Heads up:
There are no amended sections in this chapter.
The provisions of this chapter shall control the design and construction of all walls and partitions for all buildings.
Exception: Buildings and structures located within the High-Velocity Hurricane Zone shall comply with the provisions of Chapter 44.
Wall construction shall be capable of accommodating all loads imposed according to Section R301 and of transmitting the resulting loads to the supporting structural elements.
Compressible floor-covering materials that compress more than 1/32 inch (0.8 mm) when subjected to 50 pounds (23 kg) applied over 1 inch square (645 mm) of material and are greater than 1/8 inch (3 mm) in thickness in the uncompressed state shall not extend beneath walls, partitions or columns, which are fastened to the floor.
Load-bearing dimension lumber for studs, plates and headers shall be identified by a grade mark of a lumber grading or inspection agency that has been approved by an accreditation body that complies with DOC PS 20. In lieu of a grade mark, a certification of inspection issued by a lumber grading or inspection agency meeting the requirements of this section shall be accepted.
Approved end-jointed lumber identified by a grade mark conforming to Section R602.1 may be used interchangeably with solid-sawn members of the same species and grade. End-jointed lumber used in an assembly required elsewhere in this code to have a fire-resistance rating shall have the designation "Heat Resistant Adhesive" or "HRA" included in its grade mark.
Glued laminated timbers shall be manufactured and identified as required in ANSI/AITC A190.1 and ASTM D 3737.
Stress grading of structural log members of nonrectangular shape, as typically used in log buildings, shall be in accordance with ASTM D 3957. Such structural log members shall be identified by the grade mark of an approved lumber grading or inspection agency. In lieu of a grade mark on the material, a certificate of inspection as to species and grade, issued by a lumber-grading or inspection agency meeting the requirements of this section, shall be permitted to be accepted.
Structural capacities for structural composite lumber shall be established and monitored in accordance with ASTM D 5456.
Fireblocking shall be provided in accordance with Section R302.11.
Load-bearing headers are not required in interior or exterior nonbearing walls. A single flat 2-inch by 4-inch (51 mm by 102 mm) member may be used as a header in interior or exterior nonbearing walls for openings up to 8 feet (2438 mm) in width if the vertical distance to the parallel nailing surface above is not more than 24 inches (610 mm). For such nonbearing headers, no cripples or blocking are required above the header.
R602.2.2.1 [IRC 602.5] Interior nonbearing walls. Interior nonbearing walls shall be permitted to be constructed with 2-inch by 3-inch (51 mm by 76 mm) studs spaced 24 inches (610 mm) on center or, when not part of a braced wall line, 2-inch by 4-inch (51 mm by 102 mm) flat studs spaced at 16 inches (406 mm) on center. Interior nonbearing walls shall be capped with at least a single top plate. Interior nonbearing walls shall be fireblocked in accordance with Section R302.11.
Drilling and notching of studs shall be in accordance with the following:
- Notching. Any stud in an exterior wall or bearing partition may be cut or notched to a depth not exceeding 25 percent of its width. Studs in nonbearing partitions may be notched to a depth not to exceed 40 percent of a single stud width.
- Drilling. Any stud may be bored or drilled, provided that the diameter of the resulting hole is no more than 60 percent of the stud width, the edge of the hole is no more than 5/8 inch (16 mm) to the edge of the stud, and the hole is not located in the same section as a cut or notch. Studs located in exterior walls or bearing partitions drilled over 40 percent and up to 60 percent shall also be doubled with no more than two successive doubled studs bored. See Figures R602.2.3(1) and R602.2.3(2) [IRC Figures R602.6(1) and R602.6(2)].
Exception: Use of approved stud shoes is permitted when they are installed in accordance with the manufacturer's recommendations.

FIGURE R602.2.3(1) [IRC FIGURE R602.6(1)]
NOTCHING AND BORED HOLE LIMITATIONS FOR EXTERIOR WALLS AND BEARING WALLS
NOTCHING AND BORED HOLE LIMITATIONS FOR EXTERIOR WALLS AND BEARING WALLS

FIGURE R602.2.3(2) [IRC FIGURE R602.6(2)]
NOTCHING AND BORED HOLE LIMITATIONS FOR INTERIOR NONBEARING WALLS
NOTCHING AND BORED HOLE LIMITATIONS FOR INTERIOR NONBEARING WALLS
When piping or ductwork is placed in or partly in an exterior wall or interior load-bearing wall, necessitating cutting, drilling or notching of the top plate by more than 50 percent of its width, a galvanized metal tie not less than 0.054 inch thick (1.37 mm) (16 ga) and 11/2 inches (38 mm) wide shall be fastened across and to the plate at each side of the opening with not less than eight 10d (0.148 inch diameter) having a minimum length of 11/2 inches (38 mm) at each side or equivalent. The metal tie must extend a minimum of 6 inches past the opening. See Figure R602.2.3.1 [IRC Figure R602.6.1].
FIGURE R602.2.3.1 [IRC FIGURE R602.6.1]
TOP PLATE FRAMING TO ACCOMMODATE PIPING
Exception:
When the entire side of the wall with the notch or cut is covered by wood structural panel sheathing.

TOP PLATE FRAMING TO ACCOMMODATE PIPING
Exterior walls of light-frame wood construction shall be designed and constructed in accordance with the provisions of Section R301.2.1.1 or in accordance with the AF&PA NDS. Exterior walls of light-frame wood construction shall also comply with Sections R602.1 and R602.2.
Table R602.3(1) Fastener Schedule For Structural Members.
Reserved.
Reserved.
Figure R602.3(1) Typical Wall, Floor And Roof Framing.
Reserved.
Reserved.
Table R602.3(2) Alternate Attachments To Table R602.3(1).
Reserved.
Reserved.
Figure R602.3(2) Framing Details.
Reserved.
Reserved.
Table R602.3(3) Requirements For Wood Structural Panel Wall Sheathing Used To Resist Wind Pressures.
Reserved.
Reserved.
Table R602.3(4) Allowable Spans For Particleboard Wall Sheathing.
Reserved.
Reserved.
Table R602.3(5) Size, Height And Spacing Of Wood Studs.
Reserved.
Reserved.
Reserved.
Table R602.3.1 Maximum Allowable Length Of Wood Wall Studs Exposed To Wind Speeds Of 100 MPH Or Less In Seismic Design Categories A, B, C, D0, D1 and D2.
Reserved.
Reserved.
Reserved.
Reserved.
Reserved.
Reserved.
Reserved.
Reserved.
[Moved to Section R602.2.3.]
Figure R602.6(1) Notching And Bored Hole Limitations For Exterior Walls And Bearing Walls.
[Moved to Figure R602.2.3(1).]
[Moved to Figure R602.2.3(1).]
Figure R602.6(2) Notching And Bored Hole Limitations For Interior Nonbearing Walls.
[Moved to Figure R602.2.3(2).]
[Moved to Figure R602.2.3(2).]
Reserved.
Reserved.
Reserved.
Table R602.7.1 Spans For Minimum No.2 Grade Single Header.
Reserved.
Reserved.
Figure R602.7.1(1) Single Member Header In Exterior Bearing Wall.
Reserved.
Reserved.
Figure R602.7.1(2) Alternative Single Member Header Without Cripple.
Reserved.
Reserved.
Reserved.
Table R602.7.2 Maximum Spans For Wood Structural Panel Box Headers.
Reserved.
Reserved.
Figure R602.7.2 Typical Wood Structural Panel Box Header Construction.
Reserved.
Reserved.
Reserved.
Reserved.
Reserved.
Reserved.
Reserved.
Reserved.
Figure R602.10.1.1 Braced Wall Lines
Figure R602.10.1.1 Braced Wall Lines
Reserved.
Reserved.
Reserved.
Reserved.
Reserved.
Reserved.
Table R602.10.3(1) Bracing Requirements Based On Wind Speed.
Reserved.
Reserved.
Table R602.10.3(2) Wind Adjustment Factors To The Required Length Of Wall Bracing.
Reserved.
Reserved.
Table R602.10.3(3) Bracing Requirements Based On Seismic Design Category.
Reserved.
Reserved.
Table R602.10.3(4) Seismic Adjustment Factors To The Required Length Of Wall Bracing.
Reserved.
Reserved.
Reserved.
Reserved.
Reserved.
Reserved.
Table R602.10.5 Minimum Length Of Braced Wall Panels.
Reserved.
Reserved.
Figure R602.10.5 Braced Wall Panels With Continuous Sheathing.
Reserved.
Reserved.
Reserved.
Reserved.
Table R602.10.5.2 Partial Credit For Braced Wall Panels Less Than 48 Inches In Actual Length.
Reserved.
Table R602.10.5.2 Partial Credit For Braced Wall Panels Less Than 48 Inches In Actual Length.
Reserved.
Reserved.
Reserved.
Table R602.10.6.1
Minimum Hold-Down Forces For Method ABW Braced Wall Panels.
Reserved.
Figure R602.10.6.1
Method ABW—Alternate Braced Wall Panel.
Reserved.
Table R602.10.6.1
Minimum Hold-Down Forces For Method ABW Braced Wall Panels.
Reserved.
Figure R602.10.6.1
Method ABW—Alternate Braced Wall Panel.
Reserved.
Reserved.
Figure R602.10.6.3
Method PFG—Portal Frame At Garage Door Openings In Seismic Design Categories A, B And C.
Reserved.
Figure R602.10.6.3
Method PFG—Portal Frame At Garage Door Openings In Seismic Design Categories A, B And C.
Reserved.
Reserved.
Table R602.10.6.4
Tension Strap Capacity Required For Resisting Wind Pressures Perpendicular To Method PFH, PFG And CS-PF Braced Wall Panels.
Reserved.
Figure R602.10.6.4
Method CS-PF—Continuously Sheathed Portal Frame Panel Construction.
Reserved.
Table R602.10.6.4
Tension Strap Capacity Required For Resisting Wind Pressures Perpendicular To Method PFH, PFG And CS-PF Braced Wall Panels.
Reserved.
Figure R602.10.6.4
Method CS-PF—Continuously Sheathed Portal Frame Panel Construction.
Reserved.
Reserved.
Table R602.10.6.5
Method BV-WSP Wall Bracing Requirements.
Reserved.
Figure R602.10.6.5
Method BV-WSP—Wall Bracing For Dwellings With Stone And Masonry Veneer In Seismic Design Categories D0, D1 and D2.
Reserved.
Table R602.10.6.5
Method BV-WSP Wall Bracing Requirements.
Reserved.
Figure R602.10.6.5
Method BV-WSP—Wall Bracing For Dwellings With Stone And Masonry Veneer In Seismic Design Categories D0, D1 and D2.
Reserved.
Reserved.
Reserved.
Figure R602.10.7 End Conditions For Braced Wall Lines With Continuous Sheathing.
Reserved.
Reserved.
Reserved.
Figure R602.10.8(1) Braced Wall Panel Connection When Perpendicular To Floor/Ceiling Framing.
Reserved.
Reserved.
Figure R602.10.8(2) Braced Wall Panel Connection When Parallel To Floor/Ceiling Framing.
Reserved.
Reserved.
Reserved.
Reserved.
Figure R602.10.8.2(1)
Braced Wall Panel Connection To Perpendicular Rafters.
Reserved.
Figure R602.10.8.2(2)
Braced Wall Panel Connection Option To Perpendicular Rafters Or Roof Trusses.
Reserved.
Figure R602.10.8.2(3)
Braced Wall Panel Connection Option To Perpendicular Rafters Or Roof Trusses.
Reserved.
Figure R602.10.8.2(1)
Braced Wall Panel Connection To Perpendicular Rafters.
Reserved.
Figure R602.10.8.2(2)
Braced Wall Panel Connection Option To Perpendicular Rafters Or Roof Trusses.
Reserved.
Figure R602.10.8.2(3)
Braced Wall Panel Connection Option To Perpendicular Rafters Or Roof Trusses.
Reserved.
Reserved.
Reserved.
Reserved.
Reserved.
Reserved.
Reserved.
Reserved.
Reserved.
Reserved.
Reserved.
Figure R602.11.2 Stepped Foundation Construction.
Reserved.
Reserved.
Reserved.
Reserved.
Figure R602.12.1 Rectangle Circumscribing An Enclosed Building.
Reserved.
Reserved.
Reserved.
Reserved.
R602.12.3.1 Multiple bracing units. Reserved.
Reserved.
Table R602.12.4 Minimum Number Of Bracing Units On Each Side Of The Circumscribed Rectangle.
Reserved.
Reserved.
Reserved.
Figure R602.12.5 Bracing Unit Distribution.
Reserved.
Reserved.
Reserved.
R602.12.6.1 Method CS-G. Reserved. R602.12.6.2 Method CS-PF.
Reserved. R602.12.6.3 Methods PFH and PFG.
Reserved.
Reserved.
Reserved.
Wood structural panels shall conform to DOC PS 1, DOC PS 2 or ANSI/APA PRP 210 or, when manufactured in Canada, CSA O437 or CSA O325. All panels shall be identified by a grade mark or certificate of inspection issued by an approved agency.
The maximum allowable spans for wood structural panel wall sheathing shall not exceed the values set forth in the standard used for design of building as specified in Section R301.2.1.1.
Wood structural panel wall sheathing shall be attached to framing in accordance with the standard used for design of building as specified in Section R301.2.1.1. Wood structural panels marked Exposure 1 or Exterior are considered water-repellent sheathing under the code.
Particleboard shall conform to ANSI A208.1 and shall be so identified by a grade mark or certificate of inspection issued by an approved agency. Particleboard shall comply with the grades specified in the standard used for design of building as specified in Section R301.2.1.1.
Masonry construction shall be designed and constructed in accordance with the provisions of this section, TMS 403 or in accordance with the provisions of TMS 402/ACI 530/ASCE 5.
When the empirical design provisions of Chapter 5 of TMS 402/ACI 530/ASCE 5, the provisions of TMS 403, or the provisions of this section are used to design masonry, project drawings, typical details and specifications are not required to bear the seal of the architect or engineer responsible for design, unless otherwise required by the state law of the jurisdiction having authority.
The minimum nominal thickness of exterior concrete masonry walls shall be 8 inches (203 mm) or shall be designed in accordance with Section R606.1.
Reserved.
Reserved.
Where walls of masonry of hollow units or masonry-bonded hollow walls are decreased in thickness, a course of solid masonry shall be constructed between the wall below and the thinner wall above, or special units or construction shall be used to transmit the loads from face shells or wythes above to those below.
Unreinforced solid masonry parapet walls shall not be less than 8 inches (203 mm) in thickness and their height shall not exceed four times their thickness. Unreinforced hollow unit masonry parapet walls shall be not less than 8 inches (203 mm) in thickness, and their height shall not exceed three times their thickness. Masonry parapets in areas subject to wind loads shall be reinforced in accordance with ACI 530/ASCE 5/TMS 402. Masonry parapets, located in Seismic Design Category D0, D1 or D2, or on townhouses in Seismic Design Category C shall be reinforced in accordance with Section R606.12.
Solid masonry units or masonry units filled with mortar or grout shall be used for corbeling.
The maximum projection of one unit shall not exceed one-half the height of the unit or one-third the thickness at right angles to the wall. The maximum corbeled projection beyond the face of the wall shall not exceed:
When corbeled masonry is used to support floor or roof-framing members, the top course of the corbel shall be a header course or the top course bed joint shall have ties to the vertical wall.
Each masonry wythe shall be supported by at least two-thirds of the wythe thickness.
Cavity wall or masonry veneer construction may be supported on an 8-inch (203 mm) foundation wall, provided the 8-inch (203 mm) wall is corbeled to the width of the wall system above with masonry constructed of solid masonry units or masonry units filled with mortar or grout. The total horizontal projection of the corbel shall not exceed 2 inches (51 mm) with individual corbels projecting not more than one-third the thickness of the unit or one-half the height of the unit. The hollow space behind the corbeled masonry shall be filled with mortar or grout.
Concrete masonry units shall be hollow or solid unit masonry in accordance with ASTM C 90 and shall have a minimum net area compressive strength of 1900 psi in compliance with ASTM C 90. Mortar shall comply with Section R607.1. In determining the stresses in masonry, the effects of all loads and conditions of loading and the influence of all forces affecting the design and strength of the several parts shall be taken into account.
Table R606.5 Allowable Compressive Stresses For Empirical Design Of Masonry.
Reserved.
Reserved.
In walls or other structural members composed of different kinds or grades of units, materials or mortars, the maximum stress shall not exceed the allowable stress for the weakest of the combination of units, materials and mortars of which the member is composed. The net thickness of any facing unit that is used to resist stress shall not be less than 1.5 inches (38 mm).
Reserved.
Hollow piers shall be capped with 4 inches (102 mm) of solid masonry or concrete, a masonry cap block, or shall have cavities of the top course filled with concrete or grout or other approved methods.
Chases and recesses in masonry walls shall not be deeper than one-third the wall thickness, and the maximum length of a horizontal chase or horizontal projection shall not exceed 4 feet (1219 mm), and shall have at least 8 inches (203 mm) of masonry in back of the chases and recesses and between adjacent chases or recesses and the jambs of openings. Chases and recesses in masonry walls shall be designed and constructed so as not to reduce the required strength or required fire resistance of the wall and in no case shall a chase or recess be permitted within the required area of a pier. Masonry directly above chases or recesses wider than 12 inches (305 mm) shall be supported on noncombustible lintels.
When masonry units are laid in stack bond, horizontal joint reinforcement shall be placed in bed joints at not more than 16 inches (406 mm) on center. Horizontal joint reinforcement shall be a minimum of 9-gage and shall be in addition to required vertical reinforcement, Joint reinforcement shall be embedded in accordance with R606.13.6.
Reserved.
Table R606.9 Spacing Of Lateral Support For Masonry Walls.
Reserved.
Reserved.
Reserved.
R606.9.1.1 Bonding pattern. Reserved. R606.9.1.2 Metal reinforcement.
Reserved.
Reserved.
Reserved.
Figure R606.11(1) Anchorage Requirements For Masonry Walls Located In Seismic Design Category A, B Or C And Where Wind Loads Are Less Than 30 PSF.
Reserved.
Reserved.
Figure R606.11(2) Requirements for reinforced grouted masonry construction in seismic design Category C.
Reserved.
Reserved.
Figure R606.11(3) Requirements for reinforced masonry construction in seismic design Category D0, D1, or D2.
Reserved.
Reserved.
The seismic requirements of this section shall apply to the design of masonry and the construction of masonry building elements located in Seismic Design Category D0, D1 or D2. Townhouses in Seismic Design Category C shall comply with the requirements of Section R606.12.2. These requirements shall not apply to glass unit masonry conforming to Section R610 or masonry veneer conforming to Section R703.7.
Masonry structures and masonry elements shall comply with the requirements of Sections R606.12.2 through R606.12.4 based on the seismic design category established in Table R301.2(1). Masonry structures and masonry elements shall comply with the requirements of Section R606.12 or shall be designed in accordance with TMS 402/ACI 530/ASCE 5 or TMS 403.
R606.12.1.1 Floor and roof diaphragm construction. Floor and roof diaphragms shall be constructed of wood structural panels attached to wood framing in accordance with Section R602 or to cold-formed steel floor framing in accordance with AISI S230 or to cold-formed steel roof framing in accordance with AISI S230. Additionally, sheathing panel edges perpendicular to framing members shall be backed by blocking, and sheathing shall be connected to the blocking with fasteners at the edge spacing. For Seismic Design Categories C, D0, D1 and D2, where the width-to-thickness dimension of the diaphragm exceeds 2-to-1, edge spacing of fasteners shall be 4 inches (102 mm) on center.
Townhouses located in Seismic Design Category C shall comply with the requirements of this section.
Table R606.12.2.1 shall be used to determine the minimum required solid wall length without openings at each masonry exterior wall. The provided percentage of solid wall length shall include only those wall segments that are 3 feet (914 mm) or longer. The maximum clear distance between wall segments included in determining the solid wall length shall not exceed 18 feet (5486 mm). Shear wall segments required to meet the minimum wall length shall be in accordance with Section R606.12.2.2.3.
NP = Not permitted, except with design in accordance with the Florida Building Code, Building.
SESIMIC DESIGN CATEGORY | MINIMUM SOLID WALL LENGTH (percent)a | ||
One story or top story of two story | Wall supporting light-framed second story and roof | Wall supporting masonry second story and roof | |
Townhouses in C | 20 | 25 | 35 |
D0 or D1 | 25 | NP | NP |
D2 | 30 | NP | NP |
Elements not part of the lateral force-resisting system shall be analyzed to determine their effect on the response of the system. The frames or columns shall be adequate for vertical load carrying capacity and induced moment caused by the design story drift.
Masonry partition walls, masonry screen walls and other masonry elements that are not designed to resist vertical or lateral loads, other than those induced by their own weight, shall be isolated from the structure so that vertical and lateral forces are not imparted to these elements. Isolation joints and connectors between these elements and the structure shall be designed to accommodate the design story drift.
Masonry elements listed in Section R606.12.2.2.2 shall be reinforced in either the horizontal or vertical direction in accordance with the following:
- Horizontal reinforcement. Horizontal joint reinforcement shall consist of at least two longitudinal W1.7 wires spaced not more than 16 inches (406 mm) for walls greater than 4 inches (102 mm) in width and at least one longitudinal W1.7 wire spaced not more than 16 inches (406 mm) for walls not exceeding 4 inches (102 mm) in width; or at least one No. 4 bar spaced not more than 48 inches (1219 mm). Where two longitudinal wires of joint reinforcement are used, the space between these wires shall be the widest that the mortar joint will accommodate. Horizontal reinforcement shall be provided within 16 inches (406 mm) of the top and bottom of these masonry elements.
- Vertical reinforcement. Vertical reinforcement shall consist of at least one No. 4 bar spaced not more than 48 inches (1219 mm). Vertical reinforcement shall be located within 16 inches (406 mm) of the ends of masonry walls.
Connectors shall be provided to transfer forces between masonry walls and horizontal elements in accordance with the requirements of Section 1.7.4 of TMS 402/ACI 530/ASCE 5. Connectors shall be designed to transfer horizontal design forces acting either perpendicular or parallel to the wall, but not less than 200 pounds per linear foot (2919 N/m) of wall. The maximum spacing between connectors shall be 4 feet (1219 mm). Such anchorage mechanisms shall not induce tension stresses perpendicular to grain in ledgers or nailers.
Connectors shall be provided to transfer forces between masonry columns and horizontal elements in accordance with the requirements of Section 1.7.4 of TMS 402/ACI 530/ASCE 5. Where anchor bolts are used to connect horizontal elements to the tops of columns, the bolts shall be placed within lateral ties. Lateral ties shall enclose both the vertical bars in the column and the anchor bolts. There shall be a minimum of two No. 4 lateral ties provided in the top 5 inches (127 mm) of the column.
Vertical reinforcement of at least one No. 4 bar shall be provided at corners, within 16 inches (406 mm) of each side of openings, within 8 inches (203 mm) of each side of movement joints, within 8 inches (203 mm) of the ends of walls, and at a maximum spacing of 10 feet (3048 mm).
Horizontal joint reinforcement shall consist of at least two wires of W1.7 spaced not more than 16 inches (406 mm); or bond beam reinforcement of at least one No. 4 bar spaced not more than 10 feet (3048 mm) shall be provided. Horizontal reinforcement shall also be provided at the bottom and top of wall openings and shall extend not less than 24 inches (610 mm) nor less than 40 bar diameters past the opening; continuously at structurally connected roof and floor levels; and within 16 inches (406 mm) of the top of walls.
Structures in Seismic Design Category D0 or D1 shall comply with the requirements of Seismic Design Category C and the additional requirements of this section.
Masonry elements other than those covered by Section R606.12.2.2.2 shall be designed in accordance with the requirements of Chapter 1 and Sections 2.1 and 2.3 of TMS 402, ACI 530/ASCE 5 and shall meet the minimum reinforcement requirements contained in Sections R606.12.3.2 and R606.12.3.2.1. Otherwise, masonry shall be designed in accordance with TMS 403.
Exception:
Masonry walls limited to one story in height and 9 feet (2743 mm) between lateral supports need not be designed provided they comply with the minimum reinforcement requirements of Sections R606.12.3.2 and R606.12.3.2.1.
Masonry walls other than those covered by Section R606.12.2.2.3 shall be reinforced in both the vertical and horizontal direction. The sum of the cross-sectional area of horizontal and vertical reinforcement shall be at least 0.002 times the gross crosssectional area of the wall, and the minimum cross-sectional area in each direction shall be not less than 0.0007 times the gross cross-sectional area of the wall. Reinforcement shall be uniformly distributed. Table R606.12.3.2 shows the minimum reinforcing bar sizes required for varying thicknesses of masonry walls. The maximum spacing of reinforcement shall be 48 inches (1219 mm) provided that the walls are solid grouted and constructed of hollow open-end units, hollow units laid with full head joints or two wythes of solid units. The maximum spacing of reinforcement shall be 24 inches (610 mm) for all other masonry.
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 square inch per foot = 2064 mm2/m.
NOMINAL WALL THICKNESS (inches) | MINIMUM SUM OF THE VERTICAL AND HORIZONTAL REINFORCEMENT AREASa (square inches per foot) | MINIMUM REINFORCEMENT AS DISTRIBUTED IN BOTH HORIZONTAL AND VERTICAL DIRECTIONSb (square inches per foot) | MINUMUM BAR SIZE FOR REINFORCEMENT SPACED AT 48 INCHES |
6 | 0.135 | 0.047 | #4 |
8 | 0.183 | 0.064 | #5 |
10 | 0.231 | 0.081 | #6 |
12 | 0.279 | 0.098 | #6 |
- Based on the minimum reinforcing ratio of 0.002 times the gross cross-sectional area of the wall.
- Based on the minimum reinforcing ratio each direction of 0.0007 times the gross cross-sectional area of the wall.
The maximum spacing of vertical and horizontal reinforcement shall be the smaller of onethird the length of the shear wall, one-third the height of the shear wall, or 48 inches (1219 mm). The minimum cross-sectional area of vertical reinforcement shall be one-third of the required shear reinforcement. Shear reinforcement shall be anchored around vertical reinforcing bars with a standard hook.
Lateral ties in masonry columns shall be spaced not more than 8 inches (203 mm) on center and shall be at least 3/8-inch (9.5 mm) diameter. Lateral ties shall be embedded in grout.
Type N mortar or masonry cement shall not be used as part of the lateralforce-resisting system.
Standard hooks for lateral tie anchorage shall be either a 135-degree (2.4 rad) standard hook or a 180-degree (3.2 rad) standard hook.
All structures in Seismic Design Category D2 shall comply with the requirements of Seismic Design Category D1 and to the additional requirements of this section.
Stack bond masonry that is not part of the lateral force-resisting system shall have a horizontal cross-sectional area of reinforcement of at least 0.0015 times the gross cross-sectional area of masonry. Table R606.12.4.1 shows minimum reinforcing bar sizes for masonry walls. The maximum spacing of horizontal reinforcement shall be 24 inches (610 mm). These elements shall be solidly grouted and shall be constructed of hollow open-end units or two wythes of solid units.
For SI: 1 inch = 25.4 mm.
NOMINAL WALL THICKNESS (inches) | MINIMUM BAR SIZE SPACED AT 24 INCHES |
6 | #4 |
8 | #5 |
10 | #5 |
12 | #6 |
Stack bond masonry that is part of the lateral force-resisting system shall have a horizontal cross-sectional area of reinforcement of at least 0.0025 times the gross cross-sectional area of masonry. Table R606.12.4.2 shows minimum reinforcing bar sizes for masonry walls. The maximum spacing of horizontal reinforcement shall be 16 inches (406 mm). These elements shall be solidly grouted and shall be constructed of hollow open-end units or two wythes of solid units.
For SI: 1 inch = 25.4 mm.
NOMINAL WALL THICKNESS (inches) | MINIMUM BAR SIZE SPACED AT 16 INCHES |
6 | #4 |
8 | #5 |
10 | #5 |
12 | #6 |
Bundling shall be permitted when two bars are required at the same location in a wall or in a bond beam.
Splices shall be lap splices. Noncontact lap splices shall be permitted provided reinforcing bars are not spaced farther apart than 5 inches (127 mm). Splice lengths shall be in accordance with Table R606.13.2. and shall be a minimum of 25 inches (635 mm) for No. 5 bars and 20 inches (508 mm) for No. 4 bars.
TABLE 606.13.2
LAP SPLICE LENGTHS
LAP SPLICE LENGTHS
Bar Size (No.) | Lap Length (in.) |
3 | 15 |
4 | 20 |
5 | 25 |
6 | 42 |
7 | 59 |
Reinforcing bars embedded in grouted masonry cells shall have a minimum clear distance between reinforcing bars and any face of a cell of 1/4-inch (6 mm) for fine grout or 1/2-inch (13 mm) for coarse grout.
Reinforcing bars used in masonry walls shall have a masonry cover, including grout, of not less than 2 inches (51 mm) for masonry units with face exposed to earth or weather and 11/2 inch (38 mm) for masonry units not exposed to earth or weather.
Longitudinal wires of joint reinforcement shall be fully embedded in mortar or grout with a minimum cover of 5/8 inch (15.9 mm) when exposed to earth or weather and 1/2 inch (13 mm) when not exposed to earth or weather.
Cleanout openings shall be provided for cells containing spliced reinforcement when the grout pour exceeds 5 feet (1524 mm) in height. Where cleanout openings are required, an opening shall be provided in the bottom course of the masonry cell to be filled. Cleanout openings shall have a minimum opening dimension of 3 inches (914 mm).
All vertical wall reinforcement shall be terminated by hooking into a bond beam or footing with a standard hook. Standard hooks shall be formed by bending the vertical wall reinforcement in accordance with Section R606.13.3 or shall be a prefabricated standard hook. Splices to standard hooks shall be lap splices with the minimum extension length beyond the bend for standard hooks of 10 inches (254 mm) for No. 5 bars and 8 inches (203 mm) for No. 4 bars. Hooks at bond beams shall extend to the uppermost horizontal reinforcement of the bond beam and shall be embedded a minimum of 6 inches (152 mm) into the bond beam as detailed in Figure R606.13.9A and Figure R606.13.9B. Where multiple bars are required, a single standard hook shall terminate into the bond beam or footing. In narrow footings where the width is insufficient to accommodate a standard 90-degree hook and provide the concrete cover required by Section 1901.2 of the Florida Building Code, Building, the hook shall be rotated in the horizontal direction until the required concrete cover is achieved.
Vertical wall reinforcement in multistory construction shall extend through bond beams and shall be continuous with the vertical wall reinforcement of the wall above or be offset in accordance with Section R606.13.9.1 and Figure R606.13.9B.
Exception: Where more than one bar in the same cell is required for vertical wall reinforcement, only one bar shall be required to be continuous between stories.


FIGURE R606.13.9B
CONTINUITY OF FIRST- AND SECOND-FLOOR VERTICAL WALL REINFORCEMENT
CONTINUITY OF FIRST- AND SECOND-FLOOR VERTICAL WALL REINFORCEMENT
Vertical reinforcement shall be permitted to be offset between floor levels. Reinforcement for the lower story shall be anchored into the upper floor level bond beam and reinforcement for the upper story shall be anchored into the bond beams above and below in accordance with Section R606.13.8 and Figures R606.13.9A and R606.13.9B.
Beams, girders or other concentrated loads supported by a wall or column shall have a bearing of at least 3 inches (76 mm) in length measured parallel to the beam upon solid masonry not less than 4 inches (102 mm) in thickness, or upon a metal bearing plate of adequate design and dimensions to distribute the load safely, or upon a continuous reinforced masonry member projecting not less than 4 inches (102 mm) from the face of the wall.
Except where supported on a 1-inch by 4-inch (25.4 mm by 102 mm) ribbon strip and nailed to the adjoining stud and as provided in Section R602.3, the ends of each joist shall not have less than 11/2 inches (38 mm) of bearing on wood or metal, or less than 3 inches (76 mm) on masonry.
Joint reinforcement, anchors, ties and wire fabric shall conform to the following: ASTM A 82 for wire anchors and ties; ASTM A 36 for plate, headed and bent-bar anchors; ASTM A 510 for corrugated sheet metal anchors and ties; ASTM A 951 for joint reinforcement; ASTM B 227 for copper-clad steel wire ties; or ASTM A 167 for stainless steel hardware.
Minimum corrosion protection of joint reinforcement, anchor ties and wire fabric for use in masonry wall construction shall conform to Table R606.15.1.
TABLE R606.15.1
MINIMUM CORROSION PROTECTION
MINIMUM CORROSION PROTECTION
MASONRY METAL ACCESSORY | STANDARD |
Joint reinforcement, interior walls | ASTM A 641, Class 1 |
Wire ties or anchors in exterior walls completely embedded in mortar or grout | ASTM A 641, Class 3 |
Wire ties or anchors in exterior walls not completely embedded in mortar or grout | ASTM A 153, Class B-2 |
Joint reinforcement in exterior walls or interior walls exposed to moist environment | ASTM A 153, Class B-2 |
Sheet metal ties or anchors exposed to weather | ASTM A 153, Class B-2 |
Sheet metal ties or anchors completely embedded in mortar or grout | ASTM A 653, Coating Designation G60 |
Stainless steel hardware for any exposure | ASTM A 167, Type 304 |
Mortar for use in masonry construction shall be either Type M or S with a f'm of 1500- psi in accordance with ASTM C 270 and shall meet the proportion specifications of Table R607.1 or the property specifications of ASTM C 270.
TABLE R607.1
MORTAR PROPORTIONSa, b
MORTAR PROPORTIONSa, b
PROPORTIONS BY VOLUME (cementitious materials) | ||||||||
MORTAR | TYPE | Portland cement or blended cement | Mortar cement | Masonry cement | Hydrated limec or lime putty | Aggregate ratio (measured in damp, loose conditions) | ||
M | S | M | S | |||||
Cement-lime | M | 1 | — | — | — | — | 1/4 | Not less than 21/4 and not more than 3 times the sum of separate volumes of lime, if used, and cement |
S | 1 | — | — | — | — | over 1/2 to 1/4 | ||
over 11/4 to 21/2 | ||||||||
Mortar cement | M | 1 | — | — | — | — | — | |
M | — | 1 | — | — | — | |||
S | 1/2 | — | — | — | — | |||
S | — | — | 1 | — | — | |||
Masonry cement | M | 1 | — | — | — | |||
M | — | 1 | — | |||||
S | 1/2 | — | — | |||||
S | — | — | 1 |
For SI: 1 cubic foot = 0.0283 m3, 1 pound = 0.454 kg.
- For the purpose of these specifications, the weight of 1 cubic foot of the respective materials shall be considered to be as follows:
Portland cement94 poundsMasonry cementWeight printed on bagMortar cementWeight printed on bagHydrated lime40 poundsLime putty (Quicklime)80 poundsSand, damp and loose80 pounds of dry sand
- Two air-entraining materials shall not be combined in mortar.
- Hydrated lime conforming to the requirements of ASTM C 207.
Masonry foundation walls constructed as set forth in Tables R404.1.1(1) through R404.1.1(4) and mortar shall be Type M or S.
Mortar for masonry serving as the lateral-forceresisting system in Seismic Design Categories A, B and C shall be Type M, S or N mortar.
Mortar for masonry serving as the lateral-forceresisting system in Seismic Design Categories D0, D1 and D2 shall be Type M or S portland cement-lime or mortar cement mortar.
Unless otherwise required or indicated on the project drawings, head and bed joints shall be 3/8 inch (10 mm) thick, except that the thickness of the bed joint of the starting course placed over foundations shall not be less than 1/4 inch (7 mm) and not more than 3/4 inch (19 mm).
R607.2.1.1 Mortar joint thickness tolerance. Mortar joint thickness for load-bearing masonry shall be within the following tolerances from the specified dimensions:
- Bed joint: + 1/8 inch (3 mm).
- Head joint: - 1/4 inch (7 mm), + 3/8 inch (10 mm).
- Collar joints: - 1/4 inch (7 mm), + 3/8 inch (10 mm).
The mortar shall be sufficiently plastic and units shall be placed with sufficient pressure to extrude mortar from the joint and produce a tight joint. Deep furrowing of bed joints that produces voids shall not be permitted. Any units disturbed to the extent that initial bond is broken after initial placement shall be removed and relaid in fresh mortar. Surfaces to be in contact with mortar shall be clean and free of deleterious materials.
R607.2.2.1 Solid masonry. Solid masonry units shall be laid with full head and bed joints and all interior vertical joints that are designed to receive mortar shall be filled. R607.2.2.2 Hollow masonry.
For hollow masonry units, head and bed joints shall be filled solidly with mortar for a distance in from the face of the unit not less than the thickness of the face shell.
The installation of wall ties shall be as follows:
- The ends of wall ties shall be embedded in mortar joints. Wall ties shall have a minimum of 5/8-inch (15.9 mm) mortar coverage from the exposed face.
- Wall ties shall not be bent after being embedded in grout or mortar.
- For solid masonry units, solid grouted hollow units, or hollow units in anchored masonry veneer, wall ties shall be embedded in mortar bed at least 11/2 inches (38 mm).
- For hollow masonry units in other than anchored masonry veneer, wall ties shall engage outer face shells by at least 1/2 inch (13 mm).
The facing and backing of multiple-wythe masonry walls shall be bonded in accordance with Section R608.1.1, R608.1.2 or R608.1.3. In cavity walls, neither the facing nor the backing shall be less than 3 inches (76 mm) nominal in thickness and the cavity shall not be more than 4 inches (102 mm) nominal in width. The backing shall be at least as thick as the facing.
Exception: Cavities shall be permitted to exceed the 4-inch (102 mm) nominal dimension provided tie size and tie spacing have been established by calculation.
R608.1.1.1 Solid units.
Where the facing and backing (adjacent wythes) of solid masonry construction are bonded by means of masonry headers, no less than 4 percent of the wall surface of each face shall be composed of headers extending not less than 3 inches (76 mm) into the backing. The distance between adjacent full-length headers shall not exceed 24 inches (610 mm) either vertically or horizontally. In walls in which a single header does not extend through the wall, headers from the opposite sides shall overlap at least 3 inches (76 mm), or headers from opposite sides shall be covered with another header course overlapping the header below at least 3 inches (76 mm). R608.1.1.2 Hollow units.
Where two or more hollow units are used to make up the thickness of a wall, the stretcher courses shall be bonded at vertical intervals not exceeding 34 inches (864 mm) by lapping at least 3 inches (76 mm) over the unit below, or by lapping at vertical intervals not exceeding 17 inches (432 mm) with units that are at least 50 percent thicker than the units below.
Where the facing and backing (adjacent wythes) of solid masonry construction are bonded by means of masonry headers, no less than 4 percent of the wall surface of each face shall be composed of headers extending not less than 3 inches (76 mm) into the backing. The distance between adjacent full-length headers shall not exceed 24 inches (610 mm) either vertically or horizontally. In walls in which a single header does not extend through the wall, headers from the opposite sides shall overlap at least 3 inches (76 mm), or headers from opposite sides shall be covered with another header course overlapping the header below at least 3 inches (76 mm). R608.1.1.2 Hollow units.
Where two or more hollow units are used to make up the thickness of a wall, the stretcher courses shall be bonded at vertical intervals not exceeding 34 inches (864 mm) by lapping at least 3 inches (76 mm) over the unit below, or by lapping at vertical intervals not exceeding 17 inches (432 mm) with units that are at least 50 percent thicker than the units below.
Bonding with wall ties or joint reinforcement shall comply with Sections R608.1.2.1 through R608.1.2.3.
R608.1.2.1 Bonding with wall ties. Bonding with wall ties, except as required by Section R610, where the facing and backing (adjacent wythes) of masonry walls are bonded with 3/16-inch-diameter (5 mm) wall ties embedded in the horizontal mortar joints, there shall be at least one metal tie for each 4.5 square feet (0.418 m2) of wall area. Ties in alternate courses shall be staggered. The maximum vertical distance between ties shall not exceed 24 inches (610 mm), and the maximum horizontal distance shall not exceed 36 inches (914 mm). Rods or ties bent to rectangular shape shall be used with hollow masonry units laid with the cells vertical. In other walls, the ends of ties shall be bent to 90-degree (0.79 rad) angles to provide hooks no less than 2 inches (51 mm) long. Additional bonding ties shall be provided at all openings, spaced not more than 3 feet (914 mm) apart around the perimeter and within 12 inches (305 mm) of the opening. R608.1.2.2 Bonding with adjustable wall ties.
Where the facing and backing (adjacent wythes) of masonry are bonded with adjustable wall ties, there shall be at least one tie for each 2.67 square feet (0.248 m2) of wall area. Neither the vertical nor the horizontal spacing of the adjustable wall ties shall exceed 24 inches (610 mm). The maximum vertical offset of bed joints from one wythe to the other shall be 1.25 inches (32 mm). The maximum clearance between connecting parts of the ties shall be 1/16 inch (2 mm). When pintle legs are used, ties shall have at least two 3/16-inch-diameter (5 mm) legs. R608.1.2.3 Bonding with prefabricated joint reinforcement.
Where the facing and backing (adjacent wythes) of masonry are bonded with prefabricated joint reinforcement, there shall be at least one cross wire serving as a tie for each 2.67 square feet (0.248 m2) of wall area. The vertical spacing of the joint reinforcement shall not exceed 16 inches (406 mm). Cross wires on prefabricated joint reinforcement shall not be smaller than No. 9 gage. The longitudinal wires shall be embedded in the mortar.
Bonding with natural and cast stone shall conform to Sections R608.1.3.1 and R608.1.3.2.
R608.1.3.1 Ashlar masonry. In ashlar masonry, bonder units, uniformly distributed, shall be provided to the extent of not less than 10 percent of the wall area. Such bonder units shall extend not less than 4 inches (102 mm) into the backing wall. R608.1.3.2 Rubble stone masonry.
Rubble stone masonry 24 inches (610 mm) or less in thickness shall have bonder units with a maximum spacing of 3 feet (914 mm) vertically and 3 feet (914 mm) horizontally, and if the masonry is of greater thickness than 24 inches (610 mm), shall have one bonder unit for each 6 square feet (0.557 m2) of wall surface on both sides.
In each wythe of masonry laid in running bond, head joints in successive courses shall be offset by not less than one-fourth the unit length, or the masonry walls shall be reinforced longitudinally as required in Section R608.2.2.
Where unit masonry is laid with less head joint offset than in Section R608.2.1, the minimum area of horizontal reinforcement placed in mortar bed joints or in bond beams spaced not more than 48 inches (1219 mm) apart, shall be 0.0007 times the vertical cross-sectional area of the wall.
Grouted multiple-wythe masonry is a form of construction in which the space between the wythes is solidly filled with grout. It is not necessary for the cores of masonry units to be filled with grout. Grouted hollow unit masonry is a form of construction in which certain cells of hollow units are continuously filled with grout.
Grout shall consist of cementitious material and aggregate in accordance with ASTM C 476 and the proportion specifications of Table R609.1.1. Type M or Type S mortar to which sufficient water has been added to produce pouring consistency can be used as grout.
TABLE R609.1.1
GROUT PROPORTIONS BY VOLUME FOR MASONRY CONSTRUCTION
GROUT PROPORTIONS BY VOLUME FOR MASONRY CONSTRUCTION
TYPE | PORTLAND CEMENT OR BLENDED CEMENT SLAG CEMENT | HYDRATED LIME OR LIME PUTTY | AGGREGATE MEASURED IN A DAMP, LOOSE CONDITION | |
Fine | Coarse | |||
Fine | 1 | 0 to 1/10 | 21/4 to 3 times the sum of the volume of the cementitious materials | — |
Coarse | 1 | 0 to 1/10 | 21/4 to 3 times the sum of the volume of the cementitious materials | 1 to 2 times the sum of the vol- umes of the cementitious materials |
Where the following conditions are met, place grout in lifts not exceeding 12 feet 8 inches (3.86 m).
- The masonry has cured for at least 4 hours.
- The grout slump is maintained between 10 and 11 inches. (254 and 279 mm).
- No intermediate reinforced bond beams are placed between the top and the bottom of the pour height.
Otherwise, place grout in lifts not exceeding 5 feet (1.52 m). If grouting is stopped for one hour or longer, the horizontal construction joints shall be formed by stopping all tiers at the same elevation and with the grout 1 inch (25.4 mm) below the top.
Table R609.1.2 Grout Space Dimensions And Pour Heights.
Reserved.
Reserved.
Provision shall be made for cleaning grout space. Mortar projections that project more than 1/2 inch (13 mm) into grout space and any other foreign matter shall be removed from grout space prior to inspection and grouting.
All cells containing reinforcement or anchor bolts shall be grouted solid. Grout shall be a plastic mix suitable for pumping without segregation of the constituents and shall be mixed thoroughly. Grout shall have a maximum coarse aggregate size of 3/8 inch (9.5 mm), shall be placed at an 8 to 11-inch (205 mm to 279 mm) slump, and shall have a minimum specified compressive strength of 2000 psi at 28 days in accordance with ASTM C 476, or when tested in an approved manner. Grout shall be placed by pumping or by an approved alternate method and shall be placed before any initial set occurs and in no case more than 11/2 hours after water has been added. Grouting shall be done in a continuous pour in lifts, in accordance with Section 609.1.2. Grout shall be consolidated at the time of placement in accordance with the following:
- Consolidate grout pours 12 inches (305 mm) or less in height by mechanical vibration or by puddling.
- Consolidate pours exceeding 12 inches (305 mm) in height by mechanical vibration, and reconsolidate by mechanical vibration after initial water loss and settlement has occurred.
Grout shall not be pumped through aluminum pipes.
Cleanouts shall be provided at the bottom course at each pour of grout where such pour exceeds 5 feet (1524 mm) in height and where required by the building official. Cleanouts shall be provided with an opening of sufficient size to permit removal of debris. The minimum opening dimension shall be 3 inches (76 mm). The cleanouts shall be sealed before grouting and after inspection.
R609.1.5.1 Grouted multiple-wythe masonry. Cleanouts shall be provided at the bottom course of the exterior wythe at each pour of grout where such pour exceeds 5 feet (1524 mm) in height. R609.1.5.2 Grouted hollow unit masonry.
Reserved.
A reinforced bond beam shall be provided in masonry walls at the top of the wall and at each floor level of each exterior wall. Masonry walls not extending to the roof line shall have a bond beam at the top of the wall.
Exceptions:
- A bond beam is not required at the floor level for slab-on-ground floors.
- Gable endwalls shall be in conformance with Section R609.4.
Bond beams shall be one of the following:
- 8 inches thick × 8 inches high masonry.
8 inches thick × 12 inches high masonry.8 inches thick × 16 inches high masonry.8 inches thick × 24 inches high masonry.8 inchesthick × 32 inches high masonry.
- Precast units certified by the manufacturer for the uplift loads as set forth in the standard used for design of the building as specified in Section R301.2.1.1. Precast units shall be installed in accordance with the manufacturer's specifications, and approved by the building official.
The minimum reinforcement for bond beam roof diaphragm chord tension reinforcement steel shall be as set forth in Tables R609.2.2A-1 through R609.2.2A-4 for the appropriate grade of steel and exposure category. The minimum reinforcement for bond beam uplift resisting reinforcement steel shall be as set forth in Tables R609.2.2B-1 through R609.2.2B-8 for the loads set forth in the standard used for design of the building as specified in Section R301.2.1.1. The total minimum area of bond beam reinforcement shall be the sum of the required area of the diaphragm chord tension steel and the required area of bond beam uplift steel. Bond beam area shall be converted to bar size in accordance with Table R609.2.2C.
Vasd AS DETERMINED IN ACCORDANCE WITH SECTION R301.2.1.3 | BUILDING WIDTH | WALL HEIGHT | BUILDING LENGTH | ||||
40 | 50 | 60 | 70 | 80 | |||
100 | 24 | 10 | 0.037 | 0.052 | 0.069 | 0.088 | 0.110 |
24 | 8 | 0.030 | 0.042 | 0.055 | 0.071 | 0.088 | |
32 | 10 | 0.029 | 0.040 | 0.053 | 0.067 | 0.084 | |
32 | 8 | 0.023 | 0.032 | 0.042 | 0.054 | 0.067 | |
40 | 10 | 0.026 | 0.036 | 0.047 | 0.059 | 0.073 | |
40 | 8 | 0.021 | 0.029 | 0.037 | 0.047 | 0.058 | |
110 | 24 | 10 | 0,045 | 0.063 | 0.084 | 0.107 | 0.133 |
24 | 8 | 0.036 | 0.050 | 0.067 | 0.086 | 0.107 | |
32 | 10 | 0.035 | 0.048 | 0.064 | 0.082 | 0.101 | |
32 | 8 | 0.028 | 0.039 | 0.051 | 0.065 | 0.081 | |
40 | 10 | 0.032 | 0.043 | 0.057 | 0.072 | 0.088 | |
40 | 8 | 0.025 | 0.035 | 0.045 | 0.057 | 0.070 | |
120 | 24 | 10 | 0.054 | 0.075 | 0.099 | 0.127 | 0.158 |
24 | 8 | 0.043 | 0.060 | 0.080 | 0.102 | 0.127 | |
32 | 10 | 0.041 | 0.058 | 0.076 | 0.097 | 0.121 | |
32 | 8 | 0.033 | 0.046 | 0.061 | 0.078 | 0.097 | |
40 | 10 | 0.038 | 0.052 | 0.067 | 0.085 | 0.105 | |
40 | 8 | 0.030 | 0.041 | 0.054 | 0.068 | 0.084 | |
130 | 24 | 10 | 0.063 | 0.088 | 0.117 | 0.149 | 0.186 |
24 | 8 | 0.050 | 0.070 | 0.093 | 0.120 | 0.149 | |
32 | 10 | 0.049 | 0.068 | 0.089 | 0.114 | 0.142 | |
32 | 8 | 0.039 | 0.054 | 0.071 | 0.091 | 0.113 | |
40 | 10 | 0.044 | 0.061 | 0.079 | 0.100 | 0.123 | |
40 | 8 | 0.035 | 0.048 | 0.063 | 0.080 | 0.098 | |
140 | 24 | 10 | 0.073 | 0.102 | 0.135 | 0.173 | 0.216 |
24 | 8 | 0.058 | 0.082 | 0.108 | 0.139 | 0.173 | |
32 | 10 | 0.056 | 0.078 | 0.104 | 0.132 | 0.164 | |
32 | 8 | 0.045 | 0.063 | 0.083 | 0.106 | 0.131 | |
40 | 10 | 0.051 | 0.070 | 0.092 | 0.116 | 0.143 | |
40 | 8 | 0.041 | 0.056 | 0.073 | 0.093 | 0.114 | |
150 | 24 | 10 | 0.084 | 0.117 | 0.155 | 0.199 | 0.248 |
24 | 8 | 0.067 | 0.094 | 0.124 | 0.159 | 0.198 | |
32 | 10 | 0.065 | 0.090 | 0.119 | 0.152 | 0.189 | |
32 | 8 | 0.052 | 0.072 | 0.095 | 0.121 | 0.151 | |
40 | 10 | 0.059 | 0.081 | 0.105 | 0.133 | 0.164 | |
40 | 8 | 0.047 | 0.064 | 0.084 | 0.106 | 0.131 |
- Diaphragm chord tension steel area shall be added to bond beam uplift steel area for total required bond beam area of steel. Select appropriate bar size and number of bars from Table R609.2.2C.
- The tabular value for diaphragm chord tension steel area shall be permitted to be multiplied by a factor of 0.65 for bond beam spans located in the end zone.
Vasd AS DETERMINED IN ACCORDANCE WITH SECTION R301.2.1.3 | BUILDING WIDTH | WALL HEIGHT | BUILDING LENGTH | ||||
40 | 50 | 60 | 70 | 80 | |||
100 | 24 | 10 | 0.052 | 0.073 | 0.097 | 0.124 | 0.154 |
24 | 8 | 0.042 | 0.058 | 0.077 | 0.099 | 0.123 | |
32 | 10 | 0.040 | 0.056 | 0.074 | 0.095 | 0.118 | |
32 | 8 | 0.032 | 0.045 | 0.059 | 0.076 | 0.094 | |
40 | 10 | 0.037 | 0.050 | 0.066 | 0.083 | 0.102 | |
40 | 8 | 0.029 | 0.040 | 0.052 | 0.066 | 0.082 | |
110 | 24 | 10 | 0.063 | 0.088 | 0.117 | 0.150 | 0.187 |
24 | 8 | 0.051 | 0.071 | 0.094 | 0.120 | 0.149 | |
32 | 10 | 0.049 | 0.068 | 0.090 | 0.114 | 0.142 | |
32 | 8 | 0.039 | 0.054 | 0.072 | 0.092 | 0.114 | |
40 | 10 | 0.044 | 0.061 | 0.079 | 0.100 | 0.124 | |
40 | 8 | 0.035 | 0.049 | 0.063 | 0.080 | 0.099 | |
120 | 24 | 10 | 0.075 | 0.105 | 0.139 | 0.178 | 0.222 |
24 | 8 | 0.060 | 0.084 | 0.112 | 0.143 | 0.178 | |
32 | 10 | 0.058 | 0.081 | 0.107 | 0.136 | 0.169 | |
32 | 8 | 0.046 | 0.065 | 0.085 | 0.109 | 0.135 | |
40 | 10 | 0.053 | 0.072 | 0.094 | 0.119 | 0.147 | |
40 | 8 | 0.042 | 0.058 | 0.076 | 0.095 | 0.118 | |
130 | 24 | 10 | 0.088 | 0.123 | 0.164 | 0.209 | 0.261 |
24 | 8 | 0.071 | 0.099 | 0.131 | 0.168 | 0.209 | |
32 | 10 | 0.068 | 0.095 | 0.125 | 0.160 | 0.199 | |
32 | 8 | 0.055 | 0.076 | 0.100 | 0.128 | 0.159 | |
40 | 10 | 0.062 | 0.085 | 0.111 | 0.140 | 0.173 | |
40 | 8 | 0.050 | 0.068 | 0.089 | 0.112 | 0.138 | |
140 | 24 | 10 | 0.102 | 0.143 | 0.190 | 0.243 | 0.302 |
24 | 8 | 0.082 | 0.114 | 0.152 | 0.194 | 0.242 | |
32 | 10 | 0.079 | 0.110 | 0.145 | 0.185 | 0.230 | |
32 | 8 | 0.063 | 0.088 | 0.116 | 0.148 | 0.184 | |
40 | 10 | 0.072 | 0.098 | 0.129 | 0.162 | 0.200 | |
40 | 8 | 0.057 | 0.079 | 0.103 | 0.130 | 0.160 | |
150 | 24 | 10 | 0.118 | 0.164 | 0.218 | 0.279 | 0.347 |
24 | 8 | 0.094 | 0.131 | 0.174 | 0.223 | 0.278 | |
32 | 10 | 0.091 | 0.126 | 0.167 | 0.213 | 0.264 | |
32 | 8 | 0.073 | 0.101 | 0.133 | 0.170 | 0.212 | |
40 | 10 | 0.082 | 0.113 | 0.148 | 0.187 | 0.230 | |
40 | 8 | 0.066 | 0.090 | 0.118 | 0.149 | 0.184 |
- Diaphragm chord tension steel area shall be added to bond beam uplift steel area for total required bond beam area of steel. Select appropriate bar size and number of bars from Table R609.2.2C.
- The tabular value for diaphragm chord tension steel area shall be permitted to be multiplied by a factor of 0.65 for bond beam spans located in the end zone.
Vasd AS DETERMINED IN ACCORDANCE WITH SECTION R301.2.1.3 | BUILDING WIDTH | WALL HEIGHT | BUILDING LENGTH | ||||
40 | 50 | 60 | 70 | 80 | |||
100 | 24 | 10 | 0.056 | 0.078 | 0.104 | 0.133 | 0.165 |
24 | 8 | 0.045 | 0.062 | 0.083 | 0.106 | 0.132 | |
32 | 10 | 0.043 | 0.060 | 0.079 | 0.101 | 0.126 | |
32 | 8 | 0.035 | 0.048 | 0.063 | 0.081 | 0.101 | |
40 | 10 | 0.039 | 0.054 | 0.070 | 0.089 | 0.109 | |
40 | 8 | 0.031 | 0.043 | 0.056 | 0.071 | 0.087 | |
110 | 24 | 10 | 0.068 | 0.094 | 0.125 | 0.160 | 0.200 |
24 | 8 | 0.054 | 0.076 | 0.100 | 0.128 | 0.160 | |
32 | 10 | 0.052 | 0.073 | 0.096 | 0.122 | 0.152 | |
32 | 8 | 0.042 | 0.058 | 0.077 | 0.098 | 0.122 | |
40 | 10 | 0.047 | 0.065 | 0.085 | 0.107 | 0.132 | |
40 | 8 | 0.038 | 0.052 | 0.068 | 0.086 | 0.106 | |
120 | 24 | 10 | 0.081 | 0.112 | 0.149 | 0.191 | 0.238 |
24 | 8 | 0.064 | 0.090 | 0.119 | 0.153 | 0.190 | |
32 | 10 | 0.062 | 0.086 | 0.114 | 0.146 | 0.181 | |
32 | 8 | 0.050 | 0.069 | 0.091 | 0.117 | 0.145 | |
40 | 10 | 0.056 | 0.077 | 0.101 | 0.128 | 0.157 | |
40 | 8 | 0.045 | 0.062 | 0.081 | 0.102 | 0.126 | |
130 | 24 | 10 | 0.095 | 0.132 | 0.175 | 0.224 | 0.279 |
24 | 8 | 0.076 | 0.106 | 0.140 | 0.179 | 0.223 | |
32 | 10 | 0.073 | 0.101 | 0.134 | 0.171 | 0.212 | |
32 | 8 | 0.058 | 0.081 | 0.107 | 0.137 | 0.170 | |
40 | 10 | 0.066 | 0.091 | 0.119 | 0.150 | 0.185 | |
40 | 8 | 0.053 | 0.073 | 0.095 | 0.120 | 0.148 | |
140 | 24 | 10 | 0.110 | 0.153 | 0.203 | 0.260 | 0.324 |
24 | 8 | 0.088 | 0.122 | 0.162 | 0.208 | 0.259 | |
32 | 10 | 0.085 | 0.117 | 0.155 | 0.198 | 0.246 | |
32 | 8 | 0.068 | 0.094 | 0.124 | 0.159 | 0.197 | |
40 | 10 | 0.077 | 0.105 | 0.138 | 0.174 | 0.214 | |
40 | 8 | 0.062 | 0.084 | 0.110 | 0.139 | 0.171 | |
150 | 24 | 10 | 0.126 | 0.176 | 0.233 | 0.298 | 0.371 |
24 | 8 | 0.101 | 0.140 | 0.186 | 0.239 | 0.297 | |
32 | 10 | 0.097 | 0.135 | 0.178 | 0.228 | 0.283 | |
32 | 8 | 0.078 | 0.108 | 0.143 | 0.182 | 0.226 | |
40 | 10 | 0.088 | 0.121 | 0.158 | 0.200 | 0.246 | |
40 | 8 | 0.071 | 0.097 | 0.126 | 0.160 | 0.197 |
- Diaphragm chord tension steel area shall be added to bond beam uplift steel area for total required bond beam area of steel. Select appropriate bar size and number of bars from Table R609.2.2C.
- The tabular value for diaphragm chord tension steel area shall be permitted to be multiplied by a factor of 0.65 for bond beam spans located in the end zone.
Vasd AS DETERMINED IN ACCORDANCE WITH SECTION R301.2.1.3 | BUILDING WIDTH | WALL HEIGHT | BUILDING LENGTH | ||||
40 | 50 | 60 | 70 | 80 | |||
100 | 24 | 10 | 0.078 | 0.109 | 0.145 | 0.186 | 0.231 |
24 | 8 | 0.063 | 0.088 | 0.116 | 0.149 | 0.185 | |
32 | 10 | 0.060 | 0.084 | 0.111 | 0.142 | 0.176 | |
32 | 8 | 0.048 | 0.067 | 0.089 | 0.114 | 0.141 | |
40 | 10 | 0.055 | 0.075 | 0.098 | 0.124 | 0.153 | |
40 | 8 | 0.044 | 0.060 | 0.079 | 0.099 | 0.123 | |
110 | 24 | 10 | 0.095 | 0.132 | 0.176 | 0.225 | 0.280 |
24 | 8 | 0.076 | 0.106 | 0.141 | 0.180 | 0.224 | |
32 | 10 | 0.073 | 0.102 | 0.135 | 0.172 | 0.213 | |
32 | 8 | 0.059 | 0.081 | 0.108 | 0.137 | 0.171 | |
40 | 10 | 0.067 | 0.091 | 0.119 | 0.150 | 0.185 | |
40 | 8 | 0.053 | 0.073 | 0.095 | 0.120 | 0.148 | |
120 | 24 | 10 | 0.113 | 0.158 | 0.209 | 0.268 | 0.333 |
24 | 8 | 0.090 | 0.126 | 0.167 | 0.214 | 0.267 | |
32 | 10 | 0.087 | 0.121 | 0.160 | 0.204 | 0.254 | |
32 | 8 | 0.070 | 0.097 | 0.128 | 0.163 | 0.203 | |
40 | 10 | 0.079 | 0.108 | 0.142 | 0.179 | 0.221 | |
40 | 8 | 0.063 | 0.087 | 0.113 | 0.143 | 0.176 | |
130 | 24 | 10 | 0.133 | 0.185 | 0.245 | 0.314 | 0.391 |
24 | 8 | 0.1066 | 0.148 | 0.196 | 0.251 | 0.313 | |
32 | 10 | 0.102 | 0.142 | 0.188 | 0.240 | 0.298 | |
32 | 8 | 0.082 | 0.114 | 0.150 | 0.192 | 0.238 | |
40 | 10 | 0.093 | 0.127 | 0.166 | 0.210 | 0.259 | |
40 | 8 | 0.074 | 0.102 | 0.133 | 0.168 | 0.207 | |
140 | 24 | 10 | 0.154 | 0.214 | 0.285 | 0.364 | 0.454 |
24 | 8 | 0.123 | 0.172 | 0.288 | 0.291 | 0.363 | |
32 | 10 | 0.119 | 0.165 | 0.218 | 0.278 | 0.345 | |
32 | 8 | 0.095 | 0.132 | 0.174 | 0.223 | 0.276 | |
40 | 10 | 0.108 | 0.148 | 0.193 | 0.244 | 0.300 | |
40 | 8 | 0.086 | 0.118 | 0.154 | 0.195 | 0.240 | |
150 | 24 | 10 | 0.176 | 0.246 | 0.327 | 0.418 | 0.521 |
24 | 8 | 0.141 | 0.197 | 0.261 | 0.335 | 0.417 | |
32 | 10 | 0.136 | 0.189 | 0.250 | 0.319 | 0.397 | |
32 | 8 | 0.109 | 0.151 | 0.200 | 0.255 | 0.317 | |
40 | 10 | 0.124 | 0.169 | 0.221 | 0.280 | 0.345 | |
40 | 8 | 0.099 | 0.136 | 0.177 | 0.224 | 0.276 |
- Diaphragm chord tension steel area shall be added to bond beam uplift steel area for total required bond beam area of steel. Select appropriate bar size and number of bars from Table R609.2.2C.
- The tabular value for diaphragm chord tension steel area shall be permitted to be multiplied by a factor of 0.65 for bond beam spans located in the end zone.
UPLIFT, plf (ALLOWABLE STRESS DESIGN) | 8 IN. BOND BEAM/LINTEL SPAN, FT. | |||||||
4 | 6 | 8 | 10 | 12 | 14 | 16 | 18 | |
50 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
100 | 0.009 | 0.021 | 0.038 | 0.060 | 0.088 | 0.123 | NP | NP |
150 | 0.016 | 0.037 | 0.067 | 0.107 | 0.159 | NP | NP | NP |
200 | 0.023 | 0.053 | 0.096 | 0.157 | NP | NP | NP | NP |
250 | 0.030 | 0.069 | 0.127 | 0.211 | NP | NP | NP | NP |
300 | 0.037 | 0.086 | 0.160 | 0.270 | NP | NP | NP | NP |
350 | 0.044 | 0.103 | 0.194 | NP | NP | NP | NP | NP |
400 | 0.051 | 0.120 | 0.230 | NP | NP | NP | NP | NP |
450 | 0.058 | 0.138 | 0.269 | NP | NP | NP | NP | NP |
500 | 0.065 | 0.156 | NP | NP | NP | NP | NP | NP |
550 | 0.073 | 0.175 | NP | NP | NP | NP | NP | NP |
600 | 0.080 | 0.195 | NP | NP | NP | NP | NP | NP |
650 | 0.088 | 0.215 | NP | NP | NP | NP | NP | NP |
700 | 0.095 | 0.235 | NP | NP | NP | NP | NP | NP |
750 | 0.103 | 0.257 | NP | NP | NP | NP | NP | NP |
800 | 0.110 | 0.280 | NP | NP | NP | NP | NP | NP |
850 | 0.118 | NP | NP | NP | NP | NP | NP | NP |
900 | 0.126 | NP | NP | NP | NP | NP | NP | NP |
950 | 0.134 | NP | NP | NP | NP | NP | NP | NP |
1000 | 0.142 | NP | NP | NP | NP | NP | NP | NP |
1050 | 0.150 | NP | NP | NP | NP | NP | NP | NP |
1100 | 0.158 | NP | NP | NP | NP | NP | NP | NP |
- When reinforcement required is 0.00, only diaphragm chord tension reinforcement is required.
- Diaphragm chord tension steel area shall be added to bond beam uplift steel area for total required bond beam area of steel. Select appropriate bar size and number of bars from Table R609.2.2C.
UPLIFT, plf (ALLOWABLE STRESS DESIGN) | 16 IN. BOND BEAM/LINTEL SPAN, FT. | |||||||
4 | 6 | 8 | 10 | 12 | 14 | 16 | 18 | |
50 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
100 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
150 | 0.005 | 0.010 | 0.019 | 0.029 | 0.042 | 0.058 | 0.076 | 0.097 |
200 | 0.007 | 0.017 | 0.030 | 0.046 | 0.067 | 0.092 | 0.121 | 0.154 |
250 | 0.010 | 0.023 | 0.040 | 0.063 | 0.092 | 0.126 | 0.167 | 0.214 |
300 | 0.013 | 0.029 | 0.051 | 0.081 | 0.117 | 0.162 | 0.214 | 0.275 |
350 | 0.015 | 0.035 | 0.062 | 0.098 | 0.143 | 0.197 | 0.262 | NP |
400 | 0.018 | 0.041 | 0.073 | 0.116 | 0.169 | 0.234 | 0.312 | NP |
450 | 0.021 | 0.047 | 0.084 | 0.134 | 0.195 | 0.271 | NP | NP |
500 | 0.023 | 0.053 | 0.096 | 0.152 | 0.222 | 0.309 | NP | NP |
550 | 0.026 | 0.059 | 0.107 | 0.170 | 0.249 | 0.348 | NP | NP |
600 | 0.029 | 0.066 | 0.118 | 0.188 | 0.277 | 0.388 | NP | NP |
650 | 0.032 | 0.072 | 0.130 | 0.206 | 0.305 | 0.429 | NP | NP |
700 | 0.034 | 0.078 | 0.141 | 0.225 | 0.334 | NP | NP | NP |
750 | 0.037 | 0.084 | 0.152 | 0.244 | 0.363 | NP | NP | NP |
800 | 0.040 | 0.091 | 0.164 | 0.263 | 0.392 | NP | NP | NP |
850 | 0.042 | 0.097 | 0.176 | 0.282 | 0.422 | NP | NP | NP |
900 | 0.045 | 0.103 | 0.187 | 0.302 | 0.453 | NP | NP | NP |
950 | 0.048 | 0.110 | 0.199 | 0.321 | NP | NP | NP | NP |
1000 | 0.051 | 0.116 | 0.211 | 0.341 | NP | NP | NP | NP |
1050 | 0.053 | 0.122 | 0.223 | 0.362 | NP | NP | NP | NP |
1100 | 0.056 | 0.129 | 0.235 | 0.382 | NP | NP | NP | NP |
- When reinforcement required is 0.00, only diaphragm chord tension reinforcement is required.
- Diaphragm chord tension steel area shall be added to bond beam uplift steel area for total required bond beam area of steel. Select appropriate bar size and number of bars from Table R609.2.2C.
UPLIFT, plf (ALLOWABLE STRESS DESIGN) | 24 IN. BOND BEAM/LINTEL SPAN, FT. | |||||||
4 | 6 | 8 | 10 | 12 | 14 | 16 | 18 | |
50 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
100 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
150 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
200 | 0.004 | 0.008 | 0.014 | 0.022 | 0.032 | 0.043 | 0.057 | 0.072 |
250 | 0.005 | 0.012 | 0.021 | 0.032 | 0.047 | 0.064 | 0.084 | 0.106 |
300 | 0.007 | 0.015 | 0.027 | 0.043 | 0.062 | 0.085 | 0.1111 | 0.142 |
350 | 0.009 | 0.019 | 0.034 | 0.054 | 0.077 | 0.106 | 0.139 | 0.177 |
400 | 0.010 | 0.023 | 0.041 | 0.064 | 0.093 | 0.127 | 0.167 | 0.213 |
450 | 0.012 | 0.027 | 0.048 | 0.075 | 0.108 | 0.148 | 0.195 | 0.249 |
500 | 0.014 | 0.031 | 0.054 | 0.086 | 0.124 | 0.170 | 0.224 | 0.286 |
550 | 0.015 | 0.034 | 0.061 | 0.096 | 0.140 | 0.192 | 0.253 | 0.323 |
600 | 0.017 | 0.038 | 0.068 | 0.107 | 0.155 | 0.213 | 0.282 | 0.361 |
650 | 0.019 | 0.042 | 0.075 | 0.118 | 0.171 | 0.235 | 0.311 | 0.399 |
700 | 0.020 | 0.046 | 0.082 | 0.129 | 0.187 | 0.257 | 0.341 | 0.438 |
750 | 0.022 | 0.050 | 0.089 | 0.140 | 0.203 | 0.280 | 0.371 | 0.477 |
800 | 0.024 | 0.053 | 0.095 | 0.150 | 0.219 | 0.302 | 0.401 | 0.517 |
850 | 0.025 | 0.057 | 0.102 | 0.161 | 0.235 | 0.325 | 0.423 | 0.558 |
900 | 0.027 | 0.061 | 0.109 | 0.172 | 0.251 | 0.347 | 0.462 | NP |
950 | 0.029 | 0.065 | 0.116 | 0.183 | 0.268 | 0.370 | 0.494 | NP |
1000 | 0.030 | 0.069 | 0.123 | 0.194 | 0.284 | 0.394 | 0.525 | NP |
1050 | 0.032 | 0.072 | 0.130 | 0.206 | 0.301 | 0.417 | 0.557 | NP |
1100 | 0.034 | 0.076 | 0.137 | 0.217 | 0.317 | 0.440 | NP | NP |
- When reinforcement required is 0.00, only diaphragm chord tension reinforcement is required.
- Diaphragm chord tension steel area shall be added to bond beam uplift steel area for total required bond beam area of steel. Select appropriate bar size and number of bars from Table R609.2.2C.
UPLIFT, plf (ALLOWABLE STRESS DESIGN) | 32 IN. BOND BEAM/LINTEL SPAN, FT. | |||||||
4 | 6 | 8 | 10 | 12 | 14 | 16 | 18 | |
50 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
100 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
150 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
200 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
250 | 0.003 | 0.007 | 0.012 | 0.019 | 0.027 | 0.037 | 0.048 | 0.061 |
300 | 0.004 | 0.009 | 0.017 | 0.026 | 0.038 | 0.052 | 0.068 | 0.086 |
350 | 0.005 | 0.012 | 0.022 | 0.034 | 0.049 | 0.067 | 0.087 | 0.111 |
400 | 0.007 | 0.015 | 0.027 | 0.042 | 0.060 | 0.082 | 0.107 | 0.136 |
450 | 0.008 | 0.018 | 0.031 | 0.049 | 0.071 | 0.097 | 0.127 | 0.161 |
500 | 0.009 | 0.020 | 0.036 | 0.057 | 0.082 | 0.112 | 0.147 | 0.187 |
550 | 0.010 | 0.023 | 0.041 | 0.065 | 0.093 | 0.127 | 0.167 | 0.213 |
600 | 0.011 | 0.026 | 0.046 | 0.072 | 0.104 | 0.143 | 0.187 | 0.239 |
650 | 0.013 | 0.029 | 0.051 | 0.080 | 0.116 | 0.158 | 0.208 | 0.265 |
700 | 0.014 | 0.031 | 0.056 | 0.088 | 0.127 | 0.174 | 0.288 | 0.291 |
750 | 0.015 | 0.034 | 0.061 | 0.095 | 0.138 | 0.189 | 0.249 | 0.317 |
800 | 0.016 | 0.037 | 0.066 | 0.103 | 0.149 | 0.205 | 0.269 | 0.344 |
850 | 0.018 | 0.040 | 0.071 | 0.111 | 0.161 | 0.220 | 0.290 | 0.370 |
900 | 0.019 | 0.042 | 0.076 | 0.119 | 0.172 | 0.236 | 0.311 | 0.397 |
950 | 0.020 | 0.045 | 0.081 | 0.127 | 0.183 | 0.252 | 0.332 | 0.424 |
1000 | 0.021 | 0.048 | 0.085 | 0.134 | 0.195 | 0.267 | 0.353 | 0.451 |
1050 | 0.022 | 0.051 | 0.090 | 0.142 | 0.206 | 0.283 | 0.374 | 0.479 |
1100 | 0.024 | 0.053 | 0.095 | 0.150 | 0.218 | 0.299 | 0.395 | 0.506 |
- When reinforcement required is 0.00, only diaphragm chord tension reinforcement is required.
- Diaphragm chord tension steel area shall be added to bond beam uplift steel area for total required bond beam area of steel. Select appropriate bar size and number of bars from Table R609.2.2C.
UPLIFT, plf (ALLOWABLE STRESS DESIGN) | 8 IN. BOND BEAM/LINTEL SPAN, FT. | |||||||
4 | 6 | 8 | 10 | 12 | 14 | 16 | 18 | |
50 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
100 | 0.014 | 0.032 | 0.057 | 0.090 | 0.132 | 0.184 | NP | NP |
150 | 0.024 | 0.055 | 0.100 | 0.160 | 0.239 | NP | NP | NP |
200 | 0.034 | 0.079 | 0.144 | 0.235 | NP | NP | NP | NP |
250 | 0.045 | 0.103 | 0.191 | NP | NP | NP | NP | NP |
300 | 0.055 | 0.128 | 0.240 | NP | NP | NP | NP | NP |
350 | 0.066 | 0.154 | NP | NP | NP | NP | NP | NP |
400 | 0.076 | 0.180 | NP | NP | NP | NP | NP | NP |
450 | 0.087 | 0.207 | NP | NP | NP | NP | NP | NP |
500 | 0.098 | 0.234 | NP | NP | NP | NP | NP | NP |
550 | 0.109 | 0.263 | NP | NP | NP | NP | NP | NP |
600 | 0.120 | NP | NP | NP | NP | NP | NP | NP |
650 | 0.131 | NP | NP | NP | NP | NP | NP | NP |
700 | 0.143 | NP | NP | NP | NP | NP | NP | NP |
750 | 0.154 | NP | NP | NP | NP | NP | NP | NP |
800 | 0.166 | NP | NP | NP | NP | NP | NP | NP |
850 | 0.177 | NP | NP | NP | NP | NP | NP | NP |
900 | 0.189 | NP | NP | NP | NP | NP | NP | NP |
950 | 0.201 | NP | NP | NP | NP | NP | NP | NP |
1000 | 0.213 | NP | NP | NP | NP | NP | NP | NP |
1050 | 0.225 | NP | NP | NP | NP | NP | NP | NP |
1100 | 0.238 | NP | NP | NP | NP | NP | NP | NP |
- When reinforcement required is 0.00, only diaphragm chord tension reinforcement is required.
- Diaphragm chord tension steel area shall be added to bond beam uplift steel area for total required bond beam area of steel. Select appropriate bar size and number of bars from Table R609.2.2C.
UPLIFT, plf (ALLOWABLE STRESS DESIGN) | 16 IN. BOND BEAM/LINTEL SPAN, FT. | |||||||
4 | 6 | 8 | 10 | 12 | 14 | 16 | 18 | |
50 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
100 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
150 | 0.007 | 0.016 | 0.028 | 0.044 | 0.063 | 0.087 | 0.114 | 0.145 |
200 | 0.011 | 0.025 | 0.044 | 0.069 | 0.101 | 0.138 | 0.181 | 0.231 |
250 | 0.015 | 0.034 | 0.061 | 0.095 | 0.138 | 0.190 | 0.250 | 0.320 |
300 | 0.019 | 0.043 | 0.077 | 0.121 | 0.176 | 0.242 | 0.321 | 0.413 |
350 | 0.023 | 0.052 | 0.093 | 0.147 | 0.215 | 0.296 | 0.393 | NP |
400 | 0.027 | 0.061 | 0.110 | 0.174 | 0.254 | 0.351 | 0.468 | NP |
450 | 0.031 | 0.071 | 0.127 | 0.200 | 0.293 | 0.407 | NP | NP |
500 | 0.035 | 0.080 | 0.143 | 0.227 | 0.333 | 0.464 | NP | NP |
550 | 0.039 | 0.089 | 0.160 | 0.254 | 0.374 | 0.523 | NP | NP |
600 | 0.043 | 0.098 | 0.177 | 0.282 | 0.415 | 0.583 | NP | NP |
650 | 0.047 | 0.108 | 0.194 | 0.310 | 0.458 | 0.644 | NP | NP |
700 | 0.051 | 0.117 | 0.211 | 0.338 | 0.500 | NP | NP | NP |
750 | 0.056 | 0.126 | 0.229 | 0.366 | 0.544 | NP | NP | NP |
800 | 0.060 | 0.136 | 0.246 | 0.394 | 0.588 | NP | NP | NP |
850 | 0.064 | 0.145 | 0.264 | 0.423 | 0.633 | NP | NP | NP |
900 | 0.068 | 0.155 | 0.281 | 0.453 | 0.679 | NP | NP | NP |
950 | 0.072 | 0.164 | 0.299 | 0.482 | NP | NP | NP | NP |
1000 | 0.076 | 0.174 | 0.317 | 0.512 | NP | NP | NP | NP |
1050 | 0.080 | 0.183 | 0.335 | 0.542 | NP | NP | NP | NP |
1100 | 0.084 | 0.193 | 0.353 | 0.573 | NP | NP | NP | NP |
- When reinforcement required is 0.00, only diaphragm chord tension reinforcement is required.
- Diaphragm chord tension steel area shall be added to bond beam uplift steel area for total required bond beam area of steel. Select appropriate bar size and number of bars from Table R609.2.2C.
UPLIFT, plf (ALLOWABLE STRESS DESIGN) | 24 IN. BOND BEAM/LINTEL SPAN, FT. | |||||||
4 | 6 | 8 | 10 | 12 | 14 | 16 | 18 | |
50 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
100 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
150 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
200 | 0.005 | 0.012 | 0.021 | 0.033 | 0.048 | 0.065 | 0.085 | 0.108 |
250 | 0.008 | 0.017 | 0.031 | 0.049 | 0.070 | 0.096 | 0.126 | 0.160 |
300 | 0.010 | 0.023 | 0.041 | 0.065 | 0.093 | 0.127 | 0.167 | 0.212 |
350 | 0.013 | 0.029 | 0.051 | 0.080 | 0.116 | 0.159 | 0.209 | 0.266 |
400 | 0.015 | 0.034 | 0.061 | 0.096 | 0.139 | 0.191 | 0.251 | 0.319 |
450 | 0.018 | 0.040 | 0.072 | 0.112 | 0.163 | 0.223 | 0.293 | 0.374 |
500 | 0.020 | 0.046 | 0.082 | 0.128 | 0.186 | 0.255 | 0.336 | 0.429 |
550 | 0.023 | 0.051 | 0.092 | 0.144 | 0.209 | 0.287 | 0.379 | 0.485 |
600 | 0.025 | 0.057 | 0.102 | 0.161 | 0.233 | 0.320 | 0.423 | 0.542 |
650 | 0.028 | 0.063 | 0.112 | 0.177 | 0.257 | 0.353 | 0.467 | 0.599 |
700 | 0.030 | 0.069 | 0.123 | 0.193 | 0.280 | 0.386 | 0.511 | 0.657 |
750 | 0.033 | 0.074 | 0.133 | 0.209 | 0.304 | 0.419 | 0.556 | 0.716 |
800 | 0.035 | 0.080 | 0.143 | 0.226 | 0.329 | 0.453 | 0.601 | 0.776 |
850 | 0.038 | 0.086 | 0.154 | 0.242 | 0.353 | 0.487 | 0.647 | 0.837 |
900 | 0.040 | 0.091 | 0.164 | 0.259 | 0.377 | 0.521 | 0.694 | NP |
950 | 0.043 | 0.097 | 0.174 | 0.275 | 0.402 | 0.556 | 0.741 | NP |
1000 | 0.045 | 0.103 | 0.185 | 0.292 | 0.426 | 0.590 | 0.788 | NP |
1050 | 0.048 | 0.109 | 0.195 | 0.308 | 0.451 | 0.625 | 0.836 | NP |
1100 | 0.051 | 0.114 | 0.205 | 0.325 | 0.476 | 0.661 | NP | NP |
- When reinforcement required is 0.00, only diaphragm chord tension reinforcement is required.
- Diaphragm chord tension steel area shall be added to bond beam uplift steel area for total required bond beam area of steel. Select appropriate bar size and number of bars from Table R609.2.2C.
UPLIFT, plf (ALLOWABLE STRESS DESIGN) | 32 IN. BOND BEAM/LINTEL SPAN, FT. | |||||||
4 | 6 | 8 | 10 | 12 | 14 | 16 | 18 | |
50 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
100 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
150 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
200 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
250 | 0.004 | 0.010 | 0.018 | 0.028 | 0.040 | 0.055 | 0.072 | 0.091 |
300 | 0.006 | 0.014 | 0.025 | 0.039 | 0.057 | 0.077 | 0.101 | 0.129 |
350 | 0.008 | 0.018 | 0.033 | 0.051 | 0.073 | 0.100 | 0.131 | 0.166 |
400 | 0.010 | 0.022 | 0.040 | 0.062 | 0.090 | 0.123 | 0.161 | 0.204 |
450 | 0.012 | 0.026 | 0.047 | 0.074 | 0.107 | 0.145 | 0.191 | 0.242 |
500 | 0.014 | 0.031 | 0.054 | 0.085 | 0.123 | 0.168 | 0.221 | 0.281 |
550 | 0.015 | 0.035 | 0.062 | 0.097 | 0.140 | 0.191 | 0.251 | 0.319 |
600 | 0.017 | 0.039 | 0.069 | 0.108 | 0.157 | 0.214 | 0.281 | 0.358 |
650 | 0.019 | 0.043 | 0.077 | 0.120 | 0.173 | 0.237 | 0.312 | 0.397 |
700 | 0.021 | 0.047 | 0.084 | 0.132 | 0.190 | 0.260 | 0.342 | 0.436 |
750 | 0.023 | 0.051 | 0.091 | 0.143 | 0.207 | 0.284 | 0.373 | 0.476 |
800 | 0.025 | 0.055 | 0.099 | 0.155 | 0.224 | 0.307 | 0.404 | 0.515 |
850 | 0.026 | 0.059 | 0.106 | 0.166 | 0.241 | 0.330 | 0.435 | 0.556 |
900 | 0.028 | 0.064 | 0.113 | 0.178 | 0.258 | 0.354 | 0.466 | 0.596 |
950 | 0.030 | 0.068 | 0.121 | 0.190 | 0.275 | 0.377 | 0.497 | 0.636 |
1000 | 0.032 | 0.072 | 0.128 | 0.201 | 0.292 | 0.401 | 0.529 | 0.677 |
1050 | 0.034 | 0.076 | 0.136 | 0.213 | 0.309 | 0.425 | 0.561 | 0.718 |
1100 | 0.035 | 0.080 | 0.143 | 0.225 | 0.326 | 0.449 | 0.592 | 0.760 |
- When reinforcement required is 0.00, only diaphragm chord tension reinforcement is required.
- Diaphragm chord tension steel area shall be added to bond beam uplift steel area for total required bond beam area of steel. Select appropriate bar size and number of bars from Table R609.2.2C.
NUMBER OF BARS | BAR SIZE | ||
No. 4 | No. 5 | No. 6 | |
1 | 0.20 | 0.31 | 0.44 |
2 | 0.40 | 0.62 | 0.88 |
Reinforcement shall be located in the top of bond beams and in the top and bottom of bond beams also serving as lintels.
.
Corner continuity. Reinforcement in bond beams shall be continuous around corners as detailed in Figure R609.2.4.
Corner continuity. Reinforcement in bond beams shall be continuous around corners as detailed in Figure R609.2.4.
Exception: In bond beams requiring two reinforcing bars, one bar shall be continuous around corners.

Changes in bond beam height shall be permitted as detailed in Figure R609.2.5.

Precast bond beams shall properly receive and retain all vertical wall reinforcement. Precast bond beams shall contain the minimum amount of continuous reinforcement set forth in Sections R609.2.2 and R609.6 as applicable and shall be reinforced at joints o act as drag struts and diaphragm chords.
One reinforcement bar shall be provided in each corner, including interior corners and corners created by changes in wall direction or offsetting of walls.
A minimum of one bar of the size used for vertical wall reinforcement shall be provided on each side of openings wider than 6 feet (1829 mm). If more vertical reinforcement is interrupted by an opening than is provided beside the opening (total in the first and second cells adjacent to the opening), one-half of the equivalent area of reinforcement interrupted by the opening shall be placed on each side of the opening. This reinforcement shall be placed within the first and/or second cells beside the opening.
R609.3.2.1 Girders. At least one reinforcement bar shall be provided where girders or girder trusses bear on masonry walls.
Vertical reinforcement shall be provided as set forth in Tables R609.3.3.A-1 through Table R609.3.3A-4 and R609.3.3.B-1 through R609.3.3B-4, as applicable.
TABLE R609.3.3A-1 GRADE 60
SINGLE STORY AND TOP STORY WALLS PARALLEL TO RIDGE VERTICAL REINFORCEMENT SPACING NO.5 BARS (5/8 IN.)
SINGLE STORY AND TOP STORY WALLS PARALLEL TO RIDGE VERTICAL REINFORCEMENT SPACING NO.5 BARS (5/8 IN.)
EXPOSURE | B | B | B | C | C | C | |
Vasd as determined in accordance with Section R301.2.1.3 | WALL HEIGHT | BUILDING WIDTH | |||||
24 | 32 | 40 | 24 | 32 | 40 | ||
100 | 8.00 | 9.87 | 9.87 | 9.87 | 8.34 | 8.34 | 8.34 |
8.67 | 9.97 | 9.97 | 9.97 | 8.42 | 8.42 | 8.42 | |
9.33 | 10.06 | 10.06 | 10.06 | 8.49 | 8.49 | 8.49 | |
10.00 | 10.14 | 10.14 | 10.14 | 8.57 | 8.57 | 8.54 | |
EXPOSURE | B | B | B | C | C | C | |
Vasd as determined in accordance with Section R301.2.1.3 | WALL HEIGHT | BUILDING WIDTH | |||||
24 | 32 | 40 | 24 | 32 | 40 | ||
110 | 8.00 | 8.97 | 8.7 | 8.97 | 7.58 | 7.58 | 7.58 |
8.67 | 9.06 | 9.06 | 9.06 | 7.65 | 7.56 | 7.65 | |
9.33 | 9.14 | 9.14 | 9.14 | 7.72 | 7.72 | 7.72 | |
10.00 | 9.22 | 9.22 | 9.22 | 7.79 | 7.79 | 7.79 | |
EXPOSURE | B | B | B | C | C | C | |
Vasd as determined in accordance with Section R301.2.1.3 | WALL HEIGHT | BUILDING WIDTH | |||||
24 | 32 | 40 | 24 | 32 | 40 | ||
120 | 8.00 | 8.23 | 8.23 | 8.23 | 6.95 | 6.95 | 6.95 |
8.67 | 8.30 | 8.30 | 8.30 | 7.01 | 7.01 | 7.01 | |
9.33 | 8.38 | 8.38 | 8.38 | 7.08 | 7.08 | 7.08 | |
10.00 | 8.45 | 8.45 | 8.45 | 6.87 | 6.87 | 6.87 | |
EXPOSURE | B | B | B | C | C | C | |
Vasd as determined in accordance with Section R301.2.1.3 | WALL HEIGHT | BUILDING WIDTH | |||||
24 | 32 | 40 | 24 | 32 | 40 | ||
130 | 8.00 | 7.59 | 7.59 | 7.59 | 6.41 | 6.41 | 6.21 |
8.67 | 7.67 | 7.67 | 7.67 | 6.47 | 6.14 | 5.67 | |
9.33 | 7.73 | 7.73 | 7.57 | 6.03 | 5.58 | 5.19 | |
10.00 | 7.80 | 7.36 | 6.90 | 5.44 | 5.07 | 4.74 | |
EXPOSURE | B | B | B | C | C | C | |
Vasd as determined in accordance with Section R301.2.1.3 | WALL HEIGHT | BUILDING WIDTH | |||||
24 | 32 | 40 | 24 | 32 | 40 | ||
140 | 8.00 | 7.05 | 7.05 | 7.05 | 5.95 | 5.76 | 5.27 |
8.67 | 7.12 | 7.12 | 7.01 | 5.70 | 5.22 | 4.82 | |
9.33 | 7.18 | 6.88 | 6.40 | 5.14 | 4.75 | 4.41 | |
10.00 | 6.70 | 6.24 | 5.85 | 4.64 | 4.32 | 4.04 | |
EXPOSURE | B | B | B | C | C | C | |
Vasd as determined in accordance with Section R301.2.1.3 | WALL HEIGHT | BUILDING WIDTH | |||||
24 | 32 | 40 | 24 | 32 | 40 | ||
150 | 8.00 | 6.58 | 6.58 | 6.58 | 5.46 | 4.96 | 4.54 |
8.67 | 6.64 | 6.50 | 6.01 | 4.91 | 4.50 | 4.15 | |
9.33 | 6.39 | 5.91 | 5.49 | 4.43 | 4.09 | 3.80 | |
10.00 | 5.76 | 5.37 | 5.02 | 4.00 | 3.72 | 3.48 |
TABLE R609.3.3A-2 GRADE 60
SINGLE STORY AND TOP STORY WALLS PARALLEL TO RIDGE VERTICAL REINFORCEMENT SPACING NO. 4 BARS (1/2 IN.)
SINGLE STORY AND TOP STORY WALLS PARALLEL TO RIDGE VERTICAL REINFORCEMENT SPACING NO. 4 BARS (1/2 IN.)
EXPOSURE | B | B | B | C | C | C | |
Vasd as determined in accordance with Section R301.2.1.3 | WALL HEIGHT | BUILDING WIDTH | |||||
24 | 32 | 40 | 24 | 32 | 40 | ||
100 | 8.00 | 9.87 | 9.87 | 9.87 | 8.34 | 7.97 | 7.32 |
8.67 | 9.97 | 9.97 | 9.97 | 7.79 | 7.17 | 6.65 | |
9.33 | 10.06 | 9.69 | 9.08 | 6.98 | 6.48 | 6.05 | |
10.00 | 9.06 | 8.72 | 8.22 | 6.27 | 5.87 | 5.51 | |
EXPOSURE | B | B | B | C | C | C | |
Vasd as determined in accordance with Section R301.2.1.3 | WALL HEIGHT | BUILDING WIDTH | |||||
24 | 32 | 40 | 24 | 32 | 40 | ||
110 | 8.00 | 8.97 | 8.97 | 8.76 | 7.01 | 6.38 | 5.85 |
8.67 | 9.06 | 9.06 | 9.06 | 6.83 | 6.83 | 6.83 | |
9.33 | 8.45 | 8.45 | 8.45 | 5.99 | 5.99 | 5.99 | |
10.00 | 7.47 | 7.47 | 7.47 | 5.30 | 5.30 | 5.30 | |
EXPOSURE | B | B | B | C | C | C | |
Vasd as determined in accordance with Section R301.2.1.3 | WALL HEIGHT | BUILDING WIDTH | |||||
24 | 32 | 40 | 24 | 32 | 40 | ||
120 | 8.00 | 8.23 | 7.72 | 7.09 | 5.75 | 5.23 | 4.80 |
8.67 | 8.07 | 8.07 | 8.07 | 5.72 | 5.72 | 5.72 | |
9.33 | 7.08 | 7.08 | 7.08 | 5.02 | 5.02 | 5.02 | |
10.00 | 6.26 | 6.26 | 6.26 | 4.43 | 4.43 | 4.43 | |
EXPOSURE | B | B | B | C | C | C | |
Vasd as determined in accordance with Section R301.2.1.3 | WALL HEIGHT | BUILDING WIDTH | |||||
24 | 32 | 40 | 24 | 32 | 40 | ||
130 | 8.00 | 7.04 | 6.41 | 5.88 | 4.82 | 4.38 | 4.01 |
8.67 | 6.29 | 5.78 | 5.35 | 4.32 | 3.96 | 3.66 | |
9.33 | 5.65 | 5.24 | 4.88 | 3.89 | 3.60 | 3.35 | |
10.00 | 5.09 | 4.75 | 4.45 | 3.51 | 3.27 | 3.06 | |
EXPOSURE | B | B | B | C | C | C | |
Vasd as determined in accordance with Section R301.2.1.3 | WALL HEIGHT | BUILDING WIDTH | |||||
24 | 32 | 40 | 24 | 32 | 40 | ||
140 | 8.00 | 5.95 | 5.41 | 4.08 | 4.09 | 3.72 | 3.40 |
8.67 | 5.33 | 4.89 | 4.52 | 3.68 | 3.37 | 3.11 | |
9.33 | 4.79 | 4.44 | 4.13 | 3.31 | 3.08 | 2.85 | |
10.00 | 4.32 | 4.00 | 3.77 | 2.99 | 2.78 | 2.60 | |
EXPOSURE | B | B | B | C | C | C | |
Vasd as determined in accordance with Section R301.2.1.3 | WALL HEIGHT | BUILDING WIDTH | |||||
24 | 32 | 40 | 24 | 32 | 40 | ||
150 | 8.00 | 5.10 | 4.63 | 4.25 | 3.53 | 3.20 | 2.93 |
8.67 | 4.57 | 4.20 | 3.87 | 3.17 | 2.90 | 2.68 | |
9.33 | 4.12 | 3.81 | 3.54 | 2.86 | 2.64 | 2.45 | |
10.00 | 3.71 | 3.46 | 3.24 | 2.58 | 2.40 | 2.24 |
TABLE R609.3.3A-3 GRADE 40
SINGLE STORY AND TOP STORY WALLS PARALLEL TO RIDGE VERTICAL REINFORCEMENT SPACING NO.5 BARS (5/8 IN.)
SINGLE STORY AND TOP STORY WALLS PARALLEL TO RIDGE VERTICAL REINFORCEMENT SPACING NO.5 BARS (5/8 IN.)
EXPOSURE | B | B | B | C | C | C | |
Vasd as determined in accordance with Section R301.2.1.3 | WALL HEIGHT | BUILDING WIDTH | |||||
24 | 32 | 40 | 24 | 32 | 40 | ||
100 | 8.00 | 9.87 | 9.87 | 9.87 | 8.34 | 8.23 | 7.57 |
8.67 | 9.97 | 9.97 | 9.97 | 8.05 | 7.41 | 6.87 | |
9.33 | 10.06 | 10.01 | 9.38 | 7.22 | 6.70 | 6.25 | |
10.00 | 9.36 | 9.01 | 8.49 | 6.48 | 6.06 | 5.69 | |
EXPOSURE | B | B | B | C | C | C | |
Vasd as determined in accordance with Section R301.2.1.3 | WALL HEIGHT | BUILDING WIDTH | |||||
24 | 32 | 40 | 24 | 32 | 40 | ||
110 | 8.00 | 8.97 | 8.97 | 8.97 | 7.24 | 6.59 | 6.05 |
8.67 | 9.06 | 9.06 | 9.06 | 7.06 | 7.06 | 7.06 | |
9.33 | 8.73 | 8.73 | 8.73 | 6.19 | 6.19 | 6.19 | |
10.00 | 7.72 | 7.72 | 7.72 | 5.47 | 5.47 | 5.47 | |
EXPOSURE | B | B | B | C | C | C | |
Vasd as determined in accordance with Section R301.2.1.3 | WALL HEIGHT | BUILDING WIDTH | |||||
24 | 32 | 40 | 24 | 32 | 40 | ||
120 | 8.00 | 8.23 | 7.98 | 7.33 | 5.95 | 5.41 | 4.96 |
8.67 | 8.30 | 8.30 | 8.30 | 5.92 | 5.92 | 5.92 | |
9.33 | 7.32 | 7.32 | 7.32 | 5.19 | 5.19 | 5.19 | |
10.00 | 6.47 | 6.47 | 6.47 | 4.58 | 4.58 | 4.58 | |
EXPOSURE | B | B | B | C | C | C | |
Vasd as determined in accordance with Section R301.2.1.3 | WALL HEIGHT | BUILDING WIDTH | |||||
24 | 32 | 40 | 24 | 32 | 40 | ||
130 | 8.00 | 7.27 | 6.62 | 6.07 | 4.98 | 4.52 | 4.14 |
8.67 | 6.50 | 5.98 | 5.53 | 4.47 | 4.10 | 3.78 | |
9.33 | 5.84 | 5.41 | 5.04 | 4.02 | 3.72 | 3.46 | |
10.00 | 5.26 | 4.91 | 4.60 | 3.63 | 3.38 | 3.16 | |
EXPOSURE | B | B | B | C | C | C | |
Vasd as determined in accordance with Section R301.2.1.3 | WALL HEIGHT | BUILDING WIDTH | |||||
24 | 32 | 40 | 24 | 32 | 40 | ||
140 | 8.00 | 6.15 | 5.59 | 5.13 | 4.23 | 3.84 | 3.52 |
8.67 | 5.51 | 5.06 | 4.67 | 3.80 | 3.48 | 3.21 | |
9.33 | 4.95 | 4.59 | 4.27 | 3.43 | 3.17 | 2.94 | |
10.00 | 4.46 | 4.16 | 3.90 | 3.09 | 2.88 | 2.69 | |
EXPOSURE | B | B | B | C | C | C | |
Vasd as determined in accordance with Section R301.2.1.3 | WALL HEIGHT | BUILDING WIDTH | |||||
24 | 32 | 40 | 24 | 32 | 40 | ||
150 | 8.00 | 5.27 | 4.79 | 4.39 | 3.64 | 3.31 | 3.02 |
8.67 | 4.73 | 4.34 | 4.00 | 3.27 | 3.00 | 2.76 | |
9.33 | 4.26 | 3.94 | 3.66 | 2.95 | 2.73 | 2.53 | |
10.00 | 3.84 | 3.58 | 3.35 | 2.66 | 2.48 | 2.32 |
TABLE R609.3.3A-4 GRADE 40
SINGLE STORY AND TOP STORY WALLS PARALLEL TO RIDGE VERTICAL REINFORCEMENT SPACING NO. 4 BARS (1/2 IN.)
SINGLE STORY AND TOP STORY WALLS PARALLEL TO RIDGE VERTICAL REINFORCEMENT SPACING NO. 4 BARS (1/2 IN.)
EXPOSURE | B | B | B | C | C | C | |
Vasd as determined in accordance with Section R301.2.1.3 | WALL HEIGHT | BUILDING WIDTH | |||||
24 | 32 | 40 | 24 | 32 | 40 | ||
100 | 8.00 | 8.78 | 8.04 | 7.42 | 5.82 | 5.31 | 4.88 |
8.67 | 7.77 | 7.19 | 6.69 | 5.19 | 4.78 | 4.43 | |
9.33 | 6.83 | 6.46 | 6.05 | 4.66 | 4.32 | 4.03 | |
10.00 | 6.04 | 5.81 | 5.48 | 4.18 | 3.91 | 3.67 | |
EXPOSURE | B | B | B | C | C | C | |
Vasd as determined in accordance with Section R301.2.1.3 | WALL HEIGHT | BUILDING WIDTH | |||||
24 | 32 | 40 | 24 | 32 | 40 | ||
110 | 8.00 | 6.94 | 6.34 | 5.84 | 4.67 | 4.25 | 3.90 |
8.67 | 6.42 | 6.42 | 6.42 | 4.56 | 4.56 | 4.56 | |
9.33 | 5.63 | 5.63 | 5.63 | 4.00 | 4.00 | 4.00 | |
10.00 | 4.98 | 4.98 | 4.98 | 3.53 | 3.53 | 3.53 | |
EXPOSURE | B | B | B | C | C | C | |
Vasd as determined in accordance with Section R301.2.1.3 | WALL HEIGHT | BUILDING WIDTH | |||||
24 | 32 | 40 | 24 | 32 | 40 | ||
120 | 8.00 | 5.64 | 5.15 | 4.73 | 3.84 | 3.49 | 3.20 |
8.67 | 5.38 | 5.38 | 5.38 | 3.82 | 3.82 | 3.82 | |
9.33 | 4.72 | 4.72 | 4.72 | 3.35 | 3.35 | 3.35 | |
10.00 | 4.17 | 4.17 | 4.17 | 2.95 | 2.95 | 2.95 | |
EXPOSURE | B | B | B | C | C | C | |
Vasd as determined in accordance with Section R301.2.1.3 | WALL HEIGHT | BUILDING WIDTH | |||||
24 | 32 | 40 | 24 | 32 | 40 | ||
130 | 8.00 | 4.69 | 4.27 | 3.92 | 3.21 | 2.92 | 2.67 |
8.67 | 4.19 | 3.86 | 3.57 | 2.88 | 2.64 | 2.44 | |
9.33 | 3.77 | 3.49 | 3.25 | 2.60 | 2.40 | 2.23 | |
10.00 | 3.39 | 3.17 | 2.97 | 2.34 | 2.18 | 2.04 | |
EXPOSURE | B | B | B | C | C | C | |
Vasd as determined in accordance with Section R301.2.1.3 | WALL HEIGHT | BUILDING WIDTH | |||||
24 | 32 | 40 | 24 | 32 | 40 | ||
140 | 8.00 | 3.97 | 3.61 | 3.31 | 2.73 | 2.46 | 2.27 |
8.67 | 3.55 | 3.26 | 3.01 | 2.45 | 2.25 | 2.07 | |
9.33 | 3.20 | 2.96 | 2.75 | 2.21 | 2.04 | 1.90 | |
10.00 | 2.88 | 2.69 | 2.52 | 1.99 | 1.86 | 1.74 | |
EXPOSURE | B | B | B | C | C | C | |
Vasd as determined in accordance with Section R301.2.1.3 | WALL HEIGHT | BUILDING WIDTH | |||||
24 | 32 | 40 | 24 | 32 | 40 | ||
150 | 8.00 | 3.40 | 3.09 | 2.83 | 2.35 | 2.13 | 1.95 |
8.67 | 3.05 | 2.80 | 2.58 | 2.11 | 1.93 | 1.78 | |
9.33 | 2.75 | 2.54 | 2.36 | 1.90 | 1.76 | 1.63 | |
10.00 | 2.48 | 2.31 | 2.16 | 1.72 | 1.60 | 1.50 |
TABLE R609.3.3B-1 GRADE 60
MAXIMUM SPACING OF NO.5 (5/8 IN.) VERTICAL REINFORCEMENT AT CONTINUOUS CONCRETE MASONRY LOWER STORIES OF
MULTISTORY AND GABLE ENDS SINGLE STORY OR TOP STORY OF MULTISTORY, FEET
MAXIMUM SPACING OF NO.5 (5/8 IN.) VERTICAL REINFORCEMENT AT CONTINUOUS CONCRETE MASONRY LOWER STORIES OF
MULTISTORY AND GABLE ENDS SINGLE STORY OR TOP STORY OF MULTISTORY, FEET
Vasd AS DETERMINED IN ACCORDANCE WITH SECTION R301.2.1.3 | 100 | 110 | 120 | 130 | 140 | 150 | |||||||
EXP | WALL HT | END ZONE | INT ZONE | END ZONE | INT ZONE | END ZONE | INT ZONE | END ZONE | INT ZONE | END ZONE | INT ZONE | END ZONE | INT ZONE |
B | 8 | 9.87 | 10.53 | 8.97 | 9.57 | 8.23 | 8.78 | 7.59 | 8.10 | 7.05 | 7.52 | 6.58 | 7.02 |
8.67 | 9.97 | 10.59 | 9.06 | 9.63 | 8.30 | 8.82 | 7.67 | 8.15 | 7.12 | 7.56 | 6.64 | 7.06 | |
9.33 | 10.06 | 10.64 | 9.14 | 9.68 | 8.38 | 8.87 | 7.73 | 8.19 | 7.18 | 7.60 | 6.70 | 7.10 | |
10 | 10.14 | 10.69 | 9.22 | 9.72 | 8.45 | 8.91 | 7.80 | 8.23 | 7.08 | 7.64 | 6.14 | 6.85 | |
12 | 10.17 | 10.83 | 8.38 | 9.14 | 7.01 | 7.65 | 5.95 | 6.49 | 5.10 | 5.57 | 4.42 | 4.83 | |
14 | 7.75 | 8.29 | 6.37 | 6.82 | 5.33 | 5.70 | 4.51 | 4.83 | 3.86 | 4.14 | 3.34 | 3.58 | |
16 | 6.12 | 6.43 | 5.03 | 5.29 | 4.19 | 4.41 | 3.55 | 3.73 | 3.03 | 3.19 | 2.62 | 2.76 | |
18 | 4.97 | 5.14 | 4.07 | 4.21 | 3.39 | 3.51 | 2.86 | 2.96 | 2.44 | 2.53 | 2.10 | 2.18 | |
20 | 4.12 | 4.20 | 3.38 | 3.44 | 2.81 | 2.86 | 2.36 | 2.41 | 2.01 | 2.05 | 1.72 | 1.76 | |
22 | 3.48 | 3.49 | 2.84 | 2.85 | 2.36 | 2.36 | 1.98 | 1.99 | 1.68 | 1.68 | 1.43 | 1.44 | |
C | 8 | 8.34 | 8.89 | 7.58 | 8.09 | 6.95 | 7.41 | 6.41 | 6.84 | 5.95 | 6.35 | 5.56 | 5.93 |
8.67 | 8.42 | 8.94 | 7.65 | 8.13 | 7.01 | 7.45 | 6.47 | 6.88 | 6.01 | 6.39 | 5.24 | 5.96 | |
9.33 | 8.49 | 8.99 | 7.72 | 8.17 | 7.08 | 7.49 | 6.52 | 6.91 | 5.53 | 6.37 | 4.75 | 5.53 | |
10 | 8.57 | 9.03 | 7.79 | 8.21 | 6.87 | 7.53 | 5.83 | 6.50 | 5.00 | 5.58 | 4.31 | 4.84 | |
12 | 7.21 | 7.86 | 5.92 | 6.47 | 4.95 | 5.40 | 4.19 | 4.58 | 3.59 | 3.92 | 3.10 | 3.39 | |
14 | 5.47 | 5.86 | 4.49 | 4.81 | 3.75 | 4.01 | 3.16 | 3.39 | 2.70 | 2.90 | 2.33 | 2.50 | |
16 | 4.31 | 4.54 | 3.53 | 3.72 | 2.94 | 3.09 | 2.47 | 2.61 | 2.11 | 2.22 | 1.81 | 1.91 | |
18 | 3.49 | 3.61 | 2.85 | 2.95 | 2.37 | 2.45 | 1.99 | 2.06 | 1.68 | 1.75 | 1.44 | 1.49 | |
20 | 2.89 | 2.94 | 2.35 | 2.40 | 1.94 | 1.98 | 1.63 | 1.66 | 1.37 | 1.40 | 1.16 | 1.19 | |
22 | 2.43 | 2.43 | 1.97 | 1.98 | 1.62 | 1.63 | 1.35 | 1.35 | 1.13 | 1.14 | 1.03 | 1.26 |
TABLE R609.3.3B-2 GRADE
60 MAXIMUM SPACING OF NO. 4 (1/2 IN.) VERTICAL REINFORCEMENT AT CONTINUOUS MASONRY LOWER STORIES OF MULTISTORY
AND GABLE ENDS SINGLE STORY OR TOP STORY OF MULTISTORY, FEET
60 MAXIMUM SPACING OF NO. 4 (1/2 IN.) VERTICAL REINFORCEMENT AT CONTINUOUS MASONRY LOWER STORIES OF MULTISTORY
AND GABLE ENDS SINGLE STORY OR TOP STORY OF MULTISTORY, FEET
Vasd AS DETERMINED IN ACCORDANCE WITH SECTION R301.2.1.3 | 100 | 110 | 120 | 130 | 140 | 150 | |||||||
EXP | WALL HT | END ZONE | INT ZONE | END ZONE | INT ZONE | END ZONE | INT ZONE | END ZONE | INT ZONE | END ZONE | INT ZONE | END ZONE | INT ZONE |
B | 8 | 9.87 | 10.53 | 8.97 | 9.57 | 8.23 | 8.78 | 7.59 | 8.10 | 6.42 | 7.52 | 5.47 | 6.68 |
8.67 | 9.97 | 10.59 | 9.06 | 9.63 | 8.07 | 8.82 | 6.86 | 7.76 | 5.77 | 6.68 | 4.93 | 5.80 | |
9.33 | 10.06 | 10.64 | 8.45 | 9.48 | 7.08 | 7.95 | 6.02 | 6.76 | 5.17 | 5.81 | 4.46 | 5.05 | |
10 | 9.06 | 10.09 | 7.47 | 8.32 | 6.26 | 6.97 | 5.32 | 5.92 | 4.57 | 5.09 | 3.96 | 4.42 | |
12 | 6.56 | 7.16 | 5.40 | 5.89 | 4.52 | 4.93 | 3.84 | 4.19 | 3.29 | 3.59 | 2.85 | 3.12 | |
14 | 5.00 | 5.35 | 4.11 | 4.40 | 3.44 | 3.68 | 2.91 | 3.12 | 2.49 | 2.67 | 2.16 | 2.31 | |
16 | 3.95 | 4.15 | 3.24 | 3.41 | 2.71 | 2.85 | 2.29 | 2.41 | 1.96 | 2.06 | 1.69 | 1.78 | |
18 | 3.21 | 3.31 | 2.63 | 2.72 | 2.19 | 2.27 | 1.85 | 1.91 | 1.58 | 1.63 | 1.36 | 1.41 | |
20 | 2.66 | 2.71 | 2.18 | 2.22 | 1.81 | 1.84 | 1.52 | 1.55 | 1.30 | 1.32 | 1.11 | 1.13 | |
22 | 2.25 | 2.25 | 1.83 | 1.84 | 1.52 | 1.53 | 1.28 | 1.28 | 1.08 | 1.09 | 0.93 | 0.93 | |
C | 8 | 8.34 | 8.89 | 7.58 | 8.09 | 6.20 | 7.41 | 5.15 | 6.29 | 4.36 | 5.30 | 3.73 | 4.53 |
8.67 | 8.29 | 8.94 | 6.83 | 7.73 | 5.58 | 6.48 | 4.65 | 5.50 | 3.94 | 4.73 | 3.38 | 4.09 | |
9.33 | 7.28 | 8.17 | 5.99 | 6.73 | 5.02 | 5.64 | 4.21 | 4.79 | 3.57 | 4.11 | 3.06 | 3.57 | |
10 | 6.43 | 7.16 | 5.30 | 5.90 | 4.43 | 4.94 | 3.76 | 4.19 | 3.22 | 3.60 | 2.78 | 3.12 | |
12 | 4.65 | 5.07 | 3.82 | 4.17 | 3.19 | 3.49 | 2.70 | 2.95 | 2.31 | 2.53 | 2.00 | 2.19 | |
14 | 3.53 | 3.78 | 2.90 | 3.10 | 2.42 | 2.59 | 2.04 | 2.19 | 1.74 | 1.87 | 1.50 | 1.61 | |
16 | 2.78 | 2.93 | 2.28 | 2.40 | 1.90 | 2.00 | 1.60 | 1.68 | 1.36 | 1.43 | 1.17 | 1.23 | |
18 | 2.25 | 2.33 | 1.84 | 1.90 | 1.53 | 1.58 | 1.28 | 1.33 | 1.09 | 1.13 | 0.93 | 0.96 | |
20 | 1.86 | 1.90 | 1.52 | 1.55 | 1.25 | 1.28 | 1.05 | 1.07 | 0.88 | 0.90 | 0.75 | 0.77 | |
22 | 1.57 | 1.57 | 1.27 | 1.28 | 1.05 | 1.05 | 0.87 | 0.87 | 0.73 | 0.73 | 0.67 | 0.81 |
TABLE R609.3.3B-3 GRADE 40
MAXIMUM SPACING OF NO.5 (5/8 IN.) VERTICAL REINFORCEMENT AT CONTINUOUS CONCRETE MASONRY LOWER STORIES OF MULTISTORY AND GABLE ENDS SINGLE STORY OR TOP STORY OF MULTISTORY, FEET
MAXIMUM SPACING OF NO.5 (5/8 IN.) VERTICAL REINFORCEMENT AT CONTINUOUS CONCRETE MASONRY LOWER STORIES OF MULTISTORY AND GABLE ENDS SINGLE STORY OR TOP STORY OF MULTISTORY, FEET
Vasd AS DETERMINED IN ACCORDANCE WITH SECTION R301.2.1.3 | 100 | 110 | 120 | 130 | 140 | 150 | |||||||
EXP | WALL HT | END ZONE | INT ZONE | END ZONE | INT ZONE | END ZONE | INT ZONE | END ZONE | INT ZONE | END ZONE | INT ZONE | END ZONE | INT ZONE |
B | 8 | 9.87 | 10.53 | 8.97 | 9.57 | 8.23 | 8.78 | 7.59 | 8.10 | 6.63 | 7.52 | 5.65 | 6.91 |
8.67 | 9.97 | 10.59 | 9.06 | 9.63 | 8.30 | 8.82 | 7.09 | 8.02 | 5.97 | 6.90 | 5.09 | 5.99 | |
9.33 | 10.06 | 10.64 | 8.73 | 9.68 | 7.32 | 8.21 | 6.22 | 6.98 | 5.35 | 6.00 | 4.61 | 5.21 | |
10 | 9.36 | 10.42 | 7.72 | 8.60 | 6.47 | 7.20 | 5.49 | 6.12 | 4.72 | 5.26 | 4.10 | 4.57 | |
12 | 6.78 | 7.39 | 5.58 | 6.09 | 4.67 | 5.10 | 3.96 | 4.33 | 3.40 | 3.71 | 2.95 | 3.22 | |
14 | 5.16 | 5.53 | 4.25 | 4.55 | 3.55 | 3.80 | 3.01 | 3.22 | 2.58 | 2.76 | 2.23 | 2.39 | |
16 | 4.08 | 4.29 | 3.35 | 3.52 | 2.80 | 2.94 | 2.36 | 2.49 | 2.02 | 2.13 | 1.74 | 1.84 | |
18 | 3.31 | 3.43 | 2.72 | 2.81 | 2.26 | 2.34 | 1.91 | 1.98 | 1.63 | 1.69 | 1.40 | 1.45 | |
20 | 2.75 | 2.80 | 2.25 | 2.29 | 1.87 | 1.90 | 1.57 | 1.60 | 1.34 | 1.36 | 1.15 | 1.17 | |
22 | 2.32 | 2.33 | 1.90 | 1.90 | 1.57 | 1.58 | 1.32 | 1.32 | 1.12 | 1.12 | 0.00 | 0.00 | |
C | 8 | 8.34 | 8.89 | 7.58 | 8.09 | 6.40 | 7.41 | 5.32 | 6.50 | 4.50 | 5.47 | 3.86 | 4.68 |
8.67 | 8.42 | 8.94 | 7.06 | 7.99 | 5.77 | 6.69 | 4.80 | 5.69 | 4.07 | 4.89 | 3.49 | 4.22 | |
9.33 | 7.52 | 8.44 | 6.19 | 6.95 | 5.19 | 5.82 | 4.35 | 4.95 | 3.69 | 4.25 | 3.17 | 3.68 | |
10 | 6.65 | 7.40 | 5.47 | 6.10 | 4.58 | 5.10 | 3.88 | 4.33 | 3.33 | 3.72 | 2.87 | 3.22 | |
12 | 4.80 | 5.24 | 3.95 | 4.31 | 3.30 | 3.60 | 2.79 | 3.05 | 2.39 | 2.61 | 2.07 | 2.26 | |
14 | 3.65 | 3.91 | 3.00 | 3.21 | 2.50 | 2.68 | 2.11 | 2.26 | 1.80 | 1.93 | 1.55 | 1.67 | |
16 | 2.88 | 3.02 | 2.35 | 2.48 | 1.96 | 2.06 | 1.65 | 1.74 | 1.40 | 1.48 | 1.21 | 1.27 | |
18 | 2.33 | 2.41 | 1.90 | 1.97 | 1.58 | 1.63 | 1.32 | 1.37 | 1.12 | 1.16 | 0.00 | 0.00 | |
20 | 1.92 | 1.96 | 1.57 | 1.60 | 1.30 | 1.32 | 1.08 | 1.10 | 0.00 | 0.00 | 0.00 | 0.00 | |
22 | 1.62 | 1.62 | 1.31 | 1.32 | 1.08 | 1.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
TABLE R609.3.3B-4 GRADE 40
MAXIMUM SPACING OF NO. 4 (1/2 IN.) VERTICAL REINFORCEMENT AT CONTINUOUS CONCRETE OR MASONRY
LOWER STORIES OF MULTISTORY AND GABLE ENDS SINGLE STORY OR TOP STORY OF MULTISTORY, FEET
MAXIMUM SPACING OF NO. 4 (1/2 IN.) VERTICAL REINFORCEMENT AT CONTINUOUS CONCRETE OR MASONRY
LOWER STORIES OF MULTISTORY AND GABLE ENDS SINGLE STORY OR TOP STORY OF MULTISTORY, FEET
Vasd AS DETERMINED IN ACCORDANCE WITH SECTION R301.2.1.3 | 100 | 110 | 120 | 130 | 140 | 150 | |||||||
EXP | WALL HT | END ZONE | INT ZONE | END ZONE | INT ZONE | END ZONE | INT ZONE | END ZONE | INT ZONE | END ZONE | INT ZONE | END ZONE | INT ZONE |
B | 8 | 8.89 | 10.23 | 7.41 | 8.44 | 6.21 | 7.08 | 5.10 | 6.02 | 4.28 | 5.18 | 3.64 | 4.46 |
8.67 | 7.78 | 8.80 | 6.42 | 7.26 | 5.38 | 6.09 | 4.57 | 5.17 | 3.85 | 4.45 | 3.29 | 3.87 | |
9.33 | 6.83 | 7.66 | 5.63 | 6.32 | 4.72 | 5.30 | 4.01 | 4.50 | 3.45 | 3.87 | 2.97 | 3.36 | |
10 | 6.04 | 6.73 | 4.98 | 5.55 | 4.17 | 4.65 | 3.54 | 3.95 | 3.05 | 3.39 | 2.64 | 2.95 | |
12 | 4.38 | 4.77 | 3.60 | 3.93 | 3.02 | 3.29 | 2.56 | 2.79 | 2.19 | 2.40 | 1.90 | 2.08 | |
14 | 3.33 | 3.56 | 2.74 | 2.93 | 2.29 | 2.45 | 1.94 | 2.08 | 1.66 | 1.78 | 1.44 | 1.54 | |
16 | 2.63 | 2.77 | 2.16 | 2.27 | 1.80 | 1.90 | 1.53 | 1.61 | 1.30 | 1.37 | 1.13 | 1.19 | |
18 | 2.14 | 2.21 | 1.75 | 1.81 | 1.46 | 1.51 | 1.23 | 1.27 | 1.05 | 1.09 | 0.90 | 0.94 | |
20 | 1.77 | 1.81 | 1.45 | 1.48 | 1.21 | 1.23 | 1.02 | 1.03 | 0.86 | 0.88 | 0.74 | 0.76 | |
22 | 1.50 | 1.50 | 1.22 | 1.23 | 1.01 | 1.02 | 0.85 | 0.85 | 0.72 | 0.72 | 0.00 | 0.00 | |
C | 8 | 6.38 | 7.28 | 5.08 | 6.00 | 4.13 | 5.03 | 3.43 | 4.19 | 2.90 | 3.53 | 2.49 | 3.02 |
8.67 | 5.53 | 6.25 | 4.56 | 5.15 | 3.72 | 4.32 | 3.10 | 3.67 | 2.62 | 3.15 | 2.25 | 2.72 | |
9.33 | 4.85 | 5.44 | 4.00 | 4.49 | 3.35 | 3.76 | 2.80 | 3.19 | 2.38 | 2.74 | 2.04 | 2.38 | |
10 | 4.29 | 4.78 | 3.53 | 3.93 | 2.95 | 3.29 | 2.51 | 2.79 | 2.15 | 2.40 | 1.85 | 2.08 | |
12 | 3.10 | 3.38 | 2.55 | 2.78 | 2.13 | 2.32 | 1.80 | 1.97 | 1.54 | 1.69 | 1.33 | 1.46 | |
14 | 2.35 | 2.52 | 1.93 | 2.07 | 1.61 | 1.73 | 1.36 | 1.46 | 1.16 | 1.25 | 1.00 | 1.08 | |
16 | 1.85 | 1.95 | 1.52 | 1.60 | 1.26 | 1.33 | 1.06 | 1.12 | 0.91 | 0.96 | 0.78 | 0.82 | |
18 | 1.50 | 1.55 | 1.23 | 1.27 | 1.02 | 1.05 | 0.85 | 0.89 | 0.72 | 0.75 | 0.00 | 0.00 | |
20 | 1.24 | 1.26 | 1.01 | 1.03 | 0.84 | 0.85 | 0.70 | 0.71 | 0.00 | 0.00 | 0.00 | 0.00 | |
22 | 1.04 | 1.05 | 0.85 | 0.85 | 0.70 | 0.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Vertical reinforcement used in conjunction with precast bond beams shall be spaced the same as for masonry bond beams. Reinforcement shall terminate in the precast beam as set forth in Section R606.13.8.
Reinforcing steel requirements shall not be additive. A single bar shall be permitted to satisfy multiple requirements.
Vertical reinforcement shall terminate in footings and bond beams as set forth in Section R606.13.8.
Exception: Gable end trusses or wood framed gable end walls in conformance with Tables R609.4A and R609.4B and Figure R609.4. Wood gable stud wall connectors shall be capable of resisting the vertical and horizontal loads of Table R609.4B as well as the uplift load stipulated in Figure R609.4. Where masonry gable end walls do not go to the roof, a bond beam complying with Section R609.2 shall be provided at the top of the masonry.
TABLE R609.4A
WOOD GABLE BRACE NAILING
WOOD GABLE BRACE NAILING
Vasd AS DETERMINED IN ACCORDANCE WITH SECTION R301.2.1.3 | NAIL SIZE | RAKE HEIGHT | ||||||
12 | 14 | 16 | 18 | 20 | 22 | |||
EXPOSURE B | 100 | 10d | 4 | 4 | 5 | 5 | 6 | 6 |
8d | 6 | 7 | 8 | 8 | 9 | 10 | ||
110 | 10d | 4 | 5 | 6 | 6 | 7 | 7 | |
8d | 7 | 8 | 9 | 10 | 11 | 11 | ||
120 | 10d | 5 | 6 | 7 | 7 | 8 | 8 | |
8d | 9 | 10 | 11 | 12 | 13 | 13 | ||
130 | 10d | 6 | 7 | 8 | 9 | 10 | 10 | |
8d | 10 | 11 | 13 | 14 | 15 | 15 | ||
140 | 10d | 7 | 8 | 9 | 10 | 11 | 11 | |
8d | 12 | 13 | 15 | 16 | 18 | 18 | ||
150 | 10d | 8 | 9 | 11 | 12 | 13 | 13 | |
8d | 13 | 15 | 17 | 19 | 20 | 20 | ||
EXPOSURE C | 100 | 10d | 5 | 6 | 7 | 7 | 8 | 8 |
8d | 8 | 9 | 11 | 12 | 13 | 13 | ||
110 | 10d | 6 | 7 | 8 | 9 | 10 | 10 | |
8d | 10 | 11 | 13 | 14 | 15 | 15 | ||
120 | 10d | 7 | 8 | 9 | 10 | 11 | 11 | |
8d | 12 | 14 | 15 | 17 | 18 | 18 | ||
130 | 10d | 9 | 10 | 11 | 12 | 13 | 13 | |
8d | 14 | 16 | 18 | 20 | 22 | 22 | ||
140 | 10d | 10 | 12 | 13 | 14 | 15 | 15 | |
8d | 16 | 19 | 21 | 23 | 25 | 25 | ||
150 | 10d | 12 | 13 | 15 | 16 | 18 | 18 | |
8d | 19 | 21 | 24 | 26 | 29 | 29 |
TABLE R609.4B
WOOD GABLE STUD CONNECTOR LOADS
WOOD GABLE STUD CONNECTOR LOADS
Vasd AS DETERMINED IN ACCORDANCE WITH SECTION R301.2.1.3 | ROOF ZONE | CONNECTOR LOADS (Allowable Stress Design) | WALL ZONE | ||
VERT | HORIZ1 | ||||
EXPOSURE B | 100 | 2E | 43 | 16 | 1E |
2E | 43 | 11 | 1 | ||
110 | 2E | 53 | 20 | 1E | |
2E | 53 | 13 | 1 | ||
120 | 2E | 62 | 23 | 1E | |
2E | 62 | 15 | 1 | ||
130 | 2E | 73 | 27 | 1E | |
2E | 73 | 18 | 1 | ||
140 | 2E | 85 | 32 | 1E | |
2E | 85 | 21 | 1 | ||
150 | 2E | 98 | 36 | 1E | |
2E | 98 | 24 | 1 | ||
EXPOSURE C | 100 | 2E | 61 | 23 | 1E |
2E | 61 | 15 | 1 | ||
110 | 2E | 74 | 28 | 1E | |
2E | 74 | 18 | 1 | ||
120 | 2E | 88 | 33 | 1E | |
2E | 88 | 22 | 1 | ||
130 | 2E | 103 | 38 | 1E | |
2E | 103 | 25 | 1 | ||
140 | 2E | 119 | 45 | 1E | |
2E | 119 | 30 | 1 | ||
150 | 2E | 137 | 51 | 1E | |
2E | 137 | 34 | 1 |
1. Unit load on stud. Multiply by 1/2 stud length plus 1/2 wall height for total connector load.


Where concrete or masonry is carried full height to the roof line, a cast-in-place rake beam as detailed in Figure R609.4.1 shall be provided. The minimum thickness of the rake beam from top of masonry shall be 4 inches (102 mm). One No. 5 continuous reinforcing bar shall be placed in the rake beam along the roof line.

FIGURE R609.4.1
CONTINUOUS GABLE ENDWALL REINFORCEMENT ONE AND MULTISTORY
CONTINUOUS GABLE ENDWALL REINFORCEMENT ONE AND MULTISTORY
Vertical reinforcement shall be provided at the maximum spacing as set forth in Tables R609.3.3B-1 through R609.3.3.B-4 as applicable.
Required vertical reinforcement shall terminate at the rake beam in accordance with Section R606.13.8.
.
A minimum 2 feet 4 inch nailer for connecting roof sheathing shall be bolted to the top of the wall with a minimum of 1/2-inch (12.7 mm) anchor bolts spaced as set forth in Table R609.4.4. The nailer shall be permitted to be bolted to the inside or outside of the wall.
A minimum 2 feet 4 inch nailer for connecting roof sheathing shall be bolted to the top of the wall with a minimum of 1/2-inch (12.7 mm) anchor bolts spaced as set forth in Table R609.4.4. The nailer shall be permitted to be bolted to the inside or outside of the wall.
REQUIRED ROOF DIAPHRAGM CAPACITY (ALLOWABLE STRESS DESIGN) | 1/2-INCH ANCHOR BOLT MAXIMUM SPACING |
≤ 105 | 6' - 0" |
145 | 5' - 0" |
195 | 4' - 0" |
230 | 3' - 6" |
270 | 3' - 0" |
325 | 2' - 6" |
415 | 2' - 0" |
565 | 1' - 6" |
700 | 1' - 2" |
845 | 1' - 0" |
Gable overhangs up to 2 feet (610 mm) in width complying with Figure R609.4.5 shall be permitted.

FIGURE R609.4.5
GABLE OVERHANG
GABLE OVERHANG
Each exterior wall shall have the required length of effective shearwall to resist horizontal movement or forces at the ends of diaphragms in conformance with this section.
The required shearwall segment length shall be as set forth in Tables R609.5.1A through R609.5.1R as applicable.
EXP | Vasd AS DETERMINED IN ACCORDANCE WITH SECTION R301.2.1.3 |
TOP STORY | 1ST STORY OF 2 STORY OR 2ND STORY OF 3 STORY |
1ST STORY OF 3 STORY | ||||||
BUILDING WIDTH | BUILDING WIDTH | BUILDING WIDTH | ||||||||
24 | 32 | 40 | 24 | 32 | 40 | 24 | 32 | 40 | ||
B | 100 | 1.62 | 2.31 | 3.14 | 3.68 | 4.98 | 6.49 | 5.41 | 7.28 | 9.43 |
110 | 1.96 | 2.79 | 3.80 | 4.45 | 6.03 | 7.85 | 6.55 | 8.81 | 11.42 | |
120 | 2.33 | 3.32 | 4.52 | 5.30 | 7.17 | 9.34 | 7.79 | 10.48 | 13.58 | |
130 | 2.73 | 3.90 | 5.31 | 6.22 | 8.42 | 10.96 | 9.14 | 12.30 | 15.94 | |
140 | 3.17 | 4.52 | 6.16 | 7.22 | 9.376 | 12.71 | 10.60 | 14.27 | 18.49 | |
150 | 3.64 | 5.19 | 7.07 | 8.28 | 11.21 | 14.59 | 12.17 | 16.38 | 21.23 | |
C | 100 | 1.92 | 2.77 | 3.82 | 4.86 | 6.63 | 8.69 | 7.56 | 10.15 | 13.13 |
110 | 2.32 | 3.35 | 4.62 | 5.88 | 8.02 | 10.52 | 9.14 | 12.28 | 15.88 | |
120 | 2.76 | 3.99 | 5.50 | 7.00 | 9.54 | 12.52 | 10.88 | 14.61 | 18.90 | |
130 | 3.24 | 4.68 | 6.46 | 8.21 | 11.20 | 14.69 | 12.77 | 17.15 | 22.18 | |
140 | 3.76 | 5.43 | 7.49 | 9.53 | 12.99 | 17.04 | 14.81 | 19.89 | 25.73 | |
150 | 4.32 | 6.23 | 8.59 | 10.94 | 14.91 | 19.56 | 17.00 | 22.83 | 29.53 |
EXP | Vasd AS DETERMINED IN ACCORDANCE WITH SECTION R301.2.1.3 |
TOP STORY | 1ST STORY OF 2 STORY OR 2ND STORY OF 3 STORY |
1ST STORY OF 3 STORY | ||||||
BUILDING WIDTH | BUILDING WIDTH | BUILDING WIDTH | ||||||||
24 | 32 | 40 | 24 | 32 | 40 | 24 | 32 | 40 | ||
B | 100 | 1.09 | 1.55 | 2.12 | 2.48 | 3.35 | 4.37 | 3.64 | 4.90 | 6.35 |
110 | 1.32 | 1.88 | 2.56 | 3.00 | 4.06 | 5.28 | 4.41 | 5.93 | 7.68 | |
120 | 1.57 | 2.23 | 3.05 | 3.57 | 4.83 | 6.29 | 5.24 | 7.06 | 9.14 | |
130 | 1.84 | 2.62 | 3.57 | 4.19 | 5.67 | 7.38 | 6.16 | 8.28 | 10.73 | |
140 | 2.13 | 3.04 | 4.15 | 4.86 | 6.57 | 8.56 | 7.14 | 9.60 | 12.45 | |
150 | 2.45 | 3.49 | 4.76 | 5.58 | 7.54 | 9.82 | 8.19 | 11.02 | 14.29 | |
C | 100 | 1.29 | 1.86 | 2.57 | 3.27 | 4.46 | 5.85 | 5.09 | 6.83 | 8.84 |
110 | 1.56 | 2.26 | 3.11 | 3.96 | 5.40 | 7.08 | 6.16 | 8.26 | 10.69 | |
120 | 1.86 | 2.68 | 3.70 | 4.71 | 6.42 | 8.43 | 7.33 | 9.84 | 12.72 | |
130 | 2.18 | 3.15 | 4.35 | 5.53 | 7.54 | 9.89 | 8.60 | 11.54 | 14.93 | |
140 | 2.53 | 3.65 | 5.04 | 6.41 | 8.74 | 11.47 | 9.97 | 13.39 | 17.32 | |
150 | 2.91 | 4.19 | 5.79 | 7.36 | 10.04 | 13.17 | 11.45 | 15.37 | 19.88 |
Notes:
- The cumulative shear wall segment length for each side of the building shall be equal to or greater than the tabular shear wall length required. If the required shear wall segment length provided is not one continuous shear wall segment, the total shear wall length required shall be increased by 0.67 feet (8 inches) (203 mm) for each additional shear wall segment making up the total shear wall length on a side.
- The minimum shear wall segment length shall be 2 feet-0 inches (610 mm). Values less than 2 feet-0 inches are shown only for summation of shear wall segments and for interpolation purposes. A grouted cell with vertical reinforcement of the size indicated is required at each end of every shear wall segment.
- Other than incidental utility penetrations, shearwall piers and shearwall segments shall not contain openings with a maximum horizontal or vertical dimension of 5 inches (127 mm) for piers and 12 inches (305 mm) for portions of shearwall segments above and below piers. The total area of openings in any one segment of shearwall shall not exceed 144 square inches (92 903 mm2).
- Required shearwall lengths normal (perpendicular) to the ridge are per lineal foot of building length. Multiply tabular values by building length distance between adjacent shear walls perpendicular to the ridge if interior shear walls are used for total shear wall length required.
- Shear wall lengths are based on shear wall segment heights of 80 inches (2032 mm) (height from the floor to the top of the highest opening adjacent to the shear segment—corners and openings as permitted by Note 3 of this table are not considered for the purpose of this measurement). For shear segment heights other than 80 inches (2032 mm), multiply tabular length values as follows:
Segment Height (inches) Length Multiplier 88 1.09 96 1.19 104 1.28 112 1.37
EXP | Vasd AS DETERMINED IN ACCORDANCE WITH SECTION R301.2.1.3 |
TOP STORY | 1ST STORY OF 2 STORY OR 2ND STORY OF 3 STORY | 1ST STORY OF 3 STORY | ||||||
BUILDING WIDTH | BUILDING WIDTH | BUILDING WIDTH | ||||||||
24 | 32 | 40 | 24 | 32 | 40 | 24 | 32 | 40 | ||
B | 100 | 1.66 | 2.45 | 3.40 | 3.55 | 4.92 | 6.49 | 5.18 | 7.13 | 9.36 |
110 | 2.01 | 2.96 | 4.11 | 4.30 | 5.96 | 7.86 | 6.27 | 8.63 | 11.32 | |
120 | 2.39 | 3.52 | 4.89 | 5.12 | 7.09 | 9.35 | 7.46 | 10.27 | 13.47 | |
130 | 2.81 | 4.13 | 5.74 | 6.00 | 8.32 | 10.97 | 8.76 | 12.05 | 15.81 | |
140 | 3.26 | 4.79 | 6.66 | 6.96 | 9.65 | 12.73 | 10.15 | 13.98 | 18.34 | |
150 | 3.74 | 5.50 | 7.64 | 7.99 | 11.08 | 14.61 | 11.66 | 16.05 | 21.05 | |
C | 100 | 2.00 | 2.99 | 4.21 | 4.73 | 6.62 | 8.82 | 7.22 | 9.92 | 12.97 |
110 | 2.42 | 3.62 | 5.10 | 5.72 | 8.01 | 10.67 | 8.74 | 12.00 | 15.70 | |
120 | 2.88 | 4.30 | 6.07 | 6.81 | 9.53 | 12.70 | 10.40 | 14.28 | 18.68 | |
130 | 3.37 | 5.05 | 7.12 | 7.99 | 11.19 | 14.90 | 12.20 | 16.76 | 21.92 | |
140 | 3.91 | 5.86 | 8.26 | 9.27 | 12.98 | 17.28 | 14.15 | 19.43 | 25.43 | |
150 | 4.49 | 6.73 | 9.48 | 10.64 | 14.90 | 19.84 | 16.25 | 22.31 | 29.19 |
EXP | Vasd AS DETERMINED IN ACCORDANCE WITH SECTION R301.2.1.3 | TOP STORY | 1ST STORY OF 2 STORY OR 2ND STORY OF 3 STORY | 1ST STORY OF 3 STORY | ||||||
BUILDING WIDTH | BUILDING WIDTH | BUILDING WIDTH | ||||||||
24 | 32 | 40 | 24 | 32 | 40 | 24 | 32 | 40 | ||
B | 100 | 1.12 | 1.65 | 2.29 | 2.39 | 3.31 | 4.37 | 3.49 | 4.80 | 6.30 |
110 | 1.35 | 1.99 | 2.77 | 2.89 | 4.01 | 5.29 | 4.22 | 5.81 | 7.62 | |
120 | 1.61 | 2.37 | 3.29 | 3.44 | 4.77 | 6.29 | 5.02 | 6.91 | 9.07 | |
130 | 1.89 | 2.78 | 3.86 | 4.04 | 5.60 | 7.39 | 5.89 | 8.11 | 10.64 | |
140 | 2.19 | 3.23 | 4.48 | 4.69 | 6.50 | 8.57 | 6.84 | 9.41 | 12.34 | |
150 | 2.52 | 3.71 | 5.14 | 5.38 | 7.46 | 9.83 | 7.85 | 10.80 | 14.17 | |
C | 100 | 1.34 | 2.01 | 2.84 | 3.18 | 4.46 | 5.93 | 4.86 | 6.67 | 8.73 |
110 | 1.63 | 2.44 | 3.43 | 3.85 | 5.39 | 7.18 | 5.88 | 8.08 | 10.57 | |
120 | 1.94 | 2.90 | 4.08 | 4.58 | 6.42 | 8.55 | 7.00 | 9.61 | 12.57 | |
130 | 2.27 | 3.40 | 4.79 | 5.38 | 7.53 | 10.03 | 8.21 | 11.28 | 14.76 | |
140 | 2.63 | 3.94 | 5.56 | 6.24 | 8.74 | 11.63 | 9.53 | 13.08 | 17.12 | |
150 | 3.02 | 4.53 | 6.38 | 7.16 | 10.03 | 13.35 | 10.94 | 15.02 | 19.65 |
Notes:
- The cumulative shear wall segment length for each side of the building shall be equal to or greater than the tabular shear wall length required. If the required shear wall segment length provided is not one continuous shear wall segment, the total shear wall length required shall be increased by 0.67 feet (8 inches) (203 mm) for each additional shear wall segment making up the total shear wall length on a side.
- The minimum shear wall segment length shall be 2 feet-0 inches (610 mm). Values less than 2 feet-0 inches (610 mm) are shown only for summation of shear wall segments and for interpolation purposes. A grouted cell with vertical reinforcement of the size indicated is required at each end of every shear wall segment.
- Other than incidental utility penetrations, shearwall piers and shearwall segments shall not contain openings with a maximum horizontal or vertical dimension of 5 inches (127 mm) for piers and 12 inches (305 mm) for portions of shearwall segments above and below piers. The total area of openings in any one segment of shearwall shall not exceed 144 square inches (92 903 mm2).
- Required shearwall lengths normal (perpendicular) to the ridge are per lineal foot of building length. Multiply tabular values by building length distance between adjacent shear walls perpendicular to the ridge if interior shear walls are used for total shear wall length required.
- Shear wall lengths are based on shear wall segment heights of 80 inches (height from the floor to the top of the highest opening adjacent to the shear segment—corners and openings as permitted by Note 3 of this table are not considered for the purpose of this measurement). For shear segment heights other than 80 inches, multiply tabular length values as follows:
Segment Height (inches) Length Multiplier 88 1.0 96 1.19 104 1.28 112 1.37
EXP | Vasd AS DETERMINED IN ACCORDANCE WITH SECTION R301.2.1.3 | TOP STORY | 1ST STORY OF 2 STORY OR 2ND STORY OF 3 STORY | 1ST STORY OF 3 STORY | ||||||
BUILDING WIDTH | BUILDING WIDTH | BUILDING WIDTH | ||||||||
24 | 32 | 40 | 24 | 32 | 40 | 24 | 32 | 40 | ||
B | 100 | 2.11 | 3.24 | 4.64 | 2.11 | 5.72 | 7.73 | 5.77 | 8.17 | 11.00 |
110 | 2.56 | 3.92 | 5.61 | 4.85 | 6.92 | 9.36 | 6.98 | 9.89 | 13.31 | |
120 | 3.05 | 4.67 | 6.68 | 5.77 | 8.23 | 11.13 | 8.31 | 11.77 | 15.85 | |
130 | 3.57 | 5.48 | 7.84 | 6.77 | 9.66 | 13.07 | 9.75 | 13.81 | 18.60 | |
140 | 4.15 | 6.35 | 9.09 | 7.85 | 11.20 | 15.16 | 11.31 | 16.02 | 21.57 | |
150 | 4.76 | 7.29 | 10.43 | 9.01 | 12.86 | 17.40 | 12.98 | 18.39 | 24.76 | |
C | 100 | 2.63 | 4.13 | 6.03 | 5.45 | 7.90 | 10.84 | 7.22 | 9.92 | 12.97 |
110 | 3.18 | 4.99 | 7.30 | 6.60 | 9.56 | 13.12 | 8.74 | 12.00 | 15.70 | |
120 | 3.79 | 5.94 | 8.68 | 7.85 | 11.38 | 15.61 | 10.40 | 14.28 | 18.68 | |
130 | 4.45 | 6.97 | 10.19 | 9.21 | 13.35 | 18.32 | 12.20 | 16.76 | 21.92 | |
140 | 5.16 | 8.09 | 11.82 | 10.68 | 15.48 | 21.25 | 14.15 | 19.43 | 25.43 | |
150 | 5.92 | 9.28 | 13.57 | 12.26 | 17.77 | 24.39 | 16.25 | 22.31 | 29.19 |
EXP | Vasd AS DETERMINED IN ACCORDANCE WITH SECTION R301.2.1.3 | TOP STORY | 1ST STORY OF 2 STORY OR 2ND STORY OF 3 STORY | 1ST STORY OF 3 STORY | ||||||
BUILDING WIDTH | BUILDING WIDTH | BUILDING WIDTH | ||||||||
24 | 32 | 40 | 24 | 32 | 40 | 24 | 32 | 40 | ||
B | 100 | 1.42 | 2.18 | 3.12 | 2.70 | 3.85 | 5.21 | 3.88 | 5.50 | 7.41 |
110 | 1.72 | 2.64 | 3.78 | 3.26 | 4.66 | 6.30 | 4.70 | 6.66 | 8.96 | |
120 | 2.05 | 3.14 | 4.49 | 3.88 | 5.54 | 7.50 | 5.59 | 7.92 | 10.67 | |
130 | 2.41 | 3.69 | 5.27 | 4.56 | 6.50 | 8.80 | 6.56 | 9.30 | 12.52 | |
140 | 2.79 | 4.27 | 6.12 | 5.29 | 7.54 | 10.20 | 7.61 | 10.78 | 14.52 | |
150 | 3.20 | 4.91 | 7.02 | 6.07 | 8.66 | 11.71 | 8.74 | 12.38 | 16.67 | |
C | 100 | 1.77 | 2.78 | 4.06 | 3.67 | 5.32 | 7.30 | 5.38 | 7.59 | 10.18 |
110 | 2.14 | 3.36 | 4.91 | 4.44 | 6.43 | 8.83 | 6.51 | 9.19 | 12.32 | |
120 | 2.55 | 4.00 | 5.85 | 5.28 | 7.66 | 10.51 | 7.75 | 10.93 | 14.66 | |
130 | 2.99 | 4.69 | 6.86 | 6.20 | 8.99 | 12.33 | 9.09 | 12.83 | 17.21 | |
140 | 3.47 | 5.44 | 7.96 | 7.19 | 10.42 | 14.30 | 10.55 | 14.88 | 19.96 | |
150 | 3.98 | 6.25 | 9.13 | 8.26 | 11.96 | 16.42 | 12.11 | 17.09 | 22.91 |
Notes:
- The cumulative shear wall segment length for each side of the building shall be equal to or greater than the tabular shear wall length required. If the required shear wall segment length provided is not one continuous shear wall segment, the total shear wall length required shall be increased by 0.67 feet (8 inches) (203 mm) for each additional shear wall segment making up the total shear wall length on a side.
- The minimum shear wall segment length shall be 2 feet-0 inches (610 mm). Values less than 2 feet-0 (610 mm) inches are shown only for summation of shear wall segments and for interpolation purposes. A grouted cell with vertical reinforcement of the size indicated is required at each end of every shear wall segment.
- Other than incidental utility penetrations, shearwall piers and shearwall segments shall not contain openings with a maximum horizontal or vertical dimension of 5 inches (127 mm) for piers and 12 inches (305 mm) for portions of shearwall segments above and below piers. The total area of openings in any one segment of shearwall shall not exceed 144 square inches (92 903 mm2).
- Required shearwall lengths normal (perpendicular) to the ridge are per lineal foot of building length. Multiply tabular values by building length distance between adjacent shear walls perpendicular to the ridge if interior shear walls are used for total shear wall length required.
- Shear wall lengths are based on shear wall segment heights of 80 inches (2032 mm) (height from the floor to the top of the highest opening adjacent to the shear segment—corners and openings as permitted by Note 3 of this table are not considered for the purpose of this measurement). For shear segment heights other than 80 inches (2032 mm), multiply tabular length values as follows:
Segment Height (inches) Length Multiplier 88 1.09 96 1.19 104 1.28 112 1.37
EXP | Vasd AS DETERMINED IN ACCORDANCE WITH SECTION R301.2.1.3 |
TOP STORY | 1ST STORY OF 2 STORY OR 2ND STORY OF 3 STORY | 1ST STORY OF 3 STORY | ||||||
BUILDING WIDTH | BUILDING WIDTH | BUILDING WIDTH | ||||||||
24 | 32 | 40 | 24 | 32 | 40 | 24 | 32 | 40 | ||
B | 100 | 0.054 | 0.053 | 0.053 | 0.142 | 0.142 | 0.141 | 0.231 | 0.231 | 0.230 |
110 | 0.065 | 0.065 | 0.064 | 0.172 | 0.172 | 0.171 | 0.279 | 0.279 | 0.278 | |
120 | 0.077 | 0.077 | 0.076 | 0.205 | 0.204 | 0.204 | 0.333 | 0.332 | 0.331 | |
130 | 0.091 | 0.090 | 0.089 | 0.240 | 0.240 | 0.239 | 0.390 | 0.390 | 0.389 | |
140 | 0.105 | 0.104 | 0.103 | 0.279 | 0.278 | 0.277 | 0.453 | 0.452 | 0.451 | |
150 | 0.121 | 0.120 | 0.119 | 0.320 | 0.319 | 0.318 | 0.520 | 0.519 | 0.518 | |
C | 100 | 0.075 | 0.075 | 0.074 | 0.199 | 0.199 | 0.198 | 0.324 | 0.323 | 0.322 |
110 | 0.091 | 0.090 | 0.089 | 0.241 | 0.241 | 0.240 | 0.392 | 0.391 | 0.390 | |
120 | 0.108 | 0.108 | 0.106 | 0.287 | 0.287 | 0.285 | 0.466 | 0.466 | 0.464 | |
130 | 0.127 | 0.126 | 0.125 | 0.337 | 0.336 | 0.335 | 0.547 | 0.546 | 0.545 | |
140 | 0.147 | 0.147 | 0.145 | 0.391 | 0.390 | 0.388 | 0.635 | 0.634 | 0.632 | |
150 | 0.169 | 0.168 | 0.166 | 0.449 | 0.448 | 0.446 | 0.729 | 0.728 | 0.726 |
EXP | Vasd AS DETERMINED IN ACCORDANCE WITH SECTION R301.2.1.3 | TOP STORY | 1ST STORY OF 2 STORY OR 2ND STORY OF 3 STORY | 1ST STORY OF 3 STORY | ||||||
BUILDING WIDTH | BUILDING WIDTH | BUILDING WIDTH | ||||||||
24 | 32 | 40 | 24 | 32 | 40 | 24 | 32 | 40 | ||
B | 100 | 0.036 | 0.036 | 0.035 | 0.096 | 0.096 | 0.095 | 0.155 | 0.155 | 0.155 |
110 | 0.044 | 0.043 | 0.043 | 0.116 | 0.116 | 0.115 | 0.188 | 0.188 | 0.187 | |
120 | 0.052 | 0.052 | 0.051 | 0.138 | 0.138 | 0.137 | 0.224 | 0.224 | 0.223 | |
130 | 0.061 | 0.061 | 0.060 | 0.162 | 0.162 | 0.161 | 0.263 | 0.262 | 0.262 | |
140 | 0.071 | 0.070 | 0.070 | 0.188 | 0.187 | 0.186 | 0.305 | 0.304 | 0.303 | |
150 | 0.081 | 0.081 | 0.080 | 0.215 | 0.215 | 0.214 | 0.350 | 0.349 | 0.348 | |
C | 100 | 0.051 | 0.050 | 0.050 | 0.134 | 0.134 | 0.133 | 0.218 | 0.218 | 0.217 |
110 | 0.061 | 0.061 | 0.060 | 0.162 | 0.162 | 0.161 | 0.264 | 0.263 | 0.263 | |
120 | 0.073 | 0.072 | 0.072 | 0.193 | 0.193 | 0.192 | 0.314 | 0.313 | 0.313 | |
130 | 0.086 | 0.085 | 0.084 | 0.227 | 0.226 | 0.225 | 0.368 | 0.368 | 0.367 | |
140 | 0.099 | 0.099 | 0.097 | 0.263 | 0.263 | 0.261 | 0.427 | 0.427 | 0.425 | |
150 | 0.114 | 0.113 | 0.112 | 0.302 | 0.301 | 0.300 | 0.490 | 0.490 | 0.488 |
Notes:
- The cumulative shear wall segment length for each side of the building shall be equal to or greater than the tabular shear wall length required. If the required shear wall segment length provided is not one continuous shear wall segment, the total shear wall length required shall be increased by 0.67 feet (8 inches) (203 mm) for each additional shear wall segment making up the total shear wall length on a side.
- The minimum shear wall segment length shall be 2 feet-0 inches (610 mm). Values less than 2 feet-0 inches (610 mm) are shown only for summation of shear wall segments and for interpolation purposes. A grouted cell with vertical reinforcement of the size indicated is required at each end of every shear wall segment.
- Other than incidental utility penetrations, shearwall piers and shearwall segments shall not contain openings with a maximum horizontal or vertical dimension of 5 inches (127 mm) for piers and 12 inches (305 mm) for portions of shearwall segments above and below piers. The total area of openings in any one segment of shearwall shall not exceed 144 square inches (92 903 mm2).
- Required shearwall lengths normal (perpendicular) to the ridge are per lineal foot of building length. Multiply tabular values by building length distance between adjacent shear walls perpendicular to the ridge if interior shear walls are used for total shear wall length required.
- Shear wall lengths are based on shear wall segment heights of 80 inches (2032 mm) (height from the floor to the top of the highest opening adjacent to the shear segment—corners and openings as permitted by Note 3 of this table are not considered for the purpose of this measurement). For shear segment heights other than 80 inches (2032 mm), multiply tabular length values as follows:
Segment Height (inches) Length Multiplier 88 1.09 96 1.19 104 1.28 112 1.37
EXP | Vasd AS DETERMINED IN ACCORDANCE WITH SECTION R301.2.1.3 |
TOP STORY | 1ST STORY OF 2 STORY OR 2ND STORY OF 3 STORY | 1ST STORY OF 3 STORY | ||||||
BUILDING WIDTH | BUILDING WIDTH | BUILDING WIDTH | ||||||||
24 | 32 | 40 | 24 | 32 | 40 | 24 | 32 | 40 | ||
B | 100 | 0.088 | 0.102 | 0.117 | 0.166 | 0.180 | 0.195 | 0.243 | 0.257 | 0.272 |
110 | 0.107 | 0.124 | 0.142 | 0.201 | 0.217 | 0.236 | 0.294 | 0.311 | 0.329 | |
120 | 0.127 | 0.147 | 0.169 | 0.239 | 0.259 | 0.280 | 0.350 | 0.371 | 0.392 | |
130 | 0.149 | 0.173 | 0.198 | 0.280 | 0.304 | 0.329 | 0.411 | 0.435 | 0.460 | |
140 | 0.173 | 0.200 | 0.230 | 0.325 | 0.352 | 0.382 | 0.477 | 0.504 | 0.534 | |
150 | 0.199 | 0.230 | 0.264 | 0.373 | 0.404 | 0.438 | 0.548 | 0.579 | 0.613 | |
C | 100 | 0.124 | 0.143 | 0.164 | 0.232 | 0.252 | 0.273 | 0.341 | 0.361 | 0.382 |
110 | 0.150 | 0.173 | 0.199 | 0.281 | 0.305 | 0.330 | 0.413 | 0.437 | 0.462 | |
120 | 0.178 | 0.206 | 0.237 | 0.335 | 0.363 | 0.393 | 0.491 | 0.519 | 0.550 | |
130 | 0.209 | 0.242 | 0.278 | 0.393 | 0.426 | 0.461 | 0.577 | 0.610 | 0.645 | |
140 | 0.242 | 0.281 | 0.322 | 0.456 | 0.494 | 0.535 | 0.669 | 0.707 | 0.748 | |
150 | 0.278 | 0.322 | 0.370 | 0.523 | 0.567 | 0.614 | 0.768 | 0.812 | 0.859 |
EXP | Vasd AS DETERMINED IN ACCORDANCE WITH SECTION R301.2.1.3 |
TOP STORY | 1ST STORY OF 2 STORY OR 2ND STORY OF 3 STORY | 1ST STORY OF 3 STORY | ||||||
BUILDING WIDTH | BUILDING WIDTH | BUILDING WIDTH | ||||||||
24 | 32 | 40 | 24 | 32 | 40 | 24 | 32 | 40 | ||
B | 100 | 0.059 | 0.069 | 0.079 | 0.112 | 0.121 | 0.131 | 0.164 | 0.173 | 0.183 |
110 | 0.072 | 0.083 | 0.095 | 0.135 | 0.146 | 0.159 | 0.198 | 0.210 | 0.222 | |
120 | 0.086 | 0.099 | 0.114 | 0.161 | 0.174 | 0.189 | 0.236 | 0.249 | 0.264 | |
130 | 0.100 | 0.116 | 0.133 | 0.189 | 0.204 | 0.222 | 0.277 | 0.293 | 0.310 | |
140 | 0.116 | 0.135 | 0.155 | 0.219 | 0.237 | 0.257 | 0.321 | 0.339 | 0.359 | |
150 | 0.134 | 0.155 | 0.177 | 0.251 | 0.272 | 0.295 | 0.369 | 0.390 | 0.412 | |
C | 100 | 0.083 | 0.096 | 0.111 | 0.156 | 0.170 | 0.184 | 0.230 | 0.243 | 0.257 |
110 | 0.101 | 0.117 | 0.134 | 0.189 | 0.205 | 0.222 | 0.278 | 0.294 | 0.311 | |
120 | 0.120 | 0.139 | 0.159 | 0.225 | 0.244 | 0.265 | 0.331 | 0.350 | 0.370 | |
130 | 0.141 | 0.163 | 0.187 | 0.264 | 0.287 | 0.311 | 0.388 | 0.410 | 0.434 | |
140 | 0.163 | 0.189 | 0.217 | 0.307 | 0.333 | 0.360 | 0.450 | 0.476 | 0.504 | |
150 | 0.187 | 0.217 | 0.249 | 0.352 | 0.382 | 0.413 | 0.517 | 0.546 | 0.578 |
Notes:
- The cumulative shear wall segment length for each side of the building shall be equal to or greater than the tabular shear wall length required. If the required shear wall segment length provided is not one continuous shear wall segment, the total shear wall length required shall be increased by 0.67 feet (8 inches) (203 mm) for each additional shear wall segment making up the total shear wall length on a side.
- The minimum shear wall segment length shall be 2 feet-0 inches (610 mm). Values less than 2 feet-0 inches (610 mm) are shown only for summation of shear wall segments and for interpolation purposes. A grouted cell with vertical reinforcement of the size indicated is required at each end of every shear wall segment.
- Other than incidental utility penetrations, shearwall piers and shearwall segments shall not contain openings with a maximum horizontal or vertical dimension of 5 inches (127 mm) for piers and 12 inches (305 mm) for portions of shearwall segments above and below piers. The total area of openings in any one segment of shearwall shall not exceed 144 square inches (92 903 mm2).
- Required shearwall lengths normal (perpendicular) to the ridge are per lineal foot of building length. Multiply tabular values by building length distance between adjacent shear walls perpendicular to the ridge if interior shear walls are used for total shear wall length required.
- Shear wall lengths are based on shear wall segment heights of 80 inches (2032 mm) (height from the floor to the top of the highest opening adjacent to the shear segment—corners and openings as permitted by Note 3 of this table are not considered for the purpose of this measurement). For shear segment heights other than 80 inches (2032 mm), multiply tabular length values as follows:
Segment Height (inches) Length Multiplier 88 1.09 96 1.19 104 1.28 112 1.37
EXP | Vasd AS DETERMINED IN ACCORDANCE WITH SECTION R301.2.1.3 |
TOP STORY | 1ST STORY OF 2 STORY OR 2ND STORY OF 3 STORY |
1ST STORY OF 3 STORY | ||||||
BUILDING WIDTH | BUILDING WIDTH | BUILDING WIDTH | ||||||||
24 | 32 | 40 | 24 | 32 | 40 | 24 | 32 | 40 | ||
B | 100 | 0.118 | 0.142 | 0.168 | 0.196 | 0.220 | 0.246 | 0.273 | 0.297 | 0.323 |
110 | 0.143 | 0.172 | 0.204 | 0.237 | 0.266 | 0.297 | 0.331 | 0.360 | 0.391 | |
120 | 0.170 | 0.205 | 0.242 | 0.282 | 0.317 | 0.354 | 0.393 | 0.428 | 0.466 | |
130 | 0.200 | 0.241 | 0.284 | 0.331 | 0.372 | 0.415 | 0.462 | 0.503 | 0.546 | |
140 | 0.232 | 0.279 | 0.330 | 0.384 | 0.431 | 0.482 | 0.536 | 0.583 | 0.634 | |
150 | 0.266 | 0.320 | 0.378 | 0.440 | 0.495 | 0.553 | 0.615 | 0.669 | 0.727 | |
C | 100 | 0.166 | 0.200 | 0.236 | 0.274 | 0.308 | 0.345 | 0.383 | 0.417 | 0.453 |
110 | 0.200 | 0.241 | 0.285 | 0.332 | 0.373 | 0.417 | 0.464 | 0.505 | 0.549 | |
120 | 0.239 | 0.287 | 0.340 | 0.395 | 0.444 | 0.496 | 0.552 | 0.600 | 0.653 | |
130 | 0.280 | 0.337 | 0.399 | 0.464 | 0.521 | 0.582 | 0.647 | 0.705 | 0.766 | |
140 | 0.325 | 0.391 | 0.462 | 0.538 | 0.604 | 0.675 | 0.751 | 0.817 | 0.888 | |
150 | 0.373 | 0.449 | 0.531 | 0.617 | 0.694 | 0.775 | 0.862 | 0.938 | 1.020 |
EXP | Vasd AS DETERMINED IN ACCORDANCE WITH SECTION R301.2.1.3 |
TOP STORY | 1ST STORY OF 2 STORY OR 2ND STORY OF 3 STORY | 1ST STORY OF 3 STORY | ||||||
BUILDING WIDTH | BUILDING WIDTH | BUILDING WIDTH | ||||||||
24 | 32 | 40 | 24 | 32 | 40 | 24 | 32 | 40 | ||
B | 100 | 0.080 | 0.096 | 0.113 | 0.132 | 0.148 | 0.165 | 0.184 | 0.200 | 0.218 |
110 | 0.096 | 0.116 | 0.137 | 0.159 | 0.179 | 0.200 | 0.223 | 0.242 | 0.263 | |
120 | 0.115 | 0.138 | 0.163 | 0.190 | 0.213 | 0.238 | 0.265 | 0.288 | 0.313 | |
130 | 0.134 | 0.162 | 0.191 | 0.223 | 0.250 | 0.280 | 0.311 | 0.338 | 0.368 | |
140 | 0.156 | 0.188 | 0.222 | 0.258 | 0.290 | 0.324 | 0.361 | 0.392 | 0.427 | |
150 | 0.179 | 0.216 | 0.255 | 0.296 | 0.333 | 0.372 | 0.414 | 0.450 | 0.490 | |
C | 100 | 0.111 | 0.134 | 0.159 | 0.185 | 0.208 | 0.232 | 0.258 | 0.281 | 0.305 |
110 | 0.135 | 0.163 | 0.192 | 0.223 | 0.251 | 0.281 | 0.312 | 0.340 | 0.369 | |
120 | 0.161 | 0.193 | 0.229 | 0.266 | 0.299 | 0.334 | 0.371 | 0.404 | 0.439 | |
130 | 0.188 | 0.227 | 0.268 | 0.312 | 0.351 | 0.392 | 0.436 | 0.474 | 0.516 | |
140 | 0.219 | 0.263 | 0.311 | 0.362 | 0.407 | 0.455 | 0.505 | 0.550 | 0.598 | |
150 | 0.251 | 0.302 | 0.357 | 0.416 | 0.467 | 0.522 | 0.580 | 0.632 | 0.687 |
Notes:
- The cumulative shear wall segment length for each side of the building shall be equal to or greater than the tabular shear wall length required. If the required shear wall segment length provided is not one continuous shear wall segment, the total shear wall length required shall be increased by 0.67 feet (8 inches) (203 mm) for each additional shear wall segment making up the total shear wall length on a side.
- The minimum shear wall segment length shall be 2 feet-0 inches (610 mm). Values less than 2 feet-0 inches (610 mm) are shown only for summation of shear wall segments and for interpolation purposes. A grouted cell with vertical reinforcement of the size indicated is required at each end of every shear wall segment.
- Other than incidental utility penetrations, shear wall piers and shear wall segments shall not contain openings with a maximum horizontal or vertical dimension of 5 inches (127 mm) for piers and 12 inches (305 mm) for portions of shear wall segments above and below piers. The total area of openings in any one segment of shear wall shall not exceed 144 square inches (92 903 mm2).
- Required shear wall lengths normal (perpendicular) to the ridge are per lineal foot of building length. Multiply tabular values by building length distance between adjacent shear walls perpendicular to the ridge if interior shear walls are used for total shear wall length required.
- Shear wall lengths are based on shear wall segment heights of 80 inches (2032 mm) (height from the floor to the top of the highest opening adjacent to the shear segment—corners and openings as permitted by Note 3 of this table are not considered for the purpose of this measurement). For shear segment heights other than 80 inches (2032 mm), multiply tabular length values as follows:
Segment Height (inches) Length Multiplier 88 1.09 96 1.19 104 1.28 112 1.37
EXP | Vasd AS DETERMINED IN ACCORDANCE WITH SECTION R301.2.1.3 |
TOP STORY | 1ST STORY OF 2 STORY OR 2ND STORY OF 3 STORY |
1ST STORY OF 3 STORY | ||||||
BUILDING WIDTH | BUILDING WIDTH | BUILDING WIDTH | ||||||||
24 | 32 | 40 | 24 | 32 | 40 | 24 | 32 | 40 | ||
B | 100 | 2.32 | 3.31 | 4.51 | 5.29 | 7.15 | 9.31 | 7.77 | 10.45 | 13.55 |
110 | 2.81 | 4.01 | 5.46 | 6.40 | 8.65 | 11.27 | 9.40 | 12.65 | 16.39 | |
120 | 3.35 | 4.77 | 6.50 | 7.61 | 10.30 | 13.41 | 11.19 | 15.05 | 19.51 | |
130 | 3.93 | 5.59 | 7.63 | 8.94 | 12.09 | 15.74 | 13.13 | 17.67 | 22.90 | |
140 | 4.55 | 6.49 | 8.84 | 10.36 | 14.02 | 18.26 | 15.23 | 20.49 | 26.56 | |
150 | 5.23 | 7.45 | 10.15 | 11.90 | 16.09 | 20.96 | 17.48 | 23.52 | 30.48 | |
C | 100 | 2.75 | 3.98 | 5.49 | 6.98 | 9.52 | 12.49 | 10.85 | 14.57 | 18.85 |
110 | 3.33 | 4.81 | 6.64 | 8.45 | 11.52 | 15.11 | 13.13 | 17.63 | 22.81 | |
120 | 3.97 | 5.73 | 7.90 | 10.05 | 13.70 | 17.98 | 15.63 | 20.98 | 27.14 | |
130 | 4.66 | 6.72 | 9.27 | 11.80 | 16.08 | 21.10 | 18.34 | 24.63 | 31.86 | |
140 | 5.40 | 7.79 | 10.75 | 13.68 | 18.65 | 24.47 | 21.27 | 28.56 | 36.95 | |
150 | 6.20 | 8.95 | 12.34 | 15.71 | 21.41 | 28.10 | 24.42 | 32.79 | 42.41 |
Notes:
- The cumulative shear wall segment length for each side of the building shall be equal to or greater than the tabular shear wall length required. If the required shear wall segment length provided is not continuous the total shear wall length required shall be increased by 8 inches (203 mm) for each additional shear wall segment on a side.
- Minimum shear wall segment length shall be 2 feet-0 inches (610 mm). A grouted cell with reinforcing steel shall be provided at each end of every shear wall segment. A minimum length of 24 inches (610 mm) of solid wall segment, extending the full height of each wall, shall be provided at exterior corners of exterior walls. A fully grouted cell with reinforcing steel shall be provided at each end of every shear wall segment.
- Portions of walls with openings shall not be considered part of the shear wall length.
- Required shearwall lengths perpendicular to the ridge are per lineal foot of building length. Multiply tabular values by building length for total shear wall length required.
- Shearwall lengths for No. 4 reinforcement are based on shearwall segment height of 80 inches (2032 mm) and shearwall segment length of 24 inches (610 mm).
- Shearwall lengths for No. 5 reinforcement are based on shearwall segment height of 96 inches (2438 mm) and shearwall segment length of 24 inches (610 mm).
EXP | Vasd AS DETERMINED IN ACCORDANCE WITH SECTION R301.2.1.3 |
TOP STORY | 1ST STORY OF 2 STORY OR 2ND STORY OF 3 STORY | 1ST STORY OF 3 STORY | ||||||
BUILDING WIDTH | BUILDING WIDTH | BUILDING WIDTH | ||||||||
24 | 32 | 40 | 24 | 32 | 40 | 24 | 32 | 40 | ||
B | 100 | 1.59 | 2.26 | 3.08 | 3.61 | 4.88 | 6.36 | 5.30 | 7.14 | 9.25 |
110 | 1.92 | 2.73 | 3.73 | 4.37 | 5.91 | 7.69 | 6.42 | 8.63 | 11.19 | |
120 | 2.28 | 3.25 | 4.44 | 5.20 | 7.03 | 9.16 | 7.64 | 10.28 | 13.32 | |
130 | 2.68 | 3.82 | 5.21 | 6.10 | 8.25 | 10.75 | 8.96 | 12.06 | 15.63 | |
140 | 3.11 | 4.43 | 6.04 | 7.07 | 9.57 | 12.46 | 10.40 | 13.99 | 18.13 | |
150 | 3.57 | 5.08 | 6.93 | 8.12 | 10.99 | 14.31 | 11.93 | 16.06 | 20.81 | |
C | 100 | 1.88 | 2.71 | 3.75 | 4.77 | 6.50 | 8.52 | 7.41 | 9.95 | 12.87 |
110 | 2.28 | 3.28 | 4.53 | 5.77 | 7.86 | 10.31 | 8.96 | 12.04 | 15.57 | |
120 | 2.71 | 3.91 | 5.39 | 6.86 | 9.36 | 12.28 | 10.67 | 14.32 | 18.53 | |
130 | 3.18 | 4.59 | 6.33 | 8.05 | 10.98 | 14.41 | 12.52 | 16.81 | 21.75 | |
140 | 3.69 | 5.32 | 7.34 | 9.34 | 12.73 | 16.71 | 14.52 | 19.50 | 25.22 | |
150 | 4.23 | 6.11 | 8.43 | 10.72 | 14.62 | 19.18 | 16.67 | 22.38 | 28.95 |
Notes:
- The cumulative shear wall segment length for each side of the building shall be equal to or greater than the tabular shear wall length required. If the required shear wall segment length provided is not continuous the total shear wall length required shall be increased by 8 inches (203 mm) for each additional shear wall segment on a side.
- Minimum shear wall segment length shall be 2 feet-0 inches (610 mm). A grouted cell with reinforcing steel shall be provided at each end of every shear wall segment. A minimum length of 24 inches (610 mm) of solid wall segment, extending the full height of each wall, shall be provided at exterior corners of exterior walls. A fully grouted cell with reinforcing steel shall be provided at each end of every shear wall segment.
- Portions of walls with openings shall not be considered part of the shear wall length.
- Required shearwall lengths perpendicular to the ridge are per lineal foot of building length. Multiply tabular values by building length for total shear wall length required.
- Shearwall lengths for No. 4 reinforcement are based on shearwall segment height of 80 inches (2032 mm) and shearwall segment length of 24 inches (610 mm).
- Shearwall lengths for No. 5 reinforcement are based on shearwall segment height of 96 inches (2438 mm) and shearwall segment length of 24 inches (610 mm).
EXP | Vasd AS DETERMINED IN ACCORDANCE WITH SECTION R301.2.1.3 |
TOP STORY | 1ST STORY OF 2 STORY OR 2ND STORY OF 3 STORY |
1ST STORY OF 3 STORY | ||||||
BUILDING WIDTH | BUILDING WIDTH | BUILDING WIDTH | ||||||||
24 | 32 | 40 | 24 | 32 | 40 | 24 | 32 | 40 | ||
B | 100 | 2.39 | 3.51 | 4.88 | 5.10 | 7.07 | 9.32 | 7.44 | 10.24 | 13.44 |
110 | 2.89 | 4.25 | 5.90 | 6.17 | 8.55 | 11.28 | 9.00 | 12.39 | 16.26 | |
120 | 3.43 | 5.06 | 7.02 | 7.35 | 10.18 | 13.43 | 10.71 | 14.75 | 19.35 | |
130 | 4.03 | 5.94 | 8.24 | 8.62 | 11.95 | 15.76 | 12.57 | 17.31 | 22.71 | |
140 | 4.67 | 6.89 | 9.56 | 10.00 | 13.86 | 18.28 | 14.58 | 20.08 | 26.34 | |
150 | 5.37 | 7.90 | 10.98 | 11.48 | 15.91 | 20.98 | 16.74 | 23.05 | 30.23 | |
C | 100 | 2.87 | 4.29 | 6.05 | 6.79 | 9.51 | 12.66 | 10.37 | 14.24 | 18.63 |
110 | 3.47 | 5.19 | 7.32 | 8.22 | 11.51 | 15.32 | 12.55 | 17.23 | 22.54 | |
120 | 4.13 | 6.18 | 8.71 | 9.78 | 13.69 | 18.23 | 14.93 | 20.51 | 26.83 | |
130 | 4.85 | 7.26 | 10.23 | 11.48 | 16.07 | 21.40 | 17.53 | 24.06 | 31.49 | |
140 | 5.62 | 8.41 | 11.86 | 13.31 | 18.64 | 24.82 | 20.33 | 27.91 | 36.52 | |
150 | 6.45 | 9.66 | 13.62 | 15.28 | 21.39 | 28.49 | 23.33 | 32.04 | 41.92 |
Notes:
- The cumulative shear wall segment length for each side of the building shall be equal to or greater than the tabular shear wall length required. If the required shear wall segment length provided is not continuous the total shear wall length required shall be increased by 8 inches (203 mm) for each additional shear wall segment on a side.
- Minimum shear wall segment length shall be 2 feet-0 inches (610 mm). A grouted cell with reinforcing steel shall be provided at each end of every shear wall segment. A minimum length of 24 inches (610 mm) of solid wall segment, extending the full height of each wall, shall be provided at exterior corners of exterior walls. A fully grouted cell with reinforcing steel shall be provided at each end of every shear wall segment.
- Portions of walls with openings shall not be considered part of the shear wall length.
- Required shearwall lengths perpendicular to the ridge are per lineal foot of building length. Multiply tabular values by building length for total shear wall length required.
- Shearwall lengths for No. 4 reinforcement are based on shearwall segment height of 80 inches (2032 mm) and shearwall segment length of 24 inches (610 mm).
- Shearwall lengths for No. 5 reinforcement are based on shearwall segment height of 96 inches (2438 mm) and shearwall segment length of 24 inches (610 mm).
EXP | Vasd AS DETERMINED IN ACCORDANCE WITH SECTION R301.2.1.3 |
TOP STORY | 1ST STORY OF 2 STORY OR 2ND STORY OF 3 STORY | 1ST STORY OF 3 STORY | ||||||
BUILDING WIDTH | BUILDING WIDTH | BUILDING WIDTH | ||||||||
24 | 32 | 40 | 24 | 32 | 40 | 24 | 32 | 40 | ||
B | 100 | 1.63 | 2.40 | 3.33 | 3.48 | 4.83 | 6.37 | 5.08 | 6.99 | 9.17 |
110 | 1.97 | 2.90 | 4.03 | 4.21 | 5.84 | 7.70 | 6.15 | 8.46 | 11.10 | |
120 | 2.34 | 3.45 | 4.80 | 5.02 | 6.95 | 9.17 | 7.31 | 10.07 | 13.21 | |
130 | 2.75 | 4.05 | 5.63 | 5.89 | 8.16 | 10.76 | 8.58 | 11.82 | 15.50 | |
140 | 3.19 | 4.70 | 6.53 | 6.83 | 9.46 | 12.48 | 9.96 | 13.71 | 17.98 | |
150 | 3.66 | 5.40 | 7.49 | 7.84 | 10.86 | 14.32 | 11.43 | 15.73 | 20.64 | |
C | 100 | 1.96 | 2.93 | 4.13 | 4.64 | 6.49 | 8.64 | 7.08 | 9.72 | 12.72 |
110 | 2.37 | 3.55 | 5.00 | 5.61 | 7.85 | 10.46 | 8.57 | 11.76 | 15.39 | |
120 | 2.82 | 4.22 | 5.95 | 6.68 | 9.35 | 12.45 | 10.19 | 14.00 | 18.31 | |
130 | 3.31 | 4.95 | 6.98 | 7.84 | 10.97 | 14.61 | 11.96 | 16.43 | 21.49 | |
140 | 3.84 | 5.74 | 8.10 | 9.09 | 12.72 | 16.94 | 13.88 | 19.05 | 24.93 | |
150 | 4.41 | 6.59 | 9.29 | 10.43 | 14.61 | 19.45 | 15.93 | 21.87 | 28.62 |
Notes:
- The cumulative shear wall segment length for each side of the building shall be equal to or greater than the tabular shear wall length required. If the required shear wall segment length provided is not continuous the total shear wall length required shall be increased by 8 inches (610 mm) for each additional shear wall segment on a side.
- Minimum shear wall segment length shall be 2 feet-0 inches (610 mm). A grouted cell with reinforcing steel shall be provided at each end of every shear wall segment. A minimum length of 24 inches (610 mm) of solid wall segment, extending the full height of each wall, shall be provided at exterior corners of exterior walls. A fully grouted cell with reinforcing steel shall be provided at each end of every shear wall segment.
- Portions of walls with openings shall not be considered part of the shear wall length.
- Required shearwall lengths perpendicular to the ridge are per lineal foot of building length. Multiply tabular values by building length for total shear wall length required.
- Shearwall lengths for No. 4 reinforcement are based on shearwall segment height of 80 inches (2032 mm) and shearwall segment length of 24 inches (610 mm).
- Shearwall lengths for No. 5 reinforcement are based on shearwall segment height of 96 inches (2438 mm) and shearwall segment length of 24 inches (610 mm).
EXP | Vasd AS DETERMINED IN ACCORDANCE WITH SECTION R301.2.1.3 |
TOP STORY | 1ST STORY OF 2 STORY OR 2ND STORY OF 3 STORY | 1ST STORY OF 3 STORY | ||||||
BUILDING WIDTH | BUILDING WIDTH | BUILDING WIDTH | ||||||||
24 | 32 | 40 | 24 | 32 | 40 | 24 | 32 | 40 | ||
B | 100 | 3.04 | 4.65 | 6.66 | 3.04 | 8.21 | 11.11 | 8.28 | 11.74 | 15.80 |
110 | 3.68 | 5.63 | 8.06 | 6.96 | 9.93 | 13.44 | 10.02 | 14.20 | 19.12 | |
120 | 4.37 | 6.70 | 9.59 | 8.29 | 11.82 | 15.99 | 11.93 | 16.90 | 22.76 | |
130 | 5.13 | 7.86 | 11.25 | 9.72 | 13.87 | 18.77 | 14.00 | 19.84 | 26.71 | |
140 | 5.95 | 9.12 | 13.05 | 11.28 | 16.09 | 21.77 | 16.24 | 23.01 | 30.97 | |
150 | 6.83 | 10.47 | 14.98 | 12.95 | 18.47 | 24.99 | 18.64 | 26.41 | 35.56 | |
C | 100 | 3.78 | 5.93 | 8.66 | 7.83 | 11.34 | 15.57 | 10.37 | 14.24 | 18.63 |
110 | 4.57 | 7.17 | 10.48 | 9.47 | 13.73 | 18.84 | 12.55 | 17.23 | 22.54 | |
120 | 5.44 | 8.53 | 12.47 | 11.27 | 16.34 | 22.42 | 14.93 | 20.51 | 26.83 | |
130 | 6.39 | 10.01 | 14.64 | 13.23 | 19.17 | 26.31 | 17.53 | 24.06 | 31.49 | |
140 | 7.41 | 11.61 | 16.98 | 15.34 | 22.24 | 30.52 | 20.33 | 27.91 | 36.52 | |
150 | 8.50 | 13.33 | 19.49 | 17.61 | 25.53 | 35.03 | 23.33 | 32.04 | 41.92 |
Notes:
- The cumulative shear wall segment length for each side of the building shall be equal to or greater than the tabular shear wall length required. If the required shear wall segment length provided is not continuous the total shear wall length required shall be increased by 8 inches (203 mm) for each additional shear wall segment on a side.
- Minimum shear wall segment length shall be 2 feet-0 inches (610 mm). A grouted cell with reinforcing steel shall be provided at each end of every shear wall segment. A minimum length of 24 inches (610 mm) of solid wall segment, extending the full height of each wall, shall be provided at exterior corners of exterior walls. A fully grouted cell with reinforcing steel shall be provided at each end of every shear wall segment.
- Portions of walls with openings shall not be considered part of the shear wall length.
- Required shearwall lengths perpendicular to the ridge are per lineal foot of building length. Multiply tabular values by building length for total shear wall required.
- Shearwall lengths for No. 4 reinforcement are based on shearwall segment height of 80 inches (2032 mm) and shearwall segment length of 24 inches (610 mm).
- Shearwall lengths for No. 5 reinforcement are based on shearwall segment height of 96 inches (2438 mm) and shearwall segment length of 24 inches (610 mm).
EXP | Vasd AS DETERMINED IN ACCORDANCE WITH SECTION R301.2.1.3 |
TOP STORY | 1ST STORY OF 2 STORY OR 2ND STORY OF 3 STORY | 1ST STORY OF 3 STORY | ||||||
BUILDING WIDT |