ADOPTS WITH AMENDMENTS:

International Residential Code 2015 (IRC 2015)

Heads up: There are no amended sections in this chapter.

The provisions of this chapter shall control the design and construction of the foundation and foundation spaces for buildings. In addition to the provisions of this chapter, the design and construction of foundations in flood hazard areas as established by Table R301.2(1) shall meet the provisions of Section R322. Wood foundations shall be designed and installed in accordance with AWC PWF.

Exception: The provisions of this chapter shall be permitted to be used for wood foundations only in the following situations:

  1. In buildings that have no more than two floors and a roof.
  2. Where interior basement and foundation walls are constructed at intervals not exceeding 50 feet (15 240 mm).
  3. Buildings and structures located within the HighVelocity Hurricane Zone shall comply with the provisions of Chapter 44 and, as applicable, Section R322 in flood hazard areas.

Wood foundations in Seismic Design Category D0, D1 or D2 shall be designed in accordance with accepted engineering practice.

TABLE R401.1

FOUNDATION UPLIFT LIGHT STEEL & WOOD FRAME BUILDINGS IN EXPOSURE B (plf)5, 6

Roof
Angle
Bldg WidthMinimum
Building Length
Vasd as determined in accordance with Section R301.2.1.3 / Velocity Pressure
100110120130140150
151822263034
453 Stories32012173276389512644787
251473165265374492618
3019081174275384502
35251748104200305417
40353369109152240349
2 Stories2201264126195270350437
25151766129198272352
3022386290146217294
35355686118154192252
404074108146186230277
1 Story1201233466194132173
2522577596118142167
301879103129157187219
3516100128159192229267
4016120152188226268312
303 Stories3201292177271373483601
2517063143230324425
302502352125209300
3535134478115154206
40402864102145190239
2 Stories22013150103162224292
252316355784139199
3030366087116148181
35355483115150187227
403671104141181224270
1 Story120203246607693112
2515567495117140166
301378102127155185217
351499127157190226264
4016118150185223264308
203 Stories32012113203301408523647
251445130222322431547
3017485177277385501
35192058154257369489
40213572141249367493
2 Stories2201243100163231304384
25132279143214289371
30154272141217298386
35156192150232321417
401678114164254352457
1Story12012385794135179226
25126282122171223280
301285110154212275342
3514107136190257330409
4016126160227304388478

TABLE R401.1—continued

FOUNDATION UPLIFT LIGHT STEEL & WOOD FRAME BUILDINGS IN EXPOSURE C (plf)5, 6

Roof
Angle
Bldg WidthMinimum
Building Length4
Vasd as determined in accordance with Section R301.2.1.3 / Velocity Pressure
100110120130140150
212631364248
453 Stories3201237051567384510311231
25132493775186708361013
3017159278408550703867
352189203328463610767
4026102153262394537691
2 Stories22012184271368472585706
2513119200288385489601
301885147233326426533
3524113155200284383489
4036139187240297358457
1 Story120125895140189243300
251692118147178224281
3019124157193233275321
3517154193236283334388
4016182227277331389452
303 Stories32012256376507650804970
2515130232344466598740
302147127228337455582
353172116163241351469
404096146200259323392
2 Stories2201295163238320408502
25185385151223301385
303083117154195239304
3535110150195244296353
4037135182233289350415
1 Story12020587697119143169
251691117145176210245
3013123156191230272317
3514152191234280330384
4016179224273327384446
203 Stories320122854115496988601034
2513207325455595748911
3015162280409549701863
3517138260393538695863
4018124252392545709886
2 Stories22012152233320416519630
2512133215306404511625
3013130219316422536658
3514138235341456581715
4016150257373500636783
1 Story1201288136188245307373
2512114172235303377457
3012146214288370457552
3514180259346441543653
4016215306406515632758

Notes:

  1. Based on 1st floor height = 10 ft. or 11 ft. floor to floor in multistory.
  2. Based on 2nd floor height = 8 ft. or 9 ft. floor to floor in multistory.
  3. Based on 3rd floor height = 8 ft.
  4. Building length shall be equal to or greater than that shown in tables.
  5. Roof and floor framing shall span in the same direction.
  6. Includes provision for 2 foot roof overhang.
Foundations shall be capable of resisting all loads from roof uplift and building overturn. Foundation uplift for light-frame wood or steel buildings shall be calculated or determined from Table R401.1. Masonry buildings within the dimensional scope of Table R401.1 shall be assumed to be of adequate weight so as not to require uplift resistance greater than that provided by the structure and any normal foundation. Foundation construction shall also be capable of accommodating all gravity loads in accordance with Section R301 and of transmitting the resulting loads to the supporting soil. Fill soils that support footings and foundations shall be designed, installed and tested in accordance with accepted engineering practice. Gravel fill used as footings for wood and precast concrete foundations shall comply with Section R403.

Surface drainage shall be diverted to a storm sewer conveyance or other approved point of collection that does not create a hazard. Lots shall be graded to drain surface water away from foundation walls. The grade shall fall a minimum of 6 inches (152 mm) within the first 10 feet (3048 mm).

Exception: Where lot lines, walls, slopes or other physical barriers prohibit 6 inches (152 mm) of fall within 10 feet (3048 mm), drains or swales shall be constructed to ensure drainage away from the structure. Impervious surfaces within 10 feet (3048 mm) of the building foundation shall be sloped a minimum of 2 percent away from the building.

Where quantifiable data created by accepted soil science methodologies indicate expansive, compressible, shifting or other questionable soil characteristics are likely to be present, the building official shall determine whether to require a soil test to determine the soil's characteristics at a particular location. This test shall be done by an approved agency using an approved method.

In lieu of a complete geotechnical evaluation, the load-bearing values in Table R401.4.1 shall be assumed.

TABLE R401.4.1

PRESUMPTIVE LOAD-BEARING VALUES OF FOUNDATION MATERIALSa

CLASS OF MATERIALLOAD-BEARING
PRESSURE
(pounds per square foot)
Crystalline bedrock12,000
Sedimentary and foliated rock4,000
Sandy gravel and/or gravel (GW and GP)3,000
Sand, silty sand, clayey sand, silty gravel and clayey gravel (SW, SP, SM, SC, GM and GC)2,000
Clay, sandy, silty clay, clayey silt, silt and sandy siltclay (CL, ML, MH and CH)1,500b

For SI: 1 pound per square foot = 0.0479 kPa.

  1. Where soil tests are required by Section R401.4, the allowable bearing capacities of the soil shall be part of the recommendations.
  2. Where the building official determines that in-place soils with an allowable bearing capacity of less than 1,500 psf are likely to be present at the site, the allowable bearing capacity shall be determined by a soils investigation.

Instead of a complete geotechnical evaluation, where top or subsoils are compressible or shifting, they shall be removed to a depth and width sufficient to ensure stable moisture content in each active zone and shall not be used as fill or stabilized within each active zone by chemical, dewatering or presaturation.

Wood foundation systems shall be designed and installed in accordance with the provisions of this code.
Fasteners used below grade to attach plywood to the exterior side of exterior basement or crawl-space wall studs, or fasteners used in knee wall construction, shall be of Type 304 or 316 stainless steel. Fasteners used above grade to attach plywood and all lumber-to-lumber fasteners except those used in knee wall construction shall be of Type 304 or 316 stainless steel, silicon bronze, copper, hot-dipped galvanized (zinc coated) steel nails, or hot-tumbled galvanized (zinc coated) steel nails. Electro-galvanized steel nails and galvanized (zinc coated) steel staples shall not be permitted.
All lumber and plywood shall be pressure-preservative treated and dried after treatment in accordance with AWPA U1 (Commodity Specification A, Use Category 4B and Section 5.2), and shall bear the label of an accredited agency. Where lumber and/or plywood is cut or drilled after treatment, the treated surface shall be field treated with copper naphthenate, the concentration of which shall contain a minimum of 2-percent copper metal, by repeated brushing, dipping or soaking until the wood absorbs no more preservative.

Concrete shall have a minimum specified compressive strength of f 'c, as shown in Table R402.2. Concrete subject to moderate or severe weathering as indicated in Table R301.2(1) shall be air entrained as specified in Table R402.2. The maximum weight of fly ash, other pozzolans, silica fume, slag or blended cements that is included in concrete mixtures for garage floor slabs and for exterior porches, carport slabs and steps that will be exposed to deicing chemicals shall not exceed the percentages of the total weight of cementitious materials specified in Section 19.3.3.4 of ACI 318. Materials used to produce concrete and testing thereof shall comply with the applicable standards listed in Chapters 19 and 20 of ACI 318 or ACI 332.

TABLE R402.2

MINIMUM SPECIFIED COMPRESSIVE STRENGTH OF CONCRETE

TYPE OR LOCATION OF CONCRETE CONSTRUCTIONMINIMUM SPECIFIED COMPRESSIVE STRENGTHa (f'c)
Weathering Potentialb
NegligibleModerateSevere
Basement walls, foundations and other concrete not exposed to the weather2,5002,5002,500c
Basement slabs and interior slabs on grade, except garage floor slabs2,5002,5002,500c
Basement walls, foundation walls, exterior walls and other vertical concrete
work exposed to the weather
2,5003,000d3,000d
Porches, carport slabs and steps exposed to the weather, and garage floor
slabs
2,5003,000d, e, f3,500d, e, f

For SI: 1 pound per square inch = 6.895 kPa.

  1. Strength at 28 days psi.
  2. See Table R301.2(1) for weathering potential.
  3. Concrete in these locations that is subject to freezing and thawing during construction shall be air-entrained concrete in accordance with Footnote d.
  4. Concrete shall be air-entrained. Total air content (percent by volume of concrete) shall be not less than 5 percent or more than 7 percent.
  5. See Section R402.2 for maximum cementitious materials content.
  6. For garage floors with a steel-troweled finish, reduction of the total air content (percent by volume of concrete) to not less than 3 percent is permitted if the specified compressive strength of the concrete is increased to not less than 4,000 psi.
Materials for concrete shall comply with the requirements of Section R608.5.1.
Precast concrete foundations shall be designed in accordance with Section R404.5 and shall be installed in accordance with the provisions of this code and the manufacturer's instructions.

Materials used to produce precast concrete foundations shall meet the following requirements.

  1. All concrete used in the manufacture of precast concrete foundations shall have a minimum compressive strength of 5,000 psi (34 470 kPa) at 28 days. Concrete exposed to a freezing and thawing environment shall be air entrained with a minimum total air content of 5 percent.
  2. Structural reinforcing steel shall meet the requirements of ASTM A615, A706 or A996. The minimum yield strength of reinforcing steel shall be 40,000 psi (Grade 40) (276 MPa). Steel reinforcement for precast concrete foundation walls shall have a minimum concrete cover of 3/4 inch (19.1 mm).
  3. Panel-to-panel connections shall be made with Grade II steel fasteners.
  4. The use of nonstructural fibers shall conform to ASTM C1116.
  5. Grout used for bedding precast foundations placed upon concrete footings shall meet ASTM C1107.
Masonry systems shall be designed and installed in accordance with this chapter and shall have a minimum specified compressive strength of 1,500 psi (10.3 MPa).

All exterior walls shall be supported on continuous solid or fully grouted masonry or concrete footings, crushed stone footings, wood foundations, or other approved structural systems which shall be of sufficient design to accommodate all loads according to Section R301 and to transmit the resulting loads to the soil within the limitations as determined from the character of the soil. Footings shall be supported on undisturbed natural soils or engineered fill. Concrete footing shall be designed and constructed in accordance with the provisions of Section R403 or in accordance with ACI 332.

TABLE R403.1(1)

MINIMUM WIDTH AND THICKNESS FOR CONCRETE FOOTINGS FOR LIGHT-FRAME CONSTRUCTION (inches)a, b

SNOW LOAD
OR ROOF LIVE
LOAD
STORY AND TYPE
OF STRUCTURE WITH
LIGHT FRAME
LOAD-BEARING VALUE OF SOIL
(psf)
150020002500300035004000
20 psf1 story—slab-on-grade12 × 612 × 612 × 612 × 612 × 612 × 6
1 story—with crawl space12 × 612 × 612 × 612 × 612 × 612 × 6
1 story—plus basement18 × 614 × 612 × 612 × 612 × 612 × 6
2 story—slab-on-grade12 × 612 × 612 × 612 × 612 × 612 × 6
2 story—with crawl space16 × 612 × 612 × 612 × 612 × 612 × 6
2 story—plus basement22 × 616 × 613 × 612 × 612 × 612 × 6
3 story—slab-on-grade14 × 612 × 612 × 612 × 612 × 612 × 6
3 story—with crawl space19 × 614 × 612 × 612 × 612 × 612 × 6
3 story—plus basement25 × 819 × 615 × 613 × 612 × 612 × 6
30 psf1 story—slab-on-grade12 × 612 × 612 × 612 × 612 × 612 × 6
1 story—with crawl space13 × 612 × 612 × 612 × 612 × 612 × 6
1 story—plus basement19 × 614 × 612 × 612 × 612 × 612 × 6
2 story—slab-on-grade12 × 612 × 612 × 612 × 612 × 612 × 6
2 story—with crawl space17 × 613 × 612 × 612 × 612 × 612 × 6
2 story—plus basement23 × 617 × 614 × 612 × 612 × 612 × 6
3 story—slab-on-grade15 × 612 × 612 × 612 × 612 × 612 × 6
3 story—with crawl space20 × 615 × 612 × 612 × 612 × 612 × 6
3 story—plus basement26 × 820 × 616 × 613 × 612 × 612 × 6
50 psf1 story—slab-on-grade12 × 612 × 612 × 612 × 612 × 612 × 6
1 story—with crawl space16 × 612 × 612 × 612 × 612 × 612 × 6
1 story—plus basement21 × 616 × 613 × 612 × 612 × 612 × 6
2 story—slab-on-grade14 × 612 × 612 × 612 × 612 × 612 × 6
2 story—with crawl space19 × 614 × 612 × 612 × 612 × 612 × 6
2 story—plus basement25 × 719 × 615 × 612 × 612 × 612 × 6
3 story—slab-on-grade17 × 613 × 612 × 612 × 612 × 612 × 6
3 story—with crawl space22 × 617 × 613 × 612 × 612 × 612 × 6
3 story—plus basement28 × 921 × 617 × 614 × 612 × 612 × 6
70 psf1 story—slab-on-grade12 × 612 × 612 × 612 × 612 × 612 × 6
1 story—with crawl space18 × 613 × 612 × 612 × 612 × 612 × 6
1 story—plus basement24 × 718 × 614 × 612 × 612 × 612 × 6
2 story—slab-on-grade16 × 612 × 612 × 612 × 612 × 612 × 6
2 story—with crawl space21 × 616 × 613 × 612 × 612 × 612 × 6
2 story—plus basement27 × 920 × 616 × 614 × 612 × 612 × 6
3 story—slab-on-grade19 × 614 × 612 × 612 × 612 × 612 × 6
3 story—with crawl space25 × 718 × 615 × 612 × 612 × 612 × 6
3 story—plus basement30 × 1023 × 618 × 615 × 613 × 612 × 6

For SI: 1 inch = 25.4 mm, 1 plf = 14.6 N/m, 1 pound per square foot = 47.9 N/m2.

  1. Interpolation allowed. Extrapolation is not allowed.
  2. Based on 32-foot-wide house with load-bearing center wall that carries half of the tributary attic, and floor framing. For every 2 feet of adjustment to the width of the house, add or subtract 2 inches of footing width and 1 inch of footing thickness (but not less than 6 inches thick).

TABLE R403.1(2)

MINIMUM WIDTH AND THICKNESS FOR CONCRETE FOOTINGS FOR LIGHT-FRAME CONSTRUCTION WITH BRICK VENEER (inches)a, b

SNOW LOAD
OR ROOF LIVE
LOAD
STORY AND TYPE OF
STRUCTURE
WITH BRICK VENEER
LOAD-BEARING VALUE OF SOIL
(psf)
150020002500300035004000
20 psf1 story—slab-on-grade12 × 612 × 612 × 612 × 612 × 612 × 6
1 story—with crawl space15 × 612 × 612 × 612 × 612 × 612 × 6
1 story—plus basement21 × 615 × 612 × 612 × 612 × 612 × 6
2 story—slab-on-grade15 × 612 × 612 × 612 × 612 × 612 × 6
2 story—with crawl space20 × 615 × 612 × 612 × 612 × 612 × 6
2 story—plus basement26 × 820 × 616 × 613 × 612 × 612 × 6
3 story—slab-on-grade20 × 615 × 612 × 612 × 612 × 612 × 6
3 story—with crawl space26 × 819 × 615 × 613 × 612 × 612 × 6
3 story—plus basement32 × 1124 × 719 × 616 × 614 × 612 × 6
30 psf1 story—slab-on-grade12 × 612 × 612 × 612 × 612 × 612 × 6
1 story—with crawl space16 × 612 × 612 × 612 × 612 × 612 × 6
1 story—plus basement22 × 616 × 613 × 612 × 612 × 612 × 6
2 story—slab-on-grade16 × 612 × 612 × 612 × 612 × 612 × 6
2 story—with crawl space22 × 616 × 613 × 612 × 612 × 612 × 6
2 story—plus basement27 × 921 × 616 × 614 × 612 × 612 × 6
3 story—slab-on-grade21 × 616 × 613 × 612 × 612 × 612 × 6
3 story—with crawl space27 × 820 × 616 × 613 × 612 × 612 × 6
3 story—plus basement33 × 1124 × 720 × 616 × 614 × 612 × 6
50 psf1 story—slab-on-grade13 × 612 × 612 × 612 × 612 × 612 × 6
1 story—with crawl space18 × 614 × 612 × 612 × 612 × 612 × 6
1 story—plus basement24 × 718 × 614 × 612 × 612 × 612 × 6
2 story—slab-on-grade18 × 614 × 612 × 612 × 612 × 612 × 6
2 story—with crawl space24 × 718 × 614 × 612 × 612 × 612 × 6
2 story—plus basement29 × 1022 × 618 × 615 × 613 × 612 × 6
3 story—slab-on-grade27 × 718 × 613 × 612 × 612 × 612 × 6
3 story—with crawl space29 × 922 × 617 × 614 × 612 × 612 × 6
3 story—plus basement35 × 1226 × 821 × 617 × 615 × 613 × 6
70 psf1 story—slab-on-grade15 × 612 × 612 × 612 × 612 × 612 × 6
1 story—with crawl space20 × 615 × 612 × 612 × 612 × 612 × 6
1 story—plus basement26 × 820 × 616 × 613 × 612 × 612 × 6
2 story—slab-on-grade20 × 615 × 612 × 612 × 612 × 612 × 6
2 story—with crawl space26 × 819 × 615× 613 × 612 × 612 × 6
2 story—plus basement32 × 1124 × 719 × 616 × 614 × 612 × 6
3 story—slab-on-grade26 × 819 × 615 × 613 × 612 × 612 × 6
3 story—with crawl space31 × 1123 × 719 × 616 × 613 × 612 × 6
3 story—plus basement37 × 1328 × 922 × 618 × 616 × 614 × 6

For SI: 1 inch = 25.4 mm, 1 plf = 14.6 N/m, 1 pound per square foot = 47.9 N/m2.

  1. Interpolation allowed. Extrapolation is not allowed.
  2. Based on 32-foot-wide house with load-bearing center wall that carries half of the tributary attic, and floor framing. For every 2 feet of adjustment to the width of the house, add or subtract 2 inches of footing width and 1 inch of footing thickness (but not less than 6 inches thick).

TABLE R403.1(3)

MINIMUM WIDTH AND THICKNESS FOR CONCRETE FOOTINGS WITH CAST-IN-PLACE CONCRETE OR FULLY GROUTED MASONRY WALL CONSTRUCTION (inches)a, b

SNOW LOAD
OR ROOF LIVE
LOAD
STORY AND TYPE
OF STRUCTURE WITH CMU
LOAD-BEARING VALUE OF SOIL
(psf)
150020002500300035004000
20 psf1 story—slab-on-grade14 × 612 × 612 × 612 × 612 × 612 × 6
1 story—with crawl space19 × 614 × 612 × 612 × 612 × 612 × 6
1 story—plus basement25 × 819 × 615 × 613 × 612 × 612 × 6
2 story—slab-on-grade23 × 718 × 614 × 612 × 612 × 612 × 6
2 story—with crawl space29 × 922 × 617 × 614 × 612 × 612 × 6
2 story—plus basement35 × 1226 × 821 × 617 × 615 × 613 × 6
3 story—slab-on-grade32 × 1124 × 719 × 616 × 614 × 612 × 6
3 story—with crawl space38 × 1428 × 923 × 619 × 616 × 614 × 6
3 story—plus basement43 × 1733 × 1126 × 822 × 619 × 616 × 6
30 psf1 story—slab-on-grade15 × 612 × 612 × 612 × 612 × 612 × 6
1 story—with crawl space20 × 615 × 612 × 612 × 612 × 612 × 6
1 story—plus basement26 × 820 × 616 × 613 × 612 × 612 × 6
2 story—slab-on-grade24 × 718 × 615 × 612 × 612 × 612 × 6
2 story—with crawl space30 × 1022 × 618 × 615 × 613 × 612 × 6
2 story—plus basement36 × 1327 × 821 × 618 × 615 × 613 × 6
3 story—slab-on-grade33 × 1225 × 720 × 617 × 614 × 612 × 6
3 story—with crawl space39 × 1429 × 923 × 719 × 617 × 614 × 6
3 story—plus basement44 × 1733 × 1227 × 822 × 619 × 617 × 6
50 psf1 story—slab-on-grade17 × 613 × 612 × 612 × 612 × 612 × 6
1 story—with crawl space22 × 617 × 613 × 612 × 612 × 612 × 6
1 story—plus basement28 × 921 × 617 × 614 × 612 × 612 × 6
2 story—slab-on-grade27 × 820 × 616 × 613 × 612 × 612 × 6
2 story—with crawl space32 × 1124 × 719 × 616 × 614 × 612 × 6
2 story—plus basement38 × 1428 × 923 × 619 × 616 × 614 × 6
3 story—slab-on-grade35 × 1327 × 821 × 618 × 615 × 613 × 6
3 story—with crawl space41 × 1531 × 1024 × 720 × 617 × 615 × 6
3 story—plus basement47 × 1835 × 1228 × 923 × 720 × 617 × 6
70 psf1 story—slab-on-grade19 × 614 × 612 × 612 × 612 × 612 × 6
1 story—with crawl space25 × 718 × 615 × 612 × 612 × 612 × 6
1 story—plus basement30 × 1023 × 618 × 615 × 613 × 612 × 6
2 story—slab-on-grade29 × 922 × 617 × 614 × 612 × 612 × 6
2 story—with crawl space34 × 1226 × 821 × 617 × 615 × 613 × 6
2 story—plus basement40 × 1530 × 1024 × 720 × 617 × 615 × 6
3 story—slab-on-grade38 × 1428 × 923 × 619 × 616 × 614 × 6
3 story—with crawl space43 × 1632 × 1126 × 821 × 618 × 616 × 6
3 story—plus basement49 × 1937 × 1329 × 1024 × 721 × 618 × 6

For SI: 1 inch = 25.4 mm, 1 plf = 14.6 N/m, 1 pound per square foot = 47.9 N/m2.

  1. Interpolation allowed. Extrapolation is not allowed.
  2. Based on 32-foot-wide house with load-bearing center wall that carries half of the tributary attic, and floor framing. For every 2 feet of adjustment to the width of the house add or subtract 2 inches of footing width and 1 inch of footing thickness (but not less than 6 inches thick).

FIGURE 403.1(1)

CONCRETE AND MASONRY FOUNDATION DETAILS

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 mil = 0.0254.

FIGURE R403.1(2)

PERMANENT WOOD FOUNDATION BASEMENT WALL SECTION

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 mil = 0.0254 mm.

FIGURE R403.1(3)

PERMANENT WOOD FOUNDATION CRAWL SPACE SECTION

The minimum width, W, and thickness, T, for concrete footings shall be in accordance with Tables R403.1(1) through R403.1(3) and Figure R403.1(1) as applicable. Minimum sizes for concrete and masonry footings shall also be required to provide adequate resistance to uplift and overturn of the building as determined from Table R401.1 and Section R403.1.2 or as calculated using engineered design in accordance with the Florida Building Code, Building. The footing width shall be based on the load-bearing value of the soil in accordance with Table R401.4.1. Footing projections, P, shall be not less than 2 inches (51 mm) and shall not exceed the thickness of the footing. Footing thickness and projection for fireplaces shall be in accordance with Section R1001.2. The size of footings supporting piers and columns shall be based on the tributary load and allowable soil pressure in accordance with Table R401.4.1. Footings for wood foundations shall be in accordance with the details set forth in Section R403.2, and Figures R403.1(2) and R403.1(3).

Uplift resistance of common foundations are given in Table R403.1.2. Uplift resistance of these foundations may be increased by increasing the size of the concrete footing. When determining the modified uplift resistance the added weight shall be reduced by multiplying by a factor of 0.6. Other foundation systems shall be engineered in accordance with the Florida Building Code, Building.

TABLE R403.1.2

FOUNDATION UPLIFT (ASD) DESIGN DETAILS

FOOTINGTYPET
(inches)
W
(inches)
SLAB/WALL1RESISTANCE
(plf)
NOTES
AMono201265023
Mono201665853
BMono Interior2012137963
Mono Interior2016138793
C12" Stem/Joist10202284361, 2, 3
DMono20126502
Mono20166585
EMono Interior201213796
Mono Interior201613879
FStem/Joist10202082, 3
GStem/Slab102064603
HStem/Slab101263773
Stem/Slab102064603

For SI: 1 inch = 25.4 mm.

  1. Tributary width of 31/2" slab or weight of stemwall and bond beam.
  2. First floor dead load multiplied by 0.6 may also be included.
  3. All footing dowel bars shall be same size as wall steel, shall have a standard 90-degree hook, and shall be embedded a minimum of 6 inches. Dowel bars shall lap vertical wall reinforcement a minimum of 25 inches.
Exterior footings shall be placed not less than 12 inches (305 mm) below the undisturbed ground surface. Where applicable, the depth of footings shall also conform to Sections R403.1.4.1.

Except where otherwise protected from frost, foundation walls, piers and other permanent supports of buildings and structures shall be protected from frost by one or more of the following methods:

  1. Extended below the frost line specified in Table R301.2.(1).
  2. Constructed in accordance with Section R403.3.
  3. Constructed in accordance with ASCE 32.
  4. Erected on solid rock.

Exceptions:

  1. Protection of freestanding accessory structures with an area of 600 square feet (56 m2) or less, of light-frame construction, with an eave height of 10 feet (3048 mm) or less shall not be required.
  2. Protection of freestanding accessory structures with an area of 400 square feet (37 m2) or less, of other than light-frame construction, with an eave height of 10 feet (3048 mm) or less shall not be required.
  3. Decks not supported by a dwelling need not be provided with footings that extend below the frost line.

Footings shall not bear on frozen soil unless the frozen condition is permanent.

R403.1.5 Slope

ILLUSTRATION
The top surface of footings shall be level. The bottom surface of footings shall not have a slope exceeding one unit vertical in 10 units horizontal (10-percent slope). Footings shall be stepped where it is necessary to change the elevation of the top surface of the footings or where the slope of the bottom surface of the footings will exceed one unit vertical in 10 units horizontal (10-percent slope).

Wood sill plates and wood walls supported directly on continuous foundations shall be anchored to the foundation in accordance with this section.

Cold-formed steel framing shall be anchored directly to the foundation or fastened to wood sill plates anchored to the foundation. Anchorage of cold-formed steel framing and sill plates supporting cold-formed steel framing shall be in accordance with this section and Section R505.3.1 or R603.3.1.

Wood sole plates at all exterior walls on monolithic slabs, wood sole plates of braced wall panels at building interiors on monolithic slabs and all wood sill plates shall be anchored to the foundation with minimum 1/2-inch-diameter (12.7 mm) anchor bolts spaced a maximum of 6 feet (1829 mm) on center or approved anchors or anchor straps spaced as required to provide equivalent anchorage to 1/2-inch-diameter (12.7 mm) anchor bolts. Bolts shall extend a minimum of 7 inches (178 mm) into concrete or grouted cells of concrete masonry units. The bolts shall be located in the middle third of the width of the plate. A nut and washer shall be tightened on each anchor bolt. There shall be a minimum of two bolts per plate section with one bolt located not more than 12 inches (305 mm) or less than seven bolt diameters from each end of the plate section. Interior bearing wall sole plates on monolithic slab foundation that are not part of a braced wall panel shall be positively anchored with approved fasteners. Sill plates and sole plates shall be protected against decay and termites where required by Sections R317 and R318.

Exceptions:

  1. Walls 24 inches (610 mm) total length or shorter connecting offset braced wall panels shall be anchored to the foundation with a minimum of one anchor bolt located in the center third of the plate section and shall be attached to adjacent braced wall panels at corners as shown in Item 9 of Table R602.3(1).
  2. Connection of walls 12 inches (305 mm) total length or shorter connecting offset braced wall panels to the foundation without anchor bolts shall be permitted. The wall shall be attached to adjacent braced wall panels at corners as shown in Item 9 of Table R602.3(1).

In addition to the requirements of Section R403.1.6, the following requirements shall apply to wood light-frame structures in Seismic Design Categories D0, D1 and D2 and wood light-frame townhouses in Seismic Design Category C.

  1. Plate washers conforming to Section R602.11.1 shall be provided for all anchor bolts over the full length of required braced wall lines except where approved anchor straps are used. Properly sized cut washers shall be permitted for anchor bolts in wall lines not containing braced wall panels.
  2. Interior braced wall plates shall have anchor bolts spaced at not more than 6 feet (1829 mm) on center and located within 12 inches (305 mm) of the ends of each plate section when supported on a continuous foundation.
  3. Interior bearing wall sole plates shall have anchor bolts spaced at not more than 6 feet (1829 mm) on center and located within 12 inches (305 mm) of the ends of each plate section when supported on a continuous foundation.
  4. The maximum anchor bolt spacing shall be 4 feet (1219 mm) for buildings over two stories in height.
  5. Stepped cripple walls shall conform to Section R602.11.2.
  6. Where continuous wood foundations in accordance with Section R404.2 are used, the force transfer shall have a capacity equal to or greater than the connections required by Section R602.11.1 or the braced wall panel shall be connected to the wood foundations in accordance with the braced wall panel-to-floor fastening requirements of Table R602.3(1).
The placement of buildings and structures on or adjacent to slopes steeper than one unit vertical in three units horizontal (33.3-percent slope) shall conform to Sections R403.1.7.1 through R403.1.7.4.

In general, buildings below slopes shall be set a sufficient distance from the slope to provide protection from slope drainage, erosion and shallow failures. Except as provided in Section R403.1.7.4 and Figure R403.1.7.1, the following criteria will be assumed to provide this protection. Where the existing slope is steeper than one unit vertical in one unit horizontal (100-percent slope), the toe of the slope shall be assumed to be at the intersection of a horizontal plane drawn from the top of the foundation and a plane drawn tangent to the slope at an angle of 45 degrees (0.79 rad) to the horizontal. Where a retaining wall is constructed at the toe of the slope, the height of the slope shall be measured from the top of the wall to the top of the slope.

For SI: 1 foot = 304.8 mm.

FIGURE R403.1.7.1

FOUNDATION CLEARANCE FROM SLOPES

Footings on or adjacent to slope surfaces shall be founded in material with an embedment and setback from the slope surface sufficient to provide vertical and lateral support for the footing without detrimental settlement. Except as provided for in Section R403.1.7.4 and Figure R403.1.7.1, the following setback is deemed adequate to meet the criteria. Where the slope is steeper than one unit vertical in one unit horizontal (100-percent slope), the required setback shall be measured from an imaginary plane 45 degrees (0.79 rad) to the horizontal, projected upward from the toe of the slope.
On graded sites, the top of any exterior foundation shall extend above the elevation of the street gutter at point of discharge or the inlet of an approved drainage device a minimum of 12 inches (305 mm) plus 2 percent. Alternate elevations are permitted subject to the approval of the building official, provided it can be demonstrated that required drainage to the point of discharge and away from the structure is provided at all locations on the site.
Alternate setbacks and clearances are permitted, subject to the approval of the building official. The building official is permitted to require an investigation and recommendation of a qualified engineer to demonstrate that the intent of this section has been satisfied. Such an investigation shall include consideration of material, height of slope, slope gradient, load intensity and erosion characteristics of slope material.

Foundation and floor slabs for buildings located on expansive soils shall be designed in accordance with Section 1808.6 of the Florida Building Code, Building.

Exception: Slab-on-ground and other foundation systems which have performed adequately in soil conditions similar to those encountered at the building site are permitted subject to the approval of the building official.

Soils meeting all four of the following provisions shall be considered expansive, except that tests to show compliance with Items 1, 2 and 3 shall not be required if the test prescribed in Item 4 is conducted:

  1. Plasticity Index (PI) of 15 or greater, determined in accordance with ASTM D4318.
  2. More than 10 percent of the soil particles pass a No. 200 sieve (75 µm), determined in accordance with ASTM D422.
  3. More than 10 percent of the soil particles are less than 5 micrometers in size, determined in accordance with ASTM D422.
  4. Expansion Index greater than 20, determined in accordance with ASTM D4829.
Footings for wood foundations shall be in accordance with Figures R403.1(2) and R403.1(3). Gravel shall be washed and well graded. The maximum size stone shall not exceed 3/4 inch (19.1 mm). Gravel shall be free from organic, clayey or silty soils. Sand shall be coarse, not smaller than 1/16-inch (1.6 mm) grains and shall be free from organic, clayey or silty soils. Crushed stone shall have a maximum size of 1/2 inch (12.7 mm).

For buildings where the monthly mean temperature of the building is maintained at a minimum of 64°F (18°C), footings are not required to extend below the frost line when protected from frost by insulation in accordance with Figure R403.3(1) and Table R403.3(1). Foundations protected from frost in accordance with Figure R403.3(1) and Table R403.3(1) shall not be used for unheated spaces such as porches, utility rooms, garages and carports, and shall not be attached to basements or crawl spaces that are not maintained at a minimum monthly mean temperature of 64°F (18°C).

Materials used below grade for the purpose of insulating footings against frost shall be labeled as complying with ASTM C578.

For SI: 1 inch = 25.4 mm.

  1. See Table R403.3(1) for required dimensions and R-values for vertical and horizontal insulation and minimum footing depth.

FIGURE R403.3(1)

INSULATION PLACEMENT FOR FROST PROTECTED FOOTINGS IN HEATED BUILDINGS

TABLE R403.3(1)

MINIMUM FOOTING DEPTH AND INSULATION REQUIREMENTS FOR FROST-PROTECTED FOOTINGS IN HEATED BUILDINGSa

AIR FREEZING
INDEX

(°F-days)b
MINIMUM FOOTING
DEPTH, D
(inches)
VERTICAL
INSULATION

R-VALUEc, d
HORIZONTAL INSULATION
R-VALUEc, e
HORIZONTAL INSULATION DIMENSIONS
PER FIGURE R403.3(1) (inches)
Along wallsAt cornersABC
1,500 or less124.5Not requiredNot requiredNot requiredNot requiredNot required
2,000145.6Not requiredNot requiredNot requiredNot requiredNot required
2,500166.71.74.9122440
3,000167.86.58.6122440
3,500169.08.011.2243060
4,0001610.110.513.1243660

For SI: 1 inch = 25.4 mm, °C = [(°F) - 32]/1.8.

  1. Insulation requirements are for protection against frost damage in heated buildings. Greater values may be required to meet energy conservation standards.
  2. See Figure R403.3(2) or Table R403.3(2) for Air Freezing Index values.
  3. Insulation materials shall provide the stated minimum R-values under long-term exposure to moist, below-ground conditions in freezing climates. The following R-values shall be used to determine insulation thicknesses required for this application: Type II expanded polystyrene-2.4R per inch; Type IV extruded polystyrene-4.5R per inch; Type VI extruded polystyrene-4.5R per inch; Type IX expanded polystyrene-3.2R per inch; Type X extruded polystyrene-4.5R per inch.
  4. Vertical insulation shall be expanded polystyrene insulation or extruded polystyrene insulation.
  5. Horizontal insulation shall be expanded polystyrene insulation or extruded polystyrene insulation.

For SI: °C = [(°F) -32]/1.8.

Note: The air-freezing index is defined as cumulative degree days below 32°F. It is used as a measure of the combined magnitude and duration of air temperature below freezing. The index was computed over a 12-month period (July-June) for each of the 3,044 stations used in the above analysis. Date from the 1951-80 period were fitted to a Weibull probability distribution to produce an estimate of the 100-year return period.

FIGURE R403.3(2)

AIR-FREEZING INDEX AN ESTIMATE OF THE 100-YEAR RETURN PERIOD

TABLE R403.3(2)

AIR-FREEZING INDEX FOR U.S. LOCATIONS BY COUNTY

STATEAIR-FREEZING INDEX
1500 or less20002500300035004000
AlabamaAll counties
AlaskaKetchikan
Gateway,
Prince of Wales-
Outer Ketchikan
(CA), Sitka,
Wrangell-
Petersburg (CA)
Aleutians West (CA),
Haines, Juneau,
Skagway-Hoonah-
Angoon (CA), Yakutat
All counties
not listed
ArizonaAll counties
ArkansasAll counties
CaliforniaAll counties
not listed
Nevada, Sierra
ColoradoAll counties
not listed
Archuleta, Custer,
Fremont, Huerfano,
Las Animas, Ouray,
Pitkin, San Miguel
Clear Creek, Conejos,
Costilla, Dolores, Eagle,
La Plata, Park, Routt,
San Juan, Summit
Alamosa, Grand,
Jackson, Larimer,
Moffat,
Rio Blanco,
Rio Grande
Chaffee, Gunnison,
Lake, Saguache
Hinsdale,
Mineral
ConnecticutAll counties
not listed
Hartford,
Litchfield
DelawareAll counties
District of ColumbiaAll counties
FloridaAll counties
GeorgiaAll counties
HawaiiAll counties
IdahoAll counties
not listed
Adams, Bannock, Blaine,
Clearwater, Idaho,
Lincoln, Oneida, Power,
Valley, Washington
Bingham,
Bonneville, Camas,
Caribou, Elmore,
Franklin, Jefferson,
Madison, Teton
Bear Lake, Butte,
Custer, Fremont,
Lemhi
Clark
IllinoisAll counties
not listed
Boone, Bureau, Cook,
Dekalb, DuPage, Fulton,
Grundy, Henderson,
Henry, Iroquois,
Jo Daviess, Kane,
Kankakee, Kendall,
Knox, La Salle, Lake,
Lee, Livingston,
Marshall, Mason,
McHenry, McLean,
Mercer, Peoria, Putnam,
Rock Island,
Stark, Tazewell, Warren,
Whiteside, Will,
Woodford
Carroll, Ogle,
Stephenson,
Winnebago
IndianaAll counties
not listed
Allen, Benton, Cass,
Fountain, Fulton,
Howard, Jasper,
Kosciusko, La Porte,
Lake, Marshall, Miami,
Newton, Porter, Pulaski,
Starke, Steuben, Tippecanoe,
Tipton, Wabash,
Warren, White
IowaAppanoose,
Davis,
Fremont, Lee,
Van Buren
All counties
not listed
Allamakee, Black
Hawk, Boone, Bremer,
Buchanan, Buena Vista,
Butler, Calhoun,
Cerro Gordo, Cherokee,
Chickasaw, Clay,
Clayton, Delaware,
Dubuque, Fayette,
Floyd, Franklin,
Grundy, Hamilton,
Hancock, Hardin,
Humboldt, Ida,
Jackson, Jasper, Jones,
Linn, Marshall,
Palo Alto, Plymouth,
Pocahontas, Poweshiek,
Sac, Sioux, Story,
Tama, Webster,
Winnebago, Woodbury,
Worth, Wright
Dickinson,
Emmet, Howard,
Kossuth, Lyon,
Mitchell,
O'Brien, Osceola,
Winneshiek
KansasAll counties
KentuckyAll counties
LouisianaAll counties
MaineYorkKnox, Lincoln,
Sagadahoc
Androscoggin,
Cumberland, Hancock,
Kennebec, Waldo,
Washington
Aroostook,
Franklin, Oxford,
Penobscot,
Piscataquis,
Somerset
MarylandAll counties
MassachusettsAll counties
not listed
Berkshire, Franklin,
Hampden,
Worcester
MichiganBerrien,
Branch, Cass,
Kalamazoo,
Macomb, Ottawa,
St. Clair,
St. Joseph
All counties
not listed
Alger, Charlevoix,
Cheboygan, Chippewa,
Crawford, Delta,
Emmet, Iosco,
Kalkaska, Lake, Luce,
Mackinac, Menominee,
Missaukee,
Montmorency,
Ogemaw, Osceola,
Otsego, Roscommon,
Schoolcraft, Wexford
Baraga,
Dickinson, Iron,
Keweenaw,
Marquette
Gogebic,
Houghton,
Ontonagon
MinnesotaHouston, WinonaAll counties not listedAitkin, Big Stone, Carlton, Crow Wing, Douglas, Itasca, Kanabec, Lake, Morrison, Pine, Pope, Stearns, Stevens, Swift, Todd, WadenaBecker, Beltrami, Cass, Clay, Clearwater, Grant, Hubbard, Kittson, Koochiching, Lake of the Woods, Mahnomen, Marshall, Norman, Otter Tail, Pennington, Polk, Red Lake, Roseau, St. Louis, Traverse, Wilkin
MississippiAll counties
MissouriAll counties not listedAtchison, Mercer, Nodaway, Putnam
MontanaMineralBroadwater, Golden Valley, Granite, Lake, Lincoln, Missoula, Ravalli, Sanders, Sweet GrassBig Horn, Carbon, Jefferson, Judith Basin, Lewis and Clark, Meagher, Musselshell, Powder River, Powell, Silver Bow, Stillwater, WestlandCarter, Cascade, Deer Lodge, Falcon, Fergus, Flathead, Gallanting, Glacier, Madison, Park, Petroleum, Ponder, Rosebud, Teton, Treasure, YellowstoneBeaverhead, Blaine, Chouteau, Custer, Dawson, Garfield, Liberty, McCone, Prairie, Toole, WibauxDaniels, Hill, Phillips, Richland, Roosevelt, Sheridan, Valley
NebraskaAdams, Banner, Chase, Cheyenne, Clay, Deuel, Dundy, Fillmore, Franklin, Frontier, Furnas, Gage, Garden, Gosper, Harlan, Hayes, Hitchcock, Jefferson, Kimball, Morrill, Nemaha, Nuckolls, Pawnee, Perkins, Phelps, Red Willow, Richardson, Saline, Scotts Bluff, Seward, Thayer, WebsterAll counties not listedBoyd, Burt, Cedar, Cuming, Dakota, Dixon, Dodge, Knox, Thurston
NevadaAll counties not listedElko, Eureka, Nye, Washoe, White Pine
New HampshireAll counties not listedCarroll, Coos, Grafton
New JerseyAll counties
New MexicoAll counties not listedRio ArribaColfax, Mora, Taos
New YorkAlbany, Bronx, Cayuga, Columbia, Cortland, Dutchess, Genessee, Kings, Livingston, Monroe, Nassau, New York, Niagara, Onondaga, Ontario, Orange, Orleans, Putnam, Queens, Richmond, Rockland, Seneca, Suffolk, Wayne, Westchester, YatesAll counties not listedClinton, Essex, Franklin, Hamilton, Herkimer, Jefferson, Lewis, St. Lawrence, Warren
North CarolinaAll counties
North DakotaBillings, BowmanAdams, Dickey, Golden Valley, Het- tinger, LaMoure, Oliver, Ransom, Sargent, Sioux, Slope, StarkAll counties not listed
OhioAll counties not listedAshland, Crawford, Defiance, Holmes, Huron, Knox, Licking, Morrow, Paulding, Putnam, Richland, Seneca, Williams
OklahomaAll counties
OregonAll counties not listedBaker, Crook, Grant, Harney
PennsylvaniaAll counties not listedBerks, Blair, Bradford, Cambria, Cameron, Centre, Clarion, Clearfield, Clinton, Crawford, Elk, Forest, Huntingdon, Indiana, Jefferson, Lackawanna, Lycoming, McKean, Pike, Potter, Susquehanna, Tioga, Venango, Warren, Wayne, Wyoming
Rhode IslandAll counties
South CarolinaAll counties
South DakotaBennett, Custer, Fall River, Lawrence, Mellette, Shannon, Todd, TrippBon Homme, Charles Mix, Davison, Douglas, Gregory, Jackson, Jones, LymanAll counties not listedBeadle, Brookings, Brown, Campbell, Codington, Corson, Day, Deuel, Edmunds, Faulk, Grant, Hamlin, Kingsbury, Marshall, McPherson, Perkins, Roberts, Spink, Walworth
TennesseeAll counties
TexasAll counties
UtahAll counties not listedBox Elder, Morgan, WeberGarfield, Salt Lake, SummitCarbon, Daggett, Duchesne, Rich, Sanpete, Uintah, Wasatch
VermontBennington, Grand Isle, Rutland, WindhamAddison, Chittenden, Franklin, Orange, Washington, WindsorCaledonia, Essex, Lamoille, Orleans
VirginiaAll counties
WashingtonAll counties not listedChelan, Douglas, Ferry, Okanogan
West VirginiaAll counties
WisconsinKenosha, Kewaunee, Racine, Sheboygan, WalworthAll counties not listedAshland, Barron, Burnett, Chippewa, Clark, Dunn, Eau Claire, Florence, Forest, Iron, Jackson, La Crosse, Langlade, Marathon, Monroe, Pepin, Polk, Portage, Price, Rust, St. Croix, Taylor, Trempealeau, Vilas, WoodBayfield, Douglas, Lincoln, Oneida, Sawyer, Washburn
WyomingGoshen, PlatteConverse, Crook, Laramie, NiobraraCampbell, Carbon, Hot Springs, Johnson, Natrona, Sheridan, Uinta, WestonAlbany, Big Horn, Park, WashakieFremont, TetonLincoln, Sublette, Sweetwater

For SI: 1 inch = 25.4 mm.

  1. See Table R403.3(1) for required dimensions and R-values for vertical and horizontal insulation.

FIGURE R403.3(3)

INSULATION PLACEMENT FOR FROST-PROTECTED FOOTINGS ADJACENT TO UNHEATED SLAB-ON-GROUND STRUCTURE

FIGURE R403.3(4)

INSULATION PLACEMENT FOR FROST-PROTECTED FOOTINGS ADJACENT TO HEATED STRUCTURE

Foundations that adjoin frost-protected shallow foundations shall be protected from frost in accordance with Section R403.1.4.
Vertical wall insulation and horizontal insulation of frost-protected shallow foundations that adjoin a slab-on-ground foundation that does not have a monthly mean temperature maintained at a minimum of 64°F (18°C) shall be in accordance with Figure R403.3(3) and Table R403.3(1). Vertical wall insulation shall extend between the frost-protected shallow foundation and the adjoining slab foundation. Required horizontal insulation shall be continuous under the adjoining slab foundation and through any foundation walls adjoining the frost- protected shallow foundation. Where insulation passes through a foundation wall, it shall be either of a type complying with this section and having bearing capacity equal to or greater than the structural loads imposed by the building, or the building shall be designed and constructed using beams, lintels, cantilevers or other means of transferring building loads such that the structural loads of the building do not bear on the insulation.

Where a frost-protected shallow foundation abuts a structure that has a monthly mean temperature maintained at a minimum of 64°F (18°C), horizontal insulation and vertical wall insulation shall not be required between the frost-protected shallow foundation and the adjoining structure. Where the frost-protected shallow foundation abuts the heated structure, the horizontal insulation and vertical wall insulation shall extend along the adjoining foundation in accordance with Figure R403.3(4) a distance of not less than Dimension A in Table R403.3(1).

Exception: Where the frost-protected shallow foundation abuts the heated structure to form an inside corner, vertical insulation extending along the adjoining foundation is not required.

Horizontal insulation placed less than 12 inches (305 mm) below the ground surface or that portion of horizontal insulation extending outward more than 24 inches (610 mm) from the foundation edge shall be protected against damage by use of a concrete slab or asphalt paving on the ground surface directly above the insulation or by cementitious board, plywood rated for below-ground use, or other approved materials placed below ground, directly above the top surface of the insulation.
Final grade shall be sloped in accordance with Section R401.3. In other than Group I Soils, as detailed in Table R405.1, gravel or crushed stone beneath horizontal insulation below ground shall drain to daylight or into an approved sewer system.
The use of foam plastic in areas of "very heavy" termite infestation probability shall be in accordance with Section R318.4.

Footings for precast concrete foundations shall comply with Section R403.4.

TABLE R403.4

MINIMUM DEPTH OF CRUSHED STONE FOOTINGSa (D), (inches)

NUMBER
OF

STORIES
UNIFORM
WALL

LOAD
LOAD-BEARING VALUE OF SOIL (psf)
1500200030004000
MH, CH, CL, MLSC, GC, SM, GM, SP, SWGP, GW
Wall width (inches)Wall width (inches)Wall width (inches)Wall width (inches)
681012681012681012681012
Conventional light-frame construction
1-story1100 plf6444644464446444
2-story1800 plf8644644464446444
3-story2900 plf161412101086664446444
4-inch brick veneer over light-frame or 8-inch hollow concrete masonry
1-story1500 plf6444644464446444
2-story2700 plf14121081086464446444
3-story4000 plf2222201816141210108646444
8-inch solid or fully grouted masonry
1-story2000 plf10864644464446444
2-story3600 plf20181616141210886446444
3-story5300 plf3230282622222018141210810864

For SI: 1 inch = 25.4 mm, 1 plf = 14.6 N/m, 1 pound per square foot = 47.9 N/m2.

  1. Linear interpolation of stone depth between wall widths is permitted within each Load-Bearing Value of Soil (psf).

FIGURE R403.4(1)

BASEMENT OR CRAWL SPACE WITH PRECAST FOUNDATION WALL BEARING ON CRUSHED STONE

FIGURE R403.4(2)

BASEMENT OR CRAWL SPACE WITH PRECAST FOUNDATION WALL ON SPREAD FOOTING

Clean crushed stone shall be free from organic, clayey or silty soils. Crushed stone shall be angular in nature and meet ASTM C33, with the maximum size stone not to exceed 1/2 inch (12.7 mm) and the minimum stone size not to be smaller than 1/16 inch (1.6 mm). Crushed stone footings for precast foundations shall be installed in accordance with Figure R403.4(1) and Table R403.4. Crushed stone footings shall be consolidated using a vibratory plate in a maximum of 8-inch (203 mm) lifts. Crushed stone footings shall be limited to Seismic Design Categories A, B and C.
Concrete footings shall be installed in accordance with Section R403.1 and Figure R403.4(2).

Concrete foundation walls shall be selected and constructed in accordance with the provisions of Section R404.1.3. Masonry foundation walls shall be selected and constructed in accordance with the provisions of Section R404.1.2.

Concrete or masonry foundation walls shall be designed in accordance with accepted engineering practice where either of the following conditions exists:

  1. Walls are subject to hydrostatic pressure from ground water.
  2. Walls supporting more than 48 inches (1219 mm) of unbalanced backfill that do not have permanent lateral support at the top or bottom.

TABLE R404.1.1(1)

PLAIN MASONRY FOUNDATION WALLSf

MAXIMUM WALL HEIGHT
(feet)
MAXIMUM
UNBALANCED

BACKFILL HEIGHTc

(feet)
PLAIN MASONRYa MINIMUM NOMINAL WALL THICKNESS (inches)
Soil classesb
GW, GP, SW
and SP
GM, GC, SM,
SM-SC and ML
SC, MH, ML-CL
and inorganic CL
546 solidd or 86 solidd or 86 solidd or 8
56 solidd or 8810
646 solidd or 86 solidd or 86 solidd or 8
56 solidd or 8810
681012
746 solidd or 888
56 solidd or 81010
6101210 solidd
71210 solidd12 solidd
846 solidd or 86 solidd or 88
56 solidd or 81012
6101212 solidd
71212 soliddFootnote e
810 groutd12 soliddFootnote e
946 groutd or 8 solidd or 126 groutd or 8 solidd8 groutd or 10 solidd
56 groutd or 10 solidd8 groutd or 12 solidd8 groutd
68 groutd or 12 solidd10 groutd10 groutd
710 groutd10 groutd12 grout
810 groutd12 groutFootnote e
912 groutFootnote eFootnote e

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 Pa.

  1. Mortar shall be Type M or S and masonry shall be laid in running bond. Ungrouted hollow masonry units are permitted except where otherwise indicated.
  2. Soil classes are in accordance with the Unified Soil Classification System. Refer to Table R405.1.
  3. Unbalanced backfill height is the difference in height between the exterior finish ground level and the lower of the top of the concrete footing that supports the foundation wall or the interior finish ground level. Where an interior concrete slab-on-grade is provided and is in contact with the interior surface of the foundation wall, measurement of the unbalanced backfill height from the exterior finish ground level to the top of the interior concrete slab is permitted.
  4. Solid indicates solid masonry unit; grout indicates grouted hollow units.
  5. Wall construction shall be in accordance with either Table R404.1.1(2), Table R404.1.1(3), Table R404.1.1(4), or a design shall be provided.
  6. The use of this table shall be prohibited for soil classifications not shown.

TABLE R404.1.1(2)

8-INCH MASONRY FOUNDATION WALLS WITH REINFORCING WHERE d ≥ 5 INCHESa, c, f

WALL HEIGHTHEIGHT OF
UNBALANCED

BACKFILLe
MINIMUM VERTICAL REINFORCEMENT AND SPACING (INCHES)b, c
Soil classes and lateral soil loadd (psf per foot below grade)
GW, GP, SW and SP soils
30
GM, GC, SM, SM-SC and ML soils
45
SC, ML-CL and inorganic CL soils
60
6 feet 8 inches4 feet (or less)#4 at 48#4 at 48#4 at 48
5 feet#4 at 48#4 at 48#4 at 48
6 feet 8 inches#4 at 48#5 at 48#6 at 48
7 feet 4 inches4 feet (or less)#4 at 48#4 at 48#4 at 48
5 feet#4 at 48#4 at 48#4 at 48
6 feet#4 at 48#5 at 48#5 at 48
7 feet 4 inches#5 at 48#6 at 48#6 at 40
8 feet4 feet (or less)#4 at 48#4 at 48#4 at 48
5 feet#4 at 48#4 at 48#4 at 48
6 feet#4 at 48#5 at 48#5 at 48
7 feet#5 at 48#6 at 48#6 at 40
8 feet#5 at 48#6 at 48#6 at 32
8 feet 8 inches4 feet (or less)#4 at 48#4 at 48#4 at 48
5 feet#4 at 48#4 at 48#5 at 48
6 feet#4 at 48#5 at 48#6 at 48
7 feet#5 at 48#6 at 48#6 at 40
8 feet 8 inches#6 at 48#6 at 32#6 at 24
9 feet 4 inches4 feet (or less)#4 at 48#4 at 48#4 at 48
5 feet#4 at 48#4 at 48#5 at 48
6 feet#4 at 48#5 at 48#6 at 48
7 feet#5 at 48#6 at 48#6 at 40
8 feet#6 at 48#6 at 40#6 at 24
9 feet 4 inches#6 at 40#6 at 24#6 at 16
10 feet4 feet (or less)#4 at 48#4 at 48#4 at 48
5 feet#4 at 48#4 at 48#5 at 48
6 feet#4 at 48#5 at 48#6 at 48
7 feet#5 at 48#6 at 48#6 at 32
8 feet#6 at 48#6 at 32#6 at 24
9 feet#6 at 40#6 at 24#6 at 16
10 feet#6 at 32#6 at 16#6 at 16

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square foot per foot = 0.157 kPa/mm.

  1. Mortar shall be Type M or S and masonry shall be laid in running bond.
  2. Alternative reinforcing bar sizes and spacings having an equivalent cross-sectional area of reinforcement per lineal foot of wall shall be permitted provided the spacing of the reinforcement does not exceed 72 inches in Seismic Design Categories A, B and C, and 48 inches in Seismic Design Categories D0, D1 and D2.
  3. Vertical reinforcement shall be Grade 60 minimum. The distance, d, from the face of the soil side of the wall to the center of vertical reinforcement shall be not less than 5 inches.
  4. Soil classes are in accordance with the Unified Soil Classification System and design lateral soil loads are for moist conditions without hydrostatic pressure. Refer to Table R405.1.
  5. Unbalanced backfill height is the difference in height between the exterior finish ground level and the lower of the top of the concrete footing that supports the foundation wall or the interior finish ground level. Where an interior concrete slab-on-grade is provided and is in contact with the interior surface of the foundation wall, measurement of the unbalanced backfill height from the exterior finish ground level to the top of the interior concrete slab is permitted.
  6. The use of this table shall be prohibited for soil classifications not shown.

TABLE R404.1.1(3)

10-INCH MASONRY FOUNDATION WALLS WITH REINFORCING WHERE d ≥ 6.75 INCHESa, c, f

WALL HEIGHTHEIGHT OF
UNBALANCED

BACKFILLe
MINIMUM VERTICAL REINFORCEMENT AND SPACING (INCHES)b, c
Soil classes and later soil loadd (psf per foot below grade)
GW, GP, SW and SP soils
30
GM, GC, SM, SM-SC and ML soils
45
SC, ML-CL and inorganic CL soils
60
6 feet 8 inches4 feet (or less)#4 at 56#4 at 56#4 at 56
5 feet#4 at 56#4 at 56#4 at 56
6 feet 8 inches#4 at 56#5 at 56#5 at 56
7 feet 4 inches4 feet (or less)#4 at 56#4 at 56#4 at 56
5 feet#4 at 56#4 at 56#4 at 56
6 feet#4 at 56#4 at 56#5 at 56
7 feet 4 inches#4 at 56#5 at 56#6 at 56
8 feet4 feet (or less)#4 at 56#4 at 56#4 at 56
5 feet#4 at 56#4 at 56#4 at 56
6 feet#4 at 56#4 at 56#5 at 56
7 feet#4 at 56#5 at 56#6 at 56
8 feet#5 at 56#6 at 56#6 at 48
8 feet 8 inches4 feet (or less)#4 at 56#4 at 56#4 at 56
5 feet#4 at 56#4 at 56#4 at 56
6 feet#4 at 56#4 at 56#5 at 56
7 feet#4 at 56#5 at 56#6 at 56
8 feet 8 inches#5 at 56#6 at 48#6 at 32
9 feet 4 inches4 feet (or less)#4 at 56#4 at 56#4 at 56
5 feet#4 at 56#4 at 56#4 at 56
6 feet#4 at 56#5 at 56#5 at 56
7 feet#4 at 56#5 at 56#6 at 56
8 feet#5 at 56#6 at 56#6 at 40
9 feet 4 inches#6 at 56#6 at 40#6 at 24
10 feet4 feet (or less)#4 at 56#4 at 56#4 at 56
5 feet#4 at 56#4 at 56#4 at 56
6 feet#4 at 56#5 at 56#5 at 56
7 feet#5 at 56#6 at 56#6 at 48
8 feet#5 at 56#6 at 48#6 at 40
9 feet#6 at 56#6 at 40#6 at 24
10 feet#6 at 48#6 at 32#6 at 24

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square foot per foot = 0.157 kPa/mm.

  1. Mortar shall be Type M or S and masonry shall be laid in running bond.
  2. Alternative reinforcing bar sizes and spacings having an equivalent cross-sectional area of reinforcement per lineal foot of wall shall be permitted provided the spacing of the reinforcement does not exceed 72 inches in Seismic Design Categories A, B and C, and 48 inches in Seismic Design Categories D0, D1 and D2.
  3. Vertical reinforcement shall be Grade 60 minimum. The distance, d, from the face of the soil side of the wall to the center of vertical reinforcement shall be not less than 6.75 inches.
  4. Soil classes are in accordance with the Unified Soil Classification System and design lateral soil loads are for moist conditions without hydrostatic pressure. Refer to Table R405.1.
  5. Unbalanced backfill height is the difference in height between the exterior finish ground level and the lower of the top of the concrete footing that supports the foundation wall or the interior finish ground level. Where an interior concrete slab-on-grade is provided and is in contact with the interior surface of the foundation wall, measurement of the unbalanced backfill height from the exterior finish ground level to the top of the interior concrete slab is permitted.
  6. The use of this table shall be prohibited for soil classifications not shown.

TABLE R404.1.1(4)

12-INCH MASONRY FOUNDATION WALLS WITH REINFORCING WHERE d ≥ 8.75 INCHESa, c, f

WALL HEIGHTHEIGHT OF
UNBALANCED

BACKFILLe
MINIMUM VERTICAL REINFORCEMENT AND SPACING (INCHES)b, c
Soil classes and lateral soil loadd (psf per foot below grade)
GW, GP, SW and SP soils
30
GM, GC, SM, SM-SC and ML soils
45
SC, ML-CL and inorganic CL soils
60
6 feet 8 inches4 feet (or less)#4 at 72#4 at 72#4 at 72
5 feet#4 at 72#4 at 72#4 at 72
6 feet 8 inches#4 at 72#4 at 72#5 at 72
7 feet 4 inches4 feet (or less)#4 at 72#4 at 72#4 at 72
5 feet#4 at 72#4 at 72#4 at 72
6 feet#4 at 72#4 at 72#5 at 72
7 feet 4 inches#4 at 72#5 at 72#6 at 72
8 feet4 feet (or less)#4 at 72#4 at 72#4 at 72
5 feet#4 at 72#4 at 72#4 at 72
6 feet#4 at 72#4 at 72#5 at 72
7 feet#4 at 72#5 at 72#6 at 72
8 feet#5 at 72#6 at 72#6 at 64
8 feet 8 inches4 feet (or less)#4 at 72#4 at 72#4 at 72
5 feet#4 at 72#4 at 72#4 at 72
6 feet#4 at 72#4 at 72#5 at 72
7 feet#4 at 72#5 at 72#6 at 72
8 feet 8 inches#5 at 72#7 at 72#6 at 48
9 feet 4 inches4 feet (or less)#4 at 72#4 at 72#4 at 72
5 feet#4 at 72#4 at 72#4 at 72
6 feet#4 at 72#5 at 72#5 at 72
7 feet#4 at 72#5 at 72#6 at 72
8 feet#5 at 72#6 at 72#6 at 56
9 feet 4 inches#6 at 72#6 at 48#6 at 40
10 feet4 feet (or less)#4 at 72#4 at 72#4 at 72
5 feet#4 at 72#4 at 72#4 at 72
6 feet#4 at 72#5 at 72#5 at 72
7 feet#4 at 72#6 at 72#6 at 72
8 feet#5 at 72#6 at 72#6 at 48
9 feet#6 at 72#6 at 56#6 at 40
10 feet#6 at 64#6 at 40#6 at 32

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square foot per foot = 0.157 kPa/mm.

  1. Mortar shall be Type M or S and masonry shall be laid in running bond.
  2. Alternative reinforcing bar sizes and spacings having an equivalent cross-sectional area of reinforcement per lineal foot of wall shall be permitted provided the spacing of the reinforcement does not exceed 72 inches in Seismic Design Categories A, B and C, and 48 inches in Seismic Design Categories D0, D1 and D2.
  3. Vertical reinforcement shall be Grade 60 minimum. The distance, d, from the face of the soil side of the wall to the center of vertical reinforcement shall be not less than 8.75 inches.
  4. Soil classes are in accordance with the Unified Soil Classification System and design lateral soil loads are for moist conditions without hydrostatic pressure. Refer to Table R405.1.
  5. Unbalanced backfill height is the difference in height between the exterior finish ground level and the lower of the top of the concrete footing that supports the foundation wall or the interior finish ground levels. Where an interior concrete slab-on-grade is provided and in contact with the interior surface of the foundation wall, measurement of the unbalanced backfill height is permitted to be measured from the exterior finish ground level to the top of the interior concrete slab is permitted.
  6. The use of this table shall be prohibited for soil classifications not shown.

Masonry foundation walls shall be designed and constructed in accordance with the provisions of this section or in accordance with the provisions of TMS 402/ACI 530/ASCE 5. When TMS 402/ACI 530/ASCE 5 or the provisions of this section are used to design masonry foundation walls, project drawings, typical details and specifications are not required to bear the seal of the architect or engineer responsible for design, unless otherwise required by the state law of the jurisdiction having authority.

TABLE R404.1.2(1)

MINIMUM HORIZONTAL REINFORCEMENT FOR CONCRETE BASEMENT WALLSa, b

MAXIMUM UNSUPPORTED
HEIGHT OF BASEMENT WALL

(feet)
LOCATION OF HORIZONTAL REINFORCEMENT
≤ 8One No. 4 bar within 12 inches of the top of the wall story and one No. 4 bar near mid-height of the wall story.
> 8One No. 4 bar within 12 inches of the top of the wall story and one No. 4 bar near third points in the wall story.

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square inch = 6.895 kPa.

  1. Horizontal reinforcement requirements are for reinforcing bars with a minimum yield strength of 40,000 psi and concrete with a minimum concrete compressive strength of 2,500 psi.
  2. See Section R404.1.3.2 for minimum reinforcement required for foundation walls supporting above-grade concrete walls.

TABLE R404.1.2(2)

MINIMUM VERTICAL REINFORCEMENT FOR 6-INCH NOMINAL FLAT CONCRETE BASEMENT WALLSb, c, d, e, g, h, i, j, k

MAXIMUM UNSUPPORTED
WALL HEIGHT

(feet)
MAXIMUM UNBALANCED
BACKFILL HEIGHTf
(feet)
MINIMUM VERTICAL REINFORCEMENT-BAR SIZE AND SPACING (inches)
Soil classesa and design lateral soil (psf per foot of depth)
GW, GP, SW, SP
30
GM, GC, SM, SM-SC and ML
45
SC, ML-CL and inorganic CL
60
84NRNRNR
5NR6 @ 396 @ 48
65 @ 396 @ 486 @ 35
76 @ 486 @ 346 @ 25
86 @ 396 @ 256 @ 18
94NRNRNR
5NR5 @ 376 @ 48
65 @ 366 @ 446 @ 32
76 @ 476 @ 306 @ 22
86 @ 346 @ 226 @ 16
96 @ 276 @ 17DR
104NRNRNR
5NR5 @ 356 @ 48
66 @ 486 @ 416 @ 30
76 @ 436 @ 286 @ 20
86 @ 316 @ 20DR
96 @ 246 @ 15DR
106 @ 19DRDR

For SI: 1 inch = 25.4 mm; 1 foot = 304.8 mm; 1 pound per square foot per foot = 0.1571 kPa2/m, 1 pound per square inch = 6.895 kPa.

NR = Not required.

  1. Soil classes are in accordance with the Unified Soil Classification System. Refer to Table R405.1.
  2. Table values are based on reinforcing bars with a minimum yield strength of 60,000 psi concrete with a minimum specified compressive strength of 2,500 psi and vertical reinforcement being located at the centerline of the wall. See Section R404.1.3.3.7.2.
  3. Vertical reinforcement with a yield strength of less than 60,000 psi and/or bars of a different size than specified in the table are permitted in accordance with Section R404.1.3.3.7.6 and Table R404.1.2(9).
  4. Deflection criterion is L/240, where L is the height of the basement wall in inches.
  5. Interpolation is not permitted.
  6. Where walls will retain 4 feet or more of unbalanced backfill, they shall be laterally supported at the top and bottom before backfilling.
  7. NR indicates no vertical wall reinforcement is required, except for 6-inch-nominal walls formed with stay-in-place forming systems in which case vertical reinforcement shall be No. 4@48 inches on center.
  8. See Section R404.1.3.2 for minimum reinforcement required for basement walls supporting above-grade concrete walls.
  9. See Table R608.3 for tolerance from nominal thickness permitted for flat walls.
  10. DR means design is required in accordance with the applicable building code, or where there is no code, in accordance with ACI 318.
  11. The use of this table shall be prohibited for soil classifications not shown.

TABLE R404.1.2(3)

MINIMUM VERTICAL REINFORCEMENT FOR 8-INCH (203 mm) NOMINAL FLAT CONCRETE BASEMENT WALLSb, c, d, e, f, h, i, j

MAXIMUM UNSUPPORTED
WALL HEIGHT

(feet)
MAXIMUM UNBALANCED
BACKFILL HEIGHTg

(feet)
MINIMUM VERTICAL REINFORCEMENT-BAR SIZE AND SPACING (inches)
Soil classesa and design lateral soil (psf per foot of depth)
GW, GP, SW, SP
30
GM, GC, SM, SM-SC and ML
45
SC, ML-CL and inorganic CL
60
84NRNRNR
5NRNRNR
6NRNR6 @ 37
7NR6 @ 366 @ 35
86 @ 416 @ 356 @ 26
94NRNRNR
5NRNRNR
6NRNR6 @ 35
7NR6 @ 356 @ 32
86 @ 366 @ 326 @ 23
96 @ 356 @ 256 @ 18
104NRNRNR
5NRNRNR
6NRNR6 @ 35
7NR6 @ 356 @ 29
86 @ 356 @ 296 @ 21
96 @ 346 @ 226 @ 16
106 @ 276 @ 176 @ 13

For SI: 1 inch = 25.4 mm; 1 foot = 304.8 mm; 1 pound per square foot per foot = 0.1571 kPa2/m, 1 pound per square inch = 6.895 kPa.

NR = Not required.

  1. Soil classes are in accordance with the Unified Soil Classification System. Refer to Table R405.1.
  2. Table values are based on reinforcing bars with a minimum yield strength of 60,000 psi, concrete with a minimum specified compressive strength of 2,500 psi and vertical reinforcement being located at the centerline of the wall. See Section R404.1.3.3.7.2.
  3. Vertical reinforcement with a yield strength of less than 60,000 psi and/or bars of a different size than specified in the table are permitted in accordance with Section R404.1.3.3.7.6 and Table R404.1.2(9).
  4. NR indicates no vertical reinforcement is required.
  5. Deflection criterion is L/240, where L is the height of the basement wall in inches.
  6. Interpolation is not permitted.
  7. Where walls will retain 4 feet or more of unbalanced backfill, they shall be laterally supported at the top and bottom before backfilling.
  8. See Section R404.1.3.2 for minimum reinforcement required for basement walls supporting above-grade concrete walls.
  9. See Table R608.3 for tolerance from nominal thickness permitted for flat walls.
  10. The use of this table shall be prohibited for soil classifications not shown.

TABLE R404.1.2(4)

MINIMUM VERTICAL REINFORCEMENT FOR 10-INCH NOMINAL FLAT CONCRETE BASEMENT WALLSb, c, d, e, f, h, i, j

MAXIMUM UNSUPPORTED
WALL HEIGHT

(feet)
MAXIMUM UNBALANCED
BACKFILL HEIGHTg

(feet)
MINIMUM VERTICAL REINFORCEMENT-BAR SIZE AND SPACING (inches)
Soil classesa and design lateral soil (psf per foot of depth)
GW, GP, SW, SP
30
GM, GC, SM, SM-SC and ML
45
SC, ML-CL and inorganic CL
60
84NRNRNR
5NRNRNR
6NRNRNR
7NRNRNR
86 @ 486 @ 356 @ 28
94NRNRNR
5NRNRNR
6NRNRNR
7NRNR6 @ 31
8NR6 @ 316 @ 28
96 @ 376 @ 286 @ 24
104NRNRNR
5NRNRNR
6NRNRNR
7NRNR6 @ 28
8NR6 @ 286 @ 28
96 @ 336 @ 286 @ 21
106 @ 286 @ 236 @ 17

For SI: 1 inch = 25.4 mm; 1 foot = 304.8 mm; 1 pound per square foot per foot = 0.1571 kPa2/m, 1 pound per square inch = 6.895 kPa.

NR = Not required.

  1. Soil classes are in accordance with the Unified Soil Classification System. Refer to Table R405.1.
  2. Table values are based on reinforcing bars with a minimum yield strength of 60,000 psi concrete with a minimum specified compressive strength of 2,500 psi and vertical reinforcement being located at the centerline of the wall. See Section R404.1.3.3.7.2.
  3. Vertical reinforcement with a yield strength of less than 60,000 psi and/or bars of a different size than specified in the table are permitted in accordance with Section R404.1.3.3.7.6 and Table R404.1.2(9).
  4. NR indicates no vertical reinforcement is required.
  5. Deflection criterion is L/240, where L is the height of the basement wall in inches.
  6. Interpolation is not permitted.
  7. Where walls will retain 4 feet or more of unbalanced backfill, they shall be laterally supported at the top and bottom before backfilling.
  8. See Section R404.1.3.2 for minimum reinforcement required for basement walls supporting above-grade concrete walls.
  9. See Table R608.3 for tolerance from nominal thickness permitted for flat walls.
  10. The use of this table shall be prohibited for soil classifications not shown.

TABLE R404.1.2(5)

MINIMUM VERTICAL WALL REINFORCEMENT FOR 6-INCH WAFFLE-GRID BASEMENT WALLSb, c, d, e, g, h, i, j

MAXIMUM UNSUPPORTED
WALL HEIGHT

(feet)
MAXIMUM UNBALANCED
BACKFILL HEIGHTf
(feet)
MINIMUM VERTICAL REINFORCEMENT-BAR SIZE AND SPACING (inches)
Soil classesa and design lateral soil (psf per foot of depth)
GW, GP, SW, SP
30
GM, GC, SM, SM-SC and ML
45
SC, ML-CL and inorganic CL
60
844 @ 484 @ 466 @ 39
54 @ 455 @ 466 @ 47
65 @ 456 @ 40DR
76 @ 44DRDR
86 @ 32DRDR
944 @ 484 @ 464 @ 37
54 @ 425 @ 436 @ 44
65 @ 416 @ 37DR
76 @ 39DRDR
> 8DRiDRDR
1044 @ 484 @ 464 @ 35
54 @ 405 @ 406 @ 41
65 @ 386 @ 34DR
76 @ 36DRDR
> 8DRDRDR

For SI: 1 inch = 25.4 mm; 1 foot = 304.8 mm; 1 pound per square foot per foot = 0.1571 kPa2/m, 1 pound per square inch = 6.895 kPa.

  1. Soil classes are in accordance with the Unified Soil Classification System. Refer to Table R405.1.
  2. Table values are based on reinforcing bars with a minimum yield strength of 60,000 psi concrete with a minimum specified compressive strength of 2,500 psi and vertical reinforcement being located at the centerline of the wall. See Section R404.1.3.3.7.2.
  3. Maximum spacings shown are the values calculated for the specified bar size. Where the bar used is Grade 60 and the size specified in the table, the actual spacing in the wall shall not exceed a whole-number multiple of 12 inches (i.e., 12, 24, 36 and 48) that is less than or equal to the tabulated spacing. Vertical reinforcement with a yield strength of less than 60,000 psi and/or bars of a different size than specified in the table are permitted in accordance with Section R404.1.3.3.7.6 and Table R404.1.2(9).
  4. Deflection criterion is L/240, where L is the height of the basement wall in inches.
  5. Interpolation is not permitted.
  6. Where walls will retain 4 feet or more of unbalanced backfill, they shall be laterally supported at the top and bottom before backfilling.
  7. See Section R404.1.3.2 for minimum reinforcement required for basement walls supporting above-grade concrete walls.
  8. See Table R608.3 for thicknesses and dimensions of waffle-grid walls.
  9. DR means design is required in accordance with the applicable building code, or where there is no code, in accordance with ACI 318.
  10. The use of this table shall be prohibited for soil classifications not shown.

TABLE R404.1.2(6)

MINIMUM VERTICAL REINFORCEMENT FOR 8-INCH WAFFLE-GRID BASEMENT WALLSb, c, d, e, f, h, i, j, k

MAXIMUM UNSUPPORTED
WALL HEIGHT

(feet)
MAXIMUM UNBALANCED
BACKFILL HEIGHTg

(feet)
MINIMUM VERTICAL REINFORCEMENT-BAR SIZE AND SPACING (inches)
Soil classesa and design lateral soil (psf per foot of depth)
GW, GP, SW, SP
30
GM, GC, SM, SM-SC and ML
45
SC, ML-CL and inorganic CL
60
84NRNRNR
5NR5 @ 485 @ 46
65 @ 485 @ 436 @ 45
75 @ 466 @ 436 @ 31
86 @ 486 @ 326 @ 23
94NRNRNR
5NR5 @ 475 @ 46
65 @ 465 @ 396 @ 41
75 @ 426 @ 386 @ 28
86 @ 446 @ 286 @ 20
96 @ 346 @ 21DR
104NRNRNR
5NR5 @ 465 @ 44
65 @ 465 @ 376 @ 38
75 @ 386 @ 356 @ 25
86 @ 396 @ 25DR
96 @ 30DRDR
106 @ 24DRDR

For SI: 1 inch = 25.4 mm; 1 foot = 304.8 mm; 1 pound per square foot per foot = 0.1571 kPa2/m, 1 pound per square inch = 6.895 kPa.

NR = Not required.

  1. Soil classes are in accordance with the Unified Soil Classification System. Refer to Table R405.1.
  2. Table values are based on reinforcing bars with a minimum yield strength of 60,000 psi concrete with a minimum specified compressive strength of 2,500 psi and vertical reinforcement being located at the centerline of the wall. See Section R404.1.3.3.7.2.
  3. Maximum spacings shown are the values calculated for the specified bar size. Where the bar used is Grade 60 (420 MPa) and the size specified in the table, the actual spacing in the wall shall not exceed a whole-number multiple of 12 inches (i.e., 12, 24, 36 and 48) that is less than or equal to the tabulated spacing. Vertical reinforcement with a yield strength of less than 60,000 psi and/or bars of a different size than specified in the table are permitted in accordance with Section R404.1.3.3.7.6 and Table R404.1.2(9).
  4. NR indicates no vertical reinforcement is required.
  5. Deflection criterion is L/240, where L is the height of the basement wall in inches.
  6. Interpolation shall not be permitted.
  7. Where walls will retain 4 feet or more of unbalanced backfill, they shall be laterally supported at the top and bottom before backfilling.
  8. See Section R404.1.3.2 for minimum reinforcement required for basement walls supporting above-grade concrete walls.
  9. See Table R608.3 for thicknesses and dimensions of waffle-grid walls.
  10. DR means design is required in accordance with the applicable building code, or where there is no code, in accordance with ACI 318.
  11. The use of this table shall be prohibited for soil classifications not shown.

TABLE R404.1.2(7)

MINIMUM VERTICAL REINFORCEMENT FOR 6-INCH (152 mm) SCREEN-GRID BASEMENT WALLSb, c, d, e, g, h, i, j

MAXIMUM UNSUPPORTED
WALL HEIGHT

(feet)
MAXIMUM UNBALANCED
BACKFILL HEIGHTf

(feet)
MINIMUM VERTICAL REINFORCEMENT-BAR SIZE AND SPACING (inches)
Soil classesa and design lateral soil (psf per foot of depth)
GW, GP, SW, SP
30
GM, GC, SM, SM-SC and ML
45
SC, ML-CL and inorganic CL
60
844 @ 484 @ 485 @ 43
54 @ 485 @ 485 @ 37
65 @ 486 @ 456 @ 32
76 @ 48DRDR
86 @ 36DRDR
944 @ 484 @ 484 @ 41
54 @ 485 @ 486 @ 48
65 @ 456 @ 41DR
76 @ 43DRDR
> 8DRDRDR
1044 @ 484 @ 484 @ 39
54 @ 445 @ 446 @ 46
65 @ 426 @ 38DR
76 @ 40DRDR
> 8DRDRDR

For SI: 1 inch = 25.4 mm; 1 foot = 304.8 mm; 1 pound per square foot per foot = 0.1571 kPa2/m, 1 pound per square inch = 6.895 kPa.

  1. Soil classes are in accordance with the Unified Soil Classification System. Refer to Table R405.1.
  2. Table values are based on reinforcing bars with a minimum yield strength of 60,000 psi, concrete with a minimum specified compressive strength of 2,500 psi and vertical reinforcement being located at the centerline of the wall. See Section R404.1.3.3.7.2.
  3. Maximum spacings shown are the values calculated for the specified bar size. Where the bar used is Grade 60 and the size specified in the table, the actual spacing in the wall shall not exceed a whole-number multiple of 12 inches (i.e., 12, 24, 36 and 48) that is less than or equal to the tabulated spacing. Vertical reinforcement with a yield strength of less than 60,000 psi and/or bars of a different size than specified in the table are permitted in accordance with Section R404.1.3.3.7.6 and Table R404.1.2(9).
  4. Deflection criterion is L/240, where L is the height of the basement wall in inches.
  5. Interpolation is not permitted.
  6. Where walls will retain 4 feet or more of unbalanced backfill, they shall be laterally supported at the top and bottom before backfilling.
  7. See Sections R404.1.3.2 for minimum reinforcement required for basement walls supporting above-grade concrete walls.
  8. See Table R608.3 for thicknesses and dimensions of screen-grid walls.
  9. DR means design is required in accordance with the applicable building code, or where there is no code, in accordance with ACI 318.
  10. The use of this table shall be prohibited for soil classifications not shown.

TABLE R404.1.2(8)

MINIMUM VERTICAL REINFORCEMENT FOR 6-, 8-, 10- AND 12-INCH NOMINAL FLAT BASEMENT WALLSb, c, d, e, f, h, i, k, n, o

MAXIMUM
WALL

HEIGHT

(feet)
MAXIMUM
UNBALANCED

BACKFILL

HEIGHTg

(feet)
MINIMUM VERTICAL REINFORCEMENT-BAR SIZE AND SPACING (inches)
Soil classesa and design lateral soil (psf per foot of depth)
GW, GP, SW, SP
30
GM, GC, SM, SM-SC and ML
45
SC, ML-CL and inorganic CL
60
Minimum nominal wall thickness (inches)
681012681012681012
54NRNRNRNRNRNRNRNRNRNRNRNR
5NRNRNRNRNRNRNRNRNRNRNRNR
64NRNRNRNRNRNRNRNRNRNRNRNR
5NRNRNRNRNRNRlNRNR4 @ 35NRlNRNR
6NRNRNRNR5 @ 48NRNRNR5 @ 36NRNRNR
74NRNRNRNRNRNRNRNRNRNRNRNR
5NRNRNRNRNRNRNRNR5 @ 47NRNRNR
6NRNRNRNR5 @ 42NRNRNR6 @ 435 @ 48NRlNR
75 @ 46NRNRNR6 @ 425 @ 46NRlNR6 @ 346 @ 48NRNR
84NRNRNRNRNRNRNRNRNRNRNRNR
5NRNRNRNR4 @ 38NRlNRNR5 @ 43NRNRNR
64 @ 37NRlNRNR5 @ 37NRNRNR6 @ 375 @ 43NRlNR
75 @ 40NRNRNR6 @ 375 @ 41NRlNR6 @ 346 @ 43NRNR
86 @ 435 @ 47NRlNR6 @ 346 @ 43NRNR6 @ 276 @ 326 @ 44NR
94NRNRNRNRNRNRNRNRNRNRNRNR
5NRNRNRNR4 @ 35NRlNRNR5 @ 40NRNRNR
64 @ 34NRlNRNR6 @ 48NRNRNR6 @ 366 @ 39NRlNR
75 @ 36NRNRNR6 @ 345 @ 37NRNR6 @ 336 @ 385 @ 37NRl
86 @ 385 @ 41NRlNR6 @ 336 @ 385 @ 37NRl6 @ 246 @ 296 @ 394 @ 48m
96 @ 346 @ 46NRNR6 @ 266 @ 306 @ 41NR6 @ 196 @ 236 @ 306 @ 39
104NRNRNRNRNRNRNRNRNRNRNRNR
5NRNRNRNR4 @ 33NRlNRNR5 @ 38NRNRNR
65 @ 48NRlNRNR6 @ 45NRNRNR6 @ 345 @ 37NRNR
76 @ 47NRNRNR6 @ 346 @ 48NRNR6 @ 306 @ 356 @ 48NRl
86 @ 345 @ 38NRNR6 @ 306 @ 346 @ 47NRl6 @ 226 @ 266 @ 356 @ 45m
96 @ 346 @ 414 @ 48NRl6 @ 236 @ 276 @ 354 @ 48mDR6 @ 226 @ 276 @ 34
106 @ 286 @ 336 @ 45NRDRj6 @ 236 @ 296 @ 38DR6 @ 226 @ 226 @ 28

For SI: 1 inch = 25.4 mm; 1 foot = 304.8 mm; 1 pound per square foot per foot = 0.1571 kPa2/m, 1 pound per square inch = 6.895 kPa.

NR = Not required.

  1. Soil classes are in accordance with the Unified Soil Classification System. Refer to Table R405.1.
  2. Table values are based on reinforcing bars with a minimum yield strength of 60,000 psi.
  3. Vertical reinforcement with a yield strength of less than 60,000 psi and/or bars of a different size than specified in the table are permitted in accordance with Section R404.1.3.3.7.6 and Table R404.1.2(9).
  4. NR indicates no vertical wall reinforcement is required, except for 6-inch nominal walls formed with stay-in-place forming systems in which case vertical reinforcement shall be No.4@48 inches on center.
  5. Allowable deflection criterion is L/240, where L is the unsupported height of the basement wall in inches.
  6. Interpolation is not permitted.
  7. Where walls will retain 4 feet or more of unbalanced backfill, they shall be laterally supported at the top and bottom before backfilling.
  8. Vertical reinforcement shall be located to provide a cover of 11/4 inches measured from the inside face of the wall. The center of the steel shall not vary from the specified location by more than the greater of 10 percent of the wall thickness or 3/8 inch.
  9. Concrete cover for reinforcement measured from the inside face of the wall shall be not less than 3/4-inch. Concrete cover for reinforcement measured from the outside face of the wall shall be not less than 11/2 inches for No. 5 bars and smaller, and not less than 2 inches for larger bars.
  10. DR means design is required in accordance with the applicable building code, or where there is no code in accordance with ACI 318.
  11. Concrete shall have a specified compressive strength, ƒ'c, of not less than 2,500 psi at 28 days, unless a higher strength is required by Footnote l or m.
  12. The minimum thickness is permitted to be reduced 2 inches, provided the minimum specified compressive strength of concrete, ƒ'c, is 4,000 psi.
  13. A plain concrete wall with a minimum nominal thickness of 12 inches is permitted, provided minimum specified compressive strength of concrete, ƒ'c, is 3,500 psi.
  14. See Table R608.3 for tolerance from nominal thickness permitted for flat walls.
  15. The use of this table shall be prohibited for soil classifications not shown.

TABLE R404.1.2(9)

MINIMUM SPACING FOR ALTERNATE BAR SIZE AND/OR ALTERNATE GRADE OF STEELa, b, c

BAR SPACING FROM
APPLICABLE TABLE IN

SECTION R404.1.3.2

(inches)
BAR SIZE FROM APPLICABLE TABLE IN SECTION R404.1.3.2
#4#5#6
Alternate bar size and/or alternate grade of steel desired
Grade 60Grade 40Grade 60Grade 40Grade 60Grade 40
#5#6#4#5#6#4#6#4#5#6#4#5#4#5#6
Maximum spacing for alternate bar size and/or alternate grade of steel (inches)
81218581251135846245
91420691361346946346
1016227101561447957357
11172471116716571058357
12192681218817581158468
13202991319818691269469
142231914219206913610479
1523331016221021610147115710
1625351117231023711157115811
1726371118251124711168125811
1828401219261226812178135812
1929421320281227813189136913
2031441321291328913199146913
213346142231143091420101561014
223448152332143191521101671015
2336481524341533101522101671115
2437481625351534101623111771116
2539481726371635111724111881217
2640481727381737111725121881217
2742481828401738121826121981318
2843481929411840121926132081319
2945481930431941121927132091419
3047482031441943132028142191420
3148482132452044132129142291521
32484821334721451421301523101521
33484822344821471422311523101622
34484823354822481523321524101623
35484823364823481523331625111623
36484824374823481524341625111724
37484825384824481625351726111725
38484825394825481625361727121825
39484826404825481726371827121826
40484827414826481727381828121927
41484827424826481827391929121927
42484828434827481828401930132028
43484829444828481829412030132029
44484829454828481929422031132129
45484830474829481930432032142130
46484831484830482031442132142231
47484831484830482031442133142231
48484832484831482132452234152332

For SI: 1 inch = 25.4 mm, 1 pound per square inch = 6.895 kPa.

  1. This table is for use with tables in Section R404.1.3.2 that specify the minimum bar size and maximum spacing of vertical wall reinforcement for foundation walls and above-grade walls. Reinforcement specified in tables in Section R404.1.3.2 is based on Grade 60 steel reinforcement.
  2. Bar spacing shall not exceed 48 inches on center and shall be not less than one-half the nominal wall thickness.
  3. For Grade 50 steel bars (ASTM A996, Type R), use spacing for Grade 40 bars or interpolate between Grades 40 and 60.
Concrete masonry and clay masonry foundation walls shall be constructed as set forth in Table R404.1.1(1), R404.1.1(2), R404.1.1(3) or R404.1.1(4) and shall also comply with applicable provisions of Section R606. In buildings assigned to Seismic Design Categories D0, D1 and D2, concrete masonry and clay masonry foundation walls shall also comply with Section R404.1.4.1. Rubble stone masonry foundation walls shall be constructed in accordance with Sections R404.1.8 and R606.4.2. Rubble stone masonry walls shall not be used in Seismic Design Categories D0, D1 and D2.
Concrete foundation walls that support light-frame walls shall be designed and constructed in accordance with the provisions of this section, ACI 318, ACI 332 or PCA 100. Concrete foundation walls that support above-grade concrete walls that are within the applicability limits of Section R608.2 shall be designed and constructed in accordance with the provisions of this section, ACI 318, ACI 332 or PCA 100. Concrete foundation walls that support above-grade concrete walls that are not within the applicability limits of Section R608.2 shall be designed and constructed in accordance with the provisions of ACI 318, ACI 332 or PCA 100. When ACI 318, ACI 332, PCA 100 or the provisions of this section are used to design concrete foundation walls, project drawings, typical details and specifications are not required to bear the seal of the architect or engineer responsible for design, unless otherwise required by the state law of the jurisdiction having authority.
Concrete walls constructed in accordance with this code shall comply with the shapes and minimum concrete cross-sectional dimensions required by Table R608.3. Other types of forming systems resulting in concrete walls not in compliance with this section and Table R608.3 shall be designed in accordance with ACI 318.
Concrete foundation walls shall be laterally supported at the top and bottom. Horizontal reinforcement shall be provided in accordance with Table R404.1.2(1). Vertical reinforcement shall be provided in accordance with Table R404.1.2(2), R404.1.2(3), R404.1.2(4), R404.1.2(5), R404.1.2(6), R404.1.2(7) or R404.1.2(8). Vertical reinforcement for flat basement walls retaining 4 feet (1219 mm) or more of unbalanced backfill is permitted to be determined in accordance with Table R404.1.2(9). For basement walls supporting above-grade concrete walls, vertical reinforcement shall be the greater of that required by Tables R404.1.2(2) through R404.1.2(8) or by Section R608.6 for the above-grade wall. In buildings assigned to Seismic Design Category D0, D1 or D2, concrete foundation walls shall also comply with Section R404.1.4.2.

Foundation stem walls that support above-grade concrete walls shall be designed and constructed in accordance with this section.

  1. Stem walls not laterally supported at top. Concrete stem walls that are not monolithic with slabs-on-ground or are not otherwise laterally supported by slabs-on-ground shall comply with this section. Where unbalanced backfill retained by the stem wall is less than or equal to 18 inches (457 mm), the stem wall and above-grade wall it supports shall be provided with vertical reinforcement in accordance with Section R608.6 and Table R608.6(1), R608.6(2) or R608.6(3) for above-grade walls. Where unbalanced backfill retained by the stem wall is greater than 18 inches (457 mm), the stem wall and above-grade wall it supports shall be provided with vertical reinforcement in accordance with Section R608.6 and Table R608.6(4).
  2. Stem walls laterally supported at top. Concrete stem walls that are monolithic with slabs-on-ground or are otherwise laterally supported by slabs-on-ground shall be vertically reinforced in accordance with Section R608.6 and Table R608.6(1), R608.6(2) or R608.6(3) for abovegrade walls. Where the unbalanced backfill retained by the stem wall is greater than 18 inches (457 mm), the connection between the stem wall and the slab-on-ground, and the portion of the slab-on-ground providing lateral support for the wall shall be designed in accordance with PCA 100 or with accepted engineering practice. Where the unbalanced backfill retained by the stem wall is greater than 18 inches (457 mm), the minimum nominal thickness of the wall shall be 6 inches (152 mm).

Concrete foundation stem walls that support light-frame above-grade walls shall be designed and constructed in accordance with this section.

  1. Stem walls not laterally supported at top. Concrete stem walls that are not monolithic with slabs-on-ground or are not otherwise laterally supported by slabs-on-ground and retain 48 inches (1219 mm) or less of unbalanced fill, measured from the top of the wall, shall be constructed in accordance with Section R404.1.3. Foundation stem walls that retain more than 48 inches (1219 mm) of unbalanced fill, measured from the top of the wall, shall be designed in accordance with Sections R404.1.4 and R404.4.
  2. Stem walls laterally supported at top. Concrete stem walls that are monolithic with slabs-on-ground or are otherwise laterally supported by slabs-on-ground shall be constructed in accordance with Section R404.1.3. Where the unbalanced backfill retained by the stem wall is greater than 48 inches (1219 mm), the connection between the stem wall and the slab-on-ground, and the portion of the slab-on-ground providing lateral support for the wall, shall be designed in accordance with PCA 100 or in accordance with accepted engineering practice.
Materials used in concrete, the concrete itself and forms shall conform to requirements of this section or ACI 318.
The minimum specified compressive strength of concrete, ƒ'c, shall comply with Section R402.2 and shall be not less than 2,500 psi (17.2 MPa) at 28 days in buildings assigned to Seismic Design Category A, B or C and 3000 psi (20.5 MPa) in buildings assigned to Seismic Design Category D0, D1 or D2.
Mixing and delivery of concrete shall comply with ASTM C94 or ASTM C685.

The nominal maximum size of coarse aggregate shall not exceed one-fifth the narrowest distance between sides of forms, or three-fourths the clear spacing between reinforcing bars or between a bar and the side of the form.

Exception: When approved, these limitations shall not apply where removable forms are used and workability and methods of consolidation permit concrete to be placed without honeycombs or voids.

Proportions of materials for concrete shall be established to provide workability and consistency to permit concrete to be worked readily into forms and around reinforcement under conditions of placement to be employed, without segregation or excessive bleeding. Slump of concrete placed in removable forms shall not exceed 6 inches (152 mm).

Exception: When approved, the slump is permitted to exceed 6 inches (152 mm) for concrete mixtures that are resistant to segregation, and are in accordance with the form manufacturer's recommendations.

Slump of concrete placed in stay-in-place forms shall exceed 6 inches (152 mm). Slump of concrete shall be determined in accordance with ASTM C143.

Concrete shall be consolidated by suitable means during placement and shall be worked around embedded items and reinforcement and into corners of forms. Where stay-in-place forms are used, concrete shall be consolidated by internal vibration.

Exception: When approved for concrete to be placed in stay-in-place forms, self-consolidating concrete mixtures with slumps equal to or greater than 8 inches (203 mm) that are specifically designed for placement without internal vibration need not be internally vibrated.

Forms shall be made of wood, steel, aluminum, plastic, a composite of cement and foam insulation, a composite of cement and wood chips, or other approved material suitable for supporting and containing concrete. Forms shall provide sufficient strength to contain concrete during the concrete placement operation.

Form ties shall be steel, solid plastic, foam plastic, a composite of cement and wood chips, a composite of cement and foam plastic, or other suitable material capable of resisting the forces created by fluid pressure of fresh concrete.

Stay-in-place concrete forms shall comply with this section.

  1. Surface burning characteristics. The flame-spread index and smoke-developed index of forming material, other than foam plastic, left exposed on the interior shall comply with Section R302. The surface burning characteristics of foam plastic used in insulating concrete forms shall comply with Section R316.3.
  2. Interior covering. Stay-in-place forms constructed of rigid foam plastic shall be protected on the interior of the building as required by Section R316. Where gypsum board is used to protect the foam plastic, it shall be installed with a mechanical fastening system. Use of adhesives in addition to mechanical fasteners is permitted.
  3. Exterior wall covering. Stay-in-place forms constructed of rigid foam plastics shall be protected from sunlight and physical damage by the application of an approved exterior wall covering complying with this code. Exterior surfaces of other stay-in-place forming systems shall be protected in accordance with this code.
  4. Termite protection. In areas where the probability of termite infestation is "very heavy" as indicated by Table R301.2(1) or Figure R301.2(6), foam plastic insulation shall be permitted below grade on foundation walls in accordance with Section R318.8.
  5. Flat ICF wall system forms shall conform to ASTM E2634.
Steel reinforcement shall comply with the requirements of ASTM A615, A706, or A996. ASTM A996 bars produced from rail steel shall be Type R. In buildings assigned to Seismic Design Category A, B or C, the minimum yield strength of reinforcing steel shall be 40,000 psi (Grade 40) (276 MPa). In buildings assigned to Seismic Design Category D0, D1 or D2, reinforcing steel shall comply with the requirements of ASTM A706 for low-alloy steel with a minimum yield strength of 60,000 psi (Grade 60) (414 MPa).
The center of vertical reinforcement in basement walls determined from Tables R404.1.2(2) through R404.1.2(7) shall be located at the center-line of the wall. Vertical reinforcement in basement walls determined from Table R404.1.2(8) shall be located to provide a maximum cover of 11/4 inches (32 mm) measured from the inside face of the wall. Regardless of the table used to determine vertical wall reinforcement, the center of the steel shall not vary from the specified location by more than the greater of 10 percent of the wall thickness and 3/8 inch (10 mm). Horizontal and vertical reinforcement shall be located in foundation walls to provide the minimum cover required by Section R404.1.3.3.7.4.
Vertical wall reinforcement required by Section R404.1.3.2 that is interrupted by wall openings shall have additional vertical reinforcement of the same size placed within 12 inches (305 mm) of each side of the opening.
Reinforcement shall be secured in the proper location in the forms with tie wire or other bar support system to prevent displacement during the concrete placement operation. Steel reinforcement in concrete cast against the earth shall have a minimum cover of 3 inches (75 mm). Minimum cover for reinforcement in concrete cast in removable forms that will be exposed to the earth or weather shall be 11/2 inches (38 mm) for No. 5 bars and smaller, and 2 inches (50 mm) for No. 6 bars and larger. For concrete cast in removable forms that will not be exposed to the earth or weather, and for concrete cast in stay-in-place forms, minimum cover shall be 3/4 inch (19 mm). The minus tolerance for cover shall not exceed the smaller of one-third the required cover or 3/8 inch (10 mm).
Vertical and horizontal wall reinforcement shall be the longest lengths practical. Where splices are necessary in reinforcement, the length of lap splice shall be in accordance with Table R608.5.4.(1) and Figure R608.5.4(1). The maximum gap between noncontact parallel bars at a lap splice shall not exceed the smaller of one-fifth the required lap length and 6 inches (152 mm) [See Figure R608.5.4(1)].
Where tables in Section R404.1.3.2 specify vertical wall reinforcement based on minimum bar size and maximum spacing, which are based on Grade 60 (414 MPa) steel reinforcement, different size bars or bars made from a different grade of steel are permitted provided an equivalent area of steel per linear foot of wall is provided. Use of Table R404.1.2(9) is permitted to determine the maximum bar spacing for different bar sizes than specified in the tables or bars made from a different grade of steel. Bars shall not be spaced less than one-half the wall thickness, or more than 48 inches (1219 mm) on center.
Where reinforcement is required by this code to terminate with a standard hook, the hook shall comply with Section R608.5.4.5 and Figure R608.5.4(3).

Construction joints in foundation walls shall be made and located to not impair the strength of the wall. Construction joints in plain concrete walls, including walls required to have not less than No. 4 bars at 48 inches (1219 mm) on center by Sections R404.1.3.2 and R404.1.4.2, shall be located at points of lateral support, and a minimum of one No. 4 bar shall extend across the construction joint at a spacing not to exceed 24 inches (610 mm) on center. Construction joint reinforcement shall have a minimum of 12 inches (305 mm) embedment on both sides of the joint. Construction joints in reinforced concrete walls shall be located in the middle third of the span between lateral supports, or located and constructed as required for joints in plain concrete walls.

Exception: Use of vertical wall reinforcement required by this code is permitted in lieu of construction joint reinforcement provided the spacing does not exceed 24 inches (610 mm), or the combination of wall reinforcement and No.4 bars described above does not exceed 24 inches (610 mm).

Requirements for installation of masonry veneer, stucco and other wall coverings on the exterior of concrete walls and other construction details not covered in this section shall comply with the requirements of this code.
Concrete foundation walls supporting abovegrade concrete walls in townhouses assigned to Seismic Design Category C shall comply with ACI 318, ACI 332 or PCA 100 (see Section R404.1.3).

In buildings assigned to Seismic Design Category D0, D1 or D2, as established in Table R301.2(1), masonry foundation walls shall comply with this section. In addition to the requirements of Table R404.1.1(1), plain masonry foundation walls shall comply with the following:

  1. Wall height shall not exceed 8 feet (2438 mm).
  2. Unbalanced backfill height shall not exceed 4 feet (1219 mm).
  3. Minimum nominal thickness for plain masonry foundation walls shall be 8 inches (203 mm).
  4. Masonry stem walls shall have a minimum vertical reinforcement of one No. 4 (No. 13) bar located a maximum of 4 feet (1219 mm) on center in grouted cells. Vertical reinforcement shall be tied to the horizontal reinforcement in the footings.

Foundation walls, supporting more than 4 feet (1219 mm) of unbalanced backfill or exceeding 8 feet (2438 mm) in height shall be constructed in accordance with Table R404.1.1(2), R404.1.1(3) or R404.1.1(4). Masonry foundation walls shall have two No. 4 (No. 13) horizontal bars located in the upper 12 inches (305 mm) of the wall.

In buildings assigned to Seismic Design Category D0, D1 or D2, as established in Table R301.2(1), concrete foundation walls that support light-frame walls shall comply with this section, and concrete foundation walls that support above-grade concrete walls shall comply with ACI 318, ACI 332 or PCA 100 (see Section R404.1.3). In addition to the horizontal reinforcement required by Table R404.1.2(1), plain concrete walls supporting lightframe walls shall comply with the following.

  1. Wall height shall not exceed 8 feet (2438 mm).
  2. Unbalanced backfill height shall not exceed 4 feet (1219 mm).
  3. Minimum thickness for plain concrete foundation walls shall be 7.5 inches (191 mm) except that 6 inches (152 mm) is permitted where the maximum wall height is 4 feet, 6 inches (1372 mm).

Foundation walls less than 7.5 inches (191 mm) in thickness, supporting more than 4 feet (1219 mm) of unbalanced backfill or exceeding 8 feet (2438 mm) in height shall be provided with horizontal reinforcement in accordance with Table R404.1.2(1), and vertical reinforcement in accordance with Table R404.1.2(2), R404.1.2(3), R404.1.2(4), R404.1.2(5), R404.1.2(6), R404.1.2(7) or R404.1.2(8). Where Tables R404.1.2(2) through R404.1.2(8) permit plain concrete walls, not less than No. 4 (No. 13) vertical bars at a spacing not exceeding 48 inches (1219 mm) shall be provided.

The thickness of masonry or concrete foundation walls shall be not less than that required by Section R404.1.5.1 or R404.1.5.2, respectively.

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 degree = 0.0175 rad.

FIGURE R404.1.5(1)

FOUNDATION WALL CLAY MASONRY CURTAIN WALL WITH CONCRETE MASONRY PIERS

Masonry foundation walls shall be not less than the thickness of the wall supported, except that masonry foundation walls of at least 8-inch (203 mm) nominal thickness shall be permitted under brick veneered frame walls and under 10-inch-wide (254 mm) cavity walls where the total height of the wall supported, including gables, is not more than 20 feet (6096 mm), provided the requirements of Section R404.1.1 are met.

The thickness of concrete foundation walls shall be equal to or greater than the thickness of the wall in the story above. Concrete foundation walls with corbels, brackets or other projections built into the wall for support of masonry veneer or other purposes are not within the scope of the tables in this section.

Where a concrete foundation wall is reduced in thickness to provide a shelf for the support of masonry veneer, the reduced thickness shall be equal to or greater than the thickness of the wall in the story above. Vertical reinforcement for the foundation wall shall be based on Table R404.1.2(8) and located in the wall as required by Section R404.1.3.3.7.2 where that table is used. Vertical reinforcement shall be based on the thickness of the thinner portion of the wall.

Exception: Where the height of the reduced thickness portion measured to the underside of the floor assembly or sill plate above is less than or equal to 24 inches (610 mm) and the reduction in thickness does not exceed 4 inches (102 mm), the vertical reinforcement is permitted to be based on the thicker portion of the wall.

Use of pier and curtain wall foundations shall be permitted to support light-frame construction not more than two stories in height, provided the following requirements are met:

  1. All load-bearing walls shall be placed on continuous concrete footings placed integrally with the exterior wall footings.
  2. The minimum actual thickness of a load-bearing masonry wall shall be not less than 4 inches (102 mm) nominal or 33/8 inches (92 mm) actual thickness, and shall be bonded integrally with piers spaced in accordance with Section R606.6.4.
  3. Piers shall be constructed in accordance with Sections R606.7 and R606.7.1, and shall be bonded into the load-bearing masonry wall in accordance with Section R606.13.1 or R606.13.1.1.
  4. The maximum height of a 4-inch (102 mm) loadbearing masonry foundation wall supporting wood-frame walls and floors shall be not more than 4 feet (1219 mm).
  5. Anchorage shall be in accordance with Section R403.1.6, Figure R404.1.5(1), or as specified by engineered design accepted by the building official.
  6. The unbalanced fill for 4-inch (102 mm) foundation walls shall not exceed 24 inches (610 mm) for solid masonry or 12 inches (305 mm) for hollow masonry.
  7. In Seismic Design Categories D0, D1 and D2, prescriptive reinforcement shall be provided in the horizontal and vertical direction. Provide minimum horizontal joint reinforcement of two No. 9 gage wires spaced not less than 6 inches (152 mm) or one 1/4-inch-diameter (6.4 mm) wire at 10 inches (254 mm) on center vertically. Provide minimum vertical reinforcement of one No. 4 bar at 48 inches (1220 mm) on center horizontally grouted in place.
Concrete and masonry foundation walls shall extend above the finished grade adjacent to the foundation at all points a minimum of 4 inches (102 mm) where masonry veneer is used and a minimum of 6 inches (152 mm) elsewhere.

Backfill shall not be placed against the wall until the wall has sufficient strength and has been anchored to the floor above, or has been sufficiently braced to prevent damage by the backfill.

Exception: Bracing is not required for walls supporting less than 4 feet (1219 mm) of unbalanced backfill.

Rubble stone masonry foundation walls shall have a minimum thickness of 16 inches (406 mm), shall not support an unbalanced backfill exceeding 8 feet (2438 mm) in height, shall not support a soil pressure greater than 30 pounds per square foot per foot (4.71 kPa/m), and shall not be constructed in Seismic Design Categories D0, D1, D2 or townhouses in Seismic Design Category C, as established in Figure R301.2(2).
Isolated masonry piers shall be constructed in accordance with this section and the general masonry construction requirements of Section R606. Hollow masonry piers shall have a minimum nominal thickness of 8 inches (203 mm), with a nominal height not exceeding four times the nominal thickness and a nominal length not exceeding three times the nominal thickness. Where hollow masonry units are solidly filled with concrete or grout, piers shall be permitted to have a nominal height not exceeding ten times the nominal thickness. Footings for isolated masonry piers shall be sized in accordance with Section R403.1.1.
Hollow masonry piers shall be capped with 4 inches (102 mm) of solid masonry or concrete, a masonry cap block, or shall have cavities of the top course filled with concrete or grout. Where required, termite protection for the pier cap shall be provided in accordance with Section R318.
Masonry piers supporting wood girders sized in accordance with Tables R602.7(1) and R602.7(2) shall be permitted in accordance with this section. Piers supporting girders for interior bearing walls shall have a minimum nominal dimension of 12 inches (305 mm) and a maximum height of 10 feet (3048 mm) from top of footing to bottom of sill plate or girder. Piers supporting girders for exterior bearing walls shall have a minimum nominal dimension of 12 inches (305 mm) and a maximum height of 4 feet (1220 mm) from top of footing to bottom of sill plate or girder. Girders and sill plates shall be anchored to the pier or footing in accordance with Section R403.1.6 or Figure R404.1.5(1). Floor girder bearing shall be in accordance with Section R502.6.
Masonry piers supporting braced wall panels shall be designed in accordance with accepted engineering practice.
Masonry piers in dwellings located in Seismic Design Category D0, D1 or D2, and townhouses in Seismic Design Category C, shall be designed in accordance with accepted engineering practice.
Masonry piers for dwellings in flood hazard areas shall be designed in accordance with Section R322.
Wood foundation walls shall be constructed in accordance with the provisions of Sections R404.2.1 through R404.2.6 and with the details shown in Figures R403.1(2) and R403.1(3).
Load-bearing lumber shall be identified by the grade mark of a lumber grading or inspection agency which has been approved by an accreditation body that complies with DOC PS 20. In lieu of a grade mark, a certificate of inspection issued by a lumber grading or inspection agency meeting the requirements of this section shall be accepted. Wood structural panels shall conform to DOC PS 1 or DOC PS 2 and shall be identified by a grade mark or certificate of inspection issued by an approved agency.
The studs used in foundation walls shall be 2-inch by 6-inch (51 mm by 152 mm) members. When spaced 16 inches (406 mm) on center, a wood species with an Fb value of not less than 1,250 pounds per square inch (8619 kPa) as listed in ANSI AWC NDS shall be used. When spaced 12 inches (305 mm) on center, an Fb of not less than 875 psi (6033 kPa) shall be required.

For wood foundations that are not designed and installed in accordance with AWC PWF, the height of backfill against a foundation wall shall not exceed 4 feet (1219 mm). When the height of fill is more than 12 inches (305 mm) above the interior grade of a crawl space or floor of a basement, the thickness of the plywood sheathing shall meet the requirements of Table R404.2.3.

TABLE R404.2.3

PLYWOOD GRADE AND THICKNESS FOR WOOD FOUNDATION CONSTRUCTION (30 pcf equivalent-fluid weight soil pressure)

HEIGHT OF FILL
(inches)
STUD SPACING
(inches)
FACE GRAIN ACROSS STUDSFACE GRAIN PARALLEL TO STUDS
GradeaMinimum thickness
(inches)
Span ratingGradeaMinimum thickness
(inches)b, c
Span rating
2412B15/3232/16A15/3232/16
B15/32c32/16
16B15/3232/16A15/32c32/16
B19/32c (4, 5 ply)40/20
3612B15/3232/16A15/3232/16
B15/32c (4, 5 ply)32/16
B19/32 (4, 5 ply)40/20
16B15/32c32/16A19/3240/20
B23/3248/24
4812B15/3232/16A15/32c32/16
B19/32c (4, 5 ply)40/20
16B19/3240/20A19/32c40/20
A23/3248/24

For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per cubic foot = 0.1572 kN/m3.

  1. Plywood shall be of the following minimum grades in accordance with DOC PS 1 or DOC PS 2:

    1. DOC PS 1 Plywood grades marked:

      1. 1.1. Structural I C-D (Exposure 1).
      2. 1.2. C-D (Exposure 1).
    2. DOC PS 2 Plywood grades marked:

      1. 2.1. Structural I Sheathing (Exposure 1).
      2. 2.2. Sheathing (Exposure 1).
    3. Where a major portion of the wall is exposed above ground and a better appearance is desired, the following plywood grades marked exterior are suitable:

      1. 3.1. Structural I A-C, Structural I B-C or Structural I C-C (Plugged) in accordance with DOC PS 1.
      2. 3.2. A-C Group 1, B-C Group 1, C-C (Plugged) Group 1 or MDO Group 1 in accordance with DOC PS 1.
      3. 3.3. Single Floor in accordance with DOC PS 1 or DOC PS 2.
  2. Minimum thickness 15/32 inch, except crawl space sheathing shall have not less than 3/8 inch for face grain across studs 16 inches on center and maximum 2-foot depth of unequal fill.
  3. For this fill height, thickness and grade combination, panels that are continuous over less than three spans (across less than three stud spacings) require blocking 16 inches above the bottom plate. Offset adjacent blocks and fasten through studs with two 16d corrosion-resistant nails at each end.
Wood foundation walls shall not be backfilled until the basement floor and first floor have been constructed or the walls have been braced. For crawl space construction, backfill or bracing shall be installed on the interior of the walls prior to placing backfill on the exterior.
Wood foundation basements shall be drained and dampproofed in accordance with Sections R405 and R406, respectively.
Wood structural panel foundation wall sheathing shall be attached to framing in accordance with Table R602.3(1) and Section R402.1.1.
Wood sill plates shall be a minimum of 2-inch by 4-inch (51 mm by 102 mm) nominal lumber. Sill plate anchorage shall be in accordance with Sections R403.1.6 and R602.11.
Retaining walls that are not laterally supported at the top and that retain in excess of 48 inches (1219 mm) of unbalanced fill, or retaining walls exceeding 24 inches (610 mm) in height that resist lateral loads in addition to soil, shall be designed in accordance with accepted engineering practice to ensure stability against overturning, sliding, excessive foundation pressure and water uplift. Retaining walls shall be designed for a safety factor of 1.5 against lateral sliding and overturning. This section shall not apply to foundation walls supporting buildings.
Precast concrete foundation walls shall be designed in accordance with accepted engineering practice. The design and manufacture of precast concrete foundation wall panels shall comply with the materials requirements of Section R402.3 or ACI 318. The panel design drawings shall be prepared by a registered design professional where required by the statutes of the jurisdiction in which the project is to be constructed in accordance with Section R107 of the Florida Building Code, Building.

Precast concrete foundation wall design drawings shall be submitted to the building official and approved prior to installation. Drawings shall include, at a minimum, the following information:

  1. Design loading as applicable.
  2. Footing design and material.
  3. Concentrated loads and their points of application.
  4. Soil bearing capacity.
  5. Maximum allowable total uniform load.
  6. Seismic design category.
  7. Basic wind speed.
Precast concrete foundation wall panels shall be identified by a certificate of inspection label issued by an approved third-party inspection agency.

Drains shall be provided around concrete or masonry foundations that retain earth and enclose habitable or usable spaces located below grade. Drainage tiles, gravel or crushed stone drains, perforated pipe or other approved systems or materials shall be installed at or below the area to be protected and shall discharge by gravity or mechanical means into an approved drainage system. Gravel or crushed stone drains shall extend not less than 1 foot (305 mm) beyond the outside edge of the footing and 6 inches (152 mm) above the top of the footing and be covered with an approved filter membrane material. The top of open joints of drain tiles shall be protected with strips of building paper. Except where otherwise recommended by the drain manufacturer, perforated drains shall be surrounded with an approved filter membrane or the filter membrane shall cover the washed gravel or crushed rock covering the drain. Drainage tiles or perforated pipe shall be placed on a minimum of 2 inches (51 mm) of washed gravel or crushed rock not less than one sieve size larger than the tile joint opening or perforation and covered with not less than 6 inches (152 mm) of the same material.

Exception: A drainage system is not required where the foundation is installed on well-drained ground or sand-gravel mixture soils according to the Unified Soil Classification System, Group I soils, as detailed in Table R405.1.

TABLE R405.1

PROPERTIES OF SOILS CLASSIFIED ACCORDING TO THE UNIFIED SOIL CLASSIFICATION SYSTEM

SOIL
GROUP
UNIFIED SOIL
CLASSIFICATION

SYSTEM SYMBOL
SOIL DESCRIPTIONDRAINAGE
CHARACTERISTICSa
FROST HEAVE
POTENTIAL
VOLUME CHANGE
POTENTIAL

EXPANSIONb
Group IGWWell-graded gravels, gravel sand mixtures, little or no
fines
GoodLowLow
GPPoorly graded gravels or gravel sand mixtures, little or
no fines
GoodLowLow
SWWell-graded sands, gravelly sands, little or no finesGoodLowLow
SPPoorly graded sands or gravelly sands, little or no finesGoodLowLow
GMSilty gravels, gravel-sand-silt mixturesGoodMediumLow
SMSilty sand, sand-silt mixturesGoodMediumLow
Group IIGCClayey gravels, gravel-sand-clay mixturesMediumMediumLow
SCClayey sands, sand-clay mixtureMediumMediumLow
MLInorganic silts and very fine sands, rock flour, silty or
clayey fine sands or clayey silts with slight plasticity
MediumHighLow
CLInorganic clays of low to medium plasticity, gravelly
clays, sandy clays, silty clays, lean clays
MediumMediumMedium to Low
Group IIICHInorganic clays of high plasticity, fat claysPoorMediumHigh
MHInorganic silts, micaceous or diatomaceous fine sandy
or silty soils, elastic silts
PoorHighHigh
Group IVOLOrganic silts and organic silty clays of low plasticityPoorMediumMedium
OHOrganic clays of medium to high plasticity, organic
silts
UnsatisfactoryMediumHigh
PtPeat and other highly organic soilsUnsatisfactoryMediumHigh

For SI: 1 inch = 25.4 mm.

  1. The percolation rate for good drainage is over 4 inches per hour, medium drainage is 2 inches to 4 inches per hour, and poor is less than 2 inches per hour.
  2. Soils with a low potential expansion typically have a plasticity index (PI) of 0 to 15, soils with a medium potential expansion have a PI of 10 to 35 and soils with a high potential expansion have a PI greater than 20.
Precast concrete walls that retain earth and enclose habitable or useable space located below-grade that rest on crushed stone footings shall have a perforated drainage pipe installed below the base of the wall on either the interior or exterior side of the wall, not less than 1 foot (305 mm) beyond the edge of the wall. If the exterior drainage pipe is used, an approved filter membrane material shall cover the pipe. The drainage system shall discharge into an approved sewer system or to daylight.
Wood foundations enclosing habitable or usable spaces located below grade shall be adequately drained in accordance with Sections R405.2.1 through R405.2.3.
A porous layer of gravel, crushed stone or coarse sand shall be placed to a minimum thickness of 4 inches (102 mm) under the basement floor. Provision shall be made for automatic draining of this layer and the gravel or crushed stone wall footings.
A 6-mil-thick (0.15 mm) polyethylene vapor retarder shall be applied over the porous layer with the basement floor constructed over the polyethylene.
In other than Group I soils, a sump shall be provided to drain the porous layer and footings. The sump shall be not less than 24 inches (610 mm) in diameter or 20 inches square (0.0129 m2), shall extend not less than 24 inches (610 mm) below the bottom of the basement floor and shall be capable of positive gravity or mechanical drainage to remove any accumulated water. The drainage system shall discharge into an approved sewer system or to daylight.

Except where required by Section R406.2 to be waterproofed, foundation walls that retain earth and enclose interior spaces and floors below grade shall be dampproofed from the higher of (a) the top of the footing or (b) 6 inches (152 mm) below the top of the basement floor, to the finished grade. Masonry walls shall have not less than 3/8 inch (9.5 mm) portland cement parging applied to the exterior of the wall. The parging shall be dampproofed in accordance with one of the following:

  1. Bituminous coating.
  2. Three pounds per square yard (1.63 kg/m2) of acrylic modified cement.
  3. One-eighth-inch (3.2 mm) coat of surface-bonding cement complying with ASTM C887.
  4. Any material permitted for waterproofing in Section R406.2.
  5. Other approved methods or materials.

Exception: Parging of unit masonry walls is not required where a material is approved for direct application to the masonry.

Concrete walls shall be dampproofed by applying any one of the listed dampproofing materials or any one of the waterproofing materials listed in Section R406.2 to the exterior of the wall.

In areas where a high water table or other severe soil-water conditions are known to exist, exterior foundation walls that retain earth and enclose interior spaces and floors below grade shall be waterproofed from the higher of (a) the top of the footing or (b) 6 inches (152 mm) below the top of the basement floor, to the finished grade. Walls shall be waterproofed in accordance with one of the following:

  1. Two-ply hot-mopped felts.
  2. Fifty-five-pound (25 kg) roll roofing.
  3. Six-mil (0.15 mm) polyvinyl chloride.
  4. Six-mil (0.15 mm) polyethylene.
  5. Forty-mil (1 mm) polymer-modified asphalt.
  6. Sixty-mil (1.5 mm) flexible polymer cement.
  7. One-eighth-inch (3 mm) cement-based, fiber-reinforced, waterproof coating.
  8. Sixty-mil (1.5 mm) solvent-free liquid-applied synthetic rubber.

Exception: Organic-solvent-based products such as hydrocarbons, chlorinated hydrocarbons, ketones and esters shall not be used for ICF walls with expanded polystyrene form material. Use of plastic roofing cements, acrylic coatings, latex coatings, mortars and pargings to seal ICF walls is permitted. Cold-setting asphalt or hot asphalt shall conform to Type C of ASTM D449. Hot asphalt shall be applied at a temperature of less than 200°F (93°C).

All joints in membrane waterproofing shall be lapped and sealed with an adhesive compatible with the membrane.

Wood foundations enclosing habitable or usable spaces located below grade shall be dampproofed in accordance with Sections R406.3.1 through R406.3.4.
Plywood panel joints in the foundation walls shall be sealed full length with a caulking compound capable of producing a moistureproof seal under the conditions of temperature and moisture content at which it will be applied and used.
A 6-mil-thick (0.15 mm) polyethylene film shall be applied over the below-grade portion of exterior foundation walls prior to backfilling. Joints in the polyethylene film shall be lapped 6 inches (152 mm) and sealed with adhesive. The top edge of the polyethylene film shall be bonded to the sheathing to form a seal. Film areas at grade level shall be protected from mechanical damage and exposure by a pressure-preservative treated lumber or plywood strip attached to the wall several inches above finished grade level and extending approximately 9 inches (229 mm) below grade. The joint between the strip and the wall shall be caulked full length prior to fastening the strip to the wall. Where approved, other coverings appropriate to the architectural treatment shall be permitted to be used. The polyethylene film shall extend down to the bottom of the wood footing plate but shall not overlap or extend into the gravel or crushed stone footing.
The space between the excavation and the foundation wall shall be backfilled with the same material used for footings, up to a height of 1 foot (305 mm) above the footing for well-drained sites, or one-half the total back-fill height for poorly drained sites. The porous fill shall be covered with strips of 30-pound (13.6 kg) asphalt paper or 6-mil (0.15 mm) polyethylene to permit water seepage while avoiding infiltration of fine soils.
The remainder of the excavated area shall be backfilled with the same type of soil as was removed during the excavation.
Except where required by Section R406.2 to be waterproofed, precast concrete foundation walls enclosing habitable or useable spaces located below grade shall be dampproofed in accordance with Section R406.1.
Precast concrete foundation panel joints shall be sealed full height with a sealant meeting ASTM C920, Type S or M, Grade NS, Class 25, Use NT, M or A. Joint sealant shall be installed in accordance with the manufacturer's instructions.
Wood columns shall be protected against decay as set forth in Section R317.
All surfaces (inside and outside) of steel columns shall be given a shop coat of rust-inhibitive paint, except for corrosion-resistant steel and steel treated with coatings to provide corrosion resistance.

The columns shall be restrained to prevent lateral displacement at the bottom end. Wood columns shall be not less in nominal size than 4 inches by 4 inches (102 mm by 102 mm). Steel columns shall be not less than 3-inch-diameter (76 mm) Schedule 40 pipe manufactured in accordance with ASTM A53 Grade B or approved equivalent.

Exception: In Seismic Design Categories A, B and C, columns not more than 48 inches (1219 mm) in height on a pier or footing are exempt from the bottom end lateral displacement requirement within under-floor areas enclosed by a continuous foundation.

The under-floor space between the bottom of the floor joists and the earth under any building (except space occupied by a basement) shall have ventilation openings through foundation walls or exterior walls. The minimum net area of ventilation openings shall be not less than 1 square foot (0.0929 m2) for each 150 square feet (14 m2) of under-floor space area, unless the ground surface is covered by a Class 1 vapor retarder material. Where a Class 1 vapor retarder material is used, the minimum net area of ventilation openings shall be not less than 1 square foot (0.0929 m2) for each 1,500 square feet (140 m2) of under-floor space area. One such ventilating opening shall be within 3 feet (914 mm) of each corner of the building.

The minimum net area of ventilation openings shall be not less than 1 square foot (0.0929 m2) for each 150 square feet (14 m2) of under-floor area. One ventilation opening shall be within 3 feet (915 mm) of each corner of the building. Ventilation openings shall be covered for their height and width with any of the following materials provided that the least dimension of the covering shall not exceed 1/4 inch (6.4 mm):

  1. Perforated sheet metal plates not less than 0.070 inch (1.8 mm) thick.
  2. Expanded sheet metal plates not less than 0.047 inch (1.2 mm) thick.
  3. Cast-iron grill or grating.
  4. Extruded load-bearing brick vents.
  5. Hardware cloth of 0.035 inch (0.89 mm) wire or heavier.
  6. Corrosion-resistant wire mesh, with the least dimension being 1/8 inch (3.2 mm) thick.

Exception: The total area of ventilation openings shall be permitted to be reduced to 1/1,500 of the under-floor area where the ground surface is covered with an approved Class I vapor retarder material and the required openings are placed to provide cross ventilation of the space. The installation of operable louvers shall not be prohibited.

Ventilation openings in under-floor spaces specified in Sections R408.1 and R408.2 shall not be required where the following items are provided:

  1. Exposed earth is covered with a continuous Class I vapor retarder. Joints of the vapor retarder shall overlap by 6 inches (152 mm) and shall be sealed or taped. The edges of the vapor retarder shall extend not less than 6 inches (152 mm) up the stem wall and shall be attached and sealed to the stem wall or insulation.
  2. One of the following is provided for the under-floor space:

    1. 2.1. Continuously operated mechanical exhaust ventilation at a rate equal to 1 cubic foot per minute (0.47 L/s) for each 50 square feet (4.7 m2) of crawl space floor area, including an air pathway to the common area (such as a duct or transfer grille), and perimeter walls insulated in accordance with the Florida Building Code, Energy Conservation.
    2. 2.2. Conditioned air supply sized to deliver at a rate equal to 1 cubic foot per minute (0.47 L/s) for each 50 square feet (4.7 m2) of under-floor area, including a return air pathway to the common area (such as a duct or transfer grille), and perimeter walls insulated in accordance with the Florida Building Code, Energy Conservation.
    3. 2.3. Plenum in existing structures complying with Section M1601.5, if under-floor space is used as a plenum.
Access shall be provided to all under-floor spaces. Access openings through the floor shall be a minimum of 18 inches by 24 inches (457 mm by 610 mm). Openings through a perimeter wall shall be not less than 16 inches by 24 inches (407 mm by 610 mm). Where any portion of the through-wall access is below grade, an areaway not less than 16 inches by 24 inches (407 mm by 610 mm) shall be provided. The bottom of the areaway shall be below the threshold of the access opening. Through wall access openings shall not be located under a door to the residence. See Section M1305.1.4 for access requirements where mechanical equipment is located under floors.
The under-floor grade shall be cleaned of all vegetation and organic material. All wood forms used for placing concrete shall be removed before a building is occupied or used for any purpose. All construction materials shall be removed before a building is occupied or used for any purpose.
The finished grade of under-floor surface shall be permitted to be located at the bottom of the footings; however, where there is evidence that the groundwater table can rise to within 6 inches (152 mm) of the finished floor at the building perimeter or where there is evidence that the surface water does not readily drain from the building site, the grade in the under-floor space shall be as high as the outside finished grade, unless an approved drainage system is provided.

For buildings located in flood hazard areas as established in Table R301.2(1):

  1. Walls enclosing the under-floor space shall be provided with flood openings in accordance with Section R322.2.2.
  2. The finished ground level of the under-floor space shall be equal to or higher than the outside finished ground level on at least one side.

    Exception: Under-floor spaces that meet the requirements of FEMA TB 11-1.

Analyzing code differences
UpCodes Premium
Leverage the most sophisticated code compliance platform.
TRY FREE FOR TWO WEEKS VISIT PRICING