ADOPTS WITH AMENDMENTS:

International Fire Code 2018 (IFC 2018)

Part I — Administrative

Part II — General Safety Provisions

Part III — Building and Equipment Design Features

Part IV — Special Occupancies and Operations

Part V — Hazardous Materials

Part VI — Referenced Standards

Part VII — Appendices

Heads up: There are no amended sections in this chapter.

User note:

About this chapter: Chapter 27 provides requirements that are intended to control hazards associated with the manufacture of electrical circuit boards or microchips, commonly called semiconductors. Though the finished product possesses no unusual hazards, materials commonly associated with semiconductor manufacturing are often quite hazardous and include flammable liquids, pyrophoric and flammable gases, toxic substances and corrosives. The requirements of this chapter are concerned with both life safety and property protection. However, the fire code official should recognize that the risk of extraordinary property damages is far more common than the risk of personal injuries from fire. Section 415.11 of the International Building Code® also addresses these facilities that are classified as Group H-5 occupancies.

Semiconductor fabrication facilities and comparable research and development areas classified as Group H-5 shall comply with this chapter and the International Building Code. The use, storage and handling of hazardous materials in Group H-5 shall comply with this chapter, other applicable provisions of this code and the International Building Code.
The requirements set forth in this chapter are requirements specific only to Group H-5 and shall be applied as exceptions or additions to applicable requirements set forth elsewhere in this code.
Where a material poses multiple hazards, all hazards shall be addressed in accordance with Section 5001.1.
Existing buildings and existing fabrication areas shall comply with this chapter, except that transportation and handling of HPM in corridors and enclosures for stairways and ramps shall be allowed where in compliance with Section 2705.3.2 and the International Building Code.

Permits shall be required as set forth in Section 105.6.

An emergency control station shall be provided in accordance with Sections 2703.1.1 through 2703.1.3.
The emergency control station shall be located on the premises at an approved location outside the fabrication area.
Trained personnel shall continuously staff the emergency control station.

The emergency control station shall receive signals from emergency equipment and alarm and detection systems. Such emergency equipment and alarm and detection systems shall include, but not be limited to, the following where such equipment or systems are required to be provided either in this chapter or elsewhere in this code:

  1. Automatic sprinkler system alarm and monitoring systems.
  2. Manual fire alarm systems.
  3. Emergency alarm systems.
  4. Gas detection systems.
  5. Smoke detection systems.
  6. Emergency power systems.
  7. Automatic detection and alarm systems for pyrophoric liquids and Class 3 water-reactive liquids required by Section 2705.2.3.4.
  8. Exhaust ventilation flow alarm devices for pyrophoric liquids and Class 3 water-reactive liquids and cabinet exhaust ventilation systems required by Section 2705.2.3.4.
Systems, equipment and processes shall be in accordance with Sections 2703.2.1 through 2703.2.3.2.
Systems, equipment and processes shall include, but not be limited to, containers, cylinders, tanks, piping, tubing, valves and fittings.
In addition to the requirements in Section 2703.2, systems, equipment and processes shall comply with Section 5003.2, other applicable provisions of this code, the International Building Code and the International Mechanical Code.
In addition to the requirements in Section 2703.2, HPM supply piping and tubing for HPM gases and liquids shall comply with this section.
The requirements set forth in Section 5003.2.2.2 shall apply to supply piping and tubing for HPM gases and liquids.
Supply piping and tubing for HPM gases and liquids having a health-hazard ranking of 3 or 4 shall be welded throughout, except for connections located within a ventilation enclosure if the material is a gas, or an approved method of drainage or containment provided for connections if the material is a liquid.
Construction of semiconductor fabrication facilities shall be in accordance with Sections 2703.3.1 through 2703.3.9.
Construction and location of fabrication areas shall comply with the International Building Code.
Cabinets in fabrication areas containing pyrophoric liquids or Class 3 water-reactive liquids in containers or in amounts greater than 1/2 gallon (2 L) shall comply with Section 2705.2.3.4.
An emergency plan shall be established as set forth in Section 403.7.1.
Maintenance of equipment, machinery and processes shall comply with Section 5003.2.6.
Areas shall be secured in accordance with Section 5003.9.2.
Electrical wiring and equipment in HPM facilities shall comply with Sections 2703.7.1 through 2703.7.3.
Electrical wiring and equipment in fabrication areas shall comply with NFPA 70.

Electrical equipment and devices within 5 feet (1524 mm) of workstations in which flammable or pyrophoric gases or flammable liquids are used shall comply with NFPA 70 for Class I, Division 2 hazardous locations. Workstations shall not be energized without adequate exhaust ventilation in accordance with Section 2703.14.

Exception: Class I, Division 2 hazardous electrical equipment is not required where the air removal from the workstation or dilution will prevent the accumulation of flammable vapors and fumes on a continuous basis.

An approved automatic sprinkler system shall be provided in accordance with Sections 2703.10.1 through 2703.10.5 and Chapter 9.
The design of the sprinkler system in the area shall take into consideration the spray pattern and the effect on the equipment.

A sprinkler head shall be installed within each branch exhaust connection or individual plenums of workstations of combustible construction. The sprinkler head in the exhaust connection or plenum shall be located not more than 2 feet (610 mm) from the point of the duct connection or the connection to the plenum. Where necessary to prevent corrosion, the sprinkler head and connecting piping in the duct shall be coated with approved or listed corrosion-resistant materials. Access to the sprinkler head shall be provided for periodic inspection.

Exceptions:

  1. Approved alternative automatic fire-extinguishing systems are allowed. Activation of such systems shall deactivate the related processing equipment.
  2. Process equipment that operates at temperatures exceeding 932°F (500°C) and is provided with automatic shutdown capabilities for hazardous materials.
  3. Exhaust ducts 10 inches (254 mm) or less in diameter from flammable gas storage cabinets that are part of a workstation.
  4. Ducts listed or approved for use without internal automatic sprinkler protection.

Where the horizontal surface of a combustible tool is obstructed from ceiling sprinkler discharge, automatic sprinkler protection that covers the horizontal surface of the tool shall be provided.

Exceptions:

  1. An automatic gaseous fire-extinguishing local surface application system shall be allowed as an alternative to sprinklers. Gaseous-extinguishing systems shall be actuated by infrared (IR) or ultraviolet/infrared (UV/IR) optical detectors.
  2. Tools constructed of materials that are listed as Class 1 or Class 2 in accordance with UL 2360 or approved for use without internal fire-extinguishing system protection.

An approved automatic sprinkler system shall be provided in gas cabinets and exhausted enclosures containing HPM compressed gases.

Exception: Gas cabinets located in an HPM room other than those cabinets containing pyrophoric gases.

An approved automatic sprinkler system shall be provided in exhaust ducts conveying gases, vapors, fumes, mists or dusts generated from HPM in accordance with this section and the International Mechanical Code.

An approved automatic sprinkler system shall be provided in metallic and noncombustible nonmetallic exhaust ducts where all of the following conditions apply:

  1. Where the largest cross-sectional diameter is equal to or greater than 10 inches (254 mm).
  2. The ducts are within the building.
  3. The ducts are conveying flammable gases, vapors or fumes.

An approved automatic sprinkler system shall be provided in combustible nonmetallic exhaust ducts where the largest cross-sectional diameter of the duct is equal to or greater than 10 inches (254 mm).

Exceptions:

  1. Ducts listed or approved for applications without automatic sprinkler system protection.
  2. Ducts not more than 12 feet (3658 mm) in length installed below ceiling level.
Automatic sprinklers installed in exhaust duct systems shall be hydraulically designed to provide 0.5 gallons per minute (gpm) (1.9 L/min) over an area derived by multiplying the distance between the sprinklers in a horizontal duct by the width of the duct. Minimum discharge shall be 20 gpm (76 L/min) per sprinkler from the five hydraulically most remote sprinklers.
Automatic sprinklers shall be installed at 12-foot (3658 mm) intervals in horizontal ducts and at changes in direction. In vertical runs, automatic sprinklers shall be installed at the top and at alternate floor levels.
A separate indicating control valve shall be provided for sprinklers installed in exhaust ducts.
Drainage shall be provided to remove sprinkler water discharged in exhaust ducts.
Where corrosive atmospheres exist, exhaust duct sprinklers and pipe fittings shall be manufactured of corrosion-resistant materials or coated with approved materials.
Access to sprinklers in exhaust ducts shall be provided for periodic inspection and maintenance.
Automatic sprinkler systems shall be electrically supervised and provided with alarms in accordance with Chapter 9. Automatic sprinkler system alarm and supervisory signals shall be transmitted to the emergency control station.
A manual fire alarm system shall be installed throughout buildings containing a Group H-5 occupancy. Activation of the alarm system shall initiate a local alarm and transmit a signal to the emergency control station. Manual fire alarm systems shall be designed and installed in accordance with Section 907.
Emergency alarm systems shall be provided in the areas indicated in Sections 2703.12.1.1 through 2703.12.1.3.
An approved emergency alarm system shall be provided in service corridors, with not less than one alarm device in the service corridor.
An approved emergency telephone system, local alarm manual pull stations, or other approved alarm-initiating devices are allowed to be used as emergency alarm-initiating devices.
Activation of the emergency alarm system shall sound a local alarm and transmit a signal to the emergency control station.
A gas detection system complying with Section 916 shall be provided for HPM gases where the physiological warning threshold level of the gas is at a higher level than the accepted permissible exposure limit (PEL) for the gas and for flammable gases in accordance with Sections 2703.13.1 through 2703.13.2.2.
A gas detection system shall be provided in the areas identified in Sections 2703.13.1.1 through 2703.13.1.4.
A gas detection system shall be provided in HPM rooms where HPM gas is used in the room.

Where HPM gases are transported in piping placed within the space defined by the walls of a corridor and the floor or roof above the corridor, a gas detection system shall be provided where piping is located and in the corridor.

Exception: A gas detection system is not required for occasional transverse crossings of the corridors by supply piping that is enclosed in a ferrous pipe or tube for the width of the corridor.

The gas detection system shall be capable of monitoring the room, area or equipment in which the HPM gas is located at or below all the following gas concentrations:

  1. Immediately dangerous to life and health (IDLH) values where the monitoring point is within an exhausted enclosure, ventilated enclosure or gas cabinet.
  2. Permissible exposure limit (PEL) levels where the monitoring point is in an area outside an exhausted enclosure, ventilated enclosure or gas cabinet.
  3. For flammable gases, the monitoring detection threshold level shall be vapor concentrations in excess of 25 percent of the lower flammable limit (LFL) where the monitoring is within or outside an exhausted enclosure, ventilated enclosure or gas cabinet.
  4. Except as noted in this section, monitoring for highly toxic and toxic gases shall also comply with Chapter 60.
The gas detection system shall initiate a local alarm and transmit a signal to the emergency control station when a short-term hazard condition is detected. The alarm shall be both visible and audible and shall provide warning both inside and outside the area where the gas is detected. The audible alarm shall be distinct from all other alarms.

The gas detection system shall automatically close the shutoff valve at the source on gas supply piping and tubing related to the system being monitored for which gas is detected when a short-term hazard condition is detected. Automatic closure of shutoff valves shall comply with the following:

  1. Where the gas-detection sampling point initiating the gas detection system alarm is within a gas cabinet or exhausted enclosure, the shutoff valve in the gas cabinet or exhausted enclosure for the specific gas detected shall automatically close.
  2. Where the gas-detection sampling point initiating the gas detection system alarm is within a room and compressed gas containers are not in gas cabinets or exhausted enclosure, the shutoff valves on all gas lines for the specific gas detected shall automatically close.
  3. Where the gas-detection sampling point initiating the gas detection system alarm is within a piping distribution manifold enclosure, the shutoff valve supplying the manifold for the compressed gas container of the specific gas detected shall automatically close.

Exception: Where the gas-detection sampling point initiating the gas detection system alarm is at the use location or within a gas valve enclosure of a branch line downstream of a piping distribution manifold, the shutoff valve for the branch line located in the piping distribution manifold enclosure shall automatically close.

Exhaust ventilation systems and materials for exhaust ducts utilized for the exhaust of HPM shall comply with Sections 2703.14.1 through 2703.14.3, other applicable provisions of this code, the International Building Code and the International Mechanical Code.

Exhaust ventilation systems shall be provided in the following locations in accordance with the requirements of this section and the International Building Code:

  1. Fabrication areas: Exhaust ventilation for fabrication areas shall comply with the International Building Code. The fire code official is authorized to require additional manual control switches.
  2. Workstations: A ventilation system shall be provided to capture and exhaust gases, fumes and vapors at workstations.
  3. Liquid storage rooms: Exhaust ventilation for liquid storage rooms shall comply with Section 5004.3.1 and the International Building Code.
  4. HPM rooms: Exhaust ventilation for HPM rooms shall comply with Section 5004.3.1 and the International Building Code.
  5. Gas cabinets: Exhaust ventilation for gas cabinets shall comply with Section 5003.8.6.2. The gas cabinet ventilation system is allowed to connect to a workstation ventilation system. Exhaust ventilation for gas cabinets containing highly toxic or toxic gases shall also comply with Chapter 60.
  6. Exhausted enclosures: Exhaust ventilation for exhausted enclosures shall comply with Section 5003.8.5.2. Exhaust ventilation for exhausted enclosures containing highly toxic or toxic gases shall also comply with Chapter 60.
  7. Gas rooms: Exhaust ventilation for gas rooms shall comply with Section 5003.8.4.2. Exhaust ventilation for gas rooms containing highly toxic or toxic gases shall also comply with Chapter 60.
  8. Cabinets containing pyrophoric liquids or Class 3 water-reactive liquids: Exhaust ventilation for cabinets in fabrication areas containing pyrophoric liquids or Class 3 water-reactive liquids shall be as required in Section 2705.2.3.4.
Exhaust ducts penetrating fire barriers constructed in accordance with Section 707 of the International Building Code or horizontal assemblies constructed in accordance with Section 711 of the International Building Code shall be contained in a shaft of equivalent fire-resistance-rated construction. Exhaust ducts shall not penetrate fire walls. Fire dampers shall not be installed in exhaust ducts.
Treatment systems for highly toxic and toxic gases shall comply with Chapter 60.
An emergency power system shall be provided in Group H-5 occupancies in accordance with Section 1203. The emergency power system shall supply power automatically to the electrical systems specified in Section 2703.15.1 when the normal supply system is interrupted.

Emergency power shall be provided for electrically operated equipment and connected control circuits for the following systems:

  1. HPM exhaust ventilation systems.
  2. HPM gas cabinet ventilation systems.
  3. HPM exhausted enclosure ventilation systems.
  4. HPM gas room ventilation systems.
  5. HPM gas detection systems.
  6. Emergency alarm systems.
  7. Manual fire alarm systems.
  8. Automatic sprinkler system monitoring and alarm systems.
  9. Automatic alarm and detection systems for pyrophoric liquids and Class 3 water-reactive liquids required in Section 2705.2.3.4.
  10. Flow alarm switches for pyrophoric liquids and Class 3 water-reactive liquids cabinet exhaust ventilation systems required in Section 2705.2.3.4.
  11. Electrically operated systems required elsewhere in this code or in the International Building Code applicable to the use, storage or handling of HPM.
Exhaust ventilation systems are allowed to be designed to operate at not less than one-half the normal fan speed on the emergency power system where it is demonstrated that the level of exhaust will maintain a safe atmosphere.
Sub-atmospheric pressure gas systems (SAGS) shall be in accordance with NFPA 318.
Storage of hazardous materials shall comply with Section 2703 and this section and other applicable provisions of this code.
Hazardous materials storage and the maximum quantities of hazardous materials in use and storage allowed in fabrication areas shall be in accordance with Sections 2704.2.1 through 2704.2.2.1.

Storage of HPM in fabrication areas shall be within approved or listed storage cabinets, gas cabinets, exhausted enclosures or within a workstation as follows:

  1. Flammable and combustible liquid storage cabinets shall comply with Section 5704.3.2.
  2. Hazardous materials storage cabinets shall comply with Section 5003.8.7.
  3. Gas cabinets shall comply with Section 5003.8.6. Gas cabinets for highly toxic or toxic gases shall also comply with Section 6004.1.2.
  4. Exhausted enclosures shall comply with Section 5003.8.5. Exhausted enclosures for highly toxic or toxic gases shall also comply with Section Section 6004.1.3.
  5. Workstations shall comply with Section 2705.2.3.

The aggregate quantities of hazardous materials stored or used in a single fabrication area shall be limited as specified in this section.

Exception: Fabrication areas containing quantities of hazardous materials not exceeding the maximum allowable quantities per control area established by Sections 5003.1.1, 5704.3.4 and 5704.3.5.

The maximum quantities of hazardous materials stored or used in a single fabrication area shall not exceed the quantities set forth in Table 2704.2.2.1.

TABLE 2704.2.2.1

QUANTITY LIMITS FOR HAZARDOUS MATERIALS IN A SINGLE FABRICATION AREA IN GROUP H-5a

HAZARD CATEGORYSOLIDS
(pounds/square foot)
LIQUIDS
(gallons/square foot)
GAS
(cubic feet @ NTP/square foot)
Physical-hazard materials
Combustible dustNote bNot ApplicableNot Applicable
Combustible fiber
Loose
Baled
Note b
Notes b and c
Not ApplicableNot Applicable
Combustible liquid
Class II
Class IIIA
Class IIIB
Combination Class I, II and IIIA
Not Applicable0.01
0.02
Not Limited
0.04
Not Applicable
Cryogenic gas
Flammable
Oxidizing
Not ApplicableNot ApplicableNote d
1.25
ExplosivesNote bNote bNote b
Flammable gas
Gaseous
Liquefied
Not ApplicableNot ApplicableNote d
Note d
Flammable liquid
Class IA
Class IB
Class IC
Combination Class IA, IB and IC
Combination Class I, II and IIIA
Not Applicable0.0025
0.025
0.025
0.025
0.04
Not Applicable
Flammable solid0.001Not ApplicableNot Applicable
Organic peroxide Class I
Class II
Class III
Class IV
Class V
Note b
Note b
0.025
0.1
Not Limited
Not Limited
Not ApplicableNot Applicable
Oxidizing gas
Gaseous
Liquefied
Combination of Gaseous and
Liquefied
Not ApplicableNot Applicable1.25
1.25
1.25
Oxidizer
Class 4
Class 3
Class 2
Class 1
Combination oxidizer Class 1, 2, 3
Note b
0.003
0.003
0.003
0.003
Note b
0.03
0.03
0.03
0.03
Not
Applicable
Pyrophoric0.010.00125Notes d and e
Unstable reactive
Class 4
Class 3
Class 2
Class 1
Note b
0.025
0.1
Not Limited
Note b
0.0025
0.01
Not Limited
Note b
Note b
Note b
Not Limited
Water reactive
Class 3
Class 2
Class 1
Note b
0.25
Not Limited
0.00125
0.025
Not Limited
Not
Applicable
Health-hazard materials
CorrosivesNot LimitedNot LimitedNot Limited
Highly toxicsNot LimitedNot LimitedNote d
ToxicsNot LimitedNot LimitedNote d

For SI: 1 pound per square foot = 4.882 kg/m2, 1 gallon per square foot = 40.7 L/m2, 1 cubic foot @ NTP/square foot = 0.305 m3 @ NTP/m2, 1 cubic foot = 0.02832 m3.

  1. Hazardous materials within piping shall not be included in the calculated quantities.
  2. Quantity of hazardous materials in a single fabrication area shall not exceed the maximum allowable quantities per control area in Tables 5003.1.1(1) and 5003.1.1(2).
  3. Densely packed baled cotton that complies with the packing requirements of ISO 8115 shall not be included in this material class.
  4. The aggregate quantity of flammable, pyrophoric, toxic and highly toxic gases shall not exceed the greater of 0.2 cubic feet at NTP/square foot or 9,000 cubic feet at NTP.
  5. The aggregate quantity of pyrophoric gases in the building shall not exceed the amounts set forth in Table 5003.8.2.
The indoor storage of hazardous materials outside of fabrication areas shall be in accordance with Sections 2704.3.1 through 2704.3.3.
The indoor storage of HPM in quantities greater than those listed in Sections 5003.1.1 and 5704.3.4 shall be in a room complying with the requirements of the International Building Code and this code for a liquid storage room, HPM room or gas room as appropriate for the materials stored.
The indoor storage of other hazardous materials shall comply with Sections 5001, 5003 and 5004 and other applicable provisions of this code.
Incompatible hazardous materials in storage shall be separated from each other in accordance with Section 5003.9.8.
The use and handling of hazardous materials shall comply with this section, Section 2703 and other applicable provisions of this code.
The use of hazardous materials in fabrication areas shall be in accordance with Sections 2705.2.1 through 2705.2.3.4.

The aggregate quantities of hazardous materials in a single fabrication area shall comply with Section 2704.2.2, and Table 2704.2.2.1. The quantity of HPM in use at a workstation shall not exceed the quantities listed in Table 2705.2.2.

TABLE 2705.2.2

MAXIMUM QUANTITIES OF HPM AT A WORKSTATIONd

HPM CLASSIFICATIONSTATEMAXIMUM QUANTITY
Flammable, highly toxic, combinedGasCombined aggregate volume of shall not exceed an internal
cylinder volume of 39.6 gallons or 5.29 cubic feet
FlammableLiquid15 gallonsa, b
Solid5 poundsa, b
CorrosiveGasCombined aggregate volume of shall not exceed an internal
cylinder volume of 39.6 gallons
or 5.29 cubic feet
LiquidUse-open system: 25 gallonsb
Use-closed system: 150 gallonsb, e
Solid20 poundsa, b
Highly toxicLiquid15 gallonsa, b
Solid5 poundsa, b
OxidizerGasCombined aggregate volume of shall not exceed an internal
cylinder volume of 39.6 gallons
or 5.29 cubic feet
LiquidUse-open system: 12 gallonsb
Use-closed system: 60 gallonsb
Solid20 poundsa, b
PyrophoricLiquid0.5 gallonc, f
Solid4.4 poundsc, f
ToxicLiquidUse-open system: 15 gallonsb
Use-closed system: 60 gallonsb
Solid5 poundsa, b
Unstable reactive Class 3Liquid0.5 gallona, b
Solid5 poundsa, b
Water-reactive Class 3Liquid0.5 gallonc, f
SolidSee Table 2704.2.2.1

For SI: 1 pound = 0.454 kg, 1 gallon = 3.785 L.

  1. Maximum allowable quantities shall be increased 100 percent for closed system operations. Where Note b applies, the increase for both notes shall be allowed.
  2. Quantities shall be allowed to be increased 100 percent where workstations are internally protected with an approved automatic fire-extinguishing or suppression system complying with Chapter 9. Where Note a applies, the increase for both notes shall be allowed. Where Note e applies, the maximum increase allowed for both Notes b and e shall not exceed 100 percent.
  3. Allowed only in workstations that are internally protected with an approved automatic fire-extinguishing or fire protection system complying with Chapter 9 and compatible with the reactivity of materials in use at the workstation.
  4. The quantity limits apply only to materials classified as HPM.
  5. Quantities shall be allowed to be increased 100 percent for nonflammable, noncombustible corrosive liquids where the materials of construction for workstations are listed or approved for use without internal fire-extinguishing or suppression system protection. Where Note b applies, the maximum increase allowed for both Notes b and e shall not exceed 100 percent.
  6. A maximum quantity of 5.3 gallons of liquids and 44 pounds of total liquids and solids shall be allowed at a workstation where conditions are in accordance with Section 2705.2.3.4.
Workstations in fabrication areas shall be in accordance with Sections 2705.2.3.1 through 2705.2.3.4.
Workstations in fabrication areas shall be constructed of materials compatible with the materials used and stored at the workstation. The portion of the workstation that serves as a cabinet for HPM gases, Class I flammable liquids or Class II or Class IIIA combustible liquids shall be noncombustible and, if of metal, shall be not less than 0.0478-inch (18 gage) (1.2 mm) steel.

Vessels containing hazardous materials located in or connected to a workstation shall be protected as follows:

  1. HPM: Vessels containing HPM shall be protected from physical damage and shall not project from the workstation.
  2. Hazardous cryogenic fluids, gases and liquids: Hazardous cryogenic fluid, gas and liquid vessels located within a workstation shall be protected from seismic forces in an approved manner in accordance with the International Building Code.
  3. Compressed gases: Protection for compressed gas vessels shall also comply with Section 5303.5.
  4. Cryogenic fluids: Protection for cryogenic fluid vessels shall also comply with Section 5503.5.

Each workstation utilizing HPM liquids shall have all of the following:

  1. Drainage piping systems connected to a compatible system for disposition of such liquids.
  2. The work surface provided with a slope or other means for directing spilled materials to the containment or drainage system.
  3. An approved means of containing or directing spilled or leaked liquids to the drainage system.

Pyrophoric liquids and Class 3 water-reactive liquids in containers greater than 0.5-gallon (2 L) but not exceeding 5.3-gallon (20 L) capacity and pyrophoric solids in containers greater than 4.4 pounds (2 kg) but not exceeding 44 pounds (20 kg) shall be allowed at workstations where located inside cabinets and the following conditions are met:

  1. Maximum amount per cabinet: The maximum amount per cabinet shall be limited to 5.3 gallons (20 L) of liquids and 44 pounds (20 kg) of total liquids and solids.
  2. Cabinet construction: Cabinets shall be constructed in accordance with the following:

    1. 2.1. Cabinets shall be constructed of not less than 0.097-inch (2.5 mm) (12 gage) steel.
    2. 2.2. Cabinets shall be permitted to have self-closing limited access ports or noncombustible windows that provide access to equipment controls.
    3. 2.3. Cabinets shall be provided with self- or manual-closing doors. Manual-closing doors shall be equipped with a door switch that will initiate local audible and visual alarms when the door is in the open position.
  3. Cabinet exhaust ventilation system: An exhaust ventilation system shall be provided for cabinets and shall comply with the following:

    1. 3.1. The system shall be designed to operate at a negative pressure in relation to the surrounding area.
    2. 3.2. The system shall be equipped with monitoring equipment to ensure that required exhaust flow or static pressure is provided.
    3. 3.3. Low-flow or static pressure conditions shall send an alarm to the on-site emergency control station. The alarm shall be both visual and audible.
  4. Cabinet spill containment: Spill containment shall be provided in each cabinet, with the spill containment capable of holding the contents of the aggregate amount of liquids in containers in each cabinet.
  5. Valves: Valves in supply piping between the product containers in the cabinet and the workstation served by the containers shall fail in the closed position upon power failure, loss of exhaust ventilation and upon actuation of the fire control system.
  6. Fire detection system: Each cabinet shall be equipped with an automatic fire detection system complying with the following conditions:

    1. 6.1. Automatic detection system: UV/IR, high-sensitivity smoke detection (HSSD) or other approved detection systems shall be provided inside each cabinet.
    2. 6.2. Automatic shutoff: Activation of the detection system shall automatically close the shutoff valves at the source on the liquid supply.
    3. 6.3. Alarms and signals: Activation of the detection system shall initiate a local alarm within the fabrication area and transmit a signal to the emergency control station. The alarms and signals shall be both visual and audible.
The transportation and handling of hazardous materials shall comply with Sections 2705.3.1 through 2705.3.4.1 and other applicable provisions of this code.
Corridors and enclosures for exit stairways and ramps in new buildings or serving new fabrication areas shall not contain HPM, except as permitted in corridors by Section 415.11.6.4 of the International Building Code and Section 2705.3.2 of this code.
Transport in corridors and enclosures for stairways and ramps shall be in accordance with Sections 2705.3.2.1 through 2705.3.3.
Where existing fabrication areas are altered or modified in existing buildings, HPM is allowed to be transported in existing corridors where such corridors comply with Section 5003.10 of this code and Section 415.11.2 of the International Building Code.
Nonproduction HPM is allowed to be transported in corridors and enclosures for stairways and ramps where utilized for maintenance, lab work and testing when the transportation is in accordance with Section 5003.10.
Where a new fabrication area is constructed, a service corridor shall be provided where it is necessary to transport HPM from a liquid storage room, HPM room, gas room or from the outside of a building to the perimeter wall of a fabrication area. Service corridors shall be designed and constructed in accordance with the International Building Code.
Carts and trucks used to transport HPM in corridors and enclosures for stairways and ramps shall comply with Section 5003.10.3.
Carts and trucks shall be marked to indicate the contents.
UpCodes Premium
Leverage the most sophisticated code compliance platform.
TRY FREE FOR TWO WEEKS VISIT PRICING