- Allowable stress design in accordance with Sections 2304, 2305 and 2306.
- Load and resistance factor design in accordance with Sections 2304, 2305 and 2307.
- Conventional light-frame construction in accordance with Sections 2304 and 2308.
Exception: Buildings designed in accordance with the provisions of the AF&PA WFCM shall be deemed to meet the requirements of the provisions of Section 2308.
- The design and construction of log structures shall be in accordance with the provisions of ICC 400.
- ACCREDITATION BODY.
- BRACED WALL LINE.
- BRACED WALL PANEL.
- COLLECTOR.
- CONVENTIONAL LIGHT-FRAME CONSTRUCTION.
- CRIPPLE WALL.
- DIAPHRAGM, UNBLOCKED.
- DRAG STRUT.
- FIBERBOARD.
- GLUED BUILT-UP MEMBER.
- GRADE (LUMBER).
- HARDBOARD.
- NAILING, BOUNDARY.
- NAILING, EDGE.
- NAILING, FIELD.
- NOMINAL SIZE (LUMBER).
- PARTICLEBOARD.
- PERFORMANCE CATEGORY.
- PREFABRICATED WOOD I-JOIST.
- SHEAR WALL.
- Shear wall, perforated.
- Shear wall segment, perforated.
- STRUCTURAL COMPOSITE LUMBER.
- Laminated strand lumber (LSL).
- Laminated veneer lumber (LVL).
- Oriented strand lumber (OSL).
- Parallel strand lumber (PSL).
- STRUCTURAL GLUED-LAMINATED TIMBER.
- SUBDIAPHRAGM.
- TIE-DOWN (HOLD-DOWN).
- TREATED WOOD.
- Fire-retardant-treated wood.
- Preservative-treated wood.
- WOOD SHEAR PANEL.
- WOOD STRUCTURAL PANEL.
- Composite panels.
- Oriented strand board (OSB).
- Plywood.
- Identification of treating manufacturer.
- Type of preservative used.
- Minimum preservative retention (pcf).
- End use for which the product is treated.
- AWPA standard to which the product was treated.
- Identity of the accredited inspection agency.
- The identification mark of an approved agency in accordance with Section 1703.5.
- Identification of the treating manufacturer.
- The name of the fire-retardant treatment.
- The species of wood treated.
- Flame spread and smoke-developed index.
- Method of drying after treatment.
- Conformance with appropriate standards in accordance with Sections 2303.2.5 through 2303.2.8.
- For fire-retardant-treated wood exposed to weather, damp or wet locations, include the words "No increase in the listed classification when subjected to the Standard Rain Test" (ASTM D 2898).
- Slope or depth, span and spacing;
- Location of all joints and support locations;
- Number of plies if greater than one;
- Required bearing widths;
- Design loads as applicable, including;
- Other lateral loads, including drag strut loads;
- Adjustments to wood member and metal connector plate design value for conditions of use;
- Maximum reaction force and direction, including maximum uplift reaction forces where applicable;
- Metal-connector-plate type, size and thickness or gage, and the dimensioned location of each metal connector plate except where symmetrically located relative to the joint interface;
- Size, species and grade for each wood member;
- Truss-to-truss connections and truss field assembly requirements;
- Calculated span-to-deflection ratio and maximum vertical and horizontal deflection for live and total load as applicable;
- Maximum axial tension and compression forces in the truss members; and
- Required permanent individual truss member restraint location and the method and details of restraint/bracing to be used in accordance with Section 2303.4.1.2.
- Permanent individual truss member restraint/bracing shall be installed using standard industry lateral restraint/bracing details in accordance with generally accepted engineering practice. Locations for lateral restraint shall be identified on the truss design drawing.
- The trusses shall be designed so that the buckling of any individual truss member is resisted internally by the individual truss through suitable means (i.e., buckling reinforcement by T-reinforcement or L-reinforcement, proprietary reinforcement, etc.). The buckling reinforcement of individual members of the trusses shall be installed as shown on the truss design drawing or on supplemental truss member buckling reinforcement details provided by the truss designer.
- A project-specific permanent individual truss member restraint/bracing design shall be permitted to be specified by any registered design professional.
- Where a cover sheet and truss index sheet are combined into a single sheet and attached to the set of truss design drawings, the single cover/truss index sheet is the only document required to be signed and sealed by the truss designer.
- When a cover sheet and a truss index sheet are separately provided and attached to the set of truss design drawings, the cover sheet and the truss index sheet are the only documents required to be signed and sealed by the truss designer.
SHEATHING TYPE | MINIMUM THICKNESS | MAXIMUM WALL STUD SPACING |
Wood boards | 5/8 inch | 24 inches on center |
Fiberboard | 1/2 inch | 16 inches on center |
Wood structural panel | In accordance with Tables 2308.9.3(2) and 2308.9.3(3) | — |
M-S "Exterior Glue" and M-2 "Exterior Glue" Particleboard | In accordance with Section 2306.3 and Table 2308.9.3(4) | — |
Gypsum sheathing | 1/2 inch | 16 inches on center |
Gypsum wallboard | 1/2 inch | 24 inches on center |
Reinforced cement mortar | 1 inch | 24 inches on center |
MINIMUM NAIL | MINIMUM WOOD STRUCTURAL PANEL SPAN RATING |
MINIMUM NOMINAL PANEL THICKNESS (inches) |
MAXIMUM WALL STUD SPACING (inches) |
PANEL NAIL SPACING |
MAXIMUM NOMINAL DESIGN WIND SPEED, Vasdd (MPH) |
||||
Size | Penetration (inches) |
Edges (inches o.c.) |
Field (inches o.c.) |
Wind exposure category |
|||||
B | C | D | |||||||
6d common (2.0"× 0.113") | 1.5 | 24/0 | 3/8 | 16 | 6 | 12 | 110 | 90 | 85 |
24/16 | 7/16 | 16 | 6 | 12 | 110 | 100 | 90 | ||
6 | 150 | 125 | 110 | ||||||
8d common (2.5"× 0.131") | 1.75 | 24/16 | 7/16 | 16 | 6 | 12 | 130 | 110 | 105 |
6 | 150 | 125 | 110 | ||||||
24 | 6 | 12 | 110 | 90 | 85 | ||||
6 | 110 | 90 | 85 |
- Panel strength axis shall be parallel or perpendicular to supports. Three-ply plywood sheathing with studs spaced more than 16 inches on center shall be applied with panel strength axis perpendicular to supports.
- The table is based on wind pressures acting toward and away from building surfaces in accordance with Section 30.7 of ASCE 7. Lateral requirements shall be in accordance with Section 2305 or 2308.
- Wood structural panels with span ratings of wall-16 or wall-24 shall be permitted as an alternative to panels with a 24/0 span rating. Plywood siding rated 16 o.c. or 24 o.c. shall be permitted as an alternative to panels with a 24/16 span rating. Wall-16 and plywood siding 16 o.c. shall be used with studs spaced a maximum of 16 inches o.c.
- V asd shall be determined in accordance with Section 1609.3.1.
SPAN (inches) | MINIMUM NET THICKNESS (inches) OF LUMBER PLACED | |||
Perpendicular to supports | Diagonally to supports | |||
Surfaced dryc | Surfaced unseasoned | Surfaced dryc | Surfaced unseasoned | |
Floors | ||||
24 | 3/4 | 25/32 | 3/4 | 25/32 |
16 | 5/8 | 11/16 | 5/8 | 11/16 |
Roofs | ||||
24 | 5/8 | 11/16 | 3/4 | 25/32 |
SOLID FLOOR OR ROOF SHEATHING | SPACED ROOF SHEATHING | GRADING RULES |
Utility | Standard | NLGA, WCLIB, WWPA |
4 common or utility | 3 common or standard | NLGA, WCLIB, WWPA, NSLB or NELMA |
No. 3 | No. 2 | SPIB |
Merchantable | Construction common | RIS |
SHEATHING GRADES | ROOFc | FLOORd | ||||
Panel span rating roof/ floor span |
Panel thickness (inches) |
Maximum span (inches) | Loade(psf) | Maximum span (inches) |
||
With edge supportf | Without edge support | Total load | Live load | |||
16/0 | 3/8 | 16 | 16 | 40 | 30 | 0 |
20/0 | 3/8 | 20 | 20 | 40 | 30 | 0 |
24/0 | 3/8, 7/16, 1/2 | 24 | 20g | 40 | 30 | 0 |
24/16 | 7/16, 1/2 | 24 | 24 | 50 | 40 | 16 |
32/16 | 15/32, 1/2, 5/8 | 32 | 28 | 40 | 30 | 16h |
40/20 | 19/32, 5/8, 3/4, 7/8 | 40 | 32 | 40 | 30 | 20h,i |
48/24 | 23/32, 3/4, 7/8 | 48 | 36 | 45 | 35 | 24 |
54/32 | 7/8, 1 | 54 | 40 | 45 | 35 | 32 |
60/32 | 7/8, 11/8 | 60 | 48 | 45 | 35 | 32 |
SINGLE FLOOR GRADES | ROOFc | FLOORd | ||||
Panel span rating | Panel thickness (inches) |
Maximum span (inches) | Loade(psf) | Maximum span (inches) |
||
With edge supportf | Without edge support | Total load | Live load | |||
16 o.c. | 1/2, 19/32, 5/8 | 24 | 24 | 50 | 40 | 16h |
20 o.c. | 19/32, 5/8, 3/4 | 32 | 32 | 40 | 30 | 20h,i |
24 o.c. | 23/32,3/4 | 48 | 36 | 35 | 25 | 24 |
32 o.c. | 7/8, 1 | 48 | 40 | 50 | 40 | 32 |
48 o.c. | 13/32, 11/8 | 60 | 48 | 50 | 40 | 48 |
- Applies to panels 24 inches or wider.
- Floor and roof sheathing conforming with this table shall be deemed to meet the design criteria of Section 2304.7.
- Uniform load deflection limitations 1/180 of span under live load plus dead load, 1/240 under live load only.
- Panel edges shall have approved tongue-and-groove joints or shall be supported with blocking unless 1/4-inch minimum thickness underlayment or 11/2 inches of approved cellular or lightweight concrete is placed over the subfloor, or finish floor is 3/4-inch wood strip. Allowable uniform load based on deflection of 1/360 of span is 100 pounds per square foot except the span rating of 48 inches on center is based on a total load of 65 pounds per square foot.
- Allowable load at maximum span.
- Tongue-and-groove edges, panel edge clips (one midway between each support, except two equally spaced between supports 48 inches on center), lumber blocking or other. Only lumber blocking shall satisfy blocked diaphragm requirements.
- For 1/2-inch panel, maximum span shall be 24 inches.
- Span is permitted to be 24 inches on center where 3/4-inch wood strip flooring is installed at right angles to joist.
- Span is permitted to be 24 inches on center for floors where 11/2 inches of cellular or lightweight concrete is applied over the panels.
IDENTIFICATION | MAXIMUM SPACING OF JOISTS (inches) | ||||
16 | 20 | 24 | 32 | 48 | |
Species groupc | Thickness (inches) | ||||
1 | 1/2 | 5/8 | 3/4 | — | — |
2, 3 | 5/8 | 3/4 | 7/8 | — | — |
4 | 3/4 | 7/8 | 1 | — | — |
Single floor span ratingd | 16 o.c. | 20 o.c. | 24 o.c. | 32 o.c. | 48 o.c. |
- Spans limited to value shown because of possible effects of concentrated loads. Allowable uniform loads based on deflection of 1/360 of span is 100 pounds per square foot except allowable total uniform load for 11/8-inch wood structural panels over joists spaced 48 inches on center is 65 pounds per square foot. Panel edges shall have approved tongue-and-groove joints or shall be supported with blocking, unless 1/4-inch minimum thickness underlayment or 11/2 inches of approved cellular or lightweight concrete is placed over the subfloor, or finish floor is 3/4-inch wood strip.
- Floor panels conforming with this table shall be deemed to meet the design criteria of Section 2304.7.
- Applicable to all grades of sanded exterior-type plywood. See DOC PS 1 for plywood species groups.
- Applicable to Underlayment grade, C-C (Plugged) plywood, and Single Floor grade wood structural panels.
PANEL GRADE | THICKNESS (inch) | MAXIMUM SPAN (inches) | LOAD AT MAXIMUM SPAN (psf) | |
Live | Total | |||
Structural I sheathing | 7/16 | 24 | 20 | 30 |
15/32 | 24 | 35c | 45c | |
1/2 | 24 | 40c | 50c | |
19/32, 5/8 | 24 | 70 | 80 | |
23/32, 3/4 | 24 | 90 | 100 | |
Sheathing, other grades covered in DOC PS 1 or DOC PS 2 | 7/16 | 16 | 40 | 50 |
15/32 | 24 | 20 | 25 | |
1/2 | 24 | 25 | 30 | |
19/32 | 24 | 40c | 50c | |
5/8 | 24 | 45c | 55c | |
23/32, 3/4 | 24 | 60c | 65c |
- Roof sheathing conforming with this table shall be deemed to meet the design criteria of Section 2304.7.
- Uniform load deflection limitations 1/180 of span under live load plus dead load, 1/240 under live load only. Edges shall be blocked with lumber or other approved type of edge supports.
- For composite and four-ply plywood structural panel, load shall be reduced by 15 pounds per square foot.
Structural floor sheathing shall be designed in accordance with the general provisions of this code and the special provisions in this section.
Floor sheathing conforming to the provisions of Table 2304.7(1), 2304.7(2), 2304.7(3) or 2304.7(4) shall be deemed to meet the requirements of this section.
Decking that cantilevers beyond a support for a horizontal distance greater than 18 inches (457 mm), 24 inches (610 mm) or 36 inches (914 mm) for 2-inch (51 mm), 3-inch (76 mm) and 4-inch (102 mm) nominal thickness decking, respectively, shall comply with the following:
- The maximum cantilevered length shall be 30 percent of the length of the first adjacent interior span.
- A structural fascia shall be fastened to each decking piece to maintain a continuous, straight line.
- There shall be no end joints in the decking between the cantilevered end of the decking and the centerline of the first adjacent interior span.
Laminations shall be toenailed to supports with 20d or larger common nails. Where the supports are 48 inches (1219 mm) o.c. or less, alternate laminations shall be toenailed to alternate supports; where supports are spaced more than 48 inches (1219 mm) o.c., alternate laminations shall be toenailed to every support.
CONNECTION | FASTENINGa, m |
LOCATION | ||
1. Joist to sill or girder | 3 - 8d common (21/2" × 0.131") | toenail | ||
3 - 3" × 0.131"nails | ||||
3 - 3" 14 gage staples | ||||
2. Bridging to joist | 2 - 8d common (21/2" × 0.131") | toenail each end | ||
2 - 3" × 0.131" nails | ||||
2 - 3" 14 gage staples | ||||
3. 1" × 6" subfloor or less to each joist | 2 - 8d common (21/2" × 0.131") | face nail | ||
4. Wider than 1"× 6" subfloor to each joist | 3 - 8d common (21/2" × 0.131") | face nail | ||
5. 2"subfloor to joist or girder | 2 - 16d common (31/2" × 0.162") | blind and face nail | ||
6. Sole plate to joist or blocking | 16d (31/2" × 0.135") at 16" o.c. | typical face nail | ||
3" × 0.131" nails at 8" o.c. | ||||
3" 14 gage staples at 12" o.c. | ||||
Sole plate to joist or blocking at braced wall panel | 3- 16d (31/2" × 0.135") at 16" o.c. | braced wall panels | ||
4 - 3" × 0.131" nails at 16" o.c. | ||||
4 - 3" 14 gage staples at 16" o.c. | ||||
7. Top plate to stud | 2 - 16d common (31/2" × 0.162") | end nail | ||
3 - 3" × 0.131" nails | ||||
3 - 3"14 gage staples | ||||
8. Stud to sole plate | 4 - 8d common (21/2" × 0.131") | toenail | ||
4 - 3" × 0.131" nails | ||||
3 - 3" 14 gage staples | ||||
2 - 16d common (31/2" × 0.162") | end nail | |||
3 - 3" × 0.131" nails | ||||
3 - 3" 14 gage staples | ||||
9. Double studs | 16d (31/2" × 0.135")at 24" o.c. | face nail | ||
3" × 0.131" nail at 8" o.c. | ||||
3" 14 gage staple at 8" o.c. | ||||
10. Double top plates | 16d (31/2" × 0.135") at 16" o.c. | typical face nail | ||
3" × 0.131" nail at 12" o.c. | ||||
3" 14 gage staple at 12" o.c. | ||||
Double top plates | 8 - 16d common (31/2" × 0.162") | lap splice | ||
12 - 3" × 0.131"nails | ||||
12 - 3" 14 gage staples | ||||
11. Blocking between joists or rafters to top plate | 3 - 8d common (21/2" × 0.131") | toenail | ||
3 - 3" × 0.131" nails | ||||
3 - 3" 14 gage staples | ||||
12. Rim joist to top plate | 8d (21/2" × 0.131") at 6" o.c. | toenail | ||
3" × 0.131"nail at 6" o.c. | ||||
3" 14 gage staple at 6" o.c. | ||||
13. Top plates, laps and intersections | 2 - 16d common (31/2" × 0.162") | face nail | ||
3 - 3" × 0.131"nails | ||||
3 - 3" 14 gage staples | ||||
14. Continuous header, two pieces | 16d common (31/2" × 0.162") | 16"o.c. along edge | ||
15. Ceiling joists to plate | 3 - 8d common (21/2" × 0.131") | toenail | ||
5 - 3" × 0.131"nails | ||||
5 - 3" 14 gage staples | ||||
16. Continuous header to stud | 4 - 8d common (21/2" × 0.131") | toenail | ||
17. Ceiling joists, laps over partitions (see Section 2308.10.4.1, Table 2308.10.4.1) |
3 - 16d common (31/2" × 0.162") minimum, Table 2308.10.4.1 | face nail | ||
4 - 3" × 0.131" nails | ||||
4 - 3" 14 gage staples | ||||
18. Ceiling joists to parallel rafters (see Section 2308.10.4.1, Table 2308.10.4.1) |
3 - 16d common (31/2" × 0.162") minimum, Table 2308.10.4.1 | face nail | ||
4 - 3" × 0.131" nails | ||||
4 - 3" 14 gage staples | ||||
19. Rafter to plate (see Section 2308.10.1, Table 2308.10.1) |
3 - 8d common (21/2" × 0.131") | toenail | ||
3 - 3" × 0.131" nails | ||||
3 - 3" 14 gage staples | ||||
20. 1" diagonal brace to each stud and plate | 2 - 8d common (21/2" × 0.131") | face nail | ||
2 - 3" × 0.131" nails | ||||
3 - 3" 14 gage staples | ||||
21. 1" × 8" sheathing to each bearing | 3 - 8d common (21/2" × 0.131") | face nail | ||
22. Wider than 1" × 8" sheathing to each bearing | 3 - 8d common (21/2" × 0.131") | face nail | ||
23. Built-up corner studs | 16d common (31/2" × 0.162") | 24" o.c. | ||
3" × 0.131" nails | 16" o.c. | |||
3" 14 gage staples | 16" o.c. | |||
24. Built-up girder and beams | 20d common (4" × 0.192") 32" o.c. | face nail at top and bottom staggered on opposite sides | ||
3" × 0.131" nail at 24"o.c. | ||||
3" 14 gage staple at 24"o.c. | ||||
2 - 20d common (4" × 0.192") | face nail at ends and at each splice | |||
3 - 3" × 0.131" nails | ||||
3 - 3" 14 gage staples | ||||
25. 2" planks | 16d common (31/2" × 0.162") | at each bearing | ||
26. Collar tie to rafter | 3 - 10d common (3" × 0.148") | face nail | ||
4 - 3" × 0.131" nails | ||||
4 - 3" 14 gage staples | ||||
27. Jack rafter to hip | 3 - 10d common (3" × 0.148") | toenail | ||
4 - 3" × 0.131" nails | ||||
4 - 3" 14 gage staples | ||||
2 - 16d common (31/2" × 0.162") | face nail | |||
3 - 3" × 0.131" nails | ||||
3 - 3" 14 gage staples | ||||
28. Roof rafter to 2-by ridge beam | 2 - 16d common (31/2" × 0.162") | toenail | ||
3 - 3" × 0.131" nails | ||||
3 - 3" 14 gage staples | ||||
2 -16d common (31/2" × 0.162") | face nail | |||
3 - 3" × 0.131" nails | ||||
3 - 3" 14 gage staples | ||||
29. Joist to band joist | 3 - 16d common (31/2" × 0.162") | face nail | ||
4 - 3" × 0.131" nails | ||||
4 - 3" 14 gage staples | ||||
30. Ledger strip | 3 - 16d common (31/2" × 0.162") | face nail at each joist | ||
4 - 3" × 0.131" nails | ||||
4 - 3"14 gage staples | ||||
31. Wood structural panels and particleboardb Subfloor, roof and wall sheathing (to framing) |
1/2" and less | 6dc, 1 | ||
23/8" × 0.113" nailn | ||||
13/4" 16 gageo | ||||
19/32" to 3/4" | 8dd or 6de | |||
23/8" × 0.113" nailp | ||||
2" 16 gagep | ||||
8dc | ||||
7/8" to 1" | 10dd or 8de | |||
Single floor (combination subfloor-underlayment to framing) | 11/8" to 11/4" | |||
3/4" and less | 6de | |||
7/8" to 1" | 8de | |||
11/8" to 11/4" | 10dd or 8de | |||
32. Panel siding (to framing) | 1/2" or less | 6df | ||
5/8" | 8df | |||
33. Fiberboard sheathingg | 1/2" | No. 11 gage roofing nailh | ||
6d common nail (2" × 0.113") | ||||
No. 16 gage staplei | ||||
25/32" | No. 11 gage roofing nailh | |||
8d common nail (21/2" × 0.131") | ||||
No. 16 gage staplei | ||||
34. Interior paneling | 1/4" | 4dj | ||
3/8" | 6dk |
- Common or box nails are permitted to be used except where otherwise stated.
- Nails spaced at 6 inches on center at edges, 12 inches at intermediate supports except 6 inches at supports where spans are 48 inches or more. For nailing of wood structural panel and particleboard diaphragms and shear walls, refer to Section 2305. Nails for wall sheathing are permitted to be common, box or casing.
- Common or deformed shank (6d - 2" × 0.113"; 8d - 21/2" × 0.131"; 10d - 3" × 0.148").
- Common (6d - 2" × 0.113"; 8d - 21/2" × 0.131"; 10d - 3" × 0.148").
- Deformed shank (6d - 2" × 0.113"; 8d - 21/2" × 0.131"; 10d - 3" × 0.148").
- Corrosion-resistant siding (6d - 17/8" × 0.106"; 8d - 23/8" × 0.128") or casing (6d - 2" × 0.099"; 8d - 21/2" × 0.113") nail.
- Fasteners spaced 3 inches on center at exterior edges and 6 inches on center at intermediate supports, when used as structural sheathing. Spacing shall be 6 inches on center on the edges and 12 inches on center at intermediate supports for nonstructural applications.
- Corrosion-resistant roofing nails with 7/16-inch-diameter head and 11/2-inch length for 1/2-inch sheathing and 13/4-inch length for 25/32-inch sheathing.
- Corrosion-resistant staples with nominal 7/16-inch crown or 1-inch crown and 11/4-inch length for 1/2-inch sheathing and 11/2-inch length for 25/32-inch sheathing. Panel supports at 16 inches (20 inches if strength axis in the long direction of the panel, unless otherwise marked).
- Casing (11/2" × 0.080") or finish (11/2" × 0.072") nails spaced 6 inches on panel edges, 12 inches at intermediate supports.
- Panel supports at 24 inches. Casing or finish nails spaced 6 inches on panel edges, 12 inches at intermediate supports.
- For roof sheathing applications, 8d nails (21/2" × 0.113") are the minimum required for wood structural panels.
- Staples shall have a minimum crown width of 7/16 inch.
- For roof sheathing applications, fasteners spaced 4 inches on center at edges, 8 inches at intermediate supports.
- Fasteners spaced 4 inches on center at edges, 8 inches at intermediate supports for subfloor and wall sheathing and 3 inches on center at edges, 6 inches at intermediate supports for roof sheathing.
- Fasteners spaced 4 inches on center at edges, 8 inches at intermediate supports.
- Posts or columns that are either exposed to the weather or located in basements or cellars, supported by concrete piers or metal pedestals projected at least 1 inch (25 mm) above the slab or deck and 6 inches (152 mm) above exposed earth, and are separated therefrom by an impervious moisture barrier.
- Posts or columns in enclosed crawl spaces or unexcavated areas located within the periphery of the building, supported by a concrete pier or metal pedestal at a height greater than 8 inches (203 mm) from exposed ground, and are separated therefrom by an impervious moisture barrier.
(Equation 23-1) |
For SI: |
where:
A | = | Area of chord cross section, in square inches (mm2). |
b | = | Diaphragm width, in feet (mm). |
E | = | Elastic modulus of chords, in pounds per square inch (N/mm2). |
en | = | Staple deformation, in inches (mm) [see Table 2305.2(1)]. |
Gt | = | Panel rigidity through the thickness, in pounds per inch (N/mm) of panel width or depth [see Table 2305.2(2)]. |
L | = | Diaphragm length, in feet (mm). |
v | = | Maximum shear due to design loads in the direction under consideration, in pounds per linear foot (plf) (N/mm). |
Δ | = | The calculated deflection, in inches (mm). |
Σ(ΔcX ) | = | Sum of individual chord-splice slip values on both sides of the diaphragm, each multiplied by its distance to the nearest support. |
LOAD PER FASTENERb (pounds) |
FASTENER DESIGNATIONS |
14-Ga staple x 2 inches long | |
60 | 0.011 |
80 | 0.018 |
100 | 0.028 |
120 | 0.04 |
140 | 0.053 |
160 | 0.068 |
- Increase en values 20 percent for plywood grades other than Structural I.
- Load per fastener = maximum shear per foot divided by the number of fasteners per foot at interior panel edges.
- Decrease en values 50 percent for seasoned lumber (moisture content
PANEL TYPE |
SPAN RATING |
VALUES OF Gt (lb/in. panel depth or width) | |||||||
OTHER | STRUCTURAL I | ||||||||
3-ply Plywood |
4-ply Plywood |
5-ply Plywooda |
OSB | 3-ply Plywood |
4-ply Plywood |
5-ply Plywooda |
OSB | ||
Sheathing | 24/0 | 25,000 | 32,500 | 37,500 | 77,500 | 32,500 | 42,500 | 41,500 | 77,500 |
24/16 | 27,000 | 35,000 | 40,500 | 83,500 | 35,000 | 45,500 | 44,500 | 83,500 | |
32/16 | 27,000 | 35,000 | 40,500 | 83,500 | 35,000 | 45,500 | 44,500 | 83,500 | |
40/20 | 28,500 | 37,000 | 43,000 | 88,500 | 37,000 | 48,000 | 47,500 | 88,500 | |
48/24 | 31,000 | 40,500 | 46,500 | 96,000 | 40,500 | 52,500 | 51,000 | 96,000 | |
Single Floor | 16 o.c. | 27,000 | 35,000 | 40,500 | 83,500 | 35,000 | 45,500 | 44,500 | 83,500 |
20 o.c. | 28,000 | 36,500 | 42,000 | 87,000 | 36,500 | 47,500 | 46,000 | 87,000 | |
24 o.c. | 30,000 | 39,000 | 45,000 | 93,000 | 39,000 | 50,500 | 49,500 | 93,000 | |
32 o.c. | 36,000 | 47,000 | 54,000 | 110,000 | 47,000 | 61,000 | 59,500 | 110,000 | |
48 o.c. | 50,500 | 65,500 | 76,000 | 155,000 | 65,500 | 85,000 | 83,500 | 155,000 |
OTHER | STRUCTURAL I | ||||||
Thickness (in.) |
A-A, A-C |
Marine | All Other Grades |
A-A, A-C |
Marine | All Other Grades |
|
Sanded Plywood | 1/4 | 24,000 | 31,000 | 24,000 | 31,000 | 31,000 | 31,000 |
11/32 | 25,500 | 33,000 | 25,500 | 33,000 | 33,000 | 33,000 | |
3/8 | 26,000 | 34,000 | 26,000 | 34,000 | 34,000 | 34,000 | |
15/32 | 38,000 | 49,500 | 38,000 | 49,500 | 49,500 | 49,500 | |
1/2 | 38,500 | 50,000 | 38,500 | 50,000 | 50,000 | 50,000 | |
19/32 | 49,000 | 63,500 | 49,000 | 63,500 | 63,500 | 63,500 | |
5/8 | 49,500 | 64,500 | 49,500 | 64,500 | 64,500 | 64,500 | |
23/32 | 50,500 | 65,500 | 50,500 | 65,500 | 65,500 | 65,500 | |
3/4 | 51,000 | 66,500 | 51,000 | 66,500 | 66,500 | 66,500 | |
7/8 | 52,500 | 68,500 | 52,500 | 68,500 | 68,500 | 68,500 | |
1 | 73,500 | 95,500 | 73,500 | 95,500 | 95,500 | 95,500 | |
11/8 | 75,000 | 97,500 | 75,000 | 97,500 | 97,500 | 97,500 |
(Equation 23-2) |
For SI: |
where:
A | = | Area of boundary element cross section in square inches (mm2) (vertical member at shear wall boundary). |
b | = | Wall width, in feet (mm). |
da | = | Vertical elongation of overturning anchorage (including fastener slip, device elongation, anchor rod elongation, etc.) at the design shear load (v). |
E | = | Elastic modulus of boundary element (vertical member at shear wall boundary), in pounds per square inch (N/mm2). |
en | = | Staple deformation, in inches (mm) [see Table 2305.2(1)]. |
Gt | = | Panel rigidity through the thickness, in pounds per inch (N/mm) of panel width or depth [see Table 2305.2(2)]. |
h | = | Wall height, in feet (mm). |
v | = | Maximum shear due to design loads at the top of the wall, in pounds per linear foot (N/mm). |
Δ | = | The calculated deflection, in inches (mm). |
American Forest & Paper Association. | |
NDS | National Design Specification for Wood Construction |
SDPWS | Special Design Provisions for Wind and Seismic |
American Institute of Timber Construction. | |
AITC 104 | Typical Construction Details |
AITC 110 | Standard Appearance Grades for Structural Glued Laminated Timber |
AITC 113 | Standard for Dimensions of Structural Glued Laminated Timber |
AITC 117 | Standard Specifications for Structural Glued Laminated Timber of Softwood Species |
AITC 119 | Standard Specifications for Structural Glued Laminated Timber of Hardwood Species |
ANSI/AITC A190.1 | Structural Glued Laminated Timber |
AITC 200 | Inspection Manual |
American Society of Agricultural and Biological Engineers. | |
ASABE EP 484.2 | Diaphragm Design of Metal-clad, Post- Frame Rectangular Buildings |
ASABE EP 486.1 | Shallow Post Foundation Design |
ASABE 559 | Design Requirements and Bending Properties for Mechanically Laminated Columns |
APA—The Engineered Wood Association. | |
Panel Design Specification | |
Plywood Design Specification Supplement 1— Design & Fabrication of Plywood Curved Panel | |
Plywood Design Specification Supplement 2— Design & Fabrication of Glued Plywood-lumber Beams | |
Plywood Design Specification Supplement 3— Design & Fabrication of Plywood Stressed-skin Panels | |
Plywood Design Specification Supplement 4— Design & Fabrication of Plywood Sandwich Panels | |
Plywood Design Specification Supplement 5— Design & Fabrication of All-plywood Beams | |
EWS T300 | Glulam Connection Details |
EWS S560 | Field Notching and Drilling of Glued Laminated Timber Beams |
EWS S475 | Glued Laminated Beam Design Tables |
EWS X450 | Glulam in Residential Construction |
EWS X440 | Product and Application Guide: Glulam |
EWS R540 | Builders Tips: Proper Storage and Handling of Glulam Beams |
Truss Plate Institute, Inc. | |
TPI 1 | National Design Standard for Metal Plate Connected Wood Truss Construction |
PATTERN | ALLOWABLE AREA LOADa, b | |
Flexure | Deflection | |
Simple span | ||
Two-span continuous | ||
Combination simple- and two-span continuous | ||
Cantilevered pieces intermixed |
||
Controlled random layup | ||
Mechanically laminated decking | ||
2-inch decking | ||
3-inch and 4-inch decking |
- σb = Allowable total uniform load limited by bending.
σΔ = Allowable total uniform load limited by deflection. - d = Actual decking thickness.
l = Span of decking.
Fb' = Allowable bending stress adjusted by applicable factors.
E' = Modulus of elasticity adjusted by applicable factors.
PANEL GRADE | STAPLE LENGTH AND GAGEd | MINIMUM FASTENER PENETRATION IN FRAMING (inches) | MINIMUM NOMINAL PANEL THICKNESS (inch) | MINIMUM NOMINAL WIDTH OF FRAMING MEMBERS AT ADJOINING PANEL EDGES AND BOUNDARIESe (inches) | BLOCKED DIAPHRAGMS | UNBLOCKED DIAPHRAGMS | ||||
Fastener spacing (inches) at diaphragm boundaries (all cases) at continuous panel edges parallel to load (Cases 3, 4), and at all panel edges (Cases 5, 6)b | Fasteners spaced 6 max. at supported edgesb | |||||||||
6 | 4 | 21/2c | 2c | Case 1 (No unblocked edges or continuous joints parallel to load) | All other configurations (Cases 2, 3, 4, 5 and 6) | |||||
Fastener spacing (inches) at other panel edges (Cases 1, 2, 3 and 4)b | ||||||||||
6 | 6 | 4 | 3 | |||||||
Structural I grades | 11/2 16 gage | 1 | 3/8 | 2 | 175 | 235 | 350 | 400 | 155 | 115 |
3 | 200 | 265 | 395 | 450 | 175 | 130 | ||||
15/32 | 2 | 175 | 235 | 350 | 400 | 155 | 120 | |||
3 | 200 | 265 | 395 | 450 | 175 | 130 | ||||
Sheathing, single floor and other grades covered in DOC PS 1 and PS 2 | 11/2 16 gage | 1 | 3/8 | 2 | 160 | 210 | 315 | 360 | 140 | 105 |
3 | 180 | 235 | 355 | 400 | 160 | 120 | ||||
7/16 | 2 | 165 | 225 | 335 | 380 | 150 | 110 | |||
3 | 190 | 250 | 375 | 425 | 165 | 125 | ||||
15/32 | 2 | 160 | 210 | 315 | 360 | 140 | 105 | |||
3 | 180 | 235 | 355 | 405 | 160 | 120 | ||||
19/32 | 2 | 175 | 235 | 350 | 400 | 155 | 115 | |||
3 | 200 | 265 | 395 | 450 | 175 | 130 |
- For framing of other species: (1) Find specific gravity for species of lumber in AF&PA NDS. (2) For staples find shear value from table above for Structural I panels (regardless of actual grade) and multiply value by 0.82 for species with specific gravity of 0.42 or greater, or 0.65 for all other species.
- Space fasteners maximum 12 inches o.c. along intermediate framing members (6 inches o.c. where supports are spaced 48 inches o.c.).
- Framing at adjoining panel edges shall be 3 inches nominal or wider.
- Staples shall have a minimum crown width of 7/16 inch and shall be installed with their crowns parallel to the long dimension of the framing members.
- The minimum nominal width of framing members not located at boundaries or adjoining panel edges shall be 2 inches.
- For shear loads of normal or permanent load duration as defined by the AF&PA NDS, the values in the table above shall be multiplied by 0.63 or 0.56, respectively.
PANEL GRADEc | STAPLE GAGEf | MINIMUM FASTENER PENETRATION IN FRAMING (inches) | MINIMUM NOMINAL PANEL THICKNESS (inch) | MINIMUM NOMINAL WIDTH OF FRAMING MEMBER AT ADJOINING PANEL EDGES AND BOUNDARIESe | LINES OF FASTENERS | BLOCKED DIAPHRAGMS | |||||||
Cases 1 and 2d | |||||||||||||
Fastener Spacing Per Line at Boundaries (inches) | |||||||||||||
4 | 21/2 | 2 | |||||||||||
Fastener Spacing Per Line at Other Panel Edges (inches) | |||||||||||||
6 | 4 | 4 | 3 | 3 | 2 | ||||||||
Structural I grades | 14 gage staples | 2 | 15/32 | 3 | 2 | 600 | 600 | 860 | 960 | 1,060 | 1,200 | ||
4 | 3 | 860 | 900 | 1,160 | 1,295 | 1,295 | 1,400 | ||||||
19/32 | 3 | 2 | 600 | 600 | 875 | 960 | 1,075 | 1,200 | |||||
4 | 3 | 875 | 900 | 1,175 | 1,440 | 1,475 | 1,795 | ||||||
Sheathing single floor and other grades covered in DOC PS 1 and PS 2 | 14 gage staples | 2 | 15/32 | 3 | 2 | 540 | 540 | 735 | 865 | 915 | 1,080 | ||
4 | 3 | 735 | 810 | 1,005 | 1,105 | 1,105 | 1,195 | ||||||
19/32 | 3 | 2 | 600 | 600 | 865 | 960 | 1,065 | 1,200 | |||||
4 | 3 | 865 | 900 | 1,130 | 1,430 | 1,370 | 1,485 | ||||||
23/32 | 4 | 3 | 865 | 900 | 1,130 | 1,490 | 1,430 | 1,545 |
- For framing of other species: (1) Find specific gravity for species of framing lumber in AF&PA NDS. (2) For staples, find shear value from table above for Structural I panels (regardless of actual grade) and multiply value by 0.82 for species with specific gravity of 0.42 or greater, or 0.65 for all other species.
- Fastening along intermediate framing members: Space fasteners a maximum of 12 inches on center, except 6 inches on center for spans greater than 32 inches.
- Panels conforming to PS 1 or PS 2.
- This table gives shear values for Cases 1 and 2 as shown in Table 2306.2(1). The values shown are applicable to Cases 3, 4, 5 and 6 as shown in Table 2306.2(1), providing fasteners at all continuous panel edges are spaced in accordance with the boundary fastener spacing.
- The minimum nominal depth of framing members shall be 3 inches nominal. The minimum nominal width of framing members not located at boundaries or adjoining panel edges shall be 2 inches.
- Staples shall have a minimum crown width of 7/16 inch, and shall be installed with their crowns parallel to the long dimension of the framing members.
- High-load diaphragms shall be subject to special inspection in accordance with Section 1705.5.1.
- For shear loads of normal or permanent load duration as defined by the AF&PA NDS, the values in the table above shall be multiplied by 0.63 or 0.56, respectively.
Wood-frame shear walls shall be designed and constructed in accordance with AF&PA; SDPWS. Where panels are fastened to framing members with staples, requirements and limitations of AF&PA; SDPWS shall be met and the allowable shear values set forth in Table 2306.3(1), 2306.3(2) or 2306.3(3) shall be permitted. The allowable shear values in Tables 2306.3(1) and 2306.3(2) are permitted to be increased 40 percent for wind design. Panels complying with ANSI/APA PRP-210 shall be permitted to use design values for Plywood Siding in the AF&PA; SDPWS.
PANEL GRADE | MINIMUM NOMINAL PANEL THICKNESS (inch) |
MINIMUM FASTENER PENETRATION IN FRAMING (inches) |
PANELS APPLIED DIRECT TO FRAMING | PANELS APPLIED OVER 1/2" OR5/8" GYPSUM SHEATHING |
||||||||
Staple sizeh | Fastener spacing at panel edges (inches) |
Staple sizeh | Fastener spacing at panel edges (inches) |
|||||||||
6 | 4 | 3 | 2d | 6 | 4 | 3 | 2 d | |||||
Structural I sheathing | 3/8 | 1 | 11/2 16 Gage |
155 | 235 | 315 | 400 | 2 16 Gage | 155 | 235 | 310 | 400 |
7/16 | 170 | 260 | 345 | 440 | 155 | 235 | 310 | 400 | ||||
15/32 | 185 | 280 | 375 | 475 | 155 | 235 | 300 | 400 | ||||
Sheathing, plywood sidinge except Group 5 Species, ANSI/APA PRP 210 siding |
5/16c or 1/4c | 1 | 11/2 16 Gage |
145 | 220 | 295 | 375 | 2 16 Gage | 110 | 165 | 220 | 285 |
3/8 | 140 | 210 | 280 | 360 | 140 | 210 | 280 | 360 | ||||
7/16 | 155 | 230 | 310 | 395 | 140 | 210 | 280 | 360 | ||||
15/32 | 170 | 255 | 335 | 430 | 140 | 210 | 280 | 360 | ||||
19/32 | 13/4 16 Gage |
185 | 280 | 375 | 475 | — | — | — | — | — |
- For framing of other species: (1) Find specific gravity for species of lumber in AF&PA NDS. (2) For staples find shear value from table above for Structural I panels (regardless of actual grade) and multiply value by 0.82 for species with specific gravity of 0.42 or greater, or 0.65 for all other species.
- Panel edges backed with 2-inch nominal or wider framing. Install panels either horizontally or vertically. Space fasteners maximum 6 inches on center along intermediate framing members for 3/8-inch and 7/16-inch panels installed on studs spaced 24 inches on center. For other conditions and panel thickness, space fasteners maximum 12 inches on center on intermediate supports.
- 3/8-inch panel thickness or siding with a span rating of 16 inches on center is the minimum recommended where applied directly to framing as exterior siding. For grooved panel siding, the nominal panel thickness is the thickness of the panel measured at the point of fastening.
- Framing at adjoining panel edges shall be 3 inches nominal or wider.
- Values apply to all-veneer plywood. Thickness at point of fastening on panel edges governs shear values.
- Where panels are applied on both faces of a wall and fastener spacing is less than 6 inches o.c. on either side, panel joints shall be offset to fall on different framing members, or framing shall be 3 inches nominal or thicker at adjoining panel edges.
- In Seismic Design Category D, E or F, where shear design values exceed 350 pounds per linear foot, all framing members receiving edge fastening from abutting panels shall not be less than a single 3-inch nominal member, or two 2-inch nominal members fastened together in accordance with Section 2306.1 to transfer the design shear value between framing members. Wood structural panel joint and sill plate nailing shall be staggered at all panel edges. See AF&PA SDPWS for sill plate size and anchorage requirements.
- Staples shall have a minimum crown width of 7/16 inch and shall be installed with their crowns parallel to the long dimension of the framing members.
- For shear loads of normal or permanent load duration as defined by the AF&PA NDS, the values in the table above shall be multiplied by 0.63 or 0.56, respectively.
THICKNESS AND GRADE | FASTENER SIZE | ALLOWABLE SHEAR VALUE (pounds per linear foot) STAPLE SPACING AT PANEL EDGES (inches)a |
||
4 | 3 | 2 | ||
1/2" or 25/32" Structural | No. 16 gage galvanized staple, 7/16" crownf | 150 | 200 | 225 |
No. 16 gage galvanized staple, 1" crownf | 220 | 290 | 325 |
- Fiberboard sheathing shall not be used to brace concrete or masonry walls.
- Panel edges shall be backed with 2-inch or wider framing of Douglas fir-larch or Southern pine. For framing of other species: (1) Find specific gravity for species of framing lumber in AF&PA NDS. (2) For staples, multiply the shear value from the table above by 0.82 for species with specific gravity of 0.42 or greater, or 0.65 for all other species.
- Values shown are for fiberboard sheathing on one side only with long panel dimension either parallel or perpendicular to studs.
- Fastener shall be spaced 6 inches on center along intermediate framing members.
- Values are not permitted in Seismic Design Category D, E or F.
- Staple length shall not be less than 11/2 inches for 25/32-inch sheathing or 11/4 inches for 1/2-inch sheathing.
TYPE OF MATERIAL | THICKNESS OF MATERIAL |
WALL CONSTRUCTION |
STAPLE SPACINGb MAXIMUM (inches) |
SHEAR VALUEa, c (plf) |
MINIMUM STAPLE SIZEf, g |
1. Expanded metal or woven wire lath and Portland cement plaster |
7/8" | Unblocked | 6 | 180 | No. 16 gage galv. staple,7/8" legs |
2. Gypsum lath, plain or perforated | 3/8" lath and 1/2" plaster |
Unblocked | 5 | 100 | No. 16 gage galv. staple, 11/8" long |
3. Gypsum sheating | 1/2" × 2' × 8' | Unblocked | 4 | 75 | No. 16 gage galv. staple, 13/4" long |
1/2" × 4' | Blockedd Unblocked |
4 7 |
175 100 |
||
4. Gypsum board, gypsum veneer base or water-resistant gypsum backing board |
1/2" | Unblockedd | 7 | 75 | No. 16 gage galv. staple, 11/2" long |
Unblockedd | 4 | 110 | |||
Unblocked | 7 | 100 | |||
Unblocked | 4 | 125 | |||
Blockede | 7 | 125 | |||
Blockede | 4 | 150 | |||
5/8" | Unblockedd | 7 | 115 | No. 16 gage galv. staple, 11/2" legs,15/8" long | |
4 | 145 | ||||
Blockede | 7 | 145 | |||
4 | 175 | ||||
Blockede Two-ply |
Base ply: 9 Face ply: 7 |
250 | No. 16 gage galv. staple 15/8" long No. 15 gage galv. staple, 21/4" long |
- These shear walls shall not be used to resist loads imposed by masonry or concrete walls (see AF & PA SDPWS). Values shown are for short-term loading due to wind or seismic loading. Walls resisting seismic loads shall be subject to the limitations in Section 12.2.1 of ASCE 7. Values shown shall be reduced 25 percent for normal loading.
- Applies to fastening at studs, top and bottom plates and blocking.
- Except as noted, shear values are based on a maximum framing spacing of 16 inches on center.
- Maximum framing spacing of 24 inches on center.
- All edges are blocked, and edge fastening is provided at all supports and all panel edges.
- Staples shall have a minimum crown width of 7/16 inch, measured outside the legs, and shall be installed with their crowns parallel to the long dimension of the framing members.
- Staples for the attachment of gypsum lath and woven-wire lath shall have a minimum crown width of 3/4 inch, measured outside the legs.
- Buildings shall be limited to a maximum of three stories above grade plane. For the purposes of this section, for buildings assigned to Seismic Design Category D or E, cripple stud walls shall be considered to be a story.
Exception: Solid blocked cripple walls not exceeding 14 inches (356 mm) in height need not be considered a story.
- Maximum floor-to-floor height shall not exceed 11 feet, 7 inches (3531 mm). Bearing wall height shall not exceed a stud height of 10 feet (3048 mm).
- Loads as determined in Chapter 16 shall not exceed the following:
- Average dead loads shall not exceed 15 psf (718 N/m2) for combined roof and ceiling, exterior walls, floors and partitions.
Exceptions:
- Subject to the limitations of Sections 2308.11.2 and 2308.12.2, stone or masonry veneer up to the lesser of 5 inches (127 mm) thick or 50 psf (2395 N/m2) and installed in accordance with Chapter 14 is permitted to a height of 30 feet (9144 mm) above a noncombustible foundation, with an additional 8 feet (2438 mm) permitted for gable ends.
- Concrete or masonry fireplaces, heaters and chimneys shall be permitted in accordance with the provisions of this code.
- Live loads shall not exceed 40 psf (1916 N/m2) for floors.
- Ground snow loads shall not exceed 50 psf (2395 N/m2).
- Average dead loads shall not exceed 15 psf (718 N/m2) for combined roof and ceiling, exterior walls, floors and partitions.
- Vasd as determined in accordance with Section 1609.3.1 shall not exceed 100 miles per hour (mph) (44 m/s) (3-second gust).
Exception: Vasd as determined in accordance with Section 1609.3.1 shall not exceed 110 mph (48.4 m/s) (3-second gust) for buildings in Exposure Category B that are not located in a hurricane-prone region.
- Roof trusses and rafters shall not span more than 40 feet (12 192 mm) between points of vertical support.
- The use of the provisions for conventional light-frame construction in this section shall not be permitted for Risk Category IV buildings assigned to Seismic Design Category B, C, D, E or F.
- Conventional light-frame construction is limited in irregular structures assigned to Seismic Design Category D or E, as specified in Section 2308.12.6.
At exterior gable end walls braced wall panel sheathing in the top story shall be extended and fastened to roof framing where the spacing between parallel exterior braced wall lines is greater than 50 feet (15 240 mm).
Where roof trusses are used and are installed perpendicular to an exterior braced wall line, lateral forces shall be transferred from the roof diaphragm to the braced wall over the full length of the braced wall line by blocking of the ends of the trusses or by other approved methods providing equivalent lateral force transfer. Blocking shall be minimum 2 inches (51 mm) nominal thickness and shall extend to within 2 inches (51 mm) from the roof sheathing above and shall be fastened to the braced wall line top plate as specified in Table 2304.9.1, Item 11. Notching or drilling of holes in blocking in accordance with the requirements of Section 2308.8.2 or Section 2308.10.4.2 shall be permitted.
Where a girder is spliced over a support, an adequate tie shall be provided. The ends of beams or girders supported on masonry or concrete shall not have less than 3 inches (76 mm) of bearing.
JOIST SPACING (inches) |
SPECIES AND GRADE | DEAD LOAD = 10 psf | DEAD LOAD = 20 psf | |||||||
2x6 | 2x8 | 2x10 | 2x12 | 2x6 | 2x8 | 2x10 | 2x12 | |||
Maximum floor joist spans | ||||||||||
(ft. - in.) | (ft. - in.) | (ft. - in.) | (ft. - in.) | (ft. - in.) | (ft. - in.) | (ft. - in.) | (ft. - in.) | |||
12 | Douglas Fir-Larch | SS | 12-6 | 16-6 | 21-0 | 25-7 | 12-6 | 16-6 | 21-0 | 25-7 |
Douglas Fir-Larch | #1 | 12-0 | 15-10 | 20-3 | 24-8 | 12-0 | 15-7 | 19-0 | 22-0 | |
Douglas Fir-Larch | #2 | 11-10 | 15-7 | 19-10 | 23-0 | 11-6 | 14-7 | 17-9 | 20-7 | |
Douglas Fir-Larch | #3 | 9-8 | 12-4 | 15-0 | 17-5 | 8-8 | 11-0 | 13-5 | 15-7 | |
Hem-Fir | SS | 11-10 | 15-7 | 19-10 | 24-2 | 11-10 | 15-7 | 19-10 | 24-2 | |
Hem-Fir | #1 | 11-7 | 15-3 | 19-5 | 23-7 | 11-7 | 15-2 | 18-6 | 21-6 | |
Hem-Fir | #2 | 11-0 | 14-6 | 18-6 | 22-6 | 11-0 | 14-4 | 17-6 | 20-4 | |
Hem-Fir | #3 | 9-8 | 12-4 | 15-0 | 17-5 | 8-8 | 11-0 | 13-5 | 15-7 | |
Southern Pine | SS | 12-3 | 16-2 | 20-8 | 25-1 | 12-3 | 16-2 | 20-8 | 25-1 | |
Southern Pine | #1 | 12-0 | 15-10 | 20-3 | 24-8 | 12-0 | 15-10 | 20-3 | 24-8 | |
Southern Pine | #2 | 11-10 | 15-7 | 19-10 | 24-2 | 11-10 | 15-7 | 18-7 | 21-9 | |
Southern Pine | #3 | 10-5 | 13-3 | 15-8 | 18-8 | 9-4 | 11-11 | 14-0 | 16-8 | |
Spruce-Pine-Fir | SS | 11-7 | 15-3 | 19-5 | 23-7 | 11-7 | 15-3 | 19-5 | 23-7 | |
Spruce-Pine-Fir | #1 | 11-3 | 14-11 | 19-0 | 23-0 | 11-3 | 14-7 | 17-9 | 20-7 | |
Spruce-Pine-Fir | #2 | 11-3 | 14-11 | 19-0 | 23-0 | 11-3 | 14-7 | 17-9 | 20-7 | |
Spruce-Pine-Fir | #3 | 9-8 | 12-4 | 15-0 | 17-5 | 8-8 | 11-0 | 13-5 | 15-7 | |
16 | Douglas Fir-Larch | SS | 11-4 | 15-0 | 19-1 | 23-3 | 11-4 | 15-0 | 19-1 | 23-0 |
Douglas Fir-Larch | #1 | 10-11 | 14-5 | 18-5 | 21-4 | 10-8 | 13-6 | 16-5 | 19-1 | |
Douglas Fir-Larch | #2 | 10-9 | 14-1 | 17-2 | 19-11 | 9-11 | 12-7 | 15-5 | 17-10 | |
Douglas Fir-Larch | #3 | 8-5 | 10-8 | 13-0 | 15-1 | 7-6 | 9-6 | 11-8 | 13-6 | |
Hem-Fir | SS | 10-9 | 14-2 | 18-0 | 21-11 | 10-9 | 14-2 | 18-0 | 21-11 | |
Hem-Fir | #1 | 10-6 | 13-10 | 17-8 | 20-9 | 10-4 | 13-1 | 16-0 | 18-7 | |
Hem-Fir | #2 | 10-0 | 13-2 | 16-10 | 19-8 | 9-10 | 12-5 | 15-2 | 17-7 | |
Hem-Fir | #3 | 8-5 | 10-8 | 13-0 | 15-1 | 7-6 | 9-6 | 11-8 | 13-6 | |
Southern Pine | SS | 11-2 | 14-8 | 18-9 | 22-10 | 11-2 | 14-8 | 18-9 | 22-10 | |
Southern Pine | #1 | 10-11 | 14-5 | 18-5 | 22-5 | 10-11 | 14-5 | 17-11 | 21-4 | |
Southern Pine | #2 | 10-9 | 14-2 | 18-0 | 21-1 | 10-5 | 13-6 | 16-1 | 18-10 | |
Southern Pine | #3 | 9-0 | 11-6 | 13-7 | 16-2 | 8-1 | 10-3 | 12-2 | 14-6 | |
Spruce-Pine-Fir | SS | 10-6 | 13-10 | 17-8 | 21-6 | 10-6 | 13-10 | 17-8 | 21-4 | |
Spruce-Pine-Fir | #1 | 10-3 | 13-6 | 17-2 | 19-11 | 9-11 | 12-7 | 15-5 | 17-10 | |
Spruce-Pine-Fir | #2 | 10-3 | 13-6 | 17-2 | 19-11 | 9-11 | 12-7 | 15-5 | 17-10 | |
Spruce-Pine-Fir | #3 | 8-5 | 10-8 | 13-0 | 15-1 | 7-6 | 9-6 | 11-8 | 13-6 | |
19.2 | Douglas Fir-Larch | SS | 10-8 | 14-1 | 18-0 | 21-10 | 10-8 | 14-1 | 18-0 | 21-0 |
Douglas Fir-Larch | #1 | 10-4 | 13-7 | 16-9 | 19-6 | 9-8 | 12-4 | 15-0 | 17-5 | |
Douglas Fir-Larch | #2 | 10-1 | 12-10 | 15-8 | 18-3 | 9-1 | 11-6 | 14-1 | 16-3 | |
Douglas Fir-Larch | #3 | 7-8 | 9-9 | 11-10 | 13-9 | 6-10 | 8-8 | 10-7 | 12-4 | |
Hem-Fir | SS | 10-1 | 13-4 | 17-0 | 20-8 | 10-1 | 13-4 | 17-0 | 20-7 | |
Hem-Fir | #1 | 9-10 | 13-0 | 16-4 | 19-0 | 9-6 | 12-0 | 14-8 | 17-0 | |
Hem-Fir | #2 | 9-5 | 12-5 | 15-6 | 17-1 | 8-11 | 11-4 | 13-10 | 16-1 | |
Hem-Fir | #3 | 7-8 | 9-9 | 11-10 | 13-9 | 6-10 | 8-8 | 10-7 | 12-4 | |
Southern Pine | SS | 10-6 | 13-10 | 17-8 | 21-6 | 10-6 | 13-10 | 17-8 | 21-6 | |
Southern Pine | #1 | 10-4 | 13-7 | 17-4 | 21-1 | 10-4 | 13-7 | 16-4 | 19-6 | |
Southern Pine | #2 | 10-1 | 13-4 | 16-5 | 19-3 | 9-6 | 12-4 | 14-8 | 17-2 | |
Southern Pine | #3 | 8-3 | 10-6 | 12-5 | 14-9 | 7-4 | 9-5 | 11-1 | 13-2 | |
Spruce-Pine-Fir | SS | 9-10 | 13-0 | 16-7 | 20-2 | 9-10 | 13-0 | 16-7 | 19-6 | |
Spruce-Pine-Fir | #1 | 9-8 | 12-9 | 15-8 | 18-3 | 9-1 | 11-6 | 14-1 | 16-3 | |
Spruce-Pine-Fir | #2 | 9-8 | 12-9 | 15-8 | 18-3 | 9-1 | 11-6 | 14-1 | 16-3 | |
Spruce-Pine-Fir | #3 | 7-8 | 9-9 | 11-10 | 13-9 | 6-10 | 8-8 | 10-7 | 12-4 | |
24 | Douglas Fir-Larch | SS | 9-11 | 13-1 | 16-8 | 20-3 | 9-11 | 13-1 | 16-2 | 18-9 |
Douglas Fir-Larch | #1 | 9-7 | 12-4 | 15-0 | 17-5 | 8-8 | 11-0 | 13-5 | 15-7 | |
Douglas Fir-Larch | #2 | 9-1 | 11-6 | 14-1 | 16-3 | 8-1 | 10-3 | 12-7 | 14-7 | |
Douglas Fir-Larch | #3 | 6-10 | 8-8 | 10-7 | 12-4 | 6-2 | 7-9 | 9-6 | 11-0 | |
Hem-Fir | SS | 9-4 | 12-4 | 15-9 | 19-2 | 9-4 | 12-4 | 15-9 | 18-5 | |
Hem-Fir | #1 | 9-2 | 12-0 | 14-8 | 17-0 | 8-6 | 10-9 | 13-1 | 15-2 | |
Hem-Fir | #2 | 8-9 | 11-4 | 13-10 | 16-1 | 8-0 | 10-2 | 12-5 | 14-4 | |
Hem-Fir | #3 | 6-10 | 8-8 | 10-7 | 12-4 | 6-2 | 7-9 | 9-6 | 11-0 | |
Southern Pine | SS | 9-9 | 12-10 | 16-5 | 19-11 | 9-9 | 12-10 | 16-5 | 19-11 | |
Southern Pine | #1 | 9-7 | 12-7 | 16-1 | 19-6 | 9-7 | 12-4 | 14-7 | 17-5 | |
Southern Pine | #2 | 9-4 | 12-4 | 14-8 | 17-2 | 8-6 | 11-0 | 13-1 | 15-5 | |
Southern Pine | #3 | 7-4 | 9-5 | 11-1 | 13-2 | 6-7 | 8-5 | 9-11 | 11-10 | |
Spruce-Pine-Fir | SS | 9-2 | 12-1 | 15-5 | 18-9 | 9-2 | 12-1 | 15-0 | 17-5 | |
Spruce-Pine-Fir | #1 | 8-11 | 11-6 | 14-1 | 16-3 | 8-1 | 10-3 | 12-7 | 14-7 | |
Spruce-Pine-Fir | #2 | 8-11 | 11-6 | 14-1 | 16-3 | 8-1 | 10-3 | 12-7 | 14-7 | |
Spruce-Pine-Fir | #3 | 6-10 | 8-8 | 10-7 | 12-4 | 6-2 | 7-9 | 9-6 | 11-0 |
JOIST SPACING (inches) |
SPECIES AND GRADE | DEAD LOAD = 10 psf | DEAD LOAD = 20 psf | ||||||||
2x6 | 2x8 | 2x10 | 2x12 | 2x6 | 2x8 | 2x10 | 2x12 | ||||
Maximum floor joist spans | |||||||||||
(ft. - in.) | (ft. - in.) | (ft. - in.) | (ft. - in.) | (ft. - in.) | (ft. - in.) | (ft. - in.) | (ft. - in.) | ||||
12 | Douglas Fir-Larch | SS | 11-4 | 15-0 | 19-1 | 23-3 | 11-4 | 15-0 | 19-1 | 23-3 | |
Douglas Fir-Larch | #1 | 10-11 | 14-5 | 18-5 | 22-0 | 10-11 | 14-2 | 17-4 | 20-1 | ||
Douglas Fir-Larch | #2 | 10-9 | 14-2 | 17-9 | 20-7 | 10-6 | 13-3 | 16-3 | 18-10 | ||
Douglas Fir-Larch | #3 | 8-8 | 11-0 | 13-5 | 15-7 | 7-11 | 10-0 | 12-3 | 14-3 | ||
Hem-Fir | SS | 10-9 | 14-2 | 18-0 | 21-11 | 10-9 | 14-2 | 18-0 | 21-11 | ||
Hem-Fir | #1 | 10-6 | 13-10 | 17-8 | 21-6 | 10-6 | 13-10 | 16-11 | 19-7 | ||
Hem-Fir | #2 | 10-0 | 13-2 | 16-10 | 20-4 | 10-0 | 13-1 | 16-0 | 18-6 | ||
Hem-Fir | #3 | 8-8 | 11-0 | 13-5 | 15-7 | 7-11 | 10-0 | 12-3 | 14-3 | ||
Southern Pine | SS | 11-2 | 14-8 | 18-9 | 22-10 | 11-2 | 14-8 | 18-9 | 22-10 | ||
Southern Pine | #1 | 10-11 | 14-5 | 18-5 | 22-5 | 10-11 | 14-5 | 18-5 | 22-5 | ||
Southern Pine | #2 | 10-9 | 14-2 | 18-0 | 21-9 | 10-9 | 14-2 | 16-11 | 19-10 | ||
Southern Pine | #3 | 9-4 | 11-11 | 14-0 | 16-8 | 8-6 | 10-10 | 12-10 | 15-3 | ||
Spruce-Pine-Fir | SS | 10-6 | 13-10 | 17-8 | 21-6 | 10-6 | 13-10 | 17-8 | 21-6 | ||
Spruce-Pine-Fir | #1 | 10-3 | 13-6 | 17-3 | 20-7 | 10-3 | 13-3 | 16-3 | 18-10 | ||
Spruce-Pine-Fir | #2 | 10-3 | 13-6 | 17-3 | 20-7 | 10-3 | 13-3 | 16-3 | 18-10 | ||
Spruce-Pine-Fir | #3 | 8-8 | 11-0 | 13-5 | 15-7 | 7-11 | 10-0 | 12-3 | 14-3 | ||
16 | Douglas Fir-Larch | SS | 10-4 | 13-7 | 17-4 | 21-1 | 10-4 | 13-7 | 17-4 | 21-0 | |
Douglas Fir-Larch | #1 | 9-11 | 13-1 | 16-5 | 19-1 | 9-8 | 12-4 | 15-0 | 17-5 | ||
Douglas Fir-Larch | #2 | 9-9 | 12-7 | 15-5 | 17-10 | 9-1 | 11-6 | 14-1 | 16-3 | ||
Douglas Fir-Larch | #3 | 7-6 | 9-6 | 11-8 | 13-6 | 6-10 | 8-8 | 10-7 | 12-4 | ||
Hem-Fir | SS | 9-9 | 12-10 | 16-5 | 19-11 | 9-9 | 12-10 | 16-5 | 19-11 | ||
Hem-Fir | #1 | 9-6 | 12-7 | 16-0 | 18-7 | 9-6 | 12-0 | 14-8 | 17-0 | ||
Hem-Fir | #2 | 9-1 | 12-0 | 15-2 | 17-7 | 8-11 | 11-4 | 13-10 | 16-1 | ||
Hem-Fir | #3 | 7-6 | 9-6 | 11-8 | 13-6 | 6-10 | 8-8 | 10-7 | 12-4 | ||
Southern Pine | SS | 10-2 | 13-4 | 17-0 | 20-9 | 10-2 | 13-4 | 17-0 | 20-9 | ||
Southern Pine | #1 | 9-11 | 13-1 | 16-9 | 20-4 | 9-11 | 13-1 | 16-4 | 19-6 | ||
Southern Pine | #2 | 9-9 | 12-10 | 16-1 | 18-10 | 9-6 | 12-4 | 14-8 | 17-2 | ||
Southern Pine | #3 | 8-1 | 10-3 | 12-2 | 14-6 | 7-4 | 9-5 | 11-1 | 13-2 | ||
Spruce-Pine-Fir | SS | 9-6 | 12-7 | 16-0 | 19-6 | 9-6 | 12-7 | 16-0 | 19-6 | ||
Spruce-Pine-Fir | #1 | 9-4 | 12-3 | 15-5 | 17-10 | 9-1 | 11-6 | 14-1 | 16-3 | ||
Spruce-Pine-Fir | #2 | 9-4 | 12-3 | 15-5 | 17-10 | 9-1 | 11-6 | 14-1 | 16-3 | ||
Spruce-Pine-Fir | #3 | 7-6 | 9-6 | 11-8 | 13-6 | 6-10 | 8-8 | 10-7 | 12-4 | ||
19.2 | Douglas Fir-Larch | SS | 9-8 | 12-10 | 16-4 | 19-10 | 9-8 | 12-10 | 16-4 | 19-2 | |
Douglas Fir-Larch | #1 | 9-4 | 12-4 | 15-0 | 17-5 | 8-10 | 11-3 | 13-8 | 15-11 | ||
Douglas Fir-Larch | #2 | 9-1 | 11-6 | 14-1 | 16-3 | 8-3 | 10-6 | 12-10 | 14-10 | ||
Douglas Fir-Larch | #3 | 6-10 | 8-8 | 10-7 | 12-4 | 6-3 | 7-11 | 9-8 | 11-3 | ||
Hem-Fir | SS | 9-2 | 12-1 | 15-5 | 18-9 | 9-2 | 12-1 | 15-5 | 18-9 | ||
Hem-Fir | #1 | 9-0 | 11-10 | 14-8 | 17-0 | 8-8 | 10-11 | 13-4 | 15-6 | ||
Hem-Fir | #2 | 8-7 | 11-3 | 13-10 | 16-1 | 8-2 | 10-4 | 12-8 | 14-8 | ||
Hem-Fir | #3 | 6-10 | 8-8 | 10-7 | 12-4 | 6-3 | 7-11 | 9-8 | 11-3 | ||
Southern Pine | SS | 9-6 | 12-7 | 16-0 | 19-6 | 9-6 | 12-7 | 16-0 | 19-6 | ||
Southern Pine | #1 | 9-4 | 12-4 | 15-9 | 19-2 | 9-4 | 12-4 | 14-11 | 17-9 | ||
Southern Pine | #2 | 9-2 | 12 -1 | 14-8 | 17-2 | 8-8 | 11-3 | 13-5 | 15-8 | ||
Southern Pine | #3 | 7-4 | 9-5 | 11-1 | 13-2 | 6-9 | 8-7 | 10-1 | 12-1 | ||
Spruce-Pine-Fir | SS | 9-0 | 11-10 | 15-1 | 18-4 | 9-0 | 11-10 | 15-1 | 17-9 | ||
Spruce-Pine-Fir | #1 | 8-9 | 11-6 | 14-1 | 16-3 | 8-3 | 10-6 | 12-10 | 14-10 | ||
Spruce-Pine-Fir | #2 | 8-9 | 11-6 | 14-1 | 16-3 | 8-3 | 10-6 | 12-10 | 14-10 | ||
Spruce-Pine-Fir | #3 | 6-10 | 8-8 | 10-7 | 12-4 | 6-3 | 7-11 | 9-8 | 11-3 | ||
24 | Douglas Fir-Larch | SS | 9-0 | 11-11 | 15-2 | 18-5 | 9-0 | 11-11 | 14-9 | 17-1 | |
Douglas Fir-Larch | #1 | 8-8 | 11-0 | 13-5 | 15-7 | 7-11 | 10-0 | 12-3 | 14-3 | ||
Douglas Fir-Larch | #2 | 8-1 | 10-3 | 12-7 | 14-7 | 7-5 | 9-5 | 11-6 | 13-4 | ||
Douglas Fir-Larch | #3 | 6-2 | 7-9 | 9-6 | 11-0 | 5-7 | 7-1 | 8-8 | 10-1 | ||
Hem-Fir | SS | 8-6 | 11-3 | 14-4 | 17-5 | 8-6 | 11-3 | 14-4 | 16-10a | ||
Hem-Fir | #1 | 8-4 | 10-9 | 13-1 | 15-2 | 7-9 | 9-9 | 11-11 | 13-10 | ||
Hem-Fir | #2 | 7-11 | 10-2 | 12-5 | 14-4 | 7-4 | 9-3 | 11-4 | 13-1 | ||
Hem-Fir | #3 | 6-2 | 7-9 | 9-6 | 11-0 | 5-7 | 7-1 | 8-8 | 10-1 | ||
Southern Pine | SS | 8-10 | 11-8 | 14-11 | 18-1 | 8-10 | 11-8 | 14-11 | 18-1 | ||
Southern Pine | #1 | 8-8 | 11-5 | 14-7 | 17-5 | 8-8 | 11-3 | 13-4 | 15-11 | ||
Southern Pine | #2 | 8-6 | 11-0 | 13-1 | 15-5 | 7-9 | 10-0 | 12-0 | 14-0 | ||
Southern Pine | #3 | 6-7 | 8-5 | 9-11 | 11-10 | 6-0 | 7-8 | 9-1 | 10-9 | ||
Spruce-Pine-Fir | SS | 8-4 | 11-0 | 14-0 | 17-0 | 8-4 | 11-0 | 13-8 | 15-11 | ||
Spruce-Pine-Fir | #1 | 8-1 | 10-3 | 12-7 | 14-7 | 7-5 | 9-5 | 11-6 | 13-4 | ||
Spruce-Pine-Fir | #2 | 8-1 | 10-3 | 12-7 | 14-7 | 7-5 | 9-5 | 11-6 | 13-4 | ||
Spruce-Pine-Fir | #3 | 6-2 | 7-9 | 9-6 | 11-0 | 5-7 | 7-1 | 8-8 | 10-1 |
- End bearing length shall be increased to 2 inches.
STUD SIZE (inches) | BEARING WALLS | NONBEARING WALLS | ||||
Laterally unsupported stud heighta (feet) | Supporting roof and ceiling only | Supporting one floor, roof and ceiling | Supporting two floors, roof and ceiling | Laterally unsupported stud heighta (feet) | Spacing (inches) | |
Spacing (inches) | ||||||
2 × 3b | — | — | — | — | 10 | 16 |
2 × 4 | 10 | 24 | 16 | — | 14 | 24 |
3 × 4 | 10 | 24 | 24 | 16 | 14 | 24 |
2 × 5 | 10 | 24 | 24 | — | 16 | 24 |
2 × 6 | 10 | 24 | 24 | 16 | 20 | 24 |
- Listed heights are distances between points of lateral support placed perpendicular to the plane of the wall. Increases in unsupported height are permitted where justified by an analysis.
- Shall not be used in exterior walls.
- Nominal 1-inch by 4-inch (25 mm by 102 mm) continuous diagonal braces let into top and bottom plates and intervening studs, placed at an angle not more than 60 degrees (1.0 rad) or less than 45 degrees (0.79 rad) from the horizontal and attached to the framing in conformance with Table 2304.9.1.
- Wood boards of 5/8 inch (15.9 mm) net minimum thickness applied diagonally on studs spaced not over 24 inches (610 mm) o.c.
- Wood structural panel sheathing with a thickness not less than 3/8 inch (9.5 mm) for 16-inch (406 mm) or 24-inch (610 mm) stud spacing in accordance with Tables 2308.9.3(2) and 2308.9.3(3).
- Fiberboard sheathing panels not less than 1/2 inch (12.7 mm) thick applied vertically or horizontally on studs spaced not over 16 inches (406 mm) o.c. where installed with fasteners in accordance with Section 2306.6 and Table 2306.6.
- Gypsum board [sheathing 1/2-inch-thick (12.7 mm) by 4-feet-wide (1219 mm) wallboard or veneer base] on studs spaced not over 24 inches (610 mm) o.c. and nailed at 7 inches (178 mm) o.c. with nails as required by Table 2306.7.
- Particleboard wall sheathing panels where installed in accordance with Table 2308.9.3(4).
- Portland cement plaster on studs spaced 16 inches (406 mm) o.c.installed in accordance with Section 2510.
- Hardboard panel siding where installed in accordance with Section 2303.1.6 and Table 2308.9.3(5).
For Method 5, each panel must be at least 96 inches (2438 mm) in length where applied to one face of a panel and 48 inches (1219 mm) where applied to both faces. All vertical joints of panel sheathing shall occur over studs and adjacent panel joints shall be nailed to common framing members. Horizontal joints shall occur over blocking or other framing equal in size to the studding except where waived by the installation requirements for the specific sheathing materials. Sole plates shall be nailed to the floor framing and top plates shall be connected to the framing above in accordance with Section 2308.3.2. Where joists are perpendicular to braced wall lines above, blocking shall be provided under and in line with the braced wall panels.
SEISMIC DESIGN CATEGORY | MAXIMUM WALL SPACING (feet) |
REQUIRED BRACING LENGTH, b |
A, B and C | 35'-0" | Table 2308.9.3(1) and Section 2308.9.3 |
D and E | 25'-0" | Table 2308.12.4 |
BASIC COMPONENTS OF THE LATERAL BRACING SYSTEM
SEISMIC DESIGN CATEGORY |
CONDITION | CONSTRUCTION METHODSb, c | BRACED PANEL LOCATION AND LENGTHd |
|||||||
1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | |||
A and B | One story, top of two or three story | X | X | X | X | X | X | X | X | Located in accordance with Section 2308.9.3 and not more than 25 feet on center. |
First story of two story or second story of three story | X | X | X | X | X | X | X | X | ||
First story of three story | — | X | X | X | Xe | X | X | X | ||
C | One story or top of two story | — | X | X | X | X | X | X | X | Located in accordance with Section 2308.9.3 and not more than 25 feet on center. |
First story of two story | — | X | X | X | Xe | X | X | X | Located in accordance with Section 2308.9.3 and not more than 25 feet on center, but total length shall not be less than 25% of building lengthf. |
- This table specifies minimum requirements for braced panels that form interior or exterior braced wall lines.
- See Section 2308.9.3 for full description.
- See Sections 2308.9.3.1 and 2308.9.3.2 for alternative braced panel requirements.
- Building length is the dimension parallel to the braced wall length.
- Gypsum wallboard applied to framing supports that are spaced at 16 inches on center.
- The required lengths shall be doubled for gypsum board applied to only one face of a braced wall panel.
MINIMUM THICKNESSa (inch) |
MINIMUM NUMBER OF PLIES | STUD SPACING (inches) Plywood siding applied directly to studs or over sheathing |
3/8 | 3 | 16b |
1/2 | 4 | 24 |
- Thickness of grooved panels is measured at bottom of grooves.
- Spans are permitted to be 24 inches if plywood siding applied with face grain perpendicular to studs or over one of the following: (1) 1-inch board sheathing, (2) 7/16 -inch wood structural panel sheathing or (3) 3/8-inch wood structural panel sheathing with strength axis (which is the long direction of the panel unless otherwise marked) of sheathing perpendicular to studs.
MINIMUM THICKNESS (inch) |
PANEL SPAN RATING |
STUD SPACING (inches) | ||
Siding nailed to studs | Nailable sheathing | |||
Sheathing parallel to studs | Sheathing perpendicular to studs |
|||
3/8,15/32, 1/2 | 16/0, 20/0, 24/0, 32/16 Wall—24" o.c. |
24 | 16 | 24 |
7/16,15/32, 1/2 | 24/0, 24/16, 32/16 Wall—24" o.c. |
24 | 24a | 24 |
GRADE | THICKNESS (inch) |
STUD SPACING (inches) | |
Siding nailed to studs |
Sheathing under coverings specified in Section 2308.9.3 parallel or perpendicular to studs |
||
M-S "Exterior Glue" and M-2 "Exterior Glue" |
3/8 | 16 | — |
1/2 | 16 | 16 |
SIDING | MINIMUM NOMINAL THICKNESS (inch) |
2 × 4 FRAMING MAXIMUM SPACING | NAIL SIZEa, b, d | NAIL SPACING | |
General | Bracing panelsc | ||||
1. Lap siding | |||||
Direct to studs | 3/8 | 16" o.c. | 8d | 16" o.c. | Not applicable |
Over sheathing | 3/8 | 16" o.c. | 10d | 16" o.c. | Not applicable |
2. Square edge panel siding | |||||
Direct to studs | 3/8 | 24" o.c. | 6d | 6" o.c. edges; 12" o.c. at intermediate supports |
4" o.c. edges; 8" o.c. at intermediate supports |
Over sheathing | 3/8 | 24" o.c. | 8d | 6" o.c. edges; 12" o.c. at intermediate supports |
4" o.c. edges; 8" o.c. at intermediate supports |
3. Shiplap edge panel siding | |||||
Direct to studs | 3/8 | 16" o.c. | 6d | 6" o.c. edges; 12" o.c. at intermediate supports |
4" o.c. edges; 8" o.c. at intermediate supports |
Over sheathing | 3/8 | 16" o.c. | 8d | 6" o.c. edges; 12" o.c. at intermediate supports |
4" o.c. edges; 8" o.c. at intermediate supports |
- Nails shall be corrosion resistant.
- Minimum acceptable nail dimensions:
Panel Siding (inch) Lap Siding (inch) Shank diameter 0.092 0.099 Head diameter 0.225 0.240 - Where used to comply with Section 2308.9.3.
- Nail length must accommodate the sheathing and penetrate framing 11/2 inches.
- In one-story buildings, each panel shall have a length of not less than 2 feet 8 inches (813 mm) and a height of not more than 10 feet (3048 mm). Each panel shall be sheathed on one face with 3/8-inch-minimum-thickness (9.5 mm) wood structural panel sheathing nailed with 8d common or galvanized box nails in accordance with Table 2304.9.1 and blocked at wood structural panel edges. Two anchor bolts installed in accordance with Section 2308.6 shall be provided in each panel. Anchor bolts shall be placed at each panel outside quarter points. Each panel end stud shall have a tie-down device fastened to the foundation, capable of providing an approved uplift capacity of not less than 1,800 pounds (8006 N). The tie-down device shall be installed in accordance with the manufacturer's recommendations. The panels shall be supported directly on a foundation or on floor framing supported directly on a foundation that is continuous across the entire length of the braced wall line. This foundation shall be reinforced with not less than one No. 4 bar top and bottom.
Where the continuous foundation is required to have a depth greater than 12 inches (305 mm), a minimum 12-inch by 12-inch (305 mm by 305 mm) continuous footing or turned down slab edge is permitted at door openings in the braced wall line. This continuous footing or turned down slab edge shall be reinforced with not less than one No. 4 bar top and bottom. This reinforcement shall be lapped 15 inches (381 mm) with the reinforcement required in the continuous foundation located directly under the braced wall line. - In the first story of two-story buildings, each wall panel shall be braced in accordance with Section 2308.9.3.1, Item 1, except that the wood structural panel sheathing shall be provided on both faces, three anchor bolts shall be placed at one-quarter points, and tie-down device uplift capacity shall not be less than 3,000 pounds (13 344 N).
- In one-story buildings, each panel shall have a length of not less than 16 inches (406 mm) and a height of not more than 10 feet (3048 mm). Each panel shall be sheathed on one face with a single layer of 3/8 inch (9.5 mm) minimum thickness wood structural panel sheathing nailed with 8d common or galvanized box nails in accordance with Figure 2308.9.3.2. The wood structural panel sheathing shall extend up over the solid sawn or glued-laminated header and shall be nailed in accordance with Figure 2308.9.3.2. A built-up header consisting of at least two 2 × 12s and fastened in accordance with Item 24 of Table 2304.9.1 shall be permitted to be used. A spacer, if used, shall be placed on the side of the built-up beam opposite the wood structural panel sheathing. The header shall extend between the inside faces of the first full-length outer studs of each panel. The clear span of the header between the inner studs of each panel shall be not less than 6 feet (1829 mm) and not more than 18 feet (5486 mm) in length. A strap with an uplift capacity of not less than 1,000 pounds (4,400 N) shall fasten the header to the inner studs opposite the sheathing. One anchor bolt not less than 5/8 inch (15.9 mm) diameter and installed in accordance with Section 2308.6 shall be provided in the center of each sill plate. The studs at each end of the panel shall have a tie-down device fastened to the foundation with an uplift capacity of not less than 4,200 pounds (18 480 N).
Where a panel is located on one side of the opening, the header shall extend between the inside face of the first full-length stud of the panel and the bearing studs at the other end of the opening. A strap with an uplift capacity of not less than 1,000 pounds (4400 N) shall fasten the header to the bearing studs. The bearing studs shall also have a tie-down device fastened to the foundation with an uplift capacity of not less than 1,000 pounds (4400 N).
The tie-down devices shall be an embedded strap type, installed in accordance with the manufacturer's recommendations. The panels shall be supported directly on a foundation that is continuous across the entire length of the braced wall line. This foundation shall be reinforced with not less than one No. 4 bar top and bottom.
Where the continuous foundation is required to have a depth greater than 12 inches (305 mm), a minimum 12-inch by 12-inch (305 mm by 305 mm) continuous footing or turned down slab edge is permitted at door openings in the braced wall line. This continuous footing or turned down slab edge shall be reinforced with not less than one No. 4 bar top and bottom. This reinforcement shall be lapped not less than 15 inches (381 mm) with the reinforcement required in the continuous foundation located directly under the braced wall line. - In the first story of two-story buildings, each wall panel shall be braced in accordance with Item 1 above, except that each panel shall have a length of not less than 24 inches (610 mm).
ALTERNATE BRACED WALL PANEL ADJACENT TO A DOOR OR WINDOW OPENING
HEADERS SUPPORTING |
SIZE | GROUND SNOW LOAD (psf)e | |||||||||||
30 | 50 | ||||||||||||
Building widthc (feet) | |||||||||||||
20 | 28 | 36 | 20 | 28 | 36 | ||||||||
Span | NJd | Span | NJd | Span | NJd | Span | NJd | Span | NJd | Span | NJd | ||
Roof & Ceiling | 2-2×4 | 3-6 | 1 | 3-2 | 1 | 2-10 | 1 | 3-2 | 1 | 2-9 | 1 | 2-6 | 1 |
2-2×6 | 5-5 | 1 | 4-8 | 1 | 4-2 | 1 | 4-8 | 1 | 4-1 | 1 | 3-8 | 2 | |
2-2×8 | 6-10 | 1 | 5-11 | 2 | 5-4 | 2 | 5-11 | 2 | 5-2 | 2 | 4-7 | 2 | |
2-2×10 | 8-5 | 2 | 7-3 | 2 | 6-6 | 2 | 7-3 | 2 | 6-3 | 2 | 5-7 | 2 | |
2-2×12 | 9-9 | 2 | 8-5 | 2 | 7-6 | 2 | 8-5 | 2 | 7-3 | 2 | 6-6 | 2 | |
3-2×8 | 8-4 | 1 | 7-5 | 1 | 6-8 | 1 | 7-5 | 1 | 6-5 | 2 | 5-9 | 2 | |
3-2×10 | 10-6 | 1 | 9-1 | 2 | 8-2 | 2 | 9-1 | 2 | 7-10 | 2 | 7-0 | 2 | |
3-2×12 | 12-2 | 2 | 10-7 | 2 | 9-5 | 2 | 10-7 | 2 | 9-2 | 2 | 8-2 | 2 | |
4-2×8 | 9-2 | 1 | 8-4 | 1 | 7-8 | 1 | 8-4 | 1 | 7-5 | 1 | 6-8 | 1 | |
4-2×10 | 11-8 | 1 | 10-6 | 1 | 9-5 | 2 | 10-6 | 1 | 9-1 | 2 | 8-2 | 2 | |
4-2×12 | 14-1 | 1 | 12-2 | 2 | 10-11 | 2 | 12-2 | 2 | 10-7 | 2 | 9-5 | 2 | |
Roof, Ceiling & 1 Center- Bearing Floor |
2-2×4 | 3-1 | 1 | 2-9 | 1 | 2-5 | 1 | 2-9 | 1 | 2-5 | 1 | 2-2 | 1 |
2-2×6 | 4-6 | 1 | 4-0 | 1 | 3-7 | 2 | 4-1 | 1 | 3-7 | 2 | 3-3 | 2 | |
2-2×8 | 5-9 | 2 | 5-0 | 2 | 4-6 | 2 | 5-2 | 2 | 4-6 | 2 | 4-1 | 2 | |
2-2×10 | 7-0 | 2 | 6-2 | 2 | 5-6 | 2 | 6-4 | 2 | 5-6 | 2 | 5-0 | 2 | |
2-2×12 | 8-1 | 2 | 7-1 | 2 | 6-5 | 2 | 7-4 | 2 | 6-5 | 2 | 5-9 | 3 | |
3-2×8 | 7-2 | 1 | 6-3 | 2 | 5-8 | 2 | 6-5 | 2 | 5-8 | 2 | 5-1 | 2 | |
3-2×10 | 8-9 | 2 | 7-8 | 2 | 6-11 | 2 | 7-11 | 2 | 6-11 | 2 | 6-3 | 2 | |
3-2×12 | 10-2 | 2 | 8-11 | 2 | 8-0 | 2 | 9-2 | 2 | 8-0 | 2 | 7-3 | 2 | |
4-2×8 | 8-1 | 1 | 7-3 | 1 | 6-7 | 1 | 7-5 | 1 | 6-6 | 1 | 5-11 | 2 | |
4-2×10 | 10-1 | 1 | 8-10 | 2 | 8-0 | 2 | 9-1 | 2 | 8-0 | 2 | 7-2 | 2 | |
4-2×12 | 11-9 | 2 | 10-3 | 2 | 9-3 | 2 | 10-7 | 2 | 9-3 | 2 | 8-4 | 2 | |
Roof, Ceiling & 1 Clear Span Floor | 2-2×4 | 2-8 | 1 | 2-4 | 1 | 2-1 | 1 | 2-7 | 1 | 2-3 | 1 | 2-0 | 1 |
2-2×6 | 3-11 | 1 | 3-5 | 2 | 3-0 | 2 | 3-10 | 2 | 3-4 | 2 | 3-0 | 2 | |
2-2×8 | 5-0 | 2 | 4-4 | 2 | 3-10 | 2 | 4-10 | 2 | 4-2 | 2 | 3-9 | 2 | |
2-2×10 | 6-1 | 2 | 5-3 | 2 | 4-8 | 2 | 5-11 | 2 | 5-1 | 2 | 4-7 | 3 | |
2-2×12 | 7-1 | 2 | 6-1 | 3 | 5-5 | 3 | 6-10 | 2 | 5-11 | 3 | 5-4 | 3 | |
3-2×8 | 6-3 | 2 | 5-5 | 2 | 4-10 | 2 | 6-1 | 2 | 5-3 | 2 | 4-8 | 2 | |
3-2×10 | 7-7 | 2 | 6-7 | 2 | 5-11 | 2 | 7-5 | 2 | 6-5 | 2 | 5-9 | 2 | |
3-2×12 | 8-10 | 2 | 7-8 | 2 | 6-10 | 2 | 8-7 | 2 | 7-5 | 2 | 6-8 | 2 | |
4-2×8 | 7-2 | 1 | 6-3 | 2 | 5-7 | 2 | 7-0 | 1 | 6-1 | 2 | 5-5 | 2 | |
4-2×10 | 8-9 | 2 | 7-7 | 2 | 6-10 | 2 | 8-7 | 2 | 7-5 | 2 | 6-7 | 2 | |
4-2×12 | 10-2 | 2 | 8-10 | 2 | 7-11 | 2 | 9-11 | 2 | 8-7 | 2 | 7-8 | 2 | |
Roof, Ceiling & 2 Center- Bearing Floors |
2-2×4 | 2-7 | 1 | 2-3 | 1 | 2-0 | 1 | 2-6 | 1 | 2-2 | 1 | 1-11 | 1 |
2-2×6 | 3-9 | 2 | 3-3 | 2 | 2-11 | 2 | 3-8 | 2 | 3-2 | 2 | 2-10 | 2 | |
2-2×8 | 4-9 | 2 | 4-2 | 2 | 3-9 | 2 | 4-7 | 2 | 4-0 | 2 | 3-8 | 2 | |
2-2×10 | 5-9 | 2 | 5-1 | 2 | 4-7 | 3 | 5-8 | 2 | 4-11 | 2 | 4-5 | 3 | |
2-2×12 | 6-8 | 2 | 5-10 | 3 | 5-3 | 3 | 6-6 | 2 | 5-9 | 3 | 5-2 | 3 | |
3-2×8 | 5-11 | 2 | 5-2 | 2 | 4-8 | 2 | 5-9 | 2 | 5-1 | 2 | 4-7 | 2 | |
3-2×10 | 7-3 | 2 | 6-4 | 2 | 5-8 | 2 | 7-1 | 2 | 6-2 | 2 | 5-7 | 2 | |
3-2×12 | 8-5 | 2 | 7-4 | 2 | 6-7 | 2 | 8-2 | 2 | 7-2 | 2 | 6-5 | 3 | |
4-2×8 | 6-10 | 1 | 6-0 | 2 | 5-5 | 2 | 6-8 | 1 | 5-10 | 2 | 5-3 | 2 | |
4-2×10 | 8-4 | 2 | 7-4 | 2 | 6-7 | 2 | 8-2 | 2 | 7-2 | 2 | 6-5 | 2 | |
4-2×12 | 9-8 | 2 | 8-6 | 2 | 7-8 | 2 | 9-5 | 2 | 8-3 | 2 | 7-5 | 2 | |
Roof, Ceiling & 2 Clear Span Floors |
2-2×4 | 2-1 | 1 | 1-8 | 1 | 1-6 | 2 | 2-0 | 1 | 1-8 | 1 | 1-5 | 2 |
2-2×6 | 3-1 | 2 | 2-8 | 2 | 2-4 | 2 | 3-0 | 2 | 2-7 | 2 | 2-3 | 2 | |
2-2×8 | 3-10 | 2 | 3-4 | 2 | 3-0 | 3 | 3-10 | 2 | 3-4 | 2 | 2-11 | 3 | |
2-2×10 | 4-9 | 2 | 4-1 | 3 | 3-8 | 3 | 4-8 | 2 | 4-0 | 3 | 3-7 | 3 | |
2-2×12 | 5-6 | 3 | 4-9 | 3 | 4-3 | 3 | 5-5 | 3 | 4-8 | 3 | 4-2 | 3 | |
3-2×8 | 4-10 | 2 | 4-2 | 2 | 3-9 | 2 | 4-9 | 2 | 4-1 | 2 | 3-8 | 2 | |
3-2×10 | 5-11 | 2 | 5-1 | 2 | 4-7 | 3 | 5-10 | 2 | 5-0 | 2 | 4-6 | 3 | |
3-2×12 | 6-10 | 2 | 5-11 | 3 | 5-4 | 3 | 6-9 | 2 | 5-10 | 3 | 5-3 | 3 | |
4-2×8 | 5-7 | 2 | 4-10 | 2 | 4-4 | 2 | 5-6 | 2 | 4-9 | 2 | 4-3 | 2 | |
4-2×10 | 6-10 | 2 | 5-11 | 2 | 5-3 | 2 | 6-9 | 2 | 5-10 | 2 | 5-2 | 2 | |
4-2×12 | 7-11 | 2 | 6-10 | 2 | 6-2 | 3 | 7-9 | 2 | 6-9 | 2 | 6-0 | 3 |
- Spans are given in feet and inches (ft-in).
- Tabulated values are for No. 2 grade lumber.
- Building width is measured perpendicular to the ridge. For widths between those shown, spans are permitted to be interpolated.
- NJ - Number of jack studs required to support each end. Where the number of required jack studs equals one, the header is permitted to be supported by an approved framing anchor attached to the full-height wall stud and to the header.
- Use 30 pounds per square foot ground snow load for cases in which ground snow load is less than 30 pounds per square foot and the roof live load is equal to or less than 20 pounds per square foot.
HEADERS AND GIRDERS SUPPORTING | SIZE | BUILDING widthc (feet) | |||||
20 | 28 | 36 | |||||
Span | NJd | Span | NJd | Span | NJd | ||
One Floor Only | 2-2×4 | 3-1 | 1 | 2-8 | 1 | 2-5 | 1 |
2-2×6 | 4-6 | 1 | 3-11 | 1 | 3-6 | 1 | |
2-2×8 | 5-9 | 1 | 5-0 | 2 | 4-5 | 2 | |
2-2×10 | 7-0 | 2 | 6-1 | 2 | 5-5 | 2 | |
2-2×12 | 8-1 | 2 | 7-0 | 2 | 6-3 | 2 | |
3-2×8 | 7-2 | 1 | 6-3 | 1 | 5-7 | 2 | |
3-2×10 | 8-9 | 1 | 7-7 | 2 | 6-9 | 2 | |
3-2×12 | 10-2 | 2 | 8-10 | 2 | 7-10 | 2 | |
4-2×8 | 9-0 | 1 | 7-8 | 1 | 6-9 | 1 | |
4-2×10 | 10-1 | 1 | 8-9 | 1 | 7-10 | 2 | |
4-2×12 | 11-9 | 1 | 10-2 | 2 | 9-1 | 2 | |
Two Floors | 2-2×4 | 2-2 | 1 | 1-10 | 1 | 1-7 | 1 |
2-2×6 | 3-2 | 2 | 2-9 | 2 | 2-5 | 2 | |
2-2×8 | 4-1 | 2 | 3-6 | 2 | 3-2 | 2 | |
2-2×10 | 4-11 | 2 | 4-3 | 2 | 3-10 | 3 | |
2-2×12 | 5-9 | 2 | 5-0 | 3 | 4-5 | 3 | |
3-2×8 | 5-1 | 2 | 4-5 | 2 | 3-11 | 2 | |
3-2×10 | 6-2 | 2 | 5-4 | 2 | 4-10 | 2 | |
3-2×12 | 7-2 | 2 | 6-3 | 2 | 5-7 | 3 | |
4-2×8 | 6-1 | 1 | 5-3 | 2 | 4-8 | 2 | |
4-2×10 | 7-2 | 2 | 6-2 | 2 | 5-6 | 2 | |
4-2×12 | 8-4 | 2 | 7-2 | 2 | 6-5 | 2 |
- Spans are given in feet and inches (ft-in).
- Tabulated values are for No. 2 grade lumber.
- Building width is measured perpendicular to the ridge. For widths between those shown, spans are permitted to be interpolated.
- NJ - Number of jack studs required to support each end. Where the number of required jack studs equals one, the headers are permitted to be supported by an approved framing anchor attached to the full-height wall stud and to the header.
NOMINAL DESIGN WIND SPEED,Vasdi | ROOF SPAN (feet) | OVERHANGS (pounds/feet)d | ||||||
12 | 20 | 24 | 28 | 32 | 36 | 40 | ||
85 | -72 | -120 | -145 | -169 | -193 | -217 | -241 | -38.55 |
90 | -91 | -151 | -181 | -212 | -242 | -272 | -302 | -43.22 |
100 | -131 | -281 | -262 | -305 | -349 | -393 | -436 | -53.36 |
110 | -175 | -292 | -351 | -409 | -467 | -526 | -584 | -64.56 |
- The uplift connection requirements are based on a 30-foot mean roof height located in Exposure B. For Exposure C or D and for other mean roof heights, multiply the above loads by the adjustment coefficients below.
Mean Roof Height (feet) EXPOSURE 15 20 25 30 35 40 45 50 55 60 B 1.00 1.00 1.00 1.00 1.05 1.09 1.12 1.16 1.19 1.22 C 1.21 1.29 1.35 1.40 1.45 1.49 1.53 1.56 1.59 1.62 D 1.47 1.55 1.61 1.66 1.70 1.74 1.78 1.81 1.84 1.87 - The uplift connection requirements are based on the framing being spaced 24 inches on center. Multiply by 0.67 for framing spaced 16 inches on center and multiply by 0.5 for framing spaced 12 inches on center.
- The uplift connection requirements include an allowance for 10 pounds of dead load.
- The uplift connection requirements do not account for the effects of overhangs. The magnitude of the above loads shall be increased by adding the overhang loads found in the table. The overhang loads are also based on framing spaced 24 inches on center. The overhang loads given shall be multiplied by the overhang projection and added to the roof uplift value in the table.
- The uplift connection requirements are based upon wind loading on end zones as defined in Figure 28.6.3 of ASCE 7. Connection loads for connections located a distance of 20 percent of the least horizontal dimension of the building from the corner of the building are permitted to be reduced by multiplying the table connection value by 0.7 and multiplying the overhang load by 0.8.
- For wall-to-wall and wall-to-foundation connections, the capacity of the uplift connector is permitted to be reduced by 100 pounds for each full wall above. (For example, if a 500-pound rated connector is used on the roof framing, a 400-pound rated connector is permitted at the next floor level down).
- Interpolation is permitted for intermediate values of Vasd and roof spans.
- The rated capacity of approved tie-down devices is permitted to include up to a 60-percent increase for wind effects where allowed by material specifications.
- Vasd shall be determined in accordance with Section 1609.3.1.
CEILING JOIST SPACING (inches) |
SPECIES AND GRADE | DEAD LOAD = 5 pounds per square foot | |||||
2 × 4 | 2 × 6 | 2 × 8 | 2 × 10 | ||||
Maximum ceiling joist spans | |||||||
(ft. - in.) | (ft. - in.) | (ft. - in.) | (ft. - in.) | ||||
12 | Douglas Fir-Larch | SS | 13-2 | 20-8 | 26-0 | 26-0 | |
Douglas Fir-Larch | #1 | 12-8 | 19-11 | 26-0 | 26-0 | ||
Douglas Fir-Larch | #2 | 12-5 | 19-6 | 25-8 | 26-0 | ||
Douglas Fir-Larch | #3 | 10-10 | 15-10 | 20-1 | 24-6 | ||
Hem-Fir | SS | 12-5 | 19-6 | 25-8 | 26-0 | ||
Hem-Fir | #1 | 12-2 | 19-1 | 25-2 | 26-0 | ||
Hem-Fir | #2 | 11-7 | 18-2 | 24-0 | 26-0 | ||
Hem-Fir | #3 | 10-10 | 15-10 | 20-1 | 24-6 | ||
Southern Pine | SS | 12-11 | 20-3 | 26-0 | 26-0 | ||
Southern Pine | #1 | 12-8 | 19-11 | 26-0 | 26-0 | ||
Southern Pine | #2 | 12-5 | 19-6 | 25-8 | 26-0 | ||
Southern Pine | #3 | 11-6 | 17-0 | 21-8 | 25-7 | ||
Spruce-Pine-Fir | SS | 12-2 | 19-1 | 25-2 | 26-0 | ||
Spruce-Pine-Fir | #1 | 11-10 | 18-8 | 24-7 | 26-0 | ||
Spruce-Pine-Fir | #2 | 11-10 | 18-8 | 24-7 | 26-0 | ||
Spruce-Pine-Fir | #3 | 10-10 | 15-10 | 20-1 | 24-6 | ||
16 | Douglas Fir-Larch | SS | 11-11 | 18-9 | 24-8 | 26-0 | |
Douglas Fir-Larch | #1 | 11-6 | 18-1 | 23-10 | 26-0 | ||
Douglas Fir-Larch | #2 | 11-3 | 17-8 | 23-0 | 26-0 | ||
Douglas Fir-Larch | #3 | 9-5 | 13-9 | 17-5 | 21-3 | ||
Hem-Fir | SS | 11-3 | 17-8 | 23-4 | 26-0 | ||
Hem-Fir | #1 | 11-0 | 17-4 | 22-10 | 26-0 | ||
Hem-Fir | #2 | 10-6 | 16-6 | 21-9 | 26-0 | ||
Hem-Fir | #3 | 9-5 | 13-9 | 17-5 | 21-3 | ||
Southern Pine | SS | 11-9 | 18-5 | 24-3 | 26-0 | ||
Southern Pine | #1 | 11-6 | 18-1 | 23-1 | 26-0 | ||
Southern Pine | #2 | 11-3 | 17-8 | 23-4 | 26-0 | ||
Southern Pine | #3 | 10-0 | 14-9 | 18-9 | 22-2 | ||
Spruce-Pine-Fir | SS | 11-0 | 17-4 | 22-10 | 26-0 | ||
Spruce-Pine-Fir | #1 | 10-9 | 16-11 | 22-4 | 26-0 | ||
Spruce-Pine-Fir | #2 | 10-9 | 16-11 | 22-4 | 26-0 | ||
Spruce-Pine-Fir | #3 | 9-5 | 13-9 | 17-5 | 21-3 | ||
19.2 | Douglas Fir-Larch | SS | 11-3 | 17-8 | 23-3 | 26-0 | |
Douglas Fir-Larch | #1 | 10-10 | 17-0 | 22-5 | 26-0 | ||
Douglas Fir-Larch | #2 | 10-7 | 16-7 | 21-0 | 25-8 | ||
Douglas Fir-Larch | #3 | 8-7 | 12-6 | 15-10 | 19-5 | ||
Hem-Fir | SS | 10-7 | 16-8 | 21-11 | 26-0 | ||
Hem-Fir | #1 | 10-4 | 16-4 | 21-6 | 26-0 | ||
Hem-Fir | #2 | 9-11 | 15-7 | 20-6 | 25-3 | ||
Hem-Fir | #3 | 8-7 | 12-6 | 15-10 | 19-5 | ||
Southern Pine | SS | 11-0 | 17-4 | 22-10 | 26-0 | ||
Southern Pine | #1 | 10-10 | 17-0 | 22-5 | 26-0 | ||
Southern Pine | #2 | 10-7 | 16-8 | 21-11 | 26-0 | ||
Southern Pine | #3 | 9-1 | 13-6 | 17-2 | 20-3 | ||
Spruce-Pine-Fir | SS | 10-4 | 16-4 | 21-6 | 26-0 | ||
Spruce-Pine-Fir | #1 | 10-2 | 15-11 | 21-0 | 25-8 | ||
Spruce-Pine-Fir | #2 | 10-2 | 15-11 | 21-0 | 25-8 | ||
Spruce-Pine-Fir | #3 | 8-7 | 12-6 | 15-10 | 19-5 | ||
24 | Douglas Fir-Larch | SS | 10-5 | 16-4 | 21-7 | 26-0 | |
Douglas Fir-Larch | #1 | 10-0 | 15-9 | 20-1 | 24-6 | ||
Douglas Fir-Larch | #2 | 9-10 | 14-10 | 18-9 | 22-11 | ||
Douglas Fir-Larch | #3 | 7-8 | 11-2 | 14-2 | 17-4 | ||
Hem-Fir | SS | 9-10 | 15-6 | 20-5 | 26-0 | ||
Hem-Fir | #1 | 9-8 | 15-2 | 19-7 | 23-11 | ||
Hem-Fir | #2 | 9-2 | 14-5 | 18-6 | 22-7 | ||
Hem-Fir | #3 | 7-8 | 11-2 | 14-2 | 17-4 | ||
Southern Pine | SS | 10-3 | 16-1 | 21-2 | 26-0 | ||
Southern Pine | #1 | 10-0 | 15-9 | 20-10 | 26-0 | ||
Southern Pine | #2 | 9-10 | 15-6 | 20-1 | 23-11 | ||
Southern Pine | #3 | 8-2 | 12-0 | 15-4 | 18-1 | ||
Spruce-Pine-Fir | SS | 9-8 | 15-2 | 19-11 | 25-5 | ||
Spruce-Pine-Fir | #1 | 9-5 | 14-9 | 18-9 | 22-11 | ||
Spruce-Pine-Fir | #2 | 9-5 | 14-9 | 18-9 | 22-11 | ||
Spruce-Pine-Fir | #3 | 7-8 | 11-2 | 14-2 | 17-4 |
CEILING JOIST SPACING (inches) |
SPECIES AND GRADE | DEAD LOAD = 10 pounds per square foot | ||||
2 × 4 | 2 × 6 | 2 × 8 | 2 × 10 | |||
Maximum ceiling joist spans | ||||||
(ft. - in.) | (ft. - in.) | (ft. - in.) | (ft. - in.) | |||
12 | Douglas Fir-Larch | SS | 10-5 | 16-4 | 21-7 | 26-0 |
Douglas Fir-Larch | #1 | 10-0 | 15-9 | 20-1 | 24-6 | |
Douglas Fir-Larch | #2 | 9-10 | 14-10 | 18-9 | 22-11 | |
Douglas Fir-Larch | #3 | 7-8 | 11-2 | 14-2 | 17-4 | |
Hem-Fir | SS | 9-10 | 15-6 | 20-5 | 26-0 | |
Hem-Fir | #1 | 9-8 | 15-2 | 19-7 | 23-11 | |
Hem-Fir | #2 | 9-2 | 14-5 | 18-6 | 22-7 | |
Hem-Fir | #3 | 7-8 | 11-2 | 14-2 | 17-4 | |
Southern Pine | SS | 10-3 | 16-1 | 21-2 | 26-0 | |
Southern Pine | #1 | 10-0 | 15-9 | 20-10 | 26-0 | |
Southern Pine | #2 | 9-10 | 15-6 | 20-1 | 23-11 | |
Southern Pine | #3 | 8-2 | 12-0 | 15-4 | 18-1 | |
Spruce-Pine-Fir | SS | 9-8 | 15-2 | 19-11 | 25-5 | |
Spruce-Pine-Fir | #1 | 9-5 | 14-9 | 18-9 | 22-11 | |
Spruce-Pine-Fir | #2 | 9-5 | 14-9 | 18-9 | 22-11 | |
Spruce-Pine-Fir | #3 | 7-8 | 11-2 | 14-2 | 17-4 | |
16 | Douglas Fir-Larch | SS | 9-6 | 14-11 | 19-7 | 25-0 |
Douglas Fir-Larch | #1 | 9-1 | 13-9 | 17-5 | 21-3 | |
Douglas Fir-Larch | #2 | 8-9 | 12-10 | 16-3 | 19-10 | |
Douglas Fir-Larch | #3 | 6-8 | 9-8 | 12-4 | 15-0 | |
Hem-Fir | SS | 8-11 | 14-1 | 18-6 | 23-8 | |
Hem-Fir | #1 | 8-9 | 13-5 | 16-10 | 20-8 | |
Hem-Fir | #2 | 8-4 | 12-8 | 16-0 | 19-7 | |
Hem-Fir | #3 | 6-8 | 9-8 | 12-4 | 15-0 | |
Southern Pine | SS | 9-4 | 14-7 | 19-3 | 24-7 | |
Southern Pine | #1 | 9-1 | 14-4 | 18-11 | 23-1 | |
Southern Pine | #2 | 8-11 | 13-6 | 17-5 | 20-9 | |
Southern Pine | #3 | 7-1 | 10-5 | 13-3 | 15-8 | |
Spruce-Pine-Fir | SS | 8-9 | 13-9 | 18-1 | 23-1 | |
Spruce-Pine-Fir | #1 | 8-7 | 12-10 | 16-3 | 19-10 | |
Spruce-Pine-Fir | #2 | 8-7 | 12-10 | 16-3 | 19-10 | |
Spruce-Pine-Fir | #3 | 6-8 | 9-8 | 12-4 | 15-0 | |
19.2 | Douglas Fir-Larch | SS | 8-11 | 14-0 | 18-5 | 23-4 |
Douglas Fir-Larch | #1 | 8-7 | 12-6 | 15-10 | 19-5 | |
Douglas Fir-Larch | #2 | 8-0 | 11-9 | 14-10 | 18-2 | |
Douglas Fir-Larch | #3 | 6-1 | 8-10 | 11-3 | 13-8 | |
Hem-Fir | SS | 8-5 | 13-3 | 17-5 | 22-3 | |
Hem-Fir | #1 | 8-3 | 12-3 | 15-6 | 18-11 | |
Hem-Fir | #2 | 7-10 | 11-7 | 14-8 | 17-10 | |
Hem-Fir | #3 | 6-1 | 8-10 | 11-3 | 13-8 | |
Southern Pine | SS | 8-9 | 13-9 | 18-1 | 23-1 | |
Southern Pine | #1 | 8-7 | 13-6 | 17-9 | 21-1 | |
Southern Pine | #2 | 8-5 | 12-3 | 15-10 | 18-11 | |
Southern Pine | #3 | 6-5 | 9-6 | 12-1 | 14-4 | |
Spruce-Pine-Fir | SS | 8-3 | 12-11 | 17-1 | 21-8 | |
Spruce-Pine-Fir | #1 | 8-0 | 11-9 | 14-10 | 18-2 | |
Spruce-Pine-Fir | #2 | 8-0 | 11-9 | 14-10 | 18-2 | |
Spruce-Pine-Fir | #3 | 6-1 | 8-10 | 11-3 | 13-8 | |
24 | Douglas Fir-Larch | SS | 8-3 | 13-0 | 17-1 | 20-11 |
Douglas Fir-Larch | #1 | 7-8 | 11-2 | 14-2 | 17-4 | |
Douglas Fir-Larch | #2 | 7-2 | 10-6 | 13-3 | 16-3 | |
Douglas Fir-Larch | #3 | 5-5 | 7-11 | 10-0 | 12-3 | |
Hem-Fir | SS | 7-10 | 12-3 | 16-2 | 20-6 | |
Hem-Fir | #1 | 7-6 | 10-11 | 13-10 | 16-11 | |
Hem-Fir | #2 | 7-1 | 10-4 | 13-1 | 16-0 | |
Hem-Fir | #3 | 5-5 | 7-11 | 10-0 | 12-3 | |
Southern Pine | SS | 8-1 | 12-9 | 16-10 | 21-6 | |
Southern Pine | #1 | 8-0 | 12-6 | 15-10 | 18-10 | |
Southern Pine | #2 | 7-8 | 11-0 | 14-2 | 16-11 | |
Southern Pine | #3 | 5-9 | 8-6 | 10-10 | 12-10 | |
Spruce-Pine-Fir | SS | 7-8 | 12-0 | 15-10 | 19-5 | |
Spruce-Pine-Fir | #1 | 7-2 | 10-6 | 13-3 | 16-3 | |
Spruce-Pine-Fir | #2 | 7-2 | 10-6 | 13-3 | 16-3 | |
Spruce-Pine-Fir | #3 | 5-5 | 7-11 | 10-0 | 12-3 |
RAFTER SPACING (inches) |
SPECIES AND GRADE | DEAD LOAD = 10 pounds per square foot | DEAD LOAD = 20 pounds per square foot | |||||||||
2 × 4 | 2 × 6 | 2 × 8 | 2 × 10 | 2 × 12 | 2 × 4 | 2 × 6 | 2 × 8 | 2 × 10 | 2 × 12 | |||
Maximum rafter spans | ||||||||||||
(ft. - in.) | (ft. - in.) | (ft. - in.) | (ft. - in.) | (ft. - in.) | (ft. - in.) | (ft. - in.) | (ft. - in.) | (ft. - in.) | (ft. - in.) | |||
12 | Douglas Fir-Larch | SS | 11-6 | 18-0 | 23-9 | 26-0 | 26-0 | 11-6 | 18-0 | 23-5 | 26-0 | 26-0 |
Douglas Fir-Larch | #1 | 11-1 | 17-4 | 22-5 | 26-0 | 26-0 | 10-6 | 15-4 | 19-5 | 23-9 | 26-0 | |
Douglas Fir-Larch | #2 | 10-10 | 16-7 | 21-0 | 25-8 | 26-0 | 9-10 | 14-4 | 18-2 | 22-3 | 25-9 | |
Douglas Fir-Larch | #3 | 8-7 | 12-6 | 15-10 | 19-5 | 22-6 | 7-5 | 10-10 | 13-9 | 16-9 | 19-6 | |
Hem-Fir | SS | 10-10 | 17-0 | 22-5 | 26-0 | 26-0 | 10-10 | 17-0 | 22-5 | 26-0 | 26-0 | |
Hem-Fir | #1 | 10-7 | 16-8 | 21-10 | 26-0 | 26-0 | 10-3 | 14-11 | 18-11 | 23-2 | 26-0 | |
Hem-Fir | #2 | 10-1 | 15-11 | 20-8 | 25-3 | 26-0 | 9-8 | 14-2 | 17-11 | 21-11 | 25-5 | |
Hem-Fir | #3 | 8-7 | 12-6 | 15-10 | 19-5 | 22-6 | 7-5 | 10-10 | 13-9 | 16-9 | 19-6 | |
Southern Pine | SS | 11-3 | 17-8 | 23-4 | 26-0 | 26-0 | 11-3 | 17-8 | 23-4 | 26-0 | 26-0 | |
Southern Pine | #1 | 11-1 | 17-4 | 22-11 | 26-0 | 26-0 | 11-1 | 17-3 | 21-9 | 25-10 | 26-0 | |
Southern Pine | #2 | 10-10 | 17-0 | 22-5 | 26-0 | 26-0 | 10-6 | 15-1 | 19-5 | 23-2 | 26-0 | |
Southern Pine | #3 | 9-1 | 13-6 | 17-2 | 20-3 | 24-1 | 7-11 | 11-8 | 14-10 | 17-6 | 20-11 | |
Spruce-Pine-Fir | SS | 10-7 | 16-8 | 21-11 | 26-0 | 26-0 | 10-7 | 16-8 | 21-9 | 26-0 | 26-0 | |
Spruce-Pine-Fir | #1 | 10-4 | 16-3 | 21-0 | 25-8 | 26-0 | 9-10 | 14-4 | 18-2 | 22-3 | 25-9 | |
Spruce-Pine-Fir | #2 | 10-4 | 16-3 | 21-0 | 25-8 | 26-0 | 9-10 | 14-4 | 18-2 | 22-3 | 25-9 | |
Spruce-Pine-Fir | #3 | 8-7 | 12-6 | 15-10 | 19-5 | 22-6 | 7-5 | 10-10 | 13-9 | 16-9 | 19-6 | |
16 | Douglas Fir-Larch | SS | 10-5 | 16-4 | 21-7 | 26-0 | 26-0 | 10-5 | 16-0 | 20-3 | 24-9 | 26-0 |
Douglas Fir-Larch | #1 | 10-0 | 15-4 | 19-5 | 23-9 | 26-0 | 9-1 | 13-3 | 16-10 | 20-7 | 23-10 | |
Douglas Fir-Larch | #2 | 9-10 | 14-4 | 18-2 | 22-3 | 25-9 | 8-6 | 12-5 | 15-9 | 19-3 | 22-4 | |
Douglas Fir-Larch | #3 | 7-5 | 10-10 | 13-9 | 16-9 | 19-6 | 6-5 | 9-5 | 11-11 | 14-6 | 16-10 | |
Hem-Fir | SS | 9-10 | 15-6 | 20-5 | 26-0 | 26-0 | 9-10 | 15-6 | 19-11 | 24-4 | 26-0 | |
Hem-Fir | #1 | 9-8 | 14-11 | 18-11 | 23-2 | 26-0 | 8-10 | 12-11 | 16-5 | 20-0 | 23-3 | |
Hem-Fir | #2 | 9-2 | 14-2 | 17-11 | 21-11 | 25-5 | 8-5 | 12-3 | 15-6 | 18-11 | 22-0 | |
Hem-Fir | #3 | 7-5 | 10-10 | 13-9 | 16-9 | 19-6 | 6-5 | 9-5 | 11-11 | 14-6 | 16-10 | |
Southern Pine | SS | 10-3 | 16-1 | 21-2 | 26-0 | 26-0 | 10-3 | 16-1 | 21-2 | 26-0 | 26-0 | |
Southern Pine | #1 | 10-0 | 15-9 | 20-10 | 25-10 | 26-0 | 10-0 | 15-0 | 18-10 | 22-4 | 26-0 | |
Southern Pine | #2 | 9-10 | 15-1 | 19-5 | 23-2 | 26-0 | 9-1 | 13-0 | 16-10 | 20-1 | 23-7 | |
Southern Pine | #3 | 7-11 | 11-8 | 14-10 | 17-6 | 20-11 | 6-10 | 10-1 | 12-10 | 15-2 | 18-1 | |
Spruce-Pine-Fir | SS | 9-8 | 15-2 | 19-11 | 25-5 | 26-0 | 9-8 | 14-10 | 18-10 | 23-0 | 26-0 | |
Spruce-Pine-Fir | #1 | 9-5 | 14-4 | 18-2 | 22-3 | 25-9 | 8-6 | 12-5 | 15-9 | 19-3 | 22-4 | |
Spruce-Pine-Fir | #2 | 9-5 | 14-4 | 18-2 | 22-3 | 25-9 | 8-6 | 12-5 | 15-9 | 19-3 | 22-4 | |
Spruce-Pine-Fir | #3 | 7-5 | 10-10 | 13-9 | 16-9 | 19-6 | 6-5 | 9-5 | 11-11 | 14-6 | 16-10 | |
19.2 | Douglas Fir-Larch | SS | 9-10 | 15-5 | 20-4 | 25-11 | 26-0 | 9-10 | 14-7 | 18-6 | 22-7 | 26-0 |
Douglas Fir-Larch | #1 | 9-5 | 14-0 | 17-9 | 21-8 | 25-2 | 8-4 | 12-2 | 15-4 | 18-9 | 21-9 | |
Douglas Fir-Larch | #2 | 8-11 | 13-1 | 16-7 | 20-3 | 23-6 | 7-9 | 11-4 | 14-4 | 17-7 | 20-4 | |
Douglas Fir-Larch | #3 | 6-9 | 9-11 | 12-7 | 15-4 | 17-9 | 5-10 | 8-7 | 10-10 | 13-3 | 15-5 | |
Hem-Fir | SS | 9-3 | 14-7 | 19-2 | 24-6 | 26-0 | 9-3 | 14-4 | 18-2 | 22-3 | 25-9 | |
Hem-Fir | #1 | 9-1 | 13-8 | 17-4 | 21-1 | 24-6 | 8-1 | 11-10 | 15-0 | 18-4 | 21-3 | |
Hem-Fir | #2 | 8-8 | 12-11 | 16-4 | 20-0 | 23-2 | 7-8 | 11-2 | 14-2 | 17-4 | 20-1 | |
Hem-Fir | #3 | 6-9 | 9-11 | 12-7 | 15-4 | 17-9 | 5-10 | 8-7 | 10-10 | 13-3 | 15-5 | |
Southern Pine | SS | 9-8 | 15-2 | 19-11 | 25-5 | 26-0 | 9-8 | 15-2 | 19-11 | 25-5 | 26-0 | |
Southern Pine | #1 | 9-5 | 14-10 | 19-7 | 23-7 | 26-0 | 9-3 | 13-8 | 17-2 | 20-5 | 24-4 | |
Southern Pine | #2 | 9-3 | 13-9 | 17-9 | 21-2 | 24-10 | 8-4 | 11-11 | 15-4 | 18-4 | 21-6 | |
Southern Pine | #3 | 7-3 | 10-8 | 13-7 | 16-0 | 19-1 | 6-3 | 9-3 | 11-9 | 13-10 | 16-6 | |
Spruce-Pine-Fir | SS | 9-1 | 14-3 | 18-9 | 23-11 | 26-0 | 9-1 | 13-7 | 17-2 | 21-0 | 24-4 | |
Spruce-Pine-Fir | #1 | 8-10 | 13-1 | 16-7 | 20-3 | 23-6 | 7-9 | 11-4 | 14-4 | 17-7 | 20-4 | |
Spruce-Pine-Fir | #2 | 8-10 | 13-1 | 16-7 | 20-3 | 23-6 | 7-9 | 11-4 | 14-4 | 17-7 | 20-4 | |
Spruce-Pine-Fir | #3 | 6-9 | 9-11 | 12-7 | 15-4 | 17-9 | 5-10 | 8-7 | 10-10 | 13-3 | 15-5 | |
24 | Douglas Fir-Larch | SS | 9-1 | 14-4 | 18-10 | 23-4 | 26-0 | 8-11 | 13-1 | 16-7 | 20-3 | 23-5 |
Douglas Fir-Larch | #1 | 8-7 | 12-6 | 15-10 | 19-5 | 22-6 | 7-5 | 10-10 | 13-9 | 16-9 | 19-6 | |
Douglas Fir-Larch | #2 | 8-0 | 11-9 | 14-10 | 18-2 | 21-0 | 6-11 | 10-2 | 12-10 | 15-8 | 18-3 | |
Douglas Fir-Larch | #3 | 6-1 | 8-10 | 11-3 | 13-8 | 15-11 | 5-3 | 7-8 | 9-9 | 11-10 | 13-9 | |
Hem-Fir | SS | 8-7 | 13-6 | 17-10 | 22-9 | 26-0 | 8-7 | 12-10 | 16-3 | 19-10 | 23-0 | |
Hem-Fir | #1 | 8-4 | 12-3 | 15-6 | 18-11 | 21-11 | 7-3 | 10-7 | 13-5 | 16-4 | 19-0 | |
Hem-Fir | #2 | 7-11 | 11-7 | 14-8 | 17-10 | 20-9 | 6-10 | 10-0 | 12-8 | 15-6 | 17-11 | |
Hem-Fir | #3 | 6-1 | 8-10 | 11-3 | 13-8 | 15-11 | 5-3 | 7-8 | 9-9 | 11-10 | 13-9 | |
Southern Pine | SS | 8-11 | 14-1 | 18-6 | 23-8 | 26-0 | 8-11 | 14-1 | 18-6 | 22-11 | 26-0 | |
Southern Pine | #1 | 8-9 | 13-9 | 17-9 | 21-1 | 25-2 | 8-3 | 12-3 | 15-4 | 18-3 | 21-9 | |
Southern Pine | #2 | 8-7 | 12-3 | 15-10 | 18-11 | 22-2 | 7-5 | 10-8 | 13-9 | 16-5 | 19-3 | |
Southern Pine | #3 | 6-5 | 9-6 | 12-1 | 14-4 | 17-1 | 5-7 | 8-3 | 10-6 | 12-5 | 14-9 | |
Spruce-Pine-Fir | SS | 8-5 | 13-3 | 17-5 | 21-8 | 25-2 | 8-4 | 12-2 | 15-4 | 18-9 | 21-9 | |
Spruce-Pine-Fir | #1 | 8-0 | 11-9 | 14-10 | 18-2 | 21-0 | 6-11 | 10-2 | 12-10 | 15-8 | 18-3 | |
Spruce-Pine-Fir | #2 | 8-0 | 11-9 | 14-10 | 18-2 | 21-0 | 6-11 | 10-2 | 12-10 | 15-8 | 18-3 | |
Spruce-Pine-Fir | #3 | 6-1 | 8-10 | 11-3 | 13-8 | 15-11 | 5-3 | 7-8 | 9-9 | 11-10 | 13-9 |
RAFTER SPACING (inches) |
SPECIES AND GRADE | DEAD LOAD = 10 pounds per square foot | DEAD LOAD = 20 pounds per square foot | |||||||||
2 × 4 | 2 × 6 | 2 × 8 | 2 × 10 | 2 × 12 | 2 × 4 | 2 × 6 | 2 × 8 | 2 × 10 | 2 × 12 | |||
Maximum rafter spans | ||||||||||||
(ft. - in.) | (ft. - in.) | (ft. - in.) | (ft. - in.) | (ft. - in.) | (ft. - in.) | (ft. - in.) | (ft. - in.) | (ft. - in.) | (ft. - in.) | |||
12 | Douglas Fir-Larch | SS | 10-5 | 16-4 | 21-7 | 26-0 | 26-0 | 10-5 | 16-4 | 21-7 | 26-0 | 26-0 |
Douglas Fir-Larch | #1 | 10-0 | 15-9 | 20-10 | 26-0 | 26-0 | 10-0 | 15-4 | 19-5 | 23-9 | 26-0 | |
Douglas Fir-Larch | #2 | 9-10 | 15-6 | 20-5 | 25-8 | 26-0 | 9-10 | 14-4 | 18-2 | 22-3 | 25-9 | |
Douglas Fir-Larch | #3 | 8-7 | 12-6 | 15-10 | 19-5 | 22-6 | 7-5 | 10-10 | 13-9 | 16-9 | 19-6 | |
Hem-Fir | SS | 9-10 | 15-6 | 20-5 | 26-0 | 26-0 | 9-10 | 15-6 | 20-5 | 26-0 | 26-0 | |
Hem-Fir | #1 | 9-8 | 15-2 | 19-11 | 25-5 | 26-0 | 9-8 | 14-11 | 18-11 | 23-2 | 26-0 | |
Hem-Fir | #2 | 9-2 | 14-5 | 19-0 | 24-3 | 26-0 | 9-2 | 14-2 | 17-11 | 21-11 | 25-5 | |
Hem-Fir | #3 | 8-7 | 12-6 | 15-10 | 19-5 | 22-6 | 7-5 | 10-10 | 13-9 | 16-9 | 19-6 | |
Southern Pine | SS | 10-3 | 16-1 | 21-2 | 26-0 | 26-0 | 10-3 | 16-1 | 21-2 | 26-0 | 26-0 | |
Southern Pine | #1 | 10-0 | 15-9 | 20-10 | 26-0 | 26-0 | 10-0 | 15-9 | 20-10 | 25-10 | 26-0 | |
Southern Pine | #2 | 9-10 | 15-6 | 20-5 | 26-0 | 26-0 | 9-10 | 15-1 | 19-5 | 23-2 | 26-0 | |
Southern Pine | #3 | 9-1 | 13-6 | 17-2 | 20-3 | 24-1 | 7-11 | 11-8 | 14-10 | 17-6 | 20-11 | |
Spruce-Pine-Fir | SS | 9-8 | 15-2 | 19-11 | 25-5 | 26-0 | 9-8 | 15-2 | 19-11 | 25-5 | 26-0 | |
Spruce-Pine-Fir | #1 | 9-5 | 14-9 | 19-6 | 24-10 | 26-0 | 9-5 | 14-4 | 18-2 | 22-3 | 25-9 | |
Spruce-Pine-Fir | #2 | 9-5 | 14-9 | 19-6 | 24-10 | 26-0 | 9-5 | 14-4 | 18-2 | 22-3 | 25-9 | |
Spruce-Pine-Fir | #3 | 8-7 | 12-6 | 15-10 | 19-5 | 22-6 | 7-5 | 10-10 | 13-9 | 16-9 | 19-6 | |
16 | Douglas Fir-Larch | SS | 9-6 | 14-11 | 19-7 | 25-0 | 26-0 | 9-6 | 14-11 | 19-7 | 24-9 | 26-0 |
Douglas Fir-Larch | #1 | 9-1 | 14-4 | 18-11 | 23-9 | 26-0 | 9-1 | 13-3 | 16-10 | 20-7 | 23-10 | |
Douglas Fir-Larch | #2 | 8-11 | 14-1 | 18-2 | 22-3 | 25-9 | 8-6 | 12-5 | 15-9 | 19-3 | 22-4 | |
Douglas Fir-Larch | #3 | 7-5 | 10-10 | 13-9 | 16-9 | 19-6 | 6-5 | 9-5 | 11-11 | 14-6 | 16-10 | |
Hem-Fir | SS | 8-11 | 14-1 | 18-6 | 23-8 | 26-0 | 8-11 | 14-1 | 18-6 | 23-8 | 26-0 | |
Hem-Fir | #1 | 8-9 | 13-9 | 18-1 | 23-1 | 26-0 | 8-9 | 12-11 | 16-5 | 20-0 | 23-3 | |
Hem-Fir | #2 | 8-4 | 13-1 | 17-3 | 21-11 | 25-5 | 8-4 | 12-3 | 15-6 | 18-11 | 22-0 | |
Hem-Fir | #3 | 7-5 | 10-10 | 13-9 | 16-9 | 19-6 | 6-5 | 9-5 | 11-11 | 14-6 | 16-10 | |
Southern Pine | SS | 9-4 | 14-7 | 19-3 | 24-7 | 26-0 | 9-4 | 14-7 | 19-3 | 24-7 | 26-0 | |
Southern Pine | #1 | 9-1 | 14-4 | 18-11 | 24-1 | 26-0 | 9-1 | 14-4 | 18-10 | 22-4 | 26-0 | |
Southern Pine | #2 | 8-11 | 14-1 | 18-6 | 23-2 | 26-0 | 8-11 | 13-0 | 16-10 | 20-1 | 23-7 | |
Southern Pine | #3 | 7-11 | 11-8 | 14-10 | 17-6 | 20-11 | 6-10 | 10-1 | 12-10 | 15-2 | 18-1 | |
Spruce-Pine-Fir | SS | 8-9 | 13-9 | 18-1 | 23-1 | 26-0 | 8-9 | 13-9 | 18-1 | 23-0 | 26-0 | |
Spruce-Pine-Fir | #1 | 8-7 | 13-5 | 17-9 | 22-3 | 25-9 | 8-6 | 12-5 | 15-9 | 19-3 | 22-4 | |
Spruce-Pine-Fir | #2 | 8-7 | 13-5 | 17-9 | 22-3 | 25-9 | 8-6 | 12-5 | 15-9 | 19-3 | 22-4 | |
Spruce-Pine-Fir | #3 | 7-5 | 10-10 | 13-9 | 16-9 | 19-6 | 6-5 | 9-5 | 11-11 | 14-6 | 16-10 | |
19.2 | Douglas Fir-Larch | SS | 8-11 | 14-0 | 18-5 | 23-7 | 26-0 | 8-11 | 14-0 | 18-5 | 22-7 | 26-0 |
Douglas Fir-Larch | #1 | 8-7 | 13-6 | 17-9 | 21-8 | 25-2 | 8-4 | 12-2 | 15-4 | 18-9 | 21-9 | |
Douglas Fir-Larch | #2 | 8-5 | 13-1 | 16-7 | 20-3 | 23-6 | 7-9 | 11-4 | 14-4 | 17-7 | 20-4 | |
Douglas Fir-Larch | #3 | 6-9 | 9-11 | 12-7 | 15-4 | 17-9 | 5-10 | 8-7 | 10-10 | 13-3 | 15-5 | |
Hem-Fir | SS | 8-5 | 13-3 | 17-5 | 22-3 | 26-0 | 8-5 | 13-3 | 17-5 | 22-3 | 25-9 | |
Hem-Fir | #1 | 8-3 | 12-11 | 17-1 | 21-1 | 24-6 | 8-1 | 11-10 | 15-0 | 18-4 | 21-3 | |
Hem-Fir | #2 | 7-10 | 12-4 | 16-3 | 20-0 | 23-2 | 7-8 | 11-2 | 14-2 | 17-4 | 20-1 | |
Hem-Fir | #3 | 6-9 | 9-11 | 12-7 | 15-4 | 17-9 | 5-10 | 8-7 | 10-10 | 13-3 | 15-5 | |
Southern Pine | SS | 8-9 | 13-9 | 18-1 | 23-1 | 26-0 | 8-9 | 13-9 | 18-1 | 23-1 | 26-0 | |
Southern Pine | #1 | 8-7 | 13-6 | 17-9 | 22-8 | 26-0 | 8-7 | 13-6 | 17-2 | 20-5 | 24-4 | |
Southern Pine | #2 | 8-5 | 13-3 | 17-5 | 21-2 | 24-10 | 8-4 | 11-11 | 15-4 | 18-4 | 21-6 | |
Southern Pine | #3 | 7-3 | 10-8 | 13-7 | 16-0 | 19-1 | 6-3 | 9-3 | 11-9 | 13-10 | 16-6 | |
Spruce-Pine-Fir | SS | 8-3 | 12-11 | 17-1 | 21-9 | 26-0 | 8-3 | 12-11 | 17-1 | 21-0 | 24-4 | |
Spruce-Pine-Fir | #1 | 8-1 | 12-8 | 16-7 | 20-3 | 23-6 | 7-9 | 11-4 | 14-4 | 17-7 | 20-4 | |
Spruce-Pine-Fir | #2 | 8-1 | 12-8 | 16-7 | 20-3 | 23-6 | 7-9 | 11-4 | 14-4 | 17-7 | 20-4 | |
Spruce-Pine-Fir | #3 | 6-9 | 9-11 | 12-7 | 15-4 | 17-9 | 5-10 | 8-7 | 10-10 | 13-3 | 15-5 | |
24 | Douglas Fir-Larch | SS | 8-3 | 13-0 | 17-2 | 21-10 | 26-0 | 8-3 | 13-0 | 16-7 | 20-3 | 23-5 |
Douglas Fir-Larch | #1 | 8-0 | 12-6 | 15-10 | 19-5 | 22-6 | 7-5 | 10-10 | 13-9 | 16-9 | 19-6 | |
Douglas Fir-Larch | #2 | 7-10 | 11-9 | 14-10 | 18-2 | 21-0 | 6-11 | 10-2 | 12-10 | 15-8 | 18-3 | |
Douglas Fir-Larch | #3 | 6-1 | 8-10 | 11-3 | 13-8 | 15-11 | 5-3 | 7-8 | 9-9 | 11-10 | 13-9 | |
Hem-Fir | SS | 7-10 | 12-3 | 16-2 | 20-8 | 25-1 | 7-10 | 12-3 | 16-2 | 19-10 | 23-0 | |
Hem-Fir | #1 | 7-8 | 12-0 | 15-6 | 18-11 | 21-11 | 7-3 | 10-7 | 13-5 | 16-4 | 19-0 | |
Hem-Fir | #2 | 7-3 | 11-5 | 14-8 | 17-10 | 20-9 | 6-10 | 10-0 | 12-8 | 15-6 | 17-11 | |
Hem-Fir | #3 | 6-1 | 8-10 | 11-3 | 13-8 | 15-11 | 5-3 | 7-8 | 9-9 | 11-10 | 13-9 | |
Southern Pine | SS | 8-1 | 12-9 | 16-10 | 21-6 | 26-0 | 8-1 | 12-9 | 16-10 | 21-6 | 26-0 | |
Southern Pine | #1 | 8-0 | 12-6 | 16-6 | 21-1 | 25-2 | 8-0 | 12-3 | 15-4 | 18-3 | 21-9 | |
Southern Pine | #2 | 7-10 | 12-3 | 15-10 | 18-11 | 22-2 | 7-5 | 10-8 | 13-9 | 16-5 | 19-3 | |
Southern Pine | #3 | 6-5 | 9-6 | 12-1 | 14-4 | 17-1 | 5-7 | 8-3 | 10-6 | 12-5 | 14-9 | |
Spruce-Pine-Fir | SS | 7-8 | 12-0 | 15-10 | 20-2 | 24-7 | 7-8 | 12-0 | 15-4 | 18-9 | 21-9 | |
Spruce-Pine-Fir | #1 | 7-6 | 11-9 | 14-10 | 18-2 | 21-0 | 6-11 | 10-2 | 12-10 | 15-8 | 18-3 | |
Spruce-Pine-Fir | #2 | 7-6 | 11-9 | 14-10 | 18-2 | 21-0 | 6-11 | 10-2 | 12-10 | 15-8 | 18-3 | |
Spruce-Pine-Fir | #3 | 6-1 | 8-10 | 11-3 | 13-8 | 15-11 | 5-3 | 7-8 | 9-9 | 11-10 | 13-9 |
RAFTER SPACING (inches) |
SPECIES AND GRADE | DEAD LOAD = 10 pounds per square foot | DEAD LOAD = 20 pounds per square foot | |||||||||
2 × 4 | 2 × 6 | 2 × 8 | 2 × 10 | 2 × 12 | 2 × 4 | 2 × 6 | 2 × 8 | 2 × 10 | 2 × 12 | |||
Maximum rafter spans | ||||||||||||
(ft. - in.) | (ft. - in.) | (ft. - in.) | (ft. - in.) | (ft. - in.) | (ft. - in.) | (ft. - in.) | (ft. - in.) | (ft. - in.) | (ft. - in.) | |||
12 | Douglas Fir-Larch | SS | 10-0 | 15-9 | 20-9 | 26-0 | 26-0 | 10-0 | 15-9 | 20-1 | 24-6 | 26-0 |
Douglas Fir-Larch | #1 | 9-8 | 14-9 | 18-8 | 22-9 | 26-0 | 9-0 | 13-2 | 16-8 | 20-4 | 23-7 | |
Douglas Fir-Larch | #2 | 9-5 | 13-9 | 17-5 | 21-4 | 24-8 | 8-5 | 12-4 | 15-7 | 19-1 | 22-1 | |
Douglas Fir-Larch | #3 | 7-1 | 10-5 | 13-2 | 16-1 | 18-8 | 6-4 | 9-4 | 11-9 | 14-5 | 16-8 | |
Hem-Fir | SS | 9-6 | 14-10 | 19-7 | 25-0 | 26-0 | 9-6 | 14-10 | 19-7 | 24-1 | 26-0 | |
Hem-Fir | #1 | 9-3 | 14-4 | 18-2 | 22-2 | 25-9 | 8-9 | 12-10 | 16-3 | 19-10 | 23-0 | |
Hem-Fir | #2 | 8-10 | 13-7 | 17-2 | 21-0 | 24-4 | 8-4 | 12-2 | 15-4 | 18-9 | 21-9 | |
Hem-Fir | #3 | 7-1 | 10-5 | 13-2 | 16-1 | 18-8 | 6-4 | 9-4 | 11-9 | 14-5 | 16-8 | |
Southern Pine | SS | 9-10 | 15-6 | 20-5 | 26-0 | 26-0 | 9-10 | 15-6 | 20-5 | 26-0 | 26-0 | |
Southern Pine | #1 | 9-8 | 15-2 | 20-0 | 24-9 | 26-0 | 9-8 | 14-10 | 18-8 | 22-2 | 26-0 | |
Southern Pine | #2 | 9-6 | 14-5 | 18-8 | 22-3 | 26-0 | 9-0 | 12-11 | 16-8 | 19-11 | 23-4 | |
Southern Pine | #3 | 7-7 | 11-2 | 14-3 | 16-10 | 20-0 | 6-9 | 10-0 | 12-9 | 15-1 | 17-11 | |
Spruce-Pine-Fir | SS | 9-3 | 14-7 | 19-2 | 24-6 | 26-0 | 9-3 | 14-7 | 18-8 | 22-9 | 26-0 | |
Spruce-Pine-Fir | #1 | 9-1 | 13-9 | 17-5 | 21-4 | 24-8 | 8-5 | 12-4 | 15-7 | 19-1 | 22-1 | |
Spruce-Pine-Fir | #2 | 9-1 | 13-9 | 17-5 | 21-4 | 24-8 | 8-5 | 12-4 | 15-7 | 19-1 | 22-1 | |
Spruce-Pine-Fir | #3 | 7-1 | 10-5 | 13-2 | 16-1 | 18-8 | 6-4 | 9-4 | 11-9 | 14-5 | 16-8 | |
16 | Douglas Fir-Larch | SS | 9-1 | 14-4 | 18-10 | 23-9 | 26-0 | 9-1 | 13-9 | 17-5 | 21-3 | 24-8 |
Douglas Fir-Larch | #1 | 8-9 | 12-9 | 16-2 | 19-9 | 22-10 | 7-10 | 11-5 | 14-5 | 17-8 | 20-5 | |
Douglas Fir-Larch | #2 | 8-2 | 11-11 | 15-1 | 18-5 | 21-5 | 7-3 | 10-8 | 13-6 | 16-6 | 19-2 | |
Douglas Fir-Larch | #3 | 6-2 | 9-0 | 11-5 | 13-11 | 16-2 | 5-6 | 8-1 | 10-3 | 12-6 | 14-6 | |
Hem-Fir | SS | 8-7 | 13-6 | 17-10 | 22-9 | 26-0 | 8-7 | 13-6 | 17-1 | 20-10 | 24-2 | |
Hem-Fir | #1 | 8-5 | 12-5 | 15-9 | 19-3 | 22-3 | 7-7 | 11-1 | 14-1 | 17-2 | 19-11 | |
Hem-Fir | #2 | 8-0 | 11-9 | 14-11 | 18-2 | 21-1 | 7-2 | 10-6 | 13-4 | 16-3 | 18-10 | |
Hem-Fir | #3 | 6-2 | 9-0 | 11-5 | 13-11 | 16-2 | 5-6 | 8-1 | 10-3 | 12-6 | 14-6 | |
Southern Pine | SS | 8-11 | 14-1 | 18-6 | 23-8 | 26-0 | 8-11 | 14-1 | 18-6 | 23-8 | 26-0 | |
Southern Pine | #1 | 8-9 | 13-9 | 18-1 | 21-5 | 25-7 | 8-8 | 12-10 | 16-2 | 19-2 | 22-10 | |
Southern Pine | #2 | 8-7 | 12-6 | 16-2 | 19-3 | 22-7 | 7-10 | 11-2 | 14-5 | 17-3 | 20-2 | |
Southern Pine | #3 | 6-7 | 9-8 | 12-4 | 14-7 | 17-4 | 5-10 | 8-8 | 11-0 | 13-0 | 15-6 | |
Spruce-Pine-Fir | SS | 8-5 | 13-3 | 17-5 | 22-1 | 25-7 | 8-5 | 12-9 | 16-2 | 19-9 | 22-10 | |
Spruce-Pine-Fir | #1 | 8-2 | 11-11 | 15-1 | 18-5 | 21-5 | 7-3 | 10-8 | 13-6 | 16-6 | 19-2 | |
Spruce-Pine-Fir | #2 | 8-2 | 11-11 | 15-1 | 18-5 | 21-5 | 7-3 | 10-8 | 13-6 | 16-6 | 19-2 | |
Spruce-Pine-Fir | #3 | 6-2 | 9-0 | 11-5 | 13-11 | 16-2 | 5-6 | 8-1 | 10-3 | 12-6 | 14-6 | |
19.2 | Douglas Fir-Larch | SS | 8-7 | 13-6 | 17-9 | 21-8 | 25-2 | 8-7 | 12-6 | 15-10 | 19-5 | 22-6 |
Douglas Fir-Larch | #1 | 7-11 | 11-8 | 14-9 | 18-0 | 20-11 | 7-1 | 10-5 | 13-2 | 16-1 | 18-8 | |
Douglas Fir-Larch | #2 | 7-5 | 10-11 | 13-9 | 16-10 | 19-6 | 6-8 | 9-9 | 12-4 | 15-1 | 17-6 | |
Douglas Fir-Larch | #3 | 5-7 | 8-3 | 10-5 | 12-9 | 14-9 | 5-0 | 7-4 | 9-4 | 11-5 | 13-2 | |
Hem-Fir | SS | 8-1 | 12-9 | 16-9 | 21-4 | 24-8 | 8-1 | 12-4 | 15-7 | 19-1 | 22-1 | |
Hem-Fir | #1 | 7-9 | 11-4 | 14-4 | 17-7 | 20-4 | 6-11 | 10-2 | 12-10 | 15-8 | 18-2 | |
Hem-Fir | #2 | 7-4 | 10-9 | 13-7 | 16-7 | 19-3 | 6-7 | 9-7 | 12-2 | 14-10 | 17-3 | |
Hem-Fir | #3 | 5-7 | 8-3 | 10-5 | 12-9 | 14-9 | 5-0 | 7-4 | 9-4 | 11-5 | 13-2 | |
Southern Pine | SS | 8-5 | 13-3 | 17-5 | 22-3 | 26-0 | 8-5 | 13-3 | 17-5 | 22-0 | 25-9 | |
Southern Pine | #1 | 8-3 | 13-0 | 16-6 | 19-7 | 23-4 | 7-11 | 11-9 | 14-9 | 17-6 | 20-11 | |
Southern Pine | #2 | 7-11 | 11-5 | 14-9 | 17-7 | 20-7 | 7-1 | 10-2 | 13-2 | 15-9 | 18-5 | |
Southern Pine | #3 | 6-0 | 8-10 | 11-3 | 13-4 | 15-10 | 5-4 | 7-11 | 10-1 | 11-11 | 14-2 | |
Spruce-Pine-Fir | SS | 7-11 | 12-5 | 16-5 | 20-2 | 23-4 | 7-11 | 11-8 | 14-9 | 18-0 | 20-11 | |
Spruce-Pine-Fir | #1 | 7-5 | 10-11 | 13-9 | 16-10 | 19-6 | 6-8 | 9-9 | 12-4 | 15-1 | 17-6 | |
Spruce-Pine-Fir | #2 | 7-5 | 10-11 | 13-9 | 16-10 | 19-6 | 6-8 | 9-9 | 12-4 | 15-1 | 17-6 | |
Spruce-Pine-Fir | #3 | 5-7 | 8-3 | 10-5 | 12-9 | 14-9 | 5-0 | 7-4 | 9-4 | 11-5 | 13-2 | |
24 | Douglas Fir-Larch | SS | 7-11 | 12-6 | 15-10 | 19-5 | 22-6 | 7-8 | 11-3 | 14-2 | 17-4 | 20-1 |
Douglas Fir-Larch | #1 | 7-1 | 10-5 | 13-2 | 16-1 | 18-8 | 6-4 | 9-4 | 11-9 | 14-5 | 16-8 | |
Douglas Fir-Larch | #2 | 6-8 | 9-9 | 12-4 | 15-1 | 17-6 | 5-11 | 8-8 | 11-0 | 13-6 | 15-7 | |
Douglas Fir-Larch | #3 | 5-0 | 7-4 | 9-4 | 11-5 | 13-2 | 4-6 | 6-7 | 8-4 | 10-2 | 11-10 | |
Hem-Fir | SS | 7-6 | 11-10 | 15-7 | 19-1 | 22-1 | 7-6 | 11-0 | 13-11 | 17-0 | 19-9 | |
Hem-Fir | #1 | 6-11 | 10-2 | 12-10 | 15-8 | 18-2 | 6-2 | 9-1 | 11-6 | 14-0 | 16-3 | |
Hem-Fir | #2 | 6-7 | 9-7 | 12-2 | 14-10 | 17-3 | 5-10 | 8-7 | 10-10 | 13-3 | 15-5 | |
Hem-Fir | #3 | 5-0 | 7-4 | 9-4 | 11-5 | 13-2 | 4-6 | 6-7 | 8-4 | 10-2 | 11-10 | |
Southern Pine | SS | 7-10 | 12-3 | 16-2 | 20-8 | 25-1 | 7-10 | 12-3 | 16-2 | 19-8 | 23-0 | |
Southern Pine | #1 | 7-8 | 11-9 | 14-9 | 17-6 | 20-11 | 7-1 | 10-6 | 13-2 | 15-8 | 18-8 | |
Southern Pine | #2 | 7-1 | 10-2 | 13-2 | 15-9 | 18-5 | 6-4 | 9-2 | 11-9 | 14-1 | 16-6 | |
Southern Pine | #3 | 5-4 | 7-11 | 10-1 | 11-11 | 14-2 | 4-9 | 7-1 | 9-0 | 10-8 | 12-8 | |
Spruce-Pine-Fir | SS | 7-4 | 11-7 | 14-9 | 18-0 | 20-11 | 7-1 | 10-5 | 13-2 | 16-1 | 18-8 | |
Spruce-Pine-Fir | #1 | 6-8 | 9-9 | 12-4 | 15-1 | 17-6 | 5-11 | 8-8 | 11-0 | 13-6 | 15-7 | |
Spruce-Pine-Fir | #2 | 6-8 | 9-9 | 12-4 | 15-1 | 17-6 | 5-11 | 8-8 | 11-0 | 13-6 | 15-7 | |
Spruce-Pine-Fir | #3 | 5-0 | 7-4 | 9-4 | 11-5 | 13-2 | 4-6 | 6-7 | 8-4 | 10-2 | 11-10 |
RAFTER SPACING (inches) |
SPECIES AND GRADE | DEAD LOAD = 10 pounds per square foot | DEAD LOAD = 20 pounds per square foot | |||||||||
2 × 4 | 2 × 6 | 2 × 8 | 2 × 10 | 2 × 12 | 2 × 4 | 2 × 6 | 2 × 8 | 2 × 10 | 2 × 12 | |||
Maximum rafter spans | ||||||||||||
(ft. - in.) | (ft. - in.) | (ft. - in.) | (ft. - in.) | (ft. - in.) | (ft. - in.) | (ft. - in.) | (ft. - in.) | (ft. - in.) | (ft. - in.) | |||
12 | Douglas Fir-Larch | SS | 8-5 | 13-3 | 17-6 | 22-4 | 26-0 | 8-5 | 13-3 | 17-0 | 20-9 | 24-10 |
Douglas Fir-Larch | #1 | 8-2 | 12-0 | 15-3 | 18-7 | 21-7 | 7-7 | 11-2 | 14-1 | 17-3 | 20-0 | |
Douglas Fir-Larch | #2 | 7-8 | 11-3 | 14-3 | 17-5 | 20-2 | 7-1 | 10-5 | 13-2 | 16-1 | 18-8 | |
Douglas Fir-Larch | #3 | 5-10 | 8-6 | 10-9 | 13-2 | 15-3 | 5-5 | 7-10 | 10-0 | 12-2 | 14-1 | |
Hem-Fir | SS | 8-0 | 12-6 | 16-6 | 21-1 | 25-6 | 8-0 | 12-6 | 16-6 | 20-4 | 23-7 | |
Hem-Fir | #1 | 7-10 | 11-9 | 14-10 | 18-1 | 21-0 | 7-5 | 10-10 | 13-9 | 16-9 | 19-5 | |
Hem-Fir | #2 | 7-5 | 11-1 | 14-0 | 17-2 | 19-11 | 7-0 | 10-3 | 13-0 | 15-10 | 18-5 | |
Hem-Fir | #3 | 5-10 | 8-6 | 10-9 | 13-2 | 15-3 | 5-5 | 7-10 | 10-0 | 12-2 | 14-1 | |
Southern Pine | SS | 8-4 | 13-0 | 17-2 | 21-11 | 26-0 | 8-4 | 13-0 | 17-2 | 21-11 | 26-0 | |
Southern Pine | #1 | 8-2 | 12-10 | 16-10 | 20-3 | 24-1 | 8-2 | 12-6 | 15-9 | 18-9 | 22-4 | |
Southern Pine | #2 | 8-0 | 11-9 | 15-3 | 18-2 | 21-3 | 7-7 | 10-11 | 14-1 | 16-10 | 19-9 | |
Southern Pine | #3 | 6-2 | 9-2 | 11-8 | 13-9 | 16-4 | 5-9 | 8-5 | 10-9 | 12-9 | 15-2 | |
Spruce-Pine-Fir | SS | 7-10 | 12-3 | 16-2 | 20-8 | 24-1 | 7-10 | 12-3 | 15-9 | 19-3 | 22-4 | |
Spruce-Pine-Fir | #1 | 7-8 | 11-3 | 14-3 | 17-5 | 20-2 | 7-1 | 10-5 | 13-2 | 16-1 | 18-8 | |
Spruce-Pine-Fir | #2 | 7-8 | 11-3 | 14-3 | 17-5 | 20-2 | 7-1 | 10-5 | 13-2 | 16-1 | 18-8 | |
Spruce-Pine-Fir | #3 | 5-10 | 8-6 | 10-9 | 13-2 | 15-3 | 5-5 | 7-10 | 10-0 | 12-2 | 14-1 | |
16 | Douglas Fir-Larch | SS | 7-8 | 12-1 | 15-10 | 19-5 | 22-6 | 7-8 | 11-7 | 14-8 | 17-11 | 20-10 |
Douglas Fir-Larch | #1 | 7-1 | 10-5 | 13-2 | 16-1 | 18-8 | 6-7 | 9-8 | 12-2 | 14-11 | 17-3 | |
Douglas Fir-Larch | #2 | 6-8 | 9-9 | 12-4 | 15-1 | 17-6 | 6-2 | 9-0 | 11-5 | 13-11 | 16-2 | |
Douglas Fir-Larch | #3 | 5-0 | 7-4 | 9-4 | 11-5 | 13-2 | 4-8 | 6-10 | 8-8 | 10-6 | 12-3 | |
Hem-Fir | SS | 7-3 | 11-5 | 15-0 | 19-1 | 22-1 | 7-3 | 11-5 | 14-5 | 17-8 | 20-5 | |
Hem-Fir | #1 | 6-11 | 10-2 | 12-10 | 15-8 | 18-2 | 6-5 | 9-5 | 11-11 | 14-6 | 16-10 | |
Hem-Fir | #2 | 6-7 | 9-7 | 12-2 | 14-10 | 17-3 | 6-1 | 8-11 | 11-3 | 13-9 | 15-11 | |
Hem-Fir | #3 | 5-0 | 7-4 | 9-4 | 11-5 | 13-2 | 4-8 | 6-10 | 8-8 | 10-6 | 12-3 | |
Southern Pine | SS | 7-6 | 11-10 | 15-7 | 19-11 | 24-3 | 7-6 | 11-10 | 15-7 | 19-11 | 23-10 | |
Southern Pine | #1 | 7-5 | 11-7 | 14-9 | 17-6 | 20-11 | 7-4 | 10-10 | 13-8 | 16-2 | 19-4 | |
Southern Pine | #2 | 7-1 | 10-2 | 13-2 | 15-9 | 18-5 | 6-7 | 9-5 | 12-2 | 14-7 | 17-1 | |
Southern Pine | #3 | 5-4 | 7-11 | 10-1 | 11-11 | 14-2 | 4-11 | 7-4 | 9-4 | 11-0 | 13-1 | |
Spruce-Pine-Fir | SS | 7-1 | 11-2 | 14-8 | 18-0 | 20-11 | 7-1 | 10-9 | 13-8 | 16-8 | 19-4 | |
Spruce-Pine-Fir | #1 | 6-8 | 9-9 | 12-4 | 15-1 | 17-6 | 6-2 | 9-0 | 11-5 | 13-11 | 16-2 | |
Spruce-Pine-Fir | #2 | 6-8 | 9-9 | 12-4 | 15-1 | 17-6 | 6-2 | 9-0 | 11-5 | 13-11 | 16-2 | |
Spruce-Pine-Fir | #3 | 5-0 | 7-4 | 9-4 | 11-5 | 13-2 | 4-8 | 6-10 | 8-8 | 10-6 | 12-3 | |
19.2 | Douglas Fir-Larch | SS | 7-3 | 11-4 | 14-6 | 17-8 | 20-6 | 7-3 | 10-7 | 13-5 | 16-5 | 19-0 |