The construction and operation of marinas, boatyards, yacht clubs, boat condominiums, docking facilities associated with residential condominiums, multiple-docking facilities at multiple-family residences, and all associated piers, docks, and floats shall comply with NFPA 303, Fire Protection Standard for Marinas and Boatyards, and Section 28.1.
Section 28.1 shall not apply to private, non-commercial docking facility constructed or occupied for the use of the owners or residents of an associated single-family dwelling.
Section 28.1 also applies to support facilities and structures used for construction, repair, storage, hauling and launching, or fueling of vessels if fire on a pier would pose an immediate threat to these facilities, or if a fire at a referenced facility would pose an immediate threat to a docking facility. [303:1.1.1]
Section 28.1 applies to marinas and facilities servicing small recreational and commercial craft, yachts, and other craft of not more than 300 gross tons. [303:1.1.2]
No requirement in this chapter is to be construed as reducing applicable building, fire, and electrical codes. [303:1.1.4]
Placement of portable fire extinguishers shall be in accordance with 13.6.2 unless otherwise permitted by 28.1.6.1.1.1.1, 28.1.6.1.1.1.2, and 28.1.6.1.1.1.3. [303:6.2.1.1]
Placement of portable fire extinguishers on piers and along bulkheads where vessels are moored or are permitted to be moored shall meet the following criteria:
  1. Extinguishers listed for Class A, Class B, and Class C fires shall be installed at the pier/land intersection on a pier that exceeds 25 ft (7.62 m) in length.
  2. Additional fire extinguishers shall be placed such that the maximum travel distance to an extinguisher does not exceed 75 ft (22.86 m). [303:6.2.1.1.1]

(A) Portable fire extinguishers that meet the minimum requirements of 13.6.2 for extra (high) hazard type shall be installed on two sides of a fuel-dispensing area. [303:6.2.1.1.2.1]

(B) On piers or bulkheads where long fueling hoses are installed for fueling vessels, additional extinguishers installed on piers or bulkheads shall meet the requirements of 13.6.2 for extra (high) hazard type and 28.1.6.1.1.1.1. [303:6.2.1.1.2.2]

All extinguishers installed on piers shall meet the rating requirements set forth in 13.6.2 for ordinary (moderate) hazard type. [303:6.2.1.1.3]
All portable fire extinguishers shall be maintained in accordance with 13.6.3 and shall be clearly visible and marked. [303:6.2.2]
Buildings in excess of 500 ft2 (46 m2) that are constructed on piers shall be protected by an approved automatic fire-extinguishing system unless otherwise permitted by 28.1.6.2.1.2 or 28.1.6.2.1.3. [303:6.3.1.1]
Buildings of Type I or Type II construction, as specified in NFPA 220, Standard on Types of Building Construction, and without combustible contents shall not be required to be protected by an automatic fire-extinguishing system. [303:6.3.1.2]
Existing facilities shall not be required to be protected by an automatic fire-extinguishing system where acceptable to the AHJ. [303:6.3.1.3]
Marina and boatyard buildings in excess of 5000 ft2 (465 m2) in total area shall be protected by an approved automatic fire-extinguishing system unless otherwise permitted by 28.1.6.2.2.2. [303:6.3.2.1]
Existing facilities shall not be required to be protected by an automatic fire-extinguishing system where acceptable to the AHJ. [303:6.3.2.2]
Combustible piers and substructures in excess of 25 ft (7.62 m) in width or in excess of 5000 ft2 (465 m2) in area, or within 30 ft (9.14 m) of other structures or superstructures required to be so protected, shall be protected in accordance with Section 4.3 of NFPA 307, Standard for the Construction and Fire Protection of Marine Terminals, Piers, and Wharves, unless otherwise permitted by 28.1.6.2.3.2, 28.1.6.2.3.3, or 28.1.6.2.3.4. [303:6.3.3.1]
Fixed piers shall not be required to be protected as specified in 28.1.6.2.3.1 where the vertical distance from the surface of mean high water level to the underside of the pier surface does not exceed 36 in. (914 mm). [303:6.3.3.2]
Floating piers shall not be required to be protected as specified in 28.1.6.2.3.1 where the vertical distance from the surface of the water to the underside of the pier surface does not exceed 36 in. (914 mm). [303:6.3.3.3]
Existing facilities shall not be required to be protected by an automatic fire-extinguishing system where acceptable to the AHJ. [303:6.3.3.4]
Where boats are stored on multilevel racks in buildings, an approved automatic fire-extinguishing system shall be installed throughout the building unless otherwise permitted by 28.1.6.2.4.2 or 28.1.6.2.4.3. [303:6.3.4.1]
An automatic fire-extinguishing system shall not be required for buildings less than 5000 ft2 (465 m2) having multilevel racks where provided with one of the following:
  1. An automatic fire detection and alarm system supervised by a central station complying with NFPA 72
  2. An automatic fire detection and alarm system supervised by a local protective signaling system complying with NFPA 72, if the provisions of 28.1.6.2.4.2(1) are not technically feasible
  3. A full-time watch service if the provisions of 28.1.6.2.4.2(1) are not technically feasible [303:6.3.4.2]
Existing facilities shall not be required to be protected by an automatic fire-extinguishing system where acceptable to the AHJ. [303:6.3.4.3]
An approved water supply shall be provided within 100 ft (30 m) of the pier/land intersection or fire department connection serving fire protection systems. [303:6.3.5]
Access between water supplies and pier/land intersections or fire department connections shall be by roadway acceptable to the AHJ. [303:6.3.6]
Class I standpipe systems shall be provided for piers, bulkheads, and buildings where the hose lay distance from the fire apparatus exceeds 150 ft (45 m). [303:6.4.1]
Class I standpipes shall be provided in all buildings used for the rack storage of boats. [303:6.4.2]
Standpipe systems, where installed, shall be in accordance with Section 13.2, except for the provisions identified in 28.1.6.3.4 through 28.1.6.3.7. [303:6.4.3]
Hose racks, hoses, and standpipe cabinets shall not be required on piers and bulkheads. [303:6.4.4]
Supply piping for standpipes on piers and bulkheads shall be sized for the minimum flow rate for Class II systems. [303:6.4.5]
Manual dry standpipes shall be permitted. [303:6.4.6]
Flexible connections shall be permitted on floating piers where acceptable to the AHJ. [303:6.4.7]
Water supply and hoses or portable fire extinguishers and wheeled cart assemblies equipped with discharge nozzles capable of reaching all boats on the highest racks shall be provided. [303:6.5]
Hydrants and water supplies for fire protection in marinas and boatyards shall be provided in accordance with Section 13.2, Section 13.3, and 13.5.1. [303:6.6]
Fire detection devices and installation shall be in accordance with Section 13.7. [303:6.11.1]
Fire detectors shall be installed in the following interior or covered locations unless those locations are protected by a fixed automatic sprinkler system installed in accordance with NFPA 13:
  1. Rooms containing combustible storage or goods
  2. Rooms containing flammable liquid storage or use
  3. Rooms containing battery storage or maintenance
  4. Rooms containing paint and solvent storage or use
  5. Areas used for enclosed or covered storage of vessels
  6. Areas used for enclosed or covered maintenance of vessels
  7. Areas used for public assembly, dining, or lodging
  8. Kitchens and food preparation areas
  9. Dust bins and collectors
  10. Inside trash storage areas
  11. Rooms used for storing janitor supplies or linens
  12. Laundry rooms
  13. Furnace rooms [303:6.11.2]
Each berth shall be arranged such that a boat occupying the berth can be removed in an emergency without the necessity of moving other boats. [303:7.1.1]
Access to all piers, floats, and wharves shall be provided for municipal fire-fighting equipment. [303:7.1.2]
Electrical lighting shall be provided to ensure adequate illumination of all exterior areas, piers, and floats. [303:7.1.3]
Electrical lighting shall not interfere with navigation or aids to navigation. [303:7.1.4]
Only listed 120/240 V ac electrical equipment shall be operated unattended. [303:7.1.5]
The use of portable heaters in boat storage areas shall be prohibited except where necessary to accomplish repairs. [303:7.2.1.1.1]
Portable heaters used in accordance with 28.1.7.2.1.1.1 shall be used only when personnel are in attendance. [303:7.2.1.1.2]
Open flame heaters shall not be used in boat storage areas. [303:7.2.1.1.3]
Ladders long enough to reach the deck of any stored boat shall be provided and readily available. [303:7.2.1.2]
The use of blow torches or flammable paint remover shall be prohibited unless permitted by 8.7.1 of NFPA 303. [303:7.2.1.3]
The use of gasoline or other flammable solvents for cleaning purposes shall be prohibited. [303:7.2.1.4]
Where a boat is to be dry-stored for the season or stored indoors for an extended period of time, such as while awaiting repairs, the following precautions shall be taken:
  1. The vessel shall be inspected for any hazardous materials or conditions that could exist, and corrective action shall be taken.
  2. Liquefied petroleum gas (LPG) and compressed natural gas (CNG) cylinders, reserve supplies of stove alcohol or kerosene, and charcoal shall be removed from the premises or stored in a separate, designated safe area.
  3. All portable fuel tanks shall be removed from the premises or emptied and, if emptied, the cap shall be removed and the tank left open to the atmosphere.
  4. *Permanently installed fuel tanks shall be stored at least 95 percent full. [303:7.2.1.5]
No unattended electrical equipment shall be in use aboard boats. [303:7.2.1.6]
All storage areas shall be routinely raked, swept, or otherwise policed to prevent the accumulation of rubbish. [303:7.2.1.7]
Access to boats stored outside shall be such that the hose-lay distance from the fire apparatus to any portion of the boat shall not exceed 150 ft (45 m). [303:7.2.1.8.1]
Access to buildings in which boats are stored shall be such that the hose-lay distance from the fire apparatus to all exterior portions of the building shall not exceed 150 ft (45 m). [303:7.2.1.8.2]
Wet standpipe systems shall be permitted to be used to meet the requirement in 28.1.7.2.1.8.1 or 28.1.7.2.1.8.2. [303:7.2.1.8.3]
When work is being carried out onboard a vessel in an unsprinklered storage building, management shall require an inspection of the vessel at the end of the day to ensure that no hazards resulting from the day's work are present. [303:7.2.2.1]
If a guard is employed, vessels addressed in 28.1.7.2.2.1 shall be included in the regular rounds. [303:7.2.2.2]
Class I flammable liquids shall not be stored in an indoor boat storage area. [303:7.2.2.3]
Work performed on boats stored indoors shall be performed by qualified personnel. [303:7.2.2.4]
Facility management shall maintain control over all personnel access to storage facilities and boats stored indoors. [303:7.2.2.5]
Where boats are stored either inside or outside in single- or multiple-level racks, those boats shall have unimpeded vehicular access at one end, and equipment shall be available to remove any stored boat. [303:7.2.3.1]
Where boats are stored in multilevel racks, either inside or outside, for seasonal storage or for in-out operation, the following precautions shall be taken:
  1. Drain plugs shall be removed (in sprinklered buildings).
  2. Batteries shall be disconnected or the master battery switch turned off.
  3. Fuel tank valves shall be closed.
  4. For seasonal storage, the requirements of 28.1.7.2.1 shall apply. [303:7.2.3.2]
Repairs to boats that are on racks or that are inside an in-out dry storage building shall be prohibited. [303:7.2.3.3]
Portable power lines, such as drop cords, shall be prohibited from use on boats in an in-out dry storage building. [303:7.2.3.4]
The charging of batteries shall be prohibited in the in-out dry storage building. [303:7.2.3.5]
Where due to size and weight the removal of batteries for storage or charging is impractical, batteries shall be permitted to remain onboard provided the following conditions are met:
  1. The battery compartment is arranged to provide adequate ventilation.
  2. A listed battery charger is used to provide a suitable charge.
  3. The power connection to the charger consists of a three-wire cord of not less than No. 14 AWG conductors connected to a source of 110 V to 125 V single-phase current, with a control switch and approved circuit protection device designed to trip at not more than 125 percent of the rated amperage of the charger.
  4. There is no connection on the load side of the charger to any other device except the battery, and the boat battery switch is turned off.
  5. The battery is properly connected to the charger, and the grounding conductor effectively grounds the charger enclosure.
  6. Unattended battery chargers are checked at intervals not exceeding 8 hours while in operation. [303:7.2.4]
The management shall have an inspection made of each boat received for major repair or storage as soon as practicable after arrival of a boat and before commencement of any work aboard. [303:8.1.1]
The inspection required in 28.1.8.1.1 shall include the following determinations:
  1. Presence of combustible vapors in any compartment
  2. General maintenance and cleanliness, and location of any combustible materials that require removal or protection for the safe accomplishment of the particular work involved
  3. Quantity, type, and apparent condition of fire-extinguishing equipment onboard
  4. Listed and appropriate shore power inlet(s) and ship-to-shore cable(s), when present [303:8.1.2]
The management shall, as a condition to accepting a boat received for major repair or storage, require the owner to correct any inadequacies found in 28.1.8.1.2 or to authorize management to do so. [303:8.1.3]
Smoking in the working area shall be prohibited. [303:8.2.1]
Loose combustibles in the area of any hazardous work shall be removed. [303:8.2.2]
Unprotected battery terminals shall be covered to prevent inadvertent shorting from dropped tools or otherwise, and the ungrounded battery lead shall be disconnected. [303:8.2.3]
Personnel employed in the removal or installation of storage batteries shall be qualified. [303:8.2.4]
Where electric service is provided to boats in storage, the receptacle providing the power shall be protected with a ground-fault circuit-interrupter. [303:8.2.5]
The marina or boatyard operator shall post in a prominent location, or provide to boat operators using a marina or boatyard for mooring, repair, servicing, or storage, a list of safe operating procedures containing at least the following information:
  1. A prohibition against the use of any form of hibachis, charcoal, wood, or gas-type portable cooking equipment, except in specifically authorized areas that are not on the docks, on boats in the berthing area, or near flammables
  2. Procedures for disposal of trash
  3. Designation of nonsmoking areas
  4. Location of fire extinguishers and hoses
  5. Procedures for turning in a fire alarm
  6. Fueling procedures
  7. *Emergency contact information and marina address for notifying emergency services to respond to an incident [303:8.2.6]
The information on fueling procedures referred to in 28.1.8.2.6(6) shall include at least the following information:
  1. Procedures before fueling
    1. Stop all engines and auxiliaries
    2. Shut off all electricity, open flames, and heat sources
    3. Check bilges for fuel vapors
    4. Extinguish all smoking materials
    5. Close access fittings and openings that could allow fuel vapors to enter the boat's enclosed spaces
    6. Remove all personnel from the boat except the person handling the fueling hose
  2. Procedures during fueling
    1. Maintain nozzle contact with fill pipe
    2. Attend fuel-filling nozzle at all times
    3. Wipe up spills immediately
    4. Avoid overfilling
  3. Procedures after fueling and before starting engine
    1. Inspect bilges for leakage or fuel odors
    2. Ventilate until odors are removed [303:8.2.7]
Section 28.2 shall apply to marine terminals as defined herein. Special use piers and wharf structures that are not marine terminals, such as public assembly, residential, business, or recreational occupancies that differ in design and construction from cargo handling piers, require special consideration. The general principles of NFPA 307 for the construction and fire protection of piers and wharves shall be applicable to such structures and shall comply with NFPA 307, Standard for the Construction and Fire Protection of Marine Terminals, Piers, and Wharves, and Section 28.2.
Marine terminals, piers, and wharves shall comply with 28.1.8.2.7.
Section 28.2 shall not apply to marinas and boatyards. (See Section 28.1.) [307:1.3.2]
Section 28.2 shall not apply to the handling of the following:
  1. *Flammable or combustible liquids in bulk (See Chapter 66.)
  2. *Liquefied gases in bulk (See Chapter 69.) [307:1.3.3]
Nothing in Section 28.2 shall supersede any of the regulations of governmental or other regulatory authority. [307:1.1.2]
The construction, conversion, repair, or lay-up of vessels shall comply with NFPA 312, Standard for Fire Protection of Vessels During Construction, Conversion, Repair, and Lay-Up, and Section 28.3.
Nothing in Section 28.3 shall be construed as prohibiting the immediate dry-docking of a vessel whose safety is imperiled, as by being in a sinking condition or by being seriously damaged. [312:1.2.2]
In such cases, all necessary precautionary measures shall be taken as soon as practicable. [312:1.2.3]
The requirements of Section 28.3 shall not apply to situations where it is in conflict with or superseded by requirements of any government regulatory agency. [312:1.1.2]