ADOPTS WITH AMENDMENTS:

International Energy Conservation Code 2009 (IECC 2009)

Heads up: There are no amended sections in this chapter.

Part 1 — Scope and Application

101.1 Title

AMENDMENT
This section has been amended at the state or city level.
This code applies to residential and commercial buildings.
This code shall regulate the design and construction of buildings for the effective use of energy. This code is intended to provide flexibility to permit the use of innovative approaches and techniques to achieve the effective use of energy. This code is not intended to abridge safety, health or environmental requirements contained in other applicable codes or ordinances.
Where, in any specific case, different sections of this code specify different materials, methods of construction or other requirements, the most restrictive shall govern. Where there is a conflict between a general requirement and a specific requirement, the specific requirement shall govern.
Except as specified in this chapter, this code shall not be used to require the removal, alteration or abandonment of, nor prevent the continued use and maintenance of, an existing building or building system lawfully in existence at the time of adoption of this code.
Any building or structure that is listed in the State or National Register of Historic Places; designated as a historic property under local or state designation law or survey; certified as a contributing resource with a National Register listed or locally designated historic district; or with an opinion or certification that the property is eligible to be listed on the National or State Registers of Historic Places either individually or as a contributing building to a historic district by the State Historic Preservation Officer or the Keeper of the National Register of Historic Places, are exempt from this code.

Additions, alterations, renovations or repairs to an existing building, building system or portion thereof shall conform to the provisions of this code as they relate to new construction without requiring the unaltered portion(s) of the existing building or building system to comply with this code. Additions, alterations, renovations or repairs shall not create an unsafe or hazardous condition or overload existing building systems. An addition shall be deemed to comply with this code if the addition alone complies or if the existing building and addition comply with this code as a single building.

Exception: The following need not comply provided the energy use of the building is not increased:

  1. Storm windows installed over existing fenestration.
  2. Glass only replacements in an existing sash and frame.
  3. Existing ceiling, wall or floor cavities exposed during construction provided that these cavities are filled with insulation.
  4. Construction where the existing roof, wall or floor cavity is not exposed.
  5. Reroofing for roofs where neither the sheathing nor the insulation is exposed. Roofs without insulation in the cavity and where the sheathing or insulation is exposed during reroofing shall be insulated either above or below the sheathing.
  6. Replacement of existing doors that separate conditioned space from the exterior shall not require the installation of a vestibule or revolving door, provided, however, that an existing vestibule that separates a conditioned space from the exterior shall not be removed,
  7. Alterations that replace less than 50 percent of the luminaires in a space, provided that such alterations do not increase the installed interior lighting power.
  8. Alterations that replace only the bulb and ballast within the existing luminaires in a space provided that the alteration does not increase the installed interior lighting power.
Spaces undergoing a change in occupancy that would result in an increase in demand for either fossil fuel or electrical energy shall comply with this code. Where the use in a space changes from one use in Table 505.5.2 to another use in Table 505.5.2, the installed lighting wattage shall comply with Section 505.5.
Any nonconditioned space that is altered to become conditioned space shall be required to be brought into full compliance with this code.
Where a building includes both residential and commercial occupancies, each occupancy shall be separately considered and meet the applicable provisions of Chapter 4 for residential and Chapter 5 for commercial.
Residential buildings shall meet the provisions of Chapter 4. Commercial buildings shall meet the provisions of Chapter 5.
The code official shall be permitted to approve specific computer software, work- sheets, compliance manuals and other similar materials that meet the intent of this code.

The following buildings, or portions thereof, separated from the remainder of the building by building thermal envelope assemblies complying with this code shall be exempt from the building thermal envelope provisions of this code:

  1. Those with a peak design rate of energy usage less than 3.4 Btu/h•ft2 (10.7 W/m2) or 1.0 watt/ft2 (10.7 W/m2) of floor area for space conditioning purposes.
  2. Those that do not contain conditioned space.
This code is not intended to prevent the use of any material, method of construction, design or insulating system not specifically prescribed herein, provided that such construction, design or insulating system has been approved by the code official as meeting the intent of this code.
The code official or other authority having jurisdiction shall be permitted to deem a national, state or local energy efficiency program to exceed the energy efficiency required by this code. Buildings approved in writing by such an energy efficiency program shall be considered in compliance with this code. The requirements identified as "mandatory" in Chapters 4 and 5 of this code, as applicable, shall be met.

Part 2 — Administration

Section 103 Construction Documents

AMENDMENT
This section has been amended at the state or city level.

103.1 General

AMENDMENT
This section has been amended at the state or city level.

103.2 Information on Construction Documents

AMENDMENT
This section has been amended at the state or city level.

103.3 Examination of Documents

AMENDMENT
This section has been amended at the state or city level.

103.3.1 Approval of Construction Documents

AMENDMENT
This section has been amended at the state or city level.

103.3.2 Previous Approvals

AMENDMENT
This section has been amended at the state or city level.

103.3.3 Phased Approval

AMENDMENT
This section has been amended at the state or city level.

103.4 Amended Construction Documents

AMENDMENT
This section has been amended at the state or city level.

103.5 Retention of Construction Documents

AMENDMENT
This section has been amended at the state or city level.

Section 104 Inspections

AMENDMENT
This section has been amended at the state or city level.

104.1 General

AMENDMENT
This section has been amended at the state or city level.

104.2 Required Approvals

AMENDMENT
This section has been amended at the state or city level.

104.3 Final Inspection

AMENDMENT
This section has been amended at the state or city level.

104.4 Reinspection

AMENDMENT
This section has been amended at the state or city level.

104.5 Approved Inspection Agencies

AMENDMENT
This section has been amended at the state or city level.

104.6 Inspection Requests

AMENDMENT
This section has been amended at the state or city level.

104.7 Reinspection and Testing

AMENDMENT
This section has been amended at the state or city level.

104.8 Approval

AMENDMENT
This section has been amended at the state or city level.

104.8.1 Revocation

AMENDMENT
This section has been amended at the state or city level.
If a portion of this code is held to be illegal or void, such a decision shall not affect the validity of the remainder of this code.
The codes and standards referenced in this code shall be those listed in Chapter 6, and such codes and standards shall be considered as part of the requirements of this code to the prescribed extent of each such reference.
Where the provisions of this code and the referenced standards conflict, the provisions of this code shall take precedence.
References to chapter or section numbers, or to provisions not specifically identified by number, shall be construed to refer to such chapter, section or provision of this code.
The provisions of this code shall not be deemed to nullify any provisions of local, state or federal law.

Section 107 Fees

AMENDMENT
This section has been amended at the state or city level.

107.1 Fees

AMENDMENT
This section has been amended at the state or city level.

107.2 Schedule of Permit Fees

AMENDMENT
This section has been amended at the state or city level.

107.3 Work Commencing Before Permit Issuance

AMENDMENT
This section has been amended at the state or city level.

107.4 Related Fees

AMENDMENT
This section has been amended at the state or city level.

107.5 Refunds

AMENDMENT
This section has been amended at the state or city level.

Section 108 Stop Work Order

AMENDMENT
This section has been amended at the state or city level.

108.1 Authority

AMENDMENT
This section has been amended at the state or city level.

108.2 Issuance

AMENDMENT
This section has been amended at the state or city level.

108.3 Emergencies

AMENDMENT
This section has been amended at the state or city level.

108.4 Failure to Comply

AMENDMENT
This section has been amended at the state or city level.

Section 109 Board of Appeals

AMENDMENT
This section has been amended at the state or city level.

109.1 General

AMENDMENT
This section has been amended at the state or city level.

109.2 Limitations on Authority

AMENDMENT
This section has been amended at the state or city level.

109.3 Qualifications

AMENDMENT
This section has been amended at the state or city level.
UpCodes Premium
Leverage the most sophisticated code compliance platform.
TRY FREE FOR TWO WEEKS VISIT PRICING