ADOPTS WITH AMENDMENTS:

CMC 2019

Heads up: There are no amended sections in this chapter.

Division 1 Administration

AMENDMENT
This section has been amended at the state or city level.

Part I — General

AMENDMENT
This section has been amended at the state or city level.

Section 95.100 Basic Provisions

AMENDMENT
This section has been amended at the state or city level.
Chapter 1 of the 2019 California Mechanical Code (CMC) is not adopted.

Section 95.101 Title, Scope, and General

AMENDMENT
This section has been amended at the state or city level.

95.101.1 Title

AMENDMENT
This section has been amended at the state or city level.
This article is a portion of the Los Angeles Municipal Code and shall be known as the Los Angeles Mechanical Code. The abbreviation "CMC" shall mean and refer to the 2016 Edition of the California Mechanical Code. References to "LAMC" or "Code" shall mean the Los Angeles Municipal Code.

95.101.2 Purpose

AMENDMENT
This section has been amended at the state or city level.
The purpose of this article is to safeguard life, health, property and public welfare by regulating the design, construction, installation, alteration, repair, quality of materials, location, operation and maintenance of heating, ventilating, airconditioning and refrigeration equipment and other miscellaneous heat-producing appliances installed in the City. The provisions of this Code are not intended to apply to equipment installed on railroad cars, motor vehicles, aircraft or on shipboards that are not used as permanent occupancies for longer than six months.

95.101.3 Scope

AMENDMENT
This section has been amended at the state or city level.
The provisions of this Code shall apply to the addition to or erection, installation, alteration, repair, relocation, replacement, use, or maintenance of heating, ventilation, cooling, refrigeration systems; incinerators; or other miscellaneous heatproducing appliances within this jurisdiction.

Additions, alterations, repairs to, and replacement of equipment or systems shall be in accordance with the provisions for new equipment and systems, except as otherwise provided in LAMC Section 95.102.0.

95.101.3.1 Conflicts

AMENDMENT
This section has been amended at the state or city level.
Where, in a specific case, different sections of this Code or referenced standards specify different materials, methods of construction, or other requirements, the most restrictive shall govern as determined by the Authority Having Jurisdiction. Where there is a conflict between a general requirement and a specific requirement, the specific requirement shall prevail. [OSHPD 1, 2, 3 & 4]

95.101.3.1.1 Conflicts Between Codes

AMENDMENT
This section has been amended at the state or city level.
Where the requirements within the jurisdiction of this Mechanical Code conflict with the requirements of the Plumbing Code, the Plumbing Code shall prevail.

95.101.3.2 Design and Testing

AMENDMENT
This section has been amended at the state or city level.
The design and testing of equipment regulated by this Code shall be subject to the approval of the Authority Having Jurisdiction.

95.101.3.3 Appendices

AMENDMENT
This section has been amended at the state or city level.
The provisions in the appendices are intended to supplement the requirements of this Code and shall not be considered part of this Code unless formally adopted as such.

Section 95.102 Application to Existing Mechanical Systems

AMENDMENT
This section has been amended at the state or city level.
Sections 104.0 through 104.4 of Chapter 1, Division II of the CMC are adopted by reference, Section 104.5 of Chapter 1, Division II of the CMC is not adopted, and in lieu thereof, Section 95.102.5 of this Code shall apply.

95.102.1 Additions, Alterations, or Repairs

AMENDMENT
This section has been amended at the state or city level.
Additions, alterations, or repairs shall be permitted to be made to a mechanical system without requiring the existing mechanical system to be in accordance with the requirements of this Code, provided the addition, alteration, or repair is in accordance with that required for a new mechanical system. Additions, alterations, or repairs shall not cause an existing system to become unsafe or create unhealthy or overloaded conditions.

Minor additions, alterations, and repairs to existing mechanical systems shall be permitted to be installed in accordance with the law in effect at the time the original installation was made, where approved by the Authority Having Jurisdiction.

95.102.2 Existing Installations

AMENDMENT
This section has been amended at the state or city level.
Mechanical systems lawfully in existence at the time of the adoption of this Code shall be permitted to have their use, maintenance, or repair continued where the use, maintenance, or repair is in accordance with the original design and location and no hazard to life, health, or property has been created by such mechanical systems.

95.102.3 Changes in Building Occupancy

AMENDMENT
This section has been amended at the state or city level.
Mechanical systems that are a part of a building or structure undergoing a change in use or occupancy, as defined in Article 1, Chapter IX of the LAMC, shall be in accordance with the requirements of this Code that are applicable to the new use or occupancy.

95.102.4 Maintenance

AMENDMENT
This section has been amended at the state or city level.
Mechanical systems, materials, and appurtenances, both existing and new, and parts thereof, shall be maintained in operating condition in accordance with the original design and in a safe and hazard-free condition. Devices or safeguards that are required by this Code shall be maintained in accordance with the code edition under which installed. The owner or the owner's designated agent shall be responsible for maintenance of mechanical systems and equipment. To determine compliance with this subsection, the Authority Having Jurisdiction shall be permitted to cause mechanical systems or equipment to be reinspected.

95.102.4.1 Commercial HVAC Systems

AMENDMENT
This section has been amended at the state or city level.
Commercial HVAC systems both existing and new, and parts thereof shall be inspected and maintained in operating condition in accordance with ASHRAE/ACCA 180. The owner or the owner's designated agent shall be responsible for maintenance of mechanical systems and equipment. To determine compliance with this subsection, the Authority Having Jurisdiction shall be permitted to cause a HVAC system to be reinspected.

95.102.4.2 Residential HVAC Systems

AMENDMENT
This section has been amended at the state or city level.
Residential HVAC systems both existing and new, and parts thereof shall be inspected in accordance with ACCA 4 QM. The owner or the owner's designated agent shall be responsible for maintenance of mechanical systems and equipment. To determine compliance with this subsection, the Authority having Jurisdiction shall be permitted to cause a HVAC system to be reinspected.

95.102.5 Moved Buildings

AMENDMENT
This section has been amended at the state or city level.
Apartment houses and dwellings moved into or within the City and all other buildings moved within the City, may retain the existing heating, ventilation, air-conditioning and refrigeration equipment and other miscellaneous heat-producing appliances, provided the building does not become or continue to be a substandard residential building or a residential building subject to repair. However, existing mechanical equipment, including vents, which is not in good and safe condition and not working properly shall be corrected.

Existing heating, ventilation, air-conditioning and refrigeration equipment and other miscellaneous heat-producing appliances in any building, other than an apartment house or dwelling, moved from outside the City to inside the City shall comply with all the requirements of this Code.

New heating, ventilating, air-conditioning and refrigeration equipment and miscellaneous heat-producing appliances that are installed in any building relocated into or within the City shall conform to the provisions of this Code.

95.102.6 Existing Buildings

AMENDMENT
This section has been amended at the state or city level.
In existing buildings or premises in which mechanical systems are to be altered, repaired, replaced, or renovated, the Authority Having Jurisdiction has discretionary powers to permit deviation from the provisions of this Code, provided that such proposal to deviate is first submitted for determination in order that health and safety requirements, as they pertain to mechanical, shall be observed.

Section 95.103 Alternate Materials and Methods of Construction Equivalency

AMENDMENT
This section has been amended at the state or city level.

95.103.1 General

AMENDMENT
This section has been amended at the state or city level.
Nothing in this Code is intended to prevent the use of systems, methods, or devices of equivalent or superior quality, strength, fire resistance, effectiveness, durability, and safety over those prescribed by this Code. Technical documentation shall be submitted to the Authority Having Jurisdiction to demonstrate equivalency. The Authority Having Jurisdiction shall have the authority to approve or disapprove the system, method or device for the intended purpose.

Section 95.104 Modifications

AMENDMENT
This section has been amended at the state or city level.
Appeals or requests for slight modifications in individual cases from the requirements of this Code shall be made in accordance with the procedure established in LAMC Sections 98.0403.1 and 98.0403.2.

Section 95.105 Testing

AMENDMENT
This section has been amended at the state or city level.

95.105.1 General

AMENDMENT
This section has been amended at the state or city level.
The Authority Having Jurisdiction shall have authority to require tests, as proof of equivalency.

95.105.2 Approved Standards

AMENDMENT
This section has been amended at the state or city level.
Tests shall be made in accordance with approved testing standards by an approved testing agency at the expense of the applicant. In the absence of such standards, the Authority Having Jurisdiction shall have the authority to specify the test procedure.

95.105.3 Request by the Authority Having Jurisdiction

AMENDMENT
This section has been amended at the state or city level.
The Authority Having Jurisdiction shall have the authority to require tests to be made or repeated where there is reason to believe that a material or device no longer is in accordance with the requirements on which its approval was based.

Part II — Organization and Enforcement

AMENDMENT
This section has been amended at the state or city level.

Section 95.106 Powers and Duties of the Department

AMENDMENT
This section has been amended at the state or city level.

95.106.1 General

AMENDMENT
This section has been amended at the state or city level.
The powers of the Department and the Board are enumerated in Section 98.0403.1 of the Los Angeles Municipal Code.

95.106.2 Interpretation

AMENDMENT
This section has been amended at the state or city level.
  1. If two or more pertinent limitations are not identical, those limitations shall prevail that provide the greater safety to persons, property or public welfare.
  2. The Superintendent of Building or a duly authorized representative is empowered to make all interpretations concerning the provisions of this Code.

95.106.3 (Deleted by Ord. No. 184,692, Eff. 12/30/16.)

AMENDMENT
This section has been amended at the state or city level.

95.106.4 Stop Orders

AMENDMENT
This section has been amended at the state or city level.
Where work is being done contrary to the provisions of this Code, the Authority Having Jurisdiction shall have the authority to order the work stopped by notice in writing served on persons engaged in doing or causing such work to be done, and such persons shall forthwith stop work until authorized by the Authority Having Jurisdiction to proceed with the work.

95.106.5 Authority to Disconnect Utilities in Emergencies

AMENDMENT
This section has been amended at the state or city level.
The Authority Having Jurisdiction or authorized representative shall be permitted to disconnect fuel gas utility service or energy supplies to a building, structure, premises, or equipment regulated by this Code in case of emergency where necessary to eliminate an immediate hazard to life or property. The Authority Having Jurisdiction shall, wherever possible, notify the serving utility, the owner, and the occupant of the building, structure, or premises of the decision to disconnect prior to taking such action, and shall notify such serving utility, owner, and occupant of the building, structure, or premises in writing of such disconnection immediately thereafter.

95.106.6 Authority to Condemn Equipment

AMENDMENT
This section has been amended at the state or city level.
Where the Authority Having Jurisdiction ascertains that an equipment, or portion thereof, regulated by this Code has become hazardous to life, health, or property, it shall order in writing that the equipment either be removed or restored to a safe or sanitary condition. The written notice shall contain a fixed time limit for compliance with such order. Persons shall not use or maintain defective equipment after receiving a notice.

Where equipment or an installation is to be disconnected, written notice of the disconnection and causes therefore shall be given within 24 hours to the serving utility, owner, and occupant of the building, structure, or premises. Where equipment is maintained in violation of this Code, and in violation of a notice issued pursuant to the provisions of this section, the Authority Having Jurisdiction shall institute an action to prevent, restrain, correct, or abate the violation.

95.106.7 Connection After Order to Disconnect

AMENDMENT
This section has been amended at the state or city level.
Persons shall not make connections from an energy, fuel, or power supply nor supply energy or fuel to any equipment regulated by this Code that has been disconnected or ordered to be disconnected by the Authority Having Jurisdiction until it has authorized the reconnection and use of such equipment.

95.106.8 (Deleted by Ord. No. 184,692, Eff. 12/30/16.)

AMENDMENT
This section has been amended at the state or city level.

95.106.9 Cooperation of Other Officials and Officers

AMENDMENT
This section has been amended at the state or city level.
The Authority Having Jurisdiction shall be permitted to request the assistance and cooperation of other officials of this jurisdiction so far as required in the discharge of the duties required by this Code or other pertinent law or ordinance.

Section 95.107 Unsafe Equipment

AMENDMENT
This section has been amended at the state or city level.

95.107.1 General

AMENDMENT
This section has been amended at the state or city level.
Equipment regulated by this Code that is unsafe or that constitutes a fire or health hazard or is otherwise dangerous to human life is, for the purpose of this section, unsafe. Use of equipment regulated by this Code constituting a hazard to safety, health, or public welfare by reason of inadequate maintenance, dilapidation, obsolescence, fire hazard, disaster, damage, or abandonment is, for the purpose of this section, an unsafe use. Unsafe equipment is hereby declared to be a public nuisance and shall be abated by repair, rehabilitation, demolition, or removal in accordance with procedures as may be adopted by this jurisdiction. As an alternative, the Authority Having Jurisdiction or other employee or official of this jurisdiction, as designated by the governing body, shall be permitted to institute other action to prevent, restrain, correct, or abate the violation.

Section 95.108 Appeals

AMENDMENT
This section has been amended at the state or city level.
In order to hear and decide appeals of orders, decisions or determinations made by the building official relative to the application and interpretations of this Code, the appeal process shall be made in accordance with the procedure established in Sections 98.0403.1 and 98.0403.2 of the Los Angeles Municipal Code.

Section 95.109 Prohibited Acts

AMENDMENT
This section has been amended at the state or city level.
No person shall sell, offer for sale, display for sale, advertise for sale, loan, rent, or lease, dispose of by way of gift, premium or otherwise, any equipment regulated by this Code unless such equipment is listed by an approved testing agency or is of a type and construction approved by the Department.

Part III Permits and Inspections

AMENDMENT
This section has been amended at the state or city level.

Section 95.111 Permits

AMENDMENT
This section has been amended at the state or city level.

95.111.1 General

AMENDMENT
This section has been amended at the state or city level.
No person shall install or alter, repair, relocate, replace or add to any installed heating, ventilating, air-conditioning, or refrigeration equipment or other miscellaneous heat-producing appliances unless a permit for the work has been obtained from the Department, except as provided in this Code. 

EXCEPTION:
  1. A separate permit shall not be required for installation of any heating, ventilating, air-conditioning, or refrigeration equipment or other miscellaneous heat-producing appliances for which a combined building/mechanical permit has been obtained pursuant to LAMC Subdivision 91.107.2.2. 
  2. No person shall be subject to a fine or payment of an investigation fee for starting and doing any emergency repair work without a permit being first obtained, if a permit for the work is obtained on or before 12:00 noon on the third day the office of the Department is open for public business after the work was started. (See Section 98.0402 of the Los Angeles Municipal Code.) 
  3. No permit shall be required for:
    1. Any portable ventilating equipment.
    2. Any portable comfort-cooling unit.
    3. Any steam, hot or chilled water piping within any comfort- heating or cooling system regulated by this Code.
    4. Any portable evaporative cooler.
    5. Any unit refrigeration system.
    6. Any cooking range, broiler unit or domestic-type clothes dryer.
    7. Any replacement or repairing of a compressor, provided the compressor replaced or repaired is of the same horsepower rating and is installed in the same location.
    8. Any replacement or repair of controls, motors and components which are not part of, or used for, any emergency smoke-control system required by the Building Code or the Fire Code.
    9. Any replacement or repair of any component part of listed factory-assembled comfort-heating or comfortcooling equipment which does not alter its original approval and complies with all other applicable requirements of this Code.
    10. Any repair of equipment not specified here, if the total value of the repair is less than $500.00 for labor and material. For the purpose of this requirement, no permit shall be required where the work is performed on more than one piece of equipment or duct system that is located in the same building, provided the total value of material and labor for any separate and individual repair does not exceed $500.00.
    11. The replacement of defective forced-air units with one of equivalent size, Btu/hr (W) rating and vent capacity when the vent does not require replacement or relocation in a detached single-family dwelling and the replacement is performed by a contractor with a valid Certificate of Registration pursuant to LAMC Subsection 91.1704.1. A Certificate of Compliance pursuant to LAMC Subsection 91.108.12 must be filed with the City in lieu of a permit. (Amended by Ord. No. 185,587, Eff. 7/16/18.)
    12. The replacement of defective air-conditioning units when they are replaced with one of equivalent size and Btu/hr (W) rating by a contractor with a valid Certificate of Registration pursuant to LAMC Subsection 91.1704.1. A Certificate of Compliance pursuant to LAMC Subsection 91.108.12 must be filed with the City in lieu of a permit. 
The foregoing exemptions for permit requirements shall not apply where the equipment is regulated by the California Energy Commission, or the equipment is used to provide the required heating capacity for any residential occupancy, or the equipment is used as part of an emergency smoke-control system.

The foregoing exemptions from permit requirements shall not be deemed to allow any equipment regulated by this Code to be installed in a manner contrary to other provisions of this Code.

95.111.2 Permit Required

AMENDMENT
This section has been amended at the state or city level.
A permit shall be obtained for all heating, ventilating, air-conditioning or refrigeration equipment or other miscellaneous heat-producing appliances moved with, or installed in, a relocated building in the City.

95.111.3 Separate Permit

AMENDMENT
This section has been amended at the state or city level.
A separate permit shall be obtained for the equipment installed in each separate building or structure and for the work required by each building permit.

95.111.4 Incidental Gas

AMENDMENT
This section has been amended at the state or city level.

Any qualified installer as specified in LAMC Subsection 95.112.4 may install incidental gas piping to connect any heating appliance or absorption unit to the existing gas piping system, provided:

  1. The incidental piping installation complies with the requirements as set forth in the Los Angeles Plumbing Code; and
  2. There is an existing gas supply meter on the premises serving the gas piping system.

Section 95.112 Application for Permit

AMENDMENT
This section has been amended at the state or city level.

95.112.1 Applications

AMENDMENT
This section has been amended at the state or city level.
  1. To obtain a permit, the applicant shall file an application on forms furnished by the Department. The application shall contain all information necessary to the lawful enforcement of the provisions of this Code.
  2. The application shall be accompanied by approved plans and specifications when required by this Code.
  3. When the Department determines that the information on the application is in conformance with this Code, the Department shall issue a permit upon receipt of the total fees.

95.112.2 Plans and Specifications

AMENDMENT
This section has been amended at the state or city level.
  1. Except for minor installations satisfactory to the Department, plans and specifications for the complete installation of comfort-heating systems, comfort-cooling systems, absorption units, ventilation systems and hoods shall be filed with the Department and approved before the issuance of any permit for the following:
    1. Comfort-Heating, Comfort-Cooling, Absorption Unit and Ventilation Systems:
      1. Installations where the aggregate Btu/h input capacity is 500,000 Btu/h (146,500 W) and over for comfort heating, or for comfort cooling, or for absorption units.
         EXCEPTIONS:
        1. Duct alterations. 
        2. Addition of air conditioning equipment having a rating of 5 tons or less.
        3. Addition of general ventilation exhaust fans having a rating of 2000 cfm or less.
        4. Replacing air conditioning equipment with the same size and type.
      2. (Deleted by Bill No. 181,685, Eff. 5/2/11.)
    2. Smoke-control systems.
    3. Any comfort-cooling compressor or refrigeration compressor for any system which requires a machinery room.
    4. Any commercial cooking hood and ventilation system, except for approved vent-less hoods that are installed in accordance with the manufacturer's installation instructions and other conditions of approval as determined by the Los Angeles City Testing Laboratory.
    5. Product conveying ventilation systems.
  2. One complete set of plans and specifications shall be filed for checking before approval is given by the Department. After approval, the plans shall be returned to the applicant. The approved set of plans shall be on the job site for availability during construction and inspection. 
  3. When the plans and specifications do not comply with provisions of this Code, the necessary changes or revisions shall be made.
  4. The information contained on the plans shall be clearly legible and specifically indicated. No plan shall be of a scale smaller than 1/8 inch per foot .
  5. Specifications, when submitted, shall be legible and definitively stated, and be included either on the plans or on separate sheets.
  6. The approval of any plans or specifications shall not be construed to sanction any violation of this Code.
  7. No person shall materially deviate from approved plans or specifications or fail, neglect or refuse to comply with those plans or specifications unless permission to do so has first been obtained from the Department.
  8. Plans and specifications shall be prepared by and bear the signature and registration number of a professional engineer in an appropriate discipline who is duly registered by the State of California Board of Registration for Professional Engineers and Land Surveyors, except as provided by the State of California Business and Professions Code.

95.112.3 Information on Plans and Specifications

AMENDMENT
This section has been amended at the state or city level.
  1. The plans or specifications shall show all of the following: 
    1. The layout for each floor with dimensions of all working spaces and a legend of all symbols used;
    2. The location, size and materials of all air ducts, air inlets and air outlets;
    3. The location of all fans, warm-air furnaces, boilers, absorption units, refrigerant compressors and condensers;
    4. The rated capacity or horsepower of all boilers, warm-air furnaces, heat exchangers, blower fans, refrigerant compressors and absorption units;
    5. The location, size and materials of all combustion products, vents and chimneys;
    6. The location and area of all ventilation and combustion-air openings and ducts;
    7. The location of all air dampers, fire dampers, smoke-control dampers and combustion-products-type smoke detectors;
    8. The information necessary to show compliance of the mechanical equipment with the state energy standards;
    9. The occupancy of each area served by any heating, air-conditioning or ventilation system;
    10. The location of all required fire- resistive separations that are penetrated by ducts or openings of any heating, airconditioning or ventilation system;
    11. The complete drawings of all commercial hoods and ventilation systems, including the cooking appliances served by the hoods, and verify:
      1. The interconnection of the fire- extinguishing system and fuel shutoff devices;
      2. Compliance with Health Department requirements; and
      3. Compliance with South Coast Air Quality Management District requirements.
    12. The weight of the equipment.
  2. All plans and specifications required by this section shall be drawn with indelible pencil or drawn or printed in ink, or made by reproduction process which produces a permanent print. Every sheet of each set of plans and specifications shall show the address of the proposed work and the name and address of the owner or lessee of the premises.
The plans and specifications shall be of sufficient clarity to show that the proposed installation will conform to the provisions of this Code and of all applicable laws, ordinances, rules, regulations and orders.

95.112.4 Qualified Installer

AMENDMENT
This section has been amended at the state or city level.
It is unlawful for any person who is not a qualified installer to install, alter, reconstruct or repair any equipment regulated by this Code unless the person is under the direct supervision of a qualified installer.

A qualified installer is:
  1. A person who holds a valid contractor's license in the proper classification issued by the State of California; or
  2. A person who holds a valid Maintenance Certificate of Registration issued pursuant to the provisions of this Code; or
  3. A person who is the owner of a single-family dwelling and has demonstrated to the satisfaction of the Department his or her qualifications to satisfactorily perform mechanical work in the dwelling which is occupied by the owner, and their accessory buildings, provided that all of the following conditions are met:
    1. The work is performed prior to sale of the dwelling.
    2. The home owner has actually resided in the residence for the 12 months prior to completion of the work.
    3. The homeowner has not availed himself or herself of this exemption on more than two structures during any three year period.
  4. A person who is employed by a governmental agency that is required to comply with the provisions of this Code, and who is qualified, as determined by the Department, to supervise or control any work regulated by this Code.

Section 95.113 Permit Issuance

AMENDMENT
This section has been amended at the state or city level.

95.113.1 Issuance

AMENDMENT
This section has been amended at the state or city level.
The issuance of a permit is not an approval or an authorization of the work specified therein. A permit is merely an application for inspection, the issuance of which entitles the permittee to inspection of the work described therein.

95.113.2 Effect of Issuance

AMENDMENT
This section has been amended at the state or city level.
Neither the issuance of a permit nor the approval by the Department of any plans or specifications shall constitute an approval of any work or material that is in violation of any provision of this Code or of any other applicable law.

95.113.3 Expiration of Permits

AMENDMENT
This section has been amended at the state or city level.
Permits shall expire as provided for in Section 98.0602 of the Los Angeles Municipal Code.

95.113.4 Revocation of Permits

AMENDMENT
This section has been amended at the state or city level.
Permits may be revoked as provided for in Section 98.0601 of the Los Angeles Municipal Code.

Section 95.114 Permit Fees

AMENDMENT
This section has been amended at the state or city level.

95.114.1 Permit Fees

AMENDMENT
This section has been amended at the state or city level.
Before any permit required by this Code is issued, the applicant shall pay to the Department the following fees:

PERMIT FEE SCHEDULE FOR HEATING, VENTILATING, AIR-CONDITIONING AND REFRIGERATION EQUIPMENT AND MISCELLANEOUS HEAT-PRODUCING APPLIANCES


Permit Fee
1.a.    For issuing permit$24.00
b.    For issuing a supplementary permit (the fee for which shall be the difference between the fee paid for the  original permit and the fee which would have been  required had the original permit included the entire installation, repair, relocation or alteration plus$20.00
2.For the installation or relocation of each fuel-burning heating appliance regulated by this Code$19.00
3.For  each  air  inlet  and  air  outlet  served  by any  heating,  air-conditioning  or  ventilation  system$5.00
or for each 1,000 square feet (92.9 m2) or fraction thereof of conditioned area for any heating or air-conditioning system using perforated building material in lieu of conventional air inlets and outlets$38.00
4.a.    For the installation of each appliance vent system, factory-built chimney and each absorption unit vent system regulated by this Code$12.00
b.    For the installation of each unlisted single-wall metal chimney (smokestack)$57.00
Note:  This fee shall not apply to a vent system which is an integral part of an appliance or an absorption unit, which is listed for outdoor installation.
5.For the repair of, alteration of or addition to each refrigeration system, fuel- burning heating appliance, comfort-cooling unit, absorption unit, or each comfort-heating, cooling, absorption, ventilation or evaporative cooling system, including the installation of controls regulated by this Code$24.00
6.a.    For each ventilation system which is serving a commercial cooking hood$33.00
b.    For each environmental air and commercial-type clothes dryer ventilation system regulated by this Code$12.00
c.    For each product-conveying duct system regulated by this Code$59.00
7.For the installation of each hood$33.00
8.a.    For the installation of each comfort-cooling compressor of 25-horsepower (87.9 k/W) rating or less and each absorption unit having an input capacity of 500,000 Btu/h (2299.3 L/W) or less$24.00
b.    For the installation of each refrigeration compressor of 25-horsepower rating (87.9 k/W) or less, other than a compressor for a unit refrigeration system$38.00
9.a.    For the installation of each comfort-cooling compressor over 25-horsepower (87.9 k/W) rating and under 50-horsepower (175.8 k/W) rating, and each absorption unit having an input capacity over 500,000 Btu/h (2299.3 L/W) and under 1,000,000 Btu/h (4598.6 L/W)$59.00
b.    For the installation of each refrigeration compressor over 25-horsepower (87.9 k/W) rating and under 50-horsepower (175.8 k/W) rating$77.00
10.a.    For the installation of each comfort-cooling compressor of 50-horsepower (175.8 k/W) rating and over, and each absorption unit having an input capacity of 1,000,000 Btu/h (4598.6 L/W) and over$116.00
b.    For the installation of each refrigeration compressor of 50-horsepower (175.8 k/W) rating and over$158.00
11.For  the  installation  of  each  air-handling  unit  used  for  the  distribution  of  conditioned  air supply$24.00
Note:  This fee shall not apply to an air-handling unit which is a portion of a factory-assembled appliance, comfort-cooling unit, evaporative cooler or absorption unit for which a permit is required elsewhere in this Code.
12.For the installation of each evaporative cooler which is not classified as a portable evaporative cooler$24.00
13.When it shall be necessary to make an extra inspection trip due to the applicant having given an incorrect address or wrong location for any permit when obtaining a permit required by this Code, a fee shall be paid by the applicant for correcting the address or location given in such permit$36.00
14.For the installation of incidental gas piping for each existing individual metered system up to and including five outlets (see LAMC Subsection 95.111.4$25.00
      For each outlet over five$7.00
Note:  For the purpose of this fee, incidental gas piping shall mean any addition made to an existing low-pressure gas piping system to accommodate gas-burning equipment regulated by this Code.  This fee shall not apply if such piping is less than six feet (1.8 m) in length and connects to an existing gas outlet.
15.For the installation of each fire damper$12.00
16.For the installation of each smoke-control damper which is a portion of a smoke- control system that is required by the Los Angeles Municipal Code$12.00
17.For each smoke detector which is required by the Los Angeles Mechanical Code$10.00
18.For witnessing the performance test of any emergency mechanical smoke-control system, stair shaft pressurization system, smoke detector or smoke damper which is a portion of that system.  For each hour or fraction thereof$108.00
19.For witnessing the performance test of any heating or cooling equipment for automatic shutoff.  For each hour or fraction thereof$108.00
20.For witnessing the performance test of any ventilating system serving commercial food heat-processing equipment.  For each hour or fraction thereof$108.00
21.For the minimum inspection$93.00
22.For each additional inspection$93.00
23.Minimum inspection fee.  LAMC Section 98.0412: 
a.    For the installation of a single fixture described in this section$57.00
b.    Where the cumulative fees described in this section total less than the minimum fee required by the Los Angeles Mechanical Code$93.00
24.For transfer of a permit$50.00

Note: Items 18, 19 and 20. For the purpose of witness fee requirements, more than one system of the same category can be inspected in the same building spaces if completed within the same hour. For each additional category or additional hour or fraction thereof a fee of $75.00 is required. These fees are not to be included in determining plan check fee.

95.114.2 Plan Check Fees

AMENDMENT
This section has been amended at the state or city level.
  1. Before formally accepting a set of plans and specifications for checking, the Department shall collect a plan check fee.

    A complete schedule of the permit fees due shall be included with each set of plans submitted to the Department.

    The plan check fees required by the provisions of this section are in addition to the inspection fees required by LAMC Subsections 95.114.5 and 95.114.8.

    A fee as specified in Paragraph 1 of LAMC Subsection 95.114.2 shall be collected by the Department prior to approval for each set of plans submitted beyond the two required by this Code containing more than 10 sheets including calculations and documentation.

    Plan check fee shall be as follows:
    1. All projects

      Type of Installation Standard Design Additional Fee for
      Checking Analysis
      of Annual Energy Budget
      Installation of equipment as listed in Section 95.114.1 70% of permit fee
      $93.00 minimum; plus a surcharge of 10% of permit fee,
      $72.00 minimum, for checking compliance with State Energy Standards

      NOTE: For conditioned areas where the number of air inlets
      and air outlets is unknown, $12.00 for each 1000 sq. ft.
      or fraction thereof.
      60% of permit fee,
      $144.00 minimum,
      $4,037.00 maximum
    2. In addition to the above fee, a plan checking fee shall be assessed for checking the following systems:
      1. Commercial cooking ventilation systems, serving type I hoods, each .......... $216.00
      2. Commercial cooking ventilation systems, serving type II hoods each .......... $144.00
      3. Type I, Type II or fume hoods, each .......... $72.00
      4. Product conveying ventilation systems .......... $216.00
      5. Engineering calculations of smoke control systems, each .......... $1,081.00
      6. Engineering calculations of stair shaft pressurization systems, each .......... $216.00
      7. Engineered and/or proprietary duct joints, each HVAC system, minimum .......... $144.00
      8. The Department may collect a plan check fee as specified in LAMC Section 98.0415(e) for the following plan check services:
        1. Specially engineered systems;
        2. Engineered systems not listed in LAMC Subsection 95.114.1;
        3. Review of expired plans, provided that the original approved plans are submitted along with the new plans
          and the new plans have no changes other than those required to comply with the current code;
        4. Review of plans revised for reasons other than to comply with plan check corrections;
        5. Review of "As Built" plans provided that the original approved plans are submitted along with the new plans;
        6. Any time not included in the original plan check fee.
  2. Off-hour Plan Check. Upon request by an applicant and accepted by the Department, an off-hour plan check fee per LAMC Section 98.0422 may be collected.

95.114.3 Expiration of Plan Check

AMENDMENT
This section has been amended at the state or city level.
Plan check approval shall expire as provided for in Section 98.0603 of the Los Angeles Municipal Code.

95.114.4 Minimum Inspection Fee

AMENDMENT
This section has been amended at the state or city level.
  1. A minimum fee as specified in LAMC Section 98.0412 shall be paid to the Department for each mechanical installation for which a permit is required by this Code.
  2. When the cumulative fees and the issuing fee set forth in this Code are less than the minimum fee, the minimum fee shall be paid, which shall include the issuing fee.
  3. The fee for single fixture shall apply to the installation of only one mechanical fixture/equipment and shall include the issuing fee. Where the fee for a single fixture exceeds the minimum fee for single fixtures, this fee shall not apply.

95.114.5 Fees for Miscellaneous Permits

AMENDMENT
This section has been amended at the state or city level.
  1. When permission has been obtained from the Department, a permit may be issued for that portion of equipment to be concealed if the permit cannot be issued until required plans have been approved. The miscellaneous permit shall not be an authorization for the installation of any other equipment.

    The permittee shall submit plans along with this permit application which shall clearly designate the equipment to be concealed and the building area involved. If the work done on the miscellaneous permit is not in accordance with the final approved plans, the permittee shall be responsible for making all necessary corrections for compliance with the Code.

    A fee as specified in LAMC Section 98.0412 shall be paid for the inspection of this installation and shall be limited to one inspection trip and one re-inspection trip. This fee is in addition to the permit-issuing fee specified in LAMC Subsection 95.114.1.
  2. A miscellaneous permit fee as specified in LAMC Section 98.0412 shall be paid for inspection of the installation of equipment regulated by this Code which requires an inspection for determination of Code compliance and where such installation inspection is not provided for in the permit fee schedule specified in LAMC Subsection 95.114.1. This fee is in addition to the permit issuing fee specified in LAMC Subsection 95.114.1.

95.114.6 Investigation Fee

AMENDMENT
This section has been amended at the state or city level.
Except as provided in LAMC Subsection 95.111.1, whenever any work for which a permit is required under the provisions of this Code has been commenced without the authorization of a permit, a special investigation shall be made before a permit may be issued for the work. In addition to the permit fee, an investigation fee shall be collected as provided for in LAMC Section 98.0402.

95.114.7 Transfer of Permits and Plan Checks

AMENDMENT
This section has been amended at the state or city level.
No permit shall be transferable from the original permittee to any other person, unless the property owner authorizes the transfer in writing. Upon authorization, the new permittee shall file with the Department a new permit and pay to the Department a fee as specified in LAMC Section 98.0415 for issuing the new permit. This fee includes the issuing permit fee specified in the fee schedule set forth in LAMC Subsection 95.114.1.

NOTE: No plan check shall be transferable from one contractor to another unless the original plans were prepared and signed by a state-licensed engineer in the proper classification.

95.114.8 Fees for Additional Inspections

AMENDMENT
This section has been amended at the state or city level.
  1. Each permit shall be entitled to three inspection trips when the job is of a type requiring an inspection before covering or concealing the work. On jobs which may be completely inspected on one inspection trip, two inspection trips will be allowed.

    EXCEPTION: The number of inspection trips will not be limited on progress jobs, provided, however, that only one inspection will be permitted for checking a correction. For the purpose of this section, progress jobs are those in which circumstances beyond the control of the applicant make it impossible for the installation to be completed at any specific time.
  2. If more inspection trips than are specified in Subdivision 1 of this subsection are required due to the fault or error on the part of the applicant or the applicant's employees, an additional fee as specified in LAMC Section 98.0412 shall be paid by the applicant for each additional inspection trip.
  3. The Department may recheck installations at intervals of 30 days or more, where violations continue to exist, until either the violations are cleared or a total of three rechecks are made. The fees specified in Subdivision 2 of this subsection shall apply for each recheck inspection.
  4. The fees charged under this section are in addition to any other fees shown and the payment of the fees required by this section shall not exempt any person from compliance with other provisions of this Code nor from any penalty prescribed by law.
  5. Whenever special enforcement procedures are required to obtain compliance with properly executed Department notices or orders, a fee, as specified in LAMC Section 98.0407, shall be assessed in addition to the added trip fee specified in Subdivision 2 of this subsection.

95.114.9 Inspection Fees for Off-Hours Inspections

AMENDMENT
This section has been amended at the state or city level.
The Department may, at its discretion, make emergency inspections at other than normal working hours upon the request of a permittee, provided that additional fees are paid as specified in Section 98.0406 of the Los Angeles Municipal Code.

95.114.10 Fees for Off-Site Inspections

AMENDMENT
This section has been amended at the state or city level.
Upon written request, the Department may, at its discretion, make inspections at locations other than the site upon which a building will be located, provided that location is within 60 miles (96.56 km) of the Los Angeles City Hall.

A fee, in addition to fees charged elsewhere in this Code, at the rate specified in Section 98.0412 of the Los Angeles Municipal Code per hour shall be charged for such inspections, time to include travel to and from the place of inspection, with the minimum fee as specified in Section 98.0412 of the Los Angeles Municipal Code.

Section 95.115 Inspections

AMENDMENT
This section has been amended at the state or city level.

95.115.1 Inspection

AMENDMENT
This section has been amended at the state or city level.
  1. All equipment for which a permit is required by this Code shall be inspected by an authorized inspector of the Department.

    EXCEPTION: Contractors holding a Certificate of Registration complying with Section 91.108.12 of the Los Angeles Municipal Code for detached single-family dwellings.
  2. No portion of any equipment intended to be enclosed by any permanent portion of the building shall be enclosed until inspected and approved.
  3. When the installation of any equipment is complete, a second or final inspection shall be made.
  4. The first and second inspections may be made at the same time if no portion of the equipment is concealed by any permanent portion of any building.
  5. Approved fabricators. The inspections provided for in this section shall not be required for construction or installation work done on the premises of a Type II fabricator to whom an approval has been issued pursuant to the provisions of Division C of Article 6 of Chapter IX of the Los Angeles Municipal Code.

95.115.2 Request for Inspection

AMENDMENT
This section has been amended at the state or city level.
  1. The Department shall require that every request for inspection be filed at least one day before the inspection is desired. This request may be in writing or by telephone at the option of the Department.
  2. It shall be the duty of the person requesting inspection of any equipment regulated by this Code to provide access to and means for proper inspection for the equipment.
  3. The removal of any material necessary to permit an inspection shall be required by the Department by written order. The City shall not be liable for any expense entailed in the removal or replacement of any material required to permit the inspection.

Section 95.116 Connection Approval

AMENDMENT
This section has been amended at the state or city level.

95.116.1 Connection Approval

AMENDMENT
This section has been amended at the state or city level.
No equipment regulated by this Code shall be connected to the fuel or power supply until it complies with all applicable requirements of this Code and a final inspection tag of approval has been issued by the Department.

EXCEPTION: The requirements of this subsection shall not be considered to prohibit the operation of any equipment installed to replace defective equipment serving an occupied portion of a building, in the event a request for inspection of that equipment has been filed with the Department not more than 48 hours after the replacement work is completed and before any portion of the equipment is concealed by any permanent portion of the building.

95.116.2 Final Inspection

AMENDMENT
This section has been amended at the state or city level.
A final inspection tag of approval may, upon notice, be revoked by the Department if the Department finds that the equipment fails in any respect to comply with the requirements of this Code or that the installation is unsafe, dangerous or a hazard to life or property.

Section 95.117 Unconstitutional

AMENDMENT
This section has been amended at the state or city level.

95.117.1 Validity of Code

AMENDMENT
This section has been amended at the state or city level.
Where a section, subsection, sentence, clause. Or phrase of this Code is, for a reason, held to be unconstitutional, such decision shall not affect the validity of the remaining portions of this Code. The legislative body hereby declares that it would have passed this Code, and each section, subsection, sentence, clause, or phrase thereof, irrespective of the fact that one or more sections, subsections, sentences, clauses, and phrases are declared unconstitutional.

Section 95.118 Validity

AMENDMENT
This section has been amended at the state or city level.

95.118.1 Code

AMENDMENT
This section has been amended at the state or city level.
Where a provision of this Code, or the application thereof to a person or circumstance, is held invalid, the remainder of the Code, or the application of such provision to other persons or circumstances, shall not be affected.

Section 95.119 Registration

AMENDMENT
This section has been amended at the state or city level.

95.119.1 Maintenance Supervisor

AMENDMENT
This section has been amended at the state or city level.
No person shall act in the capacity of a maintenance supervisor or air balancer for smoke-control systems, unless the person has paid the filing fee and successfully passed an examination as specified in LAMC Subsection 95.119.3.

EXCEPTION: One who holds a valid contractor's license in the proper classification issued by the State of California and personally performs the work.

95.119.2 Applications

AMENDMENT
This section has been amended at the state or city level.
  1. Every applicant for Certificate of Qualification as a maintenance supervisor or air balancer shall make an application in writing to the Department on forms furnished for that purpose.
  2. Every application for a Certificate of Qualification as a comfort heating and cooling or refrigeration maintenance supervisor or air balancer shall be accompanied by a filing fee as specified in LAMC Section 98.0414.
  3. Every applicant for a Certificate of Qualification as a comfort heating and cooling or refrigeration maintenance supervisor or air balancer shall be examined as required by the provisions of LAMC Subsection 95.119.3.
Note: For the purpose of this Code, an air balancer holding a Certificate of Qualification may qualify to perform work to comply with the State Energy requirements (Parts 1 and 6, Title 24 of the California Code of Regulations).

95.119.3 Examinations

AMENDMENT
This section has been amended at the state or city level.
  1. Every applicant for a Certificate of Qualification as a comfort-heating and cooling maintenance supervisor or a refrigeration maintenance supervisor or air balancer shall be given an examination to evaluate that applicant's knowledge and experience. The extent and scope of the examination shall, in the judgement of the Superintendent of Building, be sufficient to indicate that a person who successfully passes the examination has the necessary ability to repair, maintain, alter and service refrigeration equipment, heating appliances, heating systems, gas piping, gas-control devices, vents for gas appliances, and air balancing in compliance with this Code. The examination shall include a written test and an oral interview.
  2. The Superintendent of Building is hereby granted the power and authority to make and establish such rules and regulations as he or she may consider necessary for the proper conduct of the examination. The results of each examination shall be subject to review and approval by the Superintendent.

95.119.4 Failure to Pass Examination

AMENDMENT
This section has been amended at the state or city level.
No part of any filing fee shall be returned to any applicant who fails to pass the examination for which the fees were paid. If any applicant shall fail to receive the percentage required at the first examination, the applicant shall be entitled to take a second examination without payment of a second fee, but shall be required to wait at least two weeks before taking the second examination. In case any applicant fails to pass the second examination, the applicant shall be required to wait at least six months before he or she may file another application for examination, at which time the applicant shall pay another filing fee.

95.119.5 Issuance of Maintenance Certificate of Registration

AMENDMENT
This section has been amended at the state or city level.
  1. Every applicant for a Maintenance Certificate of Registration shall make application to the Department on forms furnished for that purpose. The application shall provide the following information:
    1. Business name and address of applicant.
    2. The signature of the responsible managing officer.
    3. The name of the maintenance supervisor.
  2. Before a Maintenance Certificate of Registration is issued to any person, that person shall pay a registration fee as specified in Section 98.0414 of the Los Angeles Municipal Code.
  3. Each Maintenance Certificate of Registration issued shall expire one year following the date of issuance, but may be renewed from year to year upon payment of an annual renewal fee as specified in Section 98.0414 of the Los Angeles Municipal Code, which must be paid not later than 30 days after the date of expiration.
  4. The Department shall issue a Certificate of Qualification as a maintenance supervisor or air balancer to any person who has successfully passed the examination prescribed in Section 95.119.3.
  5. Every Certificate of Qualification as maintenance supervisor or air balancer shall expire one year following the date of issuance, buy may be renewed from year to year by the payment of an annual fee as specified in Section 98.0414 of the Los Angeles Municipal Code within 30 days after the date of expiration.
  6. A maintenance supervisor shall be limited to perform only the labor for maintenance, repair, addition to or alteration of existing equipment on premises owned by or under control of the holder of a valid Maintenance Certificate of Registration.

95.119.6 Revocation, Suspension and Voiding of Certificates

AMENDMENT
This section has been amended at the state or city level.
  1. Any Certificate of Registration or Certificate of Qualification required by this Code may be suspended or revoked in accordance with the provisions of Article 8, Chapter IX of the LAMC.
  2. Any person whose certificate is revoked hereunder shall not, for a period of 30 days thereafter, be eligible for a new certificate and shall receive a new certificate only after passing the required examination and paying the required fee.
  3. The revocation of any Certificate of Registration or Certificate of Qualification shall not exempt the holder from any other penalty provided in this Code.
  4. A Certificate of Registration shall become void 30 days after a maintenance supervisor is no longer in the employ of a holder of a Certificate of Registration.
  5. A Certificate of Qualification shall become void when the maintenance supervisor is no longer in the employ of the holder of a Certificate of Registration.

95.119.7 Exhibition of Maintenance Certificate

AMENDMENT
This section has been amended at the state or city level.
Every person holding a Certificate of Qualification as a maintenance supervisor or air balancer shall exhibit that certificate to authorized personnel of the Department upon demand.

95.119.8 Transfer of Certificates

AMENDMENT
This section has been amended at the state or city level.
No Certificate of Registration or Qualification shall be transferable.

95.119.9 Expired Certificates

AMENDMENT
This section has been amended at the state or city level.
  1. Expired certificates may be renewed at any time within 12 months following the date of expiration provided that, after the first month, the renewal fee shall be increased by 10 percent for each month after the first.
  2. After a certificate has been expired for one year, it may not be renewed. A new application and payment of the filing fees set forth in LAMC Section 95.119 will be required.