Copyright

Effective Use of the International Building Code

Preface

Ordinance

Chapter 1 Scope and Administration

Chapter 2 Definitions

Chapter 3 Use and Occupancy Classification

Chapter 4 Special Detailed Requirements Based on Use and Occupancy

Chapter 5 General Building Heights and Areas

Chapter 6 Types of Construction

Chapter 7 Fire and Smoke Protection Features

Chapter 8 Interior Finishes

Chapter 9 Fire Protection Systems

Chapter 10 Means of Egress

Chapter 11 Accessibility

Chapter 12 Interior Environment

Chapter 13 Energy Efficiency

Chapter 14 Exterior Walls

Chapter 15 Roof Assemblies and Rooftop Structures

Chapter 16 Structural Design

Chapter 17 Structural Tests and Special Inspections

Chapter 18 Soils and Foundations

Chapter 19 Concrete

Chapter 20 Aluminum

Chapter 21 Masonry

Chapter 22 Steel

Chapter 23 Wood

Chapter 24 Glass and Glazing

Chapter 25 Gypsum Board and Plaster

Chapter 26 Plastic

Chapter 27 Electrical

Chapter 28 Mechanical Systems

Chapter 29 Plumbing Systems

Chapter 30 Elevators and Conveying Systems

Chapter 31 Special Construction

Chapter 32 Encroachments Into the Public Right-Of-Way

Chapter 33 Safeguards During Construction

Chapter 34 Existing Structures

Chapter 35 Referenced Standards

Appendix A Employee Qualifications

Appendix B Board of Appeals

Appendix C Group U - Agricultural Buildings

Appendix D Fire Districts

Appendix E Supplementary Accessibility Requirements

Appendix F Rodentproofing

Appendix G Flood-Resistant Construction

Appendix H Signs

Appendix I Patio Covers

Appendix J Grading

Appendix K Administrative Provisions

The provisions of this chapter and the International Plumbing Code shall govern the erection, installation, alteration, repairs, relocation, replacement, addition to, use or maintenance of plumbing equipment and systems. Plumbing systems and equipment shall be constructed, installed and maintained in accordance with the International Plumbing Code. Private sewage disposal systems shall conform to the International Private Sewage Disposal Code.

Plumbing fixtures shall be provided for the type of occupancy and in the minimum number shown in Table 2902.1. Types of occupancies not shown in Table 2902.1 shall be considered individually by the building official. The number of occupants shall be determined by this code. Occupancy classification shall be determined in accordance with Chapter 3.

[P] TABLE 2902.1
MINIMUM NUMBER OF REQUIRED PLUMBING FIXTURESa
(See Sections 2902.2 and 2902.3)

No.

CLASSIFICATION

OCCUPANCY

DESCRIPTION

WATER CLOSETS
(URINALS SEE SECTION 419.2 OF THE INTERNATIONAL PLUMBING CODE)

LAVATORIES

BATHTUBS/
SHOWERS

DRINKING FOUNTAINSe, f
(SEE SECTION 410.1 OF THE INTERNATIONAL PLUMBING CODE)

OTHER

MALE

FEMALE

MALE

FEMALE

1

Assembly

A-1d

Theaters and other buildings for the performing arts and motion pictures

1 per 125

1 per 65

1 per 200

1 per 500

1 service sink

A-2d

Nightclubs, bars, taverns, dance halls and buildings for similar purposes

1 per 40

1 per 40

1 per 75

1 per 500

1 service sink

Restaurants, banquet halls and food courts

1 per 75

1 per 75

1 per 200

1 per 500

1 service sink

A-3d

Auditoriums without permanent seating, art galleries, exhibition halls, museums, lecture halls, libraries, arcades and gymnasiums

1 per 125

1 per 65

1 per 200

1 per 500

1 service sink

Passenger terminals and transportation facilities

1 per 500

1 per 500

1 per 750

1 per 1,000

1 service sink

Places of worship and other religious services

1 per 150

1 per 75

1 per 200

1 per 1,000

1 service sink

A-4

Coliseums, arenas, skating rinks, pools and tennis courts for indoor sporting events and activities

1 per 75 for the first 1,500 and 1 per 120 for the remainder exceeding 1,500

1 per 40 for the first 1,520 and 1 per 60 for the remainder exceeding 1,520

1 per 200

1 per 150

1 per 1,000

1 service sink

A-5

Stadiums, amusement parks, bleachers and grandstands for outdoor sporting events and activities

1 per 75 for the first 1,500 and 1 per 120 for the remainder exceeding 1,500

1 per 40 for the first 1,520 and 1 per 60 for the remainder exceeding 1,520

1 per 200

1 per 150

1 per 1,000

1 service sink

(continued)

[P] TABLE 2902.1—continued
MINIMUM NUMBER OF REQUIRED PLUMBING FIXTURESa

No.

CLASSIFICATION

OCCUPANCY

DESCRIPTION

WATER CLOSETS
(URINALS SEE SECTION 419.2 OF THE INTERNATIONAL PLUMBING CODE)

LAVATORIES

BATHTUBS
OR
SHOWERS

DRINKING FOUNTAINSe, f
(SEE SECTION 410.1 OF THE INTERNATIONAL PLUMBING CODE)

OTHER

MALE

FEMALE

MALE

FEMALE

2

Business

B

Buildings for the transaction of business, professional services, other services involving merchandise, office buildings, banks, light industrial and similar uses

1 per 25 for the first 50 and 1 per 50 for the remainder exceeding 50

1 per 40 for the first 80 and 1 per 80 for the remainder exceeding 80

1 per 100

1 service sink

3

Educational

E

Educational facilities

1 per 50

1 per 50

1 per 100

1 service sink

4

Factory and industrial

F-1 and F-2

Structures in which occupants are engaged in work fabricating, assembly or processing of products or materials

1 per 100

1 per 100

See Section 411 of the International Plumbing Code

1 per 400

1 service sink

5

Institutional

I-1

Residential care

1 per 10

1 per 10

1 per 8

1 per 100

1 service sink

I-2

Hospitals, ambulatory nursing home patientsb

1 per per roomc

1 per per roomc

1 per 15

1 per 100

1 service sink

Employees, other than residential careb

1 per 25

1 per 35

1 per 100

Visitors, other than residential care

1 per 75

1 per 100

1 per 500

I-3

Prisonsb

1 per cell

1 per cell

1 per 15

1 per 100

1 service sink

I-3

Reformatories, detention centers and correctional centersb

1 per 15

1 per 15

1 per 15

1 per 100

1 service sink

Employeesb

1 per 25

1 per 35

1 per 100

I-4

Adult day care and child care

1 per 15

1 per 15

1

1 per 100

1 service sink

6

Mercantile

M

Retail stores, service stations, shops, salesrooms, markets and shopping centers

1 per 500

1 per 750

1 per 1,000

1 service sink

7

Residential

R-1

Hotels, motels, boarding houses (transient)

1 per sleeping unit

1 per sleeping unit

1 per sleeping unit

1 service sink

R-2

Dormitories, fraternities, sororities and boarding houses (not transient)

1 per 10

1 per 10

1 per 8

1 per 100

1 service sink

R-2

Apartment house

1 per dwelling unit

1 per dwelling unit

1 per dwelling unit

1 kitchen sink per dwelling unit; 1 automatic clothes washer connection per 20 dwelling units

[P] TABLE 2902.1—continued
MINIMUM NUMBER OF REQUIRED PLUMBING FIXTURESa

No.

CLASSIFICATION

OCCUPANCY

DESCRIPTION

WATER CLOSETS
(URINALS SEE SECTION 419.2 OF THE INTERNATIONAL PLUMBING CODE)

LAVATORIES

BATHTUBS/
SHOWERS

DRINKING FOUNTAINSe, f
(SEE SECTION 410.1 OF THE INTERNATIONAL PLUMBING CODE)

OTHER

MALE

FEMALE

MALE

FEMALE

7

Residential

R-3

Congregate living facilities with 16 or fewer persons

1 per 10

1 per 10

1 per 8

1 per 100

1 service sink

R-4

Residential care/assisted living facilities

1 per 10

1 per 10

1 per 8

1 per 100

1 service sink

8

Storage

S-1
S-2

Structures for the storage of goods, warehouses, storehouses and freight depots, low and moderate hazard

1 per 100

1 per 100

See Section 411 of the International Plumbing Code

1 per 1,000

1 service sink

a. The fixtures shown are based on one fixture being the minimum required for the number of persons indicated or any fraction of the number of persons indicated. The number of occupants shall be determined by this code.

b. Toilet facilities for employees shall be separate from facilities for inmates or patients.

c. A single-occupant toilet room with one water closet and one lavatory serving not more than two adjacent patient sleeping units shall be permitted where such room is provided with direct access from each patient sleeping unit and with provisions for privacy.

d. The occupant load for seasonal outdoor seating and entertainment areas shall be included when determining the minimum number of facilities required.

e. The minimum number of required drinking fountains shall comply with Table 2902.1 and Chapter 11.

f. Drinking fountains are not required for an occupant load of 15 or fewer.

To determine the occupant load of each sex, the total occupant load shall be divided in half. To determine the required number of fixtures, the fixture ratio or ratios for each fixture type shall be applied to the occupant load of each sex in accordance with Table 2902.1. Fractional numbers resulting from applying the fixture ratios of Table 2902.1 shall be rounded up to the next whole number. For calculations involving multiple occupancies, such fractional numbers for each occupancy shall first be summed and then rounded up to the next whole number.

Exception: The total occupant load shall not be required to be divided in half where approved statistical data indicate a distribution of the sexes of other than 50 percent of each sex.

Fixtures located within family or assisted use toilet and bathing rooms required by Section 1109.2.1 are permitted to be included in the number of required fixtures for either the male or female occupants in assembly and mercantile occupancies.

Where plumbing fixtures are required, separate facilities shall be provided for each sex.

Exceptions:

1. Separate facilities shall not be required for dwelling units and sleeping units.

2. Separate facilities shall not be required in structures or tenant spaces with a total occupant load, including both employees and customers, of 15 or less.

3. Separate facilities shall not be required in mercantile occupancies in which the maximum occupant load is 50 or less.

Customers, patrons and visitors shall be provided with public toilet facilities in structures and tenant spaces intended for public utilization. The number of plumbing fixtures located within the required toilet facilities shall be provided in accordance with Section 2902.1 for all users. Employees shall be provided with toilet facilities in all occupancies. Employee toilet facilities shall either be separate or combined employee and public toilet facilities.
The route to the public toilet facilities required by Section 2902.3 shall not pass through kitchens, storage rooms or closets. Access to the required facilities shall be from within the building or from the exterior of the building. All routes shall comply with the accessibility requirements of this code. The public shall have access to the required toilet facilities at all times that the building is occupied.

In occupancies other than covered mall buildings, the required public and employee toilet facilities shall be located not more than one story above or below the space required to be provided with toilet facilities and the path of travel to such facilities shall not exceed a distance of 500 feet (152 400 mm).

Exception: The location and maximum travel distances to required employee facilities in factory and industrial occupancies are permitted to exceed that required by this section, provided that the location and maximum travel distance are approved.

In covered mall buildings, the required public and employee toilet facilities shall be located not more than one story above or below the space required to be provided with toilet facilities, and the path of travel to such facilities shall not exceed a distance of 300 feet (91 440 mm). In covered mall buildings, the required facilities shall be based on total square footage, and facilities shall be installed in each individual store or in a central toilet area located in accordance with this section. The maximum travel distance to the central toilet facilities in covered mall buildings shall be measured from the main entrance of any store or tenant space. In covered mall buildings, where employees’ toilet facilities are not provided in the individual store, the maximum travel distance shall be measured from the employees’ work area of the store or tenant space.
Where pay facilities are installed, such facilities shall be in excess of the required minimum facilities. Required facilities shall be free of charge.
A legible sign designating the sex shall be provided in a readily visible location near the entrance to each toilet facility. Signs for accessible toilet facilities shall comply with ICC A117.1.
Directional signage indicating the route to the public facilities shall be posted in accordance with Section 3107. Such signage shall be located in a corridor or aisle, at the entrance to the facilities for customers and visitors.

Each water closet utilized by the public or employees shall occupy a separate compartment with walls or partitions and a door enclosing the fixtures to ensure privacy.

Exceptions:

1. Water closet compartments shall not be required in a single-occupant toilet room with a lockable door.

2. Toilet rooms located in day care and child care facilities and containing two or more water closets shall be permitted to have one water closet without an enclosing compartment.

3. This provision is not applicable to toilet areas located within Group I-3 housing areas.

Each urinal utilized by the public or employees shall occupy a separate area with walls or partitions to provide privacy. The walls or partitions shall begin at a height not more than 12 inches (305 mm) from and extend not less than 60 inches (1524 mm) above the finished floor surface. The walls or partitions shall extend from the wall surface at each side of the urinal a minimum of 18 inches (457 mm) or to a point not less than 6 inches (152 mm) beyond the outermost front lip of the urinal measured from the finished back wall surface, whichever is greater.

Exceptions:

1. Urinal partitions shall not be required in a single occupant or family or assisted use toilet room with a lockable door.

2. Toilet rooms located in day care and child care facilities and containing two or more urinals shall be permitted to have one urinal without partitions.

Interior finish surfaces of toilet rooms shall comply with Section 1210.
Resources