ADOPTS WITH AMENDMENTS:

International Existing Building Code 2015 (IEBC 2015)

Heads up: There are no amended sections in this chapter.
Level 1 alterations as described in Section 503 shall comply with the requirements of this chapter. Level 1 alterations to historic buildings shall comply with this chapter, except as modified in Chapter 12.

An existing building or portion thereof shall not be altered such that the building becomes less safe or energy efficient than its existing condition.

Exception: Where the current level of safety or sanitation is proposed to be reduced, the portion altered shall conform to the requirements of the Florida Building Code, Building.

In flood hazard areas, alterations that constitute substantial improvement shall require that the building comply with Section 1612 of the Florida Building Code, Building, or Section R322 of the Florida Building Code, Residential, as applicable.

All newly installed interior wall and ceiling finishes shall comply with Chapter 8 of the Florida Building Code, Building.
New interior floor finish, including new carpeting used as an interior floor finish material, shall comply with Section 804 of the Florida Building Code, Building.
All newly installed interior trim materials shall comply with Section 806 of the Florida Building Code, Building.

In Group R-2 or R-3 buildings containing dwelling units and one- and two-family dwellings and townhouses regulated by the Florida Building Code, Residential, window opening control devices complying with ASTM F2090 shall be installed where an existing window is replaced and where all of the following apply to the replacement window:

  1. The window is operable;
  2. The window replacement includes replacement of the sash and the frame;
  3. One of the following applies:

    1. 3.1. In Group R-2 or R-3 buildings containing dwelling units, the top of the sill of the window opening is at a height less than 36 inches (915 mm) above the finished floor; or
    2. 3.2. In one- and two-family dwellings and townhouses regulated by the Florida Building Code, Residential, the top sill of the window opening is at a height less than 24 inches (610 mm) above the finished floor;
  4. The window will permit openings that will allow passage of a 4-inch-diameter (102 mm) sphere when the window is in its largest opened position; and
  5. The vertical distance from the top of the sill of the window opening to the finished grade or other surface below, on the exterior of the building, is greater than 72 inches (1829 mm).

The window opening control device, after operation to release the control device allowing the window to fully open, shall not reduce the minimum net clear opening area of the window unit to less than the area required by the Florida Building Code, Building.

Exceptions:

  1. Operable windows where the top of the sill of the window opening is located more than 75 feet (22 860 mm) above the finished grade or other surface below, on the exterior of the room, space or building, and that are provided with window fall prevention devices that comply with ASTM F2006.
  2. Operable windows with openings that are provided with window fall prevention devices that comply with ASTM F2090.

Where windows are required to provide emergency escape and rescue openings in Group R-2 and R-3 occupancies and one- and two-family dwellings and townhouses regulated by the Florida Building Code, Residential, replacement windows shall be exempt from the requirements of Sections 1030.2, 1030.3 and 1030.5 of the Florida Building Code, Building and Sections R310.21 and R310.2.3 of the Florida Building Code, Residential accordingly, provided the replacement window is the manufacturer's largest standard size window that will fit within the existing frame or existing rough opening. The replacement window shall be permitted to be of the same operating style as the existing window or a style that provides for an equal or greater window opening area than the existing window.

Window opening control devices complying with ASTM F2090 shall be permitted for use on windows required to provide emergency escape and rescue openings.

All new work shall comply with the materials and methods requirements in the Florida Building Code, Building; Florida Building Code, Energy Conservation; Florida Building Code, Mechanical; and Florida Building Code, Plumbing, as applicable, that specify material standards, detail of installation and connection, joints, penetrations, and continuity of any element, component, or system in the building.

The following sections of the Florida Building Code, Fuel Gas shall constitute the fuel gas materials and methods requirements for Level 1 alterations.

  1. All of Chapter 3, entitled "General Regulations," except Sections 303.7 and 306.
  2. All of Chapter 4, entitled "Gas Piping Installations," except Sections 401.8 and 402.3.

    1. 2.1. Sections 401.8 and 402.3 shall apply when the work being performed increases the load on the system such that the existing pipe does not meet the size required by code. Existing systems that are modified shall not require resizing as long as the load on the system is not increased and the system length is not increased even if the altered system does not meet code minimums.
  3. All of Chapter 5, entitled "Chimneys and Vents."
  4. All of Chapter 6, entitled "Specific Appliances."
Alterations shall be done in a manner that maintains the level of fire protection provided.
One-family and two-family dwellings and townhomes undergoing a repair, or a Level 1 alteration as defined in the Florida Building Code, may use smoke alarms powered by 10-year nonremovable, nonreplaceable batteries in lieu of retrofitting such dwelling with smoke alarms powered by the dwelling's electrical system. A battery-powered smoke alarm that is newly installed or replaces an existing battery-powered smoke alarm as a result of a Level 1 alteration must be powered by a nonremovable, nonreplaceable battery that powers the alarm for at least 10 years. The battery requirements of this section do not apply to a fire alarm, smoke detector, smoke alarm, or ancillary component that is electronically connected as a part of a centrally monitored or supervised alarm system, that uses a low-power, radio frequency wireless communication signal; or that contains multiple sensors, such as a smoke alarm combined with a carbon monoxide alarm or other multisensor devices, and is approved and listed by a nationally recognized testing laboratory.
Alterations shall be done in a manner that maintains the level of protection provided for the means of egress.
Accessibility shall be in accordance with the provisions of the Florida Building Code, Accessibility.
Reserved.
Reserved.

Reserved.

Table 705.1.4 Ramps.

Reserved.

Materials and methods of application used for recovering or replacing an existing roof covering shall comply with the requirements of Chapter 15 of the Florida Building Code, Building, or Chapter 9 of the Florida Building Code, Residential. Roof repairs to existing roofs and roof coverings shall comply with the provisions of this code.

Exception: Reroofing shall not be required to meet the minimum design slope requirement of one-quarter unit vertical in 12 units horizontal (2-percent slope) in Section 1507 of the Florida Building Code, Building for roofs that provide positive roof drainage (High-Velocity Hurricane Zones shall comply with Sections 1515.2.2.1 and 1516.2.4 of the Florida Building Code, Building).

Not more than 25 percent of the total roof area or roof section of any existing building or structure shall be repaired, replaced or recovered in any 12-month period unless the entire existing roofing system or roof section is replaced to conform to requirements of this code.
Structural roof components shall be capable of supporting the roof-covering system and the material and equipment loads that will be encountered during installation of the system.

New roof coverings shall not be installed without first removing all existing layers of roof coverings down to the roof deck where any of the following conditions occur:

  1. Where the existing roof or roof covering is water soaked or has deteriorated to the point that the existing roof or roof covering is not adequate as a base for additional roofing.
  2. Where the existing roof covering is wood shake, slate, clay, cement or asbestos-cement tile.
  3. Where the existing roof has two or more applications of any type of roof covering.
  4. When blisters exist in any roofing, unless blisters are cut or scraped open and remaining materials secured down before applying additional roofing.
  5. Where the existing roof is to be used for attachment for a new roof system and compliance with the securement provisions of Section 1504.1 of the Florida Building Code, Building cannot be met.

Exceptions:

  1. Building and structures located within the High-Velocity Hurricane Zone shall comply with the provisions of Sections 1512 through 1525 of the Florida Building Code, Building.
  2. Complete and separate roofing systems, such as standing-seam metal roof systems, that are designed to transmit the roof loads directly to the building's structural system and that do not rely on existing roofs and roof coverings for support, shall not require the removal of existing roof coverings.
  3. Reserved.
  4. The application of a new protective coating over an existing spray polyurethane foam roofing system shall be permitted without tear-off of existing roof coverings.
  5. Roof Coating. Application of elastomeric and or maintenance coating systems over existing asphalt shingles shall be in accordance with the shingle manufacturer's approved installation instructions.
Where the application of a new roof covering over wood shingle or shake roofs creates a combustible concealed space, the entire existing surface shall be covered with gypsum board, mineral fiber, glass fiber or other approved materials securely fastened in place.
Existing slate, clay or cement tile shall be permitted for reinstallation, except that damaged, cracked or broken slate or tile shall not be reinstalled. Existing vent flashing, metal edgings, drain outlets, collars and metal counterflashings shall not be reinstalled where rusted, damaged or deteriorated. Aggregate surfacing materials shall not be reinstalled (High-Velocity Hurricane Zones shall comply with Sections 1512 through 1525 of the Florida Building Code, Building).
Flashings shall be reconstructed in accordance with approved manufacturer's installation instructions. Metal flashing to which bituminous materials are to be adhered shall be primed prior to installation (HighVelocity Hurricane Zones shall comply with Sections 1512 through 1525 of the Florida Building Code, Building).

When a roof covering on an existing sitebuilt single-family residential structure is removed and replaced, the following procedures shall be permitted to be performed by the roofing contractor:

  1. Roof-decking attachment shall be as required by Section 706.7.1.
  2. A secondary water barrier shall be provided as required by Section 706.7.2.

Exception: Single-family residential structures permitted subject to the Florida Building Code are not required to comply with this section.

For site-built single-family residential structures the fastening shall be in accordance with Section 706.7.1.1 or 706.7.1.2 as appropriate for the existing construction. 8d nails shall be a minimum of 0.113 inch (2.9 mm) in diameter and shall be a minimum of 21/4 inches (57 mm) long to qualify for the provisions of this section for existing nails regardless of head shape or head diameter.
Roof decking consisting of sawn lumber or wood planks up to 12 inches wide and secured with at least two nails (minimum size 8d) to each roof framing member it crosses shall be deemed to be sufficiently connected. Sawn lumber or wood plank decking secured with smaller fasteners than 8d nails or with fewer than two nails (minimum size 8d) to each framing member it crosses shall be deemed sufficiently connected if fasteners are added such that two clipped head, round head, or ring shank nails (minimum size 8d) are in place on each framing member it crosses.

For roof decking consisting of wood structural panels, fasteners and spacing required in columns 3 and 4 of Table 706.7.1.2 are deemed to comply with the requirements of Section 707.3, Florida Building Code, Existing Building for the indicated design wind speed range. Wood structural panel connections retrofitted with a two part urethane based closed cell adhesive sprayed onto the joint between the sheathing and framing members are deemed to comply with the requirements of Section 707.3, Florida Building Code, Existing Building, provided testing using the manufacturer's recommended application on panels connected with 6d smooth shank nails at no more than a 6-inch edge and 12-inch field spacing demonstrate an uplift resistance of a minimum of 200 psf.

Supplemental fasteners as required by Table 706.7.1.2 shall be ASTM F1667 classification RSRS-01 ring shank nails with the following minimum dimensions:

  1. 0.113-inch nominal shank diameter.
  2. Ring diameter a minimum of 0.010 inch over shank diameter.
  3. 16 to 20 rings per inch.
  4. A minimum 0.280-inch full round head diameter.
  5. Ring shank to extend a minimum of 11/2 inches from the tip of the nail.
  6. Minimum 23/8 inches nail length.

TABLE 706.7.1.2

SUPPLEMENT FASTENERS AT PANEL EDGES AND INTERMEDIATE FRAMING

EXISTING FASTENERSEXISTING SPACINGVasdc 110 MPH OR LESS SUPPLEMENTAL
FASTENER SPACING SHALL BE NO
GREATER THAN
Vasdc GREATER THAN 110 MPH
SUPPLEMENTAL FASTENER SPACING

SHALL BE NO GREATER THAN
Staples or 6dAny6" o.c.b6" o.c.b
8d clipped head, round head,
smooth or ring shank
6" o.c. or lessNone necessaryNone necessary
8d clipped head, round head,
smooth or ring shank
Greater than 6" o.c.6" o.c.a6" o.c.a

For SI: 1 inch = 25.4 mm.

  1. Maximum spacing determined based on existing fasteners and supplemental fasteners.
  2. Maximum spacing determined based on supplemental fasteners only.
  3. Vasd shall be determined in accordance with Section 1609.3.1 of the Florida Building Code, Building or Section R301.2.1.3 of the Florida Building Code, Residential.

A secondary water barrier shall be installed using one of the following methods when roof covering is removed and replaced:

  1. In High-Velocity Hurricane Zone regions:

    1. All joints in structural panel roof sheathing or decking shall be covered with a minimum 4 inch (102 mm) wide strip of self-adhering polymer modified bitumen tape applied directly to the sheathing or decking. The deck and self-adhering polymer modified bitumen tape shall be covered with one of the underlayment systems approved for the particular roof covering to be applied to the roof.
    2. The entire roof deck shall be covered with an approved asphalt impregnated 30# felt underlayment or approved synthetic underlayment installed with nails and tin-tabs in accordance with Section 1518.2, 1518.3 or 1518.4 of the Florida Building Code, Building. (No additional underlayment shall be required over the top of this sheet.) The synthetic underlayment shall be fastened in accordance with the manufacturer's recommendations.
  2. Outside the High-Velocity Hurricane Zone:

    1. Underlayment shall comply with Section R905.1.1 of the Florida Building Code, Residential.

Exceptions:

  1. Roof slopes < 2:12 having a continuous roof system shall be deemed to comply with Section 706.7.2 requirements for a secondary water barrier.
  2. Clay and concrete tile roof systems installed as required by the Florida Building Code are deemed to comply with the requirements of Section 706.7.2 for Secondary Water Barriers.

When a roof covering on an existing site-built singlefamily residential structure is removed and replaced on a building that is located in the wind-borne debris region as defined in the Florida Building Code, Building and that has an insured value of $300,000 or more or, if the building is uninsured or for which documentation of insured value is not presented, has a just valuation for the structure for purposes of ad valorem taxation of $300,000 or more:

  1. Roof to wall connections shall be improved as required by Section 706.8.1.
  2. Mandated retrofits of the roof-to-wall connection shall not be required beyond a 15 percent increase in the cost of reroofing.

Exception: Single-family residential structures permitted subject to the Florida Building Code are not required to comply with this section.

Where required by Section 706.8, the intersection of roof framing with the wall below shall provide sufficient resistance to meet the uplift loads specified in Table 706.8.1 either because of existing conditions or through retrofit measures. As an alternative to an engineered design, the prescriptive retrofit solutions provided in Sections 706.8.1.1 through 706.8.1.7 shall be accepted as meeting the mandated roof-to-wall retrofit requirements.

Exceptions:

  1. Where it can be demonstrated (by code adoption date documentation and permit issuance date) that roof-to-wall connections and/or roof-tofoundation continuous load path requirements were required at the time of original construction.
  2. Roof-to-wall connections shall not be required unless evaluation and installation of connections at gable ends or all corners can be completed for 15 percent of the cost of roof replacement.

TABLE 706.8.1

REQUIRED UPLIFT CAPACITIES FOR ROOF-TO-WALL CONNECTIONSa, b (POUNDS PER LINEAR FOOT)

ULTIMATE
DESIGN
WIND
SPEED, Vultc,d
ROOF SPAN (feet)OVERHANGS
12202428323640
Within 6 feet of
building corner
85-69.85-116.42-139.70-162.99-186.27-209.55-232.84-27
90-82.67-137.78-165.34-192.90-220.45-248.01-275.57-30.3
100-110.51-184.18-221.01-257.85-294.68-331.52-368.36-37.4
110-141.27-235.45-282.55-329.64-376.73-423.82-470.91-45.3
120-174.97-291.62-349.94-408.26-466.59-524.91-583.23-53.9
130-211.60-352.66-423.19-493.72-564.26-634.79-705.32-63.2
140-251.15-418.59-502.31-586.02-669.74-753.46-837.18-73.3
150-293.64-489.40-587.28-685.16-783.04-880.92-978.80-84.2
170-387.40-645.67-774.81-903.94-1033.08-1162.21-1291.35-108
Greater than 6
feet from building
corner
85-39.10-65.17-78.20-91.24-104.27-117.30-130.34-27
90-48.20-80.33-96.39-112.46-128.52-144.59-160.66-30.3
100-67.95-113.24-135.89-158.54-181.19-203.84-226.49-37.4
110-89.78-149.63-179.55-209.48-239.40-269.33-299.25-45.3
120-113.68-189.47-227.37-265.26-303.16-341.05-378.94-53.9
130-139.67-232.78-279.34-325.90-372.45-419.01-465.57-63.2
140-167.74-279.56-335.47-391.38-447.29-503.21-559.12-73.3
150-197.88-329.80-395.76-461.72-527.68-593.64-659.60-84.2
170-264.41-440.68-528.81-616.95-705.08-793.22-881.35-108

For SI: 1 foot = 304.8 mm; 1 pound per linear foot = 1.488 kg/m; 1 mile per hour = 0.305 m/s.

  1. The uplift loads are pounds per lineal foot of building length. For roof uplift connections multiply by 1.33 for framing spaced 16-inches on center and multiply by 2 for framing spaced 24-inches on center.
  2. The uplift loads do not account for the effects of overhangs. The magnitude of the above loads shall be increased by adding the overhang loads found in the table. The overhang loads are also based on framing spaced 12-inches on center. The overhang loads given shall be multiplied by the overhang projection and added to the roof uplift value in the table.
  3. For Ultimate design wind speeds, Vult, greater than 170 mph, wind uplift forces shall be determined in accordance with Florida Building Code, Residential, Section R301.2.1.1 of the Florida Building Code, Residential or ASCE 7.
  4. Ultimate Design Wind Speeds determined from Figure 1609.3(1) in the Florida Building Code, Building or Figure R301.2(4) in the Florida Building Code, Residential.

These provisions are not intended to limit the means for gaining access to the structural elements of the roof and wall for the purposes of retrofitting the connection. The retrofit of roof to wall connections can be made by access through the area under the eave, from above through the roof, or from the interior of the house. Methods for above access include removal of roof panels or sections thereof or removal of portions of roof paneling at selected locations large enough for access, viewing, and installing the retrofit connectors and fasteners.

Where panels or sections are removed, the removed portions shall not be reused. New paneling shall be used and fastened as in new construction.

Holes shall be deemed adequately repaired if a patch of paneling is installed with no gap greater than 1/2 inch (13 mm) between the patch and the existing sheathing and if the patch is supported using one of the following methods.

  1. Solid 11/2-inch lumber shall fully support the patch and shall be secured to the existing sheathing with #8 by 11/4-inch screws spaced a minimum of 3 inches (76 mm) around the perimeter with screws a minimum of 3/4 inch from the near edge of the hole. The patch shall be secured to the lumber with #8 × 11/4-inch screws spaced on a grid no greater than 6 inches by 6 inches (152 mm × 152 mm) with no fewer than 2 screws.
  2. Holes that extend horizontally from roof framing member to adjacent roofing framing member that are less than or equal to 7 inches (178 mm) wide along the slope of the roof shall be supported by a minimum of 2 × 4 lumber whose face is attached to each roofing framing members using a minimum of 2 each 3-inch (76 mm) long fasteners (#8 screws or 10d common nails) connecting the two. The patch shall have attached to its bottom, running horizontally, a minimum 2 × 4 either flat wise or on edge secured with #8 × 11/4-inch screws a maximum of 4 inches (102 mm) on center and no more distant from the end of the added lumber than 3 inches (76 mm). The patch shall be secured with two #8 × 11/4-inch screws to each support member.
Where part of a strap is inaccessible, if the portion of the strap that is observed is fastened in compliance with these requirements, the inaccessible portion of the strap shall be presumed to comply with these requirements.
The anchorage of each of the exposed rafters or trusses within 6 feet (1829 mm) of the corner along the exterior wall on each side of each gable end shall be inspected. Wherever a strap is missing or an existing strap has fewer than four fasteners on each end, approved straps, ties or right angle brackets with a minimum uplift capacity of 500 pounds (740 kg) shall be installed that connect each rafter or truss to the top plate below. Adding fasteners to existing straps shall be allowed in lieu of adding a new strap provided the strap is manufactured to accommodate at least 4 fasteners at each end. Wherever access makes it possible (without damage of the wall or soffit finishes), both top plate members shall be connected to the stud below using a stud to plate connector with a minimum uplift capacity of 500 pounds (740 kg). Use of straps that connect directly from the rafter or truss to the wall stud below shall be allowed as an alternate provided the two members align with no more than 11/2 inches (38 mm) offset.
The anchorage of each of the exposed rafters or trusses within 6 feet (1829 mm) of the corner along the exterior wall on each side of each gable end shall be inspected. Wherever a strap is missing or an existing strap has fewer than four fasteners on each end, approved straps, ties or right angle gusset brackets with a minimum uplift capacity of 500 pounds (740 kg) shall be installed that connect each rafter or truss to the top plate below or directly to the masonry wall using approved masonry screws of a length and diameter recommended by the manufacturer. In the absence of manufacturer's recommendations, screws shall provide at least a 21/2-inch (64 mm) embedment into the concrete or masonry. When the straps or right angle gusset brackets are attached to a wood sill plate, the sill plate shall be anchored to the concrete masonry wall below. This anchorage shall be accomplished by installing 1/4- inch diameter masonry screws, each with supplementary 1/4-inch washer, having sufficient length to develop a 21/2 inch (64 mm) embedment into the concrete and masonry. These screws shall be installed within 4 inches (102 mm) of the truss or rafter on both sides of each interior rafter or truss and on the accessible wall side of the gable end truss or rafter.
Unless it is possible to verify through nondestructive inspection or from plans prepared by a design professional that the roof structure is anchored at least as well as outlined below, access shall be provided at a minimum to the hip rafter (commonly known as a "king jack"), to the hip girder and at each corner of the hip roof. The hip rafter (commonly known as a "king jack"), the hip girder and the rafters/trusses adjacent to the hip girder that are not anchored with a strap having at least four fasteners on each end, shall be connected to the top plate below using a strap or a right angle gusset bracket having a minimum uplift capacity of 500 pounds (740 kg). Adding fasteners to existing straps shall be allowed in lieu of adding a new strap provided the strap is manufactured to accommodate at least 4 fasteners at each end. Wherever access makes it possible (without damage of the wall or soffit finishes), both top plate members shall be connected to the stud below using a stud to plate connector with a minimum uplift capacity of 500 pounds (740 kg). Use of straps that connect directly from the hip rafter, hip girder or adjacent rafters/trusses to the wall stud below shall be allowed as an alternate provided the two members align with no more than 11/2 inch (38 mm) offset.
Unless it is possible to verify through nondestructive inspection or from plans prepared by a design professional that the roof structure is anchored at least as well as outlined below, access shall be provided at a minimum to the hip rafter (commonly known as a "king jack"), to the hip girder and at each corner of the hip roof. The hip rafter (commonly known as a "king jack"), the hip girder and the rafters/trusses adjacent to the hip girder that are not anchored with a strap having at least four fasteners on each end, shall be connected to the concrete masonry wall below using approved straps or right angle gusset brackets with a minimum uplift capacity of 500 pounds (740 kg). Adding fasteners to existing straps shall be allowed in lieu of adding a new strap provided the strap is manufactured to accommodate at least 4 fasteners at each end. The straps or right angle gusset brackets shall be installed such that they connect each rafter or truss to the top plate below or directly to the masonry wall using approved masonry screws of a length and diameter recommended by the manufacturer. In the absence of manufacturer's recommendations, screws shall provide at least a 21/2-inch (64 mm) embedment into the concrete or masonry. When the straps or right angle gusset brackets are attached to a wood sill plate, the sill plate shall be anchored to the concrete masonry wall below. This anchorage shall be accomplished by installing 1/4-inch (6 mm) diameter masonry screws, each with supplementary 1/4-inch (6 mm) washer, with sufficient length to develop a 21/2- inch (64 mm) embedment into the concrete and masonry. These screws shall be installed within 4 inches (102 mm) of the truss or rafter on both sides of each interior rafter or truss and on the accessible wall side of the gable end truss or rafter.
Priority shall be given to connecting the exterior corners of roofs to walls where the spans of the roofing members are greatest. For houses with both hip and gable roof ends, the priority shall be to retrofit the gable end roof-to-wall connections unless the width of the hip end is more than 1.5 times greater than the width of the gable end. When considering priorities for houses with both hip and gable roof ends, and the fifteen percent of the cost of roof replacement is sufficient to complete all of the prioritized elements pursuant to this section, but is not sufficient to complete all of the non-prioritized elements, then no portion of complete retrofit of the non-prioritized element is required.

Where alteration work includes replacement of equipment that is supported by the building or where a reroofing permit is required, the provisions of this section shall apply.

Exception: Buildings and structures located within the High-Velocity Hurricane Zone shall comply with Sections 1512 through 1525 of the Florida Building Code, Building.

Where addition or replacement of roofing or replacement of equipment results in additional dead loads, structural components supporting such reroofing or equipment shall comply with the gravity load requirements of the Florida Building Code, Building.

Exceptions:

  1. Structural elements where the additional dead load from the roofing or equipment does not increase the force in the element by more than 5 percent.
  2. Buildings constructed in accordance with the Florida Building Code, Residential or the conventional light-frame construction methods of the Florida Building Code, Building and where the dead load from the roofing or equipment is not increased by more than 5 percent.
  3. Addition of a second layer of roof covering weighing 3 pounds per square foot (0.1437 kN/m2) or less over an existing, single layer of roof covering.
The requirements of this section shall apply to alteration work requiring reroof permits.
Where a permit is issued for reroofing for more than 25 percent of the roof area of a building assigned to Seismic Design Category D, E or F that has parapets constructed of unreinforced masonry, the work shall include installation of parapet bracing to resist the reduced Florida Building Code, Building level seismic forces as specified in Section 301.1.4.2 of this code, unless an evaluation demonstrates compliance of such items.

Where roofing materials are removed from more than 50 percent of the roof diaphragm or section of a building located where the ultimate design wind speed, Vult, determined in accordance with Figure 1609.3(1) of the Florida Building Code, Building, is greater than 115 mph (51 m/s), as defined in Section 1609 (the High-Velocity Hurricane Zone shall comply with Section 1620) of the Florida Building Code, Building, roof diaphragms, connections of the roof diaphragm to roof framing members, and roof-to-wall connections shall be evaluated for the wind loads specified in the Florida Building Code, Building, including wind uplift. If the diaphragms and connections in their current condition are not capable of resisting at least 75 percent of those wind loads, they shall be replaced or strengthened in accordance with the loads specified in the Florida Building Code, Building.

Exceptions:

  1. This section does not apply to buildings permitted subject to the Florida Building Code.
  2. This section does not apply to buildings permitted subject to the 1991 Standard Building Code, or later edition, or designed to the wind loading requirements of the ASCE 7-88 or later editions, where an evaluation is performed by a registered design professional to confirm the roof diaphragm, connections of the roof diaphragm to roof framing members, and roof-to-wall connections are in compliance with the wind loading requirements of either of these standards or later editions.
  3. Buildings with steel or concrete moment resisting frames shall only be required to have the roof diaphragm panels and diaphragm connections to framing members evaluated for wind uplift.
  4. This section does not apply to site-built singlefamily dwellings. Site-built single-family dwellings shall comply with Sections 706.7 and 706.8.
  5. This section does not apply to buildings permitted within the HVHZ after January 1, 1994 subject to the 1994 South Florida Building Code, or later editions, or where the building's wind design is based on the wind loading requirements of ASCE 7-88 or later editions.

The replacement of garage doors, exterior doors, skylights, and operative and inoperative windows shall be designed and constructed to comply with Chapter 16 of the Florida Building Code, Building.

Exceptions:

  1. Opening protection exception: For one- and twofamily dwellings constructed under codes other than the Florida Building Code and located in windborne debris regions, the replacement of garage doors and exterior doors with glazing, sliding glass doors, glass patio doors, skylights, and operable and inoperable windows within any 12-month period shall not be required to have opening protection but shall be designed for wind pressures for enclosed buildings, provided the aggregate area of the glazing in the replaced components does not exceed 25 percent of the aggregate area of the glazed openings in the dwelling or dwelling unit.
  2. Opening protection exception for High-Velocity Hurricane Zones: For one- and two-family dwellings constructed under codes prior to September 1, 1994 the replacement of exterior doors with glazing, sliding glass doors, glass patio doors, skylights, and operable and inoperable windows within any 12 month period shall not be required to have opening protection provided the aggregate area of the glazing in the replaced components does not exceed 25 percent of the aggregate area of the glazed openings in the dwelling or dwelling unit.

Openings in sunrooms, enclosed balconies and enclosed porches constructed under existing roofs or decks are not required to be protected, provided the space is separated from the building interior by a wall and all openings in the separating wall are protected in accordance with Section 1609.1.2 of the Florida Building Code, Building. Such spaces shall be permitted to be designed as enclosed or partially enclosed. (High-Velocity Hurricane Zones must comply with Chapter 16 of the Florida Building Code, Building.)

Exceptions:

  1. Exterior balconies or porches under existing roofs or decks enclosed with screen or removable vinyl and acrylic panels complying with the Florida Building Code, Building, Section 2002.3.3 shall not be required to be protected and openings in the wall separating the unit from the balcony or porch shall not be required to be protected unless required by other provisions of this code.
  2. High-Velocity Hurricane Zones must comply with Chapter 16 of the Florida Building Code, Building.
Alteration subject to this chapter shall comply with the requirements of the Florida Building Code, Energy Conservation.
UpCodes Premium
Leverage the most sophisticated code compliance platform.
TRY FREE FOR TWO WEEKS VISIT PRICING