ADOPTS WITH AMENDMENTS:

International Existing Building Code 2015 (IEBC 2015)

Heads up: There are no amended sections in this chapter.

301.1 General

AMENDMENT
This section has been amended at the state or city level.
The repair, alteration, change of occupancy, addition or relocation of all existing buildings shall comply with one of the methods listed in Sections 301.1.1 through 301.1.3 as selected by the applicant. Sections 301.1.1 through 301.1.3 shall not be applied in combination with each other. Where this code requires consideration of the seismic force-resisting system of an existing building subject to repair, alteration, change of occupancy, addition or relocation of existing buildings, the seismic evaluation and design shall be based on Section 301.1.4 regardless of which compliance method is used.

Exception: Subject to the approval of the code official, alterations complying with the laws in existence at the time the building or the affected portion of the building was built shall be considered in compliance with the provisions of this code unless the building is undergoing more than a limited structural alteration as defined in Section 907.4.4. New structural members added as part of the alteration shall comply with the rule 661—301.3(103A). Alterations of existing buildings in flood hazard areas shall comply with Section 701.3.

301.1.1 Prescriptive Compliance Method

AMENDMENT
This section has been amended at the state or city level.
Repairs, alterations, additions and changes of occupancy complying with Chapter 4 of this code in buildings complying with the state fire code shall be considered in compliance with the provisions of this code.
Repairs, alterations, additions, changes in occupancy and relocated buildings complying with the applicable requirements of Chapters 5 through 13 of this code shall be considered in compliance with the provisions of this code.
Repairs, alterations, additions, changes in occupancy and relocated buildings complying with Chapter 14 of this code shall be considered in compliance with the provisions of this code.

301.1.4 Seismic Evaluation and Design Procedures

AMENDMENT
This section has been amended at the state or city level.
The seismic evaluation and design shall be based on the procedures specified in the rule 661—301.3(103A) or ASCE 41. The procedures contained in Appendix A of this code shall be permitted to be used as specified in Section 301.1.4.2.

301.1.4.1 Compliance With International Building Code Rule 661—301.3(103A)-Level Seismic Forces

AMENDMENT
This section has been amended at the state or city level.
Where compliance with the seismic design provisions of the rule 661—301.3(103A) is required, the criteria shall be in accordance with one of the following:
  1. One-hundred percent of the values in the rule 661—301.3(103A). Where the existing seismic force-resisting system is a type that can be designated as "Ordinary," values of R, Ω0and Cd used for analysis in accordance with Chapter 16 of the rule 661—301.3(103A) shall be those specified for structural systems classified as "Ordinary" in accordance with Table 12.2-1 of ASCE 7, unless it can be demonstrated that the structural system will provide performance equivalent to that of a "Detailed," "Intermediate" or "Special" system.
  2. ASCE 41, using a Tier 3 procedure and the two-level performance objective in Table 301.1.4.1 for the applicable risk category.
[BS] TABLE 301.1.4.1 PERFORMANCE OBJECTIVES FOR USE IN ASCE 41 FOR COMPLIANCE WITH RULE 661—301.3(103A)-LEVEL SEISMIC FORCES

RISK CATEGORY
(Based on IBC Table 1604.5)
STRUCTURAL PERFORMANCE LEVEL FOR USE
WITH BSE-1N EARTHQUAKE HAZARD LEVEL
STRUCTURAL PERFORMANCE LEVEL FOR USE
WITH BSE-2N EARTHQUAKE HAZARD LEVEL
I Life Safety (S-3) Collapse Prevention (S-5)
II Life Safety (S-3) Collapse Prevention (S-5)
III Damage Control (S-2) Limited Safety (S-4)
IV Immediate Occupancy (S-1) Life Safety (S-3)

301.1.4.2 Compliance With Reduced International Building Code Rule 661—301.3(103A)-Level Seismic Forces

AMENDMENT
This section has been amended at the state or city level.
Where seismic evaluation and design is permitted to meet reduced rule 661—301.3(103A) seismic force levels, the criteria used shall be in accordance with one of the following:
  1. The rule 661—301.3(103A) using 75 percent of the prescribed forces. Values of R, Ω0 and Cd used for analysis shall be as specified in Section 301.1.4.1 of this code.
  2. Structures or portions of structures that comply with the requirements of the applicable chapter in Appendix A as specified in Items 2.1 through 2.5 and subject to the limitations of the respective Appendix A chapters shall be deemed to comply with this section.
    1. The seismic evaluation and design of unreinforced masonry bearing wall buildings in Risk Category I or II are permitted to be based on the procedures specified in Appendix Chapter A1.
    2. Seismic evaluation and design of the wall anchorage system in reinforced concrete and reinforced masonry wall buildings with flexible diaphragms in Risk Category I or II are permitted to be based on the procedures specified in Chapter A2.
    3. Seismic evaluation and design of cripple walls and sill plate anchorage in residential buildings of light-frame wood construction in Risk Category I or II are permitted to be based on the procedures specified in Chapter A3.
    4. Seismic evaluation and design of soft, weak, or open-front wall conditions in multiunit residential buildings of wood construction in Risk Category I or II are permitted to be based on the procedures specified in Chapter A4.
    5. Seismic evaluation and design of concrete buildings assigned to Risk Category I, II or III are permitted to be based on the procedures specified in Chapter A5.
  3. ASCE 41, using the performance objective in Table 301.1.4.2 for the applicable risk category.


[BS] TABLE 301.1.4.2
PERFORMANCE OBJECTIVES FOR USE IN ASCE 41 FOR COMPLIANCE WITH REDUCED RULE 661—301.3(103A)-LEVEL SEISMIC FORCES
RISK CATEGORY
(Based on IBC Table 1604.5)
STRUCTURAL PERFORMANCE LEVEL FOR USE WITH BSE-1E EARTHQUAKE HAZARD LEVEL
I Life Safety (S-3)
II Life Safety (S-3)
III Damage Control (S-2). See Note a
IV Immediate Occupancy (S-1)
  1. Tier 1 evaluation at the Damage Control performance level shall use the Tier 1 Life Safety checklists and Tier 1 Quick Check provisions midway between those specified for Life Safety and Immediate Occupancy performance.
The provisions of Section 302 apply to all alterations, repairs, additions, relocations of structures and changes of occupancy regardless of compliance method.

302.2 Additional Codes

AMENDMENT
This section has been amended at the state or city level.
Alterations, repairs, additions and changes of occupancy to, or relocation of, existing buildings and structures shall comply with the provisions for alterations, repairs, additions and changes of occupancy or relocation, respectively, in this code and the International Energy Conservation Code, state fire code, rule 661—301.9(103A), state mechanical code, state plumbing code, International Property Maintenance Code, International Private Sewage Disposal Code, rule 661—301.8(103A) and NFPA 70. Where provisions of the other codes conflict with provisions of this code, the provisions of this code shall take precedence.
Materials already in use in a building in compliance with requirements or approvals in effect at the time of their erection or installation shall be permitted to remain in use unless determined by the building official to be unsafe.
Except as otherwise required or permitted by this code, materials permitted by the applicable code for new construction shall be used. Like materials shall be permitted for repairs and alterations, provided no unsafe condition is created. Hazardous materials shall not be used where the code for new construction would not permit their use in buildings of similar occupancy, purpose and location.

302.5 Occupancy and Use

AMENDMENT
This section has been amended at the state or city level.
When determining the appropriate application of the referenced sections of this code, the occupancy and use of a building shall be determined in accordance with Chapter 3 of the rule 661—301.3(103A).
UpCodes Premium
Leverage the most sophisticated code compliance platform.
TRY FREE FOR TWO WEEKS VISIT PRICING