The performance, selection, installation, operation, and use of single- and multiple-station alarms and household fire alarm systems shall comply with the requirements of this chapter.
Smoke and heat alarms shall be installed in all occupancies where required by other governing laws, codes, or standards.
The requirements of this chapter shall not apply to installations in manufactured homes.
Fire-warning equipment for residential occupancies shall provide a reliable means to notify the occupants of the presence of a threatening fire and the need to escape to a place of safety before such escape might be impeded by untenable conditions in the normal path of egress.
All devices, combinations of devices, and equipment to be installed in conformity with this chapter shall be approved or listed for the purposes for which they are intended.
Fire-warning equipment shall be installed in accordance with the listing and manufacturer's published instructions.
The installation of smoke alarms or fire alarm systems, or combinations of these, shall comply with the requirements of this chapter and shall satisfy the minimum requirements for number and location of smoke alarms or smoke detectors by one of the following arrangements:
- The required minimum number and location of smoke detection devices shall be satisfied (independently) through the installation of smoke alarms. The installation of additional smoke alarms shall be permitted. The installation of additional system-based smoke detectors, including partial or complete duplication of the smoke alarms satisfying the required minimum, shall be permitted.
- The required minimum number and location of smoke detection devices shall be satisfied (independently) through the installation of system smoke detectors. The installation of additional smoke detectors shall be permitted. The installation of additional smoke alarms, including partial or complete duplication of the smoke detectors satisfying the required minimum, shall be permitted.
Supplementary functions, including the extension of an alarm beyond the residential occupancy, shall be permitted and shall not interfere with the performance requirements of this chapter.
Fire-warning equipment to be installed in residential occupancies shall produce the audible emergency evacuation signal described in ANSI S3.41, American National Standard Emergency Evacuation Signal, whenever the intended response is to evacuate the building.
The audible emergency evacuation signal shall be permitted to be used for other devices as long as the desired response is immediate evacuation.
Fire-warning equipment producing the audible emergency evacuation signal shall be permitted to incorporate voice notification under either or both of the following conditions:
- Where the voice message is contained completely within the 1.5-second pause period of the audible emergency evacuation signal
- Where the voice message complies with 29.3.5.2(2)(a) and (b) as follows:
- The voice message is first preceded by a minimum of eight cycles of the audible emergency evacuation signal.
- The voice message periodically interrupts the signal for no longer than 10 seconds, followed by a minimum of two cycles of the audible emergency evacuation signal between each voice message. The initial eight-cycle period shall not be required to be repeated.
All audible fire alarm signals installed shall meet the performance requirements of 18.4.3, 18.4.5.1, 18.4.5.2, and 29.3.8.
When visible appliances are provided, they shall meet the requirements of Section 18.5. Since hearing deficits are often not apparent, the responsibility for advising the appropriate person(s) of the existence of this deficit shall be that of the party with hearing loss.
Notification appliances provided in sleeping rooms and guest rooms for those with hearing loss shall comply with 29.3.8.1 and 29.3.8.2, as applicable.
Notification appliances provided for those with mild to severe hearing loss shall comply with the following:
- An audible notification appliance producing a low frequency alarm signal shall be installed in the following situations:
- Where required by governing laws, codes, or standards for people with hearing loss
- Where provided voluntarily for those with hearing loss
- *The low frequency alarm signal output shall comply with the following:
- The waveform shall have a fundamental frequency of 520 Hz ±10 percent.
- The minimum sound level at the pillow shall be 75 dBA, or 15 dB above the average ambient sound level, or 5 dB above the maximum sound level having a duration of at least 60 seconds, whichever is greater.
Visible notification appliances in accordance with the requirements of 18.5.5.7 and tactile notification appliances in accordance with the requirements of Section 18.10 shall be required for those with moderately severe to profound hearing loss in the following situations:
- *Where required by governing laws, codes, or standards for people with hearing loss
- Where provided voluntarily for those with hearing loss
Signals from notification appliances shall not be required to be synchronized.
The requirements of this chapter shall assume that occupants are not intimate with the ignition and are capable of self-rescue.
The requirements of this chapter shall assume that the occupants have an escape plan.
An escape route shall be assumed to be available to occupants and to be unobstructed prior to the event of the fire.
The performance of fire-warning equipment discussed in this chapter shall depend on such equipment being properly selected, installed, operated, tested, and maintained in accordance with the provisions of this Code and with the manufacturer's published instructions provided with the equipment.
The use of fire alarm system smoke detectors and notification appliances shall be permitted to meet the fire-warning requirements for smoke alarms specified in 29.5.1.
Where required by other governing laws, codes, or standards for a specific type of occupancy, approved single- and multiple-station smoke alarms shall be installed as follows:
- *In all sleeping rooms and guest rooms
- *Outside of each separate dwelling unit sleeping area, within 21 ft (6.4 m) of any door to a sleeping room, with the distance measured along a path of travel
- On every level of a dwelling unit, including basements
- On every level of a residential board and care occupancy (small facility), including basements and excluding crawl spaces and unfinished attics
- *In the living area(s) of a guest suite
- In the living area(s) of a residential board and care occupancy (small facility)
Where the area addressed in 29.5.1.1(2) is separated from the adjacent living areas by a door, a smoke alarm shall be installed in the area between the door and the sleeping rooms, and additional alarms shall be installed on the living area side of the door as specified by 29.5.1.1 and 29.5.1.3.
In addition to the requirements of 29.5.1.1(1) through (3), where the interior floor area for a given level of a dwelling unit, excluding garage areas, is greater than 1000 ft2 (93 m2), smoke alarms shall be installed per 29.5.1.3.1 and 29.5.1.3.2.
All points on the ceiling shall have a smoke alarm within a distance of 30 ft (9.1 m) travel distance or shall have an equivalent of one smoke alarm per 500 ft2 (46 m2) of floor area. One smoke alarm per 500 ft2 (46 m2) is evaluated by dividing the total interior square footage of floor area per level by 500 ft2 (46 m2).
Where dwelling units include great rooms or vaulted/cathedral ceilings extending over multiple floors, smoke alarms located on the upper floor that are intended to protect the aforementioned area shall be permitted to be considered as part of the lower floor(s) protection scheme used to meet the requirements of 29.5.1.3.1.
Fire-warning equipment used to provide required or optional detection shall produce audible fire alarm signals that comply with 29.5.2.1.1 or 29.5.2.1.2.
Unless exempted by applicable laws, codes, or standards, smoke or heat alarms used to provide a fire-warning function, and when two or more alarms are installed within a dwelling unit, suite of rooms, or similar area, shall be arranged so that the operation of any smoke or heat alarm causes all alarms within these locations to sound.
Exception: The arrangement for all alarms to sound shall not be required for mechanically powered single-station heat alarms.
Where a household fire alarm system is used to provide a fire-warning function, notification appliances shall be installed to meet the performance requirements of 29.3.6.
Unless otherwise permitted by the authority having jurisdiction, audible fire alarm signals shall sound only in an individual dwelling unit, suite of rooms, or similar area and shall not be arranged to operate fire-warning equipment or fire alarm systems outside these locations. Remote annunciation shall be permitted.
Smoke and heat alarms shall be powered by one of the following means:
- A commercial light and power source along with a secondary power source that is capable of operating the device for at least 7 days in the normal condition, followed by 4 minutes of alarm
- If a commercial light and power source is not normally available, a noncommercial ac power source along with a secondary power source that is capable of operating the device for at least 7 days in the normal condition, followed by 4 minutes of alarm
- A nonrechargeable, nonreplaceable primary battery that is capable of operating the device for at least 10 years in the normal condition, followed by 4 minutes of alarm, followed by 7 days of trouble
- If a battery primary power supply is specifically permitted, a battery meeting the requirements of 29.6.6 (nonrechargeable primary battery) or the requirements of 29.6.7 (rechargeable primary battery)
- A suitable spring-wound mechanism for the nonelectrical portion of a listed single-station alarm with a visible indication to show that sufficient operating power is not available
Power for household fire alarm systems shall comply with the following requirements:
- Household fire alarm systems shall have two independent power sources consisting of a primary source that uses commercial light and power and a secondary source that consists of a rechargeable battery.
- The secondary source shall be capable of operating the system for at least 24 hours in the normal condition, followed by 4 minutes of alarm.
- The secondary power source shall be supervised and shall cause a distinctive audible and visible trouble signal upon removal or disconnection of a battery or a low-battery condition.
- A rechargeable battery used as a secondary power source shall meet the following criteria:
- Be automatically recharged by an ac circuit of the commercial light and power source
- Be recharged within 48 hours
- Provide a distinctive audible trouble signal before the battery is incapable of operating the device(s) for alarm purposes
- Low-power wireless systems shall comply with the performance criteria of Section 23.16.
The ac power source shall comply with the following conditions:
- A visible "power on" indicator shall be provided.
- All electrical systems designed to be installed by other than a qualified electrician shall be powered from a source not in excess of 30 volts that meets the requirements for power-limited fire alarm circuits as defined in NFPA 70, National Electrical Code, Article 760.
- A restraining means shall be used at the plug-in of any cord-connected installation.
- AC primary (main) power shall be supplied either from a dedicated branch circuit or the unswitched portion of a branch circuit also used for power and lighting.
- Operation of a switch (other than a circuit breaker) shall not cause loss of primary (main) power. Operation of a ground-fault circuit-interrupter (GFCI) receptacle shall not cause loss of primary (main) power. Smoke alarms powered by branch circuits protected by arc-fault circuit-interrupters (AFCI) or GFCI circuit breakers shall have a secondary power source.
- Neither loss nor restoration of primary (main) power shall cause an alarm signal. Exception: An alarm signal shall be permitted but shall not exceed 2 seconds.
- Where a secondary (standby) battery is provided, the primary (main) power supply shall be of sufficient capacity to operate the system under all conditions of loading with any secondary (standby) battery disconnected or fully discharged.
Where alarms include a battery that is used as a secondary power source, the following conditions shall be met:
- The secondary power source shall be supervised and shall cause a distinctive audible or visible trouble signal upon removal or disconnection of a battery or a low-battery condition.
- Acceptable replacement batteries shall be clearly identified by the manufacturer's name and model number on the unit near the battery compartment.
- A rechargeable battery used as a secondary power source shall meet the following criteria:
- Be automatically recharged by the primary power source
- Be recharged within 4 hours where power is provided from a circuit that can be switched on or off by means other than a circuit breaker, or within 48 hours where power is provided from a circuit that cannot be switched on or off by means other than a circuit breaker
- Provide a distinctive audible trouble signal before the battery is incapable of operating the device(s) for alarm purposes
- At the battery condition at which a trouble signal is obtained, be capable of producing an alarm signal for at least 4 minutes, followed by not less than 7 days of trouble signal operation
- Produce an audible trouble signal at least once every minute for 7 consecutive days
If a visible notification appliance is used in conjunction with a smoke or heat alarm application for compliance with 29.3.7, the notification appliance shall not be required to be supplied with a secondary power source.
If smoke alarms are powered by a primary battery, the battery shall be monitored to ensure the following conditions are met:
- All power requirements are met for at least 1 year of battery life, including weekly testing.
- A distinctive audible trouble signal before the battery is incapable of operating (from causes such as aging or terminal corrosion) the device(s) for alarm purposes.
- For a unit employing a lock-in alarm feature, automatic transfer is provided from alarm to a trouble condition.
- At the battery voltage at which a trouble signal is obtained, the unit is capable of producing an alarm signal for at least 4 minutes, followed by not less than 7 days of trouble signal operation.
- The audible trouble signal is produced at least once every minute for 7 consecutive days.
- Acceptable replacement batteries are clearly identified by the manufacturer's name and model number on the unit near the battery compartment.
- A noticeable, visible indication is displayed when a primary battery is removed from the unit.
If smoke alarms are powered by a rechargeable battery, the following conditions shall be met:
- The battery shall, with proper charging, be able to power the alarm for a life of 1 year.
- The battery shall be automatically recharged by an circuit of the commercial light and power source.
- The battery shall be recharged within 4 hours where power is provided from a circuit that can be switched on or off by means other than a circuit breaker, or within 48 hours where power is provided from a circuit that cannot be switched on or off by means other than a circuit breaker.
- A distinctive audible trouble signal shall sound before the battery is incapable of operating the device(s) for alarm purposes.
- For a unit employing a lock-in alarm feature, automatic transfer shall be provided from alarm to a trouble condition.
- At the battery condition at which a trouble signal is obtained, the unit shall be capable of producing an alarm signal for at least 4 minutes, followed by not less than 7 days of trouble signal operation.
- The audible trouble signal shall be produced at least once every minute for 7 consecutive days.
Where alarms include a secondary power source (non-battery), the following conditions shall be met:
- The secondary power source shall be supervised and shall cause a distinctive audible or visible trouble signal upon depletion or failure.
- A distinctive audible trouble signal shall be provided before the power source is incapable of operating the device(s) for alarm purposes.
- At a power source condition at which a trouble signal is obtained, the power source shall be capable of producing an alarm signal for at least 4 minutes, followed by not less than 7 days of trouble signal operation.
- The audible trouble signal shall be produced at least once every minute for 7 consecutive days.
- A rechargeable secondary power source shall meet the following criteria:
Any failure of any nonreliable or shortlife component that renders the detector inoperable shall result in a trouble signal or otherwise be apparent to the occupant of the living unit without the need for test.
Each device shall detect abnormal quantities of smoke or applicable fire signature, shall operate in the normal environmental conditions, and shall be in compliance with applicable standards such as ANSI/UL 268, Standard for Smoke Detectors for Fire Alarm Systems, or ANSI/UL 217, Standard for Single and Multiple Station Smoke Alarms.
Effective January 1, 2019, smoke alarms and smoke detectors used in household fire alarm systems shall be listed for resistance to common nuisance sources.
Each heat detector and heat alarm, including a heat detector or heat alarm integrally mounted on a smoke detector or smoke alarm, shall detect abnormally high temperature or rate-of-temperature rise, and all such detectors shall be listed for not less than 50 ft (15 m) spacing.
Fixed-temperature detectors or alarms shall have a temperature rating at least 25°F (14°C) above the normal ambient temperature and shall not be rated 50°F (28°C) higher than the maximum anticipated ambient temperature in the room or space where installed.
Single- and multiple-station alarms, including heat alarms, shall be provided with a convenient means for testing its operability by the occupant, system owner, or other responsible parties.
The system control equipment shall be automatically restoring upon restoration of electrical power.
The system control equipment shall be of a type that "locks in" on an alarm condition. Smoke detection circuits shall not be required to lock in.
A means for silencing the trouble notification appliance(s) shall be permitted only if the following conditions are satisfied:
- The means is key-operated or located within a locked enclosure, or arranged to provide equivalent protection against unauthorized use.
- The means transfers the trouble indication to an identified lamp or other acceptable visible indicator, and the visible indication persists until the trouble condition has been corrected.
A means for turning off activated alarm notification appliances shall be permitted only if the following conditions are satisfied:
- The means is key-operated or located within a locked cabinet, or arranged to provide equivalent protection against unauthorized use.
- The means includes the provision of a visible alarm silence indication.
Household fire alarm system smoke detectors, initiating devices, and notification appliances shall be monitored for integrity so that the occurrence of a single open or single ground fault in the interconnection, which prevents normal operation of the interconnected devices, is indicated by a distinctive trouble signal.
System control equipment shall be in compliance with applicable standards such as ANSI/UL 985, Standard for Household Fire Warning System Units; ANSI/UL 1730, Standard for Smoke Detector Monitors and Accessories for Individual Living Units of Multifamily Residences and Hotel/Motel Rooms; or ANSI/UL 864, Standard for Control Units and Accessories for Fire Alarm Systems.
If designed and installed to perform additional functions, fire-warning equipment shall operate reliably and without compromise to its primary functions.
Faults in other systems or components shall not affect the operation of the fire alarm system.
Where common wiring is employed for a combination system, the equipment for other than the fire alarm system shall be connected to the common wiring of the system so that short circuits, open circuits, grounds, or any fault in this equipment or interconnection between this equipment and the fire alarm system wiring does not interfere with the supervision of the fire alarm system or prevent alarm or trouble signal operation.
In a fire/burglar system, the operation shall be as follows:
- A fire alarm signal shall take precedence or be clearly recognizable over any other signal, even when the nonfire alarm signal is initiated first.
- Distinctive alarm signals shall be used so that fire alarms can be distinguished from other functions, such as burglar alarms. The use of a common-sounding appliance for fire and burglar alarms shall be permitted where distinctive signals are used.
Installations that include the connection of single- or multiple-station alarms with other input or output devices shall be permitted. An open, ground fault or short circuit of the wiring connecting input or output devices to the single- or multiple-station alarms shall not prevent operation of each individual alarm.
Single- or multiple-station smoke alarms shall be permitted to be connected to system control equipment located within the dwelling unit.
When connected, the actuation of a single- or multiple-station smoke alarm shall initiate an alarm signal at the system control equipment located within the dwelling unit.
A sprinkler waterflow alarm initiating device shall be permitted to be connected to the multiple-station alarms or household fire alarm system to activate an alarm signal.
Household fire alarm systems utilizing low-power wireless transmission of signals within the protected dwelling unit shall comply with the requirements of Section 23.16.
To ensure adequate transmission and reception capability, nonsupervised, low-power wireless alarms shall be capable of reliably communicating at a distance of 100 ft (30.5 m) indoors as tested to an equivalent open area test distance, DEOAT between two devices in accordance with the following equations:

where Lb is the building attenuation factor, a value dependent on the frequency of the wireless transmission. The building attenuation factor, Lb, represents the maximum attenuation value of typical floors and walls within a majority of structures. The factor Lb shall assume four walls and two floors and be calculated as follows:
Lb = 4 × Lw + 2 × Lf
where: | |
Lw | = attenuation value of a wall |
= 2 × L1 + L2 | |
Lf | = attenuation value of a floor |
= L1 + L2 + L3 + L4 | |
L1 | = frequency-dependent attenuation value for 1/2 in. (13 mm) drywall |
L2 | = frequency-dependent attenuation value for 11/2 in. (38 mm) structural lumber |
L3 | = frequency-dependent attenuation value for 3/4 in. (19 mm) plywood |
L4 | = frequency-dependent attenuation value for 1/2 in. (13 mm) glass/tile floor |
Fire alarm signals shall have priority over all other signals.
The maximum allowable response delay from activation of an initiating device to receipt and alarm/display by the receiver/control unit shall be 20 seconds.
Wireless interconnected smoke alarms (in receive mode) shall remain in alarm as long as the originating unit (transmitter) remains in alarm.
The occurrence of any single fault that disables a transceiver shall not prevent other transceivers in the system from operating.
Means to transmit alarm signals to a constantly attended, remote monitoring location shall be processed by a household fire alarm system and shall perform as described in Chapter 26, except as modified by 29.7.9.1.1 through 29.7.9.1.6.
Where a digital alarm communicator transmitter (DACT) is used, the DACT serving the protected premises shall only require a single telephone line and shall only require a call to a single digital alarm communicator receiver (DACR) number.
Where a communication or transmission means other than DACT is used, only a single communication technology and path is required to serve the protected premises.
Failure of the communication path referenced in 29.7.9.1.3 shall be annunciated at the constantly attended remote monitoring location and at the protected premises within not more than 7 days of the failure.
Supervising station systems shall not be required to comply with requirements for indication of central station service in 26.3.4.
A dedicated cellular telephone connection shall be permitted to be used as a single means to transmit alarms to a constantly attended remote monitoring location.
Remote monitoring stations shall be permitted to verify alarm signals prior to reporting them to the fire service, provided that the verification process does not delay the reporting by more than 90 seconds.
Household fire alarm systems shall be programed by the manufacturer to generate at least a monthly test of the communication or transmission means.
The activation of a keypad fire alarm signal shall require a manual operation of two simultaneous or sequential operations.
All equipment shall be installed in accordance with the manufacturer's published instructions and applicable electrical standards.
All devices shall be so located and mounted that accidental operation is not caused by jarring or vibration.
All fire-warning equipment shall be mounted so as to be supported independently of its attachment to wires.
The supplier or installing contractor shall provide the system owner or other responsible parties with the following:
- An instruction booklet illustrating typical installation layouts
- Instruction charts describing the operation, method, and frequency of testing and maintenance of fire-warning equipment
- Printed information for establishing an emergency evacuation plan
- Printed information to inform system owners where they can obtain repair or replacement service, and where and how parts requiring regular replacement, such as batteries or bulbs, can be obtained within 2 weeks
- Information noting both of the following:
- Unless otherwise recommended by the manufacturer's published instructions, smoke alarms shall be replaced when they fail to respond to tests.
- Smoke alarms installed in one- and two-family dwellings shall not remain in service longer than 10 years from the date of manufacture.
Smoke detectors shall be connected to central controls for power, signal processing, and activation of notification appliances.
The interconnection of smoke or heat alarms shall comply with the following:
- Smoke or heat alarms shall not be interconnected in numbers that exceed the manufacturer's published instructions.
- In no case shall more than 18 initiating devices be interconnected (of which 12 can be smoke alarms) where the interconnecting means is not supervised.
- In no case shall more than 64 initiating devices be interconnected (of which 42 can be smoke alarms) where the interconnecting means is supervised.
- Smoke or heat alarms shall not be interconnected with alarms from other manufacturers unless listed as being compatible with the specific model.
- When alarms of different types are interconnected, all interconnected alarms shall produce the appropriate audible response for the phenomena being detected or remain silent.
A single fault on the interconnecting means between multiple-station alarms shall not prevent single-station operation of any of the interconnected alarms.
Remote notification appliance circuits of multiple-station alarms shall be capable of being tested for integrity by activation of the test feature on any interconnected alarm. Activation of the test feature shall result in the operation of all interconnected notification appliances.
Smoke alarms, smoke detectors, devices, combination of devices, and equipment shall be installed in accordance with the manufacturer's listing and published instructions, and, unless specifically listed for the application, shall comply with requirements in 29.8.3.1 through 29.8.3.4.
Smoke alarms or smoke detectors mounted on a peaked ceiling shall be located within 36 in. (910 mm) horizontally of the peak, but not closer than 4 in. (100 mm) vertically to the peak.
Smoke alarms or smoke detectors mounted on a sloped ceiling having a rise greater than 1 ft in 8 ft (1 m in 8 m) horizontally shall be located within 36 in. (910 mm) of the high side of the ceiling, but not closer than 4 in. (100 mm) from the adjoining wall surface.
Smoke alarms or smoke detectors mounted on walls shall be located not farther than 12 in. (300 mm) from the adjoining ceiling surface.
The installation of smoke alarms and smoke detectors shall comply with the following requirements:
- Smoke alarms and smoke detectors shall not be located where ambient conditions, including humidity and temperature, are outside the limits specified by the manufacturer's published instructions.
- Smoke alarms and smoke detectors shall not be located within unfinished attics or garages or in other spaces where temperatures can fall below 40°F (4°C) or exceed 100°F (38°C).
- *Where the mounting surface could become considerably warmer or cooler than the room, such as a poorly insulated ceiling below an unfinished attic or an exterior wall, smoke alarms and smoke detectors shall be mounted on an inside wall.
- *Smoke alarms and smoke detectors shall not be installed within an area of exclusion determined by a 10 ft (3.0 m) radial distance along a horizontal flow path from a stationary or fixed cooking appliance, unless listed for installation in close proximity to cooking appliances. Smoke alarms and smoke detectors installed between 10 ft (3.0 m) and 20 ft (6.1 m) along a horizontal flow path from a stationary or fixed cooking appliance shall be equipped with an alarm-silencing means or use photoelectric detection. Exception: Smoke alarms or smoke detectors that use photoelectric detection shall be permitted for installation at a radial distance greater than 6 ft (1.8 m) from any stationary or fixed cooking appliance when the following conditions are met:
- The kitchen or cooking area and adjacent spaces have no clear interior partitions or headers and
- The 10 ft (3.0 m) area of exclusion would prohibit the placement of a smoke alarm or smoke detector required by other sections of this code.
- Effective January 1, 2016, smoke alarms and smoke detectors used in household fire alarm systems installed between 6 ft (1.8 m) and 20 ft (6.1 m) along a horizontal flow path from a stationary or fixed cooking appliance shall be listed for resistance to common nuisance sources from cooking.
- *Smoke alarms and smoke detectors shall not be installed within a 36 in. (910 mm) horizontal path from a door to a bathroom containing a shower or tub unless listed for installation in close proximity to such locations.
- Smoke alarms and smoke detectors shall not be installed within a 36 in. (910 mm) horizontal path from the supply registers of a forced air heating or cooling system and shall be installed outside of the direct airflow from those registers.
- Smoke alarms and smoke detectors shall not be installed within a 36 in. (910 mm) horizontal path from the tip of the blade of a ceiling-suspended (paddle) fan.
- Where stairs lead to other occupiable levels, a smoke alarm or smoke detector shall be located so that smoke rising in the stairway cannot be prevented from reaching the smoke alarm or smoke detector by an intervening door or obstruction.
- For stairways leading up from a basement, smoke alarms or smoke detectors shall be located on the basement ceiling near the entry to the stairs.
- *For tray-shaped ceilings (coffered ceilings), smoke alarms and smoke detectors shall be installed on the highest portion of the ceiling or on the sloped portion of the ceiling within 12 in. (300 mm) vertically down from the highest point.
- Smoke alarms and detectors installed in rooms with joists or beams shall comply with the requirements of 17.7.3.2.4.
- Heat alarms and detectors installed in rooms with joists or beams shall comply with the requirements of 17.6.3.
On smooth ceilings, heat detectors and heat alarms shall be installed within the strict limitations of their listed spacing.
For sloped ceilings having a rise greater than 1 ft in 8 ft (1 m in 8 m) horizontally, the detector or alarm shall be located within 36 in. (910 mm) of the peak. The spacing of additional detectors or alarms, if any, shall be based on a horizontal distance measurement, not on a measurement along the slope of the ceiling.
Detectors or alarms installed on an open-joisted ceiling shall have their smooth ceiling spacing reduced where this spacing is measured at right angles to solid joists; in the case of heat detectors or heat alarms, this spacing shall not exceed one-half of the listed spacing.
The installation of wiring and equipment shall be in accordance with the requirements of NFPA 70, National Electrical Code, Article 760.
The following optional functions of fire-warning equipment shall be permitted:
- Notification of the fire department, either directly or through an alarm monitoring service
- Monitoring of other safety systems, such as fire sprinklers for alarm or proper operating conditions
- Notification of occupants or others of potentially dangerous conditions, such as the presence of fuel gases or toxic gases such as carbon monoxide
- Notification of occupants or others of the activation of intrusion (burglar alarm) sensors
- Any other function, safety related or not, that could share components or wiring
Section 29.10 final content is the result of a tentative interim amendment (TIA). See page 1. |
Fire-warning equipment shall be maintained and tested in accordance with the manufacturer's published instructions and per the requirements of Chapter 14.
All alarms shall be plainly marked with the following information on the unit:
- Manufacturer's or listee's name, address, and model number
- A mark or certification that the unit has been approved or listed by a testing laboratory
- Electrical rating (where applicable)
- Manufacturer's published operating and maintenance instructions
- Test instructions
- Replacement and service instructions
- Identification of lights, switches, meters, and similar devices regarding their function, unless their function is obvious
- Distinction between alarm and trouble signals on units employing both
- The sensitivity setting for an alarm having a fixed setting (For an alarm that is intended to be adjusted in the field, the range of sensitivity shall be indicated. The marked sensitivity shall be indicated as a percent per foot obscuration level. The marking shall include a nominal value plus tolerance.)
- Reference to an installation diagram and system owner's manual
- Date of manufacture in the format YEAR (in four digits), MONTH (in letters), and DAY (in two digits) located on the outside of the alarm
Exception: Where space limitations prohibit inclusion of 29.11.1(4) and (6), it is not prohibited for this information to be in the installation instructions instead.
All household fire-warning equipment or systems shall be plainly marked with the following information on the unit:
- Manufacturer's or listee's name, address, and model number
- A mark or certification that the unit has been approved or listed by a testing laboratory
- Electrical rating (where applicable)
- Identification of all user interface components and their functions (such as, but not limited to, lights, switches, and meters) located adjacent to the component
- Manufacturer's published operating and maintenance instructions
- Test instructions
- Replacement and service instructions
- Reference to an installation wiring diagram and homeowner's manual, if not attached to control unit, by drawing number and issue number and/or date
Exception: Where space limitations prohibit inclusion of 29.11.2(5) and (7), it is not prohibited for this information to be in the installation instructions instead.