The provisions of this chapter shall control the design and construction of the interior and
exterior wall covering for all buildings.
Products sensitive to adverse weather shall not be installed until adequate weather protection for the installation is provided. Exterior sheathing shall be dry before applying exterior cover.
Interior coverings or wall finishes shall be installed in accordance with this chapter and Table
R702.1(1), Table R702.1(2), Table R702.1(3) and
Table R702.3.5. Interior masonry veneer shall comply with the requirements of
Section R703.7.1 for support and
Section R703.7.4 for anchorage, except an air space is not required. Interior finishes and materials shall conform to the
flame spread and smoke-development requirements of
Section R302.9.
TABLE R702.1(1)
THICKNESS OF PLASTER
PLASTER BASE |
FINISHED THICKNESS OF PLASTER FROM FACE OF LATH, MASONRY, CONCRETE (inches) |
Gypsum Plaster |
Cement Plaster |
Expanded metal lath |
5/8, minimuma |
5/8, minimuma |
Wire lath |
5/8, minimuma |
3/4, minimum (interior)b 7/8, minimum (exterior)b |
Gypsum lathg |
1/2, minimum |
3/4, minimum (interior)b |
Masonry wallsc |
1/2, minimum |
1/2, minimum |
Monolithic concrete wallsc, d |
5/8, maximum |
7/8, maximum |
Monolithic concrete ceilingsc, d |
3/8, maximume |
1/2, maximum |
Gypsum veneer basef, g |
1/16, minimum |
3/4, minimum (interior)b |
Gypsum sheathingg |
— |
3/4, minimum (interior)b 7/8, minimum (exterior)b |
For SI: 1 inch = 25.4 mm.
- When measured from back plane of expanded metal lath, exclusive of ribs, or self-furring lath, plaster thickness shall be 3/4 inch minimum.
- When measured from face of support or backing.
- Because masonry and concrete surfaces may vary in plane, thickness of plaster need not be uniform.
- When applied over a liquid bonding agent, finish coat may be applied directly to concrete surface.
- Approved acoustical plaster may be applied directly to concrete or over base coat plaster, beyond the maximum plaster thickness shown.
- Attachment shall be in accordance with Table R702.3.5.
- Where gypsum board is used as a base for cement plaster, a water-resistive barrier complying with Section R703.2 shall be provided.
TABLE R702.1(2)
GYPSUM PLASTER PROPORTIONSa
NUMBER |
COAT |
PLASTER BASE OR LATH |
MAXIMUM VOLUME AGGREGATE PER 100 POUNDS NEAT PLASTERb (cubic feet) |
Damp Loose Sanda |
Perlite or Vermiculitec |
Two-coat work |
Base coat |
Gypsum lath |
2.5 |
2 |
Base coat |
Masonry |
3 |
3 |
Three-coat work |
First coat |
Lath |
2d |
2 |
Second coat |
Lath |
3d |
2e |
First and second coats |
Masonry |
3 |
3 |
For SI: 1 inch = 25.4 mm, 1 cubic foot = 0.0283 m
3, 1 pound = 0.454 kg.
- Wood-fibered gypsum plaster may be mixed in the proportions of 100 pounds of gypsum to not more than 1 cubic foot of sand where applied on masonry or concrete.
- When determining the amount of aggregate in set plaster, a tolerance of 10 percent shall be allowed.
- Combinations of sand and lightweight aggregate may be used, provided the volume and weight relationship of the combined aggregate to gypsum plaster is maintained.
- If used for both first and second coats, the volume of aggregate may be 2.5 cubic feet.
- Where plaster is 1 inch or more in total thickness, the proportions for the second coat may be increased to 3 cubic feet.
TABLE R702.1(3)
CEMENT PLASTER PROPORTIONS, PARTS BY VOLUME
COAT |
CEMENT PLASTER TYPE |
CEMENTITIOUS MATERIALS |
VOLUME OF AGGREGATE PER SUM OF SEPARATE VOLUMES OF CEMENTITIOUS MATERIALSb |
Portland Cement Type I, II or III or Blended Cement Type IP, I (PM), IS or I (SM) |
Plastic Cement |
Masonry Cement Type M, S or N |
Lime |
First |
Portland or blended |
1 |
|
|
3/4 - 11/2a |
21/2 - 4 |
Masonry |
|
|
1 |
|
21/2 - 4 |
Plastic |
|
1 |
|
|
21/2 - 4 |
Second |
Portland or blended |
1 |
|
|
3/4 - 11/2 |
3 - 5 |
Masonry |
|
|
1 |
|
3 - 5 |
Plastic |
|
1 |
|
|
3 - 5 |
Finish |
Portland or blended |
1 |
|
|
3/4 - 2 |
11/2 - 3 |
Masonry |
|
|
1 |
|
11/2 - 3 |
Plastic |
|
1 |
|
|
11/2 - 3 |
For SI: 1 inch = 25.4 mm, 1 pound = 0.545 kg.
- Lime by volume of 0 to 3/4 shall be used when the plaster will be placed over low-absorption surfaces such as dense clay tile or brick.
- The same or greater sand proportion shall be used in the second coat than used in the first coat.
Gypsum plaster materials shall conform to ASTM C 5, C 22, C 28, C 35, C 59, C 61, C 587, C 631, C 847, C 933, C 1032 and C 1047, and shall be installed or applied in compliance with ASTM C 843 and C 844. Gypsum lath or gypsum base for veneer plaster shall conform to ASTM C 1396. Plaster shall not be less than three coats when applied over metal lath and not less than two coats when applied over other bases permitted by this section, except that veneer plaster may be applied in one coat not to exceed
3/
16 inch (4.76 mm) thickness, provided the total thickness is in accordance with
Table R702.1(1).
Cement plaster materials shall conform to ASTM C 91 (Type M, S or N), C 150 (Type I, II and III), C 595 [Type IP, I (PM), IS and I (SM), C 847, C 897, C 926, C 933, C 1032, C 1047 and C 1328, and shall be installed or applied in compliance with ASTM C 1063. Gypsum lath shall conform to ASTM C 1396. Plaster shall not be less than three coats when applied over metal lath and not less than two coats when applied over other bases permitted by this section, except that veneer plaster may be applied in one coat not to exceed
3/
16 inch (4.76 mm) thickness, provided the total thickness is in accordance with
Table R702.1(1).
Each coat shall be kept in a moist condition for at least 24 hours prior to application of the next coat.
Exception: Applications installed in accordance with ASTM C 926.
The finish coat for two-coat
cement plaster shall not be applied sooner than 48 hours after application of the first coat. For three coat
cement plaster the second coat shall not be applied sooner than 24 hours after application of the first coat. The finish coat for three-coat
cement plaster shall not be applied sooner than 48 hours after application of the second coat.
Support spacing for gypsum or metal lath on
walls or ceilings shall not exceed 16 inches (406 mm) for
3/
8-inch-thick (9.5 mm) or 24 inches (610 mm) for
1/
2-inch-thick (12.7 mm) plain gypsum lath. Gypsum lath shall be installed at right angles to support framing with end joints in adjacent courses staggered by at least one framing space.
All gypsum board materials and accessories shall conform to ASTM C 22, C 475, C 514, C 1002, C 1047, C 1177, C 1178, C 1278, C 1396 or C 1658 and shall be installed in accordance with the provisions of this section. Adhesives for the installation of gypsum board shall conform to ASTM C 557.
Wood framing supporting gypsum board shall not be less than 2 inches (51 mm) nominal thickness in the least dimension except that wood furring strips not less than 1-inch by 2-inch (25 mm by 51 mm) nominal dimension may be used over
solid backing or framing spaced not more than 24 inches (610 mm) on center.
Cold-formed steel framing supporting gypsum board shall not be less than 11/4 inches (32 mm) wide in the least dimension. Nonload-bearing cold-formed steel framing shall comply with ASTM C 645. Load-bearing cold-formed steel framing and all cold-formed steel framing from 0.033 inch to 0.112 inch (1 mm to 3 mm) thick shall comply with ASTM C 955.
Foam plastics for
insulating concrete form walls constructed in accordance with Sections
R404.1.2 and R611 on the interior of
habitable spaces shall be protected in accordance with
Section R316.4. Use of adhesives in conjunction with mechanical fasteners is permitted. Adhesives used for interior and exterior finishes shall be compatible with the insulating form materials.
Maximum spacing of
supports and the size and spacing of fasteners used to attach gypsum board shall comply with
Table R702.3.5. Gypsum sheathing shall be attached to
exterior walls in accordance with
Table R602.3(1). Gypsum board shall be applied at right angles or parallel to framing members. All edges and ends of gypsum board shall occur on the framing members, except those edges and ends that are perpendicular to the framing members. Interior gypsum board shall not be installed where it is directly exposed to the weather or to water.
TABLE R702.3.5
MINIMUM THICKNESS AND APPLICATION OF GYPSUM BOARD
THICKNESS OF GYPSUM BOARD (inches) | APPLICATION | ORIENTATION OF GYPSUM BOARD TO FRAMING | MAXIMUM SPACING OF FRAMING MEMBERS (inches o.c.) | MAXIMUM SPACING OF FASTENERS (inches) | SIZE OF NAILS FOR APPLICATION TO WOOD FRAMINGc |
Nailsa | Screwsb |
Application without adhesive |
3/8 | Ceilingd | Perpendicular | 16 | 7 | 12 | 13 gage, 11/4" long, 19/64" head; 0.098" diameter, 11/4" long, annular-ringed; or 4d cooler nail, 0.080" diameter, 13/8" long, 7/32" head. |
Wall | Either direction | 16 | 8 | 16 |
1/2 | Ceiling | Either direction | 16 | 7 | 12 | 13 gage, 13/8" long, 19/64" head; 0.098" diameter, 11/4" long, annular-ringed; 5d cooler nail, 0.086" diameter, 15/8" long, 15/64" head; or gypsum board nail, 0.086" diameter, 15/8" long, 9/32" head. |
Ceilingd | Perpendicular | 24 | 7 | 12 |
Wall | Either direction | 24 | 8 | 12 |
Wall | Either direction | 16 | 8 | 16 |
5/8 | Ceiling | Either direction | 16 | 7 | 12 | 13 gage, 15/8" long, 19/64" head; 0.098" diameter, 13/8" long, annular-ringed; 6d cooler nail, 0.092" diameter, 17/8" long, 1/4" head; or gypsum board nail, 0.0915" diameter, 17/8" long, 19/64" head. |
Ceilinge | Perpendicular | 24 | 7 | 12 |
Wall | Either direction | 24 | 8 | 12 |
Wall | Either direction | 16 | 8 | 16 |
Application with adhesive |
3/8 | Ceilingd | Perpendicular | 16 | 16 | 16 | Same as above for 3/8" gypsum board |
Wall | Either direction | 16 | 16 | 24 |
1/2 or 5/8 | Ceiling | Either direction | 16 | 16 | 16 | Same as above for 1/2" and 5/8" gypsum board, respectively |
Ceilingd | Perpendicular | 24 | 12 | 16 |
Wall | Either direction | 24 | 16 | 24 |
Two 3/8 layers | Ceiling | Perpendicular | 16 | 16 | 16 | Base ply nailed as above for 1/2" gypsum board; face ply installed with adhesive |
Wall | Either direction | 24 | 24 | 24 |
For SI: 1 inch = 25.4 mm.
- For application without adhesive, a pair of nails spaced not less than 2 inches apart or more than 21/2 inches apart may be used with the pair of nails spaced 12 inches on center.
- Screws shall be in accordance with Section R702.3.6. Screws for attaching gypsum board to structural insulated panels shall penetrate the wood structural panel facing not less than 7/16 inch.
- Where cold-formed steel framing is used with a clinching design to receive nails by two edges of metal, the nails shall be not less than 5/8 inch longer than the gypsum board thickness and shall have ringed shanks. Where the cold-formed steel framing has a nailing groove formed to receive the nails, the nails shall have barbed shanks or be 5d, 131/2 gage, 15/8 inches long, 15/64-inch head for 1/2-inch gypsum board; and 6d, 13 gage, 17/8 inches long, 15/64-inch head for 5/8-inch gypsum board.
- Three-eighths-inch-thick single-ply gypsum board shall not be used on a ceiling where a water-based textured finish is to be applied, or where it will be required to support insulation above a ceiling. On ceiling applications to receive a water-based texture material, either hand or spray applied, the gypsum board shall be applied perpendicular to framing. When applying a water-based texture material, the minimum gypsum board thickness shall be increased from 3/8 inch to 1/2 inch for 16-inch on center framing, and from 1/2 inch to 5/8 inch for 24-inch on center framing or 1/2-inch sag-resistant gypsum ceiling board shall be used.
- Type X gypsum board for garage ceilings beneath habitable rooms shall be installed perpendicular to the ceiling framing and shall be fastened at maximum 6 inches o.c. by minimum 17/8 inches 6d coated nails or equivalent drywall screws.
Screws for attaching gypsum board to wood framing shall be Type W or Type S in accordance with ASTM C 1002 and shall penetrate the wood not less than
5/
8 inch (16 mm). Gypsum board shall be attached to cold-formed steel framing with minimum No. 6 screws. Screws for attaching gypsum board to cold-formed steel framing less than 0.033 inch (1 mm) thick shall be Type S in accordance with ASTM C 1002 or bugle head style in accordance with ASTM C 1513 and shall penetrate the steel not less than
3/
8 inch (9.5 mm). Screws for attaching gypsum board to cold-formed steel framing 0.033 inch to 0.112 inch (1 mm to 3 mm) thick shall be in accordance with ASTM C 954 or bugle head style in accordance with ASTM C 1513. Screws for attaching gypsum board to
structural insulated panels shall penetrate the
wood structural panel facing not less than
7/
16 inch (11 mm).
Use of gypsum board shall be permitted on wood joists to create a horizontal
diaphragm in accordance with
Table R702.3.7. Gypsum board shall be installed perpendicular to ceiling framing members. End joints of adjacent courses of board shall not occur on the same joist. The maximum allowable
diaphragm proportions shall be 1
1/
2:1 between shear resisting elements. Rotation or cantilever conditions shall not be permitted. Gypsum board shall not be used in
diaphragm ceilings to resist lateral forces imposed by masonry or
concrete construction. All perimeter edges shall be blocked using wood members not less than 2-inch by 6-inch (51 mm by 152 mm) nominal dimension. Blocking material shall be installed flat over the top plate of the wall to provide a nailing surface not less than 2 inches (51 mm) in width for the attachment of the gypsum board.
TABLE R702.3.7
SHEAR CAPACITY FOR HORIZONTAL WOOD-FRAMED GYPSUM BOARD DIAPHRAGM CEILING ASSEMBLIES
MATERIAL |
THICKNESS OF MATERIAL (min.) (inch) |
SPACING OF FRAMING MEMBERS (max.) (inch) |
SHEAR VALUEa, b (plf of ceiling) |
MINIMUM FASTENER SIZEc, d |
Gypsum board |
1/2 |
16 o.c. |
90 |
5d cooler or wallboard nail; 15/8-inch long; 0.086-inch shank; 15/64-inch head |
Gypsum board |
1/2 |
24 o.c. |
70 |
5d cooler or wallboard nail; 15/8-inch long; 0.086-inch shank; 15/64-inch head |
For SI: 1 inch = 25.4 mm, 1 pound per linear foot = 1.488 kg/m.
- Values are not cumulative with other horizontal diaphragm values and are for short-term loading caused by wind or seismic loading. Values shall be reduced 25 percent for normal loading.
- Values shall be reduced 50 percent in Seismic Design Categories D0, D1, D2 and E.
- 11/4-inch, #6 Type S or W screws may be substituted for the listed nails.
- Fasteners shall be spaced not more than 7 inches on center at all supports, including perimeter blocking, and not less than 3/8 inch from the edges and ends of the gypsum board.
Gypsum board used as the base or backer for adhesive application of ceramic tile or other required nonabsorbent finish material shall conform to ASTM C 1396, C 1178 or C1278. Use of water-resistant gypsum backing board shall be permitted on ceilings where framing spacing does not exceed 12 inches (305 mm) on center for 1/2-inch-thick (12.7 mm) or 16 inches (406 mm) for 5/8-inch-thick (16 mm) gypsum board. Water-resistant gypsum board shall not be installed over a Class I or II vapor retarder in a shower or tub compartment. Cut or exposed edges, including those at wall intersections, shall be sealed as recommended by the manufacturer.
Water resistant gypsum backing board shall not be used where there will be direct exposure to water, or in areas subject to continuous high humidity.
Ceramic tile surfaces shall be installed in accordance with ANSI A108.1, A108.4, A108.5, A108.6, A108.11, A118.1, A118.3, A136.1 and A137.1.
Fiber-cement, fiber-mat reinforced cementitious backer units,
glass mat gypsum backers or fiber-reinforced gypsum backers in compliance with ASTM C 1288, C 1325, C 1178 or C 1278, respectively, and installed in accordance with manufacturers' recommendations shall be used as backers for wall tile in tub and shower areas and wall panels in shower areas.
Wood veneer paneling and hardboard paneling shall be placed on wood or cold-formed steel framing spaced not more than 16 inches (406 mm) on center. Wood veneer and hard board paneling less than 1/4-inch (6 mm) nominal thickness shall not have less than a 3/8-inch (10 mm) gypsum board backer. Wood veneer paneling not less than 1/4-inch (6 mm) nominal thickness shall conform to ANSI/HPVA HP-1. Hardboard paneling shall conform to CPA/ANSI A135.5.
Wood shakes and shingles shall conform to CSSB Grading Rules for Wood Shakes and Shingles and shall be permitted to be installed directly to the studs with maximum 24 inches (610 mm) on-center spacing.
Nails, staples or glue are permitted for attaching shakes or shingles to the wall, and attachment of the shakes or shingles directly to the surface shall be permitted provided the fasteners are appropriate for the type of wall surface material. When nails or staples are used, two fasteners shall be provided and shall be placed so that they are covered by the course above.
Where furring strips are used, they shall be 1 inch by 2 inches or 1 inch by 3 inches (25 mm by 51 mm or 25 mm by 76 mm), spaced a distance on center equal to the desired exposure, and shall be attached to the wall by nailing through other wall material into the studs.
Class I or II vapor retarders are required on the interior side of frame
walls in Climate Zones 5, 6, 7, 8 and Marine 4.
Exceptions:
- Basement walls.
- Below grade portion of any wall.
- Construction where moisture or its freezing will not damage the materials.
Class III vapor retarders shall be permitted where any one of the conditions in
Table R702.7.1 is met.
TABLE R702.7.1
CLASS III VAPOR RETARDERS
CLIMATE ZONE |
CLASS III VAPOR RETARDERS PERMITTED FOR:a |
Marine 4 |
Vented cladding over wood structural panels. |
Vented cladding over fiberboard. |
Vented cladding over gypsum. |
Insulated sheathing withR-value ≥ 2.5 over 2 × 4 wall. |
Insulated sheathing withR-value ≥ 3.75 over 2 × 6 wall. |
5 |
Vented cladding over wood structural panels. |
Vented cladding over fiberboard. |
Vented cladding over gypsum. |
Insulated sheathing withR-value ≥ 5 over 2 × 4 wall. |
Insulated sheathing withR-value ≥ 7.5 over 2 × 6 wall. |
6 |
Vented cladding over fiberboard. |
Vented cladding over gypsum. |
Insulated sheathing withR-value ≥ 7.5 over 2 × 4 wall. |
Insulated sheathing withR-value ≥ 11.25 over 2 × 6 wall. |
7 and 8 |
Insulated sheathing withR-value ≥ 10 over 2 × 4 wall. |
Insulated sheathing withR-value ≥ 15 over 2 × 6 wall. |
The
vapor retarder class shall be based on the manufacturer's certified testing or a tested assembly.
The following shall be deemed to meet the class specified:
Class I: Sheet polyethylene, unperforated aluminum foil.
Class II: Kraft-faced fiberglass batts.
Class III: Latex or enamel paint.
For the purposes of this section, vented
cladding shall include the following minimum clear air spaces. Other openings with the equivalent
vent area shall be permitted.
- Vinyl lap or horizontal aluminum siding applied over a weather resistive barrier as specified in Table R703.4.
- Brick veneer with a clear airspace as specified in Table R703.7.4.
- Other approved vented claddings.
The
exterior wall envelope shall be designed and constructed in a manner that prevents the accumulation of water within the wall assembly by providing a water-resistant barrier behind the exterior veneer as required by
Section R703.2 and a means of draining to the exterior water that enters the assembly. Protection against condensation in the
exterior wall assembly shall be provided in accordance with
Section R702.7 of this code.
Exceptions:
- A weather-resistant exterior wall envelope shall not be required over concrete or masonry walls designed in accordance with Chapter 6 and flashed according to Section R703.7 or R703.8.
- Compliance with the requirements for a means of drainage, and the requirements of Sections R703.2 and R703.8, shall not be required for an exterior wall envelope that has been demonstrated to resist wind-driven rain through testing of the exterior wall envelope, including joints, penetrations and intersections with dissimilar materials, in accordance with ASTM E 331 under the following conditions:
- Exterior wall envelope test assemblies shall include at least one opening, one control joint, one wall/eave interface and one wall sill. All tested openings and penetrations shall be representative of the intended end-use configuration.
- Exterior wall envelope test assemblies shall be at least 4 feet by 8 feet (1219 mm by 2438 mm) in size.
- Exterior wall assemblies shall be tested at a minimum differential pressure of 6.24 pounds per square foot (299 Pa).
- Exterior wall envelope assemblies shall be subjected to the minimum test exposure for a minimum of 2 hours.
The
exterior wall envelope design shall be considered to resist wind-driven rain where the results of testing indicate that water did not penetrate control joints in the
exterior wall envelope, joints at the perimeter of openings penetration or intersections of terminations with dissimilar materials.
Wall coverings, backing materials and their attachments shall be capable of resisting wind loads in accordance with Tables
R301.2(2) and
R301.2(3). Wind-pressure resistance of the siding and backing materials shall be determined by ASTM E 330 or other applicable standard test methods. Where wind-pressure resistance is determined by design analysis, data from approved design standards and analysis conforming to generally accepted engineering practice shall be used to evaluate the siding and backing material and its fastening. All applicable failure modes including bending rupture of siding, fastener withdrawal and fastener head pull-through shall be considered in the testing or design analysis. Where the wall covering and the backing material resist wind load as an assembly, use of the design capacity of the assembly shall be permitted.
One layer of No. 15 asphalt felt, free from holes and breaks, complying with ASTM D 226 for Type 1 felt or other approved
water-resistive barrier shall be applied over studs or sheathing of all
exterior walls. Such felt or material shall be applied horizontally, with the upper layer lapped over the lower layer not less than 2 inches (51 mm). Where joints occur, felt shall be lapped not less than 6 inches (152 mm). The felt or other approved material shall be continuous to the top of
walls and terminated at penetrations and building appendages in a manner to meet the requirements of the
exterior wall envelope as described in
Section R703.1.
- In detached accessory buildings.
- Under exterior wall finish materials as permitted in Table R703.4.
- Under paperbacked stucco lath when the paper backing is an approved water-resistive barrier.
Joints in wood, hardboard or
wood structural panel siding shall be made as follows unless otherwise approved. Vertical joints in panel siding shall occur over framing members, unless wood or
wood structural panel sheathing is used, and shall be shiplapped or covered with a batten. Horizontal joints in panel siding shall be lapped a minimum of 1 inch (25 mm) or shall be shiplapped or shall be flashed with Z-flashing and occur over
solid blocking, wood or
wood structural panel sheathing.
Horizontal lap siding shall be installed in accordance with the manufacturer's recommendations. Where there are no recommendations the siding shall be lapped a minimum of 1 inch (25 mm), or 1/2 inch (13 mm) if rabbeted, and shall have the ends caulked, covered with a batten or sealed and installed over a strip of flashing.
Unless specified otherwise, all wall coverings shall be securely fastened in accordance with
Table R703.4 or with other
approved aluminum, stainless steel, zinc-coated or other
approved corrosion-resistive fasteners. Where the
basic wind speed in accordance with
Figure R301.2(4)A is 110 miles per hour (49 m/s) or higher, the attachment of wall coverings shall be designed to resist the component and
cladding loads specified in
Table R301.2(2), adjusted for height and exposure in accordance with
Table R301.2(3).
TABLE R703.4
WEATHER-RESISTANT SIDING ATTACHMENT AND MINIMUM THICKNESS
SIDING MATERIAL |
NOMINAL THICKNESSa (inches) |
JOINT TREATMENT |
WATER- RESISTIVE BARRIER REQUIRED |
TYPE OF SUPPORTS FOR THE SIDING MATERIAL AND FASTENERSb, c, d
|
Wood or wood structural panel sheathing into stud |
Fiberboard sheathing into stud |
Gypsum sheathing into stud |
Foam plastic sheathing into stud |
Direct to studs |
Number or spacing of fasteners |
Horizonal aluminume |
Without insulation |
0.019f |
Lap |
Yes |
0.120 nail 11/2" long |
0.120 nail 2" long |
0.120 nail 2" long |
0.120 naily |
Not allowed |
Same as stud spacing |
0.024 |
Lap |
Yes |
0.120 nail 11/2" long |
0.120 nail 2" long |
0.120 nail 2" long |
0.120 naily |
Not allowed |
With insulation |
0.019 |
Lap |
Yes |
0.120 nail 11/2" long |
0.120 nail 21/2" long |
0.120 nail 21/2" long |
0.120 naily |
0.120 nail 11/2" long |
Anchored veneer: brick, concrete, masonry or stone |
2 |
Section R703 |
Yes |
See Section R703 and Figure R703.7g |
Adhered veneer: concrete, stone or masonryw |
— |
Section R703 |
Yes Note w |
See Section R703.6.1 g or in accordance with the manufacturer's instructions. |
Hardboardk
Panel siding-vertical
|
7/16 |
— |
Yes |
Note m |
Note m |
Note m |
Note m |
Note m |
6" panel edges 12" inter. sup.n |
Hardboardk
Lap-siding-horizontal
|
7/16 |
Note p |
Yes |
Note o |
Note o |
Note o |
Note o |
Note o |
Same as stud spacing 2 per bearing |
Steelh |
29 ga. |
Lap |
Yes |
0.113 nail 13/4" Staple-13/4" |
0.113 nail 23/4" Staple-21/2" |
0.113 nail 21/2" Staple-21/4" |
0.113 nailv Staplev |
Not allowed |
Same as stud spacing |
Particleboard panels |
3/8 - 1/2 |
— |
Yes |
6d box nail (2" × 0.099") |
6d box nail (2" × 0.099") |
6d box nail (2" × 0.099") |
box nailv |
6d box nail (2" × 0.099"), 3/8 not allowed |
6" panel edge, 12" inter. sup. |
5/8 |
— |
Yes |
6d box nail (2" × 0.099") |
8d box nail (21/2" × 0.113") |
8d box nail (21/2" × 0.113") |
box nailv |
6d box nail (2"× 0.099") |
Wood structural paneli ANSI/APA-PRP 210 sidingi (exterior grade) |
3/8 - 1/2 |
Note p |
Yes |
0.099 nail-2" |
0.113 nail-21/2" |
0.113 nail-21/2" |
0.113 nailv |
0.099 nail-2" |
6" panel edges, 12" inter. sup. |
Wood structural panel lapsiding |
3/8 - 1/2 |
Note p Note x |
Yes |
0.099 nail-2" |
0.113 nail-21/2" |
0.113 nail-21/2" |
0.113 nailx |
0.099 nail-2" |
8" along bottom edge |
Vinyl sidingl |
0.035 |
Lap |
Yes |
0.120 nail (shank) with a 0.313 head or 16-gage staple with 3/8 to1/2-inch crowny, z |
0.120 nail (shank) with a 0.313 head or 16-gage staple with 3/8 to 1/2-inch crowny |
0.120 nail (shank) with a 0.313 head or 16-gage staple with 3/8 to 1/2-inch crowny |
0.120 nail (shank) with a 0.313 head per Section R703.11.2 |
Not allowed |
16 inches on center or specified by the manufacturer instructions or test report |
Woodj rustic, drop |
3/8 Min |
Lap |
Yes |
Fastener penetration into stud-1" |
0.113 nail-21/2" Staple-2" |
Face nailing up to 6" widths, 1 nail per bear- ing; 8" widths and over, 2 nails per bearing |
Shiplap |
19/32 Average |
Lap |
Yes |
Bevel |
7/16 |
Butt tip |
3/16 |
Lap |
Yes |
Fiber cement panel sidingq |
5/16 |
Note q |
Yes Note u |
6d common corrosion- resistant nailr |
6d common corrosion- resistant nailr |
6d common corrosion- resistant nailr |
6d common corrosion- resistant nailr, v |
4d common corrosion- resistant nailr |
6" o.c. on edges, 12" o.c. on intermed. studs |
Fiber cement lap sidings |
5/16 |
Note s |
Yes Note u |
6d common corrosion- resistant nailr |
6d common corrosion- resistant nailr |
6d common corrosion- resistant nailr |
6d common corrosion- resistant nailr, v |
6d common corrosion- resistant nail or 11-gage roofing nailr |
Note t |
For SI: 1 inch = 25.4 mm.
- Based on stud spacing of 16 inches on center where studs are spaced 24 inches, siding shall be applied to sheathing approved for that spacing.
- Nail is a general description and shall be T-head, modified round head, or round head with smooth or deformed shanks.
- Staples shall have a minimum crown width of 7/16-inch outside diameter and be manufactured of minimum 16-gage wire.
- Nails or staples shall be aluminum, galvanized, or rust-preventative coated and shall be driven into the studs where fiberboard, gypsum, or foam plastic sheathing backing is used. Where wood or wood structural panel sheathing is used, fasteners shall be driven into studs unless otherwise permitted to be driven into sheathing in accordance with the siding manufacturer's installation instructions.
- Aluminum nails shall be used to attach aluminum siding.
- Aluminum (0.019 inch) shall be unbacked only when the maximum panel width is 10 inches and the maximum flat area is 8 inches. The tolerance for aluminum siding shall be +0.002 inch of the nominal dimension.
- All attachments shall be coated with a corrosion-resistant coating.
- Shall be of approved type.
- Three-eighths-inch plywood shall not be applied directly to studs spaced more than 16 inches on center when long dimension is parallel to studs. Plywood 1/2-inch or thinner shall not be applied directly to studs spaced more than 24 inches on center. The stud spacing shall not exceed the panel span rating provided by the manufacturer unless the panels are installed with the face grain perpendicular to the studs or over sheathing approved for that stud spacing.
- Wood board sidings applied vertically shall be nailed to horizontal nailing strips or blocking set 24 inches on center. Nails shall penetrate 11/2 inches into studs, studs and wood sheathing combined or blocking.
- Hardboard siding shall comply with CPA/ANSI A135.6.
- Vinyl siding shall comply with ASTM D 3679.
- Minimum shank diameter of 0.092 inch, minimum head diameter of 0.225 inch, and nail length must accommodate sheathing and penetrate framing 11/2 inches.
- When used to resist shear forces, the spacing must be 4 inches at panel edges and 8 inches on interior supports.
- Minimum shank diameter of 0.099 inch, minimum head diameter of 0.240 inch, and nail length must accommodate sheathing and penetrate framing 11/2 inches.
- Vertical end joints shall occur at studs and shall be covered with a joint cover or shall be caulked.
- See Section R703.10.1.
- Fasteners shall comply with the nominal dimensions in ASTM F 1667.
- See Section R703.10.2.
- Face nailing: one 6d common nail through the over lap ping planks at each stud. Concealed nailing: one 11 gage 11/2 inch long galv. roofing nail through the top edge of each plank at each stud.
- See Section R703.2 exceptions.
- Minimum nail length must accommodate sheathing and penetrate framing 11/2 inches.
- Adhered masonry veneer shall comply with the requirements of Section R703.6.3 and shall comply with the requirements in Sections 6.1 and 6.3 of TMS-402 ACI 530/ASCE 5.
- Vertical joints, if staggered shall be permitted to be away from studs if applied over wood structural panel sheathing.
- Minimum fastener length must accommodate sheathing and penetrate framing 0.75 inches or in accordance with the manufacturer's installation instructions.
- Where approved by the manufacturer's instructions or test report siding shall be permitted to be installed with fasteners penetrating not less than 0.75 inches through wood or wood structural sheathing with or without penetration into the framing.
Wood shakes and shingles shall conform to CSSB Grading Rules for Wood Shakes and Shingles.
Wood shakes or shingles shall be applied either single-course or double-course over nominal
1/
2-inch (13 mm) wood-based sheathing or to furring strips over
1/
2-inch (13 mm) nominal nonwood sheathing. A permeable
water-resistive barrier shall be provided over all sheathing, with horizontal overlaps in the membrane of not less than 2 inches (51 mm) and vertical overlaps of not less than 6 inches (152 mm). Where furring strips are used, they shall be 1 inch by 3 inches or 1 inch by 4 inches (25 mm by 76 mm or 25 mm by 102 mm) and shall be fastened horizontally to the studs with 7d or 8d box nails and shall be spaced a distance on center equal to the actual weather exposure of the shakes or shingles, not to exceed the maximum exposure specified in
Table R703.5.2. The spacing between adjacent shingles to allow for expansion shall not exceed
1/
4 inch (6 mm), and between adjacent shakes, it shall not exceed
1/
2 inch (13 mm). The
offset spacing between joints in adjacent courses shall be a minimum of 1
1/
2 inches (38 mm).
The maximum weather exposure for shakes and shingles shall not exceed that specified in
Table R703.5.2.
TABLE R703.5.2
MAXIMUM WEATHER EXPOSURE FOR WOOD SHAKES AND SHINGLES ON EXTERIOR WALLSa, b, c
(Dimensions are in inches)
LENGTH | EXPOSURE FOR SINGLE COURSE | EXPOSURE FOR DOUBLE COURSE |
Shinglesa | | |
16 | 71/2 | 12b |
18 | 81/2 | 14c |
24 | 111/2 | 16 |
Shakesa | | |
18 | 81/2 | 14 |
24 | 111/2 | 18 |
For SI: 1 inch = 25.4 mm.
- Dimensions given are for No. 1 grade.
- A maximum 10-inch exposure is permitted for No. 2 grade.
- A maximum 11-inch exposure is permitted for No. 2 grade.
Each shake or shingle shall be held in place by two hot-dipped zinc-coated, stainless steel, or aluminum nails or staples. The fasteners shall be long enough to penetrate the sheathing or furring strips by a minimum of 1/2 inch (13 mm) and shall not be overdriven.
Staples shall not be less than 16 gage and shall have a crown width of not less than 7/16 inch (11 mm), and the crown of the staples shall be parallel with the butt of the shake or shingle. In single-course application, the fasteners shall be concealed by the course above and shall be driven approximately 1 inch (25 mm) above the butt line of the succeeding course and 3/4 inch (19 mm) from the edge. In double-course applications, the exposed shake or shingle shall be face-nailed with two casing nails, driven approximately 2 inches (51 mm) above the butt line and 3/4 inch (19 mm) from each edge. In all applications, staples shall be concealed by the course above. With shingles wider than 8 inches (203 mm) two additional nails shall be required and shall be nailed approximately 1 inch (25 mm) apart near the center of the shingle.
The bottom courses shall be doubled.
Installation of these materials shall be in compliance with ASTM C 926 and ASTM C 1063 and the provisions of this code.
All lath and lath attachments shall be of corrosion-resistant materials. Expanded metal or woven wire lath shall be attached with 11/2-inch-long (38 mm), 11 gage nails having a 7/16-inch (11.1 mm) head, or 7/8-inch-long (22.2 mm), 16 gage staples, spaced at no more than 6 inches (152 mm), or as otherwise approved.
Plastering with portland
cement plaster shall be not less than three coats when applied over metal lath or wire lath and shall be not less than two coats when applied over masonry,
concrete, pressure-preservative treated wood or
decay-resistant wood as specified in
Section R317.1 or gypsum backing. If the plaster surface is completely covered by veneer or other
facing material or is completely concealed, plaster application need be only two coats, provided the total thickness is as set forth in
Table R702.1(1).
On wood-frame construction with an on-grade floor slab system, exterior plaster shall be applied to cover, but not extend below, lath, paper and screed.
The proportion of aggregate to cementitious materials shall be as set forth in Table R702.1(3).
A minimum 0.019-inch (0.5 mm) (No. 26 galvanized sheet gage), corrosion-resistant weep screed or plastic weep screed, with a minimum vertical attachment flange of 3
1/
2 inches (89 mm) shall be provided at or below the foundation plate line on exterior stud
walls in accordance with ASTM C 926. The weep screed shall be placed a minimum of 4 inches (102 mm) above the earth or 2 inches (51 mm) above paved areas and shall be of a type that will allow trapped water to
drain to the exterior of the building. The weather-resistant barrier shall lap the attachment flange. The exterior lath shall cover and terminate on the attachment flange of the weep screed.
Water-resistive barriers shall be installed as required in
Section R703.2 and, where applied over wood-based sheathing, shall include a water-resistive
vapor-permeable barrier with a performance at least equivalent to two layers of
Grade D paper. The individual layers shall be installed independently such that each layer provides a separate continuous plane and any flashing (installed in accordance with
Section R703.8) intended to
drain to the
water-resistive barrier is directed between the layers.
Exception: Where the water-resistive barrier that is applied over wood-based sheathing has a water resistance equal to or greater than that of 60-minute Grade D paper and is separated from the stucco by an intervening, substantially nonwater-absorbing layer or designed drainage space.
Each coat shall be kept in a moist condition for at least 48 hours prior to application of the next coat.
Exception: Applications installed in accordance with ASTM C 926.
The finish coat for two-coat
cement plaster shall not be applied sooner than seven days after application of the first coat. For three-coat
cement plaster, the second coat shall not be applied sooner than 48 hours after application of the first coat. The finish coat for three-coat
cement plaster shall not be applied sooner than seven days after application of the second coat.
Stone and masonry veneer shall be installed in accordance with this chapter,
Table R703.4 and
Figure R703.7. These veneers installed over a backing of wood or cold-formed steel shall be limited to the first
story above-
grade plane and shall not exceed 5 inches (127 mm) in thickness. See
Section R602.10 for wall bracing requirements for masonry veneer for wood-framed construction and
Section R603.9.5 for wall bracing requirements for masonry veneer for cold-formed steel construction.
Exceptions:
- For all buildings in Seismic Design Categories A, B and C, exterior stone or masonry veneer, as specified in Table R703.7(1), with a backing of wood or steel framing shall be permitted to the height specified in Table R703.7(1) above a noncombustible foundation.
- For detached one- or two-family dwellings in Seismic Design Categories D0, D1 and D2, exterior stone or masonry veneer, as specified in Table R703.7(2), with a backing of wood framing shall be permitted to the height specified in Table R703.7(2) above a noncombustible foundation.
FIGURE R703.7
MASONRY VENEER WALL DETAILS
For SI: 1 inch = 24.5 mm.
(continued)
FIGURE R703.7—continued
MASONRY VENEER WALL DETAILS
TABLE R703.7(1)
STONE OR MASONRY VENEER LIMITATIONS AND REQUIREMENTS, WOOD OR STEEL FRAMING, SEISMIC DESIGN CATEGORIES A, B AND C
SEISMIC DESIGN CATEGORY |
NUMBER OF WOOD OR STEEL- FRAMED STORIES |
MAXIMUM HEIGHT OF VENEER ABOVE NONCOMBUSTIBLE FOUNDATIONa (feet) |
MAXIMUM NOMINAL THICKNESS OF VENEER (inches) |
MAXIMUM WEIGHT OF VENEER (psf)b |
WOOD OR STEEL- FRAMED STORY |
A or B |
Steel: 1 or 2 Wood: 1, 2 or 3 |
30 |
5 |
50 |
all |
C |
1 |
30 |
5 |
50 |
1 only |
2 |
30 |
5 |
50 |
top |
bottom |
Wood only: 3 |
30 |
5 |
50 |
top |
middle |
bottom |
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square foot = 0.479 kPa.
- An additional 8 feet is permitted for gable end walls. See also story height limitations of Section R301.3.
- Maximum weight is installed weight and includes weight of mortar, grout, lath and other materials used for installation. Where veneer is placed on both faces of a wall, the combined weight shall not exceed that specified in this table.
TABLE R703.7(2)
STONE OR MASONRY VENEER LIMITATIONS AND REQUIREMENTS, ONE- AND TWO-FAMILY DETACHED DWELLINGS, WOOD FRAMING, SEISMIC DESIGN CATEGORIES D0, D1 AND D2
SEISMIC DESIGN CATEGORY |
NUMBER OF WOOD FRAMED STORIESa |
MAXIMUM HEIGHT OF VENEER ABOVE NONCOMBUSTIBLE FOUNDATION OR FOUNDATION WALL (feet) |
MAXIMUM NOMINAL THICKNESS OF VENEER (inches) |
MAXIMUM WEIGHT OF VENEER (psf)b |
D0 |
1 |
20c |
4 |
40 |
2 |
20c |
4 |
40 |
3 |
30d |
4 |
40 |
D1 |
1 |
20c |
4 |
40 |
2 |
20c |
4 |
40 |
3 |
20c |
4 |
40 |
D2 |
1 |
20c |
3 |
30 |
2 |
20c |
3 |
30 |
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square foot = 0.479 kPa, 1 pound-force = 4.448 N.
- Cripple walls are not permitted in Seismic Design Categories D0, D1 and D2.
- Maximum weight is installed weight and includes weight of mortar, grout and lath, and other materials used for installation.
- The veneer shall not exceed 20 feet in height above a noncombustible foundation, with an additional 8 feet permitted for gable end walls, or 30 feet in height with an additional 8 feet for gable end walls where the lower 10 feet has a backing of concrete or masonry wall. See also story height limitations of Section R301.3.
- The veneer shall not exceed 30 feet in height above a noncombustible foundation, with an additional 8 feet permitted for gable end walls. See also story height limitations of Section R301.3.
Veneers used as interior wall finishes shall be permitted to be supported on wood or cold-formed steel floors that are designed to support the loads imposed.
Except in
Seismic Design Categories D
0, D
1 and D
2, exterior masonry veneers having an installed weight of 40 pounds per square foot (195 kg/m
2) or less shall be permitted to be supported on wood or cold-formed steel construction. When masonry veneer supported by wood or cold-formed steel construction adjoins masonry veneer supported by the foundation, there shall be a movement joint between the veneer supported by the wood or cold-formed steel construction and the veneer supported by the foundation. The wood or cold-formed steel construction supporting the masonry veneer shall be designed to limit the deflection to
1/
600 of the span for the supporting members. The design of the wood or cold-formed steel construction shall consider the weight of the veneer and any other loads.
A minimum 6 inches by 4 inches by
5/
16 inch (152 mm by 102 mm by 8 mm) steel angle, with the long leg placed vertically, shall be anchored to double 2 inches by 4 inches (51 mm by 102 mm) wood studs at a maximum on-center spacing of 16 inches (406 mm). Anchorage of the steel angle at every double stud spacing shall be a minimum of two
7/
16 inch (11 mm)
diameter by 4 inch (102 mm) lag screws. The steel angle shall have a minimum clearance to underlying construction of
1/
16 inch (2 mm). A minimum of two-thirds the width of the masonry veneer thickness shall bear on the steel angle. Flashing and weep holes shall be located in the masonry veneer wythe in accordance with
Figure R703.7.2.1. The maximum height of masonry veneer above the steel angle support shall be 12 feet, 8 inches (3861 mm). The air space separating the masonry veneer from the wood backing shall be in accordance with Sections
R703.7.4 and
R703.7.4.2. The method of support for the masonry veneer on wood construction shall be constructed in accordance with
Figure R703.7.2.1.
The maximum slope of the roof construction without stops shall be 7:12. Roof construction with slopes greater than 7:12 but not more than 12:12 shall have stops of a minimum 3 inch by 3 inch by 1/4 inch (76 mm by 76 mm by 6 mm) steel plate welded to the angle at 24 inches (610 mm) on center along the angle or as approved by the building official.
FIGURE R703.7.2.1
EXTERIOR MASONRY VENEER SUPPORT BY STEEL ANGLES
A steel angle shall be placed directly on top of the roof construction. The roof supporting construction for the steel angle shall consist of a minimum of three 2 inch by 6 inch (51 mm by 152 mm) wood members. The wood member abutting the vertical wall stud construction shall be anchored with a minimum of three
5/
8-inch (16 mm)
diameter by 5-inch (127 mm) lag screws to every wood stud spacing. Each additional roof member shall be anchored by the use of two 10d nails at every wood stud spacing. A minimum of two-thirds the width of the masonry veneer thickness shall bear on the steel angle. Flashing and weep holes shall be located in the masonry veneer wythe in accordance with
Figure R703.7.2.2. The maximum height of the masonry veneer above the steel angle support shall be 12 feet, 8 inches (3861 mm). The air space separating the masonry veneer from the wood backing shall be in accordance with Sections
R703.7.4 and
R703.7.4.2. The support for the masonry veneer on wood construction shall be constructed in accordance with
Figure R703.7.2.2.
The maximum slope of the roof construction without stops shall be 7:12. Roof construction with slopes greater than 7:12 but not more than 12:12 shall have stops of a minimum 3 inch by 3 inch by 1/4 inch (76 mm by 76 mm by 6 mm) steel plate welded to the angle at 24 inches (610 mm) on center along the angle or as approved by the building official.
FIGURE R703.7.2.2
EXTERIOR MASONRY VENEER SUPPORT BY ROOF MEMBERS
Masonry veneer shall not support any vertical load other than the dead load of the veneer above. Veneer above openings shall be supported on lintels of
noncombustible materials. The lintels shall have a length of bearing not less than 4 inches (102 mm). Steel lintels shall be shop coated with a rust-inhibitive paint, except for lintels made of corrosion-resistant steel or steel treated with coatings to provide
corrosion resistance. Construction of openings shall comply with either
Section R703.7.3.1 or 703.7.3.2.
The allowable span shall not exceed the values set forth in
Table R703.7.3.1.
TABLE R703.7.3.1
ALLOWABLE SPANS FOR LINTELS SUPPORTING MASONRY VENEERa, b, c, d
SIZE OF STEEL ANGLEa, c, d (inches) | NO STORY ABOVE | ONE STORY ABOVE | TWO STORIES ABOVE | NO. OF 1/2-INCH OR EQUIVALENT REINFORCING BARS IN REINFORCED LINTELb, d |
3 × 3 × 1/4 | 6'-0" | 4'-6" | 3'-0" | 1 |
4 × 3 × 1/4 | 8'-0" | 6'-0" | 4'-6" | 1 |
5 × 31/2 × 5/16 | 10'-0" | 8'-0" | 6'-0" | 2 |
6 × 31/2 × 5/16 | 14'-0" | 9'-6" | 7'-0" | 2 |
2-6 × 31/2 × 5/16 | 20'-0" | 12'-0" | 9'-6" | 4 |
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm.
- Long leg of the angle shall be placed in a vertical position.
- Depth of reinforced lintels shall not be less than 8 inches and all cells of hollow masonry lintels shall be grouted solid. Reinforcing bars shall extend not less than 8 inches into the support.
- Steel members indicated are adequate typical examples; other steel members meeting structural design requirements may be used.
- Either steel angle or reinforced lintel shall span opening.
The allowable span shall not exceed 18 feet 3 inches (5562 mm) and shall be constructed to comply with
Figure R703.7.3.2 and the following:
- Provide a minimum length of 18 inches (457 mm) of masonry veneer on each side of opening as shown in Figure R703.7.3.2.
- Provide a minimum 5-inch by 31/2-inch by 5/16-inch (127 mm by 89 mm by 7.9 mm) steel angle above the opening and shore for a minimum of 7 days after installation.
- Provide double-wire joint reinforcement extending 12 inches (305 mm) beyond each side of the opening. Lap splices of joint reinforcement a minimum of 12 inches (305 mm). Comply with one of the following:
- Double-wire joint reinforcement shall be 3/16-inch (4.8 mm) diameter and shall be placed in the first two bed joints above the opening.
- Double-wire joint reinforcement shall be 9 gauge (0.144 inch or 3.66 mm diameter) and shall be placed in the first three bed joints above the opening.
- Provide the height of masonry veneer above opening, in accordance with Table R703.7.3.2.
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm.
FIGURE R703.7.3.2
MASONRY VENEER OPENING
TABLE R703.7.3.2
HEIGHT OF MASONRY VENEER ABOVE OPENING
MINIMUM HEIGHT OF MASONRY VENEER ABOVE OPENING (INCH) |
MAXIMUM HEIGHT OF MASONRY VENEER ABOVE OPENING (FEET) |
13 |
< 5 |
24 |
5 to < 12 |
60 |
12 to height above support allowed by Section R703.7 |
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm.
Masonry veneer shall be anchored to the supporting wall studs with corrosion-resistant metal ties embedded in mortar or grout and extending into the veneer a minimum of 1
1/
2 inches (38 mm), with not less than
5/
8-inch (15.9 mm) mortar or grout cover to outside face. Masonry veneer shall conform to
Table R703.7.4.
TABLE R703.7.4
TIE ATTACHMENT AND AIR SPACE REQUIREMENTS
BACKING AND TIE | MINIMUM TIE | MINIMUM TIE FASTENERa | AIR SPACE |
Wood stud backing with corrugated sheet metal | 22 U.S. gage (0.0299 in.) × 7/8 in. wide | 8d common nail b (21/2 in. × 0.131 in.) | Nominal 1 in. between sheathing and veneer |
Wood stud backing with metal strand wire | W1.7 (No. 9 U.S. gage; 0.148 in.) with hook embedded in mortar joint | 8d common nail b (21/2 in. × 0.131 in.) | Minimum nominal 1 in. between sheathing and veneer | Maximum 41/2 in. between backing and veneer |
Cold-formed steel stud backing with adjustable metal strand wire | W1.7 (No. 9 U.S. gage; 0.148 in.) with hook embedded in mortar joint | No. 10 screw extending through the steel framing a minimum of three exposed threads | Minimum nominal 1 in. between sheathing and veneer | Maximum 41/2 in. between backing and veneer |
For SI: 1 inch = 25.4 mm.
- In Seismic Design Category D0, D1 or D2, the minimum tie fastener shall be an 8d ring-shank nail (21/2 in. × 0.131 in.) or a No. 10 screw extending through the steel framing a minimum of three exposed threads.
- All fasteners shall have rust-inhibitive coating suitable for the installation in which they are being used, or be manufactured from material not susceptible to corrosion.
Veneer ties, if strand wire, shall not be less in thickness than No. 9 U.S. gage [(0.148 inch) (4 mm)] wire and shall have a hook embedded in the mortar joint, or if sheet metal, shall be not less than No. 22 U.S. gage by [(0.0299 inch) (0.76 mm)]
7/
8 inch (22 mm) corrugated. Each tie shall support not more than 2.67 square feet (0.25 m
2) of wall area and shall be spaced not more than 32 inches (813 mm) on center horizontally and 24 inches (635 mm) on center vertically.
Exception: In Seismic Design Category D0, D1 or D2 or townhouses in Seismic Design Category C or in wind areas of more than 30 pounds per square foot pressure (1.44 kPa), each tie shall support not more than 2 square feet (0.2 m2) of wall area.
Additional metal ties shall be provided around all wall openings greater than 16 inches (406 mm) in either dimension. Metal ties around the perimeter of openings shall be spaced not more than 3 feet (9144 mm) on center and placed within 12 inches (305 mm) of the wall opening.
Flashing shall be located beneath the first course of masonry above finished ground level above the foundation wall or slab and at other points of support, including structural floors, shelf angles and lintels when masonry veneers are designed in accordance with
Section R703.7. See
Section R703.8 for additional requirements.
Weepholes shall be provided in the outside wythe of masonry
walls at a maximum spacing of 33 inches (838 mm) on center. Weepholes shall not be less than
3/
16 inch (5 mm) in
diameter. Weepholes shall be located immediately above the flashing.
Approved corrosion-resistant flashing shall be applied shingle-fashion in a manner to prevent entry of water into the wall cavity or penetration of water to the building structural framing components. Self-adhered membranes used as flashing shall comply with AAMA 711. The flashing shall extend to the surface of the
exterior wall finish.
Approved corrosion-resistant flashings shall be installed at all of the following locations:
- Exterior window and door openings. Flashing at exterior window and door openings shall extend to the surface of the exterior wall finish or to the water-resistive barrier for subsequent drainage. Flashing at exterior window and door openings shall be installed in accordance with one or more of the following:
- The fenestration manufacturer's installation and flashing instructions, or for applications not addressed in the fenestration manufacturer's instructions, in accordance with the flashing manufacturer's instructions. Where flashing instructions or details are not provided, pan flashing shall be installed at the sill of exterior window and door openings. Pan flashing shall be sealed or sloped in such a manner as to direct water to the surface of the exterior wall finish or to the water-resistive barrier for subsequent drainage. Openings using pan flashing shall also incorporate flashing or protection at the head and sides.
- In accordance with the flashing design or method of a registered design professional.
- In accordance with other approved methods.
- At the intersection of chimneys or other masonry construction with frame or stucco walls, with projecting lips on both sides under stucco copings.
- Under and at the ends of masonry, wood or metal copings and sills.
- Continuously above all projecting wood trim.
- Where exterior porches, decks or stairs attach to a wall or floor assembly of wood-frame construction.
- At wall and roof intersections.
- At built-in gutters.
Exterior Insulation and Finish System (EIFS) shall comply with this chapter and Sections
R703.9.1 and
R703.9.3. EIFS with drainage shall comply with this chapter and Sections
R703.9.2,
R703.9.3 and
R703.9.4.
EIFS shall comply with ASTM E 2568.
EIFS with drainage shall comply with ASTM E 2568 and shall have an average minimum drainage efficiency of 90 percent when tested in accordance with ASTM E 2273.
Flashing of EIFS shall be provided in accordance with the requirements of
Section R703.8.
The EIFS shall terminate not less than 6 inches (152 mm) above the finished ground level.
Decorative
trim shall not be face nailed though the EIFS.
Fiber-cement panels shall comply with the requirements of ASTM C 1186, Type A, minimum
Grade II. Panels shall be installed with the long dimension either parallel or perpendicular to framing. Vertical and horizontal joints shall occur over framing members and shall be sealed with caulking, covered with battens or shall be designed to comply with
Section R703.1. Panel siding shall be installed with fasteners according to
Table R703.4 or
approved manufacturer's installation instructions.
Fiber-cement lap siding having a maximum width of 12 inches shall comply with the requirements of ASTM C 1186, Type A, minimum
Grade II. Lap siding shall be lapped a minimum of 1
1/
4 inches (32 mm) and lap siding not having tongue-and-groove end joints shall have the ends sealed with caulking, installed with an H-section joint cover, located over a strip of flashing or shall be designed to comply with
Section R703.1. Lap siding courses may be installed with the fastener heads exposed or concealed, according to
Table R703.4 or
approved manufacturers' installation instructions.
Vinyl siding shall be certified and
labeled as conforming to the requirements of ASTM D 3679 by an
approved quality control agency.
Soffit panels shall be individually fastened to a supporting component such as a nailing strip, fascia or subfascia component or as specified by the manufacturer's instructions.
Where the
basic wind speed does not exceed 90 miles per hour (40 m/s), the Exposure Category is B and gypsum wall board or equivalent is installed on the side of the wall opposite the foam plastic sheathing, the minimum siding fastener penetration into wood framing shall be 1
1/
4 inches (32 mm) using minimum 0.120-inch
diameter nail (shank) with a minimum 0.313-inch
diameter head, 16 inches on center. The foam plastic sheathing shall be minimum
1/
2-inch-thick (12.7 mm) (nominal) extruded polystyrene per ASTM C 578,
1/
2-inch-thick (12.7 mm) (nominal) polyisocyanurate per ASTM C 1289, or 1-inch-thick (25 mm) (nominal) expanded polystyrene per ASTM C 578.
Where the
basic wind speed exceeds 90 miles per hour (40 m/s) or the Exposure Category is C or D, or all conditions of
Section R703.11.2.1 are not met, the adjusted design pressure rating for the assembly shall meet or exceed the loads listed in Tables
R301.2(2) adjusted for height and exposure using
Table R301.2(3). The design wind pressure rating of the
vinyl siding for installation over
solid sheathing as provided in the
vinyl siding manufacturer's product specifications shall be adjusted for the following wall assembly conditions:
- For wall assemblies with foam plastic sheathing on the exterior side and gypsum wall board or equivalent on the interior side of the wall, the vinyl siding's design wind pressure rating shall be multiplied by 0.39.
- For wall assemblies with foam plastic sheathing on the exterior side and no gypsum wall board or equivalent on the interior side of wall, the vinyl siding's design wind pressure rating shall be multiplied by 0.27.
Where the
vinyl siding manufacturer's product specifications provide an
approved design wind pressure rating for installation over foam plastic sheathing, use of this design wind pressure rating shall be permitted and the siding shall be installed in accordance with the
manufacturer's installation instructions.
Adhered masonry veneer shall be installed in accordance with the manufacturer's instructions.
On exterior stud
walls, adhered masonry veneer shall be installed:
- Minimum of 4 inches (102 mm) above the earth;
- Minimum of 2 inches (51 mm) above paved areas; or
- Minimum of 1/2 inch (12 mm) above exterior walking surfaces which are supported by the same foundation that supports the exterior wall.
A corrosion-resistant screed or flashing of a minimum 0.019-inch (0.48 mm) or 26-gage galvanized or plastic with a minimum vertical attachment flange of 3
1/
2 inches (89 mm) shall be installed to extend a minimum of 1 inch (25 mm) below the foundation plate line on exterior stud
walls in accordance with
Section R703.8. The
water-resistive barrier, as required by
Table R703.4, Footnote w, shall lap over the exterior of the attachment flange of the screed or flashing.