ADOPTS WITH AMENDMENTS:

International Fire Code 2012 (IFC 2012)

Heads up: There are no amended sections in this chapter.
Airports, heliports, helistops and aircraft hangars shall be in accordance with this chapter.
Regulations not specifically contained herein pertaining to airports, aircraft maintenance, aircraft hangars and appurtenant operations shall be in accordance with nationally recognized standards.
For permits to operate aircraft-refueling vehicles, application of flammable or combustible finishes and hot work, see Section 105.6.
The following terms are defined in Chapter 2 :
Open flames, flame-producing devices and other sources of ignition shall not be permitted in a hangar, except in approved locations or in any location within 50 feet (15 240 mm) of an aircraft-fueling operation.
Smoking shall be prohibited in aircraft-refueling vehicles, aircraft hangars and aircraft operation areas used for cleaning, paint removal, painting operations or fueling. "No Smoking" signs shall be provided in accordance with Section 310.
Exception: Designated and approved smoking areas.
The aircraft operation area (AOA) and related areas shall be kept free from combustible debris at all times.
Fire apparatus access roads shall be provided and maintained in accordance with Chapter 5. Fire apparatus access roads and aircraft parking positions shall be designed in a manner so as to preclude the possibility of fire vehicles traveling under any portion of a parked aircraft.

2003.5 Dispensing of Flammable and Combustible Liquids

AMENDMENT
This section has been amended at the state or city level.

2003.5 Dispensing of Flammable and Combustible Liquids

AMENDMENT
This section has been amended at the state or city level.
No dispensing, transfer or storage of flammable or combustible liquids shall be permitted inside any building or structure.
Exceptions:
  1. As provided in Chapter 57 of this Code, provided, the provisions are not less protective than the provisions of any applicable codes and standards adopted by the Rules and Regulations of the Safety Fire Commissioner.
  2. When the procedures used follow the guidelines and requirements set forth in NFPA 410 — Standard for Aircraft Maintenance, adopted by this Chapter 120-3-3.
(Effective January 1, 2014)
Combustible materials stored in aircraft hangars shall be stored in approved locations and containers.
Flammable and combustible liquids shall not be dispensed into or removed from a container, tank, vehicle or aircraft except in approved locations.
The application of flammable or Class II combustible liquid finishes is prohibited unless both of the following conditions are met:
  1. The application of the liquid finish is accomplished in an approved location.
  2. The application methods and procedures are in accordance with Chapter 24.
Class IA flammable liquids shall not be used to clean aircraft, aircraft parts or aircraft engines. Cleaning with other flammable and combustible liquids shall be in accordance with Section 5705.3.6.
This section shall apply to spills of flammable and combustible liquids and other hazardous materials. Fuel spill control shall also comply with Section 2006.11.
Activities in the affected area not related to the mitigation of the spill shall cease until the spilled material has been removed or the hazard has been mitigated.
Aircraft or other vehicles shall not be moved through the spill area until the spilled material has been removed or the hazard has been mitigated.
Spills shall be reported, documented and mitigated in accordance with the provisions of this chapter and Section 5003.3.
Aircraft engines shall not be run in aircraft hangars except in approved engine test areas.
Repairing of aircraft requiring the use of open flames, spark-producing devices or the heating of parts above 500°F (260°C) shall only be done outdoors or in an area complying with the provisions of the International Building Code for a Group F-1 occupancy.
Portable fire extinguishers suitable for flammable or combustible liquid and electrical-type fires shall be provided as specified in Sections 2005.2 through 2005.6 and Section 906. Extinguishers required by this section shall be inspected and maintained in accordance with Section 906.
Vehicles used for towing aircraft shall be equipped with a minimum of one listed portable fire extinguisher complying with Section 906 and having a minimum rating of 20-B:C.
Welding apparatus shall be equipped with a minimum of one listed portable fire extinguisher complying with Section 906 and having a minimum rating of 2-A:20-B:C.
Aircraft fuel-servicing tank vehicles shall be equipped with a minimum of two listed portable fire extinguishers complying with Section 906, each having a minimum rating of 20-B:C. A portable fire extinguisher shall be readily accessible from either side of the vehicle.
Hydrant fuel-servicing vehicles shall be equipped with a minimum of one listed portable fire extinguisher complying with Section 906, and having a minimum rating of 20-B:C.
Portable fire extinguishers at fuel-dispensing stations shall be located such that pumps or dispensers are not more than 75 feet (22 860 mm) from one such extinguisher. Fire extinguishers shall be provided as follows:
  1. Where the open-hose discharge capacity of the fueling system is not more than 200 gallons per minute (13 L/s), a minimum of two listed portable fire extinguishers complying with Section 906 and having a minimum rating of 20-B:C shall be provided.
  2. Where the open-hose discharge capacity of the fueling system is more than 200 gallons per minute (13 L/s) but not more than 350 gallons per minute (22 L/s), a minimum of one listed wheeled extinguisher complying with Section 906 and having a minimum extinguishing rating of 80-B:C, and a minimum agent capacity of 125 pounds (57 kg), shall be provided.
  3. Where the open-hose discharge capacity of the fueling system is more than 350 gallons per minute (22 L/s), a minimum of two listed wheeled extinguishers complying with Section 906 and having a minimum rating of 80-B:C each, and a minimum capacity agent of 125 pounds (57 kg) of each, shall be provided.
Portable fire extinguishers required by this chapter shall be accessible at all times. Where necessary, provisions shall be made to clear accumulations of snow, ice and other forms of weather-induced obstructions.
Cabinets and enclosed compartments used to house portable fire extinguishers shall be clearly marked with the words FIRE EXTINGUISHER in letters at least 2 inches (51 mm) high. Cabinets and compartments shall be readily accessible at all times.
Use of a fire extinguisher under any circumstances shall be reported to the manager of the airport and the fire code official immediately after use.

2006.1 Aircraft Motor Vehicle Fuel-Dispensing Facilities

AMENDMENT
This section has been amended at the state or city level.

2006.1 Aircraft Motor Vehicle Fuel-Dispensing Stations and Airport Fuel Systems

AMENDMENT
This section has been amended at the state or city level.
All aircraft motor vehicle fuel-dispensing stations and airport fuel systems shall be in accordance with Chapter 120-3-11 Rules and Regulations of the Safety Fire Commissioner entitled, 'Rules and Regulations for Flammable and Combustible Liquids

(Effective January 1, 2014)

2006.2 Airport Fuel Systems

AMENDMENT
This section has been amended at the state or city level.

2006.3 Construction of Aircraft-Fueling Vehicles and Accessories

AMENDMENT
This section has been amended at the state or city level.

2006.3.1 Transfer Apparatus

AMENDMENT
This section has been amended at the state or city level.

2006.3.1.1 Internal Combustion Type

AMENDMENT
This section has been amended at the state or city level.

2006.3.1.2 Gear Operated

AMENDMENT
This section has been amended at the state or city level.

2006.3.1.3 Vibration Isolation

AMENDMENT
This section has been amended at the state or city level.

2006.3.2 Pumps

AMENDMENT
This section has been amended at the state or city level.

2006.3.3 Dispensing Hoses and Nozzles

AMENDMENT
This section has been amended at the state or city level.

2006.3.4 Protection of Electrical Equipment

AMENDMENT
This section has been amended at the state or city level.

2006.3.5 Venting of Equipment Compartments

AMENDMENT
This section has been amended at the state or city level.

2006.3.6 Accessory Equipment

AMENDMENT
This section has been amended at the state or city level.

2006.3.7 Electrical Bonding Provisions

AMENDMENT
This section has been amended at the state or city level.

2006.3.7.1 Bonding Cables

AMENDMENT
This section has been amended at the state or city level.

2006.3.7.2 Bonding Cable Protection

AMENDMENT
This section has been amended at the state or city level.

2006.3.8 Smoking

AMENDMENT
This section has been amended at the state or city level.

2006.3.9 Smoking Equipment

AMENDMENT
This section has been amended at the state or city level.

2006.4 Operation, Maintenance and Use of Aircraft-Fueling Vehicles

AMENDMENT
This section has been amended at the state or city level.

2006.4.1 Proper Maintenance

AMENDMENT
This section has been amended at the state or city level.

2006.4.2 Vehicle Integrity

AMENDMENT
This section has been amended at the state or city level.

2006.4.3 Removal From Service

AMENDMENT
This section has been amended at the state or city level.

2006.4.4 Operators

AMENDMENT
This section has been amended at the state or city level.

2006.5 Fueling and Defueling

AMENDMENT
This section has been amended at the state or city level.

2006.5.1 Positioning of Aircraft-Fueling Vehicles

AMENDMENT
This section has been amended at the state or city level.

2006.5.1.1 Fueling Vehicle Egress

AMENDMENT
This section has been amended at the state or city level.

2006.5.1.2 Aircraft Vent Openings

AMENDMENT
This section has been amended at the state or city level.

2006.5.1.3 Parking

AMENDMENT
This section has been amended at the state or city level.

2006.5.2 Electrical Bonding

AMENDMENT
This section has been amended at the state or city level.

2006.5.2.1 Conductive Hose

AMENDMENT
This section has been amended at the state or city level.

2006.5.2.2 Bonding Conductors on Transfer Nozzles

AMENDMENT
This section has been amended at the state or city level.

2006.5.2.3 Funnels

AMENDMENT
This section has been amended at the state or city level.

2006.5.3 Training

AMENDMENT
This section has been amended at the state or city level.

2006.5.3.1 Fueling Hazards

AMENDMENT
This section has been amended at the state or city level.

2006.5.3.2 Fire Safety Training

AMENDMENT
This section has been amended at the state or city level.

2006.5.3.2.1 Fire Extinguisher Training

AMENDMENT
This section has been amended at the state or city level.

2006.5.3.2.2 Documentation

AMENDMENT
This section has been amended at the state or city level.

2006.5.4 Transfer Personnel

AMENDMENT
This section has been amended at the state or city level.

2006.5.5 Fuel Flow Control

AMENDMENT
This section has been amended at the state or city level.

2006.6 Emergency Fuel Shutoff

AMENDMENT
This section has been amended at the state or city level.

2006.6.1 Accessibility

AMENDMENT
This section has been amended at the state or city level.

2006.6.2 Notification of the Fire Department

AMENDMENT
This section has been amended at the state or city level.

2006.6.3 Determining Cause

AMENDMENT
This section has been amended at the state or city level.

2006.6.4 Testing

AMENDMENT
This section has been amended at the state or city level.

2006.7 Protection of Hoses

AMENDMENT
This section has been amended at the state or city level.

2006.8 Loading and Unloading

AMENDMENT
This section has been amended at the state or city level.

2006.9 Passengers

AMENDMENT
This section has been amended at the state or city level.

2006.10 Sources of Ignition

AMENDMENT
This section has been amended at the state or city level.

2006.11 Fuel Spill Prevention and Procedures

AMENDMENT
This section has been amended at the state or city level.

2006.11.1 Fuel-Service Equipment Maintenance

AMENDMENT
This section has been amended at the state or city level.

2006.11.2 Transporting Fuel Nozzles

AMENDMENT
This section has been amended at the state or city level.

2006.11.3 Drum Fueling

AMENDMENT
This section has been amended at the state or city level.

2006.11.4 Fuel Spill Procedures

AMENDMENT
This section has been amended at the state or city level.

2006.11.5 Notification of the Fire Department

AMENDMENT
This section has been amended at the state or city level.

2006.11.6 Investigation Required

AMENDMENT
This section has been amended at the state or city level.

2006.11.7 Multiple Fuel Delivery Vehicles

AMENDMENT
This section has been amended at the state or city level.

2006.12 Aircraft Engines and Heaters

AMENDMENT
This section has been amended at the state or city level.

2006.13 Vehicle and Equipment Restrictions

AMENDMENT
This section has been amended at the state or city level.

2006.13.1 Overwing Fueling

AMENDMENT
This section has been amended at the state or city level.

2006.14 Electrical Equipment

AMENDMENT
This section has been amended at the state or city level.

2006.14.1 Other Equipment

AMENDMENT
This section has been amended at the state or city level.

2006.15 Open Flames

AMENDMENT
This section has been amended at the state or city level.

2006.15.1 Other Areas

AMENDMENT
This section has been amended at the state or city level.

2006.15.2 Matches and Lighters

AMENDMENT
This section has been amended at the state or city level.

2006.16 Lightning Procedures

AMENDMENT
This section has been amended at the state or city level.

2006.17 Fuel-Transfer Locations

AMENDMENT
This section has been amended at the state or city level.

2006.17.1 Position of Aircraft

AMENDMENT
This section has been amended at the state or city level.

2006.17.2 Fire Equipment Access

AMENDMENT
This section has been amended at the state or city level.

2006.18 Defueling Operations

AMENDMENT
This section has been amended at the state or city level.

2006.19 Maintenance of Aircraft-Fueling Hose

AMENDMENT
This section has been amended at the state or city level.

2006.19.1 Inspections

AMENDMENT
This section has been amended at the state or city level.

2006.19.1.1 Daily Inspection

AMENDMENT
This section has been amended at the state or city level.

2006.19.1.2 Monthly Inspection

AMENDMENT
This section has been amended at the state or city level.

2006.19.2 Damaged Hose

AMENDMENT
This section has been amended at the state or city level.

2006.19.3 Repairing Hose

AMENDMENT
This section has been amended at the state or city level.

2006.19.4 New Hose

AMENDMENT
This section has been amended at the state or city level.

2006.20 Aircraft Fuel-Servicing Vehicles Parking

AMENDMENT
This section has been amended at the state or city level.

2006.20.1 Parking Area Design

AMENDMENT
This section has been amended at the state or city level.

2006.21 Radar Equipment

AMENDMENT
This section has been amended at the state or city level.

2006.21.1 Direction of Radar Beams

AMENDMENT
This section has been amended at the state or city level.

2007.1 General

AMENDMENT
This section has been amended at the state or city level.

2007.1 General

AMENDMENT
This section has been amended at the state or city level.
Helistops and heliports shall be maintained in accordance with Section 2007. Helistops and heliports on buildings or structures shall be constructed in accordance with the International Building Code and the requirements set forth by NFPA 418, Standard for Heliports, adopted by this Chapter 120-3-3.

(Effective January 1, 2014)
The touchdown area shall be surrounded on all sides by a clear area having minimum average width at roof level of 15 feet (4572 mm) but no width less than 5 feet (1524 mm). The clear area shall be maintained.
Landing areas on structures shall be maintained so as to confine flammable or Class II combustible liquid spillage to the landing area itself, and provisions shall be made to drain such spillage away from exits or stairways serving the helicopter landing area or from a structure housing such exit or stairway.
Exits and stairways shall be maintained in accordance with Section 412.7 of the International Building Code.
A building with a rooftop helistop or heliport shall be provided with a Class I or III standpipe system extended to the roof level on which the helistop or heliport is located. All portions of the helistop and heliport area shall be within 150 feet (45 720 mm) of a 21/2-inch (63.5 mm) outlet on the standpipe system.
Foam fire-protection capabilities shall be provided for rooftop heliports. Such systems shall be designed, installed and maintained in accordance with the applicable provisions of Sections 903, 904 and 905.
A minimum of one portable fire extinguisher having a minimum 80-B:C rating shall be provided for each permanent takeoff and landing area and for the aircraft parking areas. Installation, inspection and maintenance of these extinguishers shall be in accordance with Section 906.
Before operating helicopters from helistops and heliports, approval shall be obtained from the Federal Aviation Administration.
UpCodes Premium
Leverage the most sophisticated code compliance platform.
TRY FREE FOR TWO WEEKS VISIT PRICING