ADOPTS WITH AMENDMENTS:

International Fire Code 2015 (IFC 2015)

Part I — Administrative

Part II — General Safety Provisions

Part III — Building and Equipment Design Features

Part IV — Special Occupancies and Operations

Part V — Hazardous Materials

Part VI — Referenced Standards

Part VII — Appendices

Heads up: There are no amended sections in this chapter.

Appendix C Fire Hydrant Locations and Distribution

AMENDMENT
This section has been amended at the state or city level.
The provisions of Appendix C, Fire Hydrant Locations and Distribution, in the International Fire Code are hereby adopted in their entirety as Appendix C to the Fire Code.
In addition to the requirements of Section 507.5.1 of the International Fire Code, fire hydrants shall be provided in accordance with this appendix for the protection of buildings, or portions of buildings, hereafter constructed or moved into the jurisdiction.
The number of fire hydrants available to a building shall be not less than the minimum specified in Table C102.1.

TABLE C102.1 REQUIRED NUMBER AND SPACING OF FIRE HYDRANTS

FIRE-FLOW REQUIREMENT
(gpm)
MINIMUM NUMBER
OF HYDRANTS
AVERAGE SPACING
BETWEEN HYDRANTSa, b, c, f, g
(feet)
MAXIMUM DISTANCE FROM ANY POINT ON STREET OR ROAD FRONTAGE TO A HYDRANTd, f, g
1,750 or less 1 500 250
2,000-2,250 2 450 225
2,500 3 450 225
3,000 3 400 225
3,500-4,000 4 350 210
4,500-5,000 5 300 180
5,500 6 300 180
6,000 6 250 150
6,500-7,000 7 250 150
7,500 or more 8 or moree 200 120

For SI: 1 foot = 304.8 mm, 1 gallon per minute = 3.785 L/m.
a. Reduce by 100 feet for dead-end streets or roads.
b. Where streets are provided with median dividers that cannot be crossed by fire fighters pulling hose lines, or where arterial streets are provided with four or more traffic lanes and have a traffic count of more than 30,000 vehicles per day, hydrant spacing shall average 500 feet on each side of the street and be arranged on an alternating basis.
c. Where new water mains are extended along streets where hydrants are not needed for protection of structures or similar fire problems, fire hydrants shall be provided at spacing not to exceed 1,000 feet to provide for transportation hazards.
d. Reduce by 50 feet for dead-end streets or roads.
e. One hydrant for each 1,000 gallons per minute or fraction thereof.
f. A 50-percent spacing increase shall be permitted where the building is equipped throughout with an approved automatic sprinkler system in accordance with Section 903.3.1.1 of the International Fire Code.
g. A 25-percent spacing increase shall be permitted where the building is equipped throughout with an approved automatic sprinkler system in accordance with Section 903.3.1.2 or 903.3.1.3 of the International Fire Code or Section P2904 of the International Residential Code.
Fire apparatus access roads and public streets providing required access to buildings in accordance with Section 503 of the International Fire Code shall be provided with one or more fire hydrants, as determined by Section C102.1. Where more than one fire hydrant is required, the distance between required fire hydrants shall be in accordance with Sections C103.2 and C103.3.
The average spacing between fire hydrants shall be in accordance with Table C102.1.

Exception: The average spacing shall be permitted to be increased by 10 percent where existing fire hydrants provide all or a portion of the required number of fire hydrants.
The maximum spacing between fire hydrants shall be in accordance with Table C102.1.
Existing fire hydrants on public streets are allowed to be considered as available to meet the requirements of Sections C102 and C103. Existing fire hydrants on adjacent properties are allowed to be considered as available to meet the requirements of Sections C102 and C103 provided that a fire apparatus access road extends between properties and that an easement is established to prevent obstruction of such roads.
ICC IFC—15 International Fire Code C101.1,
C103.1,
Table
C102.1
ICC IRC—15 International Residential Code Table
C102.1
UpCodes Premium
Leverage the most sophisticated code compliance platform.
TRY FREE FOR TWO WEEKS VISIT PRICING