The provisions of this chapter shall govern the quality, workmanship and requirements for materials covered. Materials of construction and tests shall conform to the applicable standards listed in this code.
New building materials, equipment, appliances, systems or methods of construction not provided for in this code, and any material of questioned suitability proposed for use in the construction of a building or structure, shall be subjected to the tests prescribed in this chapter and in the approved rules to determine character, quality and limitations of use.
The use of second-hand materials that meet the minimum requirements of this code for new materials shall be permitted.
The construction documents for special inspections shall
include:
- The statement of special inspections in accordance with Section 1704.3.
- The following statement:
“Special inspection reports and a final report in accordance with Section 1704.2.4 shall
be submitted to the building official prior to the time that phase of the work is approved
for occupancy.”
(Effective January 1, 2014)
The local building official or authority having jurisdiction shall be
authorized to use ACEC/SEAOG SI GL 01, Georgia Special Inspections Guidelines, in part or in
whole for the purposes of implementing and enforcing the provisions of Chapter 17, 'Special
Inspections and Tests’, and/or establishing a Special Inspections program for their jurisdiction.
(Effective January 1, 2014)
The following terms are defined in
Chapter 2:
An
approved agency shall provide all information as necessary for the
building official to determine that the agency meets the applicable requirements.
An
approved agency shall be objective, competent and independent from the contractor responsible for the work being inspected. The agency shall also disclose possible conflicts of interest so that objectivity can be confirmed.
An
approved agency shall have adequate equipment to perform required tests. The equipment shall be periodically calibrated.
An
approved agency shall employ experienced personnel educated in conducting, supervising and evaluating tests and/or inspections.
Any material, appliance, equipment, system or method of construction meeting the requirements of this code shall be approved in writing after satisfactory completion of the required tests and submission of required test reports.
For any material, appliance, equipment, system or method of construction that has been
approved, a record of such approval, including the conditions and limitations of the approval, shall be kept on file in the
building official's office and shall be open to public inspection at appropriate times.
Specific information consisting of test reports conducted by an
approved testing agency in accordance with the appropriate referenced standards, or other such information as necessary, shall be provided for the
building official to determine that the material meets the applicable code requirements.
Sufficient technical data shall be submitted to the
building official to substantiate the proposed use of any material or assembly. If it is determined that the evidence submitted is satisfactory proof of performance for the use intended, the
building official shall approve the use of the material or assembly subject to the requirements of this code. The costs, reports and investigations required under these provisions shall be paid by the applicant.
Supporting data, where necessary to assist in the approval of materials or assemblies not specifically provided for in this code, shall consist of valid research reports from approved sources.
Where materials or assemblies are required by this code to be
labeled, such materials and assemblies shall be
labeled by an
approved agency in accordance with
Section 1703. Products and materials required to be
labeled shall be
labeled in accordance with the procedures set forth in Sections
1703.5.1 through
1703.5.4.
An
approved agency shall test a representative sample of the product or material being
labeled to the relevant standard or standards. The
approved agency shall maintain a record of the tests performed. The record shall provide sufficient detail to verify compliance with the test standard.
The
approved agency shall periodically perform an inspection, which shall be in-plant if necessary, of the product or material that is to be
labeled. The inspection shall verify that the
labeled product or material is representative of the product or material tested.
The
label shall contain the manufacturer’s or distributor’s identification, model number, serial number or definitive information describing the product or material’s performance characteristics and
approved agency’s identification.
Information required to be permanently identified on the product shall be acid etched, sand blasted, ceramic fired, laser etched, embossed or of a type that, once applied, cannot be removed without being destroyed.
Where structural components or other items regulated by this code are not visible for inspection after completion of a prefabricated assembly, the applicant shall submit a report of each prefabricated assembly. The report shall indicate the complete details of the assembly, including a description of the assembly and its components, the basis upon which the assembly is being evaluated, test results and similar information and other data as necessary for the
building official to determine conformance to this code. Such a report shall be
approved by the
building official.
The applicant shall provide for
special inspections of
fabricated items in accordance with
Section 1704.2.5.
Copies of necessary test and inspection records shall be filed with the
building official.
This section provides minimum requirements for
special inspections, the statement of
special inspections, contractor responsibility and
structural observations.
Where application is made for construction as described in this section, the
owner or the
registered design professional in responsible charge acting as the
owner’s agent shall employ one or more
approved agencies to perform inspections during construction on the types of work listed under
Section 1705. These inspections are in addition to the inspections identified in
Section 110.
Exceptions:
Deleted
Where application is made for construction as described in this section, the owner or the
registered design professional in responsible charge acting as the owner’s agent shall employ one or more
approved agencies to perform inspections during construction on the types of work listed under Section 1705. These inspections are in addition to the inspections identified in Section 110.
Exceptions:
1. Special inspections are not required for construction of a minor nature or as warranted by conditions in the jurisdiction as approved by the building official.
Deleted
2. Unless otherwise required by the building official, special inspections are not required for Group U occupancies that are accessory to a residential occupancy including, but not limited to, those listed in Section 312.1.
3. Special inspections are not required for portions of structures designed and constructed in accordance with the cold-formed steel light-frame construction provisions of Section 2211.7 or the conventional light-frame construction provisions of Section 2308.
Where application is made for construction as described in this
section, the owner or the registered design professional in responsible charge acting as the
owner’s agent shall employ one or more approved agencies to perform inspections during
construction on the types of work listed under Section 1705. These inspections are in addition to
the inspections identified in Section 110.
Exceptions:
- Special inspections are not required for construction of a minor nature that does not
require the practice of professional engineering or architecture, as defined by Georgia
statutes and regulations governing the professional registration and certification of
engineers or architects or as warranted by conditions in the jurisdiction as approved by the
building official.
- Unless otherwise required by the building official, special inspections are not required for
Group U occupancies that are accessory to a residential occupancy including, but not
limited to, those listed in Section 312.1.
- Special inspections are not required for portions of structures designed and constructed in
accordance with the cold-formed steel light-frame construction provisions of Section
2211.7 or the conventional light-frame construction provisions of Section 2308.
(Effective January 1, 2014)
The
special inspector shall provide written documentation to the
building official demonstrating his or her competence and relevant experience or training. Experience or training shall be considered relevant when the documented experience or training is related in complexity to the same type of
special inspection activities for projects of similar complexity and material qualities. These qualifications are in addition to qualifications specified in other sections of this code.
The special inspector shall provide written documentation to the building official demonstrating his or her competence and relevant experience or training. Experience or training shall be considered relevant when the documented experience or training is related in complexity to the same type of
special inspection activities for projects of similar complexity and material qualities. The special inspector shall be qualified in accordance with Table 1704.2. These qualifications are in addition to qualifications specified in other sections of this code.
The registered design professional in responsible charge and engineers of record involved in the design of the project are permitted to act as the approved agency and their personnel are permitted to act as the special inspector for the work designed by them, provided they qualify as special inspectors.
(Effective January 1, 2014)
The construction or work for which
special inspection is required shall remain accessible and exposed for
special inspection purposes until completion of the required
special inspections.
The applicant shall submit a statement of
special inspections in accordance with
Section 107.1 as a condition for
permit issuance. This statement shall be in accordance with
Section 1704.3.
Exception: A statement of special inspections is not required for portions of structures designed and constructed in accordance with the cold-formed steel light-frame construction provisions of Section 2211.7 or the conventional light-frame construction provisions of Section 2308.
Deleted
Special inspectors shall keep records of inspections. The special inspector shall furnish inspection reports to the building official, and to the registered design professional in responsible charge. Reports shall indicate that work inspected was or was not completed in conformance to approved construction documents. Discrepancies shall be brought to the immediate attention of the contractor for correction. If they are not corrected, the discrepancies shall be brought to the attention of the building official and to the registered design professional in responsible charge prior to the completion of that phase of the work. A final report documenting required special inspections and correction of any discrepancies noted in the inspections shall be submitted at a point in time agreed upon prior to the start of work by the applicant and the building official.
Special inspectors shall keep records of inspections. The special
inspector shall furnish inspection reports to the building official, and to the registered design
professional in responsible charge. Reports shall indicate that work inspected was or was not
completed in conformance to approved construction documents. Discrepancies shall be brought
to the immediate attention of the contractor for correction. If they are not corrected, the
discrepancies shall be brought to the attention of the building official and to the registered design
professional in responsible charge prior to the completion of that phase of the work. A final
report documenting required special inspections and correction of any discrepancies noted in the
inspections shall be submitted to the building official prior to the time that phase of the work is
approved for occupancy.
(Effective January 1, 2014)
Where fabrication of structural load-bearing members and assemblies is being performed on the premises of a fabricator’s shop,
special inspection of the
fabricated items shall be required by this section and as required elsewhere in this code.
The
special inspector shall verify that the fabricator maintains detailed fabrication and quality control procedures that provide a basis for inspection control of the workmanship and the fabricator’s ability to conform to
approved construction documents and referenced standards. The
special inspector shall review the procedures for completeness and adequacy relative to the code requirements for the fabricator’s scope of work.
Exception: Special inspections as required by Section 1704.2.5 shall not be required where the fabricator is approved in accordance with Section 1704.2.5.2.
Special inspections required by
Section 1705 are not required where the work is done on the premises of a fabricator registered and
approved to perform such work without
special inspection. Approval shall be based upon review of the fabricator’s written procedural and quality control manuals and periodic auditing of fabrication practices by an
approved special inspection agency. At completion of fabrication, the
approved fabricator shall submit a
certificate of compliance to the
building official stating that the work was performed in accordance with the
approved construction documents.
Relocated
Where
special inspection or testing is required by
Section 1705, the
registered design professional in responsible charge shall prepare a statement of
special inspections in accordance with
Section 1704.3.1 for submittal by the applicant in accordance with
Section 1704.2.3.
The statement of
special inspections shall identify the following:
3. The type and extent of each test.
Where
Section 1705.11 or
1705.12 specifies
special inspection, testing or qualification for seismic resistance, the statement of
special inspections shall identify the
designated seismic systems and
seismic force-resisting systems that are subject to
special inspection.
Where
Section 1705.10 specifies
special inspection for wind requirements, the statement of
special inspections shall identify the
main windforce-resisting systems and wind-resisting components subject to
special inspection.
Relocated
Each contractor responsible for the construction of a main wind- or
seismic force-resisting system,
designated seismic system or a wind- or seismic-resisting component listed in the statement of
special inspections shall submit a written statement of responsibility to the
building official and the
owner prior to the commencement of work on the system or component. The contractor’s statement of responsibility shall contain acknowledgement of awareness of the special requirements contained in the statement of
special inspection.
Relocated
Where required by the provisions of
Section 1704.5.1 or
1704.5.2, the
owner shall employ a
registered design professional to perform
structural observations as defined in
Section 202.
Prior to the commencement of observations, the structural observer shall submit to the building official a written statement identifying the frequency and extent of structural observations.
At the conclusion of the work included in the permit, the structural observer shall submit to the building official a written statement that the site visits have been made and identify any reported deficiencies which, to the best of the structural observer’s knowledge, have not been resolved.
Structural observations shall be provided for those structures assigned to
Seismic Design Category D, E or F where one or more of the following conditions exist:
2. The height of the structure is greater than 75 feet (22 860 mm) above the base.
Structural observations shall be provided for those structures sited where
Vasd as determined in accordance with
Section 1609.3.1 exceeds 110 mph (49 m/sec), where one or more of the following conditions exist:
2. The
building height of the structure is greater than 75 feet (22 860 mm).
Verification and inspection of elements of buildings and structures shall be as required by this section.
Relocated
Special inspections shall be required for proposed work that is, in the opinion of the
building official, unusual in its nature, such as, but not limited to, the following examples:
1. Construction materials and systems that are alternatives to materials and systems prescribed by this code.
2. Unusual design applications of materials described in this code.
3. Materials and systems required to be installed in accordance with additional manufacturer’s instructions that prescribe requirements not contained in this code or in standards referenced by this code.
Relocated
The
special inspections for steel elements of buildings and structures shall be as required in this section.
Exception: Special inspection of the steel fabrication process shall not be required where the fabricator does not perform any welding, thermal cutting or heating operation of any kind as part of the fabrication process. In such cases, the fabricator shall be required to submit a detailed procedure for material control that demonstrates the fabricator's ability to maintain suitable records and procedures such that, at any time during the fabrication process, the material specification, and
grade for the main stress-carrying elements are capable of being determined. Mill test reports shall be identifiable to the main stress-carrying elements when required by the approved
construction documents.
Deleted
Special inspection for structural steel shall be in accordance with the quality assurance inspection requirements of AISC 360.
Special inspection for steel construction other than structural steel shall be in accordance with Table 1705.2.2 and this section.
TABLE 1705.2.2
REQUIRED VERIFICATION AND INSPECTION OF STEEL CONSTRUCTION OTHER THAN STRUCTURAL STEEL
VERIFICATION AND INSPECTION | CONTINUOUS | PERIODIC | REFERENCED STANDARDa |
1.Material verification of cold-formed steel deck: |
a.Identification markings to conform to ASTM standards specified in the approved construction documents. | — | X | Applicable ASTM material standards |
b.Manufacturer’s certified test reports. | — | X | |
2.Inspection of welding: |
a.Cold-formed steel deck: |
1)Floor and roof deck welds. | — | X | AWS D1.3 |
b.Reinforcing steel: | | | |
1)Verification of weldability of reinforcing steel other than ASTM A 706. | — | X | AWS D1.4 ACI 318: Section 3.5.2 |
2)Reinforcing steel resisting flexural and axial forces in intermediate and special moment frames, and boundary elements of special structural walls of concrete and shear reinforcement. | X | — |
3)Shear reinforcement. | X | — |
4)Other reinforcing steel. | — | X |
For SI: 1 inch = 25.4 mm.
Welding inspection and welding inspector qualification shall be in accordance with this section.
Deleted
Welding inspection and welding inspector qualification for cold-formed steel floor and
roof decks shall be in accordance with AWS D1.3.
Welding inspection and welding inspector qualification for reinforcing steel shall be in accordance with AWS D1.4 and ACI 318.
Deleted
Where a cold-formed steel truss clear span is 60 feet (18 288 mm) or greater, the
special inspector shall verify that the temporary installation restraint/bracing and the permanent individual truss member restraint/bracing are installed in accordance with the
approved truss submittal package.
The
special inspections and verifications for
concrete construction shall be as required by this section and Table 1705.3.
1. Isolated spread
concrete footings of buildings three
stories or less above
grade plane that are fully supported on earth or rock.
2.2. The footings are designed in accordance with
Table 1809.7; or
2.3. The structural design of the footing is based on a specified compressive
strength,
f '
c, no greater than 2,500 pounds per square inch (psi) (17.2 MPa), regardless of the compressive
strength specified in the
construction documents or used in the footing construction.
3. Nonstructural
concrete slabs supported directly on the ground, including prestressed slabs on
grade, where the effective prestress in the
concrete is less than 150 psi (1.03 MPa).
TABLE 1705.3
REQUIRED VERIFICATION AND INSPECTION OF CONCRETE CONSTRUCTION
VERIFICATION AND INSPECTION | CONTINUOUS | PERIODIC | REFERENCED STANDARDa | IBC REFERENCE |
1. Inspection of reinforcing steel, including prestressing tendons, and placement. | — | X | ACI 318: 3.5, 7.1-7.7 | 1910.4 |
2. Inspection of reinforcing steel welding in accordance with Table 1705.2.2, Item 2b. | — | — | AWS D1.4 ACI 318: 3.5.2 | — |
3. Inspection of anchors cast in concrete where allowable loads have been increased or where strength design is used. | — | X | ACI 318: 8.1.3, 21.1.8 | 1908.5, 1909.1 |
4. Inspection of anchors post-installed in hardened concrete membersb. | — | X | ACI 318: 3.8.6, 8.1.3, 21.1.8 | 1909.1 |
5. Verifying use of required design mix. | — | X | ACI 318: Ch. 4, 5.2-5.4 | 1904.2, 1910.2, 1910.3 |
6. At the time fresh concrete is sampled to fabricate specimens for strength tests, perform slump and air content tests, and determine the temperature of the concrete. | X | — | ASTM C 172 ASTM C 31 ACI 318: 5.6, 5.8 | 1910.10 |
7. Inspection of concrete and shotcrete placement for proper application techniques. | X | — | ACI 318: 5.9, 5.10 | 1910.6, 1910.7, 1910.8 |
8. Inspection for maintenance of specified curing temperature and techniques. | — | X | ACI 318: 5.11-5.13 | 1910.9 |
9. Inspection of prestressed concrete: | | | | |
a. Application of prestressing forces. b. Grouting of bonded prestressing tendons in the seismic force-resisting system. | X X | — | ACI 318: 18.20 ACI 318: 18.18.4 | — |
10. Erection of precast concrete members. | — | X | ACI 318: Ch. 16 | — |
11. Verification of in-situ concrete strength, prior to stressing of tendons in post-tensioned concrete and prior to removal of shores and forms from beams and structural slabs. | — | X | ACI 318: 6.2 | — |
12. Inspect formwork for shape, location and dimensions of the concrete member being formed. | — | X | ACI 318: 6.1.1 | — |
For SI: 1 inch = 25.4 mm.
In the absence of sufficient data or documentation providing evidence of conformance to quality standards for materials in Chapter 3 of ACI 318, the
building official shall require testing of materials in accordance with the appropriate standards and criteria for the material in Chapter 3 of ACI 318. Weldability of reinforcement, except that which conforms to ASTM A 706, shall be determined in accordance with the requirements of Section 3.5.2 of ACI 318.
Masonry construction shall be inspected and verified in accordance with TMS 402/ACI 530/ASCE 5 and TMS 602/ACI 530.1/ASCE 6 quality assurance program requirements.
The minimum
special inspection program for empirically designed
masonry,
glass unit masonry or
masonry veneer designed by
Section 2109,
2110 or
Chapter 14, respectively, in structures classified as
Risk Category IV, in accordance with Section 1604.5, shall comply with TMS 402/ACI 530/ASCE 5 Level B Quality Assurance.
Deleted
Relocated
Special inspection shall be performed in accordance with
Section 1705.4 for vertical
masonry foundation elements.
Special inspections of the fabrication process of prefabricated wood structural elements and assemblies shall be in accordance with
Section 1704.2.5.
Special inspections of
site-built assemblies shall be in accordance with this section.
High-load
diaphragms designed in accordance with
Section 2306.2 shall be installed with
special inspections as indicated in
Section 1704.2. The
special inspector shall inspect the
wood structural panel sheathing to ascertain whether it is of the
grade and thickness shown on the
approved building plans. Additionally, the
special inspector must verify the
nominal size of framing members at adjoining
panel edges, the nail or staple diameter and length, the number of fastener lines and that the spacing between fasteners in each line and at edge margins agrees with the
approved building plans.
Where a truss clear span is 60 feet (18 288 mm) or greater, the
special inspector shall verify that the temporary installation restraint/bracing and the permanent individual truss member restraint/bracing are installed in accordance with the
approved truss submittal package.
Special inspections for existing
site soil conditions, fill placement and load-bearing requirements shall be as required by this section and Table 1705.6. The
approved geotechnical report, and the
construction documents prepared by the
registered design professionals shall be used to determine compliance. During fill placement, the
special inspector shall determine that proper materials and procedures are used in accordance with the provisions of the
approved geotechnical report.
Exception: Where
Section 1803 does not require reporting of materials and procedures for fill placement, the
special inspector shall verify that the in-place dry density of the compacted fill is not less than 90 percent of the maximum dry density at optimum moisture content determined in accordance with ASTM D 1557.
TABLE 1705.6
REQUIRED VERIFICATION AND INSPECTION OF SOILS
VERIFICATION AND INSPECTION TASK | CONTINUOUS DURING TASK LISTED | PERIODICALLY DURING TASK LISTED |
1. Verify materials below shallow foundations are adequate to achieve the design bearing capacity. | — | X |
2. Verify excavations are extended to proper depth and have reached proper material. | — | X |
3. Perform classification and testing of compacted fill materials. | — | X |
4. Verify use of proper materials, densities and lift thicknesses during placement and compaction of compacted fill. | X | — |
5. Prior to placement of compacted fill, observe subgrade and verify that site has been prepared properly. | — | X |
Special inspections shall be performed during installation and testing of driven
deep foundation elements as required by Table 1705.7. The
approved geotechnical report and the
construction documents prepared by the
registered design professionals, shall be used to determine compliance.
TABLE 1705.7
REQUIRED VERIFICATION AND INSPECTION OF DRIVEN DEEP FOUNDATION ELEMENTS
VERIFICATION AND INSPECTION TASK | CONTINUOUS DURING TASK LISTED | PERIODICALLY DURING TASK LISTED |
1. Verify element materials, sizes and lengths comply with the requirements. | X | — |
2. Determine capacities of test elements and conduct additional load tests, as required. | X | — |
3. Observe driving operations and maintain complete and accurate records for each element. | X | — |
4. Verify placement locations and plumbness, confirm type and size of hammer, record number of blows per foot of penetration, determine required penetrations to achieve design capacity, record tip and butt elevations and document any damage to foundation element. | X | — |
5. For steel elements, perform additional inspections in accordance with Section 1705.2. | — | — |
6. For concrete elements and concrete-filled elements, perform additional inspections in accordance with Section 1705.3. | — | — |
7. For specialty elements, perform additional inspections as determined by the registered design professional in responsible charge. | — | — |
Special inspections shall be performed during installation and testing of cast-in-place
deep foundation elements as required by Table 1705.8. The
approved geotechnical report, and the
construction documents prepared by the
registered design professionals, shall be used to determine compliance.
TABLE 1705.8
REQUIRED VERIFICATION AND INSPECTION OF CAST-IN-PLACE DEEP FOUNDATION ELEMENTS
VERIFICATION AND INSPECTION TASK | CONTINUOUS DURING TASK LISTED | PERIODICALLY DURING TASK LISTED |
1. Observe drilling operations and maintain complete and accurate records for each element. | X | — |
2. Verify placement locations and plumbness, confirm element diameters, bell diameters (if applicable), lengths, embedment into bedrock (if applicable) and adequate end-bearing strata capacity. Record concrete or grout volumes. | X | — |
3. For concrete elements, perform additional inspections in accordance with Section 1705.3. | — | — |
Special inspections shall be performed continuously during installation of
helical pile foundations. The information recorded shall include installation equipment used, pile
dimensions, tip elevations, final depth, final installation torque and other pertinent installation data as required by the
registered design professional in responsible charge. The
approved geotechnical report and the
construction documents prepared by the
registered design professional shall be used to determine compliance.
Relocated
Relocated
Special inspections itemized in Sections
1705.10.1 through
1705.10.3, unless exempted by the exceptions to
Section 1704.2, are required for buildings and structures constructed in the following areas:
1. In wind Exposure Category B, where
Vasd as determined in accordance with
Section 1609.3.1 is 120 miles per hour (52.8 m/sec) or greater.
2. In wind Exposure Category C or D, where
Vasd as determined in accordance with
Section 1609.3.1 is
110 mph (49 m/sec) or greater.
Continuous special inspection is required during field gluing operations of elements of the
main windforce-resisting system.
Periodic special inspection is required for nailing, bolting, anchoring and other fastening of components within the
main windforce-resisting system, including wood
shear walls, wood
diaphragms,
drag struts, braces and hold-downs.
Exception: Special inspection is not required for wood shear walls, shear panels and diaphragms, including nailing, bolting, anchoring and other fastening to other components of the main windforce-resisting system, where the fastener spacing of the sheathing is more than 4 inches (102 mm) on center.
Periodic special inspection is required during welding operations of elements of the
main windforce-resisting system.
Periodic special inspection is required for screw attachment, bolting, anchoring and other fastening of components within the
main windforce-resisting system, including
shear walls, braces,
diaphragms,
collectors (
drag struts) and hold-downs.
Exception: Special inspection is not required for cold-formed steel light-frame shear walls, braces, diaphragms, collectors (drag struts) and hold-downs where either of the following apply:
Periodic special inspection is required for the following systems and components:
1. Roof cladding.
Special inspections itemized in Sections
1705.11.1 through
1705.11.8, unless exempted by the exceptions of
Section 1704.2, are required for the following:
3. Architectural, mechanical and electrical components in accordance with Sections
1705.11.5 and
1705.11.6.
3. The structure is a detached one- or two-family
dwelling not exceeding two
stories above grade plane and does not have any of the following horizontal or vertical irregularities in accordance with Section 12.3 of ASCE 7:
3.1. Torsional or extreme torsional irregularity.
3.2. Nonparallel systems irregularity.
3.3. Stiffness-soft
story or stiffness-extreme soft
story irregularity.
Special inspection for structural steel shall be in accordance with the quality assurance requirements of AISC 341.
Exception: Special inspections of structural steel in structures assigned to Seismic Design Category C that are not specifically detailed for seismic resistance, with a response modification coefficient, R, of 3 or less, excluding cantilever column systems.
Continuous special inspection is required during field gluing operations of elements of the
seismic force-resisting system.
Periodic special inspection is required for nailing, bolting, anchoring and other fastening of components within the
seismic force-resisting system, including wood
shear walls, wood
diaphragms,
drag struts, braces, shear
panels and hold-downs.
Exception: Special inspection is not required for wood shear walls, shear panels and diaphragms, including nailing, bolting, anchoring and other fastening to other components of the seismic force-resisting system, where the fastener spacing of the sheathing is more than 4 inches (102 mm) on center (o.c.).
Periodic special inspection is required during welding operations of elements of the
seismic force-resisting system.
Periodic special inspection is required for screw attachment, bolting, anchoring and other fastening of components within the
seismic force-resisting system, including
shear walls, braces,
diaphragms,
collectors (
drag struts) and hold-downs.
Exception: Special inspection is not required for cold-formed steel light-frame shear walls, braces, diaphragms, collectors (drag struts) and hold-downs where either of the following apply:
Deleted
Relocated
The
special inspector shall examine
designated seismic systems requiring seismic qualification in accordance with
Section 1705.12.3 and verify that the
label, anchorage or mounting conforms to the
certificate of compliance.
Periodic
special inspection is required during the erection and fastening of exterior cladding, interior and exterior nonbearing
walls and interior and exterior
veneer in structures assigned to
Seismic Design Category D, E or F.
Exceptions:
1.
Special inspection is not required for exterior cladding, interior and exterior nonbearing
walls and interior and exterior
veneer 30 feet (9144 mm) or less in height above
grade or walking surface.
2.
Special inspection is not required for exterior cladding and interior and exterior
veneer weighing 5 psf (24.5 N/m
2) or less.
Periodic
special inspection is required for the anchorage of access floors in structures assigned to
Seismic Design Category D, E or F.
Special inspection for mechanical and electrical components shall be as follows:
Relocated
Periodic
special inspection is required for the anchorage of storage racks 8 feet (2438 mm) or greater in height in structures assigned to
Seismic Design Category D, E or F.
Periodic special inspection shall be provided for seismic isolation systems during the fabrication and installation of isolator units and energy dissipation devices.
The testing and qualification specified in Sections
1705.12.1 through
1705.12.4, unless exempted from
special inspections by the exceptions of
Section 1704.2 are required as follows:
3. Architectural, mechanical and electrical components in structures assigned to
Seismic Design Category C, D, E or F and where the requirements of ASCE 7 Section 13.2.1 are met by submittal of manufacturer’s certification, in accordance with Item 2 therein, shall comply with
Section 1705.12.3.
4. The seismic isolation system in seismically isolated structures shall meet the testing requirements of
Section 1705.12.4.
Where reinforcement complying with ASTM A 615 is used to resist earthquake-induced flexural and axial forces in special moment frames, special structural
walls and coupling beams connecting special structural
walls, in structures assigned to
Seismic Design Category B, C, D, E or F, the reinforcement shall comply with Section 21.1.5.2 of ACI 318. Certified mill test reports shall be provided for each shipment of such reinforcement. Where reinforcement complying with ASTM A 615 is to be welded, chemical tests shall be performed to determine weldability in accordance with Section 3.5.2 of ACI 318.
Testing for structural steel shall be in accordance with the quality assurance requirements of AISC 341.
Exception: Testing for structural steel in structures assigned to Seismic Design Category C that are not specifically detailed for seismic resistance, with a response modification coefficient, R, of 3 or less, excluding cantilever column systems.
Deleted
The
registered design professional shall specify on the
construction documents the requirements for certification by analysis, testing or experience data for nonstructural components and
designated seismic systems in accordance with Section 13.2 of ASCE 7, where such certification is required by Section 1705.12.
Deleted
Seismic isolation systems shall be tested in accordance with Section 17.8 of ASCE 7.
Special inspections for
sprayed fire-resistant materials applied to floor, roof and
wall assemblies and structural members shall be in accordance with Sections
1705.13.1 through
1705.13.6.
Special inspections shall be based on the fire-resistance design as designated in the
approved construction documents. The tests set forth in this section shall be based on samplings from specific floor, roof and
wall assemblies and structural members.
Special inspections shall be performed after the rough installation of electrical,
automatic sprinkler, mechanical and plumbing systems and suspension systems for ceilings, where applicable.
The
special inspections shall include the following tests and observations to demonstrate compliance with the listing and the
fire-resistance rating:
1. Condition of substrates.
2. Thickness of application.
3. Density in pounds per cubic foot (kg/m3).
5. Condition of finished application.
The surfaces shall be prepared in accordance with the approved fire-resistance design and the written instructions of approved manufacturers. The prepared surface of structural members to be sprayed shall be inspected before the application of the sprayed fire-resistant material.
The substrate shall have a minimum ambient temperature before and after application as specified in the written instructions of approved manufacturers. The area for application shall be ventilated during and after application as required by the written instructions of approved manufacturers.
No more than 10 percent of the thickness measurements of the
sprayed fire-resistant materials applied to floor, roof and
wall assemblies and structural members shall be less than the thickness required by the
approved fire-resistance design, but in no case less than the minimum allowable thickness required by
Section 1705.13.4.1.
For design thicknesses 1 inch (25 mm) or greater, the minimum allowable individual thickness shall be the design thickness minus
1/
4 inch (6.4 mm). For design thicknesses less than 1 inch (25 mm), the minimum allowable individual thickness shall be the design thickness minus 25 percent. Thickness shall be determined in accordance with ASTM E 605. Samples of the
sprayed fire-resistant materials shall be selected in accordance with Sections
1705.13.4.2 and
1705.13.4.3.
The thickness of the sprayed fire-resistant material applied to floor, roof and
wall assemblies shall be determined in accordance with ASTM E 605, making not less than four measurements for each 1,000 square feet (93 m
2) of the sprayed area, or portion thereof, in each
story.
Thickness measurements shall be selected from a square area, 12 inches by 12 inches (305 mm by 305 mm) in size. A minimum of four measurements shall be made, located symmetrically within the square area.
Thickness measurements shall be selected from a square area, 12 inches by 12 inches (305 mm by 305 mm) in size. A minimum of four measurements shall be made, located symmetrically within the square area, including one each of the following: valley, crest and sides. The average of the measurements shall be reported.
The thickness of the sprayed fire-resistant material applied to structural members shall be determined in accordance with ASTM E 605. Thickness testing shall be performed on not less than 25 percent of the structural members on each floor.
At beams and girders thickness measurements shall be made at nine locations around the beam or girder at each end of a 12-inch (305 mm) length.
At joists and trusses, thickness measurements shall be made at seven locations around the joist or truss at each end of a 12-inch (305 mm) length.
At wide- flanged columns, thickness measurements shall be made at 12 locations around the column at each end of a 12-inch (305 mm) length.
At
hollow structural section and pipe columns, thickness measurements shall be made at a minimum of four locations around the column at each end of a 12-inch (305 mm) length.
The density of the sprayed fire-resistant material shall not be less than the density specified in the
approved fire-resistance design. Density of the sprayed fire-resistant material shall be determined in accordance with ASTM E 605. The test samples for determining the density of the
sprayed fire-resistant materials shall be selected as follows:
1. From each floor, roof and
wall assembly at the rate of not less than one sample for every 2,500 square feet (232 m
2) or portion thereof of the sprayed area in each
story.
2. From beams, girders, trusses and columns at the rate of not less than one sample for each type of structural member for each 2,500 square feet (232 m
2) of floor area or portion thereof in each
story.
The cohesive/adhesive bond
strength of the cured sprayed fire-resistant material applied to floor, roof and
wall assemblies and structural members shall not be less than 150 pounds per square foot (psf) (7.18 kN/m
2). The cohesive/adhesive bond
strength shall be determined in accordance with the field test specified in ASTM E 736 by testing in-place samples of the sprayed fire-resistant material selected in accordance with Sections
1705.13.6.1 through
1705.13.6.3.
The test samples for determining the cohesive/adhesive bond
strength of the
sprayed fire-resistant materials shall be selected from each floor, roof and
wall assembly at the rate of not less than one sample for every 2,500 square feet (232 m
2) of the sprayed area, or portion thereof, in each
story.
The test samples for determining the cohesive/adhesive bond
strength of the
sprayed fire-resistant materials shall be selected from beams, girders, trusses, columns and other structural members at the rate of not less than one sample for each type of structural member for each 2,500 square feet (232 m
2) of floor area or portion thereof in each
story.
Bond tests to qualify a primer, paint or encapsulant shall be conducted when the sprayed fire-resistant material is applied to a primed, painted or encapsulated surface for which acceptable bond-
strength performance between these coatings and the fire-resistant material has not been determined. A bonding agent
approved by the SFRM manufacturer shall be applied to a primed, painted or encapsulated surface where the bond
strengths are found to be less than required values.
Special inspections for mastic and
intumescent fire-resistant coatings applied to structural elements and decks shall be in accordance with AWCI 12-B.
Special inspections shall be based on the fire-resistance design as designated in the
approved construction documents.
Relocated
Special inspections shall be required for all EIFS applications.
Exceptions:
A
water-resistive barrier coating complying with ASTM E 2570 requires
special inspection of the
water-resistive barrier coating when installed over a sheathing substrate.
Relocated
In
high-rise buildings or in buildings assigned to
Risk Category III or IV in accordance with
Section 1604.5,
special inspections for through-penetrations,
membrane penetration firestops, fire-resistant
joint systems, and perimeter
fire barrier systems that are tested and listed in accordance with Sections
714.3.1.2,
714.4.1.2,
715.3 and
715.4 shall be in accordance with
Section 1705.16.1 or
1705.16.2.
Inspections of
penetration firestop systems that are tested and listed in accordance with Sections
714.3.1.2 and
714.4.1.2 shall be conducted by an approved inspection agency in accordance with ASTM E 2174.
Inspection of fire-resistant
joint systems that are tested and listed in accordance with Sections
715.3 and
715.4 shall be conducted by an approved inspection agency in accordance with ASTM E 2393.
Smoke control systems shall be tested by a
special inspector.
The test scope shall be as follows:
1. During erection of ductwork and prior to concealment for the purposes of leakage testing and recording of device location.
2. Prior to occupancy and after sufficient completion for the purposes of pressure difference testing, flow measurements and detection and control verification.
Special inspection agencies for smoke control shall have expertise in fire protection engineering, mechanical engineering and certification as air balancers.
Relocated
Deleted
The
design strengths and permissible stresses of any structural material that are identified by a
manufacturer’s designation as to manufacture and
grade by mill tests, or the
strength and stress
grade is otherwise confirmed to the satisfaction of the
building official, shall conform to the specifications and methods of design of accepted engineering practice or the
approved rules in the absence of applicable standards.
For materials that are not specifically provided for in this code, the
design strengths and permissible stresses shall be established by tests as provided for in
Section 1707.
In the absence of
approved rules or other
approved standards, the
building official shall make, or cause to be made, the necessary tests and investigations; or the
building official shall accept duly authenticated reports from
approved agencies in respect to the quality and manner of use of new materials or assemblies as provided for in
Section 104.11. The cost of all tests and other investigations required under the provisions of this code shall be borne by the applicant.
Where proposed construction is not capable of being designed by
approved engineering analysis, or where proposed construction design method does not comply with the applicable material design standard, the system of construction or the structural unit and the connections shall be subjected to the tests prescribed in
Section 1710. The
building official shall accept certified reports of such tests conducted by an
approved testing agency, provided that such tests meet the requirements of this code and
approved procedures.
Relocated
Whenever there is a reasonable doubt as to the stability or load-bearing capacity of a completed building, structure or portion thereof for the expected
loads, an engineering assessment shall be required. The engineering assessment shall involve either a structural analysis or an in-situ load test, or both. The structural analysis shall be based on actual material properties and other as-built conditions that affect stability or load-bearing capacity, and shall be conducted in accordance with the applicable design standard. If the structural assessment determines that the load-bearing capacity is less than that required by the code, load tests shall be conducted in accordance with
Section 1709.2. If the building, structure or portion thereof is found to have inadequate stability or load-bearing capacity for the expected
loads, modifications to ensure structural adequacy or the removal of the inadequate construction shall be required.
Structural components and assemblies shall be tested in accordance with the appropriate referenced standards. In the absence of a standard that contains an applicable load test procedure, the test procedure shall be developed by a
registered design professional and
approved. The test procedure shall simulate
loads and conditions of application that the completed structure or portion thereof will be subjected to in normal use.
In-situ load tests shall be conducted in accordance with
Section 1709.3.1 or
1709.3.2 and shall be supervised by a
registered design professional. The test shall simulate the applicable loading conditions specified in
Chapter 16 as necessary to address the concerns regarding structural stability of the building, structure or portion thereof.
Where a referenced standard contains an applicable load test procedure and acceptance criteria, the test procedure and acceptance criteria in the standard shall apply. In the absence of specific
load factors or acceptance criteria, the
load factors and acceptance criteria in
Section 1709.3.2 shall apply.
In the absence of applicable load test procedures contained within a standard referenced by this code or acceptance criteria for a specific material or method of construction, such
existing structure shall be subjected to a test procedure developed by a
registered design professional that simulates applicable loading and deformation conditions. For components that are not a part of the seismic load-resisting system, the test load shall be equal to two times the unfactored design
loads. The test load shall be left in place for a period of 24 hours. The structure shall be considered to have successfully met the test requirements where the following criteria are satisfied:
1. Under the design load, the deflection shall not exceed the limitations specified in
Section 1604.3.
2. Within 24 hours after removal of the test load, the structure shall have recovered not less than 75 percent of the maximum deflection.
3. During and immediately after the test, the structure shall not show evidence of failure.
In evaluating the physical properties of materials and methods of construction that are not capable of being designed by approved engineering analysis or do not comply with the applicable referenced standards, the structural adequacy shall be predetermined based on the load test criteria established in this section.
Where specific load test procedures,
load factors and acceptance criteria are included in the applicable referenced standards, such test procedures,
load factors and acceptance criteria shall apply. In the absence of specific test procedures,
load factors or acceptance criteria, the corresponding provisions in
Section 1710.3 shall apply.
Where load test procedures are not specified in the applicable referenced standards, the load-bearing and deformation capacity of structural components and assemblies shall be determined on the basis of a test procedure developed by a
registered design professional that simulates applicable loading and deformation conditions. For components and assemblies that are not a part of the
seismic force-resisting system, the test shall be as specified in
Section 1710.3.1. Load tests shall simulate the applicable loading conditions specified in
Chapter 16.
The test assembly shall be subjected to an increasing superimposed load equal to not less than two times the superimposed design load. The test load shall be left in place for a period of 24 hours. The tested assembly shall be considered to have successfully met the test requirements if the assembly recovers not less than 75 percent of the maximum deflection within 24 hours after the removal of the test load. The test assembly shall then be reloaded and subjected to an increasing superimposed load until either structural failure occurs or the superimposed load is equal to two and one-half times the load at which the deflection limitations specified in
Section 1710.3.2 were reached, or the load is equal to two and one-half times the superimposed design load. In the case of structural components and assemblies for which deflection limitations are not specified in
Section 1710.3.2, the test specimen shall be subjected to an increasing superimposed load until structural failure occurs or the load is equal to two and one-half times the desired superimposed design load. The allowable superimposed design load shall be taken as the lesser of:
2. The failure load divided by 2.5.
3. The maximum load applied divided by 2.5.
The deflection of structural members under the design load shall not exceed the limitations in
Section 1604.3.
Load-bearing wall and partition assemblies shall sustain the test load both with and without window framing. The test load shall include all design load components.
Wall and partition assemblies shall be tested both with and without door and window framing.
The design pressure rating of exterior windows and doors in buildings shall be determined in accordance with
Section 1710.5.1 or
1710.5.2.
Exception: Structural wind load design pressures for window units smaller than the size tested in accordance with
Section 1710.5.1 or
1710.5.2 shall be permitted to be higher than the design value of the tested unit provided such higher pressures are determined by accepted engineering analysis. All components of the small unit shall be the same as the tested unit. Where such calculated design pressures are used, they shall be validated by an additional test of the window unit having the highest allowable design pressure.
Exterior windows and sliding doors shall be tested and
labeled as conforming to AAMA/WDMA/CSA101/I.S.2/A440. The
label shall state the name of the manufacturer, the
approved labeling agency and the product designation as specified in AAMA/WDMA/CSA101/I.S.2/A440. Exterior side-hinged doors shall be tested and
labeled as conforming to AAMA/WDMA/CSA101/I.S.2/A440 or comply with
Section 1710.5.2. Products tested and
labeled as conforming to AAMA/WDMA/CSA 101/I.S.2/A440 shall not be subject to the requirements of Sections
2403.2 and
2403.3.
Exterior window and door assemblies shall be tested in accordance with ASTM E 330. Structural performance of garage doors and rolling doors shall be determined in accordance with either ASTM E 330 or ANSI/DASMA 108, and shall meet the acceptance criteria of ANSI/DASMA 108. Exterior window and door assemblies containing glass shall comply with
Section 2403. The design pressure for testing shall be calculated in accordance with
Chapter 16. Each assembly shall be tested for 10 seconds at a load equal to 1.5 times the design pressure.
Unit skylights and
tubular daylighting devices (TDDs) shall comply with the requirements of
Section 2405. All other
skylights and sloped glazing shall comply with the requirements of
Chapter 24.
Test specimens and construction shall be representative of the materials, workmanship and details normally used in practice. The properties of the materials used to construct the test assembly shall be determined on the basis of tests on samples taken from the load assembly or on representative samples of the materials used to construct the load test assembly. Required tests shall be conducted or witnessed by an
approved agency.
Testing of joist hangers shall be in accordance with Sections
1711.1.1 through
1711.1.3, as applicable.
The vertical load-bearing capacity, torsional moment capacity and deflection characteristics of joist hangers shall be determined in accordance with ASTM D 1761 using lumber having a specific gravity of 0.49 or greater, but not greater than 0.55, as determined in accordance with AF&PA; NDS for the joist and headers.
Exception: The joist length shall not be required to exceed 24 inches (610 mm).
The vertical load-bearing capacity for the joist hanger shall be determined by testing a minimum of three joist hanger assemblies as specified in ASTM D 1761. If the ultimate vertical load for any one of the tests varies more than 20 percent from the average ultimate vertical load, at least three additional tests shall be conducted. The allowable vertical load-bearing of the joist hanger shall be the lowest value determined from the following:
1. The lowest ultimate vertical load for a single hanger from any test divided by three (where three tests are conducted and each ultimate vertical load does not vary more than 20 percent from the average ultimate vertical load).
2. The average ultimate vertical load for a single hanger from all tests divided by three (where six or more tests are conducted).
3. The average from all tests of the vertical
loads that produce a vertical movement of the joist with respect to the header of
1/
8 inch (3.2 mm).
4. The sum of the allowable design
loads for nails or other fasteners utilized to secure the joist hanger to the wood members and allowable bearing
loads that contribute to the capacity of the hanger.
5. The allowable design load for the wood members forming the connection.
Relocated
Allowable design values for joist hangers that are determined by Item 4 or 5 in
Section 1711.1.2 shall be permitted to be modified by the appropriate load duration factors as specified in AF&PA NDS but shall not exceed the direct
loads as determined by Item 1, 2 or 3 in
Section 1711.1.2. Allowable design values determined by Item 1, 2 or 3 in
Section 1711.1.2 shall not be modified by load duration factors.
The torsional moment capacity for the joist hanger shall be determined by testing at least three joist hanger assemblies as specified in ASTM D 1761. The allowable torsional moment of the joist hanger shall be the average torsional moment at which the lateral movement of the top or bottom of the joist with respect to the original position of the joist is
1/
8 inch (3.2 mm).
Relocated
Testing of
concrete and clay roof tiles shall be in accordance with Sections
1711.2.1 and
1711.2.2, as applicable.
Concrete and clay roof tiles shall be tested to determine their resistance to overturning due to wind in accordance with SBCCI SSTD 11 and
Chapter 15.
Where
concrete and clay roof tiles do not satisfy the limitations in
Chapter 16 for rigid tile, a wind tunnel test shall be used to determine the wind characteristics of the
concrete or clay tile
roof covering in accordance with SBCCI SSTD 11 and
Chapter 15.