This Electrical Part (Chapters 34 through 43) is produced and copyrighted by the National Fire Protection Association (NFPA) and is based on the 2014 National Electrical Code® (NEC®) (NFPA 70®-2014), copyright 2013, National Fire Protection Association, all rights reserved. Use of the Electrical Part is pursuant to license with the NFPA.
The title National Electrical Code®, the acronym NEC® and the document number NFPA 70® are registered trademarks of the National Fire Protection Association, Quincy, Massachusetts. The section numbers appearing in parentheses or brackets after IRC text are the section numbers of the corresponding text in the National Electrical Code (NFPA 70).
IMPORTANT NOTICE AND DISCLAIMER CONCERNING THE NEC AND THIS ELECTRICAL PART.
This Electrical Part is a compilation of provisions extracted from the 2014 edition of the NEC. The NEC, like all NFPA codes and standards, is developed through a consensus standards development process approved by the American National Standards Institute. This process brings together volunteers representing varied viewpoints and interests to achieve consensus on fire and other safety issues. While the NFPA administers the process and establishes rules to promote fairness in the development of consensus, it does not independently test, evaluate or verify the accuracy of any information or the soundness of any judgments contained in its codes and standards.
The NFPA disclaims liability for any personal injury, property or other damages of any nature whatsoever, whether special, indirect, consequential or compensatory, directly or indirectly resulting from the publication, use of, or reliance on the NEC or this Electrical Part. The NFPA also makes no guaranty or warranty as to the accuracy or completeness of any information published in these documents.
In issuing and making the NEC and this Electrical Part available, the NFPA is not undertaking to render professional or other services for or on behalf of any person or entity. Nor is the NFPA undertaking to perform any duty owed by any person or entity to someone else. Anyone using these documents should rely on his or her own independent judgment or, as appropriate, seek the advice of a competent professional in determining the exercise of reasonable care in any given circumstances.
The NFPA has no power, nor does it undertake, to police or enforce compliance with the contents of the NEC and this Electrical Part. Nor does the NFPA list, certify, test, or inspect products, designs, or installations for compliance with these documents. Any certification or other statement of compliance with the requirements of these documents shall not be attributable to the NFPA and is solely the responsibility of the certifier or maker of the statement.
For additional notices and disclaimers concerning NFPA codes and standards see www.nfpa.org/disclaimers.
Enclosures, other than surrounding fences or walls, of panelboards, meter sockets, enclosed switches, transfer switches, circuit breakers, pullout switches and motor controllers, rated not over 600 volts nominal and intended for such locations, shall be marked with an enclosure-type number as shown in Table E3404.4.
Table E3404.4 shall be used for selecting these enclosures for use in specific locations other than hazardous (classified) locations. The enclosures are not intended to protect against conditions such as condensation, icing, corrosion, or contamination that might occur within the enclosure or enter through the conduit or unsealed openings. (110.28)
TABLE E3404.4 (Table 110.28)
ENCLOSURE SELECTION
PROVIDES A DEGREE OF PROTECTION AGAINST THE FOLLOWING ENVIRONMENTAL CONDITIONS | FOR OUTDOOR USE | |||||||||
Enclosure-type Number | ||||||||||
3 | 3R | 3S | 3X | 3RX | 3SX | 4 | 4X | 6 | 6P | |
Incidental contact with the enclosed equipment | X | X | X | X | X | X | X | X | X | X |
Rain, snow and sleet | X | X | X | X | X | X | X | X | X | X |
Sleeta | — | — | X | — | — | X | — | — | — | — |
Windblown dust | X | — | X | X | — | X | X | X | X | X |
Hosedown | — | — | — | — | — | — | X | X | X | X |
Corrosive agents | — | — | — | X | X | X | — | X | — | X |
Temporary submersion | — | — | — | — | — | — | — | — | X | X |
Prolonged submersion | — | — | — | — | — | — | — | — | — | X |
PROVIDES A DEGREE OF PROTECTION AGAINST THE FOLLOWING ENVIRONMENTAL CONDITIONS | FOR INDOOR USE | |||||||||
Enclosure-type Number | ||||||||||
1 | 2 | 4 | 4X | 5 | 6 | 6P | 12 | 12K | 13 | |
Incidental contact with the enclosed equipment | X | X | X | X | X | X | X | X | X | X |
Falling dirt | X | X | X | X | X | X | X | X | X | X |
Falling liquids and light splashing | — | X | X | X | X | X | X | X | X | X |
Circulating dust, lint, fibers and flyings | — | — | X | X | — | X | X | X | X | X |
Settling airborne dust, lint, fibers and flings | — | — | X | X | X | X | X | X | X | X |
Hosedown and splashing water | — | — | X | X | — | X | X | — | — | — |
Oil and coolant seepage | — | — | — | — | — | — | — | X | X | X |
Oil or coolant spraying and splashing | — | — | — | — | — | — | — | — | — | X |
Corrosive agents | — | — | — | X | — | — | X | — | — | — |
Temporary submersion | — | — | — | — | — | X | X | — | — | — |
Prolonged submersion | — | — | — | — | — | — | X | — | — | — |
- a. Mechanism shall be operable when ice covered.
- Note 1: The term raintight is typically used in conjunction with Enclosure Types 3, 3S, 3SX, 3X, 4, 4X, 6 and 6P. The term rainproof is typically used in conjunction with Enclosure Types 3R and 3RX. The term watertight is typically used in conjunction with Enclosure Types 4, 4X, 6 and 6P. The term driptight is typically used in conjunction with Enclosure Types 2, 5, 12, 12K and 13. The term dusttight is typically used in conjunction with Enclosure Types 3, 3S, 3SX, 3X, 5, 12, 12K and 13.
- Note 2: Ingress protection (IP) ratings are found in ANSI/NEMA 60529, Degrees of Protection Provided by Enclosures. IP ratings are not a substitute for enclosure-type ratings.
Where caution, warning, or danger signs or labels are required by this code, the labels shall meet the following requirements:
- The marking shall adequately warn of the hazard using effective words, colors, or symbols or combinations of such.
- Labels shall be permanently affixed to the equipment or wiring method.
- Labels shall not be hand written except for portions of labels or markings that are variable, or that could be subject to changes. Labels shall be legible.
- Labels shall be of sufficient durability to withstand the environment involved. [110.21(B)]
Access and working space shall be provided and maintained around all electrical equipment to permit ready and safe operation and maintenance of such equipment in accordance with this section and Figure E3405.1. (110.26)
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm.
- Equipment, piping and ducts foreign to the electrical installation shall not be placed in the shaded areas extending from the floor to a height of 6 feet above the panelboard enclosure, or to the structural ceiling, whichever is lower.
- The working space shall be clear and unobstructed from the floor to a height of 6.5 feet or the height of the equipment, whichever is greater.
- The working space shall not be designated for storage.
- Panelboards, service equipment and similar enclosures shall not be located in bathrooms, toilet rooms, clothes closets or over the steps of a stairway.
- Such work spaces shall be provided with artificial lighting where located indoors and shall not be controlled by automatic means only.
FIGURE E3405.1a, b, c, d, e
WORKING SPACE AND CLEARANCES
Except as otherwise specified in Chapters 34 through 43, the dimension of the working space in the direction of access to panelboards and live parts of other equipment likely to require examination, adjustment, servicing or maintenance while energized shall be not less than 36 inches (914 mm) in depth. Distances shall be measured from the energized parts where such parts are exposed or from the enclosure front or opening where such parts are enclosed. In addition to the 36- inch dimension (914 mm), the work space shall not be less than 30 inches (762 mm) wide in front of the electrical equipment and not less than the width of such equipment. The work space shall be clear and shall extend from the floor or platform to a height of 6.5 feet (1981 mm) or the height of the equipment, whichever is greater. In all cases, the work space shall allow at least a 90-degree (1.57 rad) opening of equipment doors or hinged panels. Equipment associated with the electrical installation located above or below the electrical equipment shall be permitted to extend not more than 6 inches (152 mm) beyond the front of the electrical equipment. [110.26(A) (1), (2), (3)]
Exceptions:
- In existing dwelling units, service equipment and panelboards that are not rated in excess of 200 amperes shall be permitted in spaces where the height of the working space is less than 6.5 feet (1981 mm). [110.26(A)(3) Exception No. 1]
- Meters that are installed in meter sockets shall be permitted to extend beyond the other equipment. Meter sockets shall not be exempt from the requirements of this section. [110.26(A)(3) Exception No. 2]
The indoor space equal to the width and depth of the panelboard and extending from the floor to a height of 6 feet (1829 mm) above the panelboard, or to the structural ceiling, whichever is lower, shall be dedicated to the electrical installation. Piping, ducts, leak protection apparatus and other equipment foreign to the electrical installation shall not be installed in such dedicated space. The area above the dedicated space shall be permitted to contain foreign systems, provided that protection is installed to avoid damage to the electrical equipment from condensation, leaks and breaks in such foreign systems (see Figure E3405.1).
Exception: Suspended ceilings with removable panels shall be permitted within the 6-foot (1829 mm) dedicated space.
Connectors and terminals for conductors that are more finely stranded than Class B and Class C stranding as shown in Table E3406.9, shall be identified for the specific conductor class or classes. (110.14)
TABLE E3406.9 (Chapter 9, Table 10)
CONDUCTOR STRANDINGc
CONDUCTOR SIZE | NUMBER OF STRANDS | |||
Copper | Aluminum | |||
AWG or kcmil | mm2 | Class B | Class C | Class B |
24-30 | 0.20-0.05 | a | — | — |
22 | 0.32 | 7 | — | — |
20 | 0.52 | 10 | — | — |
18 | 0.82 | 16 | — | — |
16 | 1.3 | 26 | — | — |
14-2 | 2.1-33.6 | 7 | 19 | 7b |
1-4/0 | 42.4-107 | 19 | 37 | 19 |
250-500 | 127-253 | 37 | 61 | 37 |
600-1000 | 304-508 | 61 | 91 | 61 |
1250-1500 | 635-759 | 91 | 127 | 91 |
1750-2000 | 886-1016 | 127 | 271 | 127 |
- Number of strands vary
- Aluminum 14 AWG (2.1 mm2) is not available.
- With the permission of Underwriters Laboratories, Inc., this material is reproduced from UL Standard 486A-B, Wire Connectors, which is copyrighted by Underwriters Laboratories, Inc., Northbrook, Illinois. While use of this material has been authorized, UL shall not be responsible for the manner in which the information is presented, nor for any interpretations thereof
Conductors in raceways shall be continuous between outlets, boxes, and devices and shall be without splices or taps in the raceway.
Exception: Splices shall be permitted within surface-mounted raceways that have a removable cover. [300.13(A)]
Equipment grounding conductors, grounding electrode conductors, and bonding jumpers shall be connected by one or more of the following means:
- Listed pressure connectors.
- Terminal bars.
- Pressure connectors listed as grounding and bonding equipment.
- Exothermic welding process.
- Machine screw-type fasteners that engage not less than two threads or are secured with a nut.
- Thread-forming machine screws that engage not less than two threads in the enclosure.
- Connections that are part of a listed assembly.
- Other listed means. [250.8 (A)]
Equipment grounding conductors of sizes 6 AWG and smaller shall be identified by a continuous green color or a continuous green color with one or more yellow stripes on the insulation or covering, except where bare. Conductors with insulation or individual covering that is green, green with one or more yellow stripes, or otherwise identified as permitted by this section shall not be used for ungrounded or grounded circuit conductors. (250.119)
Equipment grounding conductors 4 AWG and larger AWG that are not identified as required for conductors of sizes 6 AWG and smaller shall, at the time of installation, be permanently identified as an equipment grounding conductor at each end and at every point where the conductor is accessible, except where such conductors are bare.
The required identification for conductors 4 AWG and larger shall encircle the conductor and shall be accomplished by one of the following:
- Stripping the insulation or covering from the entire exposed length.
- Coloring the exposed insulation or covering green at the termination.
- Marking the exposed insulation or covering with green tape or green adhesive labels at the termination. [250.119(A)]
Exceptions:
- Conductors 4 AWG and larger shall not be required to be identified in conduit bodies that do not contain splices or unused hubs. [250.119(A)(1) Exception]
- Power-limited, Class 2 or Class 3 circuit cables containing only circuits operating at less than 50 volts shall be permitted to use a conductor with green insulation for other than equipment grounding purposes. [250.119 Exception No. 1]
Insulation on the ungrounded conductors shall be a continuous color other than white, gray and green. [310.110(C)]
Exception: An insulated conductor that is part of a cable or flexible cord assembly and that has a white or gray finish or a finish marking with three continuous white or gray stripes shall be permitted to be used as an ungrounded conductor where it is permanently reidentified to indicate its use as an ungrounded conductor by marking tape, painting, or other effective means at all terminations and at each location where the conductor is visible and accessible. Identification shall encircle the insulation and shall be a color other than white, gray, and green. [200.7(C)(1)]
Where used for single-pole, 3-way or 4-way switch loops, the reidentified conductor with white or gray insulation or three continuous white or gray stripes shall be used only for the supply to the switch, not as a return conductor from the switch to the outlet. [200.7(C)(2)]
All devices excluding panelboards, provided with terminals for the attachment of conductors and intended for connection to more than one side of the circuit shall have terminals properly marked for identification, except where the terminal intended to be connected to the grounded conductor is clearly evident. [200.10(A)]
Exception: Terminal identification shall not be required for devices that have a normal current rating of over 30 amperes, other than polarized attachment caps and polarized receptacles for attachment caps as required in Section E3407.4.2. [200.10(A) Exception]