CODES

ADOPTS WITH AMENDMENTS:

International Green Construction Code 2012 (IGCC 2012)

Chapter 1 Scope and Administration

Chapter 1 SCOPE AND ADMINISTRATION

Chapter 2 Definitions

Chapter 3 Jurisdictional Requirements and Life Cycle Assessment

Chapter 4 Site Development and Land Use

Chapter 5 Material Resource Conservation and Efficiency

Chapter 6 ENERGY CONSERVATION, EFFICIENCY AND CO2e EMISSION REDUCTION

Chapter 7 Water Resource Conservation, Quality and Efficiency

Chapter 8 Indoor Environmental Quality and Comfort

Chapter 9 Commissioning, Operation and Maintenance

Chapter 10 Existing Buildings

Chapter 11 Existing Building Site Development

Chapter 12 Referenced Standards

Appendix A Project Electives

Appendix B Radon Mitigation

Appendix C Optional Ordinance

Appendix D Enforcement Procedures

NORMATIVE APPENDIX A— PRESCRIPTIVE BUILDING ENVELOPE TABLES

NORMATIVE APPENDIX B— PRESCRIPTIVE CONTINUOUS AIR BARRIER

NORMATIVE APPENDIX C— PRESCRIPTIVE EQUIPMENT EFFICIENCY TABLES

NORMATIVE APPENDIX D— PERFORMANCE OPTION FOR ENERGY EFFICIENCY

NORMATIVE APPENDIX E— IAQ LIMIT REQUIREMENTS FOR OFFICE FURNITURE SYSTEMS AND SEATING

NORMATIVE APPENDIX F— BUILDING CONCENTRATIONS

INFORMATIVE APPENDIX G—INFORMATIVE REFERENCES

INFORMATIVE APPENDIX H— INTEGRATED DESIGN

INFORMATIVE APPENDIX I— ADDENDA DESCRIPTION INFORMATION

This chapter provides requirements for the development and maintenance of building and building sites to minimize negative environmental impacts and to protect, restore and enhance the natural features and environmental quality of the site.
An inventory and assessment of the natural resources and baseline conditions of the building site shall be submitted with the construction documents. The inventory and assessment shall:
1. Determine the location of any protection areas identified in Section 402.1 that are located on, or adjacent to, the building site;
2. Determine whether, and to the degree to which, the native soils and hydrological conditions of the building site have been disturbed and altered by previous use or development;
  1. Identify how soils will be prepared, amended and placed in a manner that establishes or restores the ability of the soil to support the vegetation that has been protected and that will be planted;
  2. Identify invasive plant species on the site for removal; and
  3. Identify native plant species on the site.

402.1 Protection by Area

STATE AMENDMENT
Where flood hazard areas, surface water bodies or wetlands, conservation areas, parklands, agricultural lands or greenfields are located on, or adjacent to, a lot, the development of the lot as a building site shall comply with the provisions of Sections 402.2 through 402.8.

402.2 Flood Hazard Areas

STATE AMENDMENT
For locations within flood hazard areas, unless compliance with Section 402.2.1 or Section 402.2.2 is required by Table 302.1, new buildings and structures and substantial improvements shall comply with Section 402.2.3.
Where this section is indicated to be applicable in Table 302.1, new buildings and structures, site disturbance, and development of land shall be prohibited within flood hazard areas.
Where this section is indicated to be applicable in Table 302.1, new buildings and structures, site disturbance, and development of land shall be prohibited within the specific flood hazard areas established pursuant to local land use authority.
New buildings, structures and substantial improvements constructed in flood hazard areas shall be in compliance with Section 1612 of the International Building Code provided the lowest floors are elevated or dry floodproofed to not less than 1 foot (25 mm) above the elevation required by Section 1612 of the International Building Code, or the elevation established by the jurisdiction, whichever is higher.
Where this section is indicated to be applicable in Table 302.1, buildings and building site improvements shall not be located over, or located within a buffer as established by the jurisdiction, around or adjacent to oceans, lakes, rivers, streams and other bodies of water that support or could support fish, recreation or industrial use. The buffer shall be measured from the ordinary high-water mark of the body of water.
Exceptions:
1. Buildings and associated site improvements specifically related to the use of the water including, but not limited to, piers, docks, fish hatcheries, and habitat restoration facilities, shall be permitted where the impacts of the construction and location adjacent to or over the water on the habitat is mitigated.
2. Buildings and associated site improvements shall be permitted where a wetlands permit has been issued under a national wetlands permitting program or otherwise issued by the authority having jurisdiction.

402.4 Wetland Protection

STATE AMENDMENT
Buildings and building site improvements shall not be located within a wetland or within a buffer as established by the jurisdiction around a wetland.
Exception: Buildings and associated site improvements specifically related to the use of the wetland including, but not limited to, piers, docks, fish hatcheries, and habitat restoration facilities, shall be permitted where the impacts of the construction and location adjacent to or over the wetland on the habitat are mitigated.

402.5 Conservation Area

STATE AMENDMENT
Where this section is indicated to be applicable in Table 302.1, site disturbance or development of land in or within 50 feet (15 240 mm) of any designated conservation area shall not be permitted.
Exception: Buildings and associated site improvements located in or within 50 feet (15 240 mm) of a conservation area shall be permitted where the building and associated site improvements serve a purpose related to the conservation area as determined by the authority that designated the conservation area.

402.6 Park Land

STATE AMENDMENT
Site disturbance or development of land located within a public park shall not be permitted.
Exceptions:
1. Buildings and site improvements shall be permitted to be located within a park where the building and site improvements serve a park-related purpose.
2. Park lands owned and managed by the Federal government shall be exempt from this prohibition.
3. Privately held property located within the established boundary of a park shall be exempt from this prohibition.

402.7 Agricultural Land

STATE AMENDMENT
Where this section is indicated to be applicable in Table 302.1, buildings and associated site improvements shall not be located on land zoned for agricultural purposes.
Exception: Buildings and associated site improvements shall be permitted to be located on agriculturally zoned land where the building serves an agriculturally related purpose, including, but not limited to, primary residence, farmhouse, migrant workers housing, farm produce storage, processing and shipping.

402.8 Greenfield Sites

STATE AMENDMENT
Where this section is indicated to be applicable in Table 302.1, site disturbance or development shall not be permitted on greenfield sites.
Exception: The development of new buildings and associated site improvements shall be permitted on greenfield sites where the jurisdiction determines that adequate infrastructure exists, or will be provided, and where the sites comply with not less than one of the following:
1. The greenfield site is located within 1/4 mile (0.4 km) of developed residential land with an average density of not less than 8 dwelling units per acre (19.8 dwelling units per hectare).
2. The greenfield site is located within 1/4 mile (0.4 km) distance, measured over roads or designated walking surfaces, of not less than 5 diverse uses and within 1/2 mile (0.8 km) walking distance of not less than 7 diverse uses. The diverse uses shall include not less than one use from each of the following categories of diverse uses: retail, service, or community facility.
3. The greenfield site has access to transit service. The building on the building site shall be located in compliance with one of the following:
3.1. Within 1/4 mile (0.4 km) distance, measured over designated walking surfaces, of existing or planned bus or streetcar stops.
3.2. Within 1/2 mile (0.8 km) distance, measured over designated walking surfaces, of existing or planned rapid transit stops, light or heavy passenger rail stations, ferry terminals, or tram terminals.
4. The greenfield site is located adjacent to areas of existing development that have connectivity of not less than 90 intersections per square mile (35 intersections per square kilometer). Not less than 25 percent of the perimeter of the building site shall adjoin, or be directly across a street, public bikeway or pedestrian pathway from the qualifying area of existing development.
4.1. Intersections included for determination of connectivity shall include the following:
4.1.1. Intersections of public streets with other public streets;
4.1.2. Intersections of public streets with bikeways and pedestrian pathways that are not part of a public street for motor vehicles; and
4.1.3. Intersections of bikeways and pedestrian pathways that are not part of a public street for motor vehicles with other bikeways and pedestrian pathways that are not part of a public street for motor vehicles.
4.2. The following areas need not be included in the determination of connectivity:
4.2.1. Water bodies, including, but not limited to lakes and wetlands.
4.2.2. Parks larger than 1/2 acre (2023 m2), designated conservation areas and areas preserved from development by the jurisdiction or by the state or federal government.
4.2.3. Large facilities including, but not limited to airports, railroad yards, college and university campuses.
For greenfield sites that are permitted to be developed, site disturbances shall be limited to the following areas:
1. Within 40 feet (18 288 mm) of the perimeter of the building;
2. Within 15 feet (4572 mm) of proposed surface walkways, roads, paved areas and utilities;
3. Within 25 feet (7620 mm) of constructed areas with permeable surfaces that require additional staging areas to limit compaction in the constructed areas.

403.1 Stormwater Management

STATE AMENDMENT
Stormwater management systems, including, but not limited to, infiltration, evapo-transpiration; rainwater harvest and runoff reuse; shall be provided and maintained on the building site.

403.1.1 Increased Runoff

STATE AMENDMENT
Stormwater management systems shall address the increase in runoff that would occur resulting from development on the building site and shall either:
1. Manage rainfall onsite and size the management system to retain not less than the volume of a single storm which is equal to the 95th-percentile rainfall event and all smaller storms and maintain the predevelopment natural runoff; or
2. Maintain or restore the predevelopment stable, natural runoff hydrology of the site throughout the development or redevelopment process. Postconstruction runoff rate, volume, and duration shall not exceed predevelopment rates. The stormwater management system design shall be based, in part, on a hydrologic analysis of the building site.
The stormwater management system shall not redirect or concentrate off-site discharge that would cause increased erosion or other drainage related damage to adjoining lots or public property.

403.1.3 Brownfields

STATE AMENDMENT
Stormwater management systems on areas of brownfields where contamination is left in place shall not use infiltration. Stormwater management systems shall not penetrate, damage, or otherwise compromise remediation actions at the building site.

403.2 Coal Tar Sealants

STATE AMENDMENT
Coal tar sealants shall not be used in any application exposed to stormwater, wash waters, condensates, snowmelt, icemelt or any source of water that could convey coal tar sealants into soils, surface waters or groundwaters.
Irrigation of exterior landscaping shall comply with Sections 404.1.1 and 404.1.2.
Outdoor landscape irrigation systems shall be designed and installed to reduce potable water use by 50 percent from a calculated mid-summer baseline in accordance with Section 404.1.2 or, where permitted by State regulation or local ordinances, the system shall be supplied by municipal reclaimed water or with alternate onsite nonpotable water complying with Chapter 7.

Exceptions: Potable water is permitted to be used as follows:

1. During the establishment phase of newly planted landscaping.
2. To irrigate food production.
3. To supplement nonpotable water irrigation of shade trees provided in accordance with Section 408.2.3.
4. Potable water is permitted for landscape irrigation where approved by local ordinance or regulation.
Where in-ground irrigation systems are provided, the systems shall comply with all of the following:
1. The design and installation of outdoor irrigation systems shall be under the supervision of an irrigation professional accredited or certified by an appropriate local or national body.
2. Landscape irrigation systems shall not direct water onto building exterior surfaces, foundations or exterior paved surfaces. Systems shall not generate runoff.
3. Where an irrigation control system is used, the system shall be one that regulates irrigation based on weather, climatological or soil moisture status data. The controller shall have integrated or separate sensors to suspend irrigation events during rainfall.
4. Irrigation zones shall be based on plant water needs with plants of similar need grouped together. Turfgrass shall not be grouped with other plantings on the same zone.
5. Microirrigation zones shall be equipped with pressure regulators that ensure zone pressure is not greater than 40 psi (275.8 kPa), filters, and flush end assemblies.
6. Sprinklers shall:
6.1. Have nozzles with matched precipitation rates.
6.2. Be prohibited on landscape areas less than 4 feet (1230 mm) in any dimension.
6.3. Be prohibited on slopes greater than 1 unit vertical to 4 units horizontal (25-percent slope).

Exception: Where the application rate of the sprinklers is less than or equal to 0.5 inches (12.7 mm) per hour.

6.4. Be permitted for use on turfgrass and crop areas only excepting microsprays of a flow less than 45 gallons (170 liters) per hour.
6.5. If of the pop-up configuration, pop-up to a height of not less than 4 inches (101 mm).
6.6. Only be installed in zones composed exclusively of sprinklers and shall be designed to achieve a lower quarter distribution uniformity of not less than 0.65.
Where available and approved for use by the authority having jurisdiction, alternate nonpotable onsite water sources complying with Chapter 7 shall be used for outdoor ornamental fountains and other water features constructed or installed on a building site. Where the fountain or water feature is the primary user of the building site’s nonpotable water source, a potable makeup water connection is prohibited.
Exception: Outdoor ornamental fountains and water features are allowed to use potable water provided water is recirculated and there is not an automatic refill valve connection to a source of potable water, and provided that either:
1. The catch basin or reservoir is no greater than 100 gallons (379 L); or
2. Less than 20 square feet (1.86 m2) of water surface area is exposed.

404.2.1 Treatment

STATE AMENDMENT
The treatment required to maintain appropriate water quality shall comply with the authority having jurisdiction.

404.2.2 Recirculation

STATE AMENDMENT
Outdoor ornamental fountains and water features shall be equipped to recirculate and reuse the supplied water.

404.2.3 Signage

STATE AMENDMENT
Signage in accordance with Chapter 7 shall be posted at each outdoor ornamental fountain and water feature where nonpotable water is used.
Soil and water quality shall be protected in accordance with Sections 405.1.14through 405.1.6.
A soil and water quality protection plan shall be submitted by the owner and approved prior to construction. The protection plan shall address the following:
1. A soils map, site plan, or grading plan that indicates designated soil management areas for all site soils, including, but not limited to:
1.1. Soils that will be retained in place and designated as vegetation and soil protection areas (VSPAs).
1.2. Topsoils that will be stockpiled for future reuse and the locations for the stockpiles.
1.3. Soils that will be disturbed during construction and plans to restore disturbed soils and underlying subsoils to soil reference conditions.
1.4. Soils that will be restored and re-vegetated.
1.5. Soils disturbed by previous development that will be restored in place and re-vegetated.
1.6. Locations for all laydown and storage areas, parking areas, haul roads and construction vehicle access, temporary utilities and construction trailer locations.
1.7. Treatment details for each zone of soil that will be restored, including the type, source and expected volume of materials, including compost amendments, mulch and topsoil.
1.8. A narrative of the measures to be taken to ensure that areas not to be disturbed and areas of restored soils are protected from compaction by vehicle traffic or storage, erosion, and contamination until project completion.
2. A written erosion, sedimentation and pollutant control program for construction activities associated with the project. The program shall describe the best management practices (BMPs) to be employed including how the BMPs accomplish the following objectives:
2.1. Prevent loss of soil during construction due to stormwater runoff or wind erosion, including the protection of topsoil by stockpiling for reuse.
2.2. Prevent sedimentation of stormwater conveyances or receiving waters or other public infrastructure.
2.3. Prevent polluting the air with dust and particulate matter.
2.4. Prevent runoff and infiltration of other pollutants from construction site, including, but not limited to thermal pollution, concrete wash, fuels, solvents, hazardous chemical runoff, pH and pavement sealants. Ensure proper disposal of pollutants.
2.5. Protect from construction activities the designated vegetation and soil protection areas, flood hazard areas and other areas of vegetation that will remain on site.
3. A written periodic maintenance protocol for landscaping and stormwater management systems, including, but not limited to:
3.1. A schedule for periodic watering of new planting that reflects different water needs during the establishment phase of new plantings as well as after establishment. Where development of the building site changed the amount of water reaching the preserved natural resource areas, include appropriate measures for maintaining the natural areas.
3.2. A schedule for the use of fertilizers appropriate to the plants species, local climate and the preestablishment and post-establishment needs of the installed landscaping. Nonorganic fertilizers shall be discontinued following plant establishment.
3.3. A requirement for a visual inspection of the site after major precipitation events to evaluate systems performance and site impacts.
3.4. A schedule of maintenance activities of the stormwater management system including, but not limited to, cleaning of gutters, downspouts, inlets and outlets, removal of sediments from pretreatment sedimentation pits and wet detention ponds, vacuum sweeping followed by high-pressure hosing at porous pavement and removal of litter and debris.
3.5. A schedule of maintenance activities for landscaped areas including, but not limited to, the removal of dead or unhealthy vegetation; reseeding of turf areas; mowing of grass to a height which optimizes lawn health and retention of precipitation.
Reserved.

405.1.2 Topsoil Protection

STATE AMENDMENT
Topsoil that could potentially be damaged by construction activities or equipment shall be removed from areas to be disturbed and stockpiled on the building site for future reuse on the building site or other approved location. Topsoil stockpiles shall be secured and protected throughout the project with temporary or permanent soil stabilization measures to prevent erosion or compaction.

TABLE 405.1.2
MAXIMUM CONE PENETROMETER READINGS

SURFACE RESISTANCE (PSI)SUBSURFACE RESISTANCE (PSI)
All
Textures Sand
Sand
(includes loamy sand, sandy loam, sandy clay loam, and sandy clay)
Silt
(includes loam, silt loam, silty clay loam, and silty clay)
Clay
(includes clay loam)
110260260225

405.1.3 Imported Soils

STATE AMENDMENT
Topsoils or soil blends imported to a building site to serve as topsoil shall not be mined from the following locations:
1. Sites that are prime farmland, unique farmland, or farmland of statewide importance.
2. Greenfield sites where development is prohibited by Section 402.8.

Exception: Soils shall be permitted to be imported from the locations in Items 1 and 2 where those soils are a byproduct of a building and building site development process provided that imported soils are reused for functions comparable to their original function.

Soils that are being placed or replaced on a building site shall be prepared, amended and placed in a manner that establishes or restores the ability of the soil to support the vegetation that has been protected and that will be planted. Soil reuse and restoration shall be in accordance with Sections 405.1.4.1 and 405.1.4.2.
Before placing stockpiled or imported topsoils, compliance with all of the following shall occur:
1. Areas shall be cleared of debris including, but not limited to, building materials, plaster, paints, road base type materials, petroleum based chemicals, and other harmful materials;
2. Areas of construction-compacted subsoil shall be scarified; and
3. The first lift of replaced soil shall be mixed into this scarification zone to improve the transition between the subsoil and overlying soil horizons.

Exception: Scarification is prohibited in all of the following locations:

1. Where scarification would damage existing tree roots.
2. On inaccessible slopes.
3. On or adjacent to trenching and drainage installations.
4. On areas intended by the design to be compacted such as abutments, footings, inslopes.
6. Other locations where scarification would damage existing structures, utilities and vegetation being preserved.

405.1.4.2 Restoration

STATE AMENDMENT
Soils disturbed during construction shall be restored in areas that will not be covered by buildings, structures or hardscapes. Soil restoration shall comply with the following:
  1. Organic matter. To provide appropriate organic matter for plant growth and for water storage and infiltration, soils shall be amended with a mature, stable compost material so that not less than the top 126 inches (305152.4 mm) of soil contains not less than 3 percent organic matter. Sphagnum peat or organic amendments that contain sphagnum peat shall not be used. Soil organic matter shall be determined in accordance with ASTM D 2974. Organic materials selected for onsite amendment or for blending of imported soils shall be renewable within a 50-year cycle.
  2. Exception: Where the reference soil for a building site has an organic level depth other than 126 inches (305 mm), soils shall be amended to organic matter levels and organic matter depth that are comparable to the site’s reference soil.

  3. Additional soil restoration criteria. In addition to compliance with Item 1, soil restoration shall comply with not less than three of the following criteria:
    1. Compaction. Bulk densities within the root zone shall not exceed the densities specified in Table 405.1.24 and shall be measured using a soil cone penetrometer in accordance with ASAE S313.3. The root zone shall be not less than 126 inches (305152.4 mm), nor less than the site’s reference soil, whichever results in the greater depth of measurement. Data derived from a soil cone penetrometer shall be reported in accordance with ASAE EP542.
    2. Infiltration rates. Infiltration rates or saturated hydraulic conductivity of the restored soils shall be comparable to the site’s reference soil. Infiltration rates shall be determined in accordance with ASTM D 3385 or ASTM D 5093. For sloped areas where the methods provided in the referenced standards cannot be used successfully, alternate methods approved by the code official shall be permitted provided that the same method is used to test both reference soil and onsite soil.
    3. Soil biological function. Where remediated soils are used, the biological function of the soils’ mineralizable nitrogen shall be permitted as a proxy assessment of biological activity.
    4. Soil chemical characteristics. Soil chemical characteristics appropriate for plant growth shall be restored. The pH, cation exchange capacity and nutrient profiles of the original undisturbed soil or the site’s reference soil shall be matched in restored soils. Salinity suitable for regionally appropriate vegetation shall be established. Soil amendments and fertilizers shall be selected from those which minimize nutrient loading to waterways or groundwater.
Where engineered growing media are used onsite, including, but not limited to vegetative roofs, trees located within hardscape areas, and special soils specified for wetlands and environmental restoration sites, such media shall comply with the best available science and practice standards for that engineered growing media and use.

405.1.6 Documentation

STATE AMENDMENT
The following shall be provided to document compliance with Sections 405.1.3 through 405.1.5:
1. Documentation, such as receipts from a soil, compost and amendments supplier, to demonstrate that techniques to restore soil occurred; and
2. Soil test results to demonstrate that the selected techniques achieved the criteria of Section 405.1.4.2. Not less than two soil tests shall be conducted on the building site. For building sites where more than 8,000 square feet (744 m2) of soil is to be disturbed during construction, there shall be not less than one report for every 4,000 square feet (372 m2) disturbed or report frequency as determined by the registered design professional.
Vegetation and soils shall be protected in accordance with Sections 405.2.1 and 405.2.2.
Where existing soils and vegetation are to be protected, a vegetation and soil protection plan establishing designated vegetation and soil protection areas (VSPAs) shall be submitted with the construction documents and other submittal documents. The protection plan shall address the following:
1. Identification of existing vegetation located on a building site that is to be preserved and protected.
2. Identification of portions of the building site to be designated as vegetation and soil protection areas (VSPAs) that are to be protected during the construction process from being affected by construction activities.
3. Specification of methods to be used such as temporary fencing or other physical barriers to maintain the protection of the designated vegetation and soil protection areas (VSPAs).
4. Specification of protected perimeters around trees and shrubs that are to be included in the designated vegetation and soil protection areas (VSPAs). Perimeters around trees shall be identified as a circle with a radius of not less than 1 foot (305 mm) for every inch (25 mm) of tree diameter with a radius of not less than 5 feet (1524 mm). The perimeters around shrubs shall be not less than twice the radius of the shrub.

Exception: Approved alternative perimeters appropriate to the location and the species of the trees and shrubs shall be permitted.

5. Specification of methods to protect the viability of the designated vegetation and soil protection areas (VSPAs) to support the remaining vegetation at the conclusion of the construction process including minimizing impacts on the existing stormwater drainage patterns associated with the VSPAs.
6. Identification of plans, methods and practices used to designate essential areas of soil and subsoil disturbance.
Where tree protection zones are specified, the specifications and documentation shall be in accordance with Part 5 of TCIA/ANSI A300.
Invasive plant species shall not be planted on a building site. A management plan for the containment, removal and replacement of any invasive plant species currently on the site shall be generated based on either published recommendation for the referenced invasive plant or guidance prepared by a qualified professional. Existing vegetation that is to be retained on a building site shall be protected as required by Section 405.2.
Invasive plant species shall not be planted on a building site. Containment or removal of any invasive plant species currently on the site is required.
Where new landscaping is installed as part of a site plan or within the building site, not less than 7550 percent of the newly landscaped area shall be planted with native plant species.

Exceptions:
  1. Locations where non-native plant species are required by laws or regulations of the District of Columbia;
  2. Vegetative roofs for buildings or structures; or
  3. Trees.
A building site waste management plan shall be developed and implemented to divert Not less than 75 percent of the land-clearing debris and excavated soilsfrom a building site shall be diverted from landfills. Land-clearing debris includes rock, trees, stumps and associated vegetation. The plan shall include provisions that address all of the followingThe building site development shall comply with the following additional requirements:
  1. Materials to be diverted from disposal by efficient usage, recycling or reuse on the building site shall be specified.
  2. Diverted materials shall not be sent to sites that are agricultural land, flood hazard areas or greenfield sites where development is prohibited by Section 402.1 except where approved by the code official.
  3. The effective destruction and disposal of invasive plant species.
  4. Where contaminated soils are removed, the methods of removal and location where the soils are to be treated and disposed.
  5. The amount of materials to be diverted shall be specified and shall be calculated by weight or volume, but not both.
  6. Where the site is located in a federal or state designated quarantine zone for invasive insect species, building site vegetation management shall comply with the quarantine rules.
  7. Receipts or other documentation related to diversion shall be maintained through the course of construction. When requested by the code official, evidence of diversion shall be provided.
Construction materials and waste and hardscape materials removed during site preparation shall be managed in accordance with Section 503.

406.3 Verification

STATE AMENDMENT
Prior to issuance of the first certificate of occupancy for occupiable space in a story above grade plane, or prior to final inspection, if a new certificate of occupancy is not required, the Department is authorized to require the owner, contractor or an approved agency to provide verification of the project's compliance with Section 406.1.
Not less than one independent, paved walkway or bicycle path suitable for bicycles, strollers, pedestrians, and other forms of nonmotorized locomotion connecting a street or other path to a building entrance shall be provided. Walkways and bicycle paths shall connect to existing paths or sidewalks, and shall be designed to connect to any planned future paths. Paved walkways and bicycle paths shall be designed to minimize stormwater runoff. Pervious and permeable pavement shall be designed in accordance with Section 408.2.4.
Buildings with a total building floor area greater than 10,000 square feet (929 m2) and that are required to be provided with long-term bicycle parking and storage in accordance with Section 407.3 shall be provided with onsite changing room and shower facilities. Not less than one shower shall be provided for each 20 long-term bicycle parking spaces, or fraction thereof.

Where more than one changing room and shower facility is required, separate facilities shall be provided for each sex.

Long-term and short-term bicycle parking shall be designated on the site plan by a registered design professional and as specified in Table 407.3. The required number of spaces shall be determined based on the net floor area of each primary use or occupancy of a building except where Table 407.3 specifies otherwise. Accessory occupancy areas shall be included in the calculation of primary occupancy area.
Exceptions:
1. Long-term bicycle parking shall not be required where the total building floor area is less than 2,500 square feet (232 m2).
2. Subject to the approval of the code official, the number of bicycle parking spaces shall be permitted to be reduced because of building site characteristics including, but not limited to, isolation from other development.

TABLE 407.3
BICYCLE PARKINGa

OCCUPANCYSPECIFIC USESHORT-TERM SPACESLONG-TERM SPACESb
A-1Movie theaters1 per 50 seats; not less than 4 spaces2 spaces
Concert halls, theaters other than for movies1 per 500 seats
A-2Restaurants1 per 50 seats; not less than 2 spaces
A-3Places of worship1 per 500 seats
A-3Assembly spaces other than places of
worship
1 per 25,000 square feet; not less than
2 spaces
1 per 50,000 square feet; not less than 2 spaces
A-4 – A-5All1 per 500 seats2 spaces
BAll1 per 50,000 square feet; not less than
2 spaces
1 per 25,000 square feet; not less than 2 spaces
ESchoolsNone1 per 250 square feet of classroom area
E, I-4Day careNone2 spaces
F, HAllNone1 per 25,000 square feet; not less than 2 spaces
I-1AllNone2 spaces
I-2All1 per 25,000 square feet; not less than
2 spaces
1 per 50,000 square feet; not less than 2 spaces
MAll1 per 25,000 square feet; not less than
2 spaces
1 per 50,000 square feet; not less than 2 spaces
R-1Hotels, motels, boarding housesNone1 per 25,000 square feet; not less than 2 spaces
R-2, R-3, R-4AllNoneNone
STransit park and ride lotsNone1 per 20 vehicle parking spaces
Commercial parking facilities1 per 20 vehicle parking spacesNone
All otherNone2 spaces
OtherOutdoor recreation, parks1 per 20 vehicle parking spaces; not
less than 2 spaces
None
For SI: 1 square foot = 0.0929 m2.
a. Requirements based on square feet shall be the net floor area of the occupancy or use.
b. When a calculation results in a fraction of space, the requirements shall be rounded to the next higher whole number.
Short-term bicycle parking shall comply with all of the following:
1. It shall be provided with illumination of not less than 1 footcandle (11 lux) at the parking surface;
2. It shall be located at the same grade as the sidewalk or at a location reachable by ramp or accessible route;
3. It shall have an area of not less than 18 inches (457 mm) by 60 inches (1524 mm) for each bicycle;
4. It shall be provided with a rack or other facility for locking or securing each bicycle; and
5. It shall be located within 100 feet (30 480 mm) of, and visible from, the main entrance.

Exception: Where directional signage is provided at the main building entrances, short-term bicycle parking shall be permitted to be provided at locations not visible from the main entrance.

Long-term bicycle parking shall comply with all of the following:
1. It shall be located on the same site and within the building or within 300 feet (91 440 mm) of the main entrances;
2. It shall be provided with illumination of not less than 1 footcandle (11 lux) at the parking surface;
3. It shall have an area of not less than 18 inches (457 mm) by 60 inches (1524 mm) for each bicycle; and
4. It shall be provided with a rack or other facility for locking or securing each bicycle.

Not less than 50 percent of long-term bicycle parking shall be within a building or provided with a permanent cover including, but not limited to, roof overhangs, awnings, or bicycle storage lockers.

Vehicle parking spaces, other than those required by Section 407.4, local zoning requirements and accessible parking required by the International Building Code, shall be permitted to be used for the installation of long term bicycle parking spaces.

Where either Section 407.4.1 or 407.4.2 is indicated to be applicable in Table 302.1, parking provided at a building site shall comply with this section. Preferred parking spaces required by this section shall be those in the parking facility that are located on the shortest route of travel from the parking facility to a building entrance, but shall not take precedence over parking spaces that are required to be accessible in accordance with the International Building Code. Where buildings have multiple entrances with adjacent parking, parking spaces required by this section shall be dispersed and located near the entrances. Such parking spaces shall be provided with approved signage that specifies the permitted usage.
Where employee parking is provided for a building that has a total building floor area greater than 10,000 square feet (929 m2), a building occupant load greater than 100 and not less than 20 employees, at least 5 percent, but not less than two, of the employee parking spaces provided shall be designated as preferred parking for high occupancy vehicles.
Where parking is provided for a building that has a total building floor area greater than 10,000 square feet (929 m2) and that has an building occupant load greater than 100, at least 5 percent, but not less than two, of the parking spaces provided shall be designated as preferred parking for low emission, hybrid, and electric vehicles.

408.1 General

STATE AMENDMENT
The heat island effect of building and building site development shall be mitigated in accordance with Sections 408.2 and 408.3.

408.2 Site Hardscape

STATE AMENDMENT
In climate zones 1 through 6, as established in the International Energy Conservation Code, not less than 50 percent of the site hardscape shall be provided with one or any combination of options described in Sections 408.2.1 through 408.2.4. For the purposes of this section, site hardscape shall not include areas of the site covered by solar photovoltaic arrays or solar thermal collectors.
Hardscape materials shall have an initial solar reflectance value of not less than 0.30 in accordance with ASTM E 1918 or ASTM C 1549.

Exception: The following materials shall be deemed to comply with this section and need not be tested:

1. Pervious and permeable concrete pavements.
2. Concrete paving without added color or stain.
Where shading is provided by a building or structure or a building element or component, such building, structure, component or element shall comply with all of the following:
  1. Where open trellis-type, free- standing structures, such as, but not limited to, covered walkways, and trellises or pergolas, are covered with native plantings, the plantings shall be designed to achieve mature coverage within five years; and
  2. Where roofed structures are used to shade parking, those roofs shall comply with Section 408.3 in climate zones 1 through 6; and
  3. Shade provided onto the hardscape by an adjacent building or structure located on the same lot shall be calculated and credited toward compliance with this section based on the projected peak sun angle on the summer solstice.
Where shading is provided by trees, such trees shall be selected and placed in accordance with all of the following:
1. Trees selected shall be those that are native or adaptive to, the region and climate zone in which the project site is located. Invasive plant species shall not be selected. Plantings shall be selected and sited to produce a hardy and drought resistant vegetated area;
2. Construction documents shall be submitted that show the planting location and anticipated ten year canopy growth of trees and that show the contributions of existing tree canopies; and
3. Shading calculations shall be shown on the construction documents demonstrating compliance with this section and shall include only those hardscape areas directly beneath the trees based on a ten year growth canopy. Duplicate shading credit shall not be granted for those areas where multiple trees shade the same hardscape.
Pervious and permeable pavements including open grid paving systems and open-graded aggregate systems shall have a percolation rate not less than 2 gallons per minute per square foot (100 L/min × m2). Pervious and permeable pavement shall be permitted where the use of these types of hardscapes does not interfere with fire and emergency apparatus or vehicle or personnel access and egress, utilities, or telecommunications lines. Aggregate used shall be of uniform size.

408.3 Roof Surfaces

STATE AMENDMENT
Not less than 75 percent of the roof surfaces of buildings and covered parking located in climate zones 1 through 3, as established in the International Energy Conservation Code, shall be a roof complying with Section 408.3.1; shall be covered with a vegetative roof complying with Section 408.3.2; or a combination of these requirements. The provisions of this section shall apply to roofs of structures providing shade to parking in accordance with Section 408.2.2 where located in climate zones 1 through 6.
Exception: Portions of roof surfaces occupied by the following shall be permitted to be deducted from the roof surface area required to comply with this section:
1. Solar thermal collectors.
3. Roof penetrations and associated equipment.
4. Portions of the roof used to capture heat for building energy technologies.
5. Rooftop decks and rooftop walkways.
Where roof coverings are used for compliance with Section 408.3, roof coverings shall comply with Section 408.3.1.1 or 408.3.1.2. The values for solar reflectance and thermal emittance shall be determined by an independent laboratory accredited by a nationally recognized accreditation program. Roof products shall be listed and labeled and certified by the manufacturer demonstrating compliance.

TABLE 408.3.1
REFLECTANCE AND EMITTANCE

ROOF SLOPEMINIMUM AGED
SOLAR
REFLECTANCE
MINIMUM AGED
THERMAL
EMITTANCE
MINIMUM
AGED SRI
2:12 or less0.550.7560
Greater than 2:120.300.7525
Roof products shall be tested for a minimum three-year aged solar reflectance in accordance with ASTM E 1918, ASTM C 1549 or the CRRC-1 Standard and thermal emittance in accordance with ASTM C 1371, ASTM E 408 or the CRRC-1 Standard, and shall comply with the minimum values in Table 408.3.1.
Roof products shall be permitted to use a solar reflectance index (SRI) where the calculated value is in compliance with Table 408.3.1 values for minimum aged SRI. The SRI value shall be determined using ASTM E 1980 with a convection coefficient of 2.1 Btu/h-ft2 (12 W/m2 × k) based on three-year aged roof samples tested in accordance with the test methods in Section 408.3.1.1.

408.3.2 Vegetative Roofs

STATE AMENDMENT
Vegetative roofs, where provided in accordance with Section 408.3, shall comply with the following:
1. All plantings shall be selected based on their hardiness zone classifications in accordance with USDA MP1475 and shall be capable of withstanding the climate conditions of the jurisdiction and the micro climate conditions of the building site including, but not limited to, wind, precipitation and temperature. Planting density shall provide foliage coverage, in the warm months, of not less than 80 percent within two years of the date of installation unless a different time period is established in the approved design. Plants shall be distributed to meet the coverage requirements. Invasive plant species shall not be planted.
2. The engineered soil medium shall be designed for the physical conditions and local climate to support the plants and shall consist of nonsynthetic materials. The planting design shall include measures to protect the engineered soil medium until the plants are established. Protection measures include, but are not limited to, installation of pregrown vegetated mats or modules, tackifying agents, fiber blankets and reinforcing mesh. The maximum wet weight and water holding capacity of an engineered soil medium shall be determined in accordance with ASTM E 2399.
3. Where access to the building facades is provided from locations on the perimeter of the roof, nonvegetated buffers adequate to support associated equipment and to protect the roof shall be provided.
4. Nonvegetated clearances as required for fire classification of vegetative roof systems shall be provided in accordance with the International Fire Code.
5. Plantings shall be capable of being managed to maintain the function of the vegetative roof as provided in the documents required by Section 904.3.
Where this section is indicated to be applicable in Table 302.1, Uplight, light trespass, and glare shall be limited for all exterior lighting equipment as described in Sections 409.2 and 409.3. The provisions of this section shall only apply to new construction and Level 3 alterations complying with the applicable requirements of the Existing Building Code.
Exception: Lighting used for the following exterior applications is exempt where equipped with a control device independent of the control of the non-exempt lighting:
1. Specialized signal, directional, and marker lighting associated with transportation.
2. Advertising signage or directional signage.
3. Lighting integral to equipment or instrumentation and installed by its manufacturer.
4. Theatrical purposes, including performance, stage, film production, and video production.
5. Athletic playing areas where lighting is equipped with hoods or louvers for glare control.
6. Temporary lighting.
7. Lighting for industrial production, material handling, transportation sites, and associated storage areas where lighting is equipped with hoods or louvers for glare control.
8. Theme elements in theme and amusement parks.
9. Roadway lighting required by governmental authorities.
10. Lighting used to highlight features of public monuments and registered landmark structures.
11. Lighting classified for and used in hazardous areas.
12. Lighting for swimming pools and water features.
13. Means of egress and emergency lighting.
14. Lighting for public safety.
14. Lighting for security.
The lighting zone for the building site shall be determined from Table 409.1.1 unless otherwise specified by the jurisdictionas clarified by Administrative Bulletins.

[E] TABLE 409.1.1
EXTERIOR LIGHTING ZONES

LIGHTING ZONEDESCRIPTION
1Developed areas of national parks, state parks,
forest land and rural areas
2Areas predominantly consisting of residential
zoning, neighborhood business districts, light
industrial with limited nighttime use and residential
mixed use areas
3All other areas (not included in other zones)
4High-activity commercial districts in major
metropolitan areas as designated by the local jurisdiction

409.2 Uplight

STATE AMENDMENT
Exterior lighting shall comply with the requirements of Table 409.2 for the exterior lighting zones (LZ) appropriate to the building site.

Exception: Lighting used for the following exterior applications shall be exempt from the requirements of Table 409.2.
  1. Lighting for building facades, landscape features, and public monuments in exterior lighting zones 3 and 4.
  2. Lighting for building facades in exterior lighting zone 2.
  3. Lighting installed below canopies.
  4. Lighting for flag poles.

TABLE 409.2
UPLIGHT RATINGSa, b

LIGHTING ZONE (LZ)
1234
Maximum Luminaire Uplight RatingU1U2U3U4
a. Uplight ratings (U) are defined by IESNA TM-15-07 Addendum A.
b. The rating shall be determined by the actual photometric geometry in the specified mounting orientation.
Where luminaires are mounted on buildings with their backlight oriented towards the building, such luminaires shall not exceed the applicable glare ratings specified in Table 409.3(1). Other exterior luminaires shall not exceed the applicable backlight and glare ratings specified in Table 409.3(2).

Table 409.3(1)
MAXIMUM GLARE RATINGS FOR BUILDING MOUNTED
LUMINAIRES WITH THE BACKLIGHT ORIENTED TOWARDS THE
BUILDINGa, b

HORIZONTAL DISTANCE TO
LIGHTING BOUNDARY (HLB)
LIGHTING ZONE (LZ)
1234
HLB > 2hmG1G2G3G4
hm < HLB ≤ 2 hmG0G1G1G2
0.5 hm ≤ HLB ≤ hmG0G0G1G1
HLB < 0.5 hmG0G0G0G1
hm = Mounting height: The distance above finished grade at which a luminaire is mounted, measured to the midpoint of the luminaire.
a. Glare (G) ratings are defined by IESNA TM-15-07 Addendum A.
b. The rating shall be determined by the actual photometric geometry in the specified mounting orientation.

Table 409.3(2)
MAXIMUM ALLOWABLE BACKLIGHT AND GLARE RATINGSa, b, c

HORIZONTAL DISTANCE TO
LIGHTING BOUNDARY (HLB)
LIGHTING ZONE (LZ)
1234
HLB > 2hmB3B4B5B5
G1G2G3G4
hm < HLB ≤ 2 hmB2B3B4B4
G1G2G3G4
0.5 hm ≤ HLB ≤ hmB1B2B3B3
G1G2G3G4
HLB< 0.5 hmB0B0B1B2
G1G2G3G4
hm = Mounting height: The distance above finished grade at which a luminaire is mounted, measured to the midpoint of the luminaire.
a. Backlight (B) and glare (G) ratings are defined by IESNA TM-15-07 Addendum A.
b. Luminaires located two mounting heights or less from the lighting boundary shall be installed with backlight towards the nearest lighting boundary, unless lighting a roadway, bikeway or walkway that intersects a public roadway.
c. The rating shall be determined by the actual photometric geometry in the specified mounting orientation.
Resources