ADOPTS WITH AMENDMENTS:

CPC 2019

Heads up: There are no amended sections in this chapter.
The provisions contained in this appendix are not mandatory unless specifically adopted by a state agency, or referenced in the adopting ordinance.

CALIFORNIA PLUMBING CODE - MATRIX ADOPTION TABLE
APPENDIX A - RECOMMENDED RULES FOR SIZING THE WATER SUPPLY SYSTEM

(Matrix Adoption Tables are non-regulatory, intended only as an aid to the code user. See Chapter 1 for state agency authority and building applications.)
Adopting Agency BSC BSC-CG SFM HCD DSA OSHPD BSCC DPH AGR DWR CEC CA SL SLC
1 2 1-AC AC SS SS/CC 1 1R 2 3 4 5
Adopt Entire Chapter X X X X X X X X X
Adopt Entire Chapter as amended (amended sections listed below)
Adopt only those sections that are listed below
Chapter/Section
This state agency does not adopt sections identified with the following symbol:
The Office of the State Fire Marshal's adoption of this chapter or individual sections is applicable to structures regulated by other state agencies pursuant to Section 1.11.0.
This appendix provides a general procedure for sizing a water supply system. Because of the variable conditions encountered, it is impractical to lay down definite detailed rules of procedure for determining the sizes of water supply pipes in an appendix, which shall necessarily be limited in length. For an adequate understanding of the problems involved, refer to Water-Distributing Systems for Buildings, Report BMS 79 of the National Bureau of Standards; and Plumbing Manual, Report BMS 66, also published by the National Bureau of Standards.
Obtain the necessary information regarding the minimum daily service pressure in the area where the building is to be located.
Where the building supply is to be metered, obtain information regarding friction loss relative to the rate of flow of meters in the range of sizes likely to be used. Friction-loss data is capable of being obtained from most manufacturers of water meters. Friction losses for disk-type meters shall be permitted to be obtained from Chart A102.2.

CHART A102.2
FRICTION LOSSES FOR DISK-TYPE WATER METERS


FLOW (gallons per minute)

For SI units: 1 inch = 25 mm, 1 pound-force per square inch= 6.8947 kPa, 1 gallon per minute = 0.06 L/s
Obtain available local information regarding the use of different kinds of pipe with respect both to durability and to decrease in capacity with the length of service in the particular water supply.
Estimate the supply demand for the building main, the principal branches and risers of the system by totaling the fixture units on each, Table A103.1, and then by reading the corresponding ordinate from Chart A103.1(1) or Chart A103.1(2), whichever is applicable.

TABLE A103.1
WATER SUPPLY FIXTURE UNITS (WSFU) AND MINIMUM FIXTURE BRANCH PIPE SIZES3
APPLIANCES, APPURTENANCES, OR FIXTURES2 MINIMUM FIXTURE
BRANCH PIPE
SIZE1,4
(inches)
Private Public ASSEMBLY6
Bathtub or Combination Bath/Shower (fill) 1/2 4.0 4.0 -
      3/4 inch Bathtub Fill Valve 3/4 10.0 10.0 -
Bidet 1/2 1.0 - -
Clothes Washer 1/2 4.0 4.0 -
Dental Unit, cuspidor 1/2 - 1.0 -
Dishwasher, domestic 1/2 1.5 1.5 -
Drinking Fountain or Water Cooler 1/2 0.5 0.5 0.75
Hose Bibb 1/2 2.5 2.5 -
Hose Bibb, each additionat7 1/2 1.0 1.0 -
Lavatory 1/2 1.0 1.0 1.0
Lawn Sprinkler, each head5 - 1.0 1.0 -
Mobile Home, each (minimum) - 12.0 - -
Sinks - - - -
      Bar 1/2 1.0 2.0 -
      Clinical Faucet 1/2 - 3.0 -
      Clinical Flushometer Valve with or without faucet 1 - 8.0 -
      Kitchen, domestic 1/2 1.5 1.5 -
      Laundry 1/2 1.5 1.5 -
      Service or Mop Basin 1/2 1.5 3.0 -
      Washup, each set of faucets 1/2 - 2.0 -
Shower per head 1/2 2.0 2.0 -
Urinal, 1.0 GPF Flushometer Valve 3/4 3.0 4.0 5.0
Urinal, greater than 1.0 GPF Flushometer Valve 3/4 4.0 5.0 6.0
Urinal, flush tank 1/2 2.0 2.0 3.0
Wash Fountain, circular spray 3/4 - 4.0 -
Water Closet, 1.6 GPF Gravity Tank 1/2 2.5 2.5 3.5
Water Closet, 1.6 GPF Flushometer Tank 1/2 2.5 2.5 3.5
Water Closet, 1.6 GPF Flushometer Valve 1 5.0 5.0 8.0
Water Closet, greater than 1.6 GPF Gravity Tank 1/2 3.0 5.5 7.0
Water Closet, greater than 1.6 GPF Flushometer Valve 1 7.0 8.0 10.0
For SI units: 1 inch = 25 mm
Notes:
  1. 1   Size of the cold branch pipe, or both the hot and cold branch pipes.
  2. 2   Appliances, appurtenances, or fixtures not included in this table shall be permitted to be sized by reference to fixtures having a similar flow rate and frequency of use.
  3. 3   The listed fixture unit values represent their total load on the cold water building supply. The separate cold water and hot water fixture unit value for fixtures having both cold and hot water connections shall be permitted to be three-quarters of the listed total value of the fixture.
  4. 4   The listed minimum supply branch pipe sizes for individual fixtures are the nominal (1.D.) pipe size.
  5. 5   For fixtures or supply connections likely to impose continuous flow demands, determine the required flow in gallons per minute (gpm) (L/s) and add it separately to the demand in gpm (L/s) for the distribution system or portions thereof.
  6. 6   Assembly [Public Use (see Table 422.1)].
  7. 7   Reduced fixture unit loading for additional hose bibbs is to be used where sizing total building demand and for pipe sizing where more than one hose bibb is supplied by a segment of water distribution pipe. The fixture branch to each hose bibb shall be sized by 2.5 fixture units.
CHART A103.1(1)
ESTIMATE CURVES FOR DEMAND LOAD


For SI units: 1 gallon per minute = 0.06 L/s


CHART A103.1(2)
ENLARGED SCALE DEMAND LOAD


For SI units: 1 gallon per minute = 0.06 L/s
Estimate continuous supply demands in gallons per minute (gpm) (L/s) for lawn sprinklers, air conditioners, etc., and add the sum to the total demand for fixtures. The result is the estimated supply demand of the building supply.

A104.1 Residual Pressures

AMENDMENT
This section has been amended at the state or city level.
Decide what is the desirable minimum residual pressure that shall be maintained at the highest fixture in the supply system. The available residual pressure shall be not less than 15 psi (103 kPa). Where fixtures, fixture fittings or both are installed that require residual pressure exceeding 15 psi (103 kPa), that minimum residual pressure shall be provided.
Determine the elevation of the highest fixture or group of fixtures above the water (street) main. Multiply this difference in elevation by 0.43. The result is the loss of static pressure in psi (kPa).
Subtract the sum of loss in static pressure and the residual pressure to be maintained at the highest fixture from the average minimum daily service pressure. The result will be the pressure available for friction loss in the supply pipes, where no water meter is used. Where a meter is to be installed, the friction loss in the meter for the estimated maximum demand should also be subtracted from the service pressure to determine the pressure loss available for friction loss in the supply pipes.
Determine the developed length of pipe from the water (street) main to the highest fixture. Where close estimates are desired, compute with the aid of Table A104.4(1), Table A104.4(2), or Table A104.4(3), whichever is applicable, the equivalent length of pipe for fittings in the line from the water (street) main to the highest fixture and add the sum to the developed length. The pressure available for friction loss in psi (kPa), divided by the developed lengths of pipe from the water (street) main to the highest fixture, times 100, will be the average permissible friction loss per 100 feet (30480 mm) length of pipe.

TABLE A104.4(1)
ALLOWANCE IN EQUIVALENT LENGTH OF PIPE FOR FRICTION LOSS IN VALVES AND THREADED FITTINGS*
EQUIVALENT LENGTH OF PIPE FOR VARIOUS FITTINGS
DIAMETER OF FITTING (inches) 90° STANDARD ELBOW (feet) 45° STANDARD ELBOW (feet) 90° STANDARD TEE (feet) COUPLING OR STRAIGHT RUN OF TEE (feet) GATE VALVE (feet) GLOBE VALVE (feet) ANGLE VALVE (feet)
3/8 1.0 0.6 1.5 0.3 0.2 8 4
1/2 2.0 1.2 3.0 0.6 0.4 15 8
3/4 2.5 1.5 4.0 0.8 0.5 20 12
1 3.0 1.8 5.0 0.9 0.6 25 15
11/4 4.0 2.4 6.0 1.2 0.8 35 18
11/2 5.0 3.0 7.0 1.5 1.0 45 22
2 7.0 4.0 10.0 2.0 1.3 55 28
21/2 8.0 5.0 12.0 2.5 1.6 65 34
3 10.0 6.0 15.0 3.0 2.0 80 40
4 14.0 8.0 21.0 4.0 2.7 125 55
5 17.0 10.0 25.0 5.0 3.3 140 70
6 20.0 12.0 30.0 6.0 4.0 165 80
For SI units: 1 inch = 25 mm, 1 foot = 304.8 mm, 1 degree = 0.017 rad
* Allowances are based on nonrecessed threaded fittings. Use one-half the allowances for recessed threaded fittings or streamlined solder fittings.


TABLE A104.4(2)
EQUIVALENT LENGTH OF COPPER TUBE SIZE CPVC PIPE FOR VARIOUS FITTINGS
DIAMETER OF FITTING (inches) 90 DEGREE ELBOW (feet) 45 DEGREE ELBOW (feet) COUPLING OR STRAIGHT RUN OF TEE (feet) 90 DEGREE STANDARD TEE (feet)
1/2 1.6 0.8 1.0 3.1
3/4 2.1 1.1 1.4 4.1
1 2.6 1.4 1.7 5.3
11/4 3.5 1.8 2.3 6.9
11/2 4.0 2.1 2.7 8.1
2 5.2 2.8 3.5 10.3
For SI units: 1 inch = 25 mm, 1 foot = 304.8 mm

TABLE A104.4(3)
EQUIVALENT LENGTH OF SCHEDULE 40 AND 80 CPVC PIPE FOR VARIOUS FITTINGS
DIAMETER OF FITTING (inches) 90 DEGREE ELBOW (feet) 45 DEGREE ELBOW (feet) COUPLING OR STRAIGHT RUN OF TEE (feet) 90 DEGREE STANDARD TEE (feet)
1/2 1.5 0.8 1.0 4.0
3/4 2.0 1.1 1.4 5.0
1 2.5 1.4 1.7 6.0
11/4 3.8 1.8 2.3 7.0
11/2 4.0 2.1 2.7 8.0
2 5.7 2.6 4.3 12.0
For SI units: 1 inch = 25 mm, 1 foot = 304.8 mm
Knowing the permissible friction loss per 100 feet (30 480 mm) of pipe and the total demand, the diameter of the building supply pipe shall be permitted to be obtained from Chart A105.1(1), Chart A105.1(2), Chart A105.1(3), Chart A105.1(4) Chart A105.1(5), Chart A105.1(6), or Chart A105.1(7), whichever is applicable. The diameter of pipe on or next above the coordinate point corresponding to the estimated total demand and the permissible friction loss will be the size needed up to the first branch from the building supply pipe.

CHART A105.1(1)


FRICTION LOSS IN HEAD (pounds-force per square inch) PER 100-FOOT LENGTH

For SI units: 1 inch = 25 nun, 1 gallon per minute = 0.06 L/s, I pound-force per square inch = 6.8947 kPa, 1 foot = 304.8 nun, 1 foot per second = 0.3048 m/s


CHART A105.1(2)


FRICTION LOSS IN HEAD (pounds-force per square inch) PER 100-FOOT LENGTH

For SI units: 1 inch = 25 mm, 1 gallon per minute = 0.06 L/s, 1 pound-force per square inch = 6.8947 kPa, 1 foot = 304.8 mm, 1 foot per second = 0.3048 m/s


CHART A105.1(3)


FRICTION LOSS IN HEAD (pounds-force per square inch) PER 100-FOOT LENGTH

For SI units: 1 inch = 25 mm, 1 gallon per minute = 0.06 L/s, 1 pound-force per square inch = 6.8947 kPa, 1 foot = 304.8 mm, 1 foot per second = 0.3048 m/s


CHART A105.1(4)


FRICTION LOSS IN HEAD (pounds-force per square inch) PER 100-FOOT LENGTH

For SI units: 1 inch = 25 mm, 1 gallon per minute = 0.06 L/s, 1 pound-force per square inch = 6.8947 kPa, 1 foot = 304.8 mm, 1 foot per second = 0.3048 m/s


CHART A105.1(5)


FRICTION LOSS IN HEAD (pounds-force per square inch) PER 100-FOOT LENGTH

For SI units: 1 inch = 25 mm, 1 gallon per minute = 0.06 L/s, 1 pound-force per square inch = 6.8947 kPa, 1 foot = 304.8 mm, 1 foot per second = 0.3048 m/s


CHART A105.1(6)


FRICTION LOSS IN HEAD (pounds-force per square inch) PER 100-FOOT LENGTH

For SI units: 1 inch = 25 mm, 1 gallon per minute = 0.06 L/s, 1 pound-force per square inch = 6.8947 kPa, 1 foot = 304.8 mm, 1 foot per second = 0.3048 m/s


CHART A105.1(7)


FRICTION LOSS IN HEAD (pounds-force per square inch) PER 100-FOOT LENGTH

For SI units: 1 inch = 25 mm, 1 gallon per minute = 0.06 L/s, 1 pound-force per square inch = 6.8947 kPa, 1 foot = 304.8 mm, 1 foot per second = 0.3048 m/s
Where copper tubing or copper alloy pipe is to be used for the supply piping and where the character of the water is such that slight changes in the hydraulic characteristics are expected, Chart A105.1(1) shall be permitted to be used.
Chart A105.1(2) shall be used for ferrous pipe with the most favorable water supply in regards to corrosion and caking. Where the water is hard or corrosive, Chart A105.1(3) or Chart A105.1(4) will be applicable. For extremely hard water, it will be advisable to make additional allowances for the reduction of the capacity of hot-water lines in service.
The required size of branches and risers shall be permitted to be obtained in the same manner as the building supply, by obtaining the demand load on each branch or riser and using the permissible friction loss computed in Section A104.0.
Where fixture branches to the building supply are sized for the same permissible friction loss per 100 feet (30480 mm) of pipe as the branches and risers to the highest level in the building and lead to the inadequate water supply to the upper floor of a building, one of the following shall be provided:
  1. Selecting the sizes of pipe for the different branches so that the total friction loss in each lower branch is approximately equal to the total loss in the riser, including both friction loss and loss in static pressure.
  2. Throttling each such branch using a valve until the preceding balance is obtained.
  3. Increasing the size of the building supply and risers above the minimum required to meet the maximum permissible friction loss.
The size of branches and mains serving flushometer tanks shall be consistent with sizing procedures for flush tank water closets.
Velocities shall not exceed 10 feet per second (ft/s) (3 m/s), except as otherwise approved by the Authority Having Jurisdiction.
Where a pressure-reducing valve is used in the building supply, the developed length of supply piping and the permissible friction loss shall be computed from the building side of the valve.
The allowances in Table A104.4(1) for fittings are based on non-recessed threaded fittings. For recessed threaded fittings and streamlined soldered fittings, one-half of the allowances given in the table will be ample.
Assume an office building of four stories and basement; pressure on the building side of the pressure-reducing valve of 55 psi (379 kPa) (after an allowance for reduced pressure falloff at peak demand); an elevation of highest fixture above the pressure-reducing valve of 45 feet (13716 mm); a developed length of pipe from the pressure-reducing valve to the most distant fixture of 200 feet (60960 mm); and fixtures to be installed with flush valves for water closets and stall urinals as follows:

     Where the pipe material and water supply are such that Chart A105.1(2) applies, the required diameter of the building supply is 31/2 inches (90 mm), and the required diameter of the branch to the hot-water heater is 11/2 inches (40 mm).

     The sizes of the various branches and risers shall be permitted to be determined in the same manner as the size of the building supply or the branch to the hot-water system, by estimating the demand for the riser or branch from Chart A103.1(1) or Chart A103.1(2) and applying the total demand estimate from the branch, riser, or section thereof to the appropriate flowchart.

A108.1 EXAMPLE
FIXTURE UNITS AND ESTIMATED DEMANDS
BUILDING SUPPLY DEMAND BRANCH TO HOT WATER SYSTEM
KIND OF FIXTURES NUMBER OF FIXTURES FIXTURE UNIT DEMAND TOTAL UNITS BUILDING SUPPLY DEMAND (gallons per minute) NUMBER OF FIXTURES FIXTURE UNIT DEMAND CALCULATION DEMAND (gallons per minute)
Water Closets 130 8.0 1040 - - - -
Urinals 30 4.0 120 - - - -
Showerheads 12 2.0 24 - 12 12 X 2 X 3/4 = 18 -
Lavatories 100 1.0 100 - 100 100 X 1 X 3/4 = 75 -
Service Sinks 27 3.0 81 - 27 27 X 3 X 3/4 = 61 -
Total - - 1365 252 - 154 55
For SI units : 1 gallon per minute = 0.06 L/s, 1 pound-force per square foot = 6.8947 kPa

Allowing for 15 psi (103 kPa) at the highest fixture under the maximum demand of 252 gallons per minute (15.90 L/s), the pressure available for friction loss is found by the following:

55 - [15 + (45 x 0.43)] = 20.65 psi (142.38 kPa)

The allowable friction loss per 100 feet (30480 mm) of the pipe is, therefore:

100 x 20.65 ÷ 200 = 10.32 psi (71.15 kPa)
UpCodes Premium
Leverage the most sophisticated code compliance platform.
TRY FREE FOR TWO WEEKS VISIT PRICING