CODES

ADOPTS WITHOUT AMENDMENTS:

International Fire Code 2012 (IFC 2012)

Chapter 1 Scope and Administration

Chapter 2 Definitions

Chapter 3 General Requirements

Chapter 4 Emergency Planning and Preparedness

Chapter 5 Fire Service Features

Chapter 6 Building Services and Systems

Chapter 7 Fire-Resistance-Rated Construction

Chapter 8 Interior Finish, Decorative Materials and Furnishings

Chapter 9 Fire Protection Systems

Chapter 10 Means of Egress

Chapter 11 Construction Requirements for Existing Buildings

Chapter 12 Through 19 Reserved

Chapter 20 Aviation Facilities

Chapter 21 Dry Cleaning

Chapter 22 Combustible Dust-Producing Operations

Chapter 23 Motor Fuel-Dispensing Facilities and Repair Garages

Chapter 24 Flammable Finishes

Chapter 25 Fruit and Crop Ripening

Chapter 26 Fumigation and Insecticidal Fogging

Chapter 27 Semiconductor Fabrication Facilities

Chapter 28 Lumber Yards and Woodworking Facilities

Chapter 29 Manufacture of Organic Coatings

Chapter 30 Industrial Ovens

Chapter 31 Tents and Other Membrane Structures

Chapter 32 High-Piled Combustible Storage

Chapter 33 Fire Safety During Construction and Demolition

Chapter 34 Tire Rebuilding and Tire Storage

Chapter 35 Welding and Other Hot Work

Chapter 36 Marinas

Chapter 37 Through 49 Reserved

Chapter 50 Hazardous Materials—General Provisions

Chapter 51 Aerosols

Chapter 52 Combustible Fibers

Chapter 53 Compressed Gases

Chapter 54 Corrosive Materials

Chapter 55 Cryogenic Fluids

Chapter 56 Explosives and Fireworks

Chapter 57 Flammable and Combustible Liquids

Chapter 58 Flammable Gases and Flammable Cryogenic Fluids

Chapter 59 Flammable Solids

Chapter 60 Highly Toxic and Toxic Materials

Chapter 61 Liquefied Petroleum Gases

Chapter 62 Organic Peroxides

Chapter 63 Oxidizers, Oxidizing Gases and Oxidizing Cryogenic Fluids

Chapter 64 Pyrophoric Materials

Chapter 65 Pyroxylin (Cellulose Nitrate) Plastics

Chapter 66 Unstable (Reactive) Materials

Chapter 67 Water-Reactive Solids and Liquids

Chapter 68 Through 79 Reserved

Chapter 80 Referenced Standards

Appendix A Board of Appeals

Appendix B Fire-Flow Requirements for Buildings

Appendix C Fire Hydrant Locations and Distribution

Appendix D Fire Apparatus Access Roads

Appendix E Hazard Categories

Appendix F Hazard Ranking

Appendix G CRYOGENIC FLUIDS—WEIGHT AND VOLUME EQUIVALENTS

Appendix H Hazardous Materials Management Plan (Hmmp) and Hazardous Materials Inventory Statement (Hmis) Instructions

Appendix I FIRE PROTECTION SYSTEMS—NONCOMPLIANT CONDITIONS

Appendix J Building Information Sign

Tire rebuilding plants, tire storage and tire byproduct facilities shall comply with this chapter, other applicable requirements of this code and NFPA 13. Tire storage in buildings shall also comply with Chapter 32.
Permits shall be required as set forth in Section 105.6.
2 .
Words and terms used in this chapter and defined in Chapter 2 shall have the meanings ascribed to them as defined therein.
Tire rebuilding plants shall comply with the requirements of the International Building Code, as to construction, separation from other buildings or other portions of the same building, and protection.
Buffing operations shall be located in a room separated from the remainder of the building housing the tire rebuilding or tire recapping operations by a 1-hour fire barrier.
Exception: Buffing operations are not required to be separated where all of the following conditions are met:
1. Buffing operations are equipped with an approved continuous automatic water-spray system directed at the point of cutting action;
2. Buffing machines are connected to particle-collecting systems providing a minimum air movement of 1,500 cubic feet per minute (cfm) (0.71 m3/s) in volume and 4,500 feet per minute (fpm) (23 m/s) in-line velocity; and
3. The collecting system shall discharge the rubber particles to an approved outdoor noncombustible or fire-resistant container, which is emptied at frequent intervals to prevent overflow.
The buffing area shall be cleaned at frequent intervals to prevent the accumulation of rubber particles.
Each spray room or spray booth where flammable or combustible solvents are applied, shall comply with Chapter 24.
Open burning is prohibited in tire storage yards.
Cutting, welding or heating devices shall not be operated in tire storage yards.
Smoking is prohibited in tire storage yards, except in designated areas.
Tire storage piles shall not be located beneath electrical power lines having a voltage in excess of 750 volts or that supply power to fire emergency systems.
The owner or individual in charge of the tire storage yard shall be required to prepare and submit to the fire code official a fire safety plan for review and approval. The fire safety plan shall include provisions for fire department vehicle access. At least one copy of the fire safety plan shall be prominently posted and maintained at the storage yard.
The telephone number of the fire department and location of the nearest telephone shall be posted conspicuously in attended locations.
Tire storage shall be restricted to individual piles not exceeding 5,000 square feet (464.5 m2) of continuous area. Piles shall not exceed 50,000 cubic feet (1416 m3) in volume or 10 feet (3048 mm) in height.
Individual tire storage piles shall be separated from other piles by a clear space of at least 40 feet (12 192 mm).
Tire storage piles shall be separated by a clear space of at least 40 feet (12 192 mm) from piles of other stored product.
Tire storage piles shall be located at least 50 feet (15 240 mm) from lot lines and buildings.
Storage yards shall be maintained free from combustible ground vegetation for a distance of 40 feet (12 192 mm) from the stored material to grass and weeds; and for a distance of 100 feet (30 480 mm) from the stored product to brush and forested areas.
Where the bulk volume of stored product is more than 150,000 cubic feet (4248 m3), storage arrangement shall be in accordance with the following:
1. Individual storage piles shall comply with size and separation requirements in Sections 3405.1 through 3405.5.
2. Adjacent storage piles shall be considered a group, and the aggregate volume of storage piles in a group shall not exceed 150,000 cubic feet (4248 m3).

Separation between groups shall be at least 75 feet (22 860 mm) wide.

Outdoor waste tire storage shall not be located under bridges, elevated trestles, elevated roadways or elevated railroads.
New tire storage yards shall be provided with fire apparatus access roads in accordance with Section 503 and Section 3406.2. Existing tire storage yards shall be provided with fire apparatus access roads where required in Chapter 11.
Fire apparatus access roads shall be located within all pile clearances identified in Section 3405.4 and within all fire breaks required in Section 3405.5. Access roadways shall be within 150 feet (45 720 mm) of any point in the storage yard where storage piles are located, at least 20 feet (6096 mm) from any storage pile.
Where the bulk volume of stored material is more than 20,000 cubic feet (566 m3), a firmly anchored fence or other approved method of security that controls unauthorized access to the storage yard shall surround the storage yard.
The fence shall be constructed of approved materials and shall be at least 6 feet (1829 mm) high and provided with gates at least 20 feet (6096 mm) wide.
All gates to the storage yard shall be locked when the storage yard is not staffed.
Gateways shall be kept clear of obstructions and be fully openable at all times.
A public or private fire protection water supply shall be provided in accordance with Section 508. The water supply shall be arranged such that any part of the storage yard can be reached by using not more than 500 feet (152 m) of hose.
Buildings or structures shall be provided with portable fire extinguishers in accordance with Section 906. Fuel-fired vehicles operating in the storage yard shall be equipped with a minimum 2-A:20-B:C-rated portable fire extinguisher.
Where tires are stored on-tread, the dimension of the pile in the direction of the wheel hole shall not be more than 50 feet (15 240 mm). Tires stored adjacent to or along one wall shall not extend more than 25 feet (7620 mm) from that wall. Other piles shall not be more than 50 feet (15 240 mm) in width.
Resources
Help us
keep law free