ADOPTS WITH AMENDMENTS:

International Existing Building Code 2015 (IEBC 2015)

Heads up: There are no amended sections in this chapter.
An addition to a building or structure shall comply with the International Codes as adopted for new construction without requiring the existing building or structure to comply with any requirements of those codes or of these provisions, except as required by this chapter. Where an addition impacts the existing building or structure, that portion shall comply with this code.
An addition shall not create or extend any nonconformity in the existing building to which the addition is being made with regard to accessibility, structural strength, fire safety, means of egress, or the capacity of mechanical, plumbing, or electrical systems.
Any repair or alteration work within an existing building to which an addition is being made shall comply with the applicable requirements for the work as classified in Chapter 5.

1102.1 Height Limitations

AMENDMENT
This section has been amended at the state or city level.
No addition shall increase the height of an existing building beyond that permitted under the applicable provisions of Chapter 5 of the rule 661—301.3(103A) for new buildings.

1102.2 Area Limitations

AMENDMENT
This section has been amended at the state or city level.
No addition shall increase the area of an existing building beyond that permitted under the applicable provisions of Chapter 5 of the rule 661—301.3(103A) for new buildings unless fire separation as required by the rule 661—301.3(103A) is provided.

Exception: In-filling of floor openings and nonoccupiable appendages such as elevator and exit stairway shafts shall be permitted beyond that permitted by the rule 661—301.3(103A).

1102.3 Fire Protection Systems

AMENDMENT
This section has been amended at the state or city level.
Existing fire areas increased by the addition shall comply with Chapter 9 of the rule 661—301.3(103A).

1103.1 Compliance With the International Building CodeRule 661—301.3(103A)

AMENDMENT
This section has been amended at the state or city level.
Additions to existing buildings or structures are new construction and shall comply with the rule 661—301.3(103A).

1103.2 Additional Gravity Loads

AMENDMENT
This section has been amended at the state or city level.
Existing structural elements supporting any additional gravity loads as a result of additions shall comply with the rule 661—301.3(103A).

Exceptions:
  1. Structural elements whose stress is not increased by more than 5 percent.
  2. Buildings of Group R occupancy with no more than five dwelling units or sleeping units used solely for residential purposes where the existing building and the addition comply with the conventional lightframe construction methods of the rule 661—301.3(103A) or the provisions of the rule 661—301.8(103A).

1103.3 Lateral Force-Resisting System

AMENDMENT
This section has been amended at the state or city level.
The lateral force-resisting system of existing buildings to which additions are made shall comply with Sections 1103.3.1, 1103.3.2 and 1103.3.3.

Exceptions:
  1. Buildings of Group R occupancy with no more than five dwelling or sleeping units used solely for residential purposes where the existing building and the addition comply with the conventional light-frame construction methods of the rule 661—301.3(103A) or the provisions of the rule 661—301.8(103A).
  2. Any existing lateral load-carrying structural element whose demand-capacity ratio with the addition considered is not more than 10 percent greater than its demand-capacity ratio with the addition ignored shall be permitted to remain unaltered. For purposes of this exception, comparisons of demand-capacity ratios and calculation of design lateral loads, forces and capacities shall account for the cumulative effects of additions and alterations since original construction. For purposes of calculating demand-capacity ratios, the demand shall consider applicable load combinations involving rule 661—301.3(103A)-level seismic forces in accordance with Section 301.1.4.1.

1103.3.1 Vertical Addition

AMENDMENT
This section has been amended at the state or city level.
Any element of the lateral force-resisting system of an existing building subjected to an increase in vertical or lateral loads from the vertical addition shall comply with the rule 661—301.3(103A) wind provisions and the rule 661—301.3(103A)-level seismic forces specified in Section 301.1.4.1 of this code.

1103.3.2 Horizontal Addition

AMENDMENT
This section has been amended at the state or city level.
Where horizontal additions are structurally connected to an existing structure, all lateral force-resisting elements of the existing structure affected by such addition shall comply with the rule 661—301.3(103A) wind provisions and the IBC level seismic forces specified in Section 301.1.4.1 of this code.
Voluntary addition of structural elements to improve the lateral force-resisting system of an existing building shall comply with Section 807.6.

1103.4 Snow Drift Loads

AMENDMENT
This section has been amended at the state or city level.
Any structural element of an existing building subjected to additional loads from the effects of snow drift as a result of an addition shall comply with the rule 661—301.3(103A).

Exceptions:
  1. Structural elements whose stress is not increased by more than 5 percent.
  2. Buildings of Group R occupancy with no more than five dwelling units or sleeping units used solely for residential purposes where the existing building and the addition comply with the conventional lightframe construction methods of the rule 661—301.3(103A) or the provisions of the rule 661—301.8(103A).

1103.5 Flood Hazard Areas

AMENDMENT
This section has been amended at the state or city level.
Additions and foundations in flood hazard areas shall comply with the following requirements:
  1. For horizontal additions that are structurally interconnected to the existing building:
    1. If the addition and all other proposed work, when combined, constitute substantial improvement, the existing building and the addition shall comply with Section 1612 of the rule 661—301.3(103A), or Section R322 of the rule 661—301.8(103A), as applicable.
    2. If the addition constitutes substantial improvement, the existing building and the addition shall comply with Section 1612 of the rule 661—301.3(103A), or Section R322 of the rule 661—301.8(103A), as applicable.
  2. For horizontal additions that are not structurally interconnected to the existing building:
    1. The addition shall comply with Section 1612 of the rule 661—301.3(103A), or Section R322 of the rule 661—301.8(103A), as applicable.
    2. If the addition and all other proposed work, when combined, constitute substantial improvement, the existing building and the addition shall comply with Section 1612 of the rule 661—301.3(103A), or Section R322 of the rule 661—301.8(103A), as applicable.
  3. For vertical additions and all other proposed work that, when combined, constitute substantial improvement, the existing building shall comply with Section 1612 of the rule 661—301.3(103A), or Section R322 of the rule 661—301.8(103A), as applicable.
  4. For a raised or extended foundation, if the foundation work and all other proposed work, when combined, constitute substantial improvement, the existing building shall comply with Section 1612 of the rule 661—301.3(103A), or Section R322 of the rule 661—301.8(103A), as applicable.
  5. For a new foundation or replacement foundation, the foundation shall comply with Section 1612 of the rule 661—301.3(103A) or Section R322 of the rule 661—301.8(103A), as applicable.

1104.1 Smoke Alarms in Existing Portions of a Building

AMENDMENT
This section has been amended at the state or city level.
Where an addition is made to a building or structure of a Group R or I-1 occupancy, the existing building shall be provided with smoke alarms as required by Section 1103.8 of the state fire code or Section R314 of the rule 661—301.8(103A) as applicable.

1105.1 Minimum Requirements

AMENDMENT
This section has been amended at the state or city level.

1105.2 Accessible Dwelling Units and Sleeping Units

AMENDMENT
This section has been amended at the state or city level.
Where Group I-1, I-2, I-3, R-1, R-2 or R-4 dwelling or sleeping units are being added, the requirements of Section 1107 of the rule 661—301.3(103A) for accessible units apply only to the quantity of spaces being added.

1105.3 Type A Dwelling or Sleeping Units

AMENDMENT
This section has been amended at the state or city level.
Where more than 20 Group R-2 dwelling or sleeping units are being added, the requirements of Section 1107 of the rule 661—301.3(103A) for Type A units and Chapter 9 of the rule 661—301.3(103A) for visible alarms apply only to the quantity of the spaces being added.

1105.4 Type B Dwelling or Sleeping Units

AMENDMENT
This section has been amended at the state or city level.
Where four or more Group I-1, I-2, R-1, R-2, R-3 or R-4 dwelling or sleeping units are being added, the requirements of Section 1107 of the rule 661—301.3(103A) for Type B units and Chapter 9 of the rule 661—301.3(103A) for visible alarms apply only to the quantity of spaces being added.

1106.1 Minimum Requirements

AMENDMENT
This section has been amended at the state or city level.
Additions to existing buildings shall conform to the energy requirements of the International Energy Conservation Code or rule 661—301.8(103A) as they relate to new construction.