The provisions of this chapter shall govern the structural design of buildings, structures and portions thereof regulated by this code.
The following terms are defined in Chapter 2:
LIVE LOAD (ROOF).
NOTATIONS.
D=Dead load.
Di =Weight of ice in accordance with Chapter 10 of ASCE 7.
E=Combined effect of horizontal and vertical earthquake induced forces as defined in Section 12.4.2 of ASCE 7.
F=Load due to fluids with well-defined pressures and maximum heights.
Fa=Flood load in accordance with Chapter 5 of ASCE 7.
H=Load due to lateral earth pressures, ground water pressure or pressure of bulk materials.
L=Roof live load greater than 20 psf (0.96 kN/m2) and floor live load.
Lr=Roof live load of 20 psf (0.96 kN/m2) or less.
R=Rain load.
S=Snow load.
T=Self-straining load.
Vasd=Nominal design wind speed (3-second gust), miles per hour (mph) (km/hr) where applicable.
Vult=Ultimate design wind speeds (3-second gust), miles per hour (mph) (km/hr) determined from Figures 1609A, 1609B, or 1609C or ASCE 7.
W=Load due to wind pressure.
Wi=Wind-on-ice in accordance with Chapter 10 of ASCE 7.

1603.1 General

AMENDMENT
This section has been amended at the state or city level.
Construction documents shall show the size, section, and relative locations of structural members with floor levels, column centers and offsets dimensioned. The design loads and other information pertinent to the structural design required by Sections 1603.1.1 through 1603.1.9 shall be indicated on the construction documents.
Exception: Construction documents for buildings constructed in accordance with the conventional light-frame construction provisions of Section 2308 shall indicate the following structural design information:
  1. Floor and roof live loads.
  2. Ground snow load, Pg.
  3. Risk Category.
  4. Wind exposure.
  5. Ultimate design wind speed (3-second gust) Vult , and effective design wind speed Veff-asd (3-second gust), miles per hour (mph) (km/hr).
  6. Design spectral response acceleration parameters, SDS and SD1
  7. Seismic design category and site class.
  8. The design load-bearing values of soils.
  9. Flood design data, if located in flood hazard areas established in Section 1612.3.
The uniformly distributed, concentrated and impact floor live load used in the design shall be indicated for floor areas. Use of live load reduction in accordance with Section 1607.10 shall be indicated for each type of live load used in the design.
The roof live load used in the design shall be indicated for roof areas (Section 1607.12).
The ground snow load, Pg, shall be indicated. In areas where the ground snow load, Pg, exceeds 10 pounds per square foot (psf) (0.479 kN/m2), the following additional information shall also be provided, regardless of whether snow loads govern the design of the roof:
  1. Flat-roof snow load, Pf.
  2. Snow exposure factor, Ce.
  3. Snow load importance factor, Is.
  4. Thermal factor, Ct.

1603.1.4 Wind Design Data

AMENDMENT
This section has been amended at the state or city level.
The following information related to wind loads shall be shown, regardless of whether wind loads govern the design of the lateral-force-resisting system of the building:
  1. Ultimate design wind speed (3-second gust) Vult , and effective design wind speed Veff-asd (3-second gust), miles per hour (mph)(km/hr).
  2. Building Risk Category.
  3. Wind exposure, if more than one wind exposure is utilized, the wind exposure for each applicable wind direction shall be indicated.
  4. The applicable internal pressure coefficient.
  5. Components and cladding. The design wind pressures in terms of psf (kN/m2) used for the design of exterior components, and cladding not specifically designed by the registered design professional.
The following information related to seismic loads shall be shown, regardless of whether seismic loads govern the design of the lateral force-resisting system of the structure:
  1. Risk category.
  2. Seismic importance factor, Ie.
  3. Mapped spectral response acceleration parameters, SS and S1.
  4. Site class.
  5. Design spectral response acceleration parameters, SDS and SD1.
  6. Seismic design category.
  7. Basic seismic force-resisting system(s).
  8. Design base shear(s).
  9. Seismic response coefficient(s), CS.
  10. Response modification coefficient(s), R.
  11. Analysis procedure used.
The design load-bearing values of soils shall be shown on the construction documents.
For buildings located in whole or in part in flood hazard areas as established in Section 1612.3, the documentation pertaining to design, if required in Section 1612.5, shall be included and the following information, referenced to the datum on the community's Flood Insurance Rate Map (FIRM), shall be shown, regardless of whether flood loads govern the design of the building:
  1. In flood hazard areas not subject to high-velocity wave action, the elevation of the proposed lowest floor, including the basement.
  2. In flood hazard areas not subject to high-velocity wave action, the elevation to which any nonresidential building will be dry flood proofed.
  3. In flood hazard areas subject to high-velocity wave action, the proposed elevation of the bottom of the lowest horizontal structural member of the lowest floor, including the basement.
Special loads that are applicable to the design of the building, structure or portions thereof shall be indicated along with the specified section of this code that addresses the special loading condition.
Construction documents or specifications shall be prepared for those systems and components requiring special inspection for seismic resistance as specified in Section 1705.11 by the registered design professional responsible for their design and shall be submitted for approval in accordance with Section 107.1. Reference to seismic standards in lieu of detailed drawings is acceptable.
Building, structures and parts thereof shall be designed and constructed in accordance with strength design, load and resistance factor design, allowable stress design, empirical design or conventional construction methods, as permitted by the applicable material chapters.
Buildings and other structures, and parts thereof, shall be designed and constructed to support safely the factored loads in load combinations defined in this code without exceeding the appropriate strength limit states for the materials of construction. Alternatively, buildings and other structures, and parts thereof, shall be designed and constructed to support safely the nominal loads in load combinations defined in this code without exceeding the appropriate specified allowable stresses for the materials of construction.

Loads and forces for occupancies or uses not covered in this chapter shall be subject to the approval of the building official.
Structural systems and members thereof shall be designed to have adequate stiffness to limit deflections and lateral drift. See Section 12.12.1 of ASCE 7 for drift limits applicable to earthquake loading.

TABLE 1604.3
DEFLECTION LIMITSa, b, c, h, i
CONSTRUCTION L S or W f D + Ld, g
Roof members:e      
Supporting plaster or stucco ceiling l/360 l/360 l/240
Supporting nonplaster ceiling l/240 l/240 l/180
Not supporting ceiling l/180 l/180 l/120
Floor members l/360 l/240
Exterior walls and interior partitions:      
With plaster or stucco finishes l/360
With other brittle finishes l/240
With flexible finishes l/120
Farm buildings l/180
Greenhouses l/120
For SI: 1 foot = 304.8 mm.
  1. For structural roofing and siding made of formed metal sheets, the total load deflection shall not exceed l/60. For secondary roof structural members supporting formed metal roofing, the live load deflection shall not exceed l/150. For secondary wall members supporting formed metal siding, the design wind load deflection shall not exceed l/90. For roofs, this exception only applies when the metal sheets have no roof covering.
  2. Interior partitions not exceeding 6 feet in height and flexible, folding and portable partitions are not governed by the provisions of this section. The deflection criterion for interior partitions is based on the horizontal load defined in Section 1607.14.
  3. See Section 2403 for glass supports.
  4. For wood structural members having a moisture content of less than 16 percent at time of installation and used under dry conditions, the deflection resulting from L + 0.5D is permitted to be substituted for the deflection resulting from L + D.
  5. The above deflections do not ensure against ponding. Roofs that do not have sufficient slope or camber to assure adequate drainage shall be investigated for ponding. See Section 1611 for rain and ponding requirements and Section 1503.4 for roof drainage requirements.
  6. The wind load is permitted to be taken as 0.42 times the "component and cladding" loads for the purpose of determining deflection limits herein.
  7. For steel structural members, the dead load shall be taken as zero.
  8. For aluminum structural members or aluminum panels used in skylights and sloped glazing framing, roofs or walls of sunroom additions or patio covers, not supporting edge of glass or aluminum sandwich panels, the total load deflection shall not exceed l/60. For continuous aluminum structural members supporting edge of glass, the total load deflection shall not exceed l/175 for each glass lite or l/60 for the entire length of the member, whichever is more stringent. For aluminum sandwich panels used in roofs or walls of sunroom additions or patio covers, the total load deflection shall not exceed l/120.
  9. For cantilever members, l shall be taken as twice the length of the cantilever.
The deflections of structural members shall not exceed the more restrictive of the limitations of Sections 1604.3.2 through 1604.3.5 or that permitted by Table 1604.3.
The deflection of reinforced concrete structural members shall not exceed that permitted by ACI 318.
The deflection of steel structural members shall not exceed that permitted by AISC 360, AISI S100, ASCE 8, SJI CJ-1.0, SJI JG-1.1, SJI K-1.1 or SJI LH/DLH-1.1, as applicable.
The deflection of masonry structural members shall not exceed that permitted by TMS 402/ACI 530/ASCE 5.
The deflection of aluminum structural members shall not exceed that permitted by AA ADM1.
The deflection limits of Section 1604.3.1 shall be used unless more restrictive deflection limits are required by a referenced standard for the element or finish material.
Load effects on structural members and their connections shall be determined by methods of structural analysis that take into account equilibrium, general stability, geometric compatibility and both short- and long-term material properties.

Members that tend to accumulate residual deformations under repeated service loads shall have included in their analysis the added eccentricities expected to occur during their service life.

Any system or method of construction to be used shall be based on a rational analysis in accordance with well-established principles of mechanics. Such analysis shall result in a system that provides a complete load path capable of transferring loads from their point of origin to the load-resisting elements.

The total lateral force shall be distributed to the various vertical elements of the lateral force-resisting system in proportion to their rigidities, considering the rigidity of the horizontal bracing system or diaphragm. Rigid elements assumed not to be a part of the lateral force-resisting system are permitted to be incorporated into buildings provided their effect on the action of the system is considered and provided for in the design. Except where diaphragms are flexible, or are permitted to be analyzed as flexible, provisions shall be made for the increased forces induced on resisting elements of the structural system resulting from torsion due to eccentricity between the center of application of the lateral forces and the center of rigidity of the lateral force-resisting system.

Every structure shall be designed to resist the overturning effects caused by the lateral forces specified in this chapter. See Section 1609 for wind loads, Section 1610 for lateral soil loads and Section 1613 for earthquake loads.
Each building and structure shall be assigned a risk category in accordance with Table 1604.5. Where a referenced standard specifies an occupancy category, the risk category shall not be taken as lower than the occupancy category specified therein.

TABLE 1604.5
RISK CATEGORY OF BUILDINGS AND OTHER STRUCTURES
RISK CATEGORY NATURE OF OCCUPANCY
I Buildings and other structures that represent a low hazard to human life in the event of failure, including but not limited to:

II Buildings and other structures except those listed in Risk Categories I, III and IV
III Buildings and other structures that represent a substantial hazard to human life in the event of failure, including but not
limited to:

IV Buildings and other structures designated as essential facilities, including but not limited to:

  • Group I-2 occupancies having surgery or emergency treatment facilities.
  • Fire, rescue, ambulance and police stations and emergency vehicle garages.
  • Designated earthquake, hurricane or other emergency shelters.
  • Designated emergency preparedness, communications and operations centers and other facilities required for emergency response.
  • Power-generating stations and other public utility facilities required as emergency backup facilities for Risk Category IV structures.
  • Buildings and other structures containing quantities of highly toxic materials that:

    • Exceed maximum allowable quantities per control area as given in Table 307.1(2) or per outdoor control area in accordance with the International Fire Code; and
    • Are sufficient to pose a threat to the public if released b.
  • Aviation control towers, air traffic control centers and emergency aircraft hangars.
  • Buildings and other structures having critical national defense functions.
  • Water storage facilities and pump structures required to maintain water pressure for fire suppression.
  1. For purposes of occupant load calculation, occupancies required by Table 1004.1.2 to use gross floor area calculations shall be permitted to use net floor areas to determine the total occupant load.
  2. Where approved by the building official, the classification of buildings and other structures as Risk Category III or IV based on their quantities of toxic, highly toxic or explosive materials is permitted to be reduced to Risk Category II, provided it can be demonstrated by a hazard assessment in accordance with Section 1.5.3 of ASCE 7 that a release of the toxic, highly toxic or explosive materials is not sufficient to pose a threat to the public.
Where a building or structure is occupied by two or more occupancies not included in the same risk category, it shall be assigned the classification of the highest risk category corresponding to the various occupancies. Where buildings or structures have two or more portions that are structurally separated, each portion shall be separately classified. Where a separated portion of a building or structure provides required access to, required egress from or shares life safety components with another portion having a higher risk category, both portions shall be assigned to the higher risk category.
The building official is authorized to require an engineering analysis or a load test, or both, of any construction whenever there is reason to question the safety of the construction for the intended occupancy. Engineering analysis and load tests shall be conducted in accordance with Section 1709.
Materials and methods of construction that are not capable of being designed by approved engineering analysis or that do not comply with the applicable referenced standards, or alternative test procedures in accordance with Section 1707, shall be load tested in accordance with Section 1710.
Buildings and other structures, and portions thereof, shall be provided with anchorage in accordance with Sections 1604.8.1 through 1604.8.3, as applicable.
Anchorage of the roof to walls and columns, and of walls and columns to foundations, shall be provided to resist the uplift and sliding forces that result from the application of the prescribed loads.
Walls that provide vertical load-bearing resistance or lateral shear resistance for a portion of the structure shall be anchored to the roof and to all floors and members that provide lateral support for the wall or that are supported by the wall. The connections shall be capable of resisting the horizontal forces specified in Section 1.4.5 of ASCE 7 for walls of structures assigned to Seismic Design Category A and to Section 12.11 of ASCE 7 for walls of structures assigned to all other seismic design categories. Required anchors in masonry walls of hollow units or cavity walls shall be embedded in a reinforced grouted structural element of the wall. See Sections 1609 for wind design requirements and 1613 for earthquake design requirements.
Where supported by attachment to an exterior wall, decks shall be positively anchored to the primary structure and designed for both vertical and lateral loads as applicable. Such attachment shall not be accomplished by the use of toenails or nails subject to withdrawal. Where positive connection to the primary building structure cannot be verified during inspection, decks shall be self-supporting. Connections of decks with cantilevered framing members to exterior walls or other framing members shall be designed for both of the following:
  1. The reactions resulting from the dead load and live load specified in Table 1607.1, or the snow load specified in Section 1608, in accordance with Section 1605, acting on all portions of the deck.
  2. The reactions resulting from the dead load and live load specified in Table 1607.1, or the snow load specified in Section 1608, in accordance with Section 1605, acting on the cantilevered portion of the deck, and no live load or snow load on the remaining portion of the deck.
Structural members, systems, components and cladding shall be designed to resist forces due to earthquakes and wind, with consideration of overturning, sliding and uplift. Continuous load paths shall be provided for transmitting these forces to the foundation. Where sliding is used to isolate the elements, the effects of friction between sliding elements shall be included as a force.
Lateral force-resisting systems shall meet seismic detailing requirements and limitations prescribed in this code and ASCE 7, excluding Chapter 14 and Appendix 11A, even when wind load effects are greater than seismic load effects.
Buildings and other structures and portions thereof shall be designed to resist:
  1. The load combinations specified in Section 1605.2, 1605.3.1 or 1605.3.2;
  2. The load combinations specified in Chapters 18 through 23; and
  3. The seismic load effects including overstrength factor in accordance with Section 12.4.3 of ASCE 7 where required by Section 12.2.5.2, 12.3.3.3 or 12.10.2.1 of ASCE 7. With the simplified procedure of ASCE 7 Section 12.14, the seismic load effects including overstrength factor in accordance with Section 12.14.3.2 of ASCE 7 shall be used.

Applicable loads shall be considered, including both earthquake and wind, in accordance with the specified load combinations. Each load combination shall also be investigated with one or more of the variable loads set to zero.

Where the load combinations with overstrength factor in Section 12.4.3.2 of ASCE 7 apply, they shall be used as follows:

  1. The basic combinations for strength design with overstrength factor in lieu of Equations 16-5 and 16-7 in Section 1605.2.
  2. The basic combinations for allowable stress design with overstrength factor in lieu of Equations 16-12, 16-14 and 16-16 in Section 1605.3.1.
  3. The basic combinations for allowable stress design with overstrength factor in lieu of Equations 16-21 and 16-22 in Section 1605.3.2.
Regardless of which load combinations are used to design for strength, where overall structure stability (such as stability against overturning, sliding, or buoyancy) is being verified, use of the load combinations specified in Section 1605.2 or 1605.3 shall be permitted. Where the load combinations specified in Section 1605.2 are used, strength reduction factors applicable to soil resistance shall be provided by a registered design professional. The stability of retaining walls shall be verified in accordance with Section 1807.2.3.
Where strength design or load and resistance factor design is used, buildings and other structures, and portions thereof, shall be designed to resist the most critical effects resulting from the following combinations of factored loads:
1.4(D +F)(Equation 16-1)
1.2(D + F) + 1.6(L + H) + 0.5(Lr or S or R)(Equation 16-2)
1.2(D + F) + 1.6(Lr or S or R) + 1.6H + (f1L or 0.5W)(Equation 16-3)
1.2(D + F) + 1.0W + f1L + 1.6H + 0.5(Lr or S or R)(Equation 16-4)
1.2(D + F) + 1.0E + f1L + 1.6H + f2S(Equation 16-5)
0.9D+ 1.0W+ 1.6H(Equation 16-6)
0.9(D + F) + 1.0E+ 1.6H(Equation 16-7)

where:

f1=1 for places of public assembly live loads in excess of 100 pounds per square foot (4.79 kN/m2), and parking garages; and 0.5 for other live loads.
f2=0.7 for roof configurations (such as saw tooth) that do not shed snow off the structure, and 0.2 for other roof configurations.
Exceptions:
  1. Where other factored load combinations are specifically required by other provisions of this code, such combinations shall take precedence.
  2. Where the effect of H resists the primary variable load effect, a load factor of 0.9 shall be included with H where H is permanent and H shall be set to zero for all other conditions.
Where flood loads, Fa, are to be considered in the design, the load combinations of Section 2.3.3 of ASCE 7 shall be used. Where self-straining loads, T, are considered in design, their structural effects in combination with other loads shall be determined in accordance with Section 2.3.5 of ASCE 7. Where an ice-sensitive structure is subjected to loads due to atmospheric icing, the load combinations of Section 2.3.4 of ASCE 7 shall be considered.
Where allowable stress design (working stress design), as permitted by this code, is used, structures and portions thereof shall resist the most critical effects resulting from the following combinations of loads:
D + F(Equation 16-8)
D + H + F + L(Equation 16-9)
D + H + F + (Lr or S or R)(Equation 16-10)
D + H + F+ 0.75(L) + 0.75(Lr or S or R) (Equation 16-11)
D + H + F + (0.6W or 0.7E)(Equation 16-12)
D + H + F + 0.75(0.6W) + 0.75L + 0.75(Lr or S or R) (Equation 16-13)
D + H + F + 0.75 (0.7 E) + 0.75 L + 0.75 S(Equation 16-14)
0.6D + 0.6W+H(Equation 16-15)
0.6(D + F) + 0.7E+H(Equation 16-16)
Exceptions:
  1. Crane hook loads need not be combined with roof live load or with more than three-fourths of the snow load or one-half of the wind load.
  2. Flat roof snow loads of 30 psf (1.44 kN/m2) or less and roof live loads of 30 psf (1.44 kN/m2) or less need not be combined with seismic loads. Where flat roof snow loads exceed 30 psf (1.44 kN/m2), 20 percent shall be combined with seismic loads.
  3. Where the effect of H resists the primary variable load effect, a load factor of 0.6 shall be included with H where H is permanent and H shall be set to zero for all other conditions.
  4. In Equation 16-15, the wind load, W, is permitted to be reduced in accordance with Exception 2 of Section 2.4.1 of ASCE 7.
  5. In Equation 16-16, 0.6 D is permitted to be increased to 0.9 D for the design of special reinforced masonry shear walls complying with Chapter 21.
Increases in allowable stresses specified in the appropriate material chapter or the referenced standards shall not be used with the load combinations of Section 1605.3.1, except that increases shall be permitted in accordance with Chapter 23.
Where flood loads, Fa, are to be considered in design, the load combinations of Section 2.4.2 of ASCE 7 shall be used. Where self-straining loads, T, are considered in design, their structural effects in combination with other loads shall be determined in accordance with Section 2.4.4 of ASCE 7. Where an ice-sensitive structure is subjected to loads due to atmospheric icing, the load combinations of Section 2.4.3 of ASCE 7 shall be considered.
In lieu of the basic load combinations specified in Section 1605.3.1, structures and portions thereof shall be permitted to be designed for the most critical effects resulting from the following combinations. When using these alternative basic load combinations that include wind or seismic loads, allowable stresses are permitted to be increased or load combinations reduced where permitted by the material chapter of this code or the referenced standards. For load combinations that include the counteracting effects of dead and wind loads, only two-thirds of the minimum dead load likely to be in place during a design wind event shall be used. When using allowable stresses which have been increased or load combinations which have been reduced as permitted by the material chapter of this code or the referenced standards, where wind loads are calculated in accordance with Chapters 26 through 31 of ASCE 7, the coefficient (ω) in the following equations shall be taken as 1.3. For other wind loads, (ω) shall be taken as 1. When allowable stresses have not been increased or load combinations have not been reduced as permitted by the material chapter of this code or the referenced standards, (ω) shall be taken as 1. When using these alternative load combinations to evaluate sliding, overturning and soil bearing at the soil-structure interface, the reduction of foundation overturning from Section 12.13.4 in ASCE 7 shall not be used. When using these alternative basic load combinations for proportioning foundations for loadings, which include seismic loads, the vertical seismic load effect, Ev, in Equation 12.4-4 of ASCE 7 is permitted to be taken equal to zero.
D + L + (Lr or S or R)(Equation 16-17)
D + L + 0.6 ωW (Equation 16-18)
D + L + 0.6 ωW + S/2(Equation 16-19)
D + L + S + 0.6 ωW/2(Equation 16-20)
D + L + S + E/1.4(Equation 16-21)
0.9D + E/1.4 (Equation 16-22)
Exceptions:
  1. Crane hook loads need not be combined with roof live loads or with more than three-fourths of the snow load or one-half of the wind load.
  2. Flat roof snow loads of 30 psf (1.44 kN/m2) or less and roof live loads of 30 psf (1.44 kN/m2) or less need not be combined with seismic loads. Where flat roof snow loads exceed 30 psf (1.44 kN/m2), 20 percent shall be combined with seismic loads.
Where F, H or T are to be considered in the design, each applicable load shall be added to the combinations specified in Section 1605.3.2. Where self-straining loads, T, are considered in design, their structural effects in combination with other loads shall be determined in accordance with Section 2.4.4 of ASCE 7.
Dead loads are those loads defined in Section 202. Dead loads shall be considered permanent loads.
For purposes of design, the actual weights of materials of construction and fixed service equipment shall be used. In the absence of definite information, values used shall be subject to the approval of the building official.
Live loads are those loads defined in Section 1602.1.

TABLE 1607.1
MINIMUM UNIFORMLY DISTRIBUTED LIVE LOADS,Lo,
AND MINIMUM CONCENTRATED LIVE LOADSg
OCCUPANCY OR USE UNIFORM (psf) CONCENTRATED (lbs.)
1. Apartments (see residential)
2. Access floor systems    
Office use
50 2,000
Computer use
100 2,000
3. Armories and drill rooms 150m
4. Assembly areas  
Fixed seats (fastened to floor)
60m
Follow spot, projections and control rooms
50
Lobbies
100m
Movable seats
100m
Stage floors
150m
Platforms (assembly)
100m
Other assembly areas
100m
5. Balconies and decksh Same as occupancy served
6. Catwalks 40 300
7. Cornices 60
8. Corridors  
First floor
100
Other floors
Same as
occupancy
served
except as
indicated
9. Dining rooms and restaurants 100m
10. Dwellings (see residential)
11. Elevator machine room grating
(on area of 2 inches by 2 inches)
300
12. Finish light floor plate construction
(on area of 1 inch by 1 inch)
200
13. Fire escapes 100
On single-family dwellings only
40
14. Garages (passenger vehicles only) 40m Note a
Trucks and buses
See Section 1607.7
15. Handrails, guards and grab bars See Section 1607.8
16. Helipads See Section 1607.6
17. Hospitals    
Corridors above first floor
80 1,000
Operating rooms, laboratories
60 1,000
Patient rooms
40 1,000
18. Hotels (see residential)
19. Libraries    
Corridors above first floor
80 1,000
Reading rooms
60 1,000
Stack rooms
150b, m 1,000
20. Manufacturing    
Heavy
250m 3,000
Light
125m 2,000
21. Marquees 75
22. Office buildings    
Corridors above first floor
80 2,000
File and computer rooms shall be designed for heavier loads based on anticipated occupancy
Lobbies and first-floor corridors
100 2,000
Offices
50 2,000
23. Penal institutions  
Cell blocks
40
100
24. Recreational uses:  
Bowling alleys, poolrooms and similar uses
75m
Dance halls and ballrooms
100m
Gymnasiums
100m
Reviewing stands, grandstands and bleachers
100c, m
Stadiums and arenas with fixed seats (fastened to floor)
60c, m
25. Residential  
One- and two-family dwellings
 
Uninhabitable attics without storagei
10
Uninhabitable attics with storagei, j, k
20
Habitable attics and sleeping areask
30
All other areas
40
Hotels and multi-family dwellings
 
Private rooms and corridors serving them
40
Public roomsm and corridors serving them
100
26. Roofs    
All roof surfaces subject to maintenance workers
  300
   
Fabric construction supported by a skeleton structure
5
nonreducible
 
All other construction
20  
Ordinary flat, pitched, and curved roofs (that are not occupiable)
20  
Primary roof members exposed to a work floor
   
Single panel point of lower chord of roof trusses or any point along primary structural members supporting roofs over manufacturing, storage warehouses, and repair garages
  2,000
All other primary roof members
  300
Occupiable roofs:
   
Roof gardens
100  
Assembly areas
100m  
All other similar areas
Note 1 Note 1
27. Schools    
Classrooms
40 1,000
Corridors above first floor
80 1,000
First-floor corridors
100 1,000
28. Scuttles, skylight ribs and accessible ceilings 200
29. Sidewalks, vehicular driveways and yards, subject to trucking 250d, m 8,000e
30. Stairs and exits    
One- and two-family dwellings
40 300f
All other
100 300f
31. Storage warehouses (shall be designed for heavier loads if required for anticipated storage)  
Heavy
250m
Light
125m
32. Stores    
Retail
   
First floor
100 1,000
Upper floors
75 1,000
Wholesale, all floors
125m 1,000
33. Vehicle barriers See Section 1607.8.3
34. Walkways and elevated platforms (other than exitways) 60
35. Yards and terraces, pedestrians 100m
For SI: 1 inch = 25.4 mm, 1 square inch = 645.16 mm2,
1 square foot = 0.0929 m2,
1 pound per square foot = 0.0479 kN/m2, 1 pound = 0.004448 kN,
1 pound per cubic foot = 16 kg/m3.
  1. Floors in garages or portions of buildings used for the storage of motor vehicles shall be designed for the uniformly distributed live loads of Table 1607.1 or the following concentrated loads: (1) for garages restricted to passenger vehicles accommodating not more than nine passengers, 3,000 pounds acting on an area of 4.5 inches by 4.5 inches; (2) for mechanical parking structures without slab or deck that are used for storing passenger vehicles only, 2,250 pounds per wheel.
  2. The loading applies to stack room floors that support nonmobile, double-faced library book stacks, subject to the following limitations:
    1. The nominal bookstack unit height shall not exceed 90 inches;
    2. The nominal shelf depth shall not exceed 12 inches for each face; and
    3. Parallel rows of double-faced book stacks shall be separated by aisles not less than 36 inches wide.
  3. Design in accordance with ICC 300.
  4. Other uniform loads in accordance with an approved method containing provisions for truck loadings shall also be considered where appropriate.
  5. The concentrated wheel load shall be applied on an area of 4.5 inches by 4.5 inches.
  6. The minimum concentrated load on stair treads shall be applied on an area of 2 inches by 2 inches. This load need not be assumed to act concurrently with the uniform load.
  7. Where snow loads occur that are in excess of the design conditions, the structure shall be designed to support the loads due to the increased loads caused by drift buildup or a greater snow design determined by the building official (see Section 1608).
  8. See Section 1604.8.3 for decks attached to exterior walls.
  9. Uninhabitable attics without storage are those where the maximum clear height between the joists and rafters is less than 42 inches, or where there are not two or more adjacent trusses with web configurations capable of accommodating an assumed rectangle 42 inches in height by 24 inches in width, or greater, within the plane of the trusses. This live load need not be assumed to act concurrently with any other live load requirements.
  10. Uninhabitable attics with storage are those where the maximum clear height between the joists and rafters is 42 inches or greater, or where there are two or more adjacent trusses with web configurations capable of accommodating an assumed rectangle 42 inches in height by 24 inches in width, or greater, within the plane of the trusses.

    The live load need only be applied to those portions of the joists or truss bottom chords where both of the following conditions are met:
    1. The attic area is accessible from an opening not less than 20 inches in width by 30 inches in length that is located where the clear height in the attic is a minimum of 30 inches; and
    2. The slopes of the joists or truss bottom chords are no greater than two units vertical in 12 units horizontal.
    The remaining portions of the joists or truss bottom chords shall be designed for a uniformly distributed concurrent live load of not less than 10 lb./ft2.
  11. Attic spaces served by stairways other than the pull-down type shall be designed to support the minimum live load specified for habitable attics and sleeping rooms.
  12. Areas of occupiable roofs, other than roof gardens and assembly areas, shall be designed for appropriate loads as approved by the building official. Unoccupied landscaped areas of roofs shall be designed in accordance with Section 1607.12.3.1.
  13. Live load reduction is not permitted unless specific exceptions of Section 1607.10 apply.
For occupancies or uses not designated in Table 1607.1, the live load shall be determined in accordance with a method approved by the building official.
The live loads used in the design of buildings and other structures shall be the maximum loads expected by the intended use or occupancy but shall in no case be less than the minimum uniformly distributed live loads given in Table 1607.1.
Floors and other similar surfaces shall be designed to support the uniformly distributed live loads prescribed in Section 1607.3 or the concentrated live loads given in Table 1607.1, whichever produces the greater load effects. Unless otherwise specified, the indicated concentration shall be assumed to be uniformly distributed over an area of 21/2 feet by 21/2 feet (762 mm by 762 mm) and shall be located so as to produce the maximum load effects in the structural members.
In office buildings and in other buildings where partition locations are subject to change, provisions for partition weight shall be made, whether or not partitions are shown on the construction documents, unless the specified live load exceeds 80 psf (3.83 kN/m2). The partition load shall not be less than a uniformly distributed live load of 15 psf (0.72 kN/m2).
Helipads shall be designed for the following live loads:
  1. A uniform live load, L, as specified below. This load shall not be reduced.
    1. 40 psf (1.92 kN/m2) where the design basis helicopter has a maximum take-off weight of 3,000 pounds (13.35 kN) or less.
    2. 60 psf (2.87 kN/m2) where the design basis helicopter has a maximum take-off weight greater than 3,000 pounds (13.35 kN).
  2. A single concentrated live load, L, of 3,000 pounds (13.35 kN) applied over an area of 4.5 inches by 4.5 inches (114 mm by 114 mm) and located so as to produce the maximum load effects on the structural elements under consideration. The concentrated load is not required to act concurrently with other uniform or concentrated live loads.
  3. Two single concentrated live loads, L, 8 feet (2438 mm) apart applied on the landing pad (representing the helicopter's two main landing gear, whether skid type or wheeled type), each having a magnitude of 0.75 times the maximum take-off weight of the helicopter, and located so as to produce the maximum load effects on the structural elements under consideration. The concentrated loads shall be applied over an area of 8 inches by 8 inches (203 mm by 203 mm) and are not required to act concurrently with other uniform or concentrated live loads.

Landing areas designed for a design basis helicopter with maximum take-off weight of 3,000 pounds (13.35 kN) shall be identified with a 3,000 pound (13.34 kN) weight limitation. The landing area weight limitation shall be indicated by the numeral "3" (kips) located in the bottom right corner of the landing area as viewed from the primary approach path. The indication for the landing area weight limitation shall be a minimum 5 feet (1524 mm) in height.

Floors and other surfaces that are intended to support vehicle loads greater than a 10,000 pound (4536 kg) gross vehicle weight rating shall comply with Sections 1607.7.1 through 1607.7.5.
Where any structure does not restrict access for vehicles that exceed a 10,000-pound (4536 kg) gross vehicle weight rating, those portions of the structure subject to such loads shall be designed using the vehicular live loads, including consideration of impact and fatigue, in accordance with the codes and specifications required by the jurisdiction having authority for the design and construction of the roadways and bridges in the same location of the structure.
Where a structure or portions of a structure are accessed and loaded by fire department access vehicles and other similar emergency vehicles, the structure shall be designed for the greater of the following loads:
  1. The actual operational loads, including outrigger reactions and contact areas of the vehicles as stipulated and approved by the building official; or
  2. The live loading specified in Section 1607.7.1.
Garages designed to accommodate vehicles that exceed a 10,000 pound (4536 kg) gross vehicle weight rating, shall be designed using the live loading specified by Section 1607.7.1. For garages the design for impact and fatigue is not required.
Exception: The vehicular live loads and load placement are allowed to be determined using the actual vehicle weights for the vehicles allowed onto the garage floors, provided such loads and placement are based on rational engineering principles and are approved by the building official, but shall not be less than 50 psf (2.9 kN/m2). This live load shall not be reduced.
Where a structure is intended to have forklifts or other movable equipment present, the structure shall be designed for the total vehicle or equipment load and the individual wheel loads for the anticipated vehicles as specified by the owner of the facility. These loads shall be posted per Section 1607.7.5.
Impact loads and fatigue loading shall be considered in the design of the supporting structure. For the purposes of design, the vehicle and wheel loads shall be increased by 30 percent to account for impact.
The maximum weight of the vehicles allowed into or on a garage or other structure shall be posted by the owner in accordance with Section 106.1.
Handrails, guards, grab bars, accessible seats, accessible benches and vehicle barriers shall be designed and constructed to the structural loading conditions set forth in this section.
Handrails and guards shall be designed to resist a linear load of 50 pounds per linear foot (plf) (0.73 kN/m) in accordance with Section 4.5.1 of ASCE 7. Glass handrail assemblies and guards shall also comply with Section 2407.
Exceptions:
  1. For one- and two-family dwellings, only the single concentrated load required by Section 1607.8.1.1 shall be applied.
  2. In Group I-3, F, H and S occupancies, for areas that are not accessible to the general public and that have an occupant load less than 50, the minimum load shall be 20 pounds per foot (0.29 kN/m).
Handrails and guards shall also be designed to resist a concentrated load of 200 pounds (0.89 kN) in accordance with Section 4.5.1 of ASCE 7.
Intermediate rails (all those except the handrail), balusters and panel fillers shall be designed to resist a concentrated load of 50 pounds (0.22 kN) in accordance with Section 4.5.1 of ASCE 7.
Grab bars, shower seats and dressing room bench seats shall be designed to resist a single concentrated load of 250 pounds (1.11 kN) applied in any direction at any point on the grab bar or seat so as to produce the maximum load effects.
Vehicle barriers for passenger vehicles shall be designed to resist a concentrated load of 6,000 pounds (26.70 kN) in accordance with Section 4.5.3 of ASCE 7. Garages accommodating trucks and buses shall be designed in accordance with an approved method that contains provisions for traffic railings.
The live loads specified in Sections 1607.3 through 1607.8 shall be assumed to include adequate allowance for ordinary impact conditions. Provisions shall be made in the structural design for uses and loads that involve unusual vibration and impact forces.
Members, elements and components subject to dynamic loads from elevators shall be designed for impact loads and deflection limits prescribed by ASME A17.1.
For the purpose of design, the weight of machinery and moving loads shall be increased as follows to allow for impact: (1) light machinery, shaft- or motor-driven, 20 percent; and (2) reciprocating machinery or power-driven units, 50 percent. Percentages shall be increased where specified by the manufacturer.
Except for uniform live loads at roofs, all other minimum uniformly distributed live loads, Lo, in Table 1607.1 are permitted to be reduced in accordance with Section 1607.10.1 or 1607.10.2. Uniform live loads at roofs are permitted to be reduced in accordance with Section 1607.12.2.
Subject to the limitations of Sections 1607.10.1.1 through 1607.10.1.3 and Table 1607.1, members for which a value of KLLAT is 400 square feet (37.16 m2) or more are permitted to be designed for a reduced uniformly distributed live load, L, in accordance with the following equation:
(Equation 16-23)
For SI:
where:
L = Reduced design live load per square foot (m2) of area supported by the member.
Lo = Unreduced design live load per square foot (m2) of area supported by the member (see Table 1607.1).
KLL = Live load element factor (see Table 1607.10.1).
AT = Tributary area, in square feet (m2).
L shall not be less than 0.50Lo for members supporting one floor and L shall not be less than 0.40Lo for members supporting two or more floors.

TABLE 1607.10.1
LIVE LOAD ELEMENT FACTOR, K
LL
ELEMENT KLL
Interior columns 4
Exterior columns without cantilever slabs 4
Edge columns with cantilever slabs 3
Corner columns with cantilever slabs 2
Edge beams without cantilever slabs 2
Interior beams 2
All other members not identified above including:
  • Edge beams with cantilever slabs
  • Cantilever beams
  • One-way slabs
  • Two-way slabs
  • Members without provisions for continuous shear transfer normal to their span
1
The tributary area, AT, for use in Equation 16-23 for one-way slabs shall not exceed an area defined by the slab span times a width normal to the span of 1.5 times the slab span.
Live loads that exceed 100 psf (4.79 kN/m2) shall not be reduced.
Exceptions:
  1. The live loads for members supporting two or more floors are permitted to be reduced by a maximum of 20 percent, but the live load shall not be less than L as calculated in Section 1607.10.1.
  2. For uses other than storage, where approved, additional live load reductions shall be permitted where shown by the registered design professional that a rational approach has been used and that such reductions are warranted.
The live loads shall not be reduced in passenger vehicle garages.
Exception: The live loads for members supporting two or more floors are permitted to be reduced by a maximum of 20 percent, but the live load shall not be less than L as calculated in Section 1607.10.1.
As an alternative to Section 1607.10.1 and subject to the limitations of Table 1607.1, uniformly distributed live loads are permitted to be reduced in accordance with the following provisions. Such reductions shall apply to slab systems, beams, girders, columns, piers, walls and foundations. 
  1. A reduction shall not be permitted where the live load exceeds 100 psf (4.79 kN/m2) except that the design live load for members supporting two or more floors is permitted to be reduced by a maximum of 20 percent.
    Exception: For uses other than storage, where approved, additional live load reductions shall be permitted where shown by the registered design professional that a rational approach has been used and that such reductions are warranted.
  2. A reduction shall not be permitted in passenger vehicle parking garages except that the live loads for members supporting two or more floors are permitted to be reduced by a maximum of 20 percent.
  3. For live loads not exceeding 100 psf (4.79 kN/m2), the design live load for any structural member supporting 150 square feet (13.94 m2) or more is permitted to be reduced in accordance with Equation 16-24.
  4. For one-way slabs, the area, A, for use in Equation 16-24 shall not exceed the product of the slab span and a width normal to the span of 0.5 times the slab span.
R = 0.08(A — 150) (Equation 16-24)

For SI: R = 0.861(A — 13.94)

Such reduction shall not exceed the smallest of:
  1. 40 percent for horizontal members;
  2. 60 percent for vertical members; or
  3. R as determined by the following equation.
R = 23.1(1+ D/Lo) (Equation 16-25)

where:

A = Area of floor supported by the member, square feet (m2).
D = Dead load per square foot (m2) of area supported.
Lo = Unreduced live load per square foot (m2) of area supported.
R = Reduction in percent.
Where uniform floor live loads are involved in the design of structural members arranged so as to create continuity, the minimum applied loads shall be the full dead loads on all spans in combination with the floor live loads on spans selected to produce the greatest load effect at each location under consideration. Floor live loads are permitted to be reduced in accordance with Section 1607.10.
The structural supports of roofs and marquees shall be designed to resist wind and, where applicable, snow and earthquake loads, in addition to the dead load of construction and the appropriate live loads as prescribed in this section, or as set forth in Table 1607.1. The live loads acting on a sloping surface shall be assumed to act vertically on the horizontal projection of that surface.
Where uniform roof live loads are reduced to less than 20 psf (0.96 kN/m2) in accordance with Section 1607.12.2.1 and are applied to the design of structural members arranged so as to create continuity, the reduced roof live load shall be applied to adjacent spans or to alternate spans, whichever produces the most unfavorable load effect. See Section 1607.12.2 for reductions in minimum roof live loads and Section 7.5 of ASCE 7 for partial snow loading.
The minimum uniformly distributed live loads of roofs and marquees, Lo, in Table 1607.1 are permitted to be reduced in accordance with Section 1607.12.2.1.
Ordinary flat, pitched and curved roofs, and awnings and canopies other than of fabric construction supported by a skeleton structure, are permitted to be designed for a reduced uniformly distributed roof live load, Lr, as specified in the following equations or other controlling combinations of loads as specified in Section 1605, whichever produces the greater load effect.

In structures such as greenhouses, where special scaffolding is used as a work surface for workers and materials during maintenance and repair operations, a lower roof load than specified in the following equations shall not be used unless approved by the building official. Such structures shall be designed for a minimum roof live load of 12 psf (0.58 kN/m2).

Lr = Lo R1R2 (Equation 16-26)

where: 12 ≤ Lr≤ 20

For SI: Lr = Lo R1R2

where: 0.58 ≤ Lr≤ 0.96
Lo = Unreduced roof live load per square foot (m2) of horizontal projection supported by the member (see Table 1607.1).
Lr = Reduced roof live load per square foot (m2) of horizontal projection supported by the member.

The reduction factors R1 and R2 shall be determined as follows:
R1 = 1 for At ≤ 200 square feet (18.58 m2) (Equation 16-27)
R1 = 1.2 - 0.001Atfor 200 square feet
< At< 600 square feet
(Equation 16-28)

For SI: 1.2 - 0.011At for 18.58 square meters < At< 55.74 square meters


R1 = 0.6 for At ≥ 600 square feet (55.74 m2) (Equation 16-29)
where:
At = Tributary area (span length multiplied by effective width) in square feet (m2) supported by the member, and

R2= 1 for F ≤ 4 (Equation 16-30)
R2= 1.2 - 0.05 F for 4 < F < 12 (Equation 16-31)
R2= 0.6 for F ≥ 12 (Equation 16-32)
where:
F = For a sloped roof, the number of inches of rise per foot (for SI: F = 0.12 × slope, with slope expressed as a percentage), or for an arch or dome, the rise-to-span ratio multiplied by 32.
Areas of roofs that are occupiable, such as roof gardens, or for assembly or other similar purposes, and marquees are permitted to have their uniformly distributed live loads reduced in accordance with Section 1607.10.
The uniform design live load in unoccupied landscaped areas on roofs shall be 20 psf (0.958 kN/m2). The weight of all landscaping materials shall be considered as dead load and shall be computed on the basis of saturation of the soil.
Awnings and canopies shall be designed for uniform live loads as required in Table 1607.1 as well as for snow loads and wind loads as specified in Sections 1608 and 1609.
The crane live load shall be the rated capacity of the crane. Design loads for the runway beams, including connections and support brackets, of moving bridge cranes and monorail cranes shall include the maximum wheel loads of the crane and the vertical impact, lateral and longitudinal forces induced by the moving crane.
The maximum wheel loads shall be the wheel loads produced by the weight of the bridge, as applicable, plus the sum of the rated capacity and the weight of the trolley with the trolley positioned on its runway at the location where the resulting load effect is maximum.
The maximum wheel loads of the crane shall be increased by the percentages shown below to determine the induced vertical impact or vibration force:
Monorail cranes (powered) 25 percent
Cab-operated or remotely operated bridge
cranes (powered)
25 percent
Pendant-operated bridge cranes
(powered)
10 percent
Bridge cranes or monorail cranes with
hand-geared bridge, trolley and hoist
0 percent
The lateral force on crane runway beams with electrically powered trolleys shall be calculated as 20 percent of the sum of the rated capacity of the crane and the weight of the hoist and trolley. The lateral force shall be assumed to act horizontally at the traction surface of a runway beam, in either direction perpendicular to the beam, and shall be distributed with due regard to the lateral stiffness of the runway beam and supporting structure.
The longitudinal force on crane runway beams, except for bridge cranes with hand-geared bridges, shall be calculated as 10 percent of the maximum wheel loads of the crane. The longitudinal force shall be assumed to act horizontally at the traction surface of a runway beam, in either direction parallel to the beam.
Interior walls and partitions that exceed 6 feet (1829 mm) in height, including their finish materials, shall have adequate strength to resist the loads to which they are subjected but not less than a horizontal load of 5 psf (0.240 kN/m2).
Exception: Fabric partitions complying with Section 1607.14.1 shall not be required to resist the minimum horizontal load of 5 psf (0.24 kN/m2).
Fabric partitions that exceed 6 feet (1829 mm) in height, including their finish materials, shall have adequate strength to resist the following load conditions:
  1. A horizontal distributed load of 5 psf (0.24 kN/m2) applied to the partition framing. The total area used to determine the distributed load shall be the area of the fabric face between the framing members to which the fabric is attached. The total distributed load shall be uniformly applied to such framing members in proportion to the length of each member.
  2. A concentrated load of 40 pounds (0.176 kN) applied to an 8-inch diameter (203 mm) area [50.3 square inches (32 452 mm2)] of the fabric face at a height of 54 inches (1372 mm) above the floor.
Design snow loads shall be determined in accordance with Chapter 7 of ASCE 7, but the design roof load shall not be less than that determined by Section 1607.
The ground snow loads to be used in determining the design snow loads for roofs shall be determined in accordance with ASCE 7 or Figure 1608.2 for the contiguous United States and Table 1608.2 for Alaska. Site-specific case studies shall be made in areas designated "CS" in Figure 1608.2. Ground snow loads for sites at elevations above the limits indicated in Figure 1608.2 and for all sites within the CS areas shall be approved. Ground snow load determination for such sites shall be based on an extreme value statistical analysis of data available in the vicinity of the site using a value with a 2-percent annual probability of being exceeded (50-year mean recurrence interval). Snow loads are zero for Hawaii, except in mountainous regions as approved by the building official.
TABLE 1608.2
GROUND SNOW LOADS, pg, FOR ALASKAN LOCATIONS
LOCATION POUNDS PER SQUARE FOOT
Adak 30
Anchorage 50
Angoon 70
Barrow 25
Barter Island 35
Bethel 40
Big Delta 50
Cold Bay 25
Cordova 100
Fairbanks 60
Fort Yukon 60
Galena 60
Gulkana 70
Homer 40
Juneau 60
Kenai 70
Kodiak 30
Kotzebue 60
McGrath 70
Nenana 80
Nome 70
Palmer 50
Petersburg 150
St. Paul Islands 40
Seward 50
Shemya 25
Sitka 50
Talkeetna 120
Unalakleet 50
Valdez 160
Whittier 300
Wrangell 60
Yakutat 150


For SI: 1 pound per square foot = 0.0479 kN/m2.
FIGURE 1608.2
GROUND SNOW LOADS, pg, FOR THE UNITED STATES (psf)
Susceptible bays of roofs shall be evaluated for ponding instability in accordance with Section 7.11 of ASCE 7.
FIGURE 1609A
ULTIMATE DESIGN WIND SPEEDS, VULT, FOR RISK CATEGORY II BUILDINGS AND OTHER STRUCTURES


FIGURE 1609B
ULTIMATE DESIGN WIND SPEEDS, VULT, FOR RISK CATEGORY III AND IV BUILDINGS AND OTHER STRUCTURES


FIGURE 1609C
ULTIMATE DESIGN WIND SPEEDS, VULT, FOR RISK CATEGORY I BUILDINGS AND OTHER STRUCTURES
Buildings, structures and parts thereof shall be designed to withstand the minimum wind loads prescribed herein. Decreases in wind loads shall not be made for the effect of shielding by other structures.

1609.1.1 Determination of Wind Loads

AMENDMENT
This section has been amended at the state or city level.
Wind loads on every building or structure shall be determined in accordance with Chapters 26 to 30 of ASCE 7. Minimum values for Directionality Factor, Kd, Velocity Pressure Exposure Coefficient, Kz, and Topographic Factor, Kzt, shall be determined in accordance with Section 1609. The type of opening protection required, the ultimate design wind speed, Vult, and the exposure category for a site is permitted to be determined in accordance with Section 1609 or ASCE 7. Wind shall be assumed to come from any horizontal direction and wind pressures shall be assumed to act normal to the surface considered.
Exceptions:
  1. Subject to the limitations of Section 1609.1.1.1, the provisions of ICC 600 shall be permitted for applicable Group R-2 and R-3 buildings.
  2. Subject to the limitations of Section 1609.1.1.1, residential structures using the provisions of the AWC WFCM.
  3. Subject to the limitations of Section 1609.1.1.1, residential structures using the provisions of AISI S230.
  4. Designs using NAAMM FP 1001.
  5. Designs using TIA-222 for antenna-supporting structures and antennas, provided the effect of topography is included in accordance with Section 1609.3.3 Topographic effects.
  6. Wind tunnel tests in accordance with Chapter 31 of ASCE 7, subject to the limitations in Section 1609.1.1.2.
The wind speeds in Figures 1609A, 1609B and 1609C are ultimate design wind speeds, Vult. Values of effective nominal design wind speeds, Veff-asd, determined in accordance with Sections 1609.3.1 and 1609.3.2, shall be used when the standards referenced in Exceptions 1 through 4 are used.

1609.1.1.1 Applicability

AMENDMENT
This section has been amended at the state or city level.
The provisions of ICC 600 are applicable only to buildings located within Exposure B or C as defined in Section 1609.4. The prescriptive provisions of ICC 600, AWC WFCM, or AISI S230 shall not be permitted for either of the following cases:
  1. Structures which are more than three stories above grade plane in height.
  2. Structures designed using exception 4 in Section 1609.1.2 Protection of Openings.

1609.1.2 Protection of Openings

AMENDMENT
This section has been amended at the state or city level.
In wind-borne debris regions, glazing in buildings shall be impact-resistant or protected with an impact-resistant covering meeting the requirements of an approved impact-resistant standard or ASTM E 1996 and ASTM E 1886 referenced herein as follows:
  1. Glazed openings located within 30 feet (9144 mm) of grade shall meet the requirements of the Large Missile Test of ASTM E 1996- 14.
  2. Glazed openings located more than 30 feet (9144 mm) above grade shall meet the provisions of the Small Missile Test of ASTM E 1996-14.
  3. Glazing in Risk Category III buildings defined by Table 1604.5 of the following occupancies shall be provided with windborne debris protection:
    1. Covered structures whose primary occupancy is public assembly with an occupant load greater than 300.
    2. Health care facilities with an occupant load of 50 or more resident patients, but not having surgery or emergency treatment facilities.
    3. Any other public building with an occupant load greater than 5,000.
Exceptions:
  1. Wood structural panels with a minimum thickness of 7/16 inch (11 mm) and a maximum panel span of 8 feet (2438 mm) shall be permitted for opening protection in one- and two-story buildings classified as Group R-3 or R-4 occupancy. Panels shall be precut so that they shall be attached to the framing surrounding the opening containing the product with the glazed opening. Panels shall be predrilled as required for the anchorage method and shall be secured with the attachment hardware provided. Attachments shall be designed to resist the components and cladding loads determined in accordance with the provisions of ASCE 7, with corrosion-resistant attachment hardware provided and anchors permanently installed on the building. Attachment in accordance with Table 1609.1.2 with corrosion-resistant attachment hardware provided and anchors permanently installed on the building is permitted for buildings with a mean roof height of 33 feet (10 058 mm) or less where effective ultimate design wind speeds, Veff-ult do not exceed 175 mph (78 m/s).
  2. Glazing in Risk Category I buildings as defined in Section 1604.5, including greenhouses that are occupied for growing plants on a production or research basis, without public access shall be permitted to be unprotected.
  3. Glazing in Risk Category II, III or IV buildings located over 60 feet (18 288 mm) above the ground and over 30 feet (9144 mm) above aggregate surface roofs located within 1,500 feet (458 m) of the building shall be permitted to be unprotected.
  4. Risk Category II buildings shall be permitted to be designed with unprotected openings subject to the following requirements:
    1. For each direction of wind, determination of enclosure classification shall be based on the assumption that all unprotected glazing on windward walls are openings while glazing on the remaining walls and roof are intact and are not assumed to be openings.
    2. Partially enclosed and open occupancy R-3 buildings without wind-borne debris protection shall also include a residential safe room in accordance with Section 425, Hawaii residential safe room, or alternatively provide an equivalently sized room structurally protected by construction complying with Section 425.5.
TABLE 1609.1.2
WIND-BORNE DEBRIS PROTECTION FASTENING SCHEDULE FOR WOOD STRUCTURAL PANELSa, b, c, d
FASTENER TYPEFASTENER SPACING (inches)
Panel Span
≤ 4 feet
Panel Span > 4 feet and ≤ 6 feet Panel Span > 6 feet and ≤ 8 feet
No. 8 Wood screw
based anchor with 2
-inch embedment length
16"10"8"
No. 10 Wood screw
-based anchor with 2-inch embedment length
16"12"9"
1/4-inch lag-screw-based anchor with 2-inch embedment length16"16"16"
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound = 0.454 kg, 1 mile per hour = 1.609 km/h.
  1. This table is based on a 175 mph effective ultimate design wind speed and a mean roof height of 45 feet.
  2. Fasteners shall be installed at opposing ends of the wood structural panel. Fasteners shall be located a minimum of 1 inch from the edge of the panel.
  3. Anchors shall penetrate through the exterior wall covering with an embedment length of 2 inches minimum into the building frame. Fasteners shall be located a minimum of 2-1/2 inches from the edge of concrete block or concrete.
  4. Where panels are attached to masonry or masonry/stucco, they shall be attached utilizing vibration-resistant anchors having a minimum withdrawal capacity of 1,500 pounds.
Louvers protecting intake and exhaust ventilation ducts not assumed to be open that are located within 30 feet (9144 mm) of grade shall meet the requirements of AMCA 540.
The text of Section 6.2.2 of ASTM E 1996 shall be substituted as follows:

6.2.2 Unless otherwise specified, select the wind zone based on the strength design wind speed, Vult, as follows:

6.2.2.1 Wind Zone 1—130 mph ≤ ultimate design wind speed, Vult< 140 mph.

6.2.2.2 Wind Zone 2—140 mph ≤ ultimate design wind speed, Vult< 150 mph at greater than one mile (1.6 km) from the coastline. The coastline shall be measured from the mean high water mark.

6.2.2.3 Wind Zone 3—150 mph (58 m/s) ≤ ultimate design wind speed, Vult ≤ 160 mph (63 m/s), or 140 mph (54 m/s) ≤ ultimate design wind speed, Vult ≤ 160 mph (63 m/s) and within one mile(1.6 km) of the coastline. The coastline shall be measured from the mean high water mark.

6.2.2.4 Wind Zone 4— ultimate design wind speed, Vult >160 mph (63 m/s).

Garage door glazed opening protection for wind-borne debris shall meet the requirements of an approved impact-resisting standard or ANSI/DASMA 115.
For the purposes of Section 1609 and as used elsewhere in this code, the following terms are defined in Chapter 2.
WIND SPEED, Vult.
WIND SPEED, Vasd.

1609.3 Ultimate Design Basic Wind Speed and Topographic and Directionality Factors

AMENDMENT
This section has been amended at the state or city level.
The ultimate design wind speed, Vult in mph, for the determination of the wind loads shall be determined by Figure 1609A, 1609B and 1609C. The ultimate design wind speed Vult, for use in the design of Risk Category II buildings and structures shall be obtained from Figure 1609A. The ultimate design wind speed, Vult, for use in the design of Risk Category III and IV buildings and structures shall be obtained from Figure 1609B. The ultimate design wind speed, Veff-ult, for use in the design of Risk Category I buildings and structures shall be obtained from Figure 1609C.

The effective ultimate design wind speed, Vult, for the special wind regions indicated near mountainous terrain and near gorges shall be in accordance with Section 1609.3.2.
Special wind regions near mountainous terrain and valleys are accounted within the Topographic Factor defined in Section 1609.3.3. Wind speeds derived from simulation techniques shall only be used in lieu of the wind speeds given in Figure 1609 when:
  1. Approved simulation or extreme-value statistical-analysis procedures are used (the use of regional wind speed data obtained from anemometers is not permitted to define the hurricane wind speed risk in Hawaii); and
  2. The ultimate design wind speeds resulting from the study shall not be less than the resulting 700-year return period wind speed for Risk Category II and 1700-year return period wind speed for Risk Category III and IV , and 300-year return period design wind speed for Risk Category I.

1609.3.1 Effective Wind Speed Conversion

AMENDMENT
This section has been amended at the state or city level.
For Section 2308.10.1 and the exceptions permitted under Section 1609.1.1, and when otherwise required, the nominal design wind speed value used for determination of the wind loads, shall be the effective design wind speed, Veff-asd, determined by multiplying the effective ultimate design wind speed values, Veff-ult given in Section 1609.3.2 by √0.625, in accordance with Equation 16-33.

Veff-asd = Veff-ult √0.625 (Equation 16-33)

1609.3.2 Effective ultimate design wind speed, Veff-ult, contour maps

AMENDMENT
This section has been amended at the state or city level.
Figures 1609.3.2.1(a) through 1609.3.2.1(f), Figures 1609.3.2.2(a) through 1609.3.2.2(f), and Figures 1609.3.2.3(a) through 1609.3.2.3(f) are added as follows:

Figure 1609.3.2.1(a)
County of Hawaii Effective Ultimate Wind Speed, Veff-ult, for Components and Cladding for Risk Category I Buildings less than 100 feet Tall


Figure 1609.3.2.1(b)
County of Maui, Island of Maui Effective Ultimate Wind Speed, Veff-ult, for Components and Cladding for Risk Category I Buildings less than 100 feet Tall


Figure 1609.3.2.1(c)
County of Maui, Island of Molokai Effective Ultimate Wind Speed, Veff-ult, for Components and Cladding for Risk Category I Buildings less than 100 feet Tall


Figure 1609.3.2.1(d)
County of Maui, Island of Lanai Effective Ultimate Wind Speed, Veff-ult, for Components and Cladding for Risk Category I Buildings less than 100 feet Tall


Figure 1609.3.2.1(e)
City and County of Honolulu Effective Ultimate Wind Speed, Veff-ult, for Components and Cladding for Risk Category I Buildings less than 60 feet Tall


Figure 1609.3.2.1(f)
County of Kauai Effective Ultimate Wind Speed, Veff-ult, for Components and Cladding for Risk Category I Buildings less than 100 feet Tall


Figure 1609.3.2.2(a)
County of Hawaii Effective Ultimate Wind Speed, Veff-ult, for Components and Cladding for Risk Category II Buildings less than 100 feet Tall


Figure 1609.3.2.2(b)
County of Maui, Island of Maui Effective Ultimate Wind Speed, Veff-ult, for Components and Cladding for Risk Category II Buildings less than 100 feet Tall


Figure 1609.3.2.2(c)
County of Maui, Island of Molokai Effective Ultimate Wind Speed, Veff-ult, for Components and Cladding for Risk Category II Buildings less than 100 feet Tall


Figure 1609.3.2.2(d)
County of Maui, Island of Lanai Effective Ultimate Wind Speed, Veff-ult, for Components and Cladding for Risk Category II Buildings less than 100 feet Tall


Figure 1609.3.2.2(e)
City and County of Honolulu Effective Ultimate Wind Speed, Veff-ult, for Components and Cladding for Risk Category II Buildings less than 60 feet Tall


Figure 1609.3.2.2(f)
County of Kauai Effective Ultimate Wind Speed, Veff-ult, for Components and Cladding for Risk Category II Buildings less than 100 feet Tall


Figure 1609.3.2.3(a)
County of Hawaii Effective Ultimate Wind Speed, Veff-ult, for Components and Cladding for Risk Category III and IV Buildings less than 100 feet Tall


Figure 1609.3.2.3(b)
County of Maui, Island of Maui Effective Ultimate Wind Speed, Veff-ult, for Components and Cladding for Risk Category III and IV Buildings less than 100 feet Tall


Figure 1609.3.2.3(c)
County of Maui, Island of Molokai Effective Ultimate Wind Speed, Veff-ult, for Components and Cladding for Risk Category III and IV Buildings less than 100 feet Tall


Figure 1609.3.2.3(d)
County of Maui, Island of Lanai Effective Ultimate Wind Speed, Veff-ult, for Components and Cladding for Risk Category III and IV Buildings less than 100 feet Tall


Figure 1609.3.2.3(e)
City and County of Honolulu Effective Ultimate Wind Speed, Veff-ult, for Components and Cladding for Risk Category III and IV Buildings less than 60 feet Tall


Figure 1609.3.2.3(f)
County of Kauai Effective Ultimate Wind Speed, Veff-ult, for Components and Cladding for Risk Category III and IV Buildings less than 100 feet Tall

1609.3.3 Topographic Effects

AMENDMENT
This section has been amended at the state or city level.
Wind speed-up effects caused by topography shall be included in the calculation of wind loads by using the factor Kzt, where Kzt is given in Figures 1609.3.3(a) through 1609.3.3(f).

Exception: Site-specific probabilistic analysis of directional Kzt based on wind-tunnel testing of topographic speed-up shall be permitted to be submitted for approval by the building official.


Figure 1609.3.3(a)
County of Hawaii Peak Gust Topographic Factor Kzt


Figure 1609.3.3(b)
County of Maui, Island of Maui Peak Gust Topographic Factor Kzt


Figure 1609.3.3(c)
County of Maui, Island of Molokai Peak Gust Topographic Factor Kzt


Figure 1609.3.3(d)
County of Maui, Island of Lanai Peak Gust Topographic Factor Kzt


Figure 1609.3.3(e)
City and County of Honolulu Peak Topographic Factor Kzt for Building Heights up to 100 feeta,b

  1. Site-specific probabilistic analysis of directional Kzt based on wind-tunnel testing of topographic speed-up shall be permitted to be submitted for approval by the building official. For buildings taller than 160 feet, this submittal shall include peak gust velocity profiles for all wind direction sectors.
  2. At Exposure B sites with ground elevations less than 500 feet, Kzt values ≥1.2 shall be permitted to be reduced for building heights greater than 100 feet by multiplying Kzt mapped in Figure 1609.3.3(e) by the height adjustments given in the Table 1609.3.3(e)2. Interpolation is permitted.
Table 1609.3.3(e)2
Height Adjustment of Mapped Kzt Values at Sites with Ground Elevation Less than 500 feet

Building roof height above ground (ft) ≤100 120 140 160 180 200 220 ≥240
Adjustment factor to
Kzt ≥1.2
100% 98% 96% 94% 92% 90% 92% 94%


Figure 1609.3.3(f)
County of Kauai Peak Gust Topographic Factor Kzt

1609.3.4 Directionality Factor

AMENDMENT
This section has been amended at the state or city level.
The wind directionality factor, Kd, shall be determined from Tables 1609.3.4(a)(1) through 1609.3.4(a)(3) and 1609.3.4(b)(1) through 1609.3.4(b)(3), and Figures 1609.3.4(a)(4) and 1609.3.4(b)(4).

Table 1609.3.4(a)(1)
Kd Values for Main Wind Force Resisting Systems Sited in Hawaii County a,b
Topographic Location
on the Island of
Hawaii
Main Wind Force Resisting
Systems
Main Wind Force Resisting
Systems with totally
independent systems in
each orthogonal direction
Biaxially
Symmetric and
Axisymmetric
Structures of
any Height and
Arched Roof
Structures
Mean Roof
Height less
than or equal
to 100 ft.
Mean Roof
Height
greater
than 100 ft.
Mean Roof
Height less
than or equal
to 100 ft.
Mean Roof
Height
greater
than 100 ft.
Sites in North Kohala,
South Kohala, South
Kona, South Hilo, and
Puna Districts at an
elevation not greater
than 3000 ft.
0.65 0.70 0.70 0.75 0.85
All other sites 0.70 0.80 0.75 0.80 0.95
  1. The values of Kd for other non-building structures indicated in ASCE-7 Table 26-4 shall be permitted.
  2. Site-specific probabilistic analysis of Kd based on wind-tunnel testing of topography and peak gust velocity profile shall be permitted to be submitted for approval by the Building Official, but Kd shall have a value not less than 0.65.

Table 1609.3.4(a)(2)
Kd Values for Main Wind Force Resisting Systems Sited in Maui Countya,b
Topographic Location
in the County of Maui
Main Wind Force Resisting
Systems
Main Wind Force Resisting
Systems with totally
independent systems in
each orthogonal direction
Biaxially
Symmetric and
Axisymmetric
Structures of
any Height
and Arched
Roof
Structures
Mean Roof
Height less
than or equal
to 100 ft.
Mean Roof
Height
greater
than 100 ft.
Mean Roof
Height less
than or equal
to 100 ft.
Mean Roof
Height
greater
than 100 ft.
Sites on the Island of
Maui at an elevation
not greater than 1000
ft.
0.60 0.65 0.70 0.75 0.85
Sites on the Island of
Maui at an elevation
greater than 1000 ft.
0.65 .70 0.75 0.80 0.90
All other sites on the
Islands of Molokai and
Lanai
0.80 0.85 0.80 0.85 0.95
  1. The values of Kd for other non-building structures indicated in ASCE-7 Table 26-4 shall be permitted.
  2. Site-specific probabilistic analysis of Kd based on wind-tunnel testing of topography and peak gust velocity profile shall be permitted to be submitted for approval by the Building Official, but Kd shall have a value not less than 0.60.

Table 1609.3.4(a)(3)
Kd Values for Main Wind Force Resisting Systems Sited on Oahu, Hawaiia,b
Topographic Location on
Oahu, Hawaii
Main Wind Force
Resisting Systems
Main Wind Force
Resisting Systems with
totally independent
systems in each
orthogonal direction
Biaxially
Symmetric
and
Axisymmetri
c Structures
of any
Height and
Arched Roof
Structures
Mean Roof
Height less
than or
equal to
100 ft.
Mean
Roof
Height
greater
than 100
ft.
Mean Roof
Height less
than or
equal to
100 ft.
Mean Roof
Height
greater
than 100 ft.
Sites within valleys at an
elevation of at least 50 ft. but
not greater than 500 ft.
0.65 0.70 0.70 0.75 0.85
Central Oahu above an
elevation of 500 ft, the Ewa
and Kapolei plains, and
coastal areas with Kzt (10m)
not greater than 1.2
0.75 0.80 0.75 0.80 0.95
All other areas, including
Hills, Hillsides, Ridges,
Bluffs, and Escarpments at
any elevation or height;
coastal and inland areas
with Kzt (10m) greater than
1.2
0.70 0.75 0.75 0.80 0.90
  1. The values of Kd for other non-building structures indicated in ASCE-7 Table 26-4 shall be permitted.
  2. Site-specific probabilistic analysis of Kd based on wind-tunnel testing of topography and peak gust velocity profile shall be permitted to be submitted for approval by the Building Official, but Kd shall have a value not less than 0.65.


Figure 1609.3.4(a)(4)
Kd Values for Main Wind Force Resisting Systems Sited on Kauai County, Hawaiia,b
  1. The values of Kd for other non-building structures indicated in ASCE-7 Table 26-4 shall be permitted.
  2. Site-specific probabilistic analysis of Kd based on wind-tunnel testing of topography and peak gust velocity profile shall be permitted to be submitted for approval by the Building Official, but Kd shall have a value not less than 0.65.

Table 1609.3.4(b)(1)
Kd Values for Components and Cladding of Buildings Sited in Hawaii Countya,b
Topographic Location on the
Island of Hawaii
Components and Cladding
Mean Roof
Height less
than or equal
to 100 ft.
Mean Roof
Height
greater than
100 ft.
Risk Category
IV Buildings
and Structures
Sites in North Kohala, South
Kohala, South Kona, South Hilo,
and Puna Districts at an elevation
not greater than 3000 ft.
0.65 0.70 0.75
All other sites 0.75 0.80 0.85
  1. The values of Kd for other non-building structures indicated in ASCE-7 Table 26-4 shall be permitted.
  2. Site-specific probabilistic analysis of Kd based on wind-tunnel testing of topography and peak gust velocity profile shall be permitted to be submitted for approval by the Building Official, but in any case subject to a minimum value of 0.65.
Table 1609.3.4(b)(2)
Kd Values for Components and Cladding of Buildings Sited in Maui Countya,b
Topographic Location on the
County of Maui
Components and Cladding
Mean Roof
Height less
than or equal
to 100 ft.
Mean Roof
Height
greater
than 100 ft.
Risk Category
IV Buildings
and Structures
Sites on the Island of Maui at an
elevation not greater than 1000 ft
0.65 0.70 0.75
Sites on the Island of Maui at an
elevation greater than 1000 ft.
0.70 0.75 0.85
All other sites on the Islands of
Molokai and Lanai
0.80 0.85 0.85
  1. The values of Kd for other non-building structures indicated in ASCE-7 Table 26-4 shall be permitted.
  2. Site-specific probabilistic analysis of Kd based on wind-tunnel testing of topography and peak gust velocity profile shall be permitted to be submitted for approval by the Building Official, but in any case subject to a minimum value of 0.65.

Table 1609.3.4(b)(3)
Kd Values for Components and Cladding of Buildings Sited on Oahu, Hawaiia,b
Topographic Location on Oahu Components and Cladding
Mean Roof
Height less
than or equal
to 100 ft.
Mean Roof
Height
greater
than 100 ft.
Risk Category
IV Buildings
and
Structures
Sites within valleys at an
elevation of at least 50 ft. but not
greater than 500 ft.
0.65 0.70 0.75
Central Oahu above an elevation
of 500 ft, the Ewa and Kapolei
plains, and coastal areas with Kzt
(10m) not greater than 1.2
0.75 0.80 0.85
All other areas, including Hills,
Hillsides, Ridges, Bluffs, and
Escarpments at any elevation or
height; coastal and inland areas
with Kzt (10m) greater than 1.2
0.70 0.75 0.80
  1. The values of Kd for other non-building structures indicated in ASCE-7 Table 26-4 shall be permitted.
  2. Site-specific probabilistic analysis of Kd based on wind-tunnel testing of topography and peak gust velocity profile shall be permitted to be submitted for approval by the Building Official, but in any case subject to a minimum value of 0.65.


Figure 1609.3.4(b)(4)
Kd Values for Components and Cladding of Buildings Sited on Kauai County, Hawaiia,b
  1. The values of Kd for other non-building structures indicated in ASCE-7 Table 26-4 shall be permitted.
  2. Site-specific probabilistic analysis of Kd based on wind-tunnel testing of topography and peak gust velocity profile shall be permitted to be submitted for approval by the Building Official, but Kd shall have a value not less than 0.65.

1609.4 Exposure Category

AMENDMENT
This section has been amended at the state or city level.
For each wind direction considered, an exposure category that adequately reflects the characteristics of ground surface irregularities shall be determined for the site at which the building or structure is to be constructed. Account shall be taken of variations in ground surface roughness that arise from natural topography and vegetation as well as from constructed features.
Notes:
  1. Intermediate exposures, between categories B and C and between C and D, are permitted when substantiated per ASCE 7 recognized methodology.
  2. Sites located within the C (coastal) zone shall be permitted to be evaluated for exposure category B for the wind directions where an adjacent B zone exists in the applicable upwind sector.
  3. Sites located within 600 feet from the coastline shall be exposure category D for onshore wind directions.
  4. For buildings whose height is equal to or greater then 130 ft, exposure category shall be determined per Section 1609.4.1.
  5. For building whose mean roof height is less than or equal to 30 ft, exposure category shall be permitted to be evaluated per Section 1609.4.
Figure 1609.4 (a)
Exposure Category Zones for Hawaii County


Notes:
  1. Intermediate exposures, between categories B and C and between C and D, are permitted when substantiated per ASCE 7 recognized methodology.
  2. Sites located within the C (coastal) zone shall be permitted to be evaluated for exposure category B for the wind directions where an adjacent B zone exists in the applicable upwind sector.
  3. Sites located within 600 feet from the coastline shall be exposure category D for onshore wind directions.
  4. For buildings whose height is equal to or greater then 130 ft, exposure category shall be determined per Section 1609.4.1.
  5. For building whose mean roof height is less than or equal to 30 ft, exposure category shall be permitted to be evaluated per Section 1609.4.
Figure 1609.4. (b)
Exposure Category Zones for Island of Maui, Maui County


Figure 1609.4 (c)
Exposure Category Zones for Islands of Molokai and Lanai, Maui County


Notes:
  1. Intermediate exposures, between categories B and C and between C and D, are permitted when substantiated per ASCE 7 recognized methodology.
  2. Sites located within the C (coastal) zone shall be permitted to be evaluated for exposure category B for the wind directions where an adjacent B zone exists in the applicable upwind sector.
  3. Sites located within 600 feet from the coastline shall be exposure category D for onshore wind directions.
  4. For buildings whose height is equal to or greater then 130 ft, exposure category shall be determined per Section 1609.4.1.
  5. For building whose mean roof height is less than or equal to 30 ft, exposure category shall be permitted to be evaluated per Section 1609.4.
Figure 1609.4 (d)
Exposure Category Zones for the City and County of Honolulu


Notes:
  1. Intermediate exposures, between categories B and C and between C and D, are permitted when substantiated per ASCE 7 recognized methodology.
  2. Sites located within the C (coastal) zone shall be permitted to be evaluated for exposure category B for the wind directions where an adjacent B zone exists in the applicable upwind sector.
  3. Sites located within 600 feet from the coastline shall be exposure category D for onshore wind directions.
  4. For buildings whose height is equal to or greater then 130 ft, exposure category shall be determined per Section 1609.4.1.
  5. For building whose mean roof height is less than or equal to 30 ft, exposure category shall be permitted to be evaluated per Section 1609.4.
Figure 1609.4 (e)
Exposure Category Zones for Kauai County

1609.4.1 Wind Directions and Sectors

AMENDMENT
This section has been amended at the state or city level.
For each selected wind direction considered, at which the wind loads are to be evaluated, the an exposure of the building or structure shall be determined for the two upwind sectors extending 45 degrees (0.79 rad) either side of the selected wind direction. The exposures in these two sectors shall be determined in accordance with Sections 1609.4.2 and 1609.4.3 and the exposure resulting in the highest wind loads shall be used to represent winds from that direction.

Exception: Exposure categories shall be permitted to be determined using Figures 1609.4(a) through 1609.4(e).
A ground surface roughness within each 45-degree (0.79 rad) sector shall be determined for a distance upwind of the site as defined in Section 1609.4.3 from the categories defined below, for the purpose of assigning an exposure category as defined in Section 1609.4.3.
Surface Roughness B.
Urban and suburban areas, wooded areas or other terrain with numerous closely spaced obstructions having the size of single-family dwellings or larger.
Surface Roughness C.
Open terrain with scattered obstructions having heights generally less than 30 feet (9144 mm). This category includes flat open country, and grasslands.
Surface Roughness D.
Flat, unobstructed areas and water surfaces. This category includes smooth mud flats, salt flats and unbroken ice.
An exposure category shall be determined in accordance with the following:
Exposure B. For buildings with a mean roof height of less than or equal to 30 feet (9144 mm), Exposure B shall apply where the ground surface roughness, as defined by Surface Roughness B, prevails in the upwind direction for a distance of at least 1,500 feet (457 m). For buildings with a mean roof height greater than 30 feet (9144 mm), Exposure B shall apply where Surface Roughness B prevails in the upwind direction for a distance of at least 2,600 feet (792 m) or 20 times the height of the building, whichever is greater.
Exposure C. Exposure C shall apply for all cases where Exposures B or D do not apply.
Exposure D. Exposure D shall apply where the ground surface roughness, as defined by Surface Roughness D, prevails in the upwind direction for a distance of at least 5,000 feet (1524 m) or 20 times the height of the building, whichever is greater. Exposure D shall also apply where the ground surface roughness immediately upwind of the site is B or C, and the site is within a distance of 600 feet (183 m) or 20 times the building height, whichever is greater, from an exposure D condition as defined in the previous sentence.
Roof systems shall be designed and constructed in accordance with Sections 1609.5.1 through 1609.5.3, as applicable.
The roof deck shall be designed to withstand the wind pressures determined in accordance with ASCE 7.
Roof coverings shall comply with Section 1609.5.1.
Exception: Rigid tile roof coverings that are air permeable and installed over a roof deck complying with Section 1609.5.1 are permitted to be designed in accordance with Section 1609.5.3.

Asphalt shingles installed over a roof deck complying with Section 1609.5.1 shall comply with the wind-resistance requirements of Section 1507.2.7.1.

Wind loads on rigid tile roof coverings shall be determined in accordance with the following equation:

(Equation 16-34)
For SI:




where:
b=Exposed width, feet (mm) of the roof tile.
CL=Lift coefficient. The lift coefficient for concrete and clay tile shall be 0.2 or shall be determined by test in accordance with Section 1711.2.
GCp=Roof pressure coefficient for each applicable roof zone determined from Chapter 30 of ASCE 7. Roof coefficients shall not be adjusted for internal pressure.
L=Length, feet (mm) of the roof tile.
La=Moment arm, feet (mm) from the axis of rotation to the point of uplift on the roof tile. The point of uplift shall be taken at 0.76L from the head of the tile and the middle of the exposed width. For roof tiles with nails or screws (with or without a tail clip), the axis of rotation shall be taken as the head of the tile for direct deck application or as the top edge of the batten for battened applications. For roof tiles fastened only by a nail or screw along the side of the tile, the axis of rotation shall be determined by testing. For roof tiles installed with battens and fastened only by a clip near the tail of the tile, the moment arm shall be determined about the top edge of the batten with consideration given for the point of rotation of the tiles based on straight bond or broken bond and the tile profile.
Ma=Aerodynamic uplift moment, feet-pounds (N-mm) acting to raise the tail of the tile.
qh=Wind velocity pressure, psf (kN/m2) determined from Section 27.3.2 of ASCE 7.
Concrete and clay roof tiles complying with the following limitations shall be designed to withstand the aerodynamic uplift moment as determined by this section.
  1. The roof tiles shall be either loose laid on battens, mechanically fastened, mortar set or adhesive set.
  2. The roof tiles shall be installed on solid sheathing which has been designed as components and cladding.
  3. An underlayment shall be installed in accordance with Chapter 15.
  4. The tile shall be single lapped interlocking with a minimum head lap of not less than 2 inches (51 mm).
  5. The length of the tile shall be between 1.0 and 1.75 feet (305 mm and 533 mm).
  6. The exposed width of the tile shall be between 0.67 and 1.25 feet (204 mm and 381 mm).
  7. The maximum thickness of the tail of the tile shall not exceed 1.3 inches (33 mm).
  8. Roof tiles using mortar set or adhesive set systems shall have at least two-thirds of the tile's area free of mortar or adhesive contact.

1609.5.4 Roof-Mounted Solar Collectors for Buildings

AMENDMENT
This section has been amended at the state or city level.
The design wind force for roof-mounted solar collector panels located on buildings shall be determined based on the location and height of the panel system and the configuration of the roof, in accordance with Sections 1609.5.4.1 through 1609.5.4.6.

     In addition to all the other applicable provisions of this Code, the roof itself shall be designed for both of the following:
  1. The case where solar collectors are present. Wind loads acting on solar collectors in accordance with this section shall be applied simultaneously with roof wind loads specified in other sections acting on areas of the roof not covered by the plan projection of solar collectors. For this case, unless otherwise noted, roof wind loads specified in other sections need not be applied on areas of the roof covered by the plan projection of solar collectors.
  2. Cases where the solar arrays have been removed or are absent. The following variables are defined for use in determining the design wind force applied to rooftop solar collectors/panels:

    A = the area of the solar panel element.
    d1 = horizontal distance measured from the edge of one panel to the building edge or to an adjacent array. The distance is perpendicular to the panel edge ignoring any rooftop equipment. See Figures 1609.5-1 or 1609.5-3, in ft.
    d2 = horizontal distance measured from the edge of one panel to the nearest edge in the next row of panels. See Figure 1609.5-1 or 1609.5-3, in ft.
    F = the design wind force normal to each panel determined in accordance with Section 1609.5.4
    h1 = height of a solar panel above the roof at the lower edge of the panel measured perpendicular to the surface of the roof, See Figures 1609.5-1 or 1609.5-3, in ft.
    h2 = height of a solar panel above the roof at the upper edge of the panel measured perpendicular to the surface of the roof, See Figures 1609.5-1 or 1609.5-3, in ft.
    Lp = panel chord dimension, in ft, for use with rooftop solar collectors as shown in Figures 1609.5-1 or 1609.5-3.
    θ = Angle of the roof surface, in degrees. See Figures 1609.5-1 or 1609.5-3.
    ω = Angle that the solar panel makes with the roof surface, in degrees. See Figures 1609.5-1 or 1609.5-3.
The design wind force determined in accordance with this section shall apply to rooftop solar collectors meeting the following conditions:
  1. Rooftop solar collectors are located on enclosed or partially enclosed buildings of any height.
  2. Panels are parallel to the roof surface, within a tolerance of 2°.
  3. The maximum height above the roof surface, h2, shall not exceed 10 inches (254 mm).
  4. A minimum gap of 0.25 inches (6.4 mm) shall be provided between all panels.
  5. The spacing of gaps between panels shall not exceed 6.7 ft (2.04 m).
  6. The array shall be located at least 2h2 from the nearest roof edge, gable ridge, or hip ridge.

The design wind force for rooftop solar collectors shall be determined by Equation 1609-1:

F = qhGCpγEγα A (lb) (N) (Equation 1609-1)

Where:

qh = velocity pressure at the mean roof height.
GCp = external pressure coefficient for Components and Cladding of roofs with respective roof zoning for the corresponding location on the roof, with the effective wind area, A, equal to that of the solar panel
γE = solar array edge factor for use with rooftop solar collectors.
γE = 1.5 for panels that are exposed and those within a distance 1.5(Lp) from the end of a row at an exposed edge of the array; γE = 1.0 elsewhere, as illustrated by the example array configuration shown in Figure 1609.5-3.

A panel is defined as exposed if d1 to the roof edge > 0.5h and one of the following applies:
  1. d1 to the adjacent array > 4 ft (1.22m)
  2. d2 to the next adjacent panel > 4 ft (1.22m)
γα = solar collector pressure equalization factor, from Figure 1609.5-2.


Alternatively, it shall be permitted to determine the normal design wind force in accordance with Equation 1609-2:

F = 40 A (Veff-ult/105)2 (lbs) (Equation 1609-2)


Veff-ult = the Effective Ultimate Design Wind Speed as determined from Figures 1609.3.2.1(a) through 1609.3.2.1(f), Figures 1609.3.2.2(a) through 1609.3.2.2(f), or Figures 1609.3.2.3(a) through 1609.3.2.3(f).


The force F shall be permitted to be applied to the centroid of the calculated pressure.
The design wind force determined in accordance with this section shall apply to rooftop solar collectors meeting the following conditions:
  1. Rooftop solar collectors are located on enclosed or partially enclosed buildings of any height.
  2. Flat, gable, or hip roofs with slopes, θ ≤ 7o.
  3. Panels installation shall conform to the following limitations:

    Lp ≤ 6.7 ft (2.04 m)
    ω ≤ 35o
    h1 ≤ 2 ft (0.61 m)
    h2 ≤ 4 ft (1.22 m)
  4. A minimum gap of 0.25 inches (6.4 mm) shall be provided between all panels.
  5. The spacing of gaps between panels shall not exceed 6.7 ft (2.04 m).
  6. The minimum horizontal clear distance between the panels and the edge of the roof shall be the larger of 2(h2hpt) and 4 ft. The design wind force for rooftop solar collectors shall be determined by Eq. 1609-3:

F = qhGCrn A (lb/ft2) (N/m2) (Equation 1609-3)

where

GCrn = γpγcγE (GCrn)nom (Equation 1609-4)


Where:

(GCrn)nom = nominal net pressure coefficient from Figure 1609.5-3.
γp = = parapet height factor.
hpt = mean parapet height above the adjacent roof surface (ft).
γc =
γE = 1.5 for panels that are exposed and those within a distance 1.5(Lp) from the end of a row at an exposed edge of the array; γE = 1.0 elsewhere, as illustrated by the example array configuration shown in Figure 1609.5-3.


     A panel is defined as exposed if d1 to the roof edge > 0.5h and one of the following applies:
  1. d1 to the adjacent array > max (4h2, 4 ft(1.22m))
  2. d2 to the next adjacent panel > max (4h2, 4 ft (1.22m))

     The force F shall be permitted to be applied to the centroid of the calculated pressure.

Figure 1609.5-1 Solar Collector Dimensions.


Figure 1609.5-2 Solar Collector Pressure Equalization Factor, γa, for enclosed and partially enclosed buildings of all heights.

Figure 1609.5-3 ROOFTOP SOLAR COLLECTORS FOR BUILDINGS OF ALL HEIGHTS WITH FLATROOFS OR GABLE OR HIP ROOFS WITH SLOPES LESS THAN 7° (SEE NOTES 1-3 BELOW)


Notes for Figure 1609.5-3:
  1. (GCrn) acts towards (+) and away (-) from the top surface of the panels.
  2. Linear interpolation shall be permitted for ω between 5o and 15o.
  3. Notation:

    An =
    An = normalized wind area for rooftop solar collectors
    Lb =
    WL = width of a building on its longest side in Figure 1609.5-3, in ft.
    Ws = width of a building on its shortest side in Figure 1609.5-2, in ft.

1609.5.4.3 Roof-Mounted Panels for All Other Conditions

AMENDMENT
This section has been amended at the state or city level.
The normal force on roof-mounted panels not regulated by Section 1609.5.4.1 or 1609.5.4.2 shall be determined by Equation 1609-5:

F = qh(GCp)CN A (lb) (N) (Equation 1609-5)

Where:

CN = pressure coefficients for monoslope free roofs from ASCE 7-10 Table 30.8-1 considering each elevated panel as a free roof surface in clear wind flow. The angle θ used for the determination of CN shall be measured as the angle of the panel with respect to the plane of the roof (ω in Figure 1609.5-1). Values of CN for forces on the panel may be taken as the Zone 1 coefficients.

Exception: Zone 2 coefficients for CN shall be used where the panel angle , ω, is greater than 7.5 degrees; panels are located a distance less than or equal to twice the roof height measured from a roof corner; and the parapet is greater than 24 inches (610 mm) in height above the roof.
GCp = the component and cladding external pressure coefficient for roofs for the roof zone corresponding to the location of the solar panel, and the effective wind area shall be that of the solar panel. The minimum magnitude of negative pressure values of GCp in Zone 1 shall be taken as -1.0.
A = the total area of the solar panel element.


Alternatively, it shall be permitted to determine the normal force in accordance with Equation 1609-6:

F = 100 A (Veff-ult/105)2 (lbs) (Equation 1609-6)

Where:
Veff-ult = the Effective Ultimate Design Wind Speed as determined from Figures 1609.3.2.1(a) through 1609.3.2.1(f), Figures 1609.3.2.2(a) through 1609.3.2.2(f), and Figures 1609.3.2.3(a) through 1609.3.2.3(f).


     When located in roof zone 2 or 3 as defined in ASCE 7, the force F shall be applied with an eccentricity equal to a third of the solar panel width.

1609.5.4.3.1 Additive Panel Wind Loads

AMENDMENT
This section has been amended at the state or city level.
The load on the panel shall be applied as point load anchorage reactions additive to the resultant of the pressure determined acting on the portion of the roof underlying the panel.

1609.5.4.4 Ballasted Panels

AMENDMENT
This section has been amended at the state or city level.
Panels that are ballasted for uplift resistance and tilted at an angle α of 10 degrees or more from a horizontal plane shall be designed to resist the force determined by Equation 1609-7:

(Equation 1609-7)

Where:
F = the normal force on each panel determined in accordance with Section 1609.5.4
α = the angle of the roof plane with respect to horizontal.
β = the angle of tilt of the panel with respect to the roof plane.
μ = the static friction coefficient between the panel base and its bearing surface.


     Alternatively, to resist uplift and sliding, ballasted panels that are tilted at an angle of less than 10 degrees from a horizontal plane shall each be ballasted to resist a force equal to 2 times the normal force on each panel determined in Sections 1609.5.4.1 or 1609.5.4.2. Ballasted panels that are tilted at an angle between 10 degrees to 25 degrees from a horizontal plane shall each be ballasted to resist a force equal to 8 times the normal force on each panel determined in Sections 1609.5.4.1 or 1609.5.4.2.

1609.5.4.5 Permeability

AMENDMENT
This section has been amended at the state or city level.
A reduction of load on the panels for permeability of the panel system shall not be permitted unless demonstrated by approved wind-tunnel testing or recognized documentation for the type of panel system being considered. Testing or documentation shall replicate the panel separation spacing and height above the roof.

1609.5.4.6 Shielding

AMENDMENT
This section has been amended at the state or city level.
A reduction of load on the panels for shielding provided by the roof or other obstruction shall not be permitted unless demonstrated by approved wind-tunnel testing or recognized documentation for the type of panel system being considered. Testing or documentation shall replicate the panel separation spacing and height above the roof.
The alternate wind design provisions in this section are simplifications of the ASCE 7 Directional Procedure.
As an alternative to ASCE 7 Chapters 27 and 30, the following provisions are permitted to be used to determine the wind effects on regularly shaped buildings, or other structures that are regularly shaped, which meet all of the following conditions:
  1. The building or other structure is less than or equal to 75 feet (22 860 mm) in height with a height-to-least-width ratio of 4 or less, or the building or other structure has a fundamental frequency greater than or equal to 1 hertz.
  2. The building or other structure is not sensitive to dynamic effects.
  3. The building or other structure is not located on a site for which channeling effects or buffeting in the wake of upwind obstructions warrant special consideration.
  4. The building shall meet the requirements of a simple diaphragm building as defined in ASCE 7 Section 26.2, where wind loads are only transmitted to the main windforce-resisting system (MWFRS) at the diaphragms.
  5. For open buildings, multispan gable roofs, stepped roofs, sawtooth roofs, domed roofs, roofs with slopes greater than 45 degrees (0.79 rad), solid free-standing walls and solid signs, and rooftop equipment, apply ASCE 7 provisions.
The following modifications shall be made to certain subsections in ASCE 7: in Section 1609.6.2, symbols and notations that are specific to this section are used in conjunction with the symbols and notations in ASCE 7 Section 26.3.

1609.6.2 Symbols and Notations

AMENDMENT
This section has been amended at the state or city level.
Coefficients and variables used in the alternative all-heights method equations are as follows:
Cnet = Net-pressure coefficient based on Kd [(G) (Cp) - (GCpi)], in accordance with Table 1609.6.2; determined using G = Gust effect factor for rigid structures in accordance with ASCE 7 Section 26.9 and Kd = Wind directionality factor in accordance with ASCE 7 Table 26-6.
Pnet = Design wind pressure to be used in determination of wind loads on buildings or other structures or their components and cladding, in psf (kN/m2).

TABLE 1609.6.2
NET PRESSURE COEFFICIENTS, Cneta, b
STRUCTURE OR
PART THEREOF
DESCRIPTION Cnet FACTOR
1. Main windforce-
resisting frames and
systems
Walls:
Enclosed
Partially enclosed
+ Internal
pressure
- Internal
pressure
+ Internal
pressure
- Internal
pressure
Windward wall
0.43
0.73
0.11
1.05
Leeward wall
-0.51
-0.21
-0.83
0.11
Sidewall
-0.66
-0.35
-0.97
-0.04
Parapet wall Windward
1.28
1.28
Leeward
-0.85
-0.85
Roofs:
Enclosed
Partially enclosed
Wind perpendicular to ridge
+ Internal
pressure
- Internal
pressure
+ Internal
pressure
- Internal
pressure
Leeward roof or flat roof
-0.66
-0.35
-0.97
-0.04
Windward roof slopes:
Slope < 2:12 (10°)
-1.09
-0.79
-1.41
-0.47
-0.28
0.02
-0.60
0.34
Slope = 4:12 (18°)
-0.73
-0.42
-1.04
-0.11
-0.05
0.25
-0.37
0.57
Slope = 5:12 (23°)
-0.58
-0.28
-0.90
0.04
0.03
0.34
-0.29
0.65
Slope = 6:12 (27°)
-0.47
-0.16
-0.78
0.15
0.06
0.37
-0.25
0.68
Slope = 7:12 (30°)
-0.37
-0.06
-0.68
0.25
0.07
0.37
-0.25
0.69
Slope = 9:12 (37°)
-0.27
0.04
-0.58
0.35
0.14
0.44
-0.18
0.76
Slope = 12:12 (45°)
0.14
0.44
-0.18
0.76
Wind parallel to ridge and flat roofs
-1.09
-0.79
-1.41
-0.47
Nonbuilding Structures: Chimneys, Tanks and Similar Structures:
 
h/D
1
7
25
Square (Wind normal to face)
0.99
1.07
1.53
Square (Wind on diagonal)
0.77
0.84
1.15
Hexagonal or Octagonal
0.81
0.97
1.13
Round
0.65
0.81
0.97
Open signs and lattice frameworks
Ratio of solid to gross area
 
< 0.1
0.1 to 0.29
0.3 to 0.7
Flat
1.45
1.30
1.16
Round
0.87
0.94
1.08
2. Components and
cladding not in areas
of discontinuity—
roofs and overhangs
Roof elements and slopes
Enclosed
Partially enclosed
Gable of hipped configurations (Zone 1)
 
 
Flat < Slope < 6:12 (27°) See ASCE 7 Figure 30.4-2B Zone 1
 
 
Positive
10 square feet or less
0.58
0.89
100 square feet or more
0.41
0.72
Negative
10 square feet or less
-1.00
-1.32
100 square feet or more
-0.92
-1.23
Overhang: Flat < Slope < 6:12 (27°) See ASCE 7 Figure 30.4-2A Zone 1
Negative
10 square feet or less
-1.45
100 square feet or more
-1.36
500 square feet or more
-0.94
6:12 (27°) < Slope < 12:12 (45°) See ASCE 7 Figure 30.4-2C Zone 1
Positive
10 square feet or less
0.92
1.23
100 square feet or more
0.83
1.15
Negative
10 square feet or less
-1.00
-1.32
100 square feet or more
-0.83
-1.15
Monosloped configurations (Zone 1)
Enclosed
Partially enclosed
Flat < Slope < 7:12 (30°) See ASCE 7 Figure 30.4-5B Zone 1
Positive
10 square feet or less
0.49
0.81
100 square feet or more
0.41
0.72
Negative
10 square feet or less
-1.26
-1.57
100 square feet or more
-1.09
-1.40
Tall flat-topped roofs h > 60 feet
Enclosed
Partially enclosed
Flat < Slope < 2:12 (10°) (Zone 1) See ASCE 7 Figure 30.8-1 Zone 1
Negative
10 square feet or less
-1.34
-1.66
500 square feet or more
-0.92
-1.23
3. Components and
cladding in areas of
discontinuities—
roofs and overhangs
Gable or hipped configurations at ridges, eaves and rakes (Zone 2)
Flat < Slope < 6:12 (27°) See ASCE 7 Figure 30.4-2B Zone 2
Positive
10 square feet or less
0.58
0.89
100 square feet or more
0.41
0.72
Negative
10 square feet or less
-1.68
-2.00
100 square feet or more
-1.17
-1.49
Overhang for Slope Flat < Slope < 6:12 (27°) See ASCE 7 Figure 30.4-2B Zone 2
Negative
10 square feet or less
-1.87
100 square feet or more
-1.87
6:12 (27°) < Slope < 12:12 (45°) Figure 30.4-2C
Enclosed
Partially enclosed
Positive
10 square feet or less
0.92
1.23
100 square feet or more
0.83
1.15
Negative
10 square feet or less
-1.17
-1.49
100 square feet or more
-1.00
-1.32
Overhang for 6:12 (27°) < Slope < 12:12 (45°) See ASCE 7 Figure 30.4-2C Zone 2
Negative
10 square feet or less
-1.70
500 square feet or more
-1.53
Monosloped configurations at ridges, eaves and rakes (Zone 2)
Flat < Slope < 7:12 (30°) See ASCE 7 Figure 30.4-5B Zone 2
Positive
10 square feet or less
0.49
0.81
100 square feet or more
0.41
0.72
Negative
10 square feet or less
-1.51
-1.83
100 square feet or more
-1.43
-1.74
Tall flat topped roofs h > 60 feet
Enclosed
Partially enclosed
Flat < Slope < 2:12 (10°) (Zone 2) See ASCE 7 Figure 30.8-1 Zone 2
Negative
10 square feet or less
-2.11
-2.42
500 square feet or more
-1.51
-1.83
Gable or hipped configurations at corners (Zone 3) See ASCE 7 Figure 30.4-2B Zone 3
Flat < Slope < 6:12 (27°)
Enclosed
Partially enclosed
Positive
10 square feet or less
0.58
0.89
100 square feet or more
0.41
0.72
Negative
10 square feet or less
-2.53
-2.85
100 square feet or more
-1.85
-2.17
Overhang for Slope Flat < Slope < 6:12 (27°) See ASCE 7 Figure 30.4-2B Zone 3
Negative
10 square feet or less
-3.15
100 square feet or more
-2.13
6:12 (27°) < 12:12 (45°) See ASCE 7 Figure 30.4-2C Zone 3
Positive
10 square feet or less
0.92
1.23
100 square feet or more
0.83
1.15
Negative
10 square feet or less
-1.17
-1.49
100 square feet or more
-1.00
-1.32
Overhang for 6:12 (27°) < Slope < 12:12 (45°)
Enclosed
Partially enclosed
Negative
10 square feet or less
-1.70
100 square feet or more
-1.53
Monosloped Configurations at corners (Zone 3) See ASCE 7 Figure 30.4-5B Zone 3
Flat < Slope < 7:12 (30°)
Positive
10 square feet or less
0.49
0.81
100 square feet or more
0.41
0.72
Negative
10 square feet or less
-2.62
-2.93
100 square feet or more
-1.85
-2.17
Tall flat topped roofs h > 60 feet
Enclosed
Partially enclosed
Flat < Slope < 2:12 (10°) (Zone 3) See ASCE 7 Figure 30.8-1 Zone 3
Negative
10 square feet or less
-2.87
-3.19
500 square feet or more
-2.11
-2.42
4. Components and
cladding not in areas of
discontinuity—
walls andparapets
Wall Elements: h ≤ 60 feet (Zone 4) ASCE 7 Figure 30.4-1
Enclosed
Partially enclosed
Positive
10 square feet or less
1.00
1.32
500 square feet or more
0.75
1.06
Negative
10 square feet or less
-1.09
-1.40
500 square feet or more
-0.83
-1.15
Wall Elements: h > 60 feet (Zone 4) ASCE 7 Figure 30.6-1
Positive
20 square feet or less
0.92
1.23
500 square feet or more
0.66
0.98
Negative
20 square feet or less
-0.92
-1.23
500 square feet or more
-0.75
-1.06
Parapet Walls
Positive
2.87
3.19
Negative
-1.68
-2.00
5. Components and
cladding in areas of
discontinuity—walls and
parapets
Wall elements: h ≤ 60 feet (Zone 5) Figure 30.4-1
Enclosed
Partially enclosed
Positive
10 square feet or less
1.00
1.32
500 square feet or more
0.75
1.06
Negative
10 square feet or less
-1.34
-1.66
500 square feet or more
-0.83
-1.15
Wall elements: h > 60 feet (Zone 4) ASCE 7 Figure 30.6-1
Positive
20 square feet or less
0.92
1.23
 
500 square feet or more
0.66
0.98
Negative
20 square feet or less
-1.68
-2.00
500 square feet or more
-1.00
-1.32
Parapet walls
Positive
3.64
3.95
Negative
-2.45
-2.76

For SI: 1 foot = 304.8 mm, 1 square foot = 0.0929m2, 1 degree = 0.0175 rad.
  1. Linear interpolation between values in the table is permitted.
  2. Some Cnet values have been grouped together. Less conservative results may be obtained by applying ASCE 7 provisions.

1609.6.3 Design Equations

AMENDMENT
This section has been amended at the state or city level.
When using the alternative all-heights method, the MWFRS, and components and cladding of every structure shall be designed to resist the effects of wind pressures on the building envelope in accordance with Equation 16-35.
Pnet = 0.00256Vult2KzCnetKzt(Kd /0.85) (Equation 16-35)
Design wind forces for the MWFRS shall not be less than 16 psf (0.77 kN/m2) multiplied by the area of the structure projected on a plane normal to the assumed wind direction (see ASCE 7 Section 27.4.7 for criteria). Design net wind pressure for components and cladding shall not be less than 16 psf (0.77 kN/m2) acting in either direction normal to the surface.
The MWFRS and the components and cladding of every building or other structure shall be designed for the pressures calculated using Equation 16-35.
The MWFRS shall be investigated for the torsional effects identified in ASCE 7 Figure 27.4-8.

1609.6.4.2 Determination of Kz, Kzt and Kd

AMENDMENT
This section has been amended at the state or city level.
Velocity pressure exposure coefficient, Kz, shall be determined in accordance with ASCE 7 Section 27.3.1. The topographic factor, Kzt, shall be determined in accordance with Section 1609.3.3. The wind directionality factor, Kd, shall be determined in accordance with Section 1609.3.4.
  1. For the windward side of a structure, Kzt and Kz shall be based on height z.
  2. For leeward and sidewalls, and for windward and leeward roofs, Kz shall be based on mean roof height h, and Kzt shall be based on height z.
For the design of the MWFRS and for components and cladding, the sum of the internal and external net pressure shall be based on the net pressure coefficient, Cnet.
  1. The pressure coefficient, Cnet, for walls and roofs shall be determined from Table 1609.6.2.
  2. Where Cnet has more than one value, the more severe wind load condition shall be used for design.
When using the alternative all-heights method, wind pressures shall be applied simultaneously on, and in a direction normal to, all building envelope wall and roof surfaces.
Wind pressure for each component or cladding element is applied as follows using Cnet values based on the effective wind area, A, contained within the zones in areas of discontinuity of width and/or length "a," "2a" or "4a" at: corners of roofs and walls; edge strips for ridges, rakes and eaves; or field areas on walls or roofs as indicated in figures in tables in ASCE 7 as referenced in Table 1609.6.2 in accordance with the following:
  1. Calculated pressures at local discontinuities acting over specific edge strips or corner boundary areas.
  2. Include "field" (Zone 1, 2 or 4, as applicable) pressures applied to areas beyond the boundaries of the areas of discontinuity.
  3. Where applicable, the calculated pressures at discontinuities (Zone 2 or 3) shall be combined with design pressures that apply specifically on rakes or eave overhangs.
Foundation walls and retaining walls shall be designed to resist lateral soil loads. Soil loads specified in Table 1610.1 shall be used as the minimum design lateral soil loads unless determined otherwise by a geotechnical investigation in accordance with Section 1803. Foundation walls and other walls in which horizontal movement is restricted at the top shall be designed for at-rest pressure. Retaining walls free to move and rotate at the top shall be permitted to be designed for active pressure. Design lateral pressure from surcharge loads shall be added to the lateral earth pressure load. Design lateral pressure shall be increased if soils at the site are expansive. Foundation walls shall be designed to support the weight of the full hydrostatic pressure of undrained backfill unless a drainage system is installed in accordance with Sections 1805.4.2 and 1805.4.3.
Exception: Foundation walls extending not more than 8 feet (2438 mm) below grade and laterally supported at the top by flexible diaphragms shall be permitted to be designed for active pressure.
TABLE 1610.1
LATERAL SOIL LOAD
DESCRIPTION OF BACKFILL MATERIALcUNIFIED SOIL
CLASSIFICATION
DESIGN LATERAL SOIL LOADa
(pound per square foot per foot of depth)
Active pressureAt-rest pressure
Well-graded, clean gravels; gravel-sand mixesGW3060
Poorly graded clean gravels; gravel-sand mixesGP3060
Silty gravels, poorly graded gravel-sand mixesGM4060
Clayey gravels, poorly graded gravel-and-clay mixesGC4560
Well-graded, clean sands; gravelly sand mixesSW3060
Poorly graded clean sands; sand-gravel mixesSP3060
Silty sands, poorly graded sand-silt mixesSM4560
Sand-silt clay mix with plastic finesSM-SC45100
Clayey sands, poorly graded sand-clay mixesSC60100
Inorganic silts and clayey siltsML45100
Mixture of inorganic silt and clayML-CL60100
Inorganic clays of low to medium plasticityCL60100
Organic silts and silt clays, low plasticityOLNote bNote b
Inorganic clayey silts, elastic siltsMHNote bNote b
Inorganic clays of high plasticityCHNote bNote b
Organic clays and silty claysOHNote bNote b
For SI: 1 pound per square foot per foot of depth = 0.157 kPa/m, 1 foot = 304.8 mm.
  1. Design lateral soil loads are given for moist conditions for the specified soils at their optimum densities. Actual field conditions shall govern. Submerged or saturated soil pressures shall include the weight of the buoyant soil plus the hydrostatic loads.
  2. Unsuitable as backfill material.
  3. The definition and classification of soil materials shall be in accordance with ASTM D 2487.
Each portion of a roof shall be designed to sustain the load of rainwater that will accumulate on it if the primary drainage system for that portion is blocked plus the uniform load caused by water that rises above the inlet of the secondary drainage system at its design flow. The design rainfall shall be based on the 100-year hourly rainfall rate indicated in Figure 1611.1 or on other rainfall rates determined from approved local weather data.
R = 5.2(ds + dh)(Equation 16-36)

For SI: R = 0.0098(ds + dh)

where:

dh=Additional depth of water on the undeflected roof above the inlet of secondary drainage system at its design flow (i.e., the hydraulic head), in inches (mm).
ds=Depth of water on the undeflected roof up to the inlet of secondary drainage system when the primary drainage system is blocked (i.e., the static head), in inches (mm).
R=Rain load on the undeflected roof, in psf (kN/m2). When the phrase "undeflected roof" is used, deflections from loads (including dead loads) shall not be considered when determining the amount of rain on the roof.
[P] FIGURE 1611.1
100-YEAR, 1-HOUR RAINFALL (INCHES) WESTERN UNITED STATES
For SI: 1 inch = 25.4 mm.
Source: National Weather Service, National Oceanic and Atmospheric Administration, Washington, DC.
[P] FIGURE 1611.1—continued
100-YEAR, 1-HOUR RAINFALL (INCHES) CENTRAL UNITED STATES
For SI: 1 inch = 25.4 mm.
Source: National Weather Service, National Oceanic and Atmospheric Administration, Washington, DC.
[P] FIGURE 1611.1—continued
100-YEAR, 1-HOUR RAINFALL (INCHES) EASTERN UNITED STATES
For SI: 1 inch = 25.4 mm.
Source: National Weather Service, National Oceanic and Atmospheric Administration, Washington, DC.
[P] FIGURE 1611.1—continued
100-YEAR, 1-HOUR RAINFALL (INCHES) ALASKA
For SI: 1 inch = 25.4 mm.
Source: National Weather Service, National Oceanic and Atmospheric Administration, Washington, DC.
[P] FIGURE 1611.1—continued
100-YEAR, 1-HOUR RAINFALL (INCHES) HAWAII
For SI: 1 inch = 25.4 mm.
Source: National Weather Service, National Oceanic and Atmospheric Administration, Washington, DC.
Susceptible bays of roofs shall be evaluated for ponding instability in accordance with Section 8.4 of ASCE 7.
Roofs equipped with hardware to control the rate of drainage shall be equipped with a secondary drainage system at a higher elevation that limits accumulation of water on the roof above that elevation. Such roofs shall be designed to sustain the load of rainwater that will accumulate on them to the elevation of the secondary drainage system plus the uniform load caused by water that rises above the inlet of the secondary drainage system at its design flow determined from Section 1611.1. Such roofs shall also be checked for ponding instability in accordance with Section 1611.2.
Within flood hazard areas as established in Section 1612.3, all new construction of buildings, structures and portions of buildings and structures, including substantial improvement and restoration of substantial damage to buildings and structures, shall be designed and constructed to resist the effects of flood hazards and flood loads. For buildings that are located in more than one flood hazard area, the provisions associated with the most restrictive flood hazard area shall apply.
To establish flood hazard areas, the applicable governing authority shall adopt a flood hazard map and supporting data. The flood hazard map shall include, at a minimum, areas of special flood hazard as identified by the Federal Emergency Management Agency in an engineering report entitled "The Flood Insurance Study for [INSERT NAME OF JURISDICTION]," dated [INSERT DATE OF ISSUANCE], as amended or revised with the accompanying Flood Insurance Rate Map (FIRM) and Flood Boundary and Floodway Map (FBFM) and related supporting data along with any revisions thereto. The adopted flood hazard map and supporting data are hereby adopted by reference and declared to be part of this section.
Where design flood elevations are not included in the flood hazard areas established in Section 1612.3, or where floodways are not designated, the building official is authorized to require the applicant to:
  1. Obtain and reasonably utilize any design flood elevation and floodway data available from a federal, state or other source; or
  2. Determine the design flood elevation and/or floodway in accordance with accepted hydrologic and hydraulic engineering practices used to define special flood hazard areas. Determinations shall be undertaken by a registered design professional who shall document that the technical methods used reflect currently accepted engineering practice.
In riverine flood hazard areas where design flood elevations are specified but floodways have not been designated, the applicant shall provide a floodway analysis that demonstrates that the proposed work will not increase the design flood elevation more than 1 foot (305 mm) at any point within the jurisdiction of the applicable governing authority.
The design and construction of buildings and structures located in flood hazard areas, including flood hazard areas subject to high-velocity wave action, shall be in accordance with Chapter 5 of ASCE 7 and with ASCE 24.
The following documentation shall be prepared and sealed by a registered design professional and submitted to the building official:
  1. For construction in flood hazard areas not subject to high-velocity wave action:
    1. The elevation of the lowest floor, including the basement, as required by the lowest floor elevation inspection in Section 110.3.3.
    2. For fully enclosed areas below the design flood elevation where provisions to allow for the automatic entry and exit of floodwaters do not meet the minimum requirements in Section 2.6.2.1 of ASCE 24, construction documents shall include a statement that the design will provide for equalization of hydrostatic flood forces in accordance with Section 2.6.2.2 of ASCE 24.
    3. For dry floodproofed nonresidential buildings, construction documents shall include a statement that the dry floodproofing is designed in accordance with ASCE 24.
  2. For construction in flood hazard areas subject to high-velocity wave action:
    1. The elevation of the bottom of the lowest horizontal structural member as required by the lowest floor elevation inspection in Section 110.3.3.
    2. Construction documents shall include a statement that the building is designed in accordance with ASCE 24, including that the pile or column foundation and building or structure to be attached thereto is designed to be anchored to resist flotation, collapse and lateral movement due to the effects of wind and flood loads acting simultaneously on all building components, and other load requirements of Chapter 16.
    3. For breakaway walls designed to have a resistance of more than 20 psf (0.96 kN/m2) determined using allowable stress design, construction documents shall include a statement that the breakaway wall is designed in accordance with ASCE 24.
Every structure, and portion thereof, including nonstructural components that are permanently attached to structures and their supports and attachments, shall be designed and constructed to resist the effects of earthquake motions in accordance with ASCE 7, excluding Chapter 14 and Appendix 11A. The seismic design category for a structure is permitted to be determined in accordance with Section 1613 or ASCE 7.
Exceptions:
  1. Detached one- and two-family dwellings, assigned to Seismic Design Category A, B or C, or located where the mapped short-period spectral response acceleration, SS, is less than 0.4 g.
  2. The seismic force-resisting system of wood-frame buildings that conform to the provisions of Section 2308 are not required to be analyzed as specified in this section.
  3. Agricultural storage structures intended only for incidental human occupancy.
  4. Structures that require special consideration of their response characteristics and environment that are not addressed by this code or ASCE 7 and for which other regulations provide seismic criteria, such as vehicular bridges, electrical transmission towers, hydraulic structures, buried utility lines and their appurtenances and nuclear reactors.
The following terms are defined in Chapter 2:
RISK-TARGETED MAXIMUM CONSIDERED EARTHQUAKE (MCER) GROUND MOTION RESPONSE ACCELERATION.
Seismic ground motion values shall be determined in accordance with this section.
The parameters Ss and S1 shall be determined from the 0.2 and 1-second spectral response accelerations shown on Figures 1613.3.1(1) through 1613.3.1(6). Where S1 is less than or equal to 0.04 and Ss is less than or equal to 0.15, the structure is permitted to be assigned to Seismic Design Category A. The parameters SS and S1 shall be, respectively, 1.5 and 0.6 for Guam and 1.0 and 0.4 for American Samoa.
FIGURE 1613.3.1(1) 
RISK-TARGETED MAXIMUM CONSIDERED EARTHQUAKE (MCER) GROUND MOTION RESPONSE ACCELERATIONS
FOR THE CONTERMINOUS UNITED STATES OF 0.2-SECOND SPECTRAL RESPONSE ACCELERATION
(5% OF CRITICAL DAMPING), SITE CLASS B


FIGURE 1613.3.1(2)
RISK-TARGETED MAXIMUM CONSIDERED EARTHQUAKE (MCER) GROUND MOTION RESPONSE ACCELERATIONS
FOR THE CONTERMINOUS UNITED STATES OF 1-SECOND SPECTRAL RESPONSE ACCELERATION
(5% OF CRITICAL DAMPING), SITE CLASS B

(continued)

FIGURE 1613.3.1(2)—continued
RISK-TARGETED MAXIMUM CONSIDERED EARTHQUAKE (MCER) GROUND MOTION RESPONSE ACCELERATIONS
FOR THE CONTERMINOUS UNITED STATES OF 1-SECOND SPECTRAL RESPONSE ACCELERATION
(5% OF CRITICAL DAMPING), SITE CLASS B


FIGURE 1613.3.1(3)
RISK-TARGETED MAXIMUM CONSIDERED EARTHQUAKE (MCER) GROUND MOTION RESPONSE ACCELERATIONS
FOR HAWAII OF 0.2- AND 1-SECOND SPECTRAL RESPONSE ACCELERATION
(5% OF CRITICAL DAMPING), SITE CLASS B


FIGURE 1613.3.1(4)
RISK-TARGETED MAXIMUM CONSIDERED EARTHQUAKE (MCER) GROUND MOTION RESPONSE ACCELERATIONS
FOR ALASKA OF 0.2-SECOND SPECTRAL RESPONSE ACCELERATION
(5% OF CRITICAL DAMPING), SITE CLASS B


FIGURE 1613.3.1(5)
RISK-TARGETED MAXIMUM CONSIDERED EARTHQUAKE (MCER) GROUND MOTION RESPONSE ACCELERATIONS
FOR ALASKA OF 1.0-SECOND SPECTRAL RESPONSE ACCELERATION
(5% OF CRITICAL DAMPING), SITE CLASS B


FIGURE 1613.3.1(6)
RISK-TARGETED MAXIMUM CONSIDERED EARTHQUAKE (MCER) GROUND MOTION RESPONSE ACCELERATIONS
FOR PUERTO RICO AND THE UNITED STATES VIRGIN ISLANDS OF 0.2- AND 1-SECOND SPECTRAL RESPONSE ACCELERATION (5% OF CRITICAL DAMPING), SITE CLASS B
Based on the site soil properties, the site shall be classified as Site Class A, B, C, D, E or F in accordance with Chapter 20 of ASCE 7. Where the soil properties are not known in sufficient detail to determine the site class, Site Class D shall be used unless the building official or geotechnical data determines Site Class E or F soils are present at the site.
The maximum considered earthquake spectral response acceleration for short periods, SMS, and at 1-second period, SM1, adjusted for site class effects shall be determined by Equations 16-37 and 16-38, respectively:
SMS = FaSs(Equation 16-37)
SM1= FvS1(Equation 16-38)
where:
Fa=Site coefficient defined in Table 1613.3.3(1).
Fv=Site coefficient defined in Table 1613.3.3(2).
SS=The mapped spectral accelerations for short periods as determined in Section 1613.3.1.
S1=The mapped spectral accelerations for a 1-second period as determined in Section 1613.3.1.
TABLE 1613.3.3(1)
VALUES OF SITE COEFFICIENT Faa
SITE CLASSMAPPED SPECTRAL RESPONSE ACCELERATION AT SHORT PERIOD
Ss 0.25Ss = 0.50Ss = 0.75Ss = 1.00Ss1.25
A0.80.80.80.80.8
B1.01.01.01.01.0
C1.21.21.11.01.0
D1.61.41.21.11.0
E2.51.71.20.90.9
FNote bNote bNote bNote bNote b
  1. Use straight-line interpolation for intermediate values of mapped spectral response acceleration at short period, Ss.
  2. Values shall be determined in accordance with Section 11.4.7 of ASCE 7.
TABLE 1613.3.3(2)
VALUES OF SITE COEFFICIENT FVa
SITE CLASSMAPPED SPECTRAL RESPONSE ACCELERATION AT 1-SECOND PERIOD
S1 0.1S1 = 0.2S1 = 0.3S1 = 0.4S1 ≥ 0.5
A0.80.80.80.80.8
B1.01.01.01.01.0
C1.71.61.51.41.3
D2.42.01.81.61.5
E3.53.22.82.42.4
FNote bNote bNote bNote bNote b
  1. Use straight-line interpolation for intermediate values of mapped spectral response acceleration at 1-second period, S1.
  2. Values shall be determined in accordance with Section 11.4.7 of ASCE 7.
Five-percent damped design spectral response acceleration at short periods, SDS, and at 1-second period, SD1, shall be determined from Equations 16-39 and 16-40, respectively:
(Equation 16-39)
(Equation 16-40)
where:
SMS=The maximum considered earthquake spectral response accelerations for short period as determined in Section 1613.3.3.
SM1=The maximum considered earthquake spectral response accelerations for 1-second period as determined in Section 1613.3.3.

1613.3.5 Determination of Seismic Design Category

AMENDMENT
This section has been amended at the state or city level.
Structures classified as Risk Category I, II or III that are located where the mapped spectral response acceleration parameter at 1-second period, S1, is greater than or equal to 0.75 shall be assigned to Seismic Design Category E. Structures classified as Risk Category IV that are located where the mapped spectral response acceleration parameter at 1-second period, S1, is greater than or equal to 0.75 shall be assigned to Seismic Design Category F. All other structures shall be assigned to a seismic design category based on their risk category and the design spectral response acceleration parameters, SDS and SD1, determined in accordance with Section 1613.3.4 or the site-specific procedures of ASCE 7. Each building and structure shall be assigned to the more severe seismic design category in accordance with Table 1613.3.5(1) or 1613.3.5(2), irrespective of the fundamental period of vibration of the structure, T.
TABLE 1613.3.5(1)
SEISMIC DESIGN CATEGORY BASED ON SHORT-PERIOD (0.2 second) RESPONSE ACCELERATION
VALUE OF SDS RISK CATEGORY
I or II III IV
SDS < 0.167g A A A
0.167g ≤ SDS < 0.33g B B C
0.33g ≤ SDS < 0.50g C C D
0.50g ≤ SDS < 0.60g C D D
0.60gSDS D D D

TABLE 1613.3.5(2)
SEISMIC DESIGN CATEGORY BASED ON 1-SECOND PERIOD RESPONSE ACCELERATION
VALUE OF SD1 RISK CATEGORY
I or II III IV
SD1 < 0.067g A A A
0.067g ≤ SD1 < 0.133g B B C
0.133g ≤ SD1 < 0.20g C C D
0.20g ≤ SD1 < 0.25g C D D
0.25gSD1 D D D
Where S1 is less than 0.75, the seismic design category is permitted to be determined from Table 1613.3.5(1) alone when all of the following apply:
  1. In each of the two orthogonal directions, the approximate fundamental period of the structure, Ta, in each of the two orthogonal directions determined in accordance with Section 12.8.2.1 of ASCE 7, is less than 0.8 Ts determined in accordance with Section 11.4.5 of ASCE 7.
  2. In each of the two orthogonal directions, the fundamental period of the structure used to calculate the story drift is less than Ts.
  3. Equation 12.8-2 of ASCE 7 is used to determine the seismic response coefficient, Cs.
  4. The diaphragms are rigid as defined in Section 12.3.1 of ASCE 7 or, for diaphragms that are flexible, the distances between vertical elements of the seismic force-resisting system do not exceed 40 feet (12 192 mm).
Where the alternate simplified design procedure of ASCE 7 is used, the seismic design category shall be determined in accordance with ASCE 7.
The provisions of Section 1613.4 shall be permitted as alternatives to the relevant provisions of ASCE 7.
Add the following exception to the end of Section 17.5.4.2 of ASCE 7:
Exception: For isolated structures designed in accordance with this standard, the structural system limitations including structural height limits in Table 12.2-1 for ordinary steel concentrically braced frames (OCBFs) as defined in Chapter 11 and ordinary moment frames (OMFs) as defined in Chapter 11 are permitted to be taken as 160 feet (48 768 mm) for structures assigned to Seismic Design Category D, E or F, provided that the following conditions are satisfied:
  1. The value of RI as defined in Chapter 17 is taken as 1.
  2. For OMFs and OCBFs, design is in accordance with AISC 341.
Ice-sensitive structures shall be designed for atmospheric ice loads in accordance with Chapter 10 of ASCE 7.

Section 1615 Tsunami Loads

AMENDMENT
This section has been amended at the state or city level.

1615.1 General

AMENDMENT
This section has been amended at the state or city level.
The design and construction of Risk Category III and IV buildings and structures and Risk Category II buildings taller than 75 feet, where located in the Tsunami Design Zones defined in the ASCE 7 Tsunami Design Geodatabase (version 2016-1.0), shall be in accordance with Chapter 6 of ASCE 7-16.

1615.2 Definitions

AMENDMENT
This section has been amended at the state or city level.
TSUNAMI DESIGN GEODATABASE. The ASCE database (version 2016-1.0) of Tsunami Design Zone maps and associated design data for the states of Alaska, California, Hawaii, Oregon, and Washington.

TSUNAMI DESIGN ZONE. An area identified on the Tsunami Design Zone map between the shoreline and the inundation limit, within which certain structures designated in Chapter 16 are designed for or protected from inundation."

Section 1615 1616 Structural Integrity

AMENDMENT
This section has been amended at the state or city level.
Any references to section 1615 in other parts of this code pertaining to structural integrity shall refer to section 1616 structural integrity.

1615.1 1616.1 General

AMENDMENT
This section has been amended at the state or city level.
High-rise buildings that are assigned to Risk Category III or IV shall comply with the requirements of this section. Frame structures shall comply with the requirements of Section 1616.3. Bearing wall structures shall comply with the requirements of Section 1616.4.

1615.2 1616.2 Definitions

AMENDMENT
This section has been amended at the state or city level.
The following words and terms are defined in Chapter 2:

1615.3 1616.3 Frame Structures

AMENDMENT
This section has been amended at the state or city level.
Frame structures shall comply with the requirements of this section.

1615.3.1 1616.3.1 Concrete Frame Structures

AMENDMENT
This section has been amended at the state or city level.
Frame structures constructed primarily of reinforced or prestressed concrete, either cast-in-place or precast, or a combination of these, shall conform to the requirements of ACI 318 Sections 7.13, 13.3.8.5, 13.3.8.6, 16.5, 18.12.6, 18.12.7 and 18.12.8 as applicable. Where ACI 318 requires that nonprestressed reinforcing or prestressing steel pass through the region bounded by the longitudinal column reinforcement, that reinforcing or prestressing steel shall have a minimum nominal tensile strength equal to two-thirds of the required one-way vertical strength of the connection of the floor or roof system to the column in each direction of beam or slab reinforcement passing through the column.

Exception: Where concrete slabs with continuous reinforcement having an area not less than 0.0015 times the concrete area in each of two orthogonal directions are present and are either monolithic with or equivalently bonded to beams, girders or columns, the longitudinal reinforcing or prestressing steel passing through the column reinforcement shall have a nominal tensile strength of one-third of the required one-way vertical strength of the connection of the floor or roof system to the column in each direction of beam or slab reinforcement passing through the column.

Frame structures constructed with a structural steel frame or a frame composed of open web steel joists, joist girders with or without other structural steel elements or a frame composed of composite steel or composite steel joists and reinforced concrete elements shall conform to the requirements of this section.

1615.3.2.1 1616.3.2.1 Columns

AMENDMENT
This section has been amended at the state or city level.
Each column splice shall have the minimum design strength in tension to transfer the design dead and live load tributary to the column between the splice and the splice or base immediately below.

1615.3.2.2 1616.3.2.2 Beams

AMENDMENT
This section has been amended at the state or city level.
End connections of all beams and girders shall have a minimum nominal axial tensile strength equal to the required vertical shear strength for allowable stress design (ASD) or two-thirds of the required shear strength for load and resistance factor design (LRFD) but not less than 10 kips (45 kN). For the purpose of this section, the shear force and the axial tensile force need not be considered to act simultaneously.

Exception: Where beams, girders, open web joist and joist girders support a concrete slab or concrete slab on metal deck that is attached to the beam or girder with not less than 3/8-inch-diameter (9.5 mm) headed shear studs, at a spacing of not more than 12 inches (305 mm) on center, averaged over the length of the member, or other attachment having equivalent shear strength, and the slab contains continuous distributed reinforcement in each of two orthogonal directions with an area not less than 0.0015 times the concrete area, the nominal axial tension strength of the end connection shall be permitted to be taken as half the required vertical shear strength for ASD or one-third of the required shear strength for LRFD, but not less than 10 kips (45 kN).

1615.4 1616.4 Bearing Wall Structures

AMENDMENT
This section has been amended at the state or city level.
Bearing wall structures shall have vertical ties in all load-bearing walls and longitudinal ties, transverse ties and perimeter ties at each floor level in accordance with this section and as shown in Figure 1616.4.
FIGURE 1616.4
LONGITUDINAL, PERIMETER, TRANSVERSE AND VERTICAL TIES

1615.4.1 1616.4.1 Concrete Wall Structures

AMENDMENT
This section has been amended at the state or city level.
Precast bearing wall structures constructed solely of reinforced or prestressed concrete, or combinations of these shall conform to the requirements of Sections 7.13, 13.3.8.5 and 16.5 of ACI 318.

1615.4.2 1616.4.2 Other Bearing Wall Structures

AMENDMENT
This section has been amended at the state or city level.
Ties in bearing wall structures other than those covered in Section 1616.4.1 shall conform to this section.

1615.4.2.1 1616.4.2.1 Longitudinal Ties

AMENDMENT
This section has been amended at the state or city level.
Longitudinal ties shall consist of continuous reinforcement in slabs; continuous or spliced decks or sheathing; continuous or spliced members framing to, within or across walls; or connections of continuous framing members to walls. Longitudinal ties shall extend across interior load-bearing walls and shall connect to exterior load-bearing walls and shall be spaced at not greater than 10 feet (3038 mm) on center. Ties shall have a minimum nominal tensile strength, TT, given by Equation 16-41. For ASD the minimum nominal tensile strength shall be permitted to be taken as 1.5 times the allowable tensile stress times the area of the tie.
TT = w LS ≤ αTS(Equation 16-41)

where:

L=The span of the horizontal element in the direction of the tie, between bearing walls, feet (m).
w=The weight per unit area of the floor or roof in the span being tied to or across the wall, psf (N/m2).
S=The spacing between ties, feet (m).
αT=A coefficient with a value of 1,500 pounds per foot (2.25 kN/m) for masonry bearing wall structures and a value of 375 pounds per foot (0.6 kN/m) for structures with bearing walls of cold-formed steel light-frame construction.

1615.4.2.2 1616.4.2.2 Transverse Ties

AMENDMENT
This section has been amended at the state or city level.
Transverse ties shall consist of continuous reinforcement in slabs; continuous or spliced decks or sheathing; continuous or spliced members framing to, within or across walls; or connections of continuous framing members to walls. Transverse ties shall be placed no farther apart than the spacing of load-bearing walls. Transverse ties shall have minimum nominal tensile strength TT, given by Equation 16-41. For ASD the minimum nominal tensile strength shall be permitted to be taken as 1.5 times the allowable tensile stress times the area of the tie.

1615.4.2.3 1616.4.2.3 Perimeter Ties

AMENDMENT
This section has been amended at the state or city level.
Perimeter ties shall consist of continuous reinforcement in slabs; continuous or spliced decks or sheathing; continuous or spliced members framing to, within or across walls; or connections of continuous framing members to walls. Ties around the perimeter of each floor and roof shall be located within 4 feet (1219 mm) of the edge and shall provide a nominal strength in tension not less than Tp, given by Equation 16-42. For ASD the minimum nominal tensile strength shall be permitted to be taken as 1.5 times the allowable tensile stress times the area of the tie.
Tp= 200w ≤βT(Equation 16-42)

For SI: Tp= 90.7w βT

where:

w=As defined in Section 1616.4.2.1.
βT=A coefficient with a value of 16,000 pounds (7200 kN) for structures with masonry bearing walls and a value of 4,000 pounds (1300 kN) for structures with bearing walls of cold-formed steel light-frame construction.

1615.4.2.4 1616.4.2.4 Vertical Ties

AMENDMENT
This section has been amended at the state or city level.
Vertical ties shall consist of continuous or spliced reinforcing, continuous or spliced members, wall sheathing or other engineered systems. Vertical tension ties shall be provided in bearing walls and shall be continuous over the height of the building. The minimum nominal tensile strength for vertical ties within a bearing wall shall be equal to the weight of the wall within that story plus the weight of the diaphragm tributary to the wall in the story below. No fewer than two ties shall be provided for each wall. The strength of each tie need not exceed 3,000 pounds per foot (450 kN/m) of wall tributary to the tie for walls of masonry construction or 750 pounds per foot (140 kN/m) of wall tributary to the tie for walls of cold-formed steel light-frame construction.