Learn how an architect optimized his design workflow
Register for webinar
Adopts With Amendments:

International Building Code 2018 (IBC 2018)

Heads up: There are no amended sections in this chapter.
The provisions of this chapter govern the quality, design, fabrication and erection of steel used structurally in buildings or structures.
Exception: Buildings and structures located within the high-velocity hurricane zone shall comply with the provisions of Sections 2204 through 2209 and 2214 through 2224.
Identification of structural steel elements shall be in accordance with AISC 360. Identification of cold-formed steel members shall be in accordance with AISI S100. Identification of cold-formed steel light-frame construction shall also comply with the requirements contained in AISI S240 or AISI S220, as applicable. Other steel furnished for structural load-carrying purposes shall be properly identified for conformity to the ordered grade in accordance with the specified ASTM standard or other specification and the provisions of this chapter. Steel that is not readily identifiable as to grade from marking and test records shall be tested to determine conformity to such standards.
Painting of structural steel elements shall be in accordance with AISC 360. Painting of open-web steel joists and joist girders shall be in accordance with SJI 200 and SJI 100. Individual structural members and assembled panels of cold-formed steel construction shall be protected against corrosion in accordance with the requirements contained in AISI S100. Protection of cold-formed steel light-frame construction shall be in accordance with AISI S240 or AISI S220, as applicable.
The details of design, workmanship and technique for welding and qualification of welding personnel shall be in accordance with the specifications listed in Sections 2205, 2206, 2207, 2208, 2210 and 2211 (see Section 2222 for HVHZ) and 2211 (see Section 2222 for HVHZ).
The design, installation and inspection of bolts shall be in accordance with the requirements of Sections 2205, 2206, 2207, 2210 and 2211.
Anchor rods shall be set in accordance with the approved construction documents. The protrusion of the threaded ends through the connected material shall fully engage the threads of the nuts but shall not be greater than the length of the threads on the bolts.
The design, fabrication and erection of structural steel elements in buildings, structures and portions thereof shall be in accordance with AISC 360.
Where required, the seismic design, fabrication and erection of buildings, structures and portions thereof shall be in accordance with Section 2205.2.1 or 2205.2.2, as applicable.
The design, detailing, fabrication and erection of structural steel seismic force-resisting systems shall be in accordance with the provisions of Section 2205.2.1.1 or 2205.2.1.2, as applicable.
Structures assigned to Seismic Design Category B or C shall be of any construction permitted in Section 2205. Where a response modification coefficient, R, in accordance with ASCE 7, Table 12.2-1, is used for the design of structures assigned to Seismic Design Category B or C, the structures shall be designed and detailed in accordance with the requirements of AISC 341.
Exception: The response modification coefficient, R, designated for "Steel systems not specifically detailed for seismic resistance, excluding cantilever column systems" in ASCE 7, Table 12.2-1, shall be permitted for systems designed and detailed in accordance with AISC 360, and need not be designed and detailed in accordance with AISC 341.
Structures assigned to Seismic Design Category D, E or F shall be designed and detailed in accordance with AISC 341, except as permitted in ASCE 7, Table 15.4-1.
The design, detailing, fabrication and erection of structural steel elements in seismic force-resisting systems other than those covered in Section 2205.2.1, including struts, collectors, chords and foundation elements, shall be in accordance with AISC 341 where either of the following applies:
  1. The structure is assigned to Seismic Design Category D, E or F, except as permitted in ASCE 7, Table 15.4-1.
  2. A response modification coefficient, R, greater than 3 in accordance with ASCE 7, Table 12.2-1, is used for the design of the structure assigned to Seismic Design Category B or C.
Systems of structural steel elements acting compositely with reinforced concrete shall be designed in accordance with AISC 360 and ACI 318, excluding ACI 318 Chapter 14.
Where required, the seismic design, fabrication and erection of composite steel and concrete systems shall be in accordance with Section 2206.2.1.
Where a response modification coefficient, R, in accordance with ASCE 7, Table 12.2-1, is used for the design of systems of structural steel acting compositely with reinforced concrete, the structures shall be designed and detailed in accordance with the requirements of AISC 341.
The design, manufacture and use of open-web steel joists and joist girders shall be in accordance with either SJI 200 or SJI 100, as applicable.
Where required, the seismic design of buildings shall be in accordance with the additional provisions of Section 2205.2 or 2211.1.
The registered design professional shall indicate on the construction documents the steel joist and steel joist girder designations from the specifications listed in Section 2207.1; and shall indicate the requirements for joist and joist girder design, layout, end supports, anchorage, bridging design that differs from the SJI specifications listed in Section 2207.1, bridging termination connections and bearing connection design to resist uplift and lateral loads. These documents shall indicate special requirements as follows:
  1. Special loads including:
    1. 1.1. Concentrated loads.
    2. 1.2. Nonuniform loads.
    3. 1.3. Net uplift loads.
    4. 1.4. Axial loads.
    5. 1.5. End moments.
    6. 1.6. Connection forces.
  2. Special considerations including:
    1. 2.1. Profiles for joist and joist girder configurations that differ from those defined by the SJI specifications listed in Section 2207.1.
    2. 2.2. Oversized or other nonstandard web openings.
    3. 2.3. Extended ends.
  3. Live and total load deflection criteria for joists and joist girder configurations that differ from those defined by the SJI specifications listed in Section 2207.1.
The steel joist and joist girder manufacturer shall design the steel joists and steel joist girders in accordance with the SJI specifications listed in Section 2207.1 to support the load requirements of Section 2207.2. The registered design professional shall be permitted to require submission of the steel joist and joist girder calculations as prepared by a registered design professional responsible for the product design. Where requested by the registered design professional, the steel joist manufacturer shall submit design calculations with a cover letter bearing the seal and signature of the joist manufacturer's registered design professional. In addition to the design calculations submitted under seal and signature, the following shall be included:
  1. Bridging design that differs from the SJI specifications listed in Section 2207.1, such as cantilevered conditions and net uplift.
  2. Connection design for:
    1. 2.1. Connections that differ from the SJI specifications listed in Section 2207.1, such as flush-framed or framed connections.
    2. 2.2. Field splices.
    3. 2.3. Joist headers.
Steel joist placement plans shall be provided to show the steel joist products as specified on the approved construction documents and are to be utilized for field installation in accordance with specific project requirements as stated in Section 2207.2. Steel joist placement plans shall include, at a minimum, the following:
  1. Listing of applicable loads as stated in Section 2207.2 and used in the design of the steel joists and joist girders as specified in the approved construction documents.
  2. Profiles for joist and joist girder configurations that differ from those defined by the SJI specifications listed in Section 2207.1.
  3. Connection requirements for:
    1. 3.1. Joist supports.
    2. 3.2. Joist girder supports.
    3. 3.3. Field splices.
    4. 3.4. Bridging attachments.
  4. Live and total load deflection criteria for joists and joist girder configurations that differ from those defined by the SJI specifications listed in Section 2207.1.
  5. Size, location and connections for bridging.
  6. Joist headers.
Steel joist placement plans do not require the seal and signature of the joist manufacturer's registered design professional.
At completion of manufacture, the steel joist manufacturer shall submit a certificate of compliance to the owner or the owner's authorized agent for submittal to the building official as specified in Section 1704.5 stating that work was performed in accordance with approved construction documents and with SJI specifications listed in Section 2207.1.
The design, fabrication and erection including related connections, and protective coatings of steel cables for buildings shall be in accordance with ASCE 19.
The design, testing and utilization of storage racks made of cold-formed or hot-rolled steel structural members shall be in accordance with RMI/ANSI MH 16.1. Where required by ASCE 7, the seismic design of storage racks shall be in accordance with Section 15.5.3 of ASCE 7.
The design, testing and utilization of cantilevered storage racks made of cold-formed or hot-rolled steel structural members shall be in accordance with RMI ANSI/MH 16.3. Where required by ASCE 7, the seismic design of cantilevered steel storage racks shall be in accordance with Section 15.5.3 of ASCE 7.
The design of cold-formed carbon and low-alloy steel structural members shall be in accordance with AISI S100. The design of cold-formed stainless-steel structural members shall be in accordance with ASCE 8. Cold-formed steel light-frame construction shall also comply with Section 2211. Where required, the seismic design of cold-formed steel structures shall be in accordance with the additional provisions of Section 2210.2.
The design and construction of cold-formed steel decks shall be in accordance with this section.
Noncomposite steel floor decks shall be permitted to be designed and constructed in accordance with ANSI/SDI-NC1.0.
Steel roof decks shall be permitted to be designed and constructed in accordance with ANSI/SDI-RD1.0.
Composite slabs of concrete and steel deck shall be permitted to be designed and constructed in accordance with SDI-C.
Where a response modification coefficient, R, in accordance with ASCE 7, Table 12.2-1, is used for the design of cold-formed steel structures, the structures shall be designed and detailed in accordance with the requirements of AISI S100, ASCE 8, or, for cold-formed steel special-bolted moment frames, AISI S400.
Allowable loads for joist hangers and connectors shall be in accordance with either AISI S914 or the procedure in ASTM D7147. Allowable loads for hold-downs shall be in accordance with AISI S913.
For cold-formed steel light-frame construction, the design and installation of the following structural framing systems, including their members and connections, shall be in accordance with AISI S240 and Sections 2211.1.1 through 2211.1.3, as applicable:
  1. Floor and roof systems,
  2. Structural walls,
  3. Shear walls, strap braced walls and diaphragms to resist in-plane lateral loads, and
  4. Trusses.
The design of cold-formed steel light-frame construction to resist seismic forces shall be in accordance with the provisions of Section 2211.1.1.1 or 2211.1.1.2, as applicable.
Where a response modification coefficient, R, in accordance with ASCE 7, Table 12.2-1 is used for the design of cold-formed steel light-frame construction assigned to Seismic Design Category B or C, the seismic forceresisting system shall be designed and detailed in accordance with the requirements of AISI S400.
Exception: The response modification coefficient, R, designated for "Steel systems not specifically detailed for seismic resistance, excluding cantilever column systems" in ASCE 7, Table 12.2-1 shall be permitted for systems designed and detailed in accordance with AISI S240 and need not be designed and detailed in accordance with AISI S400.
In cold-formed steel light-frame construction assigned to Seismic Design Category D, E, or F, the seismic forceresisting system shall be designed and detailed in accordance with AISI S400.
Detached one- and two-family dwellings and townhouses, less than or equal to three stories above grade plane, shall be permitted to be constructed in accordance with AISI S230 subject to the limitations therein.
Cold-formed steel trusses shall comply with the provisions of Sections 2211.1.3.1 through 2211.1.3.3.
The truss design drawings shall conform to the requirements of Section I1 of AISI S202 and shall be provided with the shipment of trusses delivered to the job site. The truss design drawings shall include the details of permanent individual truss member restraint/bracing in accordance with Section I1.6 of AISI S202 where these methods are utilized to provide restraint/bracing.
The owner or the owner's authorized agent shall contract with a registered design professional for the design of the temporary installation restraint/bracing and the permanent individual truss member restraint/bracing for trusses with clear spans 60 feet (18 288 mm) or greater.
For cold-formed steel light-frame construction, the design and installation of nonstructural members and connections shall be in accordance with AISI S220.
Gable endwalls shall be structurally continuous between points of lateral support.
Gable endwalls adjacent to cathedral ceilings shall be structurally continuous from the uppermost floor to the ceiling diaphragm or to the roof diaphragm.
Steel and iron members shall be designed by methods admitting of rational analysis according to established principles or methods.
The design, fabrication and erection of iron and steel for buildings and other structures shall be as set forth in this chapter. The requirements set forth in Sections 2215 through 2221 herein, inclusive, apply to structural steel for buildings and other structures. Sections 2222 and 2223, apply to cold-formed members of sheet or strip steel and cold-formed steel light-frame construction.
The following standards, as set forth in Chapter 35 of this code, are hereby adopted.
  1. American Institute of Steel Construction, AISC.
    1. DG03, Serviceability Design Considerations for Steel Buildings, AISC.
    2. DG09, Torsional Analysis of Structural Steel Members, AISC.
    3. DG15, AISC Rehabilitation and Retrofit Guide: A Reference for Historic Shapes and Specifications, AISC.
    4. AISC Steel Construction Manual, AISC.
    5. Detailing for Steel Construction, AISC.
  2. American Iron and Steel Institute, AISI.
    1. AISI S100, North American Specification for the Design of Cold-Formed Steel Structural Members.
    2. AISI S230, Standard for Cold-Formed Steel Framing—Prescriptive Method for One and Two Family Dwellings.
    3. AISI S240, North American Standard for Cold-Formed Steel Structural Framing.
  3. American Society of Civil Engineers, ASCE.
    1. ASCE 8, Specification for the Design of Cold-Formed Stainless Steel Structural Members.
  4. American National Standards Institute/American Welding Society, ANSI/AWS.
    1. Specification for Welding Procedure and Performance Qualification, AWS B2.1.
    2. Structural Welding Code—Steel, ANSI/AWS D1.1—D1.1M.
    3. Structural Welding Code—Sheet Metal, ANSI/AWS D1.3—D1.3M.
    4. Structural Welding Code—Reinforcing Steel, ANSI/AWS D1.4.
    5. Sheet Metal Welding Code, AWS D9.1—D9.1M.
    1. Standard Specification for General Requirements for Rolled Steel Plates, Shapes, Sheet Piling and Bars for Structural Use, ASTM A6.
    2. Standard Specification for Sheet Steel, Carbon, Metallic, and Nonmetallic Coated for Cold-formed Steel Framing Members, ASTM A1003-A1003M.
    3. Standard Specification for High Strength Structural Bolts, Steel and Alloy Steel, Heat Treated, 120 ksi (830 MPa) and 150 ksi (1040 MPa) Minimum Tensile Strength, Inch and Metric Dimensions, ASTM F3125-F3125M.
  5. National Association of Architectural Metal Manufacturers, NAAMM.
    1. NAAMM MBG 531, Metal Grating Manual.
  6. Research Council on Structural Connections, RCSC.
    1. Specification for Structural Joints Using High-Strength Bolts, RCSC.
  7. Steel Deck Institute, Inc., SDI.
    1. Diaphragm Design Manual, SDI.
    2. SDI-C Standard for Composite Steel Floor Deck Slabs.
    3. SDI-RD Standard for Steel Roof Deck.
    4. SDI-NC Standard for Non-Composite Steel Floor Deck.
  8. Steel Joist Institute, SJI.
    1. 44th Edition Standard Specifications Load Tables and Weight Tables for Steel Joists and Joist Girders, SJI.
    2. "Structural Design of Steel Joist Roofs to Resist Ponding Loads," Technical Digest No. 3, SJI.
    3. "Vibration of Steel Joist-Concrete Slab Floors," Technical Digest No. 5, SJI.
    4. "Design of Steel Joist Roofs to Resist Uplift Loads," Technical Digest No. 6, SJI.
    5. "Welding of Open Web Steel Joist and Joist Girders," Technical Digest No. 8, SJI.
    6. "Handling and Erection of Steel Joists and Joist Girders," Technical Digest No. 9, SJI.
    7. 90 Years of Open Web Steel Joist Construction, SJI.
    8. "Design of Lateral Load Resisting Frames Using Steel Joists and Joist Girders," Technical Digest No. 11, SJI.
  9. Steel Tube Institute, STI.
    1. HSS Design Manual, Volume 1: Section Properties & Design Information.
    2. HSS Design Manual, Volume 2: Member Design.
    3. HSS Design Manual, Volume 3: Connections at HSS Members.
    4. HSS Design Manual, Volume 4: Truss & Bracing Connections.
All steel shall be straight and true, and any section damaged to be out of shape shall not be used. Steel previously used or fabricated for use or fabricated in error shall not be used except with the approval of the building official. Filled holes or welds shall not be concealed. Straightened or retempered fire-burned steel shall not be used except with the approval of the building official.
Design shall be based on the dead, live, wind and other loads set forth in Chapter 16 (High-Velocity Hurricane Zones) and the additional stress considerations set forth in this chapter.
The minimum thickness of material shall not be less than as set forth in the applicable standards listed in Section 2214.3 except as otherwise set forth herein.
Tubular columns and other primary compression members, excluding secondary posts and struts not subject to bending and whose design load does not exceed 2,000 pounds (8900 N), shall have a minimum least dimension of 21/2 inches (64 mm) and a minimum wall thickness of 3/16 inch (4.8 mm).
Tubular members when filled with concrete shall have 1/4-inch diameter (6.4 mm) pressure relief holes drilled through the shell, within 6 inches (152 mm) of the top and bottom of the exposed length of the member and one hole at midheight.
Concrete fill in tubular members shall not be assumed to carry any of the load except in compression members having a least dimension of 8 inches (203 mm) or greater and having a 1 inch (25 mm) inspection hole in the plate at each end.
Open web steel joists shall comply with the standards set forth in Section 2214.3.
Joists shall not bear directly on unit masonry unless masonry is designed as engineered unit masonry with properly reinforced, grout-filled continuous bond beam.
The ends of every joist shall be bolted, welded or encased in concrete at each point of bearing to provide not less than 100 percent of the net uplift reaction specified in the structural construction documents.
The ends of joists shall have a minimum bearing, on reinforced concrete and steel supports as specified in the standard set forth in Section 2214.3(9).
Cold-formed steel construction shall include individual structural members, structural decks or wall panels, and nonstructural roofing, siding and other construction elements formed from sheet or strip steel and as set forth in Section 2214.3(2) and (3).
Cold-formed steel used in structural applications shall conform to the standards set forth in Section 2214.3(2) and (3).
Galvanizing as referred to herein is to be zinc coating conforming to the standard set forth in Section 2214.3(5)(b).
Design, fabrication and erection of individual cold-formed steel structural members shall be as set forth herein.
All structural members shall be positively connected to resist the loads set forth in Chapter 16 (High-Velocity Hurricane Zones).
All connections shall be by welding, riveting, bolting or other approved fastening devices or methods providing positive attachment and resistance to loosening. Fasteners shall be of compatible material.
Cables and rods shall not be used as lateral bracing in habitable structures. Lateral bracing, when used, shall have a slenderness ratio of 300 or less, unless restricted by any other section of this code.
All doors shall be anchored as part of the frame in the closed position.
No increase in strength shall be allowed for the effect of cold work.
Decks and panels with or without an approved fill material may be designed as diaphragms in accordance with Diaphragm Design Manual of the Steel Deck Institute, provided other limitations in this code are complied with.
Poured fill on roof and floor decks shall not be assumed to have any structural value to support or resist vertical or lateral loads or to provide stability or diaphragm action unless so designed, and poured fill and/or applied materials do not degrade when subjected to moisture.
Positive attachment of sheets shall be provided to resist uplift forces. Attachment shall be as set forth in Section 2222.3.1 and as required by rational analysis, and/or tests, but not less frequently than the following maximum spacing:
  1. One fastener shall be placed near the corner of each sheet or at overlapping corners of sheets.
  2. Along each supporting member, the spacing of fasteners shall not exceed 8 inches (203 mm) on centers at ends of sheets or 12 inches (305 mm) on centers.
  3. The spacing of edge fasteners between panels, and between panels and supporting members, parallel to the direction of span, where continuous interlock is not otherwise provided shall be not more than 12 inches (305 mm) on centers.
  4. Fastening shall be by bolting, welding or other approved fastening device that provides a resistance to lateral movement as required by rational analysis or by test, but not less than 400 pounds per lineal foot (5838 N/m).
  5. Poured lightweight concrete fill will be acceptable as continuous interlock.
  6. Attachment to the supporting structure shall be provided at all perimeters and discontinuities by fasteners spaced at no more than 8 inches (203 mm) on center.
  7. Wall panels shall be attached as set forth in Section 2222.4.2(1), (2) and (3).
Metal siding and roof panels shall be not less than 24 gauge.
Exception: Roof panels having an approved fill material designed to act as a diaphragm may use a lighter deck gauge provided that the product approval for the fill material allows its use over the same deck gauge, but in no case shall the deck be less than 26 gauge. The permit applicant shall provide the building official with signed and sealed structural calculations for the diaphragm design prepared by a licensed architect or engineer proficient in structural design. The diaphragm design shall comply with the applicable requirements of Chapter 16 and Chapter 22 (High-Velocity Hurricane Zones).
Deflection of structural metal siding shall not exceed L/240.
Deflection of structural metal roof panels shall not exceed L/180.
The bending stress of metal siding and roof panels shall be designed using a safety factor of not less than 2.5.
Minimum roof decking uplift loads shall comply with the design requirements of Chapter 16 (High-Velocity Hurricane Zones) utilizing rational analysis, but not less than UL 580 Class 90.
Metal siding and roof panels shall be designed, where possible, to be continuous over two or more spans.
Steel sheet sections not suitable by rational analysis for self-supporting structural sheets shall be termed roofing and siding. Roofing and siding shall be used only over solid wood sheathing or equivalent backing.
Attachment of sheets shall be as set forth in Section 2222.4.2.
All members shall be treated with protective paint coatings or equivalent protection except as permitted in Sections 2222.6.1 or 2222.6.2.
All steel sheets having a thickness of less than 20 gauge, i.e., materials of higher gauge, shall be galvanized in accordance with the standards of Section 2214.3(5)(b) herein to provide a minimum coating designation of G90.
Abrasions or damages to the protective coating shall be spot-treated with a material and in a manner compatible to the shop protective coating.
Welding shall conform to the requirements of Sections 2214.3.
Metal buildings (preengineered structures) shall include, but not be limited to, tapered or straight web structural steel frames and predominantly cold-formed steel secondary components, including, but not limited to, girts, purlins, roof sheets, wall sheets, etc.
Frames and components shall comply with the standards set forth in Section 2214.3.
Structural construction documents for preengineered structures shall indicate the necessary measures for adapting the structures to the specific site. The structural construction documents shall indicate all openings, concentrated loads and other special requirements. Foundation conditions assumed in the design shall be indicated as well as the location and magnitude of building reactions on that foundation under all design conditions.
A building or component system in this section shall have a structural engineer of record and/or architect of record responsible for the overall design and performance of the entire building including the foundation and the anchorage of the preengineered metal systems buildings thereto. The structural engineer of record and/or the architect of record shall provide the structural construction documents necessary for permitting.
Calculations for drift and deflection of the metal system building shall be by the specialty engineer.
Calculations for deflection shall be done using only the bare frame method. Reductions based on engineering judgment using the assumed composite stiffness of the building envelope shall not be allowed. Drift shall follow AISC serviceability design considerations for low-rise buildings. The use of composite stiffness for deflection calculations shall be permitted only when actual calculations for the stiffness are included with the design for the specific project. When maximum deflections are specified by the structural construction documents, calculations shall be included in the design data.
The manufacturer shall design the metal system building and/or component system in accordance with the provisions of Chapter 16 (High-Velocity Hurricane Zones), and the design shall be signed, dated and sealed by the specialty engineer and reviewed by the structural engineer of record and/or the architect of record. The manufacturer of the metal system building and or component system shall be responsible to provide all reactions to the structural engineer of record and/or the architect of record.
Fastenings shall be by bolting, welding or other approved fastening device that provides a resistance to lateral movement as required by rational analysis or by test, but not less than 400 pounds per lineal foot (5838 N/m).
Temporary bracing shall be provided during erection and shall remain in place until all structural frames, purlins, girts, flange braces, cable or rod bracing and sheets used as diaphragms have been installed.
The fusion welding of structural members and structural sheets defined in Section 2222.4 and less than 22 gauge (0.0299 inch nominal) in thickness shall have minimum of 5/8 inch (17 mm) diameter welds through weld washers not less than 14-gauge in thickness and 1 inch (25 mm) in diameter, contoured if necessary to provide continuous contact, or an equivalent device.
Clip-mounted standing-seam roof sheets shall not be used as diaphragms nor shall they be considered as adequate lateral bracing of the flange of the secondary member to which they are attached unless one or both of these features are designed into the sheathing system and the manufacturer can certify by testing and/or analysis that such capabilities exist and are appropriately defined.
Structural standing-seam roof sheets shall be a minimum of 24 gauge [0.0239 inch (0.6 mm) nominal] in thickness.
Direct screw attached roof and wall sheets may be used as diaphragms provided the sheets are a minimum of 24 gauge [0.0239 inch (0.6 mm) nominal] in thickness. Additionally, these sheets shall be considered to laterally brace the flange of the secondary member to which they are attached.
See Section 2222 for additional requirements for roof sheets, wall sheets, roof panels and wall panels.
Adequate bracing shall be provided to the compression flanges of secondary members with special attention to those members subject to uplift or outward pressures where no roof or wall sheets are attached to provide such bracing. Sag rods shall not be considered bracing when located in the neutral axis of the web of the secondary members.
Roof purlins and wall girts shall be laterally braced in addition to relying on deck and panel diaphragm action.
The ends and bearing points of secondary members shall be designed to carry 100 percent of dead, live and collateral loads superimposed on them by wind.
Upward or outward forces of wind are to be calculated without live and collateral loads. When downward or inward forces caused by wind are involved, the dead forces plus collateral load forces must be combined but the roof live load may be omitted.
Cables and rods shall not be used as lateral bracing in habitable structures. Lateral bracing, when used, shall have a slenderness ratio of 300 or less, unless restricted by any other section of this code.
All doors shall be anchored as part of the frame in the closed position.
See Section 2222 for additional requirements for metal building systems and components.
CHAIN LINK FENCE MINIMUM REQUIREMENTS
Fence Height (ft)
Terminal Post Dimensions
(o.d. x wall
thickness)
(in inches)
Line Post Dimensions
(o.d. x wall
thickness)
(in inches)
Terminal Post Concrete
Foundation Size
(diameter x depth)
(in inches)
Line Post Concrete
Foundation Size
(diameter x depth)
(in inches)
Up to 4 2 3/8 × 0.042 1 5/8 × 0.047 10 × 24 8 × 24
Over 4 to 5 2 3/8 × 0.042 1 7/8 × 0.055 10 × 24 8 × 24
Over 5 to 6 2 3/8 × 0.042 1 7/8 × 0.065 10 × 24 8 × 24
Over 6 to 8 2 3/8 × 0.110 2 3/8 × 0.095 10 × 36 10 × 36
Over 8 to 10 2 7/8 × 0.110 2 3/8 × 0.130 12 × 40 10 × 40
Over 10 to 12 2 7/8 × 0.160 2 7/8 × 0.120 12 × 42 12 × 42
For SI: 1 inch = 25.4 mm.
NOTES:
  1. This table is applicable only to fences with unrestricted airflow.
  2. Fabric: 121/2 gauge minimum.
  3. Tension bands: Use one less than the height of the fence in feet evenly spaced.
  4. Fabric ties: Must be minimum the same gauge of the fabric.
  5. Fabric tie spacing on the top rail: Five ties between posts, evenly spaced.
  6. Fabric tie spacing on line posts: One less than height of the fence in feet, evenly spaced.
  7. Either top rail or top tension wire shall be used.
  8. Braces must be used at terminal posts if top tension wire is used instead of top rail.
  9. Post spacing: 10 foot (3 m) on center maximum.
  10. Posts shall be embedded to within 6 inches (152 mm) from the bottom of the foundation.
  11. In order to follow the contour of the land, the bottom of the fence may clear the contour of the ground by up to 5 inches (127 mm) without increasing table values to the next higher limit.
Chain link fences in excess of 12 feet (3.7 m) in height shall be designed according to the loads specified in Chapter 16 (High-Velocity Hurricane Zones).
Chain link fences less than 12 feet (3.7 m) in height shall be designed according to the loads specified in Chapter 16 (High-Velocity Hurricane Zones) or may be constructed to meet the minimum requirements specified in Table 2224.
Linked Resources
P
P Premium Feature

This feature is included in the premium subscription. Visit the feature page to learn more.

Learn More
Bookmarks
P
P Premium Feature

This feature is included in the premium subscription. Visit the feature page to learn more.

Learn More