ADOPTS WITH AMENDMENTS:

International Existing Building Code 2012 (IEBC 2012)

Heads up: There are no amended sections in this chapter.
Level 3 alterations as described in Section 505 shall comply with the requirements of this chapter.
In addition to the provisions of this chapter, work shall comply with all of the requirements of Chapters 7 and 8. The requirements of Sections 803, 804 and 805 shall apply within all work areas whether or not they include exits and corridors shared by more than one tenant and regardless of the occupant load.
Exception: Buildings in which the reconfiguration of space affecting exits or shared egress access is exclusively the result of compliance with the accessibility requirements of Section 705.2 shall not be required to comply with this chapter.

902.1 High-Rise Buildings

AMENDMENT
This section has been amended at the state or city level.

902.1 High-Rise Building

AMENDMENT
This section has been amended at the state or city level.
Any building having occupied floors more than 75 feet (22 860 mm) above the lowest level of fire department vehicle access shall comply with the requirements of Sections 902.1.1 and 902.1.2.

Exception: Existing high-rise buildings that are stripped of all systems and interior walls in all areas other than those used as a public garage, leaving no more than the structure, shaft walls and the exterior envelope assemblies, shall be rebuilt in full compliance with Section 403 of the Building Code, 12 DCMR A.
When a floor is served by a recirculating air or exhaust system with a capacity greater than 15,000 cubic feet per minute (701 m3/s), that system shall be equipped with approved smoke and heat detection devices installed in accordance with the International Mechanical Code.
Where there is an elevator or elevators for public use, at least one elevator serving the work area shall comply with this section. Existing elevators with a travel distance of 25 feet (7620 mm) or more above or below the main floor or other level of a building and intended to serve the needs of emergency personnel for fire-fighting or rescue purposes shall be provided with emergency operation in accordance with ASME A17.3. New elevators shall be provided with Phase I emergency recall operation and Phase II emergency in-car operation in accordance with ASME A17.1.
Boiler and furnace equipment rooms adjacent to or within the following facilities shall be enclosed by 1-hour fire-resistance-rated construction: day nurseries, children's shelter facilities, residential childcare facilities, and similar facilities with children below the age of 21/2 years or that are classified as Group I-2 occupancies, shelter facilities, residences for the developmentally disabled, group homes, teaching family homes, transitional living homes, rooming and boarding houses, hotels, and multiple dwellings.
Exceptions:
  1. Furnace and boiler equipment of low-pressure type, operating at pressures of 15 pounds per square inch gauge (psig) (103.4 KPa) or less for steam equipment or 170 psig (1171 KPa) or less for hot water equipment, when installed in accordance with manufacturer recommendations.
  2. Furnace and boiler equipment of residential R-3 type with 200,000 British thermal units (Btu) (2.11 × 108 J) per hour input rating or less is not required to be enclosed.
  3. Furnace rooms protected with automatic sprinkler protection.
Emergency controls for boilers and furnace equipment shall be provided in accordance with the International Mechanical Code in all buildings classified as day nurseries, children's shelter facilities, residential childcare facilities, and similar facilities with children below the age of 21/2 years or that are classified as Group I-2 occupancies, and in group homes, teaching family homes, and supervised transitional living homes in accordance with the following:
  1. Emergency shutoff switches for furnaces and boilers in basements shall be located at the top of the stairs leading to the basement; and
  2. Emergency shutoff switches for furnaces and boilers in other enclosed rooms shall be located outside of such room.
Existing stairways that are part of the means of egress shall be enclosed in accordance with Section 803.2.1 from the highest work area floor to, and including, the level of exit discharge and all floors below.
Fire separation in Group R-3 occupancies shall be in accordance with Section 903.2.1.
Where the work area is in any attached dwelling unit in Group R-3 or any multiple single-family dwelling (townhouse), walls separating the dwelling units that are not continuous from the foundation to the underside of the roof sheathing shall be constructed to provide a continuous fire separation using construction materials consistent with the existing wall or complying with the requirements for new structures. All work shall be performed on the side of the dwelling unit wall that is part of the work area.
Exception: Where alterations or repairs do not result in the removal of wall or ceiling finishes exposing the structure, walls are not required to be continuous through concealed floor spaces.
Interior finish in exits serving the work area shall comply with Section 803.4 between the highest floor on which there is a work area to the floor of exit discharge.

903.4 Air-Borne Sound

AMENDMENT
This section has been amended at the state or city level.
Walls, partitions and floor/ceiling assemblies separating dwelling units from each other or from public or service areas shall have a sound transmission class (STC) of not less than 50 (45 if field tested) for air-borne noise when tested in accordance with ASTM E 90. Walls, partitions and floor/ceiling assemblies separating Group A-2 occupancies from dwelling units shall have a sound transmission class (STC) of not less than 55 and shall be field tested to achieve a rating of not less than 50 for air-borne noise. Penetrations or openings in construction assemblies for piping; electrical devices; recessed cabinets; bathtubs; soffits; or heating, ventilating or exhaust ducts shall be sealed, lined, insulated or otherwise treated to maintain the required ratings. This requirement shall not apply to dwelling unit entrance doors; however, such doors shall be tight fitting to the frame and sill.

Exception: Group A-2 occupancies that do not utilize amplified music as part of their use shall be exempt from these provisions.
Automatic sprinkler systems shall be provided in all work areas when required by Section 804.2 or this section.

904.1.1 High-Rise Buildings

AMENDMENT
This section has been amended at the state or city level.

904.1.1 High-Rise Buildings

AMENDMENT
This section has been amended at the state or city level.
In high-rise buildings, work areas shall be provided with automatic sprinkler protection in accordance with Section 903 of the Building Code, 12 DCMR A.

904.1.1.1

AMENDMENT
This section has been amended at the state or city level.
Where Level 3 work areas occur on 75 percent or more of the building floors, excluding mechanical, parking and non-occupiable levels, automatic sprinkler protection shall be provided throughout the entire building in accordance with Section 903 of the Building Code.

904.1.1.2

AMENDMENT
This section has been amended at the state or city level.
Where an automatic sprinkler system with sprinkler control valves and water flow devices is provided for each floor throughout the building in accordance with Section 903 of the Building Code, modifications to the minimum type of construction and fire resistance rating requirements of the Construction Codes are permitted as described in Section 403.2 of the Building Code.

904.1.1.3 Additional Requirements for Alterations to 100% Percent of Floors

AMENDMENT
This section has been amended at the state or city level.
Where Level 3 alteration work areas occur on all floors, excluding mechanical, parking and non-occupiable levels, the building shall comply with the following additional requirements:
  1. Emergency voice/alarm communication systems. Provide an emergency voice/alarm communication system in accordance with Section 403.4.4 of the Building Code.
  2. Emergency responder radio coverage. Provide a two-way fire department communications system in accordance with Section 403.4.5 of the Building Code.
  3. Fire command center. Provide a fire command center in accordance with Section 403.4.6 of the Building Code.

    Exception: Where the following features do not exist in the building or cannot be readily provided as part of a Level 3 alteration, they are not required to be added for compliance with Section 911.1 of the Building Code: annunciator unit visually indicating the location of the elevators and whether they are operational; status indicators and controls for air-handling systems and emergency and standby power status indicators.
  4. Standby power and emergency power systems. Provide standby power and emergency power systems in accordance with Sections 403.4.8 and 403.4.9 of the Building Code.

904.1.2 Rubbish and Linen Chutes

AMENDMENT
This section has been amended at the state or city level.

904.1.2 Rubbish and Linen Chutes

AMENDMENT
This section has been amended at the state or city level.
Rubbish and linen chutes located in the work area shall be provided with automatic sprinkler system protection where protection of the rubbish and linen chute would be required under the provisions of the Building Code for new construction.
Fire alarm and detection systems complying with Sections 804.4.1 and 804.4.3 shall be provided throughout the building in accordance with the International Building Code.
Where required by the International Building Code, a manual fire alarm system shall be provided throughout the work area. Alarm notification appliances shall be provided on such floors and shall be automatically activated as required by the International Building Code.
Exceptions:
  1. Alarm-initiating and notification appliances shall not be required to be installed in tenant spaces outside of the work area.
  2. Visual alarm notification appliances are not required, except where an existing alarm system is upgraded or replaced or where a new fire alarm system is installed.
Where required by the International Building Code for new buildings, automatic fire detection systems shall be provided throughout the work area.
The means of egress shall comply with the requirements of Section 805 except as specifically required in Sections 905.2 and 905.3.
Means of egress from the highest work area floor to the floor of exit discharge shall be provided with artificial lighting within the exit enclosure in accordance with the requirements of the International Building Code.
Means of egress from the highest work area floor to the floor of exit discharge shall be provided with exit signs in accordance with the requirements of the International Building Code.
A building, facility or element that is altered shall comply with this section and Sections 705 and 806.
Where four or more Group I-1, I-2, R-1, R-2, R-3 or R-4 dwelling or sleeping units are being altered or added, the requirements of Section 1107 of the International Building Code for Type B units and Chapter 9 of the International Building Code for visible alarms apply only to the quantity of the spaces being altered or added.
Where buildings are undergoing Level 3 alterations including structural alterations, the provisions of this section shall apply.
New structural elements shall comply with Section 807.2.
Existing structural elements carrying gravity loads shall comply with Section 807.4.
All existing elements of the lateral force-resisting system shall comply with this section.
Exceptions:
  1. Buildings of Group R occupancy with no more than five dwelling or sleeping units used solely for residential purposes that are altered based on the conventional light-frame construction methods of the International Building Code or in compliance with the provisions of the International Residential Code.
  2. Where such alterations involve only the lowest story of a building and the change of occupancy provisions of Chapter 10 do not apply, only the lateral force-resisting components in and below that story need comply with this section.
An engineering evaluation and analysis that establishes the structural adequacy of the altered structure shall be prepared by a registered design professional and submitted to the code official.
Where more than 30 percent of the total floor and roof areas of the building or structure have been or are proposed to be involved in structural alteration within a five-year period, the evaluation and analysis shall demonstrate that the altered building or structure complies with the International Building Code for wind loading and with reduced IBC-level seismic forces. The areas to be counted toward the 30 percent shall be those areas tributary to the vertical load-carrying components, such as joists, beams, columns, walls and other structural components that have been or will be removed, added or altered, as well as areas such as mezzanines, penthouses, roof structures and in-filled courts and shafts.
Where the work does not involve a substantial structural alteration, the existing elements of the lateral load-resisting system shall comply with Section 807.5.
For any building assigned to Seismic Design Category D, E or F with a structural system consisting of concrete or reinforced masonry walls with a flexible roof diaphragm or unreinforced masonry walls with any type of roof diaphragm, the alteration work shall include installation of wall anchors at the roof line to resist the reduced IBC-level seismic forces, unless an evaluation demonstrates compliance of existing wall anchorage.
Parapets constructed of unreinforced masonry in buildings assigned to Seismic Design Category D, E or F shall have bracing installed as needed to resist the reduced IBC-level seismic forces, unless an evaluation demonstrates compliance of such items.
Level 3 alterations to existing buildings or structures are permitted without requiring the entire building or structure to comply with the energy requirements of the International Energy Conservation Code or International Residential Code. The alterations shall conform to the energy requirements of the International Energy Conservation Code or International Residential Code as they relate to new construction only.
UpCodes Premium
Leverage the most sophisticated code compliance platform.
TRY FREE FOR TWO WEEKS VISIT PRICING