2001.1 Scope

AMENDMENT
This section has been amended at the state or city level.
Airports, heliports, helistops and aircraft hangars shall be in accordance with this chapter and Section 412.

2001.2 Regulations Not Covered

AMENDMENT
This section has been amended at the state or city level.

2001.3 Permits

AMENDMENT
This section has been amended at the state or city level.
Open flames, flame-producing devices and other sources of ignition shall not be permitted in a hangar, except in approved locations or in any location within 50 feet (15 240 mm) of an aircraft-fueling operation.

2003.2 Smoking

AMENDMENT
This section has been amended at the state or city level.
The prohibition of smoking and posting of "No Smoking" signs shall comply with the Connecticut State Fire Prevention Code.

2003.3 Housekeeping

AMENDMENT
This section has been amended at the state or city level.
Fire apparatus access roads shall be provided and maintained in accordance with Chapter 5. Fire apparatus access roads and aircraft parking positions shall be designed in a manner so as to preclude the possibility of fire vehicles traveling under any portion of a parked aircraft.
The dispensing, transferring and storage of flammable and combustible liquids shall be in accordance with this chapter and Chapter 57. Aircraft motor vehicle fuel-dispensing facilities shall be in accordance with Chapter 23.

2003.6 Combustible Storage

AMENDMENT
This section has been amended at the state or city level.

2003.7 Hazardous Material Storage

AMENDMENT
This section has been amended at the state or city level.
Hazardous materials storage shall be in accordance with the Connecticut State Fire Prevention Code.

Section 2004 Aircraft Maintenance

AMENDMENT
This section has been amended at the state or city level.

2004.1 Transferring Flammable and Combustible Liquids

AMENDMENT
This section has been amended at the state or city level.

2004.2 Application of Flammable and Combustible Liquid Finishes

AMENDMENT
This section has been amended at the state or city level.

2004.3 Cleaning Parts

AMENDMENT
This section has been amended at the state or city level.

2004.4 Spills

AMENDMENT
This section has been amended at the state or city level.

2004.4.1 Cessation of Work

AMENDMENT
This section has been amended at the state or city level.

2004.4.2 Vehicle Movement

AMENDMENT
This section has been amended at the state or city level.

2004.4.3 Mitigation

AMENDMENT
This section has been amended at the state or city level.

2004.5 Running Engines

AMENDMENT
This section has been amended at the state or city level.

2004.6 Open Flame

AMENDMENT
This section has been amended at the state or city level.

2004.7 Other Aircraft Maintenance

AMENDMENT
This section has been amended at the state or city level.

2005.1 General

AMENDMENT
This section has been amended at the state or city level.
Portable fire extinguishers suitable for flammable or combustible liquid and electrical-type fires shall be provided in accordance with Section 906 at fuel-dispensing stations.

2005.2 On Towing Vehicles

AMENDMENT
This section has been amended at the state or city level.

2005.3 On Welding Apparatus

AMENDMENT
This section has been amended at the state or city level.

2005.4 On Aircraft Fuel-Servicing Tank Vehicles

AMENDMENT
This section has been amended at the state or city level.

2005.5 On Hydrant Fuel-Servicing Vehicles

AMENDMENT
This section has been amended at the state or city level.

2005.6 At Fuel-Dispensing Stations

AMENDMENT
This section has been amended at the state or city level.

2005.7 Fire Extinguisher Access

AMENDMENT
This section has been amended at the state or city level.

2005.7.1 Cabinets

AMENDMENT
This section has been amended at the state or city level.

2005.8 Reporting Use

AMENDMENT
This section has been amended at the state or city level.
Aircraft motor vehicle fuel-dispensing facilities shall be in accordance with Chapter 23.
Airport fuel systems shall be designed and constructed in accordance with NFPA 407.

2006.3 Construction of Aircraft-Fueling Vehicles and Accessories

AMENDMENT
This section has been amended at the state or city level.

2006.3.1 Transfer Apparatus

AMENDMENT
This section has been amended at the state or city level.

2006.3.1.1 Internal Combustion Type

AMENDMENT
This section has been amended at the state or city level.

2006.3.1.2 Gear Operated

AMENDMENT
This section has been amended at the state or city level.

2006.3.1.3 Vibration Isolation

AMENDMENT
This section has been amended at the state or city level.

2006.3.2 Pumps

AMENDMENT
This section has been amended at the state or city level.

2006.3.3 Dispensing Hoses and Nozzles

AMENDMENT
This section has been amended at the state or city level.

2006.3.4 Protection of Electrical Equipment

AMENDMENT
This section has been amended at the state or city level.

2006.3.5 Venting of Equipment Compartments

AMENDMENT
This section has been amended at the state or city level.

2006.3.6 Accessory Equipment

AMENDMENT
This section has been amended at the state or city level.

2006.3.7 Electrical Bonding Provisions

AMENDMENT
This section has been amended at the state or city level.

2006.3.7.1 Bonding Cables

AMENDMENT
This section has been amended at the state or city level.

2006.3.7.2 Bonding Cable Protection

AMENDMENT
This section has been amended at the state or city level.

2006.3.8 Smoking

AMENDMENT
This section has been amended at the state or city level.

2006.3.9 Smoking Equipment

AMENDMENT
This section has been amended at the state or city level.

2006.4 Operation, Maintenance and Use of Aircraft-Fueling Vehicles

AMENDMENT
This section has been amended at the state or city level.

2006.4.1 Proper Maintenance

AMENDMENT
This section has been amended at the state or city level.

2006.4.2 Vehicle Integrity

AMENDMENT
This section has been amended at the state or city level.

2006.4.3 Removal From Service

AMENDMENT
This section has been amended at the state or city level.

2006.4.4 Operators

AMENDMENT
This section has been amended at the state or city level.

2006.5 Fueling and Defueling

AMENDMENT
This section has been amended at the state or city level.

2006.5.1 Positioning of Aircraft-Fueling Vehicles

AMENDMENT
This section has been amended at the state or city level.

2006.5.1.1 Fueling Vehicle Egress

AMENDMENT
This section has been amended at the state or city level.

2006.5.1.2 Aircraft Vent Openings

AMENDMENT
This section has been amended at the state or city level.

2006.5.1.3 Parking

AMENDMENT
This section has been amended at the state or city level.

2006.5.2 Electrical Bonding

AMENDMENT
This section has been amended at the state or city level.

2006.5.2.1 Conductive Hose

AMENDMENT
This section has been amended at the state or city level.

2006.5.2.2 Bonding Conductors on Transfer Nozzles

AMENDMENT
This section has been amended at the state or city level.

2006.5.2.3 Funnels

AMENDMENT
This section has been amended at the state or city level.

2006.5.3 Training

AMENDMENT
This section has been amended at the state or city level.

2006.5.3.1 Fueling Hazards

AMENDMENT
This section has been amended at the state or city level.

2006.5.3.2 Fire Safety Training

AMENDMENT
This section has been amended at the state or city level.

2006.5.3.2.1 Fire Extinguisher Training

AMENDMENT
This section has been amended at the state or city level.

2006.5.3.2.2 Records

AMENDMENT
This section has been amended at the state or city level.

2006.5.4 Transfer Personnel

AMENDMENT
This section has been amended at the state or city level.

2006.5.5 Fuel Flow Control

AMENDMENT
This section has been amended at the state or city level.

2006.6 Emergency Fuel Shutoff

AMENDMENT
This section has been amended at the state or city level.

2006.6.1 Accessibility

AMENDMENT
This section has been amended at the state or city level.

2006.6.2 Notification of the Fire Department

AMENDMENT
This section has been amended at the state or city level.

2006.6.3 Determining Cause

AMENDMENT
This section has been amended at the state or city level.

2006.6.4 Testing

AMENDMENT
This section has been amended at the state or city level.

2006.7 Protection of Hoses

AMENDMENT
This section has been amended at the state or city level.

2006.8 Loading and Unloading

AMENDMENT
This section has been amended at the state or city level.

2006.9 Passengers

AMENDMENT
This section has been amended at the state or city level.

2006.10 Sources of Ignition

AMENDMENT
This section has been amended at the state or city level.

2006.11 Fuel Spill Prevention and Procedures

AMENDMENT
This section has been amended at the state or city level.

2006.11.1 Fuel-Service Equipment Maintenance

AMENDMENT
This section has been amended at the state or city level.

2006.11.2 Transporting Fuel Nozzles

AMENDMENT
This section has been amended at the state or city level.

2006.11.3 Drum Fueling

AMENDMENT
This section has been amended at the state or city level.

2006.11.4 Fuel Spill Procedures

AMENDMENT
This section has been amended at the state or city level.

2006.11.5 Notification of the Fire Department

AMENDMENT
This section has been amended at the state or city level.

2006.11.6 Investigation Required

AMENDMENT
This section has been amended at the state or city level.

2006.11.7 Multiple Fuel Delivery Vehicles

AMENDMENT
This section has been amended at the state or city level.

2006.12 Aircraft Engines and Heaters

AMENDMENT
This section has been amended at the state or city level.

2006.13 Vehicle and Equipment Restrictions

AMENDMENT
This section has been amended at the state or city level.

2006.13.1 Overwing Fueling

AMENDMENT
This section has been amended at the state or city level.

2006.14 Electrical Equipment

AMENDMENT
This section has been amended at the state or city level.

2006.14.1 Other Equipment

AMENDMENT
This section has been amended at the state or city level.

2006.15 Open Flames

AMENDMENT
This section has been amended at the state or city level.

2006.15.1 Other Areas

AMENDMENT
This section has been amended at the state or city level.

2006.15.2 Matches and Lighters

AMENDMENT
This section has been amended at the state or city level.

2006.16 Lightning Procedures

AMENDMENT
This section has been amended at the state or city level.
Aircraft fuel-transfer operations shall be prohibited indoors.

Exception: In aircraft hangars built in accordance with the provisions of the International Building Code for Group F-1 occupancies, aircraft fuel-transfer operations are allowed where either of the following conditions exist:
  1. Necessary to accomplish aircraft fuel-system maintenance operations. Such operations shall be performed in accordance with nationally recognized standards.
  2. The fuel being used has a flash point greater than 100°F (37.8°C).

2006.17.1 Position of Aircraft

AMENDMENT
This section has been amended at the state or city level.

2006.17.2 Fire Equipment Access

AMENDMENT
This section has been amended at the state or city level.

2006.18 Defueling Operations

AMENDMENT
This section has been amended at the state or city level.

2006.19 Maintenance of Aircraft-Fueling Hose

AMENDMENT
This section has been amended at the state or city level.

2006.19.1 Inspections

AMENDMENT
This section has been amended at the state or city level.

2006.19.1.1 Daily Inspection

AMENDMENT
This section has been amended at the state or city level.

2006.19.1.2 Monthly Inspection

AMENDMENT
This section has been amended at the state or city level.

2006.19.2 Damaged Hose

AMENDMENT
This section has been amended at the state or city level.

2006.19.3 Repairing Hose

AMENDMENT
This section has been amended at the state or city level.

2006.19.4 New Hose

AMENDMENT
This section has been amended at the state or city level.
Unattended aircraft fuel-servicing vehicles shall be parked in areas that provide for both the unencumbered dispersal of vehicles in the event of an emergency and the control of leakage such that adjacent buildings and storm drains are not contaminated by leaking fuel.
Parking areas for tank vehicles shall be designed and utilized such that a clearance of 10 feet (3048 mm) is maintained between each parked vehicle for fire department access. In addition, a minimum clearance of 50 feet (15 240 mm) shall be maintained between tank vehicles and parked aircraft and structures other than those used for the maintenance and/or garaging of aircraft fuel-servicing vehicles.

2006.21 Radar Equipment

AMENDMENT
This section has been amended at the state or city level.

2006.21.1 Direction of Radar Beams

AMENDMENT
This section has been amended at the state or city level.
Helistops and heliports shall be maintained in accordance with Sections 2007.2 through 2007.8. Helistops and heliports on buildings shall be constructed in accordance with the International Building Code.
The touchdown area shall be surrounded on all sides by a clear area having minimum average width at roof level of 15 feet (4572 mm) but no width less than 5 feet (1524 mm). The clear area shall be maintained.
Landing areas on structures shall be maintained so as to confine flammable or Class II combustible liquid spillage to the landing area itself, and provisions shall be made to drain such spillage away from exits or stairways serving the helicopter landing area or from a structure housing such exit or stairway.
Exits and stairways shall be maintained in accordance with Section 412.7 of the International Building Code.
A building with a rooftop helistop or heliport shall be provided with a Class I or III standpipe system extended to the roof level on which the helistop or heliport is located. All portions of the helistop and heliport area shall be within 150 feet (45 720 mm) of a 21/2-inch (63.5 mm) outlet on the standpipe system.
Foam fire-protection capabilities shall be provided for rooftop heliports. Such systems shall be designed, installed and maintained in accordance with the applicable provisions of Sections 903, 904 and 905.

2007.7 Portable Fire Extinguishers

AMENDMENT
This section has been amended at the state or city level.
Portable fire extinguishers in accordance with Section 906 shall be provided for each permanent takeoff and landing area and for the aircraft parking areas.
Before operating helicopters from helistops and heliports, approval shall be obtained from the Federal Aviation Administration.