ADOPTS WITH AMENDMENTS:

International Building Code 2018 (IBC 2018)

Heads up: There are no amended sections in this chapter.
The provisions of this chapter shall govern the quality, workmanship and requirements for materials covered. Materials of construction and tests shall conform to the applicable standards listed in this code.
New building materials, equipment, appliances, systems or methods of construction not provided for in this code, and any material of questioned suitability proposed for use in the construction of a building or structure, shall be subjected to the tests prescribed in this chapter and in the approved rules to determine character, quality and limitations of use.
An approved agency shall provide all information as necessary for the building official to determine that the agency meets the applicable requirements specified in Sections 1703.1.1 through 1703.1.3.
An approved agency shall be objective, competent and independent from the contractor responsible for the work being inspected. The agency shall also disclose to the building official and the registered design professional in responsible charge possible conflicts of interest so that objectivity can be confirmed.
An approved agency shall have adequate equipment to perform required tests. The equipment shall be periodically calibrated.
An approved agency shall employ experienced personnel educated in conducting, supervising and evaluating tests and special inspections.
Any material, appliance, equipment, system or method of construction meeting the requirements of this code shall be approved in writing after satisfactory completion of the required tests and submission of required test reports.
For any material, appliance, equipment, system or method of construction that has been approved, a record of such approval, including the conditions and limitations of the approval, shall be kept on file in the building official's office and shall be available for public review at appropriate times.
Specific information consisting of test reports conducted by an approved agency in accordance with the appropriate referenced standards, or other such information as necessary, shall be provided for the building official to determine that the product, material or assembly meets the applicable code requirements.
Sufficient technical data shall be submitted to the building official to substantiate the proposed use of any product, material or assembly. If it is determined that the evidence submitted is satisfactory proof of performance for the use intended, the building official shall approve the use of the product, material or assembly subject to the requirements of this code. The costs, reports and investigations required under these provisions shall be paid by the owner or the owner's authorized agent.
Supporting data, where necessary to assist in the approval of products, materials or assemblies not specifically provided for in this code, shall consist of valid research reports from approved sources.
Products, materials or assemblies required to be labeled shall be labeled in accordance with the procedures set forth in Sections 1703.5.1 through 1703.5.4.
An approved agency shall test a representative sample of the product, material or assembly being labeled to the relevant standard or standards. The approved agency shall maintain a record of the tests performed. The record shall provide sufficient detail to verify compliance with the test standard.
The approved agency shall periodically perform an inspection, which shall be in-plant if necessary, of the product or material that is to be labeled. The inspection shall verify that the labeled product, material or assembly is representative of the product, material or assembly tested.
The label shall contain the manufacturer's identification, model number, serial number or definitive information describing the performance characteristics of the product, material or assembly and the approved agency's identification.
Information required to be permanently identified on the product, material or assembly shall be acid etched, sand blasted, ceramic fired, laser etched, embossed or of a type that, once applied, cannot be removed without being destroyed.
Where structural components or other items regulated by this code are not visible for inspection after completion of a prefabricated assembly, the owner or the owner's authorized agent shall submit a report of each prefabricated assembly. The report shall indicate the complete details of the assembly, including a description of the assembly and its components, the basis upon which the assembly is being evaluated, test results and similar information and other data as necessary for the building official to determine conformance to this code. Such a report shall be approved by the building official.
Copies of necessary test and special inspection records shall be filed with the building official.
The design strengths and permissible stresses of any structural material that are identified by a manufacturer's designation as to manufacture and grade by mill tests, or the strength and stress grade is otherwise confirmed to the satisfaction of the building official, shall conform to the specifications and methods of design of accepted engineering practice or the approved rules in the absence of applicable standards.
For materials that are not specifically provided for in this code, the design strengths and permissible stresses shall be established by tests as provided for in Section 1707.
In the absence of approved rules or other approved standards, the building official shall make, or cause to be made, the necessary tests and investigations; or the building official shall accept duly authenticated reports from approved agencies in respect to the quality and manner of use of new materials or assemblies as provided for in Section 104.11. The cost of all tests and other investigations required under the provisions of this code shall be borne by the owner or the owner's authorized agent.
Whenever there is a reasonable doubt as to the stability or load-bearing capacity of a completed building, structure or portion thereof for the expected loads, an engineering assessment shall be required. The engineering assessment shall involve either a structural analysis or an in-situ load test, or both. The structural analysis shall be based on actual material properties and other as-built conditions that affect stability or load-bearing capacity, and shall be conducted in accordance with the applicable design standard. If the structural assessment determines that the load-bearing capacity is less than that required by the code, load tests shall be conducted in accordance with Section 1708.2. If the building, structure or portion thereof is found to have inadequate stability or load-bearing capacity for the expected loads, modifications to ensure structural adequacy or the removal of the inadequate construction shall be required.
Structural components and assemblies shall be tested in accordance with the appropriate referenced standards. In the absence of a standard that contains an applicable load test procedure, the test procedure shall be developed by a registered design professional and approved. The test procedure shall simulate loads and conditions of application that the completed structure or portion thereof will be subjected to in normal use.
In-situ load tests shall be conducted in accordance with Section 1708.3.1 or 1708.3.2 and shall be supervised by a registered design professional. The test shall simulate the applicable loading conditions specified in Chapter 16 as necessary to address the concerns regarding structural stability of the building, structure or portion thereof.
Where a referenced standard contains an applicable load test procedure and acceptance criteria, the test procedure and acceptance criteria in the standard shall apply. In the absence of specific load factors or acceptance criteria, the load factors and acceptance criteria in Section 1708.3.2 shall apply.

In the absence of applicable load test procedures contained within a standard referenced by this code or acceptance criteria for a specific material or method of construction, such existing structure shall be subjected to a test procedure developed by a registered design professional that simulates applicable loading and deformation conditions. For components that are not a part of the seismic force-resisting system, at a minimum the test load shall be equal to the specified factored design loads. For materials such as wood that have strengths that are dependent on load duration, the test load shall be adjusted to account for the difference in load duration of the test compared to the expected duration of the design loads being considered. For statically loaded components, the test load shall be left in place for a period of 24 hours. For components that carry dynamic loads (e.g., machine supports or fall arrest anchors), the load shall be left in place for a period consistent with the component's actual function. The structure shall be considered to have successfully met the test requirements where the following criteria are satisfied:

  1. Under the design load, the deflection shall not exceed the limitations specified in Section 1604.3.
  2. Within 24 hours after removal of the test load, the structure shall have recovered not less than 75 percent of the maximum deflection.
  3. During and immediately after the test, the structure shall not show evidence of failure.
Where proposed construction is not capable of being designed by approved engineering analysis, or where proposed construction design method does not comply with the applicable material design standard, the system of construction or the structural unit and the connections shall be subjected to the tests prescribed in Section 1709. The building official shall accept certified reports of such tests conducted by an approved testing agency, provided that such tests meet the requirements of this code and approved procedures.
Where specific load test procedures, load factors and acceptance criteria are included in the applicable referenced standards, such test procedures, load factors and acceptance criteria shall apply. In the absence of specific test procedures, load factors or acceptance criteria, the corresponding provisions in Section 1709.3 shall apply.
Where load test procedures are not specified in the applicable referenced standards, the load-bearing and deformation capacity of structural components and assemblies shall be determined on the basis of a test procedure developed by a registered design professional that simulates applicable loading and deformation conditions. For components and assemblies that are not a part of the seismic force-resisting system, the test shall be as specified in Section 1709.3.1. Load tests shall simulate the applicable loading conditions specified in Chapter 16.

The test assembly shall be subjected to an increasing superimposed load equal to not less than two times the superimposed design load. The test load shall be left in place for a period of 24 hours. The tested assembly shall be considered to have successfully met the test requirements if the assembly recovers not less than 75 percent of the maximum deflection within 24 hours after the removal of the test load. The test assembly shall then be reloaded and subjected to an increasing superimposed load until either structural failure occurs or the superimposed load is equal to two and one-half times the load at which the deflection limitations specified in Section 1709.3.2 were reached, or the load is equal to two and one-half times the superimposed design load. In the case of structural components and assemblies for which deflection limitations are not specified in Section 1709.3.2, the test specimen shall be subjected to an increasing superimposed load until structural failure occurs or the load is equal to two and one-half times the desired superimposed design load. The allowable superimposed design load shall be taken as the lesser of:

  1. The load at the deflection limitation given in Section 1709.3.2.
  2. The failure load divided by 2.5.
  3. The maximum load applied divided by 2.5.
The deflection of structural members under the design load shall not exceed the limitations in Section 1604.3. The HVHZ shall comply with Section 1616.3.1.
Load-bearing wall and partition assemblies shall sustain the test load both with and without window framing. The test load shall include all design load components. Wall and partition assemblies shall be tested both with and without door and window framing.

The design pressure rating of exterior windows and doors in buildings shall be determined in accordance with Section 1709.5.1 or 1709.5.2. For the purposes of this section, the required design pressure shall be determined using the allowable stress design load combinations of Section 1605.3.

Exception: Custom doors. Custom (one-of-a-kind) exterior door assemblies shall be tested by an approved testing laboratory or be designed and engineered in accordance with accepted engineering practices by a Florida registered design professional. Signed and sealed copies of the rational analysis and calculations shall be provided to the building official upon permit application.

Exterior windows and sliding doors shall be tested and labeled as conforming to AAMA/WDMA/CSA101/I.S.2/A440 or TAS 202 (HVHZ shall comply with TAS 202 and ASTM E1300 or Section 2404). Exterior side-hinged doors shall be tested and labeled as conforming to AAMA/WDMA/CSA101/I.S.2/A440 or comply with Section 1709.5.2. Products tested and labeled as conforming to AAMA/WDMA/CSA101/I.S.2/A440 shall not be subject to the requirements of Sections 2403.2 and 2403.3. Exterior windows and doors shall be labeled with a permanent label, marking, or etching providing traceability to the manufacturer and product. The following shall also be required either on a permanent label or on a temporary supplemental label applied by the manufacturer: information identifying the manufacturer, the product model/series number, positive and negative design pressure rating, product maximum size tested, impact-resistant rating if applicable, Florida product approval number or Miami-Dade product approval number, applicable test standard(s), and approved product certification agency, testing laboratory, evaluation entity or Miami-Dade product approval.

The labels are limited to one design pressure rating per referenced standard. The temporary supplemental label shall remain on the window or door until final approval by the building official.

Exceptions:

  1. Door assemblies installed in nonhabitable areas where the door assembly and area are designed to accept water infiltration need not be tested for water infiltration.
  2. Door assemblies installed where the overhang (OH) ratio is equal to or more than 1 need not be tested for water infiltration. The overhang ratio shall be calculated by the following equation:

    OH ratio = OH Length/OH Height

    where:

    OH length = The horizontal measure of how far an overhang over a door projects out from door surface.

    OH height = The vertical measure of the distance from the door sill to the bottom of the overhang over a door.

  3. Structural wind load design pressures for window and door assemblies other than the size tested in accordance with Section 1709.5.1 shall be permitted to be different than the design value of the tested assembly provided such different pressures are determined by accepted engineering analysis. All components of the alternate size assembly shall be the same as the tested or labeled assembly; however, lineal components shall be permitted to vary in length compared to the tested or labeled assembly.

    1. Operable windows and doors rated in this manner shall comply with the following:

      1. For windows and doors (other than sliding or bi-fold), the frame area of the alternate size unit shall not exceed the frame area of the tested approved unit.
      2. For sliding or bi-fold doors, the panel area of the alternate size unit shall not exceed the panel area of the tested approved unit.
      3. Shall vary from the tested approved unit only in width, height or load requirements.
      4. Shall not exceed 100 percent of the proportional deflection and fiber stress of the intermediate members of the approved unit.
      5. Shall not exceed 100 percent of the concentrated load at the juncture of the intermediate members and the frame of the approved unit.
      6. Shall not exceed the air and water infiltration resistance of the tested approved unit.
      7. Shall not exceed the maximum cyclic pressure of the tested approved unit when tested in accordance with TAS 201 and TAS 203 or ASTM E1886 and ASTM E1996 where applicable.
    2. Nonoperable windows and doors rated in this manner shall comply with the following:

      1. The frame area of the alternate size unit shall not exceed the frame area of the tested approved unit.
      2. Shall vary from the tested approved unit only in width, height or load requirements.
      3. The maximum uniform load distribution (ULD) of any side shall be equal to the uniform load carried by the side divided by the length of the side.
      4. The ULD of any member shall not exceed the ULD of the corresponding member of the tested approved unit.
      5. The ULD of each member shall be calculated in accordance with standard engineering analysis.
      6. Shall not exceed the air and water infiltration resistance of the tested approved unit.
      7. Shall not exceed the maximum cyclic pressure of the tested approved unit when tested in accordance with TAS 201 and TAS 203 or ASTM E1886 and ASTM E1996 where applicable.
  4. Pass-through windows for serving from a single-family kitchen, where protected by a roof overhang of 5 feet (1.5 m) or more shall be exempted from the requirements of the water infiltration test.

Exterior window and door assemblies shall be tested in accordance with ASTM E330 or TAS 202 (HVHZ shall comply with TAS 202). Exterior window and door assemblies containing glass shall comply with Section 2403. The design pressure for testing shall be calculated in accordance with Chapter 16. Each assembly shall be tested for 10 seconds at a load equal to 1.5 times the design pressure.

Exceptions:

  1. Door assemblies installed in nonhabitable areas where the door assembly and area are designed to accept water infiltration need not be tested for water infiltration.
  2. Door assemblies installed where the overhang (OH) ratio is equal to or more than 1 need not be tested for water infiltration. The overhang ratio shall be calculated by the following equation:

    OH ratio = OH Length/OH Height

    where:

    OH Length = The horizontal measure of how far an overhang over a door projects out from the door's surface.

    OH Height = The vertical measure of the distance from the door's sill to the bottom of the overhang over a door.

  3. For window and door assemblies tested in accordance with this section, structural wind load design pressures for window and door assemblies other than the size tested in accordance with this section shall be permitted to be different than the design value of the tested assembly provided such different pressures are determined by accepted engineering analysis. All components of the alternate size assembly shall be the same as the tested assembly except for length. Where engineering analysis is used, the glass shall comply with Section 2403.
Sectional garage doors and rolling doors shall be tested for determination of structural performance under uniform static air pressure difference in accordance with ANSI/DASMA 108, ASTM E330 Procedure A, or TAS 202. For sectional garage doors and rolling doors tested in accordance with ASTM E330, acceptance criteria shall be in accordance with ANSI/DASMA 108. (HVHZ shall comply with TAS 202.) Design pressures shall be determined from Table 1609.6(1) or ASCE 7. The design pressures, as determined from ASCE 7, are permitted to be multiplied by 0.6.
Garage doors shall be labeled with a permanent label provided by the garage door manufacturer. The label shall identify the garage door manufacturer, the garage door model/series number, the positive and negative design pressure rating, indicate impact rated if applicable, the installation instruction drawing reference number, the Florida product approval or MiamiDade product approval number if applicable, and the applicable test standards. The required garage door components for an approved garage door assembly may be indicated using a checklist form on the label. If a checklist format is used on the label, the door installer or the garage door manufacturer shall mark the selected components on the checklist that are required to assemble an approved garage door system. The installation instructions shall be provided and available on the job site.
Door components evaluated by an approved product evaluation entity, certification agency, testing laboratory or engineer may be interchangeable in exterior door assemblies provided that the door components provide equal or greater structural performance as demonstrated by accepted engineering practices.
Test specimens and construction shall be representative of the materials, workmanship and details normally used in practice. The properties of the materials used to construct the test assembly shall be determined on the basis of tests on samples taken from the load assembly or on representative samples of the materials used to construct the load test assembly. Required tests shall be conducted or witnessed by an approved agency.
Mullions or mulled fenestration assemblies shall be tested by an approved testing laboratory in accordance with either ASTM E330, or TAS 202 (HVHZ shall comply with TAS 202), or shall be engineered using accepted engineering practice such as AAMA 450. Mullions tested as stand-alone units or qualified by engineering shall use performance criteria cited in Sections 1709.8.1, 1709.8.2 and 1709.8.3.
Mullions shall be designed to transfer the design pressure loads applied by the window and door assemblies to the rough opening substrate.
Mullions shall be capable of resisting the design pressure loads applied by the window and door assemblies to be supported without deflecting more than L/175, for spans up to and including 13 feet 6 inches, and L/240 + 1/4 inch for spans over 13 feet 6 inches, where L is the span of the mullion in inches.
Mullions that are tested by an approved testing laboratory shall be capable of resisting a load of 1.5 times the design pressure loads applied by the window and door assemblies to be supported. The design pressures, as determined from ASCE 7, are permitted to be multiplied by 0.6. Mullions that are qualified by engineering shall be capable of resisting the design pressure loads applied by the window and door assemblies to be supported without exceeding the allowable stress of the mullion elements.
Glazed curtain wall, window wall and storefront systems shall be tested in accordance with the requirements of this section and the laboratory test requirements of the American Architectural Manufacturers Association (AAMA) Standard 501, HVHZ shall comply with Section 2411.3.2.1.1.
A permanent label shall be provided by the product approval holder on all impact-resistant coverings.

The following information shall be included on the labels on impact-resistant coverings:

  1. Product approval holder name and address.
  2. All applicable methods of approval. Methods of approval include, but are not limited to Miami-Dade NOA; Florida Building Commission, TDI Product Evaluation; ICC-ES.
  3. The test standard or standards specified in Section 1609.1.2, including standards referenced within the test standards specified in Section 1609.1.2 used to demonstrate code compliance.
  4. For products with a Florida product approval number or a Miami-Dade County Building and Neighborhood Compliance Department Notice of Acceptance Number (NOA), such numbers shall be included on the label.

The location of the label on the impact-resistant covering shall be as follows:

  1. Accordions: Bottom of the locking bar or center mate facing the exterior or outside.
  2. Rollup: On the bottom of the hood facing the exterior or outside or on the bottom slat facing the exterior or outside.
  3. Bahama Awning or Colonial Hinged: On the bottom, placed on the back of the shutter.
  4. Panels: For metal and plastic panels, the label may be embossed or printed spaced not more than every 3 lineal feet on each panel. The label shall be applied by the holder of the product approval and shall face the exterior or outside.
  5. Framed products: The label shall be on the side or bottom facing the exterior or outside.
  6. Labels on all other products shall face the exterior or outside.
All impact-resistant coverings shall be installed in accordance with the manufacturer's installation instructions and in accordance with the product approval. Installation instructions shall be provided and shall be available to inspection personnel on the job site. Opening protection components, fasteners, and other parts evaluated by an approved product evaluation entity, certification agency, testing laboratory, architect, or engineer and approved by the holder of the product approval may be interchangeable in opening protection assemblies provided that the opening protection component(s) provide equal or greater structural performance and durability as demonstrated by testing in accordance with approved test standards.
Manufactured soffit materials and systems shall be subject to statewide or local product approval as specified in Florida Administrative Code Rule 61G-20. The net free area of the manufactured soffit material or system shall be included in the product approval submittal documents.
Individual manufactured soffit pieces shall be marked at not more than 4 feet (1.2 m) on center with a number or marking that ties the product back to the manufacturer.

The following information shall be included on the manufactured soffit material packaging or on the individual manufactured soffit material or system pieces:

  1. Product approval holder and/or manufacturer name and city and state of manufacturing plant.
  2. Product model number or name.
  3. Method of approval and approval numbers as applicable. Methods of approval include, but are not limited to: Florida Building Commission FL #; MiamiDade NOA; TDI Product Evaluation; and ICC-ES.
  4. The test standard or standards specified in Chapter 14 used to demonstrate code compliance.
  5. The net free area shall be included on the packaging or label.
The methods cited in this section apply only to anchorage of window and door assemblies to the main windforce-resisting system.
Window and door assemblies shall be anchored in accordance with the published manufacturer's recommendations to achieve the design pressure specified. Substitute anchoring systems used for substrates not specified by the fenestration manufacturer shall provide equal or greater anchoring performance as demonstrated by accepted engineering practice.

Where the wood shim or buck thickness is less than 11/2 inches (38 mm), window and door assemblies shall be anchored through the main frame or by jamb clip or subframe system, in accordance with the manufacturer's published installation instructions. Anchors shall be securely fastened directly into the masonry, concrete or other structural substrate material. Unless otherwise tested, bucks shall fully support the window or door frame. Shims shall be made from materials capable of sustaining applicable loads, located and applied in a thickness capable of sustaining applicable loads. Anchors shall be provided to transfer load from the window or door frame to the rough opening substrate.

Where the wood buck thickness is 11/2 inches (38 mm) or greater, the buck shall be securely fastened to transfer load to the masonry, concrete or other structural substrate and the buck shall fully support the window or door frame. Window and door assemblies shall be anchored through the main frame or by jamb clip or subframe system or through the flange to the secured wood buck in accordance with the manufacturer's published installation instructions. Unless otherwise tested, bucks shall fully support the window or door. Shims shall be made from materials capable of sustaining applicable loads, located and applied in a thickness capable of sustaining applicable loads. Anchors shall be provided to transfer load from the window or door frame assembly to the secured wood buck.

Where the framing material is wood or other approved framing material, window and door assemblies shall be anchored through the main frame or by jamb clip or subframe system or through the flange in accordance with the manufacturer's published installation instructions. Shims shall be made from materials capable of sustaining applicable loads, located and applied in a thickness capable of sustaining applicable loads. Anchors shall be provided to transfer load from the window or door frame to the rough opening substrate.
UpCodes Premium
Leverage the most sophisticated code compliance platform.
TRY FREE FOR TWO WEEKS VISIT PRICING