ADOPTS WITH AMENDMENTS:

International Fire Code 2012 (IFC 2012)

Heads up: There are no amended sections in this chapter.

1101.1 Scope

AMENDMENT
This section has been amended at the state or city level.

1101.1 Scope

AMENDMENT
This section has been amended at the state or city level.
The provisions of this chapter shall apply to existing buildings constructed prior to the effective date of this Chapter 120-3-3.

1101.2 Intent

AMENDMENT
This section has been amended at the state or city level.

1101.2 Intent

AMENDMENT
This section has been amended at the state or city level.
The intent of this chapter is to provide a minimum degree of fire and life safety to persons occupying buildings by providing for existing building rehabilitation activities including repair, renovation, modification, reconstruction, change of use or occupancy classification, and additions to such buildings.

(Effective January 1, 2014)

1101.3 Permits

AMENDMENT
This section has been amended at the state or city level.

1101.3 Permits

AMENDMENT
This section has been amended at the state or city level.
Construction permits for buildings falling under State jurisdiction, as set forth in O.C.G.A. 25-2.13, shall be required for the activities noted in 4601.1 when the criteria of O.C.G.A. 25-2-14(d) for an existing building to be classified as a proposed (new) building or structure are met.. For local jurisdictions, permits shall be required as set forth in Section 105.7 of this Code and the International Building Code.

(Effective January 1, 2014)
When a building is found to be in noncompliance with this chapter, the fire code official shall duly notify the owner of the building. Upon receipt of such notice, the owner shall, subject to the following time limits, take necessary actions to comply with the provisions of this chapter.
Construction documents necessary to comply with this chapter shall be completed and submitted within a time schedule approved by the fire code official.
Work necessary to comply with this chapter shall be completed within a time schedule approved by the fire code official.
The fire code official is authorized to grant necessary extensions of time when it can be shown that the specified time periods are not physically practical or pose an undue hardship. The granting of an extension of time for compliance shall be based on the showing of good cause and subject to the filing of an acceptable systematic plan of correction with the fire code official.

Section 1102 Definition

AMENDMENT
This section has been amended at the state or city level.

1102.1 Definition

AMENDMENT
This section has been amended at the state or city level.

Section 1102 Fire and Life Safety Requirements for Existing Buildings and Structures

AMENDMENT
This section has been amended at the state or city level.

1102.1 General

AMENDMENT
This section has been amended at the state or city level.
The intents and purposes of this section shall be met through the application of the applicable provisions of this Code, the Life Safety Code, and other codes and standards as adopted by Chapter 120-3-3 of the Rules and Regulations of the Georgia Safety Fire Commissioner, as they apply to existing conditions and routine maintenance of fire and life safety protection systems and devices. For building rehabilitation activities, including repair, renovation, modification, reconstruction, change of use or occupancy classification, and additions to such buildings, the definitions and requirements of Chapter 43, of the Life Safety Code, adopted by Chapter 120-3-3 of the Rules and Regulations of the Georgia Safety Fire Commissioner shall apply.

(Effective January 1, 2014)

Section 1103 Fire Safety Requirements for Existing Buildings

AMENDMENT
This section has been amended at the state or city level.

1103.1 Required Construction

AMENDMENT
This section has been amended at the state or city level.

1103.2 Emergency Responder Radio Coverage in Existing Buildings

AMENDMENT
This section has been amended at the state or city level.

1103.3 Elevator Operation

AMENDMENT
This section has been amended at the state or city level.

1103.4 Vertical Openings

AMENDMENT
This section has been amended at the state or city level.

1103.4.1 Group I Occupancies

AMENDMENT
This section has been amended at the state or city level.

1103.4.2 Three to Five Stories

AMENDMENT
This section has been amended at the state or city level.

1103.4.3 More Than Five Stories

AMENDMENT
This section has been amended at the state or city level.

1103.4.4 Atriums and Covered Malls

AMENDMENT
This section has been amended at the state or city level.

1103.4.5 Escalators in Group B and M Occupancies

AMENDMENT
This section has been amended at the state or city level.

1103.4.6 Escalators Connecting Four or Fewer Stories

AMENDMENT
This section has been amended at the state or city level.

1103.4.7 Escalators Connecting More Than Four Stories

AMENDMENT
This section has been amended at the state or city level.

1103.5 Sprinkler Systems

AMENDMENT
This section has been amended at the state or city level.

1103.5.1 Pyroxylin Plastics

AMENDMENT
This section has been amended at the state or city level.

1103.5.2 Group I-2

AMENDMENT
This section has been amended at the state or city level.

1103.6 Standpipes

AMENDMENT
This section has been amended at the state or city level.

1103.6.1 Existing Multiple-Story Buildings

AMENDMENT
This section has been amended at the state or city level.

1103.6.2 Existing Helistops and Heliports

AMENDMENT
This section has been amended at the state or city level.

1103.7 Fire Alarm Systems

AMENDMENT
This section has been amended at the state or city level.

1103.7.1 Group E

AMENDMENT
This section has been amended at the state or city level.

1103.7.2 Group I-1

AMENDMENT
This section has been amended at the state or city level.

1103.7.3 Group I-2

AMENDMENT
This section has been amended at the state or city level.

1103.7.4 Group I-3

AMENDMENT
This section has been amended at the state or city level.

1103.7.5 Group R-1

AMENDMENT
This section has been amended at the state or city level.

1103.7.5.1 Group R-1 Hotel and Motel Manual Fire Alarm System

AMENDMENT
This section has been amended at the state or city level.

1103.7.5.1.1 Group R-1 Hotel and Motel Automatic Smoke Detection System

AMENDMENT
This section has been amended at the state or city level.

1103.7.5.2 Group R-1 Boarding and Rooming Houses Manual Fire Alarm System

AMENDMENT
This section has been amended at the state or city level.

1103.7.5.2.1 Group R-1 Boarding and Rooming Houses Automatic Smoke Detection System

AMENDMENT
This section has been amended at the state or city level.

1103.7.6 Group R-2

AMENDMENT
This section has been amended at the state or city level.

1103.7.7 Group R-4

AMENDMENT
This section has been amended at the state or city level.

1103.8 Single- And Multiple-Station Smoke Alarms

AMENDMENT
This section has been amended at the state or city level.

1103.8.1 Where Required

AMENDMENT
This section has been amended at the state or city level.

1103.8.2 Interconnection

AMENDMENT
This section has been amended at the state or city level.

1103.8.3 Power Source

AMENDMENT
This section has been amended at the state or city level.

1103.9 Carbon Monoxide Alarms

AMENDMENT
This section has been amended at the state or city level.

Section 1104 Means of Egress for Existing Buildings

AMENDMENT
This section has been amended at the state or city level.

1104.1 General

AMENDMENT
This section has been amended at the state or city level.

1104.2 Elevators, Escalators and Moving Walks

AMENDMENT
This section has been amended at the state or city level.

1104.3 Exit Sign Illumination

AMENDMENT
This section has been amended at the state or city level.

1104.4 Power Source

AMENDMENT
This section has been amended at the state or city level.

1104.5 Illumination Emergency Power

AMENDMENT
This section has been amended at the state or city level.

1104.5.1 Emergency Power Duration and Installation

AMENDMENT
This section has been amended at the state or city level.

1104.6 Guards

AMENDMENT
This section has been amended at the state or city level.

1104.6.1 Height of Guards

AMENDMENT
This section has been amended at the state or city level.

1104.6.2 Opening Limitations

AMENDMENT
This section has been amended at the state or city level.

1104.7 Size of Doors

AMENDMENT
This section has been amended at the state or city level.

1104.8 Opening Force for Doors

AMENDMENT
This section has been amended at the state or city level.

1104.9 Revolving Doors

AMENDMENT
This section has been amended at the state or city level.

1104.9.1 Egress Component

AMENDMENT
This section has been amended at the state or city level.

1104.10 Stair Dimensions for Existing Stairs

AMENDMENT
This section has been amended at the state or city level.

1104.10.1 Dimensions for Replacement Stairs

AMENDMENT
This section has been amended at the state or city level.

1104.11 Winders

AMENDMENT
This section has been amended at the state or city level.

1104.12 Circular Stairways

AMENDMENT
This section has been amended at the state or city level.

1104.13 Stairway Handrails

AMENDMENT
This section has been amended at the state or city level.

1104.13.1 Height

AMENDMENT
This section has been amended at the state or city level.

1104.14 Slope of Ramps

AMENDMENT
This section has been amended at the state or city level.

1104.15 Width of Ramps

AMENDMENT
This section has been amended at the state or city level.

1104.16 Fire Escape Stairs

AMENDMENT
This section has been amended at the state or city level.

1104.16.1 Existing Means of Egress

AMENDMENT
This section has been amended at the state or city level.

1104.16.2 Protection of Openings

AMENDMENT
This section has been amended at the state or city level.

1104.16.3 Dimensions

AMENDMENT
This section has been amended at the state or city level.

1104.16.4 Access

AMENDMENT
This section has been amended at the state or city level.

1104.16.5 Materials and Strength

AMENDMENT
This section has been amended at the state or city level.

1104.16.5.1 Examination

AMENDMENT
This section has been amended at the state or city level.

1104.16.6 Termination

AMENDMENT
This section has been amended at the state or city level.

1104.16.7 Maintenance

AMENDMENT
This section has been amended at the state or city level.

1104.17 Corridors

AMENDMENT
This section has been amended at the state or city level.

1104.17.1 Corridor Openings

AMENDMENT
This section has been amended at the state or city level.

1104.17.2 Dead Ends

AMENDMENT
This section has been amended at the state or city level.

1104.18 Exit Access Travel Distance

AMENDMENT
This section has been amended at the state or city level.

1104.19 Common Path of Egress Travel

AMENDMENT
This section has been amended at the state or city level.

1104.20 Stairway Discharge Identification

AMENDMENT
This section has been amended at the state or city level.

1104.21 Exterior Stairway Protection

AMENDMENT
This section has been amended at the state or city level.

1104.22 Minimum Aisle Width

AMENDMENT
This section has been amended at the state or city level.

1104.23 Stairway Floor Number Signs

AMENDMENT
This section has been amended at the state or city level.

1104.24 Egress Path Markings

AMENDMENT
This section has been amended at the state or city level.
Existing tire storage yards shall be provided with fire apparatus access roads in accordance with Sections 1105.1.1 and 1105.1.2.
Access roadways shall be within 150 feet (45 720 mm) of any point in the storage yard where storage piles are located, at least 20 feet (6096 mm) from any storage pile.
Fire apparatus access roads shall be located within all pile clearances identified in Section 3405.4 and within all fire breaks required in Section 3405.5.