ADOPTS WITH AMENDMENTS:

CPC 2019

Heads up: There are no amended sections in this chapter.
CALIFORNIA PLUMBING CODE - MATRIX ADOPTION TABLE
CHAPTER 16 - NONPOTABLE RAINWATER CATCHMENT SYSTEMS

(Matrix Adoption Tables are non-regulatory, intended only as an aid to the code user. See Chapter 1 for state agency authority and building applications.)
Adopting Agency BSC BSC-CG SFM HCD DSA OSHPD BSCC DPH AGR DWR CEC CA SL SLC
1 2 1-AC AC SS SS/CC 1 1R 2 3 4 5
Adopt Entire Chapter
Adopt Entire Chapter as
amended (amended sections
listed below)
X X X
Adopt only those sections
that are listed below
Chapter/Section
1601.1 X
1601.2 X X
1601.3 & Exceptions 1 & 2 X X X
1601.5 X X
1601.6 X X
1601.7 X X
1602.4 X X
1602.7 (Ref. 1602.7.3) X
1602.9.3 X
1602.9.4 X X
1602.9.6 X
1602.9.6.1 X X
Table 1602.9.6 X X
1603.4 X X
1603.5 X X
1603.6 X X
1603.7 A, B X X
1603.9 X X
1603.15 X
1604.1 - 1604.3 X X
1605.3 X X
1605.3.2 X X
1605.3.3 X X
1605.3.4
This state agency does not adopt sections identified with the following symbol:
The Office of the State Fire Marshal's adoption of this chapter or individual sections is applicable to structures regulated by other state agencies pursuant to Section 1.11.0.
The provisions of this chapter shall apply to the installation, construction, alteration, and repair of nonpotable rainwater catchment systems.
Where approved or required by the Authority Having Jurisdiction, rainwater shall be permitted to be used instead of potable water for the applications identified in this chapter.
Rainwater catchment systems shall be designed in accordance with this chapter by a person registered or licensed to perform plumbing design work or who demonstrates competency to design the rainwater catchment system as required by the Authority Having Jurisdiction. Components, piping, and fittings used in a rainwater catchment system shall be listed.

[HCD 1] Irrigation design plans shall meet the requirements of the California Code of Regulations, Title 23, Division 2, Chapter 2.7, Model Water Efficient Landscape Ordinance.

Exceptions:
  1. A person registered or licensed to perform plumbing design work is not required to design rainwater catchment systems used for irrigation with a maximum storage capacity of 360 gallons (1363 L).
  2. A person registered or licensed to perform plumbing design work is not required to design rainwater catchment systems for single family dwellings where outlets, piping, and system components are located on the exterior of the building.
It shall be unlawful for a person to construct, install, alter, or cause to be constructed, installed, or altered a nonpotable rainwater catchment system in a building or on a premise without first obtaining a permit to do such work from the Authority Having Jurisdiction.

Exceptions:
  1. A permit is not required for exterior rainwater catchment systems used for outdoor non-spray irrigation with a maximum storage capacity of 5000 gallons (18 927 L) where the tank is supported directly upon grade and the ratio of height to diameter or width does not exceed 2 to 1 and it does not require electrical power or a makeup water supply connection.
  2. [HCD 1 & HCD 2] A permit is not required for exterior rainwater catchment systems used for spray irrigation with a maximum storage capacity of 360 gallons (1363 L).
System components shall be properly identified as to the manufacturer.
Rainwater catchment systems and components shall be inspected and maintained in accordance the manufacturer's recommendations and/or as required by the enforcing agency.
The required maintenance and inspection of rainwater catchment systems shall be the responsibility of the property owner unless otherwise required by the Authority Having Jurisdiction.

TABLE 1601.5
MINIMUM ALTERNATE WATER SOURCE TESTING,
INSPECTION, AND MAINTENANCE FREQUENCY
DESCRIPTION MINIMUM FREQUENCY
Inspect and clean filters and
screens, and replace (where necessary).
Every 3 months
Inspect and verify that disinfection, filters, and water quality treatment devices and systems are operational and maintaining minimum water quality requirements as determined by the Authority Having Jurisdiction. In accordance with manufacturer's instructions and the Authority Having Jurisdiction.
Inspect and clear debris from rainwater gutters, downspouts, and roof washers. Every 6 months
Inspect and clear debris from the roof or another above-ground rainwater collection surfaces. Every 6 months
Remove tree branches and vegetation overhanging a roof or other aboveground rainwater collection surfaces. As needed
Inspect pumps and verify operation. After initial installation and every 12 months thereafter
Inspect valves and verify operation. After initial installation and every 12 months thereafter
Inspect pressure tanks and verify operation. After initial installation and every 12 months thereafter
Clear debris from and inspect storage tanks, locking devices, and verify operation. After initial installation and every 12 months thereafter
Inspect caution labels and marking. After initial installation and every 12 months thereafter
Cross-connection inspection and test.* After initial installation and every 12 months thereafter
Test water quality of rainwater catchment systems required by Section 1602.9.6 to maintain a minimum water quality. Every 12 months. After system renovation or repair.
* The cross-connection test shall be performed in the presence of the Authority Having Jurisdiction in accordance with the requirements of this chapter.
An operation and maintenance manual for rainwater catchment systems required to have a permit in accordance with Section 1601.3, shall be supplied to the building owner by the system designer or installer. The operating and maintenance manual shall include the following:
  1. Diagram(s) of the entire system and the location of system components.
  2. Instructions for operating and maintaining the system.
  3. Instructions on maintaining the required water quality for rainwater catchment systems.
  4. Details on startup, shutdown, and deactivating the system for maintenance, repair, or other purposes.
  5. Applicable testing, inspection, and maintenance frequencies in accordance with Section 1601.5.
  6. A method of contacting the installer and/or manufacturer(s).
  7. Directions to the owner or occupant that the manual shall remain with the building throughout the life cycle of the structure.
The minimum water quality for rainwater catchment systems shall comply with the applicable water quality requirements for the intended application as determined by the Authority Having Jurisdiction. Water quality for nonpotable rainwater catchment systems shall comply with Section 1602.9.6. In the absence of water quality requirements for harvested rainwater, Table 1602.9.6 shall apply.

Exceptions:
  1. Water treatment is not required for rainwater catchment systems used for aboveground irrigation with a maximum storage capacity of 360 gallons (1363 L).
  2. Water treatment is not required for rainwater catchment systems used for surface, subsurface or drip irrigation.
The installation, construction, alteration, and repair of rainwater catchments systems intended to supply uses such as water closets, urinals, trap primers for floor drains and floor sinks, irrigation, industrial processes, water features, cooling tower makeup and other uses shall be approved by the Authority Having Jurisdiction.
No permit for a rainwater catchment system shall be issued until complete plumbing plans, with data satisfactory to the Authority Having Jurisdiction, have been submitted and approved.
No changes or connections shall be made to either the rainwater catchment system or the potable water system within a site containing a rainwater catchment system requiring a permit without approval by the Authority Having Jurisdiction.
Rainwater catchment systems shall have no direct connection to a potable water supply or alternate water source system. Potable or reclaimed (recycled) water is permitted to be used as makeup water for a rainwater catchment system provided the potable or reclaimed (recycled) water supply connection is protected by an air gap or reduced-pressure principle backflow preventer in accordance with this code.
Where a portion of a rainwater catchment system is installed within a building, a cross-connection test is required in accordance with Section 1605.3. Before the building is occupied or the system is activated, the installer shall perform the initial cross-connection test in the presence of the Authority Having Jurisdiction and other authorities having jurisdiction. The test shall be ruled successful by the Authority Having Jurisdiction before final approval is granted.
The design and size of rainwater drains, gutters, conductors, and leaders shall comply with Chapter 11 of this code.
Rainwater catchment water supply and distribution materials shall comply with the requirements of this code for potable water supply and distribution systems unless otherwise provided for in this section.
Materials used in rainwater catchment drainage systems, including gutters, downspouts, conductors, and leaders shall be in accordance with the requirements of this code for storm drainage.
Rainwater catchment systems shall have a colored background in accordance with Section 601.3. Rainwater catchment systems shall be marked, in lettering in accordance with Section 601.3.3, with the words: "CAUTION: NONPOTABLE RAINWATER WATER, DO NOT DRINK."
The design and installation of nonpotable rainwater catchment systems shall be in accordance with Section 1602.9.1 through Section 1603.16.
Outside hose bibbs shall be allowed on rainwater piping systems. Hose bibbs supplying rainwater shall be marked with the words: "CAUTION: NONPOTABLE WATER, DO NOT DRINK'' and Figure 1602.9.1.

FIGURE 1602.9.1
The rainwater catchment system and the potable water system within the building shall be provided with the required appurtenances (e.g., valves, air or vacuum relief valves, etc.) to allow for deactivation or drainage as required for a cross-connection test in accordance with Section 1605.3.
Rainwater shall be collected from roof surfaces or other impervious manmade, above-ground collection surfaces. Rainwater collected from surface water runoff, vehicular parking surfaces or manmade surfaces at or below grade shall comply with the water quality requirements for onsite treated nonpotable gray water in Section 1504.0.

Exception: Collected rainwater or storm water used exclusively for subsurface landscape irrigation.
Natural precipitation collected from surface water runoff, vehicular parking surfaces, or manmade surfaces at or below grade shall be in accordance with the water quality requirements for on-site treated nonpotable gray water systems in Section 1506.0.

Exception: Collected rainwater or storm water used exclusively for subsurface landscape irrigation.
Overflows and bleed-off pipes from roof-mounted equipment and appliances shall not discharge onto roof surfaces that are intended to collect rainwater.
The minimum water quality for harvested rainwater shall meet the applicable water quality requirements for the intended applications as determined by the Authority Having Jurisdiction. In the absence of water quality requirements determined by the Authority Having Jurisdiction, the minimum treatment and water quality shall be in accordance with Table 1602.9.6.

Exception: [BSC] No treatment is required for rainwater used for non-spray irrigation where the maximum storage volume is less than 5000 gallons (18 927 L) where the tank is supported directly upon grade and the ratio of height to diameter or width does not exceed 2 to 1.

TABLE 1602.9.6
MINIMUM WATER QUALITY
APPLICATION MINIMUM TREATMENT MINIMUM WATER QUALITY
Car washing Debris excluder or other approved means in accordance
with Section 1603.14, and 100 microns (100 µm) in
accordance with Section 1603.15 for drip irrigation.
N/A
Surface, Subsurface and drip irrigation Debris excluder or other approved means in accordance
with Section 1603.14, and 100 microns (100 µm) in
accordance with Section 1603.15 for drip irrigation.
N/A
Spray irrigation where the maximum storage
volume is less than 360 gallons (1363 L)
Debris excluder or other approved means in accordance
with Section 1603.14, and disinfection in accordance
with Section 1603.12.
N/A
Spray irrigation where the maximum storage
volume is equal to or more than 360 gallons
(1363 L)
Debris excluder or other approved means in accordance
with Section 1603.14
Escherichia coli: < 100
CFU/100 mL, and Turbidity: <
10 NTU
Urinal and water closet flushing, clothes washing,
and trap priming
Debris excluder or other approved means in accordance
with Section 1603.14, and 100 microns (100 µm) in
accordance with Section 1603.15
Escherichia coli: < 100
CFU/100 mL, and Turbidity: <
10 NTU
Ornamental fountains and other water features Debris excluder or other approved means in accordance
with Section 1603.14.
Escherichia coli: < 100
CFU/100 mL, and Turbidity: <
10 NTU
Cooling tower make up water Debris excluder or other approved means in accordance
with Section 1603.14, and 100 microns (100 µm) in
accordance with Section 1603.15.
Escherichia coli: < 100
CFU/100 mL, and Turbidity: <
10 NTU
For SI units: 1 micron = 1 µm, 1 gallon = 3.785 L
Where the initial quality of the collected rainwater requires disinfection or other treatment or both, the collected rainwater shall be treated as necessary to ensure the required water quality is delivered at the point of use. Where chlorine is used for disinfection or treatment, water shall be tested for residual chlorine in accordance with ASTM D1253. The levels of residual chlorine shall not exceed the levels allowed for the intended use in accordance with the requirements of the local Enforcing Agency.
Rainwater storage tanks shall be constructed and installed in accordance with Section 1603.2 through Section 1603.9.
Rainwater storage tanks shall be constructed of solid, durable materials not subject to excessive corrosion or decay and shall be watertight.
Rainwater storage tanks shall be permitted to be installed above or below grade.
Above grade, storage tanks shall be of an opaque material, approved for aboveground use in direct sunlight or shall be shielded from direct sunlight. Tanks shall be installed in an accessible location to allow for inspection and cleaning. The tank shall be installed on a foundation or platform that is constructed to accommodate loads in accordance with the California Building Code.

Exception: Tanks may be installed directly on grade in accordance with 1601.3.
Rainwater storage tanks installed below grade shall be structurally designed to withstand anticipated earth or other loads. Holding tank covers shall be capable of supporting an earth load of not less than 300 pounds per square foot (lb/ft2) (1465 kg/m2) where the tank is designed for underground installation. Below grade rainwater tanks installed underground shall be provided with manholes. Below grade storage tanks, located outside of the building, shall be provided with either a manhole not less than 24 inches (610 mm) square or a manhole with an inside diameter of not less than 24 inches (610 mm). Service ports in manhole covers shall be not less than 8 inches (203 mm) in diameter. The manhole opening shall be located not less than 4 inches (102 mm) above the surrounding grade. The surrounding grade shall be sloped away from the manhole. Underground tanks shall be ballasted, anchored, or otherwise secured, to prevent the tank from floating out of the ground where empty. The combined weight of the tank and hold down system shall meet or exceed the buoyancy force of the tank.
Rainwater storage tanks shall be provided with a means of draining and cleaning. The overflow drain shall not be equipped with a shutoff valve. The overflow outlet shall discharge in accordance with this code for storm drainage systems. Where discharging to the storm drainage system, the overflow drain and tank drain shall be protected from backflow of the storm drainage system by a backwater valve or other approved method. Backwater valves shall be installed so that access is provided to the working parts for service and repair.
The overflow outlet shall be sized to accommodate the flow of the rainwater entering the tank and not less than the aggregate cross-sectional area of inflow pipes.
Rainwater tank openings shall be protected to prevent the entrance of insects, birds, or rodents into the tank and piping systems.
  1. Animals and Insects. Screens installed on vent pipes, inlets, and overflow pipes shall have an aperture of not greater than 1/16 of an inch (1.6 mm) and shall be close fitting.
  2. Human Access. A minimum of one access opening shall be provided to allow inspection and cleaning. Rainwater tank manholes and access openings shall be secured by either a lockable device or other approved method to prevent unauthorized access.
Rainwater tanks shall be permanently marked with the capacity and the language: "NONPOTABLE RAINWATER." Where openings are provided to allow a person to enter the tank, the opening shall be marked with the following language: "DANGER-CONFINED SPACE."
Where venting using drainage or overflow piping is not provided or is considered insufficient, a vent shall be installed on each tank. The vent shall extend from the top of the tank and terminate not less than 6 inches (152 mm) above grade and shall be provided with a vent sized in accordance with this code, and based on the size of the influent pipe. The vent terminal shall be directed downward and covered with a 1/16 of an inch (2.4 mm) mesh screen to prevent the entry of vermin and insects. Tank vent pipes shall not be connected to the sanitary drainage system vent.
Pumps serving rainwater catchment systems shall be listed. Pumps supplying water to water closets, urinals, and trap primers shall be capable of delivering not less than 15 pounds-force per square inch (psi) (103 kPa) residual pressure at the highest and most remote outlet served. Where the water pressure in the rainwater supply system within the building exceeds 80 psi (552 kPa), a pressure reducing valve reducing the pressure to 80 psi (552 kPa) or less to water outlets in the building shall be installed in accordance with this code.
Primary and secondary roof drains, conductors, leaders, and gutters shall be designed and installed in accordance with this code.
Devices and equipment used to treat rainwater to maintain the minimum water quality requirements determined by the Authority Having Jurisdiction shall be listed or labeled (third-party certified) by a listing agency (accredited conformity assessment body) and approved for the intended application.
Tanks and piping installed in locations subject to freezing shall be provided with an approved means of freeze protection.
The rainwater catchment conveyance system shall be equipped with a debris excluder or other approved means to prevent the accumulation of leaves, needles, other debris and sediment from entering the storage tank. Devices or methods used to remove debris or sediment shall be accessible and sized and installed in accordance with manufacturer's installation instructions.
A filter permitting the passage of particulates not larger than 100 microns (100 μm) shall be provided for rainwater supplied to water closets, urinals, trap primers, and drip irrigation systems.
Gutters shall maintain a minimum slope and be sized in accordance with Section 1103.3.
Signs in buildings using rainwater shall be in accordance with Section 1604.2 and Section 1604.3, and applicable requirements of the California Building Code.
A sign shall be installed in restrooms in commercial, industrial, and institutional occupancies, and in residential common use areas using nonpotable rainwater for water closets, urinals, or both. Signs shall comply with all applicable requirements of the California Building Code. Each sign shall contain the following text:

TO CONSERVE WATER, THIS BUILDING USES RAINWATER TO FLUSH TOILETS AND URINALS.
Each equipment room containing nonpotable rainwater equipment shall have a sign posted with the following wording in 1 inch (25.4 mm) letters:

CAUTION NONPOTABLE WATER, DO NOT DRINK. DO NOT CONNECT TO DRINKING WATER SYSTEM. NOTICE: CONTACT BUILDING MANAGEMENT BEFORE PERFORMING ANY WORK ON THIS WATER SYSTEM.

This sign shall be posted in a location that is visible to anyone working on or near rainwater water equipment.

Rainwater catchment systems shall be inspected and tested in accordance with Section 1605.2 and Section 1605.3.
Rainwater catchment systems shall be inspected and tested in accordance with the applicable provisions of this code for testing of potable water and storm drainage systems. Storage tanks shall be filled with water to the overflow opening for a period of 24 hours, and during the inspection, or by other means as approved by the Authority Having Jurisdiction. Seams and joints shall be exposed during the inspection and checked for watertightness.
An initial visual inspection and an initial cross-connection test shall be performed on both the potable and rainwater catchment water systems before the initial operation of the rainwater catchment system. During an initial or subsequent cross-connection test, the potable and rainwater catchment water systems shall be isolated from each other and independently inspected and tested to ensure there is no crossconnection in accordance with Section 1602.5. Initial or subsequent inspections or tests shall be performed in accordance with Section 1605.3.1 through Section 1605.3.3.
Prior to commencing the cross-connection testing, a dual system inspection shall be conducted by the Authority Having Jurisdiction and other authorities having jurisdiction as follows:
  1. Pumps, equipment, equipment room signs, and exposed piping in an equipment room shall be checked.
A cross-connection test shall be performed in the presence of the Authority Having Jurisdiction or other authorities having jurisdiction to determine whether a cross-connection has occurred as follows:
  1. The potable water system shall be activated and pressurized. The rainwater catchment water system shall be shut down and completely drained.
  2. The potable water system shall remain pressurized for a minimum period of time specified by the Authority Having Jurisdiction while the rainwater catchment water system is empty. The minimum period the rainwater catchment water system is to remain depressurized shall be determined on a case-by-case basis, taking into account the size and complexity of the potable and rainwater catchment water distribution systems, but in no case shall that period be less than 1 hour.
  3. Fixtures, potable, and rainwater shall be tested and inspected for flow. Flow from a rainwater catchment water system outlet shall indicate a cross-connection. No flow from a potable water outlet shall indicate that it is connected to the rainwater water system.
  4. The drain on the rainwater catchment water system shall be checked for flow during the test and at the end of the period.
  5. The potable water system shall then be completely drained.
  6. The rainwater catchment water system shall then be activated and pressurized. When rainwater is not available for the initial cross-connection test, a temporary connection to a potable water supply shall be required. At the conclusion of the initial crossconnection test, the temporary connection to the potable water supply shall be disconnected.
  7. The rainwater catchment water system shall remain pressurized for a minimum period of time specified by the Authority Having Jurisdiction while the potable water system is empty. The minimum period the potable water system is to remain depressurized shall be determined on a case-by-case basis, but in no case shall that period be less than 1 hour.
  8. Fixtures, potable and rainwater catchment, shall be tested and inspected for flow. Flow from a potable water system outlet shall indicate a cross-connection. No flow from a rainwater catchment water outlet shall indicate that it is connected to the potable water system.
  9. The drain on the potable water system shall be checked for flow during the test and at the end of the period.
  10. Where there is no flow detected in the fixtures which would indicate a cross-connection, the potable water system shall be repressurized.
In the event that a cross-connection is discovered, the following procedure shall be activated immediately:
  1. Rainwater catchment water piping to the building shall be shutdown at the supply source(s), and the rainwater water riser shall be drained.
  2. Potable water piping to the building shall be shutdown at the meter.
  3. The cross-connection shall be uncovered and disconnected.
  4. The building shall be retested following procedures listed in Section 1605.3.1 and Section 1605.3.2.
  5. The potable water system shall be chlorinated with 50 ppm chlorine for 24 hours.
  6. The potable water system shall be flushed after 24 hours, and a standard bacteriological test shall be performed. Where test results are acceptable, the potable water system shall be permitted to be recharged.
UpCodes Premium
Leverage the most sophisticated code compliance platform.
TRY FREE FOR TWO WEEKS VISIT PRICING