Reporting of emergencies, coordination with emergency response forces, emergency plans and procedures for managing or responding to emergencies shall comply with the provisions of this section.
Exception: Firms that have approved on-premises fire-fighting organizations and that are in compliance with approved procedures for fire reporting.

401.2 Approval

ILLUSTRATION
Where required by this code, fire safety plans, emergency procedures and employee training programs shall be approved by the fire code official.
Notification of emergency responders shall be in accordance with Sections 401.3.1 through 401.3.3.
In the event an unwanted fire occurs on a property, the owner or occupant shall immediately report such condition to the fire department.
Upon activation of a fire alarm signal, employees or staff shall immediately notify the fire department.
A person shall not, by verbal or written directive, require any delay in the reporting of a fire to the fire department.
In the event an unwanted fire is detected in a building or a fire alarm activates, the emergency plan shall be implemented.
A person shall not give, signal or transmit a false alarm.
The sounding of a fire alarm signal and the carrying out of an emergency evacuation drill in accordance with the provisions of Section 405 shall be allowed.
Evacuations made necessary by the unplanned activation of a fire alarm system or by any other emergency shall not be substituted for a required evacuation drill.
It shall be unlawful to interfere with, attempt to interfere with, conspire to interfere with, obstruct or restrict the mobility of or block the path of travel of a fire department emergency vehicle in any way, or to interfere with, attempt to interfere with, conspire to interfere with, obstruct or hamper any fire department operation.
The following terms are defined in Chapter 2 :
When, in the opinion of the fire code official, it is essential for public safety in a place of assembly or any other place where people congregate, because of the number of persons, or the nature of the performance, exhibition, display, contest or activity, the owner, agent or lessee shall provide one or more fire watch personnel, as required and approved, to remain on duty during the times such places are open to the public, or when such activity is being conducted.
Fire watch personnel shall keep diligent watch for fires, obstructions to means of egress and other hazards during the time such place is open to the public or such activity is being conducted and take prompt measures for remediation of hazards, extinguishment of fires that occur and assist in the evacuation of the public from the structures.
In other than Group A or E occupancies, where the fire code official determines that an indoor or outdoor gathering of persons has an adverse impact on public safety through diminished access to buildings, structures, fire hydrants and fire apparatus access roads or where such gatherings adversely affect public safety services of any kind, the fire code official shall have the authority to order the development of, or prescribe a plan for, the provision of an approved level of public safety.
The public safety plan, where required by Section 403.2, shall address such items as emergency vehicle ingress and egress, fire protection, emergency egress or escape routes, emergency medical services, public assembly areas and the directing of both attendees and vehicles (including the parking of vehicles), vendor and food concession distribution, and the need for the presence of law enforcement, and fire and emergency medical services personnel at the event.

403.3 Crowd Managers

AMENDMENT
This section has been amended at the state or city level.

403.3 Crowd Managers

AMENDMENT
This section has been amended at the state or city level.
Crowd managers shall be provided as set forth in 408.2.3 of this Code.

(Effective January 1, 2014)
Fire safety, evacuation and lockdown plans and associated drills shall comply with the requirements of Sections 404.2 through 404.5.1.

404.2 Where Required

AMENDMENT
This section has been amended at the state or city level.

404.2 Where Required

AMENDMENT
This section has been amended at the state or city level.
An approved fire safety and evacuation plan shall be prepared and maintained for the following occupancies and buildings.
  1. Group A, other than Group A occupancies used exclusively for purposes of religious worship that have an occupant load less than 2,000.
  2. Group B buildings having an occupant load of 500 or more persons or more than 100 persons above or below the lowest level of exit discharge.
  3. Group E.
  4. Group F.
  5. Group H.
  6. Group I. (Includes "Assisted Living Communities" and 'Memory Care Units". See (g) following Table 405.2).
  7. Group R-1.
  8. Group R-2 college and university buildings.
  9. Group R-3 care facilities where required by the authority having jurisdiction
  10. Group R-4.
  11. High-rise buildings.
  12. Group M buildings having an occupant load of 500 or more persons or more than 100 persons above or below the lowest level of exit discharge.
  13. Covered malls exceeding 50,000 square feet (4645 m2) in aggregate floor area.
  14. Underground buildings.
  15. Buildings with an atrium and having an occupancy classification of Group A, E or M.

(Effective January 1, 2014)
Fire safety and evacuation plan contents shall be in accordance with Sections 404.3.1 and 404.3.2.
Fire evacuation plans shall include the following:
  1. Emergency egress or escape routes and whether evacuation of the building is to be complete or, where approved, by selected floors or areas only.
  2. Procedures for employees who must remain to operate critical equipment before evacuating.
  3. Procedures for assisted rescue for persons unable to use the general means of egress unassisted.
  4. Procedures for accounting for employees and occupants after evacuation has been completed.
  5. Identification and assignment of personnel responsible for rescue or emergency medical aid.
  6. The preferred and any alternative means of notifying occupants of a fire or emergency.
  7. The preferred and any alternative means of reporting fires and other emergencies to the fire department or designated emergency response organization.
  8. Identification and assignment of personnel who can be contacted for further information or explanation of duties under the plan.
  9. A description of the emergency voice/alarm communication system alert tone and preprogrammed voice messages, where provided.
Fire safety plans shall include the following:
  1. The procedure for reporting a fire or other emergency.
  2. The life safety strategy and procedures for notifying, relocating or evacuating occupants, including occupants who need assistance.
  3. Site plans indicating the following:
    1. The occupancy assembly point.
    2. The locations of fire hydrants.
    3. The normal routes of fire department vehicle access.
  4. Floor plans identifying the locations of the following:
    1. Exits.
    2. Primary evacuation routes.
    3. Secondary evacuation routes.
    4. Accessible egress routes.
    5. Areas of refuge.
    6. Exterior areas for assisted rescue.
    7. Manual fire alarm boxes.
    8. Portable fire extinguishers.
    9. Occupant-use hose stations.
    10. Fire alarm annunciators and controls.
  5. A list of major fire hazards associated with the normal use and occupancy of the premises, including maintenance and housekeeping procedures.
  6. Identification and assignment of personnel responsible for maintenance of systems and equipment installed to prevent or control fires.
  7. Identification and assignment of personnel responsible for maintenance, housekeeping and controlling fuel hazard sources.
Where facilities develop a lockdown plan, the lockdown plan shall be in accordance with Sections 404.3.3.1 through 404.3.3.3.
Lockdown plans shall be approved by the fire code official and shall include the following:
  1. Initiation. The plan shall include instructions for reporting an emergency that requires a lockdown.
  2. Accountability. The plan shall include accountability procedures for staff to report the presence or absence of occupants.
  3. Recall. The plan shall include a prearranged signal for returning to normal activity.
  4. Communication and coordination. The plan shall include an approved means of two-way communication between a central location and each secured area.
The training frequency shall be included in the lockdown plan. The lockdown drills shall not substitute for any of the fire and evacuation drills required in Section 405.2.
The method of notifying building occupants of a lockdown shall be included in the plan. The method of notification shall be separate and distinct from the fire alarm signal.
Fire safety and evacuation plans shall be reviewed or updated annually or as necessitated by changes in staff assignments, occupancy or the physical arrangement of the building.
Fire safety and evacuation plans shall be available in the workplace for reference and review by employees, and copies shall be furnished to the fire code official for review upon request.
The fire safety and evacuation plans shall be distributed to the tenants and building service employees by the owner or owner's agent. Tenants shall distribute to their employees applicable parts of the fire safety plan affecting the employees' actions in the event of a fire or other emergency.
Emergency evacuation drills complying with the provisions of this section shall be conducted at least annually in the occupancies listed in Section 404.2 or when required by the fire code official. Drills shall be designed in cooperation with the local authorities.

405.2 Frequency

AMENDMENT
This section has been amended at the state or city level.
Required emergency evacuation drills shall be held at the intervals specified in Table 405.2 or more frequently where necessary to familiarize all occupants with the drill procedure.
  1. The frequency shall be allowed to be modified in accordance with Section 408.3.2.
  2. Fire and evacuation drills in (Group I-1 and Group R-4) residential care facilities, residential board and care facilities, personal care homes, and assisted living communities shall include resident participation in accordance with Section 408.6.5 or 408.11.5, as may be applicable. Where occupants receive habilitation or rehabilitation training, fire prevention and fire safety practices shall be included as part of the training program. "Personal Care Homes" and "Residential Board and Care Occupancies" are defined in Section 120-3-3-.03 of Chapter 120-3-3 of the Rules and Regulations of the Safety Fire Commissioner.
  3. Group B buildings having an occupant load of 500 or more persons or more than 100 persons above or below the lowest level of exit discharge.
  4. Applicable to Group R-2 college and university buildings in accordance with Section 408.3.
  5. Drills shall be reported electronically to the Office of the Safety Fire Commissioner.
  6. Or, as otherwise directed by the authority having jurisdiction as set forth in 404.2 (9).
  7. Health care facilities include "Limited Care Facilities" and "Limited Care (Custodial Care) Facilities", as defined in Section 120-3-3-.03 of the Rules and Regulations of the Safety Fire Commissioner.
(Effective January 1, 2014)
Responsibility for the planning and conduct of drills shall be assigned to competent persons designated to exercise leadership.
Drills shall be held at unexpected times and under varying conditions to simulate the unusual conditions that occur in case of fire.
Records shall be maintained of required emergency evacuation drills and include the following information:
  1. Identity of the person conducting the drill.
  2. Date and time of the drill.
  3. Notification method used.
  4. Staff members on duty and participating.
  5. Number of occupants evacuated.
  6. Special conditions simulated.
  7. Problems encountered.
  8. Weather conditions when occupants were evacuated.
  9. Time required to accomplish complete evacuation.
Where required by the fire code official, prior notification of emergency evacuation drills shall be given to the fire code official.
Where a fire alarm system is provided, emergency evacuation drills shall be initiated by activating the fire alarm system.
As building occupants arrive at the assembly point, efforts shall be made to determine if all occupants have been successfully evacuated or have been accounted for.
An electrically or mechanically operated signal used to recall occupants after an evacuation shall be separate and distinct from the signal used to initiate the evacuation. The recall signal initiation means shall be manually operated and under the control of the person in charge of the premises or the official in charge of the incident. No one shall reenter the premises until authorized to do so by the official in charge.
Employees in the occupancies listed in Section 404.2 shall be trained in the fire emergency procedures described in their fire evacuation and fire safety plans. Training shall be based on these plans and as described in Section 404.3.
Employees shall receive training in the contents of fire safety and evacuation plans and their duties as part of new employee orientation and at least annually thereafter. Records shall be kept and made available to the fire code official upon request.

406.2.1 Care-Giver Training

AMENDMENT
This section has been amended at the state or city level.
A minimum of five hours initial fire safety training and recommendation for receipt of a certificate of training for successful completion of the training shall be required for all directors, operators and all staff members of day-care facilities (adult and children), and for administrator's, directors, operators and all staff of assisted living communities, assisted living facilities, community living arrangements, memory care units, personal care homes, and residential board and care homes, as defined in Chapter 2 of this Code or as defined by the Life Safety Code, and or as adopted by Chapter 120-3-3 of the Rules and Regulations of the Safety Fire Commissioner. The curriculum for the fire safety training shall receive written approval by the State Fire Marshal's Office and be taught by an instructor registered with the Safety Fire Commissioner's Office. All persons as required herein to obtain such required training shall receive this training within 90 days from receipt of a license, being commissioned or the opening of a new facility. Such new persons shall receive a minimum of five hours initial fire safety training and recommendation for receipt of a certificate of training for successful completion of the training within 90 days of employment. In addition, a minimum of two hours of fire safety refresher training shall be required for receipt of a certificate of training for successful completion of the refresher training. The refresher training shall be required for all persons coming under 406.2.1, every three years from the date initial training is received. The curriculum for the fire safety refresher training shall receive written approval by the State Fire Marshal's Office and be taught by an instructor registered with the Safety Fire Commissioner's Office. Registered instructors shall deliver the training based on policies and direction from the State Fire Marshal's Office. Instructors found not to be delivering the training in accordance with the said policies and direction shall be removed from the registry and prohibited from delivering future training.

(Effective January 1, 2014)
Employees shall be trained in fire prevention, evacuation and fire safety in accordance with Sections 406.3.1 through 406.3.4.
Employees shall be apprised of the fire hazards of the materials and processes to which they are exposed. Each employee shall be instructed in the proper procedures for preventing fires in the conduct of their assigned duties.
Employees shall be familiarized with the fire alarm and evacuation signals, their assigned duties in the event of an alarm or emergency, evacuation routes, areas of refuge, exterior assembly areas and procedures for evacuation.
Where a facility has a lockdown plan, employees shall be trained on their assigned duties and procedures in the event of an emergency lockdown.
Employees assigned fire-fighting duties shall be trained to know the locations and proper use of portable fire extinguishers or other manual fire-fighting equipment and the protective clothing or equipment required for its safe and proper use.
The provisions of Sections 407.2 through 407.7 shall be applicable where hazardous materials subject to permits under Section 5001.5 are located on the premises or where required by the fire code official.
Material Safety Data Sheets (MSDS) for all hazardous materials shall be either readily available on the premises as a paper copy, or where approved, shall be permitted to be readily retrievable by electronic access.
Individual containers of hazardous materials, cartons or packages shall be marked or labeled in accordance with applicable federal regulations. Buildings, rooms and spaces containing hazardous materials shall be identified by hazard warning signs in accordance with Section 5003.5.
Persons responsible for the operation of areas in which hazardous materials are stored, dispensed, handled or used shall be familiar with the chemical nature of the materials and the appropriate mitigating actions necessary in the event of a fire, leak or spill. Responsible persons shall be designated and trained to be liaison personnel for the fire department. These persons shall aid the fire department in preplanning emergency responses and identification of the locations where hazardous materials are located, and shall have access to Material Safety Data Sheets and be knowledgeable in the site emergency response procedures.
Where required by the fire code official, each application for a permit shall include a Hazardous Materials Inventory Statement (HMIS) in accordance with Section 5001.5.2.
Where required by the fire code official, each application for a permit shall include a Hazardous Materials Management Plan (HMMP) in accordance with Section 5001.5.1. The fire code official is authorized to accept a similar plan required by other regulations.
The permit holder or applicant shall submit to the fire code official a facility closure plan in accordance with Section 5001.6.3 to terminate storage, dispensing, handling or use of hazardous materials.
In addition to the other requirements of this chapter, the provisions of this section are applicable to specific occupancies listed herein.
Group A occupancies shall comply with the requirements of Sections 408.2.1 and 408.2.2 and Sections 401 through 406.
The fire safety and evacuation plans for assembly occupancies shall include the information required by Section 404.3 and a detailed seating plan, occupant load and occupant load limit. Deviations from the approved plans shall be allowed provided the occupant load limit for the occupancy is not exceeded and the aisles and exit accessways remain unobstructed.
In theaters, motion picture theaters, auditoriums and similar assembly occupancies in Group A used for noncontinuous programs, an audible announcement shall be made not more than 10 minutes prior to the start of each program to notify the occupants of the location of the exits to be used in the event of a fire or other emergency.
Exception: In motion picture theaters, the announcement is allowed to be projected upon the screen in a manner approved by the fire code official.

408.2.3 Crowd Managers

AMENDMENT
This section has been amended at the state or city level.
Assembly occupancies having occupant loads of 100 or more shall be provided with a minimum of one trained crowd manager or crowd manager supervisor. Where the occupant load exceeds 250, additional trained crowd managers or crowd manager supervisors shall be provided at a ratio of 1:250, crowd manager / supervisor to occupants, respectively, unless otherwise permitted by the following:
  1. This requirement shall not apply to assembly occupancies used exclusively for religious worship with an occupant load not exceeding 2000.
  2. With the exception of assembly occupancies noted above where alcoholic beverages are consumed, the ratio of trained crowd managers to occupants shall be permitted to be reduced where, in the opinion of the authority having jurisdiction, the existence of an approved, supervised sprinkler system and the nature of the event warrant.

408.2.3.1 Training

AMENDMENT
This section has been amended at the state or city level.
The crowd manager shall receive training approved by the Fire Code Official in crowd management techniques.

408.2.3.2 Fire Watch Personnel

AMENDMENT
This section has been amended at the state or city level.
The provisions of 403.1 shall also be applicable.

408.2.3.3 Tents and Membrane Structures

AMENDMENT
This section has been amended at the state or city level.
Crowd managers shall be provided as specified in Section 3104.20.2 for tents and membrane structures.

(Effective January 1, 2014)
Group E occupancies shall comply with the requirements of Sections 408.3.1 through 408.3.4 and Sections 401 through 406. Group R-2 college and university buildings shall comply with the requirements of Sections 408.3.1 and 408.3.3 and Sections 401 through 406.
The first emergency evacuation drill of each school year shall be conducted within 10 days of the beginning of classes.
In severe climates, the fire code official shall have the authority to modify the emergency evacuation drill frequency specified in Section 405.2.
Emergency evacuation drills shall be conducted at different hours of the day or evening, during the changing of classes, when the school is at assembly, during the recess or gymnastic periods, or during other times to avoid distinction between drills and actual fires. In Group R-2 college and university buildings, one required drill shall be held during hours after sunset or before sunrise.
Outdoor assembly areas shall be designated and shall be located a safe distance from the building being evacuated so as to avoid interference with fire department operations. The assembly areas shall be arranged to keep each class separate to provide accountability of all individuals.

408.4 Group H-5 Occupancies

AMENDMENT
This section has been amended at the state or city level.

408.4.1 Plans and Diagrams

AMENDMENT
This section has been amended at the state or city level.

408.4.2 Plan Updating

AMENDMENT
This section has been amended at the state or city level.

408.4.3 Emergency Response Team

AMENDMENT
This section has been amended at the state or city level.

408.4.4 Emergency Drills

AMENDMENT
This section has been amended at the state or city level.

408.4 Group F Occupancies

AMENDMENT
This section has been amended at the state or city level.
Group F occupancies shall comply with the requirements of Sections 408.4.1 through 408.4.4 and Sections 401 through 407.

408.4.1 Plans and Diagrams

AMENDMENT
This section has been amended at the state or city level.
In addition to the requirements of Section 404 and Section 407.6, plans and diagrams shall be maintained in approved locations indicating any hazardous areas within the facility and locations of exits.

408.4.2 Plan Updating

AMENDMENT
This section has been amended at the state or city level.
The plans and diagrams required by Section 408.4.1 shall be maintained up to date and the fire code official and fire department shall be informed of all major changes.

408.4.3 Emergency Response Team

AMENDMENT
This section has been amended at the state or city level.
Responsible persons shall be designated as the on-site emergency response team and trained to be liaison personnel for the fire department. These persons shall aid the fire department in preplanning emergency responses, identifying hazardous locations and be familiar with the chemical nature of any hazardous material stored on site. An adequate number of personnel for each work shift shall be designated.

408.4.3.1 Disaster Training

AMENDMENT
This section has been amended at the state or city level.
Malfunctions of the process should be simulated and emergency actions undertaken. Disaster drills that simulate a major catastrophic situation should be undertaken periodically with the cooperation and participation of public fire, police, and other local community emergency units nearby cooperating plants if involved.

408.4.4 Employee Training

AMENDMENT
This section has been amended at the state or city level.
The requirements of Sections 408.4.4.1 thru 408.4.6 shall be for new employees and shall be also be applied retroactively with a completion date of January 1, 2011, for existing employees.

408.4.4.1 Initial Training

AMENDMENT
This section has been amended at the state or city level.
Initial training shall be provided to employees and contractors who are involved in operating, maintaining, and supervising facilities that handle combustible particulate solids. Initial training shall ensure that all employees are knowledgeable about the following:
  1. Hazards of their workplace
  2. General orientation, including plant safety rules
  3. Process description
  4. Equipment operation, safe startup and shutdown, and response to upset conditions
  5. The necessity for proper functioning of related fire and explosion protection systems
  6. Equipment maintenance requirements and practices
  7. Housekeeping requirements
  8. Emergency response plans

408.5 Group I-1 Occupancies

AMENDMENT
This section has been amended at the state or city level.

408.5.1 Fire Safety and Evacuation Plan

AMENDMENT
This section has been amended at the state or city level.

408.5.2 Staff Training

AMENDMENT
This section has been amended at the state or city level.

408.5.3 Resident Training

AMENDMENT
This section has been amended at the state or city level.

408.5.4 Drill Frequency

AMENDMENT
This section has been amended at the state or city level.

408.5.5 Resident Participation

AMENDMENT
This section has been amended at the state or city level.

408.5 Group H Occupancies

AMENDMENT
This section has been amended at the state or city level.
Group H occupancies shall comply with the requirements of Sections 408.5.1 through 408.5.4 and Sections 401 through 407.

408.5.1 Plans and Diagrams

AMENDMENT
This section has been amended at the state or city level.
In addition to the requirements of Section 404 and Section 407.6, plans and diagrams shall be maintained in approved locations indicating the approximate plan for each area, the amount and type of HPM stored, handled and used, locations of shutoff valves for HPM supply piping, emergency telephone locations and locations of exits.

408.5.2 Plan Updating

AMENDMENT
This section has been amended at the state or city level.
The plans and diagrams required by Section 408.5.1 shall be maintained up to date and the fire code official and fire department shall be informed of all major changes.

408.5.3 Emergency Response Team

AMENDMENT
This section has been amended at the state or city level.
Responsible persons shall be designated as the on-site emergency response team and trained to be liaison personnel for the fire department. These persons shall aid the fire department in preplanning emergency responses, identifying locations where HPM is stored, handled and used, and be familiar with the chemical nature of such material. An adequate number of personnel for each work shift shall be designated.

408.5.3.1 Disaster Training

AMENDMENT
This section has been amended at the state or city level.
Malfunctions of the process should be simulated and emergency actions undertaken. Disaster drills that simulate a major catastrophic situation should be undertaken periodically with the cooperation and participation of public fire, police, and other local community emergency units nearby cooperating plants if involved

408.5.4 Employee Training

AMENDMENT
This section has been amended at the state or city level.
The requirements of Sections 408.5.4.1 thru 408.5.6 shall be for new employees and shall be also be applied retroactively with a completion date of January 1, 2011, for currently existing employees.

408.5.4.1 Initial Training

AMENDMENT
This section has been amended at the state or city level.
Initial training shall be provided to employees who are involved in operating, maintaining, and supervising facilities that handle combustible particulate solids. Initial training shall ensure that all employees are knowledgeable about the following:
  1. Hazards of their workplace
  2. General orientation, including plant safety rules
  3. Process description
  4. Equipment operation, safe startup and shutdown, and response to upset conditions
  5. The necessity for proper functioning of related fire and explosion protection systems
  6. Equipment maintenance requirements and practices
  7. Housekeeping requirements
  8. Emergency response plans

408.5.5 Notification of Hazards

AMENDMENT
This section has been amended at the state or city level.
All employees shall receive monthly notification of hazards and safety information related to the industry's operation.

408.5.5.1 Notification Frequency

AMENDMENT
This section has been amended at the state or city level.
Notification of hazards shall be by means of internal written or electronic correspondence, postings of information at conspicuous locations and/or by other means to disseminate information to employees to ensure they are knowledgeable about the hazards of their workplace. Monthly notifications can include such topics as prescribed in 408.5.4.1.

408.5.6 Certification

AMENDMENT
This section has been amended at the state or city level.
For those industries having operations involving the manufacturing, processing, and/or handling of combustible particulate solids including manufacturing processes that create combustible dust listed under Rule 120-3-24-.021(b), the employer's authorized agent shall electronically file to the Safety Fire Commissioner a written affidavit certifying annually that the training and monthly notifications required by Section 408.5.4.1 have been completed for the past calendar year.

408.5.7 Emergency Drills

AMENDMENT
This section has been amended at the state or city level.
Emergency drills of the on-site emergency response team shall be conducted on a regular basis but not less than once every three months. Records of drills conducted shall be maintained and available for inspection by the Fire Code Official.

408.6 Group I-2 Occupancies

AMENDMENT
This section has been amended at the state or city level.

408.6.1 Evacuation Not Required

AMENDMENT
This section has been amended at the state or city level.

408.6.2 Coded Alarm Signal

AMENDMENT
This section has been amended at the state or city level.

408.6 Group I-1 Occupancies

AMENDMENT
This section has been amended at the state or city level.
Group I-1 occupancies shall comply with the requirements of Sections 408.6.1 through 408.6.5 and Sections 401 through 406.

408.6.1 Fire Safety and Evacuation Plan

AMENDMENT
This section has been amended at the state or city level.
The fire safety and evacuation plan required by Section 404 shall include special staff actions including fire protection procedures necessary for residents and shall be amended or revised upon admission of any resident with unusual needs.

408.6.2 Staff Training

AMENDMENT
This section has been amended at the state or city level.
Employees shall be periodically instructed and kept informed of their duties and responsibilities under the plan. Such instruction shall be reviewed by the staff at least every two months. A copy of the plan shall be readily available at all times within the facility.

408.6.2.1

AMENDMENT
This section has been amended at the state or city level.
Management and employees shall be subject to the care-giver training provisions of 406.2.1 by January 1, 2015.

408.6.3 Resident Training

AMENDMENT
This section has been amended at the state or city level.
Residents capable of assisting in their own evacuation shall be trained in the proper actions to take in the event of a fire. The training shall include actions to take if the primary escape route is blocked. Where the resident is given rehabilitation or habilitation training, training in fire prevention and actions to take in the event of a fire shall be a part of the rehabilitation training program. Residents shall be trained to assist each other in case of fire to the extent their physical and mental abilities permit them to do so without additional personal risk.

408.6.4 Drill Frequency

AMENDMENT
This section has been amended at the state or city level.
Emergency evacuation drills shall be conducted at least quarterly per year on each shift. Drills are required to comply with the time requirements of Section 405.4.

408.6.5 Resident Participation

AMENDMENT
This section has been amended at the state or city level.
Emergency evacuation drills shall involve the actual evacuation of residents to a selected assembly point and shall provide residents with experience in exiting through all required exits. All required exits shall be used during emergency evacuation drills.
Exception: Actual exiting from windows shall not be required. Opening the window and signaling for help shall be an acceptable alternative.

408.7 Group I-3 Occupancies

AMENDMENT
This section has been amended at the state or city level.

408.7.1 Employee Training

AMENDMENT
This section has been amended at the state or city level.

408.7.2 Staffing

AMENDMENT
This section has been amended at the state or city level.

408.7.3 Notification

AMENDMENT
This section has been amended at the state or city level.

408.7.4 Keys

AMENDMENT
This section has been amended at the state or city level.

408.7 Group I-2 Occupancies

AMENDMENT
This section has been amended at the state or city level.
Group I-2 occupancies shall comply with the requirements of Sections 408.7.1 and 408.7.2 and Sections 401 through 406. Drills are not required to comply with the time requirements of Section 405.4.

408.7.1 Evacuation Not Required

AMENDMENT
This section has been amended at the state or city level.
During emergency evacuation drills, the movement of patients to safe areas or to the exterior of the building is not required.

408.7.2 Coded Alarm Signal

AMENDMENT
This section has been amended at the state or city level.
When emergency evacuation drills are conducted after visiting hours or when patients or residents are expected to be asleep, a coded announcement is allowed instead of audible alarms.

408.8 Group R-1 Occupancies

AMENDMENT
This section has been amended at the state or city level.

408.8.1 Evacuation Diagrams

AMENDMENT
This section has been amended at the state or city level.

408.8.2 Emergency Duties

AMENDMENT
This section has been amended at the state or city level.

408.8.3 Fire Safety and Evacuation Instructions

AMENDMENT
This section has been amended at the state or city level.

408.8 Group I-3 Occupancies

AMENDMENT
This section has been amended at the state or city level.
Group I-3 occupancies shall comply with the requirements of Sections 408.8.1 through 408.8.4 and Sections 401 through 406.

408.8.1 Employee Training

AMENDMENT
This section has been amended at the state or city level.
Employees shall be instructed in the proper use of portable fire extinguishers and other manual fire suppression equipment. Training of new staff shall be provided promptly upon entrance on duty. Refresher training shall be provided at least annually.

408.8.2 Staffing

AMENDMENT
This section has been amended at the state or city level.
Group I-3 occupancies shall be provided with 24-hour staffing. Staff shall be within three floors or 300 feet (91 440 mm) horizontal distance of the access door of each resident housing area. In Use Conditions 3, 4 and 5, as defined in Chapter 2, the arrangement shall be such that the staff involved can start release of locks necessary for emergency evacuation or rescue and initiate other necessary emergency actions within 2 minutes of an alarm.
Exception: Staff shall not be required to be within three floors or 300 feet (9144 mm) in areas in which all locks are unlocked remotely and automatically in accordance with Section 408.4 of the International Building Code.

408.8.3 Notification

AMENDMENT
This section has been amended at the state or city level.
Provisions shall be made for residents in Use Conditions 3, 4 and 5, as defined in Chapter 2, to readily notify staff of an emergency.

408.8.4 Keys

AMENDMENT
This section has been amended at the state or city level.
Keys necessary for unlocking doors installed in a means of egress shall be individually identifiable by both touch and sight.

408.9 Group R-2 Occupancies

AMENDMENT
This section has been amended at the state or city level.

408.9.1 Emergency Guide

AMENDMENT
This section has been amended at the state or city level.

408.9.2 Evacuation Diagrams in Group R-2 Dormitories

AMENDMENT
This section has been amended at the state or city level.

408.9.3 Maintenance

AMENDMENT
This section has been amended at the state or city level.

408.9.4 Distribution

AMENDMENT
This section has been amended at the state or city level.

408.9 Group R-1 Occupancies

AMENDMENT
This section has been amended at the state or city level.
Group R-1 occupancies shall comply with the requirements of Sections 408.9.1 through 408.9.3 and Sections 401 through 406.

408.9.1 Evacuation Diagrams

AMENDMENT
This section has been amended at the state or city level.
A diagram depicting two evacuation routes shall be posted on or immediately adjacent to every required egress door from each hotel, motel or dormitory sleeping unit.

408.9.2 Emergency Duties

AMENDMENT
This section has been amended at the state or city level.
Upon discovery of a fire or suspected fire, hotel, motel and dormitory employees shall perform the following duties:
  1. Activate the fire alarm system, where provided.
  2. Notify the public fire department.
  3. Take other action as previously instructed.

408.9.3 Fire Safety and Evacuation Instructions

AMENDMENT
This section has been amended at the state or city level.
Information shall be provided in the fire safety and evacuation plan required by Section 404 to allow guests to decide whether to evacuate to the outside, evacuate to an area of refuge, remain in place, or any combination of the three.

408.10 Group R-4 Occupancies

AMENDMENT
This section has been amended at the state or city level.

408.10.1 Fire Safety and Evacuation Plan

AMENDMENT
This section has been amended at the state or city level.

408.10.2 Staff Training

AMENDMENT
This section has been amended at the state or city level.

408.10.3 Resident Training

AMENDMENT
This section has been amended at the state or city level.

408.10.4 Drill Frequency

AMENDMENT
This section has been amended at the state or city level.

408.10.5 Resident Participation

AMENDMENT
This section has been amended at the state or city level.

408.10 Group R-2 Occupancies

AMENDMENT
This section has been amended at the state or city level.
Group R-2 occupancies shall comply with the requirements of Sections 408.10.1 through 408.10.3 and Sections 401 through 406.

408.10.1 Emergency Guide

AMENDMENT
This section has been amended at the state or city level.
A fire emergency guide shall be provided which describes the location, function and use of fire protection equipment and appliances accessible to residents, including fire alarm systems, smoke alarms, and portable fire extinguishers. The guide shall also include an emergency evacuation plan for each dwelling unit.

408.10.2 Maintenance

AMENDMENT
This section has been amended at the state or city level.
Emergency guides shall be reviewed and approved in accordance with Section 401.2.

408.10.3 Distribution

AMENDMENT
This section has been amended at the state or city level.
A copy of the emergency guide shall be given to each tenant prior to initial occupancy.

408.11 Covered and Open Mall Buildings

AMENDMENT
This section has been amended at the state or city level.

408.11.1 Lease Plan

AMENDMENT
This section has been amended at the state or city level.

408.11.1.1 Approval

AMENDMENT
This section has been amended at the state or city level.

408.11.1.2 Revisions

AMENDMENT
This section has been amended at the state or city level.

408.11.2 Tenant Identification

AMENDMENT
This section has been amended at the state or city level.

408.11.3 Maintenance

AMENDMENT
This section has been amended at the state or city level.

408.11 Group R-4 Occupancies

AMENDMENT
This section has been amended at the state or city level.
Group R-4 occupancies shall comply with the requirements of Sections 408.11.1 through 408.11.5 and Sections 401 through 406.

408.11.1 Fire Safety and Evacuation Plan

AMENDMENT
This section has been amended at the state or city level.
The fire safety and evacuation plan required by Section 404 shall include special staff actions, including fire protection procedures necessary for residents, and shall be amended or revised upon admission of a resident with unusual needs.

408.11.2 Staff Training

AMENDMENT
This section has been amended at the state or city level.
Employees shall be periodically instructed and kept informed of their duties and responsibilities under the plan. Such instruction shall be reviewed by the staff at least every two months. A copy of the plan shall be readily available at all times within the facility.

408.11.2.1

AMENDMENT
This section has been amended at the state or city level.
Management and employees shall be subject to the care-giver training provisions of 406.2.1 by January 1, 2015.

408.11.3 Resident Training

AMENDMENT
This section has been amended at the state or city level.
Residents capable of assisting in their own evacuation shall be trained in the proper actions to take in the event of a fire. The training shall include actions to take if the primary escape route is blocked. Where the resident is given rehabilitation or habilitation training, training in fire prevention and actions to take in the event of a fire shall be a part of the rehabilitation training program. Residents shall be trained to assist each other in case of fire to the extent their physical and mental abilities permit them to do so without additional personal risk.

408.11.4 Drill Frequency

AMENDMENT
This section has been amended at the state or city level.
Emergency evacuation drills shall be conducted at least quarterly each on each shift. Twelve drills shall be conducted in the first year of operation. Drills are not required to comply with the time requirements of Section 405.4.

408.11.5 Resident Participation

AMENDMENT
This section has been amended at the state or city level.
Emergency evacuation drills shall involve the actual evacuation of residents to a selected assembly point and shall provide residents with experience in exiting through all required exits. All required exits shall be used during emergency evacuation drills.
Exception: Actual exiting from windows shall not be required. Opening the window and signaling for help shall be an acceptable alternative.

408.12 Covered Mall Buildings

AMENDMENT
This section has been amended at the state or city level.
Covered mall buildings shall comply with the provisions of Sections 408.12.1 through 408.12.3.

408.12.1 Lease Plan

AMENDMENT
This section has been amended at the state or city level.
A lease plan shall be prepared for each covered mall building. The plan shall include the following information in addition to that required by Section 404.3.2:
  1. Each occupancy, including identification of tenant.
  2. Exits from each tenant space.
  3. Fire protection features, including the following:
    1. Fire department connections.
    2. Fire command center.
    3. Smoke management system controls.
    4. Elevators and elevator controls.
    5. Hose valves outlets.
    6. Sprinkler and standpipe control valves.
    7. Automatic fire-extinguishing system areas.
    8. Automatic fire detector zones.
    9. Fire barriers.

408.12.1.1 Approval

AMENDMENT
This section has been amended at the state or city level.
The lease plan shall be submitted to the fire code official for approval, and shall be maintained on site for immediate reference by responding fire service personnel.

408.12.1.2 Revisions

AMENDMENT
This section has been amended at the state or city level.
The lease plans shall be revised annually or as often as necessary to keep them current. Modifications or changes in tenants or occupancies shall not be made without prior approval of the fire code official and building official.

408.12.2 Tenant Identification

AMENDMENT
This section has been amended at the state or city level.
Each occupied tenant space provided with a secondary exit to the exterior or exit corridor shall be provided with tenant identification by business name and/or address. Letters and numbers shall be posted on the corridor side of the door, be plainly legible and shall contrast with their background.
Exception: Tenant identification is not required for anchor stores.

408.12.3 Maintenance

AMENDMENT
This section has been amended at the state or city level.
Unoccupied tenant spaces shall be:
  1. Kept free from the storage of any materials.
  2. Separated from the remainder of the building by partitions of at least 0.5-inch-thick (12.7 mm) gypsum board or an approved equivalent to the underside of the ceiling of the adjoining tenant spaces.
  3. Without doors or other access openings other than one door that shall be kept keylocked in the closed position except during that time when opened for inspection.
  4. Kept free from combustible waste and be broom swept clean.
(Effective January 1, 2014)