||||||||||||||
1701.1.3 | X | X | X | ||||||||||||||||||||
1703.4 | X | X | X | ||||||||||||||||||||
1704.2, Exception 5 | X | X | |||||||||||||||||||||
1704.2, Exceptions 3 & 4 | X | X | X | ||||||||||||||||||||
1704.2.3 | X | ||||||||||||||||||||||
1704.2.3 Exception | X | X | X | ||||||||||||||||||||
1704.2.4 | X | X | X | ||||||||||||||||||||
1704.2.5.1 | X | X | X | ||||||||||||||||||||
1704.3.2 | X | X | X | ||||||||||||||||||||
1705.2.1 | X | X | X | ||||||||||||||||||||
1705.2.3.1 | X | X | X | ||||||||||||||||||||
1705.2.4.1 | X | X | X | ||||||||||||||||||||
1705.2.5 | X | X | X | ||||||||||||||||||||
1705.2.6 | X | X | X | ||||||||||||||||||||
1705.3 Exception | X | X | X | ||||||||||||||||||||
1705.3.3 | X | X | X | ||||||||||||||||||||
1705.3.3.1 | X | X | X | ||||||||||||||||||||
Table 1705.3 | X | X | X | ||||||||||||||||||||
1705.3.4 | X | X | X | ||||||||||||||||||||
1705.3.5 | X | X | X | ||||||||||||||||||||
1705.3.6 | X | X | X | ||||||||||||||||||||
1705.3.7 | X | X | X | ||||||||||||||||||||
1705.3.8 | X | X | X | ||||||||||||||||||||
1705.4 | X | X | X | ||||||||||||||||||||
1705.4.1 | X | X | X | ||||||||||||||||||||
1705.5.3 | X | X | X | ||||||||||||||||||||
1705.5.4 | X | X | X | ||||||||||||||||||||
1705.5.5 | X | X | X | ||||||||||||||||||||
1705.5.6 | X | X | X | ||||||||||||||||||||
1705.6.1 | X | X | X | ||||||||||||||||||||
1705.7.1 | X | X | X | ||||||||||||||||||||
1705.13.1.1 Exception | X | X | X | ||||||||||||||||||||
1705.13.1.2 Exception | X | X | X | ||||||||||||||||||||
1705.13.3.1 | X | X | X | ||||||||||||||||||||
1705.13.2 | X | X | X | ||||||||||||||||||||
1705.17 | X | X | X | ||||||||||||||||||||
1705.19 | X | X | X | ||||||||||||||||||||
1705.19.1 | X | X | X | ||||||||||||||||||||
1707.1 | X | X | X |
The Office of the State Fire Marshal's adoption of this chapter or individual sections is applicable to structures regulated by other state agencies pursuant to Section 1.11.
User notes:
About this chapter: Chapter 17 provides a variety of procedures and criteria for testing materials and assemblies, and labeling materials and assemblies. Its key purposes are to establish where additional inspections/observations and testing must be provided, and the submittals and verifications that must be provided to the building official. This chapter expands on the inspections of Chapter 1 by requiring special inspection by a qualified individual where indicated and, in some cases, structural observation by a registered design professional. Quality assurance measures that verify proper assembly of structural components and the suitability of the installed materials are intended to provide a building that, once constructed, complies with the minimum structural and fire-resistance code requirements as well as the approved design. To determine this compliance often requires frequent inspections and testing at specific stages of construction.
Code development reminder: Code change proposals to sections preceded by the designation [BF] will be considered by the IBC—Fire Safety Code Development Committee during the 2018 (Group A) Code Development Cycle. Sections preceded by the designation [F] will be considered by the International Fire Code Development Committee during the 2018 (Group A) Code Development Cycle. All other code change proposals will be considered by the IBC—Structural Code Development Committee during the Group B cycle. See explanation on page ix.
The provisions of this chapter shall govern the quality, workmanship and requirements for materials covered. Materials of construction and tests shall conform to the applicable standards listed in this code.
Structures regulated by the Office of Statewide Health Planning and Development (OSHPD), which include hospital buildings removed from general acute care service, skilled nursing facility buildings, intermediate care facility buildings and acute psychiatric hospital buildings as listed in Sections 1.10.1, 1.10.2 and 1.10.5.
Single-story Type V skilled nursing or intermediate care facilities utilizing wood-frame or light-steel-frame construction as defined in Health and Safety Code Section 129725 need not comply with [OSHPD 2] amendments, except those in Sections 1701.1, 1703.4, 1704.2, 1705.3.3, 1705.5.3, 1705.13.3.1.
[OSHPD 2] — For applications listed in Section 1.10.2.
[OSHPD 5] — For applications listed in Section 1.10.5.
- Form. Application for a Certificate of Registration shall be made on a form furnished by the Department.
- Information Necessary. The application shall bear the name and address of the applicant and, if the applicant is employed by a firm, partnership or corporation, the names of the principal officers should also be included. The application shall carry other information deemed necessary by the Department.
- Verification. The applicant shall declare that the information contained in the application is true and correct.
- Fee. The application shall be accompanied by an examination fee of $188.
- Examination Required. Before issuance of a Certificate of Registration, the applicant shall have successfully passed the examination required for the issuance of the Certificate of Registration within ninety (90) days preceding the date of the issuance. To be eligible for the examination for a Certificate of Registration, the applicant shall have a valid California State Contractor's License in an appropriate specialty and a valid City Business Tax Certificate.
- Board of Examiners. The Superintendent of Building and/or Board of Examiners composed of three qualified persons appointed by the Superintendent of Building shall conduct examinations. The results of every examination shall be subject to the approval of the Superintendent of Building. Each examiner shall serve at the pleasure of the Superintendent of Building and shall serve for a period of one year unless re-appointed by the Superintendent of Building. (Amended by Ord. No. 185,587, Eff. 7/16/18.)
- Scope of Examination. The examination shall, in the judgment of the Superintendent of Building, fairly determine the ability of the applicant to perform properly the work, which he or she would be authorized to do by the Certificate of Registration requested, and may include the following:
- A written test.
- Practical tests as may be required.
- An oral interview as may be required.
- Other tests as may be required by the Board of Examiners.
- Time of Examination. The applicant shall be examined as soon as practicable after filing an application.
- Rules and Regulations. The Department shall have the authority to establish rules and regulations for the conduct of examinations.
- Fitness of Applicant. Any applicant may be required to submit satisfactory proof of his or her fitness to carry out the intent of this Code.
- Failure to Pass. An applicant who fails to pass an examination shall not be eligible for another examination until four (4) weeks after taking the previous examination.
- The Superintendent of Building shall issue separate Certificates of Registration for each of the following categories:
- FAU/AC units; evaporative coolers.
- Domestic water piping/plumbing fixtures/hot water heaters/solar panels.
- Reroofing and roof repair.
- Electrical equipment/fixtures/smoke detectors.
- Masonry and concrete fences.
- Masonry chimney repairs.
- Shower pan replacement.
- Upon payment of a $45 fee, the Department may issue a Certificate of Registration to every applicant who passes the required examination for a Certified Licensed Contractor.
- Each Certificate of Registration shall expire twelve (12) months from the date of issuance.
- The Superintendent of Building shall keep on file a list, open to public inspection, of the names of all registered certified licensed contractors, showing the type of work each has been authorized to inspect.
- Renewal of Certificates. Expired Certificates of Registration may be renewed at any time within thirty (30) days following the date of expiration. After a Certificate of Registration has been expired for thirty (30) days, it may not be renewed; rather, a new application for a new certificate must be submitted at that time.
- Every person having a fixed place of business shall keep his or her Certificate of Registration posted in some conspicuous location at his or her place of business during the time the certificate is in force.
- Every person not having a fixed place of business shall carry his or her Certificate of Registration with him or her at all times while doing any inspections or other work pursuant to this certificate.
The Superintendent of Building may revoke, suspend or refuse to renew any Certificate of Registration upon a showing of incompetence, willful or negligent failure to observe or report violations of this Code, or failure to maintain a valid active California State Contractor's License in the same specialty as the certification. Prior to any action, the holder shall be given an opportunity to appear before the Superintendent of Building and be heard.
Suspension or revocation of any Certificate of Registration issued under this Section shall be in accordance with the provisions of Article 8, Chapter IX of the LAMC.
Where application is made to the building official for construction as specified in Section 105, or 1.8.4, as applicable, the owner or the owner's authorized agent, other than the contractor, shall employ one or more approved agencies to provide special inspections and tests during construction on the types of work specified in Section 1705 and identify the approved agencies to the building official. These special inspections and tests are in addition to the inspections by the building official that are identified in Section 110.
[OSHPD 1R, 2 & 5] In addition, the approved agencies shall provide special inspections and tests during construction on the types of work listed under Chapters 17, 18, 19, 20, 21, 22, 23 and 25, and noted in the Test, Inspection and Observation (TIO) program as required by the Office.
The inspectors shall act under the direction of the architect or structural engineer or both, and be responsible to the Owner. Where California Administrative Code Section 7-115(a) 2 permits construction documents to be prepared under the responsible charge of a mechanical, electrical or civil engineer, inspectors shall be permitted to work under the direction of an engineer in the appropriate branch as permitted therein.
Where application is made for construction as described in this section, the owner or the registered design professional in responsible charge acting as the owner's agent shall employ one or more Registered Deputy Inspectors to perform inspections during construction on the types of work listed under CBC Section 1705. The Registered Deputy Inspector shall be a qualified person as set forth in LAMC Subsection 91.1704.2.1 and shall demonstrate competence to the satisfaction of the Superintendent of Building for inspection of the particular type of construction or operation requiring special inspection.
The special inspections shall be in addition to the inspections made by the employees of the Department as set forth in LAMC Section 91.108.
All special inspections shall be made by a Registered Deputy Inspector. Whenever the term "Special Inspector" is used in this Code, it shall mean "Registered Deputy Inspector" as described in LAMC Subdivision 91.1704.2.1.
Exceptions:
- Special inspections and tests are not required for construction of a minor nature or as warranted by conditions in the jurisdiction as approved by the building officialSuperintendent of Building.
- Unless otherwise required by the building officialSuperintendent of Building, special inspections and tests are not required for Group U occupancies that are accessory to a residential occupancy including, but not limited to, those listed in CBC Section 312.1.
- Special inspections and tests are not required for portions of structures designed and constructed in accordance with the cold-formed steel light-frame construction provisions of CBC Section 2211.71.2 or the conventional light-frame construction provisions of CBC Section 2308. [OSHPD 1R, 2 & 5] Not permitted by OSHPD.
- The contractor is permitted to employ the approved agencies where the contractor is also the owner. [OSHPD 1R, 2 & 5] Not permitted by OSHPD.
- [HCD 1] The provisions of Health and Safety Code Division 13, Part 6 and the California Code of Regulations, Title 25, Division 1, Chapter 3, commencing with Section 3000, shall apply to the construction and inspection of factory-built housing as defined in Health and Safety Code Section 19971.
Prior to the start of the construction, the approved agencies shall provide written documentation to the building official demonstrating the competence and relevant experience or training of the special inspectors who will perform the special inspections and tests during construction. Experience or training shall be considered to be relevant where the documented experience or training is related in complexity to the same type of special inspection or testing activities for projects of similar complexity and material qualities. These qualifications are in addition to qualifications specified in other sections of this code.
The registered design professional in responsible charge and engineers of record involved in the design of the project are permitted to act as the approved agency and their personnel are permitted to act as special inspectors for the work designed by them, provided they qualify as special inspectors.
An applicant for Deputy Inspector shall provide written documentation to the Superintendent of Building demonstrating his or her competence and relevant experience or training. Experience or training shall be considered relevant when the documented experience or training is related in complexity to the same type of special inspection activities for projects of similar complexity and material qualities. These qualifications are in addition to qualifications specified in other sections of this Code.
Application for registration as a Registered Deputy Inspector shall be made to the Superintendent of Building on a form furnished by the Department. A separate application shall be made for each type of registration desired. Registration is available for the following types of inspections: Reinforced Concrete (RC), Structural Masonry (SM), Structural Steel/Welding (SSW), Grading (GD), Sprayed Fire resistant Materials (SFRM), Methane Barrier (MB) and Wood (WD).
A committee appointed by the Superintendent of Building shall examine each applicant as to his or her experience and training for performing the duties of an inspector of the type for which application has been made. Additionally, the applicant will be examined on the applicant's knowledge of the LAMC and Registered Deputy Inspector duties, responsibilities and procedures. When satisfied as to the fitness of the applicant, the Superintendent of Building shall issue a Certificate of Registration. Upon application for renewal of a Certificate of Registration, the applicant shall be re-examined to ascertain the applicant's fitness to perform the duties of inspector of the type for which application has been made.
Nothing here shall be deemed to prohibit any one person from being qualified for more than one type of special inspection, provided he or she applies, pays the required fees, takes the required examinations and is duly qualified by the Superintendent of Building for each type.
Each Certificate of Registration shall expire three (3) years from the date of issuance, but may be renewed by the Superintendent of Building within a grace period of thirty (30) days thereafter.
The Department shall maintain a list of the names of all Registered Deputy Inspectors, showing the type of work each has been authorized to inspect. This list shall be available to the public.
Upon evidence satisfactory to the Superintendent of Building of incompetence, of willful or negligent failure to observe or report violations of this Code, or of any other failure to perform properly and effectively the duties assumed by a Registered Deputy Inspector, the Superintendent of Building may revoke, suspend or refuse to renew any Certificate of Registration. But, prior to that action, the holder shall be given an opportunity to appear before the Superintendent of Building and be heard.
Except where there is a City employee inspecting buildings or structures being erected or repaired by the City, no Registered Deputy Inspector shall receive any compensation from the City. A Registered Deputy Inspector shall undertake and perform the duties of inspection solely on the request of the owner or the owner's agent. The designation shall be deemed to indicate that the duties incident to the inspection are within the course and scope of the Registered Deputy Inspector's employment by the owner or agent, and except where the Registered Deputy Inspector is in fact an employee of the City, the Registered Deputy Inspector shall not be deemed an employee of the City, a contractor, a subcontractor or a material vendor for any purpose.
The registered design professional in responsible charge and engineers of record involved in the design of the project are permitted to act as the supervising agency and their personnel are permitted to act as the deputy inspector for the work designed by them, provided they qualify as Registered Deputy Inspectors.
- The Registered Deputy Inspector employed on any work must be present during the execution of all the work the Registered Deputy Inspector has undertaken to inspect. The Registered Deputy Inspector shall notify the Department of the commencement of inspection of a job and shall specify the type of inspection for which the Registered Deputy Inspector has been engaged. This notification shall be made no later than the last working day preceding the commencement of inspection. The Registered Deputy Inspector shall report to the job sufficiently in advance of construction to review the plans and to inspect all materials to be used or concealed within the work, shall inspect the construction, erection, placing or other use of the materials, and shall observe whether there is compliance with the Code as to all of the foregoing. During the execution of the work, the Registered Deputy Inspector shall not undertake or engage in any other task or occupation that will interfere with the proper performance of his or her duties relating to the inspections. The Registered Deputy Inspector shall report, as directed, to the Superintendent of Building, noting all violations of this Code that have occurred and any other information as may be required. At the conclusion of the Registered Deputy Inspector's duties on any project, which has been completed in accordance with this Code, the Registered Deputy Inspector shall submit a report to the Department setting forth the portion of the work inspected. The report shall be made on forms supplied by the Department and shall be filed with the Department. (Amended by Ord. No. 185,587, Eff. 7/16/18.)
- Nothing here shall be deemed to authorize any Registered Deputy Inspector to approve any inspection required by this Code, other than the special inspection for which the Registered Deputy Inspector was hired and is of the type for which the Registered Deputy Inspector is registered. (Amended by Ord. No. 185,587, Eff. 7/16/18.)
- Where, in the opinion of the Department, the magnitude or complexity of a job warrants it, additional Registered Deputy Inspectors may be required.
- Where, in the opinion of the Department, the Registered Deputy Inspector is negligent in the performance of the Deputy Inspector's duties, the job shall be stopped.
- Nothing herein shall be deemed to authorize any Registered Deputy Inspector to approve the pouring of concrete, the placement of masonry, structural steel or fill prior to the approval of the regular building inspector.
- New Application. Before accepting any application for registration as a Registered Deputy Inspector, the Department shall collect a new examination fee of $528. A separate application shall be submitted and a separate examination fee shall be collected for each additional type of registration desired. When the applicant passes the examination(s), a Certificate(s) of Registration for each type of examination passed shall be issued. If the applicant fails to pass an examination, the applicant may reapply and again pay the examination fees. No refund(s) will be given to the applicant after the Department has administered the examination(s).
- Renewal Application. Before renewing a Certificate of Registration as a Registered Deputy Inspector, the Department shall collect a renewal Registration and examination fee in the amount of $482. A separate application shall be submitted and a separate examination fee shall be collected for each additional type of renewal registration desired. When the applicant passes the examination(s), a Certificate(s) of Registration for each type of examination passed shall be issued. If the applicant fails to pass the examination(s), the applicant may reapply; however, the applicant must again pay the renewal Registration and examination fees before the Department can issue the Certificate of Registration(s). No refund(s) will be given to applicant after the Department has administered the examination.
- International Code Council (ICC) Certification(s). International Code Council (ICC) Certification(s) is required prior to taking the Department's new or renewal examination(s). In addition to ICC's certification, the Department's examination will be required for each type of registration and fees collected as specified in this Section.
Exception: If the ICC does not have an examination for a Department registration, the applicant will be required to take the Department examination only.
The ICC Certification may not be required when the Department registration is utilized by the Department of Public Works for City business only.
The permit applicant shall submit a statement of special inspections in accordance with Section 107.1, Chapter 1, Division II,LAMC Subsection 91.106.3.3. The statement of special inspections shall be prepared by the registered design professional in responsible charge as a condition for permit issuance. This statement shall be in accordance with Section LAMC Subsection 91.1704.3.
- A statement of special inspections is not required for portions of structures designed and constructed in accordance with the cold-formed steel light-frame construction provisions of CBC Section 2211.1.2 or the conventional light-frame construction provisions of LAMC Section 91.2308 [OSHPD 1R, 2 & 5]Not permitted by OSHPD.
Where special inspections or tests are required by Section 1705, the registered design professional in responsible charge shall prepare a statement of special inspections in accordance with Section 1704.3.1 for submittal by the applicant in accordance with Section 1704.2.3.
Exception: The statement of special inspections is permitted to be prepared by a qualified person approved by the building official for construction not designed by a registered design professional.
The statement of special inspections shall identify the following:
- The materials, systems, components and work required to have special inspections or tests by the building official or by the registered design professional responsible for each portion of the work.
- The type and extent of each special inspection.
- The type and extent of each test.
- Additional requirements for special inspections or tests for seismic or wind resistance as specified in Sections 1705.11, 1705.12 and 1705.13.
- For each type of special inspection, identification as to whether it will be continuous special inspection, periodic special inspection or performed in accordance with the notation used in the referenced standard where the inspections are defined.
[OSHPD 1R, 2 & 5] Where Section 1705.12 or 1705.13 specifies special inspections or tests for seismic resistance, the statement of special inspections shall identify the equipment/components that require special seismic certification and seismic force-resisting systems that are subject to the special inspection or tests.
In addition to the submittal of reports of special inspections and tests in accordance with Section 1704.2.4, reports and certificates shall be submitted by the owner or the owner's authorized agent to the building official for each of the following:
- Certificates of compliance for the fabrication of structural, load-bearing or lateral load-resisting members or assemblies on the premises of an approved fabricator in accordance with Section 1704.2.5.1.
- Certificates of compliance for the seismic qualification of nonstructural components, supports and attachments in accordance with Section 1705.13.2.
- Certificates of compliance for designated seismic systems in accordance with Section 1705.13.3.
- Reports of preconstruction tests for shotcrete in accordance with Section 1908.5.
- Certificates of compliance for open web steel joists and joist girders in accordance with Section 2207.5.
- Reports of material properties verifying compliance with the requirements of AWS D1.4 for weldability as specified in Section 26.6.4 of ACI 318 for reinforcing bars in concrete complying with a standard other than ASTM A706 that are to be welded.
- Reports of mill tests in accordance with Section 20.2.2.5 of ACI 318 for reinforcing bars complying with ASTM A615 and used to resist earthquake-induced flexural or axial forces in the special moment frames, special structural walls or coupling beams connecting special structural walls of seismic force-resisting systems in structures assigned to Seismic Design Category B, C, D, E or F.
Where required by the provisions of LAMC Subsections 91.1704.6.1, 91.1704.6.2 or 91.1704.6.3, the owner or the owner's authorized agent shall employ the a registered design professional in responsible charge for the structural design, or another registered design professional designated by the registered design professional in responsible charge of the structural design to perform structural observations as defined in CBC Section 202. to perform structural observations. Structural observation does not include or waive the responsibility for the inspections in Section 110 or the special inspections in Section 1705 or other sections of this code.
Prior to the commencement of observations, the structural observer shall submit to the Superintendent of Building a written statement identifying the frequency and extent of proposed structural observations.
At the conclusion of the work included in the permit, the structural observer shall submit to the building official a written statement that the site visits have been made and identify any reported deficiencies that, to the best of the structural observer's knowledge, have not been resolved.
The owner or owner's representative shall coordinate and call a preconstruction meeting between the engineer or architect responsible for the structural design, structural observer, contractor, affected subcontractors and deputy inspectors. The structural observer shall preside over the meeting. The purpose of the meeting shall be to identify the major structural elements and connections that affect the vertical and lateral load systems of the structure and to review scheduling of the required observations. A record of the meeting shall be included in the first report submitted to the Superintendent of Building.
Observed deficiencies shall be reported, in writing, to the owner's representative, Registered Deputy Inspector, contractor and the Superintendent of Building. Upon the form prescribed by the Superintendent of Building, the structural observer shall submit to the Superintendent of Building a written statement at each significant construction stage stating that the site visits have been made and identify any reported deficiencies which, to the best of the structural observer's knowledge, have not been resolved. A final report by the structural observer, which states that all observed deficiencies have been resolved, is required before acceptance of the work by the Superintendent of Building.
Structural observations shall be provided for those structures where one or more of the following conditions exist:
- The structure is classified as Risk Category IV.
- The structure is a high-rise building.
- Such observation is required by the registered design professional responsible for the structural design.
- Such observation is specifically required by the building official.
Structural observations shall be provided for those structures assigned to Seismic Design Category D, E or F where one or more of the following conditions exist:
- The structure is classified as Risk Category III or IV.
- The structure is assigned to Seismic Design Category E, is classified as Risk Category I or II, and is greater than two stories above the grade planeclassified as Risk Category I or II in accordance with CBC Table 1604.5, and a lateral design is required for the structure or portion thereof.
- When so designated by the registered design professional responsible for the structural design.
- When such observation is specifically required by the Department.
Special inspections and tests shall be required for proposed work that is, in the opinion of the building official, unusual in its nature, such as, but not limited to, the following examples:
- Construction materials and systems that are alternatives to materials and systems prescribed by this code.
- Unusual design applications of materials described in this code.
- Materials and systems required to be installed in accordance with additional manufacturer's instructions that prescribe requirements not contained in this code or in standards referenced by this code.
Inspections by Department Approved Special Activity Inspectors will be required in accordance with regulations promulgated by the Superintendent of Building where:
- The structure is more than five stories or 60 feet (18,288 mm) in height.
- The structure exceeds 50,000 square feet (4645 m2) of ground area or 200,000 square feet (18 580 m2) of total floor area.
- Nondestructive structural testing methods are utilized.
- The quality identification markings of the materials used are not inspectable after installation.
- The manner of use of materials precludes full inspection after installation.
Exception: The Department may waive continuous or periodic inspection required by this Section where minor quantities are involved and no unusual hazards exist.
- In addition to the projects included in the above categories, the Superintendent of Building may require Special Activity inspections if the Superintendent of Building determines that these inspections are needed to ensure compliance with the provisions of this Code and the work involves:
- Unique, novel or innovative construction;
- Highly complex or intricate construction;
- Unique, novel or innovative grading, earth support or foundation procedures; or
- New methods of construction not yet provided for in the rules and regulations.
The special inspections and nondestructive testing of steel construction in buildings, structures, and portions thereof shall be in accordance with this section.
Exception: Special inspections of the steel fabrication process shall not be required where the fabrication process for the entire building or structure does not include any welding, thermal cutting or heating operation of any kind. In such cases, the fabricator shall be required to submit a detailed procedure for material control that demonstrates the fabricator's ability to maintain suitable records and procedures such that, at any time during the fabrication process, the material specification and grade for the main stress-carrying elements are capable of being determined. Mill test reports shall be identifiable to the main stress-carrying elements where required by the approved construction documents.
Special inspections and nondestructive testing of structural steel elements in buildings, structures and portions thereof shall be in accordance with the quality assurance inspection requirements of AISC 360.
Exception: Special inspection of railing systems composed of structural steel elements shall be limited to welding inspection of welds at the base of cantilevered rail posts.
AISC 360, Chapter N and AISC 341, Chapter J are adopted, except as noted below:
The following provisions of AISC 360, Chapter N are not adopted:
- N4, Item 2 (Quality Assurance Inspector Qualifications).
- N5, Item 2 (Quality Assurance).
- N5, Item 3 (Coordinated Inspection).
- N5, Item 4 (Inspection of Welding).
- N6 (Approved Fabricators and Erectors).
- N7 (Nonconforming Material and Workmanship).
Special inspections of open-web steel joists and joist girders in buildings, structures and portions thereof shall be in accordance with Table 1705.2.3.
TYPE | CONTINUOUS SPECIAL INSPECTION |
PERIODIC SPECIAL INSPECTION |
REFERENCED STANDARDa |
1.Installation of open-web steel joists and joist girders. | |||
a. End connections — welding or bolted. | — | X | SJI specifications listed in Section 2207.1. |
b. Bridging — horizontal or diagonal. | — | — | — |
1.Standard bridging. | — | X | SJI specifications listed in Section 2207.1. |
2.Bridging that differs from the SJI
specifications listed in Section 2207.1.
|
— | X | — |
For SI: 1 inch = 25.4 mm.
- Where applicable, see Section 1705.12, Special inspections for seismic resistance.
The welding inspector shall make a systematic daily record of all welds. This record shall include:
- Identification marks of welders.
- List of defective welds.
- Manner of correction of defects.
Special inspections and tests of concrete construction shall be performed in accordance with this section and LAMC Table 1705.3.
Exception: Special inspections and tests shall not be required for: [OSHPD 1R, 2 & 5] Exceptions 1 through 4 are not permitted by OSHPD.
- Isolated spread concrete footings of buildings three stories or less above grade plane that are fully supported on earth or rock, where the structural design of the footing is based on a specified compressive strength, f'c, no greater than 2,500 pounds per square inch (psi) (17.2 MPa).
-
Continuous concrete footings supporting walls of buildings three stories or less above grade plane that are fully supported on earth or rock where:
- 2.1. The footings support walls of light-frame construction.
- 2.2. The footings are designed in accordance with LAMC Table 1809.7.; or
- 2.3. The structural design of the footing is based on a specified compressive strength, f 'c, not more than 2,500 pounds per square inch (psi) (17.2 MPa), regardless of the compressive strength specified in the approved construction documents or used in the footing construction.
- Nonstructural concrete slabs supported directly on the ground, including prestressed slabs on grade, where the effective prestress in the concrete is less than 150 psi (1.03 MPa).
- Concrete foundation walls constructed in accordance with CBC Table 1807.1.6.2.
- Concrete patios, driveways and sidewalks, on grade.
TYPE | CONTINUOUS SPECIAL INSPECTION |
PERIODIC SPECIAL INSPECTION | REFERENCED STANDARDa | LAIBC REFERENCE |
1. Inspect reinforcement, including prestressing tendons, and verify placement. |
— | X | ACI 318: Ch. 20, 25.2, 25.3, 26.6.1-26.6.3 | 1908.4 |
2. Reinforcing bar welding: | X | |||
|
— | X | AWS D1.4 | |
|
X | ACI 318: 26.6.4 | — | |
|
X | |||
3. Inspect anchors cast in concrete. | — | X | ACI 318: 17.8.2 | — |
4. Inspect anchors post-installed in hardened concrete members.b | ||||
|
X | X | ACI 318: 17.8.2.4 | — |
|
X | ACI 318: 17.8.2 | ||
5. Verify use of required design mix. | — | X | ACI 318: Ch. 19, 26.4.3, 26.4.4 | 1904.1, 1904.2, 1908.2, 1908.3 |
6. Prior to concrete placement, fabricate specimens for strength tests, perform slump and air content tests, and determine the temperature of the concrete. | X | — | ASTM C172 ASTM C31 ACI 318: 26.5, 26.12 |
1908.10 |
7. Inspect concrete and shotcrete placement for proper application techniques. | X | — | ACI 318: 26.5 | 1908.6, 1908.7, 1908.8 |
8. Verify maintenance of specified curing temperature and techniques. | — | X | ACI 318: 26.5.3-26.5.5 | 1908.9 |
9.Inspect prestressed concrete for: | ||||
|
X | — | ACI 318: 26.10 | — |
|
X |
|||
10. Inspect erection of precast concrete members. | — | X | ACI 318: 26.9 | — |
11. Verify in-situ concrete strength, prior to stressing of tendons in post-tensioned concrete and prior to removal of shores and forms from beams and structural slabs. | — | X | ACI 318: 26.11.2 | — |
12. Inspect formwork for shape, location and dimensions of the concrete member being formed. | — | X | ACI 318: 26.11.1.2(b) | — |
For SI: 1 inch = 25.4 mm.
- Where applicable, see CBC Section 1705.12, Special inspections for seismic resistance.
- Specific requirements for special inspection shall be included in the research report for the anchor issued by an approved source in accordance with 17.8.2 in ACI 318, or other qualification procedures. Where specific requirements are not provided, special inspection requirements shall be specified by the registered design professional and shall be approved by the building official prior to the commencement of the work.
During the construction of all buildings over 160 feet (48.768 m) in height with concrete special moment-resisting space frames, a structural inspector under the supervision of the engineer responsible for the structural design shall be present to inspect the materials and workmanship for conformance with approved plans, specifications and change orders involved in construction of the ductile frames and shear walls. This inspection may be made by one or more structural inspectors, provided that at least one structural inspector is present during the placement of all concrete and reinforcement in the structural frame and shear walls.
The number of structural inspectors to be provided for each structure shall be determined by the engineer responsible for the structural design, provided that more than one structural inspector shall be provided where the magnitude of a structure prevents a single inspector from adequately performing the inspection.
The owner shall provide each structural inspector. Each structural inspector shall be paid by the owner directly or through the person responsible for the structural design. Each structural inspector shall be responsible to the person who prepared the structural design.
The inspection by the structural inspector or inspectors shall be in addition to inspections made by Department employees as specified in LAMC Section 91.108 and by Registered Deputy Inspectors as specified for other parts of the work in LAMC Section 91.1704.
Prior to the issuance of the Certificate of Occupancy, each structural inspector shall submit a report in writing to the engineer and the Department certifying that the portions of the structural frame inspected by the inspector were constructed in accordance with the approved plans, specifications, change orders and Division 19, Article 1, Chapter IX of the LAMC.
- The concrete plant complies fully with the requirements of ASTM C94, Sections 9 and 10, and has a current certificate from the National Ready Mixed Concrete Association or another agency acceptable to the enforcement agency. The certification shall indicate that the plant has automatic batching and recording capabilities.
- For single-story light-framed construction (without basement or retaining walls higher than 6 feet in height measured from bottom of footing to top of wall) and isolated foundations supporting equipment only, where deep foundation elements are not used.
- An approved agency shall check the first batch at the start of the day to verify materials and proportions conform to the approved mix design.
- A licensed weighmaster shall positively identify quantity of materials and certify each load by a batch ticket.
- Batch tickets, including material quantities and weights, shall accompany the load, shall be transmitted to the inspector of record by the truck driver with load identified thereon. The load shall not be placed without a batch ticket identifying the mix. The inspector of record shall keep a daily record of placements, identifying each truck, its load, time of receipt at the job site and approximate location of deposit in the structure and shall maintain a copy of the daily record as required by the enforcement agency.
- In addition to the general inspection required for concrete work, all plant fabrication of prestressed concrete members or tensioning of post-tensioned members constructed at the site shall be continuously inspected by an inspector specially approved for this purpose by the enforcement agency.
Exception: The special inspector need not be continuously present for the placement of prestress or post-tensioned cables or tendons. - The prestressed concrete plant fabrication inspector shall check the materials, equipment, tensioning procedure and construction of the prestressed members and prepare daily written reports. The approved agency shall make a verified report identifying the members by mark and shall include such pertinent data as lot numbers of tendons used, tendon jacking forces, age and strength of concrete at time of tendon release and such other information that may be required.
- The inspector of prestressed members post-tensioned at the site shall check the condition of the prestressing tendons, anchorage assemblies and concrete in the area of the anchorage, the tensioning equipment and the tensioning procedure and prepare daily written reports. The approved agency shall make a verified report of the prestressing operation identifying the members or tendons by mark and including such pertinent data as the initial cable slack, net elongation of tendons, jacking force developed, and such other information as may be required.
- The verified reports of construction shall show that of the inspector's own personal knowledge, the work covered by the report has been performed and materials used and installed in every material respect in compliance with the duly approved plans and specifications for plant fabrication inspection. The verified report shall be accompanied by test reports required for materials used. For site post-tensioning inspections the verified report shall be accompanied by copies of calibration charts, certified by an approved testing laboratory, showing the relationship between gage readings and force applied by the jacks used in the prestressing procedure
Special inspections and tests of masonry construction shall be performed in accordance with the quality assurance program requirements of TMS 402 and TMS 602, [OSHPD 1R, 2 & 5] as set forth in Tables 3 and 4, Level 3 requirements, and Chapter 21. Testing shall be performed in accordance with Section 2105. Special inspection and testing of post-installed anchors in masonry shall be required in accordance with requirements for concrete in Chapters 17 and 19.
Exception: [OSHPD 1R, 2 & 5] Not permitted by OSHPD. Special inspections and tests shall not be required for:
- Empirically designed masonry, glass unit masonry or masonry veneer designed in accordance with Section 2109, 2110 or Chapter 14, respectively, where they are part of a structure classified as Risk Category I, II or III.
- Masonry foundation walls constructed in accordance with Table 1807.1.6.3(1), 1807.1.6.3(2), 1807.1.6.3(3) or 1807.1.6.3(4).
- Masonry fireplaces, masonry heaters or masonry chimneys installed or constructed in accordance with Section 2111, 2112 or 2113, respectively.
[OSHPD 1R, 2 & 5] Glass unit masonry and masonry veneer in Risk Category II, III or IV. Special inspections and tests for glass unit masonry or masonry veneer designed by Section 2110 or Chapter 14, respectively, in structures classified as Risk Category II, III or IV, shall be performed in accordance with TMS 602 Tables 3 and 4, Level 2 Quality Assurance.
The approved agency shall verify that proper quality control procedures and tests have been employed for all materials and the manufacturing process, and shall perform visual inspection of the finished product. Each inspected member shall be stamped by the approved agency with an identification mark.
The approved agency shall verify that proper quality control procedures and tests have been employed for all materials and the manufacturing process, and shall perform visual inspection of the finished product. Each inspected truss shall be stamped with an identification mark by the approved agency.
Special inspections defined per LAMC Subsections 91.7008.2 and 91.7011.3 and tests offor existing site soil conditions, fill placement and load-bearing requirements shall be as required by performed in accordance with this section and LAMC Table 1705.6. The approved geotechnical report and the construction documents prepared by the registered design professionals shall be used to determine compliance. During fill placement, the special inspector shall verifydetermine that proper materials and procedures are used in accordance with the provisions of the approved geotechnical report as specified in CBC Section 1803.6.
Exception: Where Section 1803 does not require reporting of materials and procedures for fill placement, the special inspector shall verify that the in-place dry density of the compacted fill is not less than 90 percent of the maximum dry density at optimum moisture content determined in accordance with ASTM D1557.
TABLE 1705.6
REQUIRED VERIFACATIONSPECIAL INSPECTIONS AND INSPECTION TESTS OF SOILS
TYPEVERIFICATION AND INSPECTION TASK | CONTINUOUS SPECIAL INSPECTIONDURING TASK LISTED |
PERIODICALLY SPECIAL INSPECTIONDURING TASK LISTED |
1.Verify materials below shallow foundations are adequate to achieve the design bearing capacity. | — | X |
2.Verify excavations are extended to proper depth and have reached proper material. | — | X |
3.Perform classification and testing of compacted fill materials. | — | X |
4.Verify use of proper materials, densities and lift thicknesses during placement and compaction of compacted fill. | Xa | — |
5.Prior to placement of compacted fill, inspectobserve subgrade and verify that site has been prepared properly. | — | X |
- Frequency of special inspections to be determined by the registered design professional responsible for the project.
The duties of the geotechnical engineer or his or her qualified representative shall include, but need not be limited to, the inspection of cleared areas and benches prepared to receive fill; inspection of the removal of all unsuitable soils and other materials; the approval of soils to be used as fill material; the inspection of placement and compaction of fill materials; the testing of the completed fills; and the inspection or review of geotechnical drainage devices, buttress fills or other similar protective measures in accordance with the approved construction documents.
A verified report shall be submitted by the geotechnical engineer as required by the California Administrative Code. The report shall indicate that all tests and inspections required by the approved construction documents were completed and whether the tested materials and/or inspected work meet the requirements of the approved construction documents.
- 1.1. A contiguous grading area exceeding 60,000 square feet (5574 m2).
- 1.2. An excavated or filled slope steeper than 2 horizontal in 1 vertical (50% slope).
- 1.3. An excavated slope exceeding 40 feet (12,192 mm) in height and the top of which is within 20 feet (6096 mm) of a property line coterminous with improved private property or a public way.
- 1.4. Foundation excavations below a 1 horizontal in 1 vertical plane inward and down from the property line.
Special inspections and tests shall be performed during installation ofand testing of the driven deep foundation elements as specified inby CBC Table 1705.7. The approved geotechnical report, required by CBC Section 1803.6 and the construction documents prepared by the registered design professionals shall be used to determine compliance. Special inspections for connecting grade beams shall be in accordance with LAMC Section 91.1705.3.
TABLE 1705.7
REQUIRED SPECIAL INSPECTIONS AND TESTS OF DRIVEN DEEP FOUNDATION ELEMENTS
TYPE | CONTINUOUS SPECIAL INSPECTION | PERIODIC SPECIAL INSPECTION |
1.Verify element materials, sizes and lengths comply with the requirements. | X | — |
2.Determine capacities of test elements and conduct additional load tests, as required. | X | — |
3.Inspect driving operations and maintain complete and accurate records for each element. | X | — |
4.Verify placement locations and plumbness, confirm type and size of hammer, record number of blows per foot of penetration, determine required penetrations to achieve design capacity, record tip and butt elevations and document any damage to foundation element. | X | — |
5.For steel elements, perform additional special inspections in accordance with Section 1705.2. | — | — |
6.For concrete elements and concrete-filled elements, perform tests and additional special inspections in accordance with Section 1705.3. | — | — |
7.For specialty elements, perform additional inspections as determined by the registered design professional in responsible charge. | — | — |
The representative of the geotechnical engineer shall make a report of the deep foundation pile-driving operation giving such pertinent data as the physical characteristics of the deep foundation pile-driving equipment, identifying marks for each deep foundation pile, total depth of embedment for each deep foundation; and when the allowable deep foundation pile loads are determined by a dynamic load formula, the design formula used, and the permanent penetration under the last 10 blows. One copy of the report shall be sent to the enforcement agency.
Special inspections and tests shall be performed during installation and testing of cast-in-place deep foundation elements as specified inby CBC Table 1705.8. The approved geotechnical report, required by CBC Section 1803.6 and the construction documents prepared by the registered design professionals shall be used to determine compliance. Special inspections for connecting grade beams shall be in accordance with LAMC Section 91.1705.3.
TABLE 1705.8
REQUIRED SPECIAL INSPECTIONS AND TESTS OF CAST-IN-PLACE DEEP FOUNDATION ELEMENTS
TYPE | CONTINUOUS SPECIAL INSPECTION | PERIODIC SPECIAL INSPECTION |
1. Inspect drilling operations and maintain complete and accurate records for each element. | X | — |
2. Verify placement locations and plumbness, confirm element diameters, bell diameters (if
applicable), lengths, embedment into bedrock (if applicable) and adequate end-bearing strata
capacity. Record concrete or grout volumes. |
X | — |
3. For concrete elements, perform tests and additional special inspections in accordance with Section 1705.3. | — | — |
Special inspections for wind resistance specified in Sections 1705.11.1 through 1705.11.3, unless exempted by the exceptions to Section 1704.2, are required for buildings and structures constructed in the following areas:
- In wind Exposure Category B, where Vasd as determined in accordance with Section 1609.3.1 is 120 miles per hour (52.8 m/sec) or greater.
- In wind Exposure Category C or D, where Vasd as determined in accordance with Section 1609.3.1 is 110 mph (49 m/sec) or greater.
Continuous special inspection is required during field gluing operations of elements of the main windforce-resisting system. Periodic special inspection is required for nailing, bolting, anchoring and other fastening of elements of the main windforce-resisting system, including wood shear walls, wood diaphragms, drag struts, braces and hold-downs.
Exception: Special inspections are not required for wood shear walls, shear panels and diaphragms, including nailing, bolting, anchoring and other fastening to other elements of the main windforce-resisting system, where the specified fastener spacing at panel edges is more than 4 inches (102 mm) on center.
Periodic special inspection is required for welding operations of elements of the main windforce-resisting system. Periodic special inspection is required for screw attachment, bolting, anchoring and other fastening of elements of the main windforce-resisting system, including shear walls, braces, diaphragms, collectors (drag struts) and hold-downs.
Exception: Special inspections are not required for cold-formed steel light-frame shear walls and diaphragms, including screwing, bolting, anchoring and other fastening to components of the windforce resisting system, where either of the following applies:
- The sheathing is gypsum board or fiberboard.
- The sheathing is wood structural panel or steel sheets on only one side of the shear wall, shear panel or diaphragm assembly and the fastener spacing of the sheathing is more than 4 inches (102 mm) on center (o.c.).
Periodic special inspection is required for fastening of the following systems and components:
- Roof covering, roof deck and roof framing connections.
- Exterior wall covering and wall connections to roof and floor diaphragms and framing.
Special inspections for seismic resistance shall be required as specified in Sections 1705.12.1 through 1705.12.9, unless exempted by the exceptions of Section 1704.2.
Exception: The special inspections specified in Sections 1705.12.1 through 1705.12.9 are not required for structures designed and constructed in accordance with one of the following:
- The structure consists of light-frame construction; the design spectral response acceleration at short periods, SDS, as determined in Section 1613.2.4, does not exceed 0.5; and the building height of the structure does not exceed 35 feet (10 668 mm).
- The seismic force-resisting system of the structure consists of reinforced masonry or reinforced concrete; the design spectral response acceleration at short periods, SDS, as determined in Section 1613.2.4, does not exceed 0.5; and the building height of the structure does not exceed 25 feet (7620 mm).
The structure is a detached one- or two-family dwelling not exceeding two stories above grade plane and does not have any of the following horizontal or vertical irregularities in accordance with Section 12.3 of ASCE 7:
- Single-pass fillet welds not exceeding 5/16-inch (7.9 mm) in size.
- Floor and roof deck welding.
Special inspections of structural steel in the seismic force-resisting systems in buildings and structures assigned to Seismic Design Category B, C, D, E or F shall be performed in accordance with the quality assurance requirements of AISC 341.
Exceptions:
- In buildings and structures assigned to Seismic Design Category B or C, special inspections are not required for structural steel seismic force-resisting systems where the response modification coefficient, R, designated for "Steel systems not specifically detailed for seismic resistance, excluding cantilever column systems" in ASCE 7, Table 12.2-1, has been used for design and detailing.
- In structures assigned to Seismic Design Category D, E, or F, special inspections are not required for structural steel seismic force-resisting systems where design and detailing in accordance with AISC 360 is permitted by ASCE 7, Table 15.4-1.
For buildings exceeding 160 feet (48,768 mm) in height, the engineer responsible for the structural design and the general contractor responsible for the construction, or their competent authorized representatives, shall make periodic inspections of the work at the site to verify general compliance with the approved plans, specifications and change orders. The engineer and general contractor shall submit a statement in writing to the Department stating that they know from personal knowledge that the materials installed and the structural work performed is in compliance with the approved plans, specifications and change orders.
The phrase "personal knowledge" as used above in reference to the engineer and general contractor means the knowledge resulting from the general observation by the engineer and the general supervision by the contractor of the work, as required by both in the superintendence of the building's construction, and as distinguished from the continuous personal superintendence of the special inspector and/or deputy inspector who are continuously at the site during the progress of the work. The exercise of reasonable diligence to obtain the facts is required and anyone who intentionally remains unaware may be charged with knowledge. The interpretation of personal knowledge as it applies to the special inspector and/or deputy inspector is that the inspector(s) must have actual personal knowledge that the requirements of the plans and specifications are being carried out, which is obtained by the inspector's continuous observation of the work of construction at the site in all stages of its progress.
Special inspections of structural steel elements in the seismic force-resisting systems of buildings and structures assigned to Seismic Design Category B, C, D, E or F other than those covered in Section 1705.12.1.1, including struts, collectors, chords and foundation elements, shall be performed in accordance with the quality assurance requirements of AISC 341.
Exceptions:
- In buildings and structures assigned to Seismic Design Category B or C, special inspections of structural steel elements are not required for seismic force-resisting systems with a response modification coefficient, R, of 3 or less.
- In structures assigned to Seismic Design Category D, E, or F, special inspections of structural steel elements are not required for seismic force-resisting systems where design and detailing other than AISC 341 is permitted by ASCE 7, Table 15.4-1. Special inspection shall be in accordance with the applicable referenced standard listed in ASCE 7, Table 15.4-1.
For the seismic force-resisting systems of structures assigned to Seismic Design Category C, D, E or F:
- Continuous special inspection shall be required during field gluing operations of elements of the seismic force-resisting system.
- Periodic special inspection shall be required for nailing, bolting, anchoring and other fastening of elements of the seismic force-resisting system, including wood shear walls, wood diaphragms, drag struts, braces, shear panels and hold-downs.
Exception: Special inspections are not required for wood shear walls, shear panels and diaphragms, including nailing, bolting, anchoring and other fastening to other elements of the seismic force-resisting system, where the fastener spacing of the sheathing is more than 4 inches (102 mm) on center.
For the seismic force-resisting systems of structures assigned to Seismic Design Category C, D, E or F, periodic special inspection shall be required for both:
- Welding operations of elements of the seismic force-resisting system.
- Screw attachment, bolting, anchoring and other fastening of elements of the seismic force-resisting system, including shear walls, braces, diaphragms, collectors (drag struts) and hold-downs.
Exception: Special inspections are not required for cold-formed steel light-frame shear walls and diaphragms, including screw installation, bolting, anchoring and other fastening to components of the seismic force-resisting system, where either of the following applies:
- The sheathing is gypsum board or fiberboard.
- The sheathing is wood structural panel or steel sheets on only one side of the shear wall, shear panel or diaphragm assembly and the fastener spacing of the sheathing is more than 4 inches (102 mm) on center.
Periodic special inspection is required for the erection and fastening of exterior cladding, interior and exterior nonbearing walls and interior and exterior veneer in structures assigned to Seismic Design Category D, E or F.
Exception: Periodic special inspection is not required for the following:
- Exterior cladding, interior and exterior nonbearing walls and interior and exterior veneer 30 feet (9144 mm) or less in height above grade or walking surface.
- Exterior cladding and interior and exterior veneer weighing 5 psf (24.5 N/m2) or less.
- Interior nonbearing walls weighing 15 psf (73.5 N/m2) or less.
Periodic special inspection of plumbing, mechanical and electrical components shall be required for the following:
- Anchorage of electrical equipment for emergency and standby power systems in structures assigned to Seismic Design Category C, D, E or F.
- Anchorage of other electrical equipment in structures assigned to Seismic Design Category E or F.
- Installation and anchorage of piping systems designed to carry hazardous materials and their associated mechanical units in structures assigned to Seismic Design Category C, D, E or F.
- Installation and anchorage of ductwork designed to carry hazardous materials in structures assigned to Seismic Design Category C, D, E or F.
- Installation and anchorage of vibration isolation systems in structures assigned to Seismic Design Category C, D, E or F where the approved construction documents require a nominal clearance of 1/4 inch (6.4 mm) or less between the equipment support frame and restraint.
Installation of mechanical and electrical equipment, including duct work, piping systems and their structural supports, where automatic fire sprinkler systems are installed in structures assigned to Seismic Design Category C, D, E or F to verify one of the following:
- 6.1. Minimum clearances have been provided as required by Section 13.2.3 ASCE/SEI 7.
- 6.2. A nominal clearance of not less than 3 inches (76 mm) has been be provided between fire protection sprinkler system drops and sprigs and: structural members not used collectively or independently to support the sprinklers; equipment attached to the building structure; and other systems' piping.
Where flexible sprinkler hose fittings are used, special inspection of minimum clearances is not required.
Testing for structural steel shall be in accordance with the quality assurance requirements of AISC 341 and the additional requirements in this Section. Nondestructive testing shall be performed by an approved agency and the written report, including the test results, shall be submitted for evaluation by the Superintendent of Building. The acceptance criteria for nondestructive testing shall be as required in AWS D1.1 as specified by the registered design professional.
Base metal thicker than 1.5 inches (38 mm), where subject to through-thickness weld shrinkage strains, shall be ultrasonically tested for discontinuities behind and adjacent to those welds after joint completion. Any material discontinuities shall be accepted or rejected on the basis of ASTM A 435 or ASTM A 898 (Level 1 criteria) and criteria as established by the registered design professional(s) in responsible charge, and the construction documents.
Nondestructive testing of structural steel in the seismic force-resisting systems in buildings and structures assigned to Seismic Design Category B, C, D, E or F shall be performed in accordance with the quality assurance requirements of AISC 341.
Exceptions: [OSHPD 1R, 2 & 5] Not permitted by OSHPD.
- In buildings and structures assigned to Seismic Design Category B or C, nondestructive testing is not required for structural steel seismic force-resisting systems where the response modification coefficient, R, designated for "Steel systems not specifically detailed for seismic resistance, excluding cantilever column systems" in ASCE 7, Table 12.2-1, has been used for design and detailing.
- In structures assigned to Seismic Design Category D, E, or F, nondestructive testing is not required for structural steel seismic force-resisting systems where design and detailing in accordance with AISC 360 is permitted by ASCE 7, Table 15.4-1.
Nondestructive testing of structural steel elements in the seismic force-resisting systems of buildings and structures assigned to Seismic Design Category B, C, D, E or F other than those covered in Section 1705.13.1.1, including struts, collectors, chords and foundation elements, shall be performed in accordance with the quality assurance requirements of AISC 341.
Exceptions: [OSHPD 1R, 2 & 5] Not permitted by OSHPD.
- In buildings and structures assigned to Seismic Design Category B or C, nondestructive testing of structural steel elements is not required for seismic force-resisting systems with a response modification coefficient, R, of 3 or less.
- In structures assigned to Seismic Design Category D, E or F, nondestructive testing of structural steel elements is not required for seismic force-resisting systems where design and detailing other than AISC 341 is permitted by ASCE 7, Table 15.4-1. Nondestructive testing of structural steel elements shall be in accordance with the applicable referenced standard listed in ASCE 7, Table 15.4-1.
[OSHPD 1R, 2 & 5] Seismic sway bracing components satisfying requirements of FM 1950 or using an alternative testing protocol approved by the building official shall be deemed to satisfy the requirements of this section.
- Special seismic certification shall be required for life-safety components, such as emergency and standby power systems, mechanical smoke removal systems, and fire sprinkler/fire protection systems.
- Medical, mechanical and electrical equipment and components required for life support for patients shall have special seismic certification in accordance with Section 1705A.13.3.
The special inspections and tests shall include the following to demonstrate compliance with the listing and the fire-resistance rating:
- Condition of substrates.
- Thickness of application.
- Density in pounds per cubic foot (kg/m3).
- Bond strength adhesion/cohesion.
- Condition of finished application.
The density of the sprayed fire-resistant material shall be not less than the density specified in the approved fire-resistance design. Density of the sprayed fire-resistant material shall be determined in accordance with ASTM E605. The test samples for determining the density of the sprayed fire-resistant materials shall be selected as follows:
- From each floor, roof and wall assembly at the rate of not less than one sample for every 2,500 square feet (232 m2) or portion thereof of the sprayed area in each story.
- From beams, girders, trusses and columns at the rate of not less than one sample for each type of structural member for each 2,500 square feet (232 m2) of floor area or portion thereof in each story.
Special inspections shall be required for all EIFS applications.
- Special inspections shall not be required for EIFS applications installed over a water-resistive barrier with a means of draining moisture to the exterior.
- Special inspections shall not be required for EIFS applications installed over masonry or concrete walls.
The test scope shall be as follows:
- During erection of ductwork and prior to concealment for the purposes of leakage testing and recording of device location.
- Prior to occupancy and after sufficient completion for the purposes of pressure difference testing, flow measurements and detection and control verification.
[BSC] In the absence of approved rules or other approved standards, the building official shall make, or cause to be made, the necessary tests and investigations; or the building official shall accept duly authenticated reports from approved agencies in respect to the quality and manner of use of new materials or assemblies as provided for in Section 1.2.1, Chapter 1, Division I. The cost of all tests and other investigations required under the provisions of this code shall be borne by the applicant.
In the absence of applicable load test procedures contained within a material standard referenced by this code or acceptance criteria for a specific material or method of construction, such existing structure shall be subjected to an approved test procedure developed by a registered design professional that simulates applicable loading and deformation conditions. For components that are not a part of the seismic force-resisting system, at a minimum the test load shall be equal to the specified factored design loads. For materials such as wood that have strengths that are dependent on load duration, the test load shall be adjusted to account for the difference in load duration of the test compared to the expected duration of the design loads being considered. For statically loaded components, the test load shall be left in place for a period of 24 hours. For components that carry dynamic loads (for example, machine supports or fall arrest anchors), the load shall be left in place for a period consistent with the component's actual function. The structure shall be considered to have successfully met the test requirements where the following criteria are satisfied:
- Under the design load, the deflection shall not exceed the limitations specified in Section 1604.3.
- Within 24 hours after removal of the test load, the structure shall have recovered not less than 75 percent of the maximum deflection.
- During and immediately after the test, the structure shall not show evidence of failure.
The test assembly shall be subjected to an increasing superimposed load equal to not less than two times the superimposed design load. The test load shall be left in place for a period of 24 hours. The tested assembly shall be considered to have successfully met the test requirements if the assembly recovers not less than 75 percent of the maximum deflection within 24 hours after the removal of the test load. The test assembly shall then be reloaded and subjected to an increasing superimposed load until either structural failure occurs or the superimposed load is equal to two and one-half times the load at which the deflection limitations specified in Section 1709.3.2 were reached, or the load is equal to two and one-half times the superimposed design load. In the case of structural components and assemblies for which deflection limitations are not specified in Section 1709.3.2, the test specimen shall be subjected to an increasing superimposed load until structural failure occurs or the load is equal to two and one-half times the desired superimposed design load. The allowable superimposed design load shall be taken as the lesser of:
- The load at the deflection limitation given in Section 1709.3.2.
- The failure load divided by 2.5.
- The maximum load applied divided by 2.5.
The design pressure rating of exterior windows and doors in buildings shall be determined in accordance with Section 1709.5.1 or 1709.5.2. For exterior windows and doors tested in accordance with Sections 1709.5.1 or 1709.5.2, required design wind pressures determined from ASCE 7 shall be permitted to be converted to allowable stress design by multiplying by 0.6.
Exception: Structural wind load design pressures for window units smaller than the size tested in accordance with Section 1709.5.1 or 1709.5.2 shall be permitted to be higher than the design value of the tested unit provided such higher pressures are determined by accepted engineering analysis. Components of the small unit shall be the same as the tested unit. Where such calculated design pressures are used, they shall be validated by an additional test of the window unit having the highest allowable design pressure.
The Department may allow the use of a certified installer if:
- The certified installer obtains a Certificate of Registration in accordance with the provisions of this section.
- The certified installer files with the Department a Certificate of Compliance for each dwelling unit for which certification is being made. The Certificate of Compliance shall be on a form provided by the Department and shall be signed by the property owner and the certified installer.
- The Certificate of Compliance processing fee is paid in accordance with LAMC Subsection 91.107.7.
- The certified installer files the Certificate of Compliance with the Department within 15 days after completion of the installation.
The Superintendent of Building or a Board of Examiners composed of qualified person(s) appointed by the Superintendent of Building shall conduct examinations.
The results of every examination shall be subject to the approval of the Superintendent.
Each examiner shall serve at the pleasure of the Superintendent of Building and shall serve for a period of one year unless reappointed by the Superintendent of Building.
- A written test.
- Practical tests as may be required.
- An oral interview as may be required.
- Other tests as may be required by the Board of Examiners.