ADOPTS WITH AMENDMENTS:

CBC 2016

Heads up: There are no amended sections in this chapter.
CALIFORNIA BUILDING CODE — MATRIX ADOPTION TABLE
CHAPTER 22 — STEEL
(Matrix Adoption Tables are non-regulatory, intended only as an aid to the user.
See Chapter 1 for state agency authority and building applications.)
Adopting agency BSC BSC-CG SFM HCD DSA OSHPD BSCC DPH AGR DWR CEC CA SL SLC
1 2 1/AC AC SS SS/CC 1 2 3 4
Adopt entire chapter X X X X
Adopt entire chapter as amended (amended sections listed below) X
Adopt only those sections that are listed below
Chapter / Section
2201.1.1 X
2201.1.2 X
2201.1.3 X
2201.1.4 X
2212 X
The provisions of this chapter govern the quality, design, fabrication and erection of steel construction.

[DSA-SS/CC] The scope of application of Chapter 22 is as follows:

Community college buildings regulated by the Division of the State Architect-Structural Safety/Community Colleges (DSA-SS/CC), as listed in Section 1.9.2.2.

Division of the State Architect-Structural Safety/Community Colleges amendments appear in this chapter preceded with the appropriate acronym, as follows:

[DSA-SS/CC] - For community college buildings listed in Section 1.9.2.2

[DSA-SS/CC] Where reference within this chapter is made to sections in Chapter 17 the provisions in Chapter 17A, shall apply instead.

[DSA-SS/CC] See Section 2212 for additional requirements.

Identification of structural steel elements shall be in accordance with AISC 360. Identification of cold-formed steel members shall be in accordance with AISI S100. Identification of cold-formed steel light-frame construction shall also comply with the requirements contained in AISI S200 or AISI S220, as applicable. Other steel furnished for structural load-carrying purposes shall be properly identified for conformity to the ordered grade in accordance with the specified ASTM standard or other specification and the provisions of this chapter. Steel that is not readily identifiable as to grade from marking and test records shall be tested to determine conformity to such standards.
Painting of structural steel elements shall be in accordance with AISC 360. Painting of open-web steel joists and joist girders shall be in accordance with SJI CJ, SJI JG, SJI K and SJI LH/DLH. Individual structural members and assembled panels of cold-formed steel construction shall be protected against corrosion in accordance with the requirements contained in AISI S100. Protection of cold-formed steel light-frame construction shall be in accordance with AISI S200 or AISI S220, as applicable.

2204.1 Welding

AMENDMENT
This section has been amended at the state or city level.
The details of design, workmanship and technique for welding, inspection of welding and qualification of welding operators shall conform to the requirements listed in CBC Sections 2205, 2206, 2207, 2208, 2209, 2210 and 2211. Special inspection of welding shall be provided where required by CBC Section 1705.

All welding, except when performed at the shop of an approved fabricator, shall be done by operators certified by the Department for the type of operation involved in accordance with the provisions of CBC Section 1705.2.2.1.

Complete details of location, type, size and amount of all welds shall be clearly shown on the plans. Where symbols are used on the plans, they shall be the "Standard Welding Symbols," AWS A 2.4, of the American Welding Society (AWS). When it is necessary to use a special erection sequence of welding to minimize locked-up stresses or distortion, the Department may require the erection sequence of welding to be shown on the plans.

Welding procedures are qualified if they are in accordance with the AWS. Other welding procedures require special qualification approval by the Department. Each application for a special qualification shall be accompanied by a fee of $50.00.
The design, installation and inspection of bolts shall be in accordance with the requirements of Sections 2205, 2206, 2207, 2210 and 2211. For special inspection of the installation of high-strength bolts, see Section 1705.2.
Anchor rods shall be set in accordance with the approved construction documents. The protrusion of the threaded ends through the connected material shall fully engage the threads of the nuts but shall not be greater than the length of the threads on the bolts.
The design, fabrication and erection of structural steel elements in buildings, structures and portions thereof shall be in accordance with AISC 360.
Where required, the seismic design, fabrication and erection of buildings, structures and portions thereof shall be in accordance with Section 2205.2.1 or 2205.2.2, as applicable.
The design, detailing, fabrication and erection of structural steel seismic force-resisting systems shall be in accordance with the provisions of Section 2205.2.1.1 or 2205.2.1.2, as applicable.

Structures assigned to Seismic Design Category B or C shall be of any construction permitted in Section 2205. Where a response modification coefficient, R, in accordance with ASCE 7, Table 12.2-1, is used for the design of structures assigned to Seismic Design Category B or C, the structures shall be designed and detailed in accordance with the requirements of AISC 341.

Exception: The response modification coefficient, R, designated for "Steel systems not specifically detailed for seismic resistance, excluding cantilever column systems" in ASCE 7, Table 12.2-1, shall be permitted for systems designed and detailed in accordance with AISC 360, and need not be designed and detailed in accordance with AISC 341.

Structures assigned to Seismic Design Category D, E or F shall be designed and detailed in accordance with AISC 341, except as permitted in ASCE 7, Table 15.4-1.

The design, detailing, fabrication and erection of structural steel elements in seismic force-resisting systems other than those covered in Section 2205.2.1, including struts, collectors, chords and foundation elements, shall be in accordance with AISC 341 where either of the following applies:

  1. The structure is assigned to Seismic Design Category D, E or F, except as permitted in ASCE 7, Table 15.4-1.
  2. A response modification coefficient, R, greater than 3 in accordance with ASCE 7, Table 12.2-1, is used for the design of the structure assigned to Seismic Design Category B or C.
AISC 341, Section F2.5b. is modified to add a new requirement as follows:

Section F2.5b(4) - The use of rectangular HSS are not permitted for bracing members, unless filled solid with cement grout having a minimum compressive strength of 3000 psi (20.7 MPa) at 28 days. The effects of composite action in the filled composite brace shall be considered in the sectional properties of the system where it results in the more severe loading condition or detailing.
Systems of structural steel elements acting compositely with reinforced concrete shall be designed in accordance with AISC 360 and ACI 318, excluding ACI 318 Chapter 14.
Where required, the seismic design, fabrication and erection of composite steel and concrete systems shall be in accordance with Section 2206.2.1.
Where a response modification coefficient, R, in accordance with ASCE 7, Table 12.2-1, is used for the design of systems of structural steel acting compositely with reinforced concrete, the structures shall be designed and detailed in accordance with the requirements of AISC 341.

The design, manufacture and use of open-web steel joists and joist girders shall be in accordance with one of the following Steel Joist Institute (SJI) specifications:

  1. SJI CJ
  2. SJI K
  3. SJI LH/DLH
  4. SJI JG
Where required, the seismic design of buildings shall be in accordance with the additional provisions of Section 2205.2 or 2211.6.

The registered design professional shall indicate on the construction documents the steel joist and steel joist girder designations from the specifications listed in Section 2207.1; and shall indicate the requirements for joist and joist girder design, layout, end supports, anchorage, bridging design that differs from the SJI specifications listed in Section 2207.1, bridging termination connections and bearing connection design to resist uplift and lateral loads. These documents shall indicate special requirements as follows:

  1. Special loads including:

    1. 1.1. Concentrated loads.
    2. 1.2. Nonuniform loads.
    3. 1.3. Net uplift loads.
    4. 1.4. Axial loads.
    5. 1.5. End moments.
    6. 1.6. Connection forces.
  2. Special considerations including:

    1. 2.1. Profiles for joist and joist girder configurations that differ from those defined by the SJI specifications listed in Section 2207.1.
    2. 2.2. Oversized or other nonstandard web openings.
    3. 2.3. Extended ends.
  3. Live and total load deflection criteria for joists and joist girder configurations that differ from those defined by the SJI specifications listed in Section 2207.1.

The steel joist and joist girder manufacturer shall design the steel joists and steel joist girders in accordance with the SJI specifications listed in Section 2207.1 to support the load requirements of Section 2207.2. The registered design professional shall be permitted to require submission of the steel joist and joist girder calculations as prepared by a registered design professional responsible for the product design. Where requested by the registered design professional, the steel joist manufacturer shall submit design calculations with a cover letter bearing the seal and signature of the joist manufacturer's registered design professional. In addition to the design calculations submitted under seal and signature, the following shall be included:

  1. Bridging design that differs from the SJI specifications listed in Section 2207.1, such as cantilevered conditions and net uplift.
  2. Connection design for:

    1. 2.1. Connections that differ from the SJI specifications listed in Section 2207.1, such as flush-framed or framed connections.
    2. 2.2. Field splices.
    3. 2.3. Joist headers.

Steel joist placement plans shall be provided to show the steel joist products as specified on the approved construction documents and are to be utilized for field installation in accordance with specific project requirements as stated in Section 2207.2. Steel joist placement plans shall include, at a minimum, the following:

  1. Listing of applicable loads as stated in Section 2207.2 and used in the design of the steel joists and joist girders as specified in the approved construction documents.
  2. Profiles for joist and joist girder configurations that differ from those defined by the SJI specifications listed in Section 2207.1.
  3. Connection requirements for:

    1. 3.1. Joist supports.
    2. 3.2. Joist girder supports.
    3. 3.3. Field splices.
    4. 3.4. Bridging attachments.
  4. Live and total load deflection criteria for joists and joist girder configurations that differ from those defined by the SJI specifications listed in Section 2207.1.
  5. Size, location and connections for bridging.
  6. Joist headers.

Steel joist placement plans do not require the seal and signature of the joist manufacturer's registered design professional.

At completion of manufacture, the steel joist manufacturer shall submit a certificate of compliance to the owner or the owner's authorized agent for submittal to the building official as specified in Section 1704.5 stating that work was performed in accordance with approved construction documents and with SJI specifications listed in Section 2207.1.
The design, fabrication and erection including related connections, and protective coatings of steel cables for buildings shall be in accordance with ASCE 19.

The design strength of steel cables shall be determined by the provisions of ASCE 19 except as modified by these provisions.

  1. A load factor of 1.1 shall be applied to the prestress force included in T3 and T4 as defined in Section 3.12.
  2. In Section 3.2.1, Item (c) shall be replaced with "1.5 T3" and Item (d) shall be replaced with "1.5 T4."
The design, testing and utilization of storage racks made of cold-formed or hot-rolled steel structural members shall be in accordance with RMI/ANSI MH 16.1. Where required by ASCE 7, the seismic design of storage racks shall be in accordance with Section 15.5.3 of ASCE 7.
The design of cold-formed carbon and low-alloy steel structural members shall be in accordance with AISI S100. The design of cold-formed stainless-steel structural members shall be in accordance with ASCE 8. Cold-formed steel light-frame construction shall also comply with Section 2211. Where required, the seismic design of cold-formed steel structures shall be in accordance with the additional provisions of Section 2210.2.
The design and construction of cold-formed steel decks shall be in accordance with this section.
Noncomposite steel floor decks shall be permitted to be designed and constructed in accordance with ANSI/SDI-NC1.0.
Steel roof decks shall be permitted to be designed and constructed in accordance with ANSI/SDI-RD1.0.
Composite slabs of concrete and steel deck shall be permitted to be designed and constructed in accordance with SDI-C.
Where a response modification coefficient, R, in accordance with ASCE 7, Table 12.2-1, is used for the design of cold-formed steel structures, the structures shall be designed and detailed in accordance with the requirements of AISI S100, ASCE 8, or, for cold-formed steel special-bolted moment frames, AISI S110.
The design and installation of structural and nonstructural members utilized in cold-formed steel light-frame construction where the specified minimum base steel thickness is not greater than 0.1180 inches (2.997 mm) shall be in accordance with AISI S200 and Sections 2211.2 through 2211.7, or AISI S220, as applicable.
Headers, including box and back-to-back headers, and double and single L-headers shall be designed in accordance with AISI S212 or AISI S100.
Cold-formed steel trusses shall be designed in accordance with AISI S214, Sections 2211.3.1 through 2211.3.4 and accepted engineering practice.
The truss design drawings shall conform to the requirements of Section B2.3 of AISI S214 and shall be provided with the shipment of trusses delivered to the job site. The truss design drawings shall include the details of permanent individual truss member restraint/bracing in accordance with Section B6(a) or B 6(c) of AISI S214 where these methods are utilized to provide restraint/bracing.
AISI S214 Section B4.2 shall be deleted.
The owner or the owner's authorized agent shall contract with a registered design professional for the design of the temporary installation restraint/bracing and the permanent individual truss member restraint/bracing for trusses with clear spans 60 feet (18 288 mm) or greater. Special inspection of trusses over 60 feet (18 288 mm) in length shall be in accordance with Section 1705.2.
Trusses not part of a manufacturing process that provides requirements for quality control done under the supervision of a third-party quality control agency, shall be manufactured in compliance with Sections 1704.2.5 and 1705.2, as applicable.
Structural wall studs shall be designed in accordance with either AISI S211 or AISI S100.
Framing for floor and roof systems in buildings shall be designed in accordance with either AISI S210 or AISI S100.
Light-frame shear walls, diagonal strap bracing that is part of a structural wall and diaphragms used to resist wind, seismic and other in-plane lateral loads shall be designed in accordance with AISI S213.
Detached one- and two-family dwellings and townhouses, less than or equal to three stories above grade plane, shall be permitted to be constructed in accordance with AISI S230 subject to the limitations therein.

When shear and/or tensile forces are intended to be transferred between column base plates and anchor bolts, provision shall be made in the design to eliminate the effects of oversized holes permitted in base plates by AISC 360 by use of shear lugs and/or welded shear transfer plates or other means acceptable to the enforcement agency, when the oversized holes are larger than the anchor bolt by more than 1/8 inch (3.2 mm). When welded shear transfer plates and shear lugs or other means acceptable to the enforcement agency are not used, the anchor bolts shall be checked for the induced bending stresses in combination with the shear stresses.

Replace Section A4.1 item (3) as follows:

(3) Locations and dimensions of protected zones, including provision by the owner or owner's designated representative for construction to permanently mark and maintain the protection.

Add Section D1.6 as follows:

6. Diaphragm bracing systems. The required strength of diagonal bracing members used as the diaphragm shall be determined from either of the following:

  1. The load effect resulting from the diaphragm analysis per the applicable building code provided the members satisfy all of the following requirements:

    1. Diagonal bracing members comply with Section D1.1 for moderately ductile members.
    2. Each diagonal bracing member resists no more than 30 percent of the diaphragm shear at each line of resistance.
    3. Diagonal bracing members shall not support gravity loads other than self-weight.
    4. The slenderness ratio (KL/r) of diagonal bracing members shall not exceed except tension-only bracing.
  2. The load effect required for collectors using the load combinations stipulated in the applicable building code.

Modify Section D2.6c(b)(ii) as follows:

  1. the moment calculated using the load combinations of the applicable building code, including the amplified seismic load, provided the connection or other mechanism within the column base is designed to have the ductility necessary to accommodate the column base rotation resulting from the design story drift.

Add Section D2.9 as follows:

9. Diaphragm bracing systems. The required strength of the connections of diagonal bracing members used as the diaphragm shall be the load effect required for collectors using the load combinations stipulated in the applicable building code.

Modify Section F2.3 Exception (2)(a) as follows:

  1. The maximum of the forces determined using load combination stipulated by the applicable building code including the amplified seismic load, applied to the building frame model in which all compression braces have been removed and those determined with no compression braces removed per D1.4a(2).

Add Section F1.4c as follows:

4c. Multi-tiered braced frames: Braced frames configured with two or more tiers of bracing between diaphragm levels or locations of out-of-plane support shall comply with the additional requirements of Section F2.4e.

Modify Section F2.4a by adding the following:

Where each framing bay on a line of resistance does not have opposing diagonal braces within the same column bay, then the collector forces along that line shall be designed considering the redistribution of seismic forces to other bays as a result of the post-buckled redistribution of loads using the analysis requirements of Section F2.3. The collector shall not be designed for a load less than that stipulated by the applicable building code:

The required strength of the collector need not exceed the forces determined using load combination stipulated by the applicable building code, including the amplified seismic load, applied to the building model in which all compression braces have been removed.

Add Section F2.4e as follows:

4c. Multi-tiered braced frames: Braced frames configured with two or more tiers of bracing between diaphragm levels or locations of out-of-plane support shall comply with the additional requirements of this section:

  1. Braces shall be used in symmetrical pairs at every tier level.
  2. Horizontal beams at intermediate tier levels for V- and inverted V-brace configurations shall have out-of-plane strength, stiffness, and beam-to-column connections adequate to resist torsional moments arising from brace buckling when braces are designed to buckle out-of-plane.
  3. Columns shall be restrained against rotation about their longitudinal axis at each intermediate tier level and shall resist out-of-plane bending moments due to second-order effects, geometric imperfections, and out-of-plane brace buckling.

In addition to the requirements of Section 2206.2, steel and concrete composite special moment frame with the approved moment connections in accordance with AISC 358 Chapter 10 shall be permitted provided:

  1. Beams are provided with reduced beam sections (RBS),

  2. Web extension to beam web two-sided fillet weld welds are sized to develop expected strength of the beam web and shall not be less than a 1/4 inch fillet weld, and
  3. The built-up box column wall thickness shall not be less than 1.25 inches and the HSS column wall thickness shall not be less than 1/2 inch.

Joist and joist girder design calculations and profiles with member sizes and connection details, and joist placement plans shall be provided to the enforcement agency and approved prior to joist fabrication, in accordance with Title 24, Part 1. Joist and joist girder design calculations and profiles with member sizes and connection details shall bear the signature and stamp or seal of the registered engineer or licensed architect responsible for the joist design. Alterations to the approved joist and joist girder design calculations and profiles with member sizes and connection details, or to fabricated joists are subject to the approval of the enforcement agency.

The chords of all joists shall be laterally supported at all points where the chords change direction.

Complete engineering analysis and truss design drawings shall accompany the construction documents submitted to the enforcement agency for approval. When load testing is required the test report shall be submitted with the truss design drawings and engineering analysis to the enforcement agency.

AISI S214 Section B4.2 shall not be deleted.

Cold-formed steel stud foundation plates or sills shall be bolted or fastened to the foundation or foundation wall in accordance with Section 2304.3.4, Item 2.

Shear wall assemblies in accordance with Section C2.2.3 of AISI-S213 are not permitted within the seismic force-resisting system of buildings or structures assigned to Occupancy Category II, III, IV, or buildings designed to be relocatable.

High-strength bolts, nuts and washers shall be sampled and tested by an approved independent testing laboratory for conformance with the requirements of Section 2205.

End-welded studs shall be sampled and tested in accordance with the requirements of the AWS D1.1.

UpCodes Premium
Leverage the most sophisticated code compliance platform.
TRY FREE FOR TWO WEEKS VISIT PRICING