The provisions of Appendix H, Hazardous Materials Management Plan (HMMP) and Hazardous Materials Inventory Statement (HMIS) Instructions, in the International Fire Code are hereby adopted in their entirety as Appendix H to the Fire Code.
(See Example Format in Figure 1).
  1. Fill out items and sign the declaration.
  2. Part A of this section is required to be updated and submitted annually, or within 30 days of a process or management change.
(See Example Format in Figure 2).

1. Provide a site plan on 81/2 by 11 inch (215 mm by 279 mm) paper, showing the locations of all buildings, structures, outdoor chemical control or storage and use areas, parking lots, internal roads, storm and sanitary sewers, wells and adjacent property uses. Indicate the approximate scale, northern direction and date the drawing was completed.
(See Example Format in Figure 3).

  1. Provide a floor plan of each building identified on the site plan as containing hazardous materials on 81/2 -inch by 11-inch (215 mm by 279 mm) paper, identifying the northern direction, and showing the location of each storage and use area.
  2.  Identify storage and use areas, including hazard waste storage areas.
  3. Show the following:
    1. Accesses to each storage and use area.
    2. Location of emergency equipment.
    3. Location where liaison will meet emergency responders.
    4. Facility evacuation meeting point locations.
    5. The general purpose of other areas within the building.
    6. Location of all aboveground and underground tanks to include sumps, vaults, below-grade treatment systems, piping, etc.
    7. Show hazard classes in each area.
    8. Show locations of all Group H occupancies, control areas, and exterior storage and use areas.
    9. Show emergency exits.
1. HMIS Summary Report (see Example Format in Figure 4).

1.1. Complete a summary report for each control area and Group H occupancy.

1.2. The storage summary report includes the HMIS Inventory Report amounts in storage, use-closed and use-open conditions.

1.3. Provide separate summary reports for storage, use-closed and use-open conditions.

1.4. IBC/IFC Hazard Class.

1.5. Inventory Amount. [Solid (lb), Liquid (gal), Gas (cu ft, gal or lbs)].

1.6. IBC/IFC Maximum Allowable Quantity per control area (MAQ). (If applicable, double MAQ for sprinkler protection and/or storage in cabinets. For wholesale and retail sales occupancies, go to Tables 5003.11.1 and 5704.3.4.1 of the International Fire Code for MAQs.).

2. HMIS Inventory Report (see Example Format in Figure 5).

2.1. Complete an inventory report by listing products by location.

2.2. Product Name.

2.3. Components. (For mixtures specify percentages of major components if available.)

2.4. Chemical Abstract Service (CAS) Number. (For mixtures list CAS Numbers of major components if available.)

2.5. Location. (Identify the control area or, if it is a Group H occupancy, provide the classification, such as H-2, H-3, etc.)

2.6. Container with a capacity of greater than 55 gallons (208 L). (If product container, vessel or tank could exceed 55 gallons, indicate yes in column.)

2.7. Hazard Classification. (List applicable classifications for each product.)

2.8. Stored. (Amount of product in storage conditions.)

2.9. Closed. (Amount of product in use-closed systems.)

2.10. Open. (Amount of product in use-open systems.)

Facilities that have prepared, filed and submitted a Tier II Inventory Report required by the U.S. Environmental Protection Agency (USEPA) or required by a state that has secured USEPA approval for a similar form shall be deemed to have complied with this section.
  1. Emergency Notification. (See Example Format in Figure 6.)
  2. Where OSHA or state regulations require a facility to have either an Emergency Action Plan (EAP) or an Emergency Response Plan (ERP), the EAP or ERP shall be included as part of the HMMP.
ICC IBC—15 International Building Code H102.1
ICC IFC—15 International Fire Code H102.1


FIGURE 1 HAZARDOUS MATERIALS MANAGEMENT PLAN SECTION I: FACILITY DESCRIPTION



FIGURE 2 HAZARDOUS MATERIALS MANAGEMENT PLAN SECTION I: FACILITY DESCRIPTION



FIGURE 3 HAZARDOUS MATERIALS MANAGEMENT PLAN SECTION I: FACILITY DESCRIPTION PART C—FACILITY MAP



FIGURE 4 SECTION II—HAZARDOUS MATERIALS INVENTORY STATEMENT (HMIS) HMIS SUMMARY REPORTa (Storageb Conditions)c

IBC/IFC HAZARD CLASS HAZARD CLASS INVENTORY AMOUNT IBC/IFC MAXIMUM ALLOWABLE QUANTITYd
(Abbrev) Solid (lb) Liquid (gal) Gas (cu ft, gal, lb) Solid (lb) Liquid (gal) Gas (cu ft, gal, lb)
Combustible
Liquid
C2 5 120
C3A 330
C3B 6 13,200
Combustible Fiber Loose/Baled
Cryogenics, Flammable Cryo-Flam 45
Cryogenic, Oxidizing Cryo-OX 45
Flammable Gas FLG
(Gaseous) 150 1,000
(Liquefied) 30
Flammable Liquid F1A 30
F1B & F1C 5 120
Combination (1A, 1B, 1C) 5 120
Flammable Solid FLS 125
Organic Peroxide OPU 0
OP1 5
OP2 50
OP3 125
OP4 NL
OP5 NL
Oxidizer OX4 0
OX3 10
OX2 250
OX1 4,000

a. Complete a summary report for each control area and Group H occupancy.
b. Storage = storage + use-closed + use-open systems.
c. Separate reports are required for use-closed and use-open systems.
d. Include increases for sprinklefrs or storage in cabinets, if applicable.
(This is an example; add additional hazard classes as needed.)


FIGURE 5 SECTION II — HAZARDOUS MATERIALS INVENTORY STATEMENT (HMIS) HMIS INVENTORY REPORT (Sort Products Alphabetically by Location of Product and then Alphabetically by Product Name)

Product Name
(Components)c
CAS Number Locationa Container
> 55 galb
Haz Class 1 Haz Class 2 Haz Class 3 Stored (Ibs) Stored (gal) Stored (gas)d Closed (lbs) Closed (gal) Closed gasd Open (Ibs) Open
(gal)
ACETYLENE
(Acetylene gas)
74-86-2 Control
Area 1
FLG UR2 150
BLACK AEROSOL
SPRAY PAINT

(Mixture)
Mixture Control
Area 1
A-L3 24
GASOLINE,
UNLEADED

(Gasoline-Mixture)
Methyl-t-Butyl-Ether-15%
Diisopropyl Ether-7%
Ethanol-11%
Toluene-12%
Xylene-11%

8006-61-9

1634-04-4
108-20-3
64-17-5
108-88-3
1330-20-7
Control
Area 1
F1B 5
MOTOR OIL-10W40 (Hydrotreated Heavy
Paraffinic Distillate-85%;
Additives-20%)
64742-54-7
Mixture
Control
Area 1
C3B 3
DIESEL
(Diesel-99-100%;
Additives)
68476-34-6 Proprietary Control
Area 2
Yes C2 225
TRANSMISSION FLUID
(Oil-Solvent-Neutral;
Performance Additives)
64742-65-0 Control
Area 2
C3B 3
OXYGEN, GAS
(Oxygen)
7782-44-7 H-3 OXG 5,000

a. Identify the control area or, if it is a Group H occupancy, provide the classification, such as H-2, H-3, etc.
b. If the product container, vessel or tank could exceed 55 gallons, indicate yes in the column.
c. Specify percentages of main components if available.
d. In cubic feet, gallons or pounds.
(This is an example; add additional hazard classes as needed.)


FIGURE 6 HAZARDOUS MATERIALS MANAGEMENT PLAN SECTION III: EMERGENCY PLAN