ADOPTS WITH AMENDMENTS:

International Building Code 2015 (IBC 2015)

Heads up: There are no amended sections in this chapter.
The provisions of this chapter shall govern special building construction including membrane structures, temporary structures, pedestrian walkways and tunnels, automatic vehicular gates, awnings and canopies, marquees, signs, and towers and antennas.

3101.2 Other Requirements

AMENDMENT
This section has been amended at the state or city level.
Special construction encroaching into the public right-of-way or public space shall conform to the pertinent standards set forth in Chapter 32, and other applicable requirements, including the D.C. Department of Transportation (DDOT) regulations set forth in 24 DCMR, and D.C. Official Code, Title 10, Subtitle III.

3102.1 General

AMENDMENT
This section has been amended at the state or city level.
The provisions of Sections 3102.1 through 3102.8 shall apply to air-supported, air-inflated, membrane-covered cable, membrane-covered frame and tensile membrane structures, collectively known as membrane structures, erected for a period of 180 days or longer. Those erected for a shorter period of time shall comply with Section 3103 as applicable, except that membrane structures erected on a building, balcony, deck or other structure for any period of time shall comply with Sections 3102.1 through 3102.8. Membrane structures covering water storage facilities, water clarifiers, water treatment plants, sewage treatment plants, greenhouses and similar facilities not used for human occupancy are required to meet only the requirements of Sections 3102.3.1 and 3102.7.
Tensile membrane structures, including permanent and temporary structures, shall be designed and constructed in accordance with ASCE 55. The provisions in Sections 3102.3 through 3102.6 shall apply.
Noncombustible membrane structures shall be classified as Type IIB construction. Noncombustible frame or cable-supported structures covered by an approved membrane in accordance with Section 3102.3.1 shall be classified as Type IIB construction. Heavy timber frame-supported structures covered by an approved membrane in accordance with Section 3102.3.1 shall be classified as Type IV construction. Other membrane structures shall be classified as Type V construction.
Exception: Plastic less than 30 feet (9144 mm) above any floor used in greenhouses, where occupancy by the general public is not authorized, and for aquaculture pond covers is not required to meet the fire propagation performance criteria of Test Method 1 or Test Method 2, as appropriate, of NFPA 701.
Membranes and interior liners shall be either noncombustible as set forth in Section 703.5 or meet the fire propagation performance criteria of Test Method 1 or Test Method 2, as appropriate, of NFPA 701 and the manufacturer's test protocol.
Exception: Plastic less than 20 mil (0.5 mm) in thickness used in greenhouses, where occupancy by the general public is not authorized, and for aquaculture pond covers is not required to meet the fire propagation performance criteria of Test Method 1 or Test Method 2, as appropriate, of NFPA 701.
The area of a membrane structure shall not exceed the limitations specified in Section 506.
Membrane structures shall not exceed one story nor shall such structures exceed the height limitations in feet specified in Section 504.3.
Exception: Noncombustible membrane structures serving as roofs only.
Membrane structures shall be permitted to be utilized as specified in this section as a portion of buildings of other types of construction. Height and area limits shall be as specified for the type of construction and occupancy of the building.
A noncombustible membrane shall be permitted for use as the roof or as a skylight of any building or atrium of a building of any type of construction provided the membrane is not less than 20 feet (6096 mm) above any floor, balcony or gallery.
A membrane meeting the fire propagation performance criteria of Test Method 1 or Test Method 2, as appropriate, of NFPA 701 shall be permitted to be used as the roof or as a skylight on buildings of Type IIB, III, IV and V construction, provided the membrane is not less than 20 feet (6096 mm) above any floor, balcony or gallery.
The structure shall be designed and constructed to sustain dead loads; loads due to tension or inflation; live loads including wind, snow or flood and seismic loads and in accordance with Chapter 16.
For membrane-covered frame structures, the membrane shall not be considered to provide lateral restraint in the calculation of the capacities of the frame members.
Air-supported and air-inflated structures shall be provided with primary and auxiliary inflation systems to meet the minimum requirements of Sections 3102.8.1 through 3102.8.3.
This inflation system shall consist of one or more blowers and shall include provisions for automatic control to maintain the required inflation pressures. The system shall be so designed as to prevent overpressurization of the system.
In addition to the primary inflation system, in buildings larger than 1,500 square feet (140 m2) in area, an auxiliary inflation system shall be provided with sufficient capacity to maintain the inflation of the structure in case of primary system failure. The auxiliary inflation system shall operate automatically when there is a loss of internal pressure and when the primary blower system becomes inoperative.
Blower equipment shall meet all of the following requirements:
  1. Blowers shall be powered by continuous-rated motors at the maximum power required for any flow condition as required by the structural design.
  2. Blowers shall be provided with inlet screens, belt guards and other protective devices as required by the building official to provide protection from injury.
  3. Blowers shall be housed within a weather-protecting structure.
  4. Blowers shall be equipped with backdraft check dampers to minimize air loss when inoperative.
  5. Blower inlets shall be located to provide protection from air contamination. The location of inlets shall be approved.

3102.8.2 Standby Power

ILLUSTRATION
Wherever an auxiliary inflation system is required, an approved standby power-generating system shall be provided. The system shall be equipped with a suitable means for automatically starting the generator set upon failure of the normal electrical service and for automatic transfer and operation of all of the required electrical functions at full power within 60 seconds of such service failure. Standby power shall be capable of operating independently for not less than 4 hours.
A system capable of supporting the membrane in the event of deflation shall be provided for in air-supported and air-inflated structures having an occupant load of 50 or more or where covering a swimming pool regardless of occupant load. The support system shall be capable of maintaining membrane structures used as a roof for Type I construction not less than 20 feet (6096 mm) above floor or seating areas. The support system shall be capable of maintaining other membranes not less than 7 feet (2134 mm) above the floor, seating area or surface of the water.

3103.1 General

AMENDMENT
This section has been amended at the state or city level.
The provisions of Sections 3103.1 through 3103.4 shall apply to structures erected for a period of less than 180 days.
Exception: Tents and other membrane structures erected for a period of less than 180 days shall comply with the provisions of Sections 3103 and 3104 of the Fire Code. Those erected for a longer period of time shall comply with applicable sections of this code. Membrane structures erected on a building, balcony, deck or other structure for any period of time shall comply with Sections 3102.1 through 3102.8.

3103.1.1 Conformance

AMENDMENT
This section has been amended at the state or city level.
Temporary structures and uses shall conform to the structural strength, fire safety, means of egress, accessibility, light, ventilation and sanitary requirements of this code as necessary to ensure public health, safety and general welfare.

3103.1.2 Permit Required

AMENDMENT
This section has been amended at the state or city level.
Temporary structures that cover an area greater than 150 square feet (13.9 m2), including connecting areas or spaces with a common means of egress or entrance shall not be erected, operated or maintained for any purpose without obtaining a permit from the code official. Activities or uses regulated by Chapter 3 of the Fire Code require a separate permit issued by the fire code official.
A permit application and construction documents shall be submitted for each installation of a temporary structure. The construction documents shall include a site plan indicating the location of the temporary structure and information delineating the means of egress and the occupant load.
Temporary structures shall be located in accordance with the requirements of Table 602 based on the fire-resistance rating of the exterior walls for the proposed type of construction.

3103.4 Means of Egress

ILLUSTRATION
Temporary structures shall conform to the means of egress requirements of Chapter 10 and shall have an exit access travel distance of 100 feet (30 480 mm) or less.
This section shall apply to connections between buildings such as pedestrian walkways or tunnels, located at, above or below grade level, that are used as a means of travel by persons. The pedestrian walkway shall not contribute to the building area or the number of stories or height of connected buildings.
Pedestrian walkways shall be designed and constructed in accordance with Sections 3104.2 through 3104.9. Tunnels shall be designed and constructed in accordance with Sections 3104.2 and 3104.10.
Buildings connected by pedestrian walkways or tunnels shall be considered to be separate structures.
Exceptions:
  1. Buildings that are on the same lot and considered as portions of a single building in accordance with Section 503.1.2.
  2. For purposes of calculating the number of Type B units required by Chapter 11, structurally connected buildings and buildings with multiple wings shall be considered one structure.
The pedestrian walkway shall be of noncombustible construction.
Exceptions:
  1. Combustible construction shall be permitted where connected buildings are of combustible construction.
  2. Fire-retardant-treated wood, in accordance with Section 603.1, Item 1.3, shall be permitted for the roof construction of the pedestrian walkway where connected buildings are a minimum of Type I or II construction.
Only materials and decorations approved by the building official shall be located in the pedestrian walkway.
The connection of a pedestrian walkway to a building shall comply with Section 3104.5.1, 3104.5.2, 3104.5.3 or 3104.5.4.
Exception: Buildings that are on the same lot and considered as portions of a single building in accordance with Section 503.1.2.

3104.5.1 Fire Barriers

ILLUSTRATION
Pedestrian walkways shall be separated from the interior of the building by not less than 2- hour fire barriers constructed in accordance with Section 707 and Sections 3104.5.1.1 through 3104.5.1.3.
Exterior walls of buildings connected to pedestrian walkways shall be 2-hour fire-resistance-rated. This protection shall extend not less than 10 feet (3048 mm) in every direction surrounding the perimeter of the pedestrian walkway.
Openings in exterior walls required to be fire-resistance-rated in accordance with Section 3104.5.1.1 shall be equipped with opening protectives providing a not less than 3/4-hour fire protection rating in accordance with Section 716.
The fire barrier shall be supported by construction as required by Section 707.5.1.
The wall separating the pedestrian walkway and the building shall comply with Section 3104.5.2.1 or 3104.5.2.2 where:
  1. The distance between the connected buildings is more than 10 feet (3048 mm).
  2. The pedestrian walkway and connected buildings are equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1, and the roof of the walkway is not more than 55 feet (16 764 mm) above grade connecting to the fifth, or lower, story above grade plane, of each building.
Exception: Open parking garages need not be equipped with an automatic sprinkler system.
The wall shall be capable of resisting the passage of smoke.
The wall shall be constructed of a tempered, wired or laminated glass wall and doors or glass separating the interior of the building from the pedestrian walkway. The glass shall be protected by an automatic sprinkler system in accordance with Section 903.3.1.1 that, when actuated, shall completely wet the entire surface of interior sides of the wall or glass. Obstructions shall not be installed between the sprinkler heads and the wall or glass. The glass shall be in a gasketed frame and installed in such a manner that the framing system will deflect without breaking (loading) the glass before the sprinkler operates.
Where the distance between the connected buildings is more than 10 feet (3048 mm), the walls at the intersection of the pedestrian walkway and each building need not be fire-resistance-rated provided both sidewalls of the pedestrian walkway are not less than 50 percent open with the open area uniformly distributed to prevent the accumulation of smoke and toxic gases. The roof of the walkway shall be located not more than 40 feet (12 160 mm) above grade plane, and the walkway shall only be permitted to connect to the third or lower story of each building.
Exception: Where the pedestrian walkway is protected with a sprinkler system in accordance with Section 903.3.1.1, the roof of the walkway shall be located not more than 55 feet (16 764 mm) above grade plane and the walkway shall only be permitted to connect to the fifth or lower story of each building.
Where exterior walls of connected buildings are required by Section 705 to have a fire-resistance rating greater than 2 hours, the walls at the intersection of the pedestrian walkway and each building need not be fire-resistance-rated provided:
  1. The pedestrian walkway is equipped throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.1.
  2. The roof of the walkway is not located more than 55 feet (16 764 mm) above grade plane and the walkway connects to the fifth, or lower, story above grade plane of each building.
Access shall be provided at all times to a pedestrian walkway that serves as a required exit.
The unobstructed width of pedestrian walkways shall be not less than 36 inches (914 mm). The total width shall be not greater than 30 feet (9144 mm).

3104.9 Exit Access Travel

ILLUSTRATION
The length of exit access travel shall be 200 feet (60 960 mm) or less.
Exceptions:
  1. Exit access travel distance on a pedestrian walkway equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 shall be 250 feet (76 200 mm) or less.
  2. Exit access travel distance on a pedestrian walkway constructed with both sides not less than 50 percent open shall be 300 feet (91 440 mm) or less.
  3. Exit access travel distance on a pedestrian walkway constructed with both sides not less than 50 percent open, and equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1, shall be 400 feet (122 m) or less.
Separation between the tunneled walkway and the building to which it is connected shall be not less than 2-hour fire-resistant construction and openings therein shall be protected in accordance with Table 716.5.

3105.1 General

AMENDMENT
This section has been amended at the state or city level.
Awnings and canopies shall comply with the requirements of this Section 3105, other applicable sections of the Construction Codes, the Zoning Regulations and other applicable requirements. Awnings or canopies projecting over or into public space shall also comply with Section 3202.12.
The following term is defined in Chapter 2:

RETRACTABLE AWNING.
Awnings and canopies shall be designed and constructed to withstand wind or other lateral loads and live loads as required by Chapter 16 with due allowance for shape, open construction and similar features that relieve the pressures or loads. Structural members shall be protected to prevent deterioration. Awnings shall have frames of noncombustible material, fire-retardant-treated wood, wood of Type IV size, or 1-hour construction with combustible or noncombustible covers and shall be either fixed, retractable, folding or collapsible.
Awnings and canopies shall be provided with an approved covering that meets the fire propagation performance criteria of Test Method 1 or Test Method 2, as appropriate, of NFPA 701 or has a flame spread index not greater than 25 when tested in accordance with ASTM E84 or UL 723.
Exception: The fire propagation performance and flame spread index requirements shall not apply to awnings installed on detached one- and two-family dwellings.

3105.5 Fixed or Permanent Awnings

AMENDMENT
This section has been amended at the state or city level.
The minimum clearance from the sidewalk or any other space used by the public to the lowest part of any fixed or permanent awning shall be 8 feet (2438 mm). Fixed or permanent awnings installed above the first story shall not project more than 5 feet (1524 mm) from the face of the building.
Exception: Above doors on detached one and two family dwellings, and townhouses not more than three stories above grade in height with a separate means of egress, the minimum clearance from the sidewalk or any other space used by the public to the lowest part of the awning shall be 80 inches (2032 mm).

3105.6 Retractable Awnings

AMENDMENT
This section has been amended at the state or city level.
The minimum clearance from the sidewalk or any other space used by the public to the lowest part of any retractable awning shall be 8feet (2438 mm). Retractable awnings shall be securely fastened to the building and, in the fully extended position, no part of the awning shall be closer than 12 inches (305 mm) to the vertical plane of the lot line. Retractable awnings shall be equipped with a mechanism or device for raising and holding the awning in a retracted or closed position against the face of the building.
Exception: Above doors on detached one and two family dwellings and townhouses not more than three stories above grade in height with a separate means of egress, the minimum clearance from the sidewalk or any other space used by the public to the lowest part of the awning shall be 80 inches (2032 mm).

3105.7 Canopies

AMENDMENT
This section has been amended at the state or city level.
Canopies shall not extend closer than 2 feet (610 mm) from the lot line. The minimum clearance from the sidewalk or any other space used by the public to the lowest part of any canopy shall be 8 feet (2438 mm).

3105.8 Lettering on Awnings or Canopies

AMENDMENT
This section has been amended at the state or city level.
Lettering on awnings or canopies shall comply with Appendix N or any superseding regulations adopted pursuant to the Sign Legislation.

3106.1 General

AMENDMENT
This section has been amended at the state or city level.
Marquees shall comply with Sections 3106.3 through 3106.5 and other applicable sections of this code. Marquees projecting over or into public space shall also comply with Section 3202.12.3.

3106.2 Thickness

AMENDMENT
This section has been amended at the state or city level.

3106.2 [Reserved]

AMENDMENT
This section has been amended at the state or city level.
Where the roof or any part thereof is a skylight, the skylight shall comply with the requirements of Chapter 24. Every roof and skylight of a marquee shall be sloped to downspouts that shall conduct any drainage from the marquee in such a manner so as not to spill over the sidewalk.
Every marquee shall be so located as not to interfere with the operation of any exterior standpipe, and such that the marquee does not obstruct the clear passage of stairways or exit discharge from the building or the installation or maintenance of street lighting.
A marquee shall be supported entirely from the building and constructed of noncombustible materials. Marquees shall be designed as required in Chapter 16. Structural members shall be protected to prevent deterioration.

3107.1 General

AMENDMENT
This section has been amended at the state or city level.
Signs shall be designed, constructed and maintained in accordance with the applicable requirements of the Construction Codes, including, but not limited to, the Property Maintenance Code, and Chapters 1, 16, 24 and 26 and Appendix N of the Building Code, except to the extent that any of the provisions of the Construction Codes are superseded by regulations adopted in the District of Columbia pursuant to the Sign Legislation.
Towers shall be designed and constructed in accordance with the provisions of TIA-222. Towers shall be designed for seismic loads; exceptions related to seismic design listed in Section 2.7.3 of TIA-222 shall not apply. In Section 2.6.6.2 of TIA 222, the horizontal extent of Topographic Category 2, escarpments, shall be 16 times the height of the escarpment.
Exception: Single free-standing poles used to support antennas not greater than 75 feet (22 860 mm), measured from the top of the pole to grade, shall not be required to be noncombustible.
Towers shall be located such that guy wires and other accessories shall not cross or encroach upon any street or other public space, or over above-ground electric utility lines, or encroach upon any privately owned property without the written consent of the owner of the encroached-upon property, space or aboveground electric utility lines. Towers shall be equipped with climbing and working facilities in compliance with TIA-222. Access to the tower sites shall be limited as required by applicable OSHA, FCC and EPA regulations.
The design and construction of swimming pools, spas and hot tubs shall comply with the International Swimming Pool and Spa Code.
Automatic vehicular gates shall comply with the requirements of Sections 3110.2 through 3110.4 and other applicable sections of this code.
The following term is defined in Chapter 2:

VEHICULAR GATE.
Vehicular gates intended for automation shall be designed, constructed and installed to comply with the requirements of ASTM F2200.
Vehicular gate openers, where provided, shall be listed in accordance with UL 325.
Photovoltaic panels and modules shall comply with the requirements of this code and the International Fire Code.
Photovoltaic panels and modules installed on a roof or as an integral part of a roof assembly shall comply with the requirements of Chapter 15 and the International Fire Code.

Section 3112 Fences

AMENDMENT
This section has been amended at the state or city level.

3112.1 General

AMENDMENT
This section has been amended at the state or city level.
Fences shall comply with the requirements of this section, other applicable sections of the Construction Codes and other municipal regulations. All barbed wire and similar fences shall comply with the requirements of Section 3112.4.
Exception: Fences or portions of fences located on privately-owned land beyond a building restriction line shall comply with the requirements for fences in public space set forth in 24 DCMR § 103.

3112.1.1 Fence Walls

AMENDMENT
This section has been amended at the state or city level.
Fence walls shall conform to the requirements for fences.

3112.1.2 Screens or Trellises

AMENDMENT
This section has been amended at the state or city level.
Screens or trellises shall conform to the requirements for fences.

3112.1.3 Height Measurement

AMENDMENT
This section has been amended at the state or city level.
The measurement of the height of a fence shall be made from the top of the fence to grade, on the side of the fence where grade level is higher.

3112.1.4 Permit Applications

AMENDMENT
This section has been amended at the state or city level.
Application for permits to erect or increase the height of a fence, or change the grade adjacent to a fence, shall be accompanied by an official building plat upon which the proposed fence location is indicated. Review and approval by the Zoning Administrator shall be required before a permit shall be issued.
Exception: Review or approval by the Zoning Administrator shall not be required where: (a) an existing lawful fence is replaced; (b) the extent, location, and the height of the fence is unchanged; and (c) the adjacent grade is unchanged.

3112.2 Party Line Fences

AMENDMENT
This section has been amended at the state or city level.
Only those portions of the length of a fence, including footings, which are partly on each side of a party line shall be considered as party line fences. Permit applications for party line fences shall be signed by the owners of the adjoining properties on which the fence is to be located.

3112.2.1 Fence Materials

AMENDMENT
This section has been amended at the state or city level.
A party line fence shall be a wood, woven wire, or iron fence of open pattern, unless otherwise agreed upon by the adjoining owners.

3112.2.2 Height Agreements

AMENDMENT
This section has been amended at the state or city level.
Where owners propose to erect a party line fence over 7 feet (2134 mm) in height in Residential Zones or on properties with frontage on the Anacostia or Potomac Rivers, or over 10 feet (3048 mm) in Mixed Use, Special Purpose, Commercial, or PDR Zones, a written agreement as to the height of the party line fence shall be executed by the owners of the properties on which the fence is to be located and such agreement shall be filed with the code official before issuance of a permit.

3112.3 Other Fences

AMENDMENT
This section has been amended at the state or city level.
Fences other than party line fences shall comply with Sections 3112.3.1 through 3112.3.5.

3112.3.1 Fences Abutting Streets

AMENDMENT
This section has been amended at the state or city level.
Fences abutting a street shall not exceed 7 feet (2134 mm) in height in Residential Zones or on properties with frontage on the Anacostia or Potomac Rivers, nor 10 feet (3048 mm) in height in Mixed Use, Special Purpose, Commercial, or PDR Zones.

3112.3.1.1 Special Provisions Applicable to Historic Districts and Landmarks

AMENDMENT
This section has been amended at the state or city level.
Within a historic district or at a designated historic landmark, fences or walls between the front façade of a structure and the front lot line shall not exceed 3 feet 6 inches (1067 mm) in height. Fences between the front façade of a structure and the front lot line shall be at least 50 percent open. (The ratio shall be computed in elevation by dividing the fence elements themselves by the open space between the fence elements.) The code official is authorized to allow fences or walls covered by this subsection to exceed 3 feet 6 inches (1067 mm) in height upon recommendation of the Historic Preservation Office.

3112.3.2 Fences Abutting Alleys

AMENDMENT
This section has been amended at the state or city level.
Fences abutting alleys shall not exceed 7 feet (2134 mm) in height in Residential Zones or on properties with frontage on the Anacostia or Potomac Rivers, nor 10 feet (3048 mm) in Mixed Use, Special Purpose, Commercial, or PDR Zones.
Exception: The code official is authorized to approve a greater height where the alley is 15 feet (4572 mm) wide or more.

3112.3.3 Fences Near Party Lines

AMENDMENT
This section has been amended at the state or city level.
Fences located 10 feet (3048 mm) or less from a party line shall not exceed 7 feet (2134 mm) in height in Residential Zones or on properties with frontage on the Anacostia or Potomac Rivers, nor 10 feet (3048 mm) in Special Purpose, Mixed Use, Commercial, or PDR Zones. Fences shall not obstruct light or ventilation for any required window.
Exception: Where the written consent of the adjoining owners is filed with the code official, the code official is authorized to approve a greater height, not to exceed 10 feet (3048 mm).

3112.3.4 Fences Located in Lot Interior

AMENDMENT
This section has been amended at the state or city level.
Fences more than 10 feet (3048 mm) from (a) a lot line, including a party line; (b) an alley; or (c) if applicable, a building restriction line, shall not be subject to height limitations except as necessary to avoid (i) encroachment on a required yard or court, or (ii) obstruction of the light or ventilation for any required window.

3112.3.5 Gate Height

AMENDMENT
This section has been amended at the state or city level.
Gates shall not exceed the height of the fence.

3112.4 Barbed Wire Fences

AMENDMENT
This section has been amended at the state or city level.
Fences, barriers or obstructions, composed in whole, or in any part, of barbed wire (collectively referred to as "barbed wire fences") are prohibited in the District of Columbia, except as expressly permitted by this Section 3112.4. The term barbed wire shall include (a) barbed, razor or electrified wire; (b) sharp or jagged glass; (c) metal such as, but not limited to, razor-spikes; or (d) similar materials.

3112.4.1 Barbed Wire Fences on Private Property

AMENDMENT
This section has been amended at the state or city level.
Barbed wire fences on private property that meet the following conditions are permitted:
  1. The barbed wire fence is not located in a Residential Zone or along the zoning boundary lines of any Residential Zone, except where the code official determines that the condition or the nature of the improvements located upon the premises pose a significant, demonstrable hazard to members of the public;
  2. The barbed wire fence is not located on the lot line, or building restriction line if one exists, and does not project beyond the lot line or building restriction line;
  3. The minimum height of the lowest strand of barbed wire is 6 feet (1829 mm) above adjacent ground; and
  4. The barbed wire fence complies with any other applicable requirements, including, but not limited to, Sections 802.17, 804.14 and 825.13 of the Zoning Regulations.

3112.4.2 Barbed Wire Fences in Public Space

AMENDMENT
This section has been amended at the state or city level.
No barbed wire fence shall be erected, constructed, or maintained, along the lot line or building restriction line, if one exists, or in or upon any street, or other public space, including but not limited to any sidewalk, public parking or building restriction area, in the District of Columbia.
UpCodes Premium
Leverage the most sophisticated code compliance platform.
TRY FREE FOR TWO WEEKS VISIT PRICING