ADOPTS WITH AMENDMENTS:

International Building Code 2015 (IBC 2015)

Heads up: There are no amended sections in this chapter.

The provisions of this chapter and the Florida Building Code, Plumbing shall govern the erection, installation, alteration, repairs, relocation, replacement, addition to, use or maintenance of plumbing equipment and systems. Toilet and bathing rooms shall be constructed in accordance with Section 1210. Plumbing systems and equipment shall be constructed, installed and maintained in accordance with the Florida Building Code, Plumbing. Private sewage disposal systems shall conform to Chapter 64E—6, Florida Administrative Code, for Onsite Sewage Treatment and Disposal Systems.

Plumbing fixtures shall be provided in the minimum number as shown in Table 2902.1 based on the actual use of the building or space. Uses not shown in Table 2902.1 shall be considered individually by the code official. The number of occupants shall be determined by this code.

[P] TABLE 2902.1

MINIMUM NUMBER OF REQUIRED PLUMBING FIXTURESa (See Sections 2902.1.1 and 2902.2)

No.CLASSIFICATIONOCCUPANCYDESCRIPTIONWATER CLOSETS
(URINALS SEE

SECTION 419.2 OF
THE Florida Building Code, Plumbing)
LAVATORIESBATHTUBS/
SHOWERS
DRINKING
FOUNTAINS

(SEE

SECTION 410 OF THE
Florida Building Code, Plumbing)
OTHER
MaleFemaleMaleFemale
1AssemblyA-1dTheaters and other
buildings for the per-
forming arts and motion
pictures
1 per 1251 per 651 per 2001 per 5001 service
sink
A-2dNightclubs, bars, taverns,
dance halls and
buildings for similar
purposes
1 per 401 per 401 per 751 per 5001 service
sink
Restaurants, banquet
halls and food courts
1 per 751 per 751 per 2001 per 5001 service
sink
A-3dAuditoriums without
permanent seating, art
galleries, exhibition
halls, museums, lecture
halls, libraries, arcades
and gymnasiums
1 per 1251 per 651 per 2001 per 5001 service
sink
Passenger terminals and
transportation facilities
1 per 5001 per 5001 per 7501 per 1,0001 service
sink
Places of worship and
other religious services
1 per 1501 per 751 per 2001 per 1,0001 service
sink
A-4Coliseums, arenas,
skating rinks,
pools and tennis
courts for indoor
sporting events and
activities
1 per 75 for
the first
1,500 and 1
per 120 for
the remainder
exceeding 1,500
1 per 40 for
the first
1,520 and 1
per 60 for
the remainder
exceeding 1,520
1 per 2001 per 1501 per 1,0001 service
sink
A-5Stadiums, amusement
parks, bleachers and
outdoor sporting
events and
activities
1 per 75 for
the first
1,500 and 1
per 120 for
the remainder
exceeding 1,500
1 per 40 for
the first
1,520 and 1
per 60 for
the remainder
exceeding 1,520
1 per 2001 per 1501 per 1,0001 service
sink
2BusinessBBuildings for the
transaction of business,
professional
services, other services
involving merchandise,
office buildings,
banks, light industrial
and similar uses
1 per 25 for the first 50
and 1 per 50 for the
remainder exceeding 50
1 per 40 for the
first 80 and 1 per
80 for the
remainder
exceeding 80
1 per 1001 service
sinke
3EducationalEEducational 1 per 501 per 501 per 1001 service
sink
4Factory and industrialF-1 and F-2Structures in which
occupants are
engaged in work
fabricating, assembly
or processing
of products or
materials
1 per 1001 per 100See Florida Building Code, Plumbing1 per 4001 service
sink
5InstitutionalI-1Residential care1 per 101 per 101 per 81 per 1001 service
sink
I-2Hospitals, ambulatory
nursing home
care recipientb
1 per roomc1 per roomc1 per 151 per 1001 service
sink
Employees, other careb1 per 251 per 351 per 100
Visitors, other than 1 per 751 per 1001 per 500
I-3Prisonsb1 per cell1 per cell1 per 151 per 1001 service
sink
I-3Reformatories,
detention centers
and correctional
centersb
1 per 151 per 151 per 151 per 1001 service
sink
Employeesb1 per 251 per 351 per 100
I-4Adult day care and
child day care
1 per 151 per 1511 per 1001 service
sink
6MercantileMRetail stores,
service stations,
shops, salesrooms,
markets and shop-
ping centers
1 per 5001 per 7501 per 1,0001 service
sinke
7ResidentialR-1Hotels, motels, (transient)1 per sleeping
unit
1 per sleeping
unit
1 per
sleeping
unit
1 service
sink
R-2Dormitories, fraternities,
sororities
and boarding
houses (not transient)
1 per 101 per 101 per 81 per 1001 service
sink
R-2Apartment house1 per dwelling
unit
1 per dwelling
unit
1 per unit1 kitchen sink
unit; 1 automatic
clothes washer
connection per 20
dwelling units
R-3One- and two-family
with five or fewer
guest rooms
1 per dwelling
unit
1 per 101 per unit1 kitchen sink
unit; 1 automatic
clothes washer
connection per
dwelling unit
R-3Congregate living
facilities with 16 or
fewer persons
1 per 101 per 101 per 81 per 1001 service sink
R-4Congregate living
facilities with 16 or
fewer persons
1 per 101 per 101 per 81 per 1001 service sink
8StorageS-1 Structures for the
storage of goods,
warehouses, store-
houses and freight
depots, low and
moderate hazard
1 per 1001 per 100See
Section 411 of the
Florida Building Code, Plumbing
1 per 1,0001 service sink
  1. The fixtures shown are based on one fixture being the minimum required for the number of persons indicated or any fraction of the number of persons indicated. The number of occupants shall be determined by this code.
  2. Toilet facilities for employees shall be separate from facilities for inmates or care recipients.
  3. A single-occupant toilet room with one water closet and one lavatory serving not more than two adjacent patient sleeping units shall be permitted, provided that each patient sleeping unit has direct access to the toilet room and provisions for privacy for the toilet room user are provided.
  4. The occupant load for seasonal outdoor seating and entertainment areas shall be included when determining the minimum number of facilities required.
  5. For business and mercantile occupancies with an occupant load of 15 or fewer, service sinks shall not be required.

To determine the occupant load of each sex, the total occupant load shall be divided in half. To determine the required number of fixtures, the fixture ratio or ratios for each fixture type shall be applied to the occupant load of each sex in accordance with Table 2902.1. Fractional numbers resulting from applying the fixture ratios of Table 2902.1 shall be rounded up to the next whole number. For calculations involving multiple occupancies, such fractional numbers for each occupancy shall first be summed and then rounded up to the next whole number.

Exception: The total occupant load shall not be required to be divided in half where approved statistical data indicate a distribution of the sexes of other than 50 percent of each sex.

Fixtures located within family or assisted-use toilet and bathing rooms required by Section 1109.2.1 are permitted to be included in the number of required fixtures for either the male or female occupants in assembly and mercantile occupancies.

Where plumbing fixtures are required, separate facilities shall be provided for each sex.

Exceptions:

  1. Separate facilities shall not be required for dwelling units and sleeping units.
  2. Separate facilities shall not be required in structures or tenant spaces with a total occupant load, including both employees and customers, of 15 or fewer.
  3. Separate facilities shall not be required in mercantile occupancies in which the maximum occupant load is 100 or less.
Where a building or tenant space requires a separate toilet facility for each sex and each toilet facility is required to have only one water closet, two family or assisted-use toilet facilities shall be permitted to serve as the required separate facilities. Family or assisted-use toilet facilities shall not be required to be identified for exclusive use by either sex as required by Section 2902.4.

Customers, patrons and visitors shall be provided with public toilet facilities in structures and tenant spaces intended for public utilization. The number of plumbing fixtures located within the required toilet facilities shall be provided in accordance with Section 2902.1 for all users. Employees shall be provided with toilet facilities in all occupancies. Employee toilet facilities shall be either separate or combined employee and public toilet facilities.

Exception: Public toilet facilities shall not be required in:

  1. Open or enclosed parking garages where there are no parking attendants.
  2. Structures and tenant spaces intended for quick transactions, including takeout, pickup and drop-off, having a public access area less than or equal to 300 square feet (28 m2).

[P] 2902.3.1 Access

ILLUSTRATION
The route to the public toilet facilities required by Section 2902.3 shall not pass through kitchens, storage rooms or closets. Access to the required facilities shall be from within the building or from the exterior of the building. Routes shall comply with the accessibility requirements of this code. The public shall have access to the required toilet facilities at all times that the building is occupied.

In occupancies other than covered and open mall buildings, the required public and employee toilet facilities shall be located not more than one story above or below the space required to be provided with toilet facilities, and the path of travel to such facilities shall not exceed a distance of 500 feet (152 m).

Exception: The location and maximum distances of travel to required employee facilities in factory and industrial occupancies are permitted to exceed that required by this section, provided that the location and maximum distance of travel are approved.

In covered and open mall buildings, the required public and employee toilet facilities shall be located not more than one story above or below the space required to be provided with toilet facilities, and the path of travel to such facilities shall not exceed a distance of 300 feet (91 mm). In mall buildings, the required facilities shall be based on total square footage (m2) within a covered mall building or within the perimeter line of an open mall building, and facilities shall be installed in each individual store or in a central toilet area located in accordance with this section. The maximum distance of travel to central toilet facilities in mall buildings shall be measured from the main entrance of any store or tenant space. In mall buildings, where employees' toilet facilities are not provided in the individual store, the maximum distance of travel shall be measured from the employees' work area of the store or tenant space.
Where pay facilities are installed, such facilities shall be in excess of the required minimum facilities. Required facilities shall be free of charge.
Where a toilet room is provided for the use of multiple occupants, the egress door for the room shall not be lockable from the inside of the room. This section does not apply to family or assisted-use toilet rooms.
Toilet rooms shall not open directly into a room used for the preparation of food for service to the public.
Required public facilities shall be provided with signs that designate the sex as required by Section 2902.2. Signs shall be readily visible and located near the entrance to each toilet facility. Signs for accessible toilet facilities shall comply with the Florida Building Code, Accessibility.
Directional signage indicating the route to the required public toilet facilities shall be posted in a lobby, corridor, aisle or similar space, such that the sign can be readily seen from the main entrance to the building or tenant space.
Drinking fountains shall not be required to be located in individual tenant spaces provided that public drinking fountains are located within a distance of travel of 500 feet (152 m) of the most remote location in the tenant space and not more than one story above or below the tenant space. Where the tenant space is in a covered or open mall, such distance shall not exceed 300 feet (91 440 mm). Drinking fountains shall be located on an accessible route.
Drinking fountains shall not be required for an occupant load of 15 or fewer.
UpCodes Premium
Leverage the most sophisticated code compliance platform.
TRY FREE FOR TWO WEEKS VISIT PRICING