Where water-based fire protection systems are required to be protected against damage from earthquakes, the requirements of Chapter 18 shall apply, unless the requirements of 18.1.2 are met.
Alternative methods of providing earthquake protection of sprinkler systems based on a seismic analysis certified by a registered professional engineer such that system performance will be at least equal to that of the building structure under expected seismic forces shall be permitted.
Braces and restraints shall not obstruct sprinklers and shall comply with the obstruction rules of Chapters 10 through 14.
Flexible couplings joining grooved end pipe shall be provided as flexure joints to allow individual sections of piping 21/2 in. (65 mm) or larger to move differentially with the individual sections of the building to which it is attached.
Flexible couplings shall be arranged to coincide with structural separations within a building.
Systems having more flexible couplings than required by this section shall be provided with additional sway bracing as required in 18.5.5.9.
The flexible couplings shall be installed as follows:
- * Within 24 in. (600 mm) of the top and bottom of all risers, unless the following provisions are met:
- In risers less than 3 ft (900 mm) in length, flexible couplings shall be permitted to be omitted.
- In risers 3 ft to 7 ft (900 mm to 2100 mm) in length, one flexible coupling shall be adequate.
- Within 12 in. (300 mm) above and within 24 in. (600 mm) below the floor in multistory buildings, unless the following provision is met:
- * In risers up to 7 ft (2.1 m) in length terminating above the roof assembly or top landing, the flexible coupling shall not be required above the landing or roof assembly.
- On both sides of concrete or masonry walls within 1 ft (300 mm) of the wall surface, unless clearance is provided in accordance with Section 18.4
- * Within 24 in. (600 mm) of building expansion joints
- Within 24 in. (600 mm) of the top of drops exceeding 15 ft (4.6 m) in length to portions of systems supplying more than one sprinkler, regardless of pipe size
- Within 24 in. (600 mm) above and 24 in. (600 mm) below any intermediate points of support for a riser or other vertical pipe
When the flexible coupling below the floor is above the tie-in main to the main supplying that floor, a flexible coupling shall be provided in accordance with one of the following:
- * On the horizontal portion within 24 in. (600 mm) of the tie-in where the tie-in is horizontal
- * On the vertical portion of the tie-in where the tie-in incorporates a riser
Flexible couplings for drops to hose lines, rack sprinklers, mezzanines, and freestanding structures shall be installed regardless of pipe sizes as follows:
- Within 24 in. (600 mm) of the top of the drop
- Within 24 in. (600 mm) above the uppermost drop support attachment, where drop supports are provided to the structure, rack, or mezzanine
- Within 24 in. (600 mm) above the bottom of the drop where no additional drop support is provided
An approved seismic separation assembly shall be installed where sprinkler piping, regardless of size, crosses building seismic separation joints at ground level and above.
Seismic separation assemblies shall consist of flexible fittings or flexible piping so as to allow movement sufficient to accommodate closing of the separation, opening of the separation to twice its normal size, and movement relative to the separation in the other two dimensions in an amount equal to the separation distance.
The seismic separation assembly shall include a four-way brace upstream and downstream within 6 ft (1.8 m) of the seismic separation assembly.
Bracing shall not be attached to the seismic separation assembly.
Clearance shall be provided around all piping extending through walls, floors, platforms, and foundations, including drains, fire department connections, and other auxiliary piping.
Unless any of the requirements of 18.4.3 through 18.4.7 or 18.4.10 are met, where pipe passes through holes in platforms, foundations, walls, or floors, the holes shall be sized such that the diameter of the holes is nominally 2 in. (50 mm) larger than the pipe for pipe 1 in. (25 mm) nominal to 31/2 in. (90 mm) nominal and 4 in. (100 mm) larger than the pipe for pipe 4 in. (100 mm) nominal and larger.
Where clearance is provided by a pipe sleeve, a nominal diameter 2 in. (50 mm) larger than the nominal diameter of the pipe shall be acceptable for pipe sizes 1 in. (25 mm) through 31/2 in. (90 mm), and the clearance provided by a pipe sleeve of nominal diameter 4 in. (100 mm) larger than the nominal diameter of the pipe shall be acceptable for pipe sizes 4 in. (100 mm) and larger.
No clearance shall be required for piping passing through gypsum board or equally frangible construction.
No clearance shall be required if flexible couplings are located within 1 ft (300 mm) of each side of a wall or if the requirements of 18.2.3.1 (2) are met.
No clearance shall be required where horizontal piping passes perpendicularly through successive studs or joists that form a wall or floor/ceiling assembly.
No clearance shall be required where nonmetallic pipe has been demonstrated to have inherent flexibility equal to or greater than the minimum provided by flexible couplings located within 1 ft (300 mm) of each side of a wall, floor, platform, or foundation.
Where required, the clearance shall be filled with a flexible material that is compatible with the piping material.
The installed horizontal and upward vertical clearance between horizontal sprinkler piping and structural members not penetrated or used, collectively or independently, to support the piping shall be at least 2 in. (50 mm).
No clearance shall be required where piping is supported by holes through structural members as permitted by 17.1.7.3.
The installed clearance between a sprinkler and structural elements not used collectively or independently to support the sprinklers shall be at least 3 in. (75 mm).
Where sprinklers are installed using flexible sprinkler hose, clearance for the sprinkler shall not be required.
Clearance shall not be required for piping that is vertically supported by the bottom edge of holes through structural members as permitted by 17.1.7.3.
No horizontal clearance (tight fit) shall be provided for piping that is laterally supported by the side edges of holes through structural members.
The system piping shall be braced to resist both lateral and longitudinal horizontal seismic loads and to prevent vertical motion resulting from seismic loads.
The structural components to which bracing is attached shall be determined to be capable of resisting the added applied seismic loads.
When a shared support structure is used to support gravity and seismic loads, the structure shall be designed to support these loads for all pipe and distribution systems on the structure using either 18.5.9.3 or 18.5.9.4 with an importance factor, Ip, of 1.5 being applied to all of the distribution systems.
If a shared support structure is used to support sprinkler pipe and other distribution systems per 17.1.4.1 and that structure does not provide seismic resistance as required in 18.5.1.4, the following shall be met:
- The sprinkler pipe shall be braced using the method in 18.5.6 with the zone of influence including the water-filled sprinkler pipe and all other distribution systems that are not independently equipped with seismic protection and attached to the shared support structure.
- The sprinkler sway bracing attachment shall be connected to the same building or structure as the shared support structure.
Bracing requirements of Section 18.5 shall not apply to drain piping downstream of the drain valve.
Sway bracing assemblies shall be listed for a maximum load rating, unless the requirements of 18.5.2.2 are met.
Where sway bracing utilizing pipe, angles, flats, or rods as shown in Table 18.5.11.8(a) through Table 18.5.11.8(f) is used, the components shall not require listing.
Bracing fittings and connections used with those specific materials shall be listed.
The listed load rating shall be reduced as shown in Table 18.5.2.3 to determine the allowable load for installations where the brace is less than 90 degrees from vertical.
Table 18.5.2.3 Listed Horizontal Load Adjustment
Brace Angle Degrees from Vertical | Allowable Horizontal Load |
---|---|
30 to 44 | Listed load rating divided by 2.000 |
45 to 59 | Listed load rating divided by 1.414 |
60 to 89 | Listed load rating divided by 1.155 |
90 | Listed load rating |
Maximum allowable horizontal loads shall be determined by testing at angles of 30, 45, 60, and 90 degrees from vertical and confirmed to be equal to or greater than those calculated using 18.5.2.3.
For attachments to structures, additional tests shall be performed at 0 degrees.
Unless permitted by 18.5.3.2, components of sway brace assemblies shall be ferrous.
Nonferrous components that have been proven by fire tests to be adequate for the hazard application, that are listed for this purpose, and that are in compliance with the other requirements of this section shall be acceptable.
Sway braces shall be designed to withstand forces in tension and compression, unless the requirements of 18.5.4.2 are met.
Tension-only bracing systems shall be permitted for use where listed for this service and where installed in accordance with their listing limitations, including installation instructions.
For all braces, whether or not listed, the maximum allowable load shall be based on the weakest component of the brace with safety factors.
Lateral sway bracing shall be provided on all feed and cross mains regardless of size and all branch lines and other piping with a diameter of 21/2 in. (65 mm) and larger.
Where branch lines are not provided with lateral sway bracing, they shall be provided with restraint in accordance with Section 18.6.
The spacing between lateral sway braces shall be in accordance with either Table 18.5.5.2(a) through Table 18.5.5.2(l) or 18.5.5.3, based on the piping material of the sprinkler system.
Table 18.5.5.2(a) Maximum Load (Fpw) in Zone of Influence (lb), (Fy = 30 ksi) Schedule 10 Steel Pipe
Diameter of Pipe (in.) Being Braced | Lateral Sway Brace Spacing (ft) | ||||
---|---|---|---|---|---|
20 | 25 | 30 | 35 | 40 | |
1 | 111 | 89 | 73 | 63 | 52 |
11/4 | 176 | 141 | 116 | 99 | 83 |
11/2 | 241 | 193 | 158 | 136 | 114 |
2 | 390 | 312 | 256 | 219 | 183 |
21/2 | 641 | 513 | 420 | 360 | 301 |
3 | 966 | 773 | 633 | 543 | 454 |
31/2 | 1281 | 1025 | 840 | 720 | 603 |
4 | 1634 | 1307 | 1071 | 918 | 769 |
5 | 2814 | 2251 | 1844 | 1581 | 1324 |
6 and larger* | 4039 | 3231 | 2647 | 2269 | 1900 |
Note: ASTM A106 Grade B or ASTM A53 Grade B has an Fy = 35 ksi. An Fy = 30 ksi was used as a conservative value to account for differences in material properties as well as other operational stresses.
*Larger diameter pipe can be used when justified by engineering analysis.
Table 18.5.5.2(b) Maximum Load (Fpw) in Zone of Influence (kg), (Fy = 207 N/mm2) Schedule 10 Steel Pipe
Diameter of Pipe (mm) Being Braced | Lateral Sway Brace Spacing (m) | ||||
---|---|---|---|---|---|
6.1 | 7.6 | 9.1 | 11 | 12 | |
25 | 50 | 40 | 33 | 29 | 24 |
32 | 80 | 64 | 53 | 45 | 38 |
40 | 109 | 88 | 72 | 62 | 52 |
50 | 177 | 142 | 116 | 99 | 83 |
65 | 291 | 233 | 191 | 163 | 137 |
80 | 438 | 351 | 287 | 246 | 206 |
90 | 581 | 465 | 381 | 327 | 273 |
100 | 741 | 593 | 486 | 416 | 349 |
125 | 1276 | 1021 | 836 | 717 | 601 |
150* | 1832 | 1466 | 1201 | 1029 | 862 |
Note: ASTM A106 Grade B or ASTM A53 Grade B has an Fy = 241 N/mm2. An Fy = 207 N/mm2 was used also as a conservative value to account for differences in material properties as well as other operational stresses.
*Larger diameter pipe can be used when justified by engineering analysis.
Table 18.5.5.2(c) Maximum Load (Fpw) in Zone of Influence (lb), (Fy = 30 ksi) Schedule 40 Steel Pipe
Diameter of Pipe (in.) Being Braced | Lateral Sway Brace Spacing (ft) | ||||
---|---|---|---|---|---|
20 | 25 | 30 | 35 | 40 | |
1 | 121 | 97 | 79 | 68 | 57 |
11/4 | 214 | 171 | 140 | 120 | 100 |
11/2 | 306 | 245 | 201 | 172 | 144 |
2 | 520 | 416 | 341 | 292 | 245 |
21/2 | 984 | 787 | 645 | 553 | 463 |
3 | 1597 | 1278 | 1047 | 897 | 751 |
31/2 | 2219 | 1775 | 1455 | 1247 | 1044 |
4 | 2981 | 2385 | 1954 | 1675 | 1402 |
5 | 5061 | 4049 | 3317 | 2843 | 2381 |
6 and larger* | 7893 | 6314 | 5173 | 4434 | 3713 |
Note: ASTM A106 Grade B or ASTM A53 Grade B has an Fy = 35 ksi. An Fy = 30 ksi was used as a conservative value to account for differences in material properties as well as other operational stresses.
*Larger diameter pipe can be used when justified by engineering analysis.
Table 18.5.5.2(d) Maximum Load (Fpw) in Zone of Influence (kg), (Fy = 207 N/mm2) Schedule 40 Steel Pipe
Diameter of Pipe (in.) Being Braced | Lateral Sway Brace Spacing (m) | ||||
---|---|---|---|---|---|
6.1 | 7.6 | 9.1 | 11 | 12 | |
25 | 55 | 44 | 36 | 31 | 26 |
32 | 97 | 78 | 63 | 54 | 45 |
40 | 139 | 111 | 91 | 78 | 65 |
50 | 236 | 189 | 155 | 132 | 111 |
65 | 446 | 357 | 293 | 251 | 210 |
80 | 724 | 580 | 475 | 407 | 341 |
90 | 1007 | 805 | 660 | 566 | 474 |
100 | 1352 | 1082 | 886 | 760 | 636 |
125 | 2296 | 1837 | 1505 | 1290 | 1080 |
150* | 3580 | 2864 | 2346 | 2011 | 1684 |
Note: ASTM A106 Grade B or ASTM A53 Grade B has an Fy = 241 N/mm2. An Fy = 207 N/mm2 was used also as a conservative value to account for differences in material properties as well as other operational stresses.
*Larger diameter pipe can be used when justified by engineering analysis.
Table 18.5.5.2(e) Maximum Load (Fpw) in Zone of Influence (lb), (Fy = 30 ksi) Schedule 5 Steel Pipe
Diameter of Pipe (in.) Being Braced | Lateral Sway Brace Spacing (ft) | ||||
---|---|---|---|---|---|
20 | 25 | 30 | 35 | 40 | |
1 | 71 | 56 | 46 | 40 | 33 |
11/4 | 116 | 93 | 76 | 65 | 55 |
11/2 | 154 | 124 | 101 | 87 | 73 |
2 | 246 | 197 | 161 | 138 | 116 |
21/2 | 459 | 367 | 301 | 258 | 216 |
3 | 691 | 552 | 453 | 388 | 325 |
31/2 | 910 | 728 | 597 | 511 | 428 |
4* | 1160 | 928 | 760 | 652 | 546 |
Note: ASTM A106 Grade B or ASTM A53 Grade B has an Fy = 35 ksi. An Fy = 30 ksi was used as a conservative value to account for differences in material properties as well as other operational stresses.
*Larger diameter pipe can be used when justified by engineering analysis.
Table 18.5.5.2(f) Maximum Load (Fpw) in Zone of Influence (kg), (Fy = 207 N/mm2) Schedule 5 Steel Pipe
Diameter of Pipe (mm) Being Braced | Lateral Sway Brace Spacing (m) | ||||
---|---|---|---|---|---|
6.1 | 7.6 | 9.1 | 11 | 12 | |
25 | 32 | 25 | 21 | 18 | 15 |
32 | 53 | 42 | 34 | 29 | 25 |
40 | 70 | 56 | 46 | 39 | 33 |
50 | 112 | 89 | 73 | 63 | 53 |
65 | 208 | 166 | 137 | 117 | 98 |
80 | 313 | 250 | 205 | 176 | 147 |
90 | 413 | 330 | 271 | 232 | 194 |
100* | 526 | 421 | 345 | 296 | 248 |
Note: ASTM A106 Grade B or ASTM A53 Grade B has an Fy = 241 N/mm2. An Fy = 207 N/mm2 was used also as a conservative value to account for differences in material properties as well as other operational stresses.
*Larger diameter pipe can be used when justified by engineering analysis.
Table 18.5.5.2(g) Maximum Load (Fpw) in Zone of Influence (lb), (Fy = 8 ksi) CPVC Pipe
Diameter of Pipe (in.) Being Braced | Lateral Sway Brace Spacing (ft) | ||||
---|---|---|---|---|---|
20 | 25 | 30 | 35 | 40 | |
3/4 | 15 | 12 | 10 | 8 | 7 |
1 | 28 | 22 | 18 | 15 | 13 |
11/4 | 56 | 45 | 37 | 30 | 26 |
11/2 | 83 | 67 | 55 | 45 | 39 |
2 | 161 | 129 | 105 | 87 | 76 |
21/2 | 286 | 229 | 188 | 154 | 135 |
3 | 516 | 413 | 338 | 278 | 243 |
Table 18.5.5.2(h) Maximum Load (Fpw) in Zone of Influence (kg), (Fy = 55 N/mm2) CPVC Pipe
Diameter of Pipe (in.) Being Braced | Lateral Sway Brace Spacing (m) | ||||
---|---|---|---|---|---|
6.1 | 7.6 | 9.1 | 11 | 12 | |
20 | 7 | 5 | 5 | 4 | 3 |
25 | 13 | 10 | 8 | 7 | 6 |
32 | 25 | 20 | 17 | 14 | 12 |
40 | 38 | 30 | 25 | 20 | 18 |
50 | 73 | 59 | 48 | 39 | 34 |
65 | 130 | 104 | 85 | 70 | 61 |
80 | 234 | 187 | 153 | 126 | 110 |
Table 18.5.5.2(i) Maximum Load (Fpw) in Zone of Influence (lb), (Fy = 30 ksi) Type M Copper Tube (with Soldered Joints)
Diameter of Pipe (in.) Being Braced | Lateral Sway Brace Spacing (ft) | ||||
---|---|---|---|---|---|
20 | 25 | 30 | 35 | 40 | |
3/4 | 16 | 13 | 10 | 9 | 8 |
1 | 29 | 24 | 19 | 16 | 14 |
11/4 | 53 | 42 | 35 | 28 | 25 |
11/2 | 86 | 69 | 56 | 46 | 41 |
2* | 180 | 144 | 118 | 97 | 85 |
*Larger diameter pipe can be used when justified by engineering analysis.
Table 18.5.5.2(j) Maximum Load (Fpw) in Zone of Influence (kg), (Fy = 3207 N/mm2) Type M Copper Tube (with Soldered Joints)
Diameter of Pipe (in.) Being Braced | Lateral Sway Brace Spacing (m) | ||||
---|---|---|---|---|---|
6.1 | 7.6 | 9.1 | 11 | 12 | |
20 | 7.3 | 5.9 | 5 | 4.1 | 3.6 |
25 | 13.2 | 10.9 | 8.6 | 7.3 | 6.4 |
32 | 24 | 19.1 | 15.9 | 12.7 | 11.3 |
40 | 39 | 31.3 | 25.4 | 20.9 | 18.6 |
50* | 81.6 | 65.3 | 53 | 44 | 38.6 |
*Larger diameter pipe can be used when justified by engineering analysis.
Table 18.5.5.2(k) Maximum Load (Fpw) in Zone of Influence (lb), (Fy = 9 ksi) Type M Copper Tube (with Brazed Joints)
Diameter of Pipe (in.) Being Braced | Lateral Sway Spacing (ft) | ||||
---|---|---|---|---|---|
20 | 25 | 30 | 35 | 40 | |
3/4 | 6 | 5 | 4 | 3 | 3 |
1 | 11 | 9 | 7 | 6 | 5 |
11/4 | 20 | 16 | 13 | 12 | 10 |
11/2 | 33 | 27 | 22 | 19 | 16 |
2* | 70 | 56 | 46 | 39 | 33 |
*Larger diameter pipe can be used when justified by engineering analysis.
Table 18.5.5.2(l) Maximum Load (Fpw) in Zone of Influence (lb), (Fy = 9 ksi) Red Brass Pipe (with Brazed Joints)
Diameter of Pipe (in.) Being Braced | Lateral Sway Spacing (ft) | ||||
---|---|---|---|---|---|
20 | 25 | 30 | 35 | 40 | |
3/4 | 34 | 27 | 22 | 19 | 16 |
1 | 61 | 49 | 40 | 35 | 29 |
11/4 | 116 | 93 | 76 | 65 | 55 |
11/2 | 161 | 129 | 105 | 90 | 76 |
2* | 272 | 218 | 178 | 153 | 128 |
*Larger diameter pipe can be used when justified by engineering analysis.
Specially listed nonstandard pipe shall be permitted using the values in Table 18.5.5.2(e) and Table 18.5.5.2(f) or with values provided by the manufacturer.
Spacing shall not exceed a maximum interval of 40 ft (12 m) on center.
The maximum permissible load in the zone of influence of a sway brace shall not exceed the values given in Table 18.5.5.2(a) through Table 18.5.5.2(1) or the values calculated in accordance with 18.5.5.3.
When determining permissible loads in accordance with 18.5.5.2 or 18.5.5.2.1 on a main with varying sizes, the allowable load shall be based on the smallest pipe size within the zone of influence.
The maximum load (Fpw) in the zone of influence for specially listed pipe shall be calculated. (See Annex E.)
The requirements of 18.5.5.1 shall not apply to 21/2 in. (65 mm) starter pieces that do not exceed 12 ft (3.7 m) in length.
The distance between the last brace and the end of the pipe shall not exceed 6 ft (1.8 m).
Where there is a change in direction of the piping, the cumulative distance between consecutive lateral sway braces shall not exceed the maximum permitted distance in accordance with 18.5.5.2.2.
The last length of pipe at the end of a feed or cross main shall be provided with a lateral brace.
Lateral braces shall be allowed to act as longitudinal braces if they are within 24 in. (600 mm) of the centerline of the piping braced longitudinally and the lateral brace is on a pipe of equal or greater size than the pipe being braced longitudinally.
Where flexible couplings are installed on mains other than as required in Section 18.2, a lateral brace shall be provided within 24 in. (600 mm) of every other coupling, including flexible couplings at grooved fittings, but not more than 40 ft (12 m) on center.
The lateral sway bracing required by 18.5.5 shall be permitted to be omitted when 18.5.5.10.1 for branch lines or 18.5.5.10.2 for mains is met.
Branch lines shall comply with the following:
- * The branch lines shall be individually supported within 6 in. (150 mm) of the structure, measured between the top of the pipe and the point of attachment to the building structure.
- At least 75 percent of all the hangers on the branch line shall meet the requirements of 18.5.5.10.1(1).
- Consecutive hangers on the branch line shall not be permitted to exceed the limitation in 18.5.5.10.1(1).
Mains shall comply with all the following:
- * The main piping shall be individually supported within 6 in. (150 mm) of the structure, measured between the top of the pipe and the point of attachment to the building structure.
- At least 75 percent of all the hangers on the main shall meet the requirements of 18.5.5.10.2(1).
- Consecutive hangers on the main shall not be permitted to exceed the limitation in 18.5.5.10.2(1)
- The seismic coefficient (Cp) shall not exceed 0.5.
- The nominal pipe diameter shall not exceed 6 in. (150 mm) for feed mains and 4 in. (100 mm) for cross mains.
- Hangers shall not be omitted in accordance with 17.4.4.3, 17.4.4.4, or 17.4.4.5.
Branch lines permitted to omit lateral sway bracing by 18.5.5.10 shall not be omitted from load calculations for the mains serving them in 18.5.9.6.
The lateral sway bracing required by 18.5.5 shall be permitted to be omitted when 18.5.5.11.1 for branch lines or 18.5.5.11.2 for mains is met.
Branch lines shall comply with the following:
- The branch lines shall be individually supported by wraparound u-hooks or u-hooks arranged to keep pipe tight to the structural element provided the legs are bent out at least 30 degrees from the vertical and the maximum length of each leg and the rod size satisfies the conditions of Table 18.5.11.8(a) through Table 18.5.11.8(f), or the length of the rod shall be calculated.
- At least 75 percent of all the hangers on the branch line shall meet the requirements of 18.5.5.11.2(1).
- Consecutive hangers on the branch line shall not be permitted to exceed the limitation in 18.5.5.11.2(1).
Mains shall comply with all the following:
- The main piping shall be individually supported by wraparound u-hooks or u-hooks arranged to keep pipe tight to the structural element provided the legs are bent out at least 30 degrees from the vertical and the maximum length of each leg and rod size satisfies the conditions of Table 18.5.11.8(a) through Table 18.5.11.8(f).
- At least 75 percent of all the hangers on the main shall meet the requirements of 18.5.5.11.2(1).
- Consecutive hangers on the main shall not be permitted to exceed the limitation in 18.5.5.11.2(1).
- The seismic coefficient (Cp) shall not exceed 0.5.
- The nominal pipe diameter shall not exceed 6 in. (150 mm) for feed mains and 4 in. (100 mm) for cross mains.
- Hangers shall not be omitted in accordance with 17.4.4.3, 17.4.4.4, or 17.4.4.5.
Longitudinal sway bracing spaced at a maximum of 80 ft (24 m) on center shall be provided for feed and cross mains.
Longitudinal braces shall be allowed to act as lateral braces if they are within 24 in. (600 mm) of the centerline of the piping braced laterally.
The distance between the last brace and the end of the pipe or a change in direction shall not exceed 40 ft (12 m).
Each run of pipe between changes in direction shall be provided with both lateral and longitudinal bracing, unless the requirements of 18.5.7.2 are met.
Pipe runs less than 12 ft (3.7 m) in length shall be permitted to be supported by the braces on adjacent runs of pipe.
The four-way brace shall not be required for risers up to 7 ft (2.1 m) in length that terminate above the roof assembly or top landing.
Riser nipples shall be permitted to omit the four-way brace required by 18.5.8.1.
When a four-way brace at the top of a riser is attached on the horizontal piping, it shall be within 24 in. (600 mm) of the centerline of the riser and the loads for that brace shall include both the vertical and horizontal pipe.
Four-way bracing shall not be required where risers penetrate intermediate floors in multistory buildings where the clearance does not exceed the limits of Section 18.4.
The horizontal seismic load for the braces shall be as determined in 18.5.9.6 or 18.5.9.7, or as required by the authority having jurisdiction.
The weight of the system being braced (Wp) shall be taken as 1.15 times the weight of the water-filled piping. (See A.18.5.9.1.)
The horizontal force, Fpw, acting on the brace shall be taken as Fpw = CpWp, where Cp is the seismic coefficient selected in Table 18.5.9.3 utilizing the short period response parameter, Ss.
Table 18.5.9.3 Seismic Coefficient Table
Ss | Cp | Sp | Cp |
---|---|---|---|
0.33 or less | 0.35 | 2.2 | 1.03 |
0.4 | 0.38 | 2.3 | 1.07 |
0.5 | 0.4 | 2.4 | 1.12 |
0.6 | 0.42 | 2.5 | 1.17 |
0.7 | 0.42 | 2.6 | 1.21 |
0.8 | 0.44 | 2.7 | 1.26 |
0.9 | 0.48 | 2.8 | 1.31 |
1 | 0.51 | 2.9 | 1.35 |
1.1 | 0.54 | 3 | 1.4 |
1.2 | 0.57 | 3.1 | 1.45 |
1.3 | 0.61 | 3.2 | 1.49 |
1.4 | 0.65 | 3.3 | 1.54 |
1.5 | 0.7 | 3.4 | 1.59 |
1.6 | 0.75 | 3.5 | 1.63 |
1.7 | 0.79 | 3.6 | 1.68 |
1.8 | 0.84 | 3.7 | 1.73 |
1.9 | 0.89 | 3.8 | 1.77 |
2 | 0.93 | 3.9 | 1.82 |
2.1 | 0.98 | 4 | 1.87 |
The value of Ss used in Table 18.5.9.3 shall be obtained from the authority having jurisdiction or from seismic hazard maps.
Linear interpolation shall be permitted to be used for intermediate values of Ss.
The horizontal force, Fpw, acting on the brace shall be permitted to be determined in accordance with 13.3.1 of ASCE/SEI 7, Minimum Design Loads for Buildings and Other Structures, multiplied by 0.7 to convert to allowable stress design (ASD).
Where data for determining Cp are not available, the horizontal seismic force acting on the braces shall be determined as specified in 18.5.9.3 with Cp = 0.5.
The zone of influence for lateral braces shall include all branch lines, drops, sprigs, and mains tributary to the brace, except branch lines that are provided with longitudinal bracing or as prohibited by 18.5.9.6.1.
When riser nipples are provided in systems requiring seismic protection, they shall satisfy the following equation, unless one of the following conditions is met:
[18.5.9.6.1]
- Where riser nipples are 4 ft (1.2 m) or less in length and Cp is 0.50 or less
- Where riser nipples are 3 ft (900 mm) or less in length and Cp is less than 0.67
- Where riser nipples are 2 ft (600 mm) in length or less and Cp is less than is 1.0

where: | ||
Hr | = | length of riser nipple piping (in inches) |
Wp | = | tributary weight (in pounds) for the branch line or portion of branch line within the zone of influence including the riser nipple |
Cp | = | seismic coefficient |
S | = | sectional modulus of the riser nipple pipe |
Fy | = | allowable yield strength of 30,000 psi (2070 bar) for steel, 30,000 psi for copper (soldered), 8000 psi (550 bar) for CPVC |
If the calculated value is equal to or greater than the yield strength of the riser nipple, the longitudinal seismic load of each line shall be evaluated individually, and branch lines shall be provided with longitudinal sway bracing per 18.5.6.
The zone of influence for longitudinal braces shall include all mains tributary to the brace.
Where the horizontal seismic loads used exceed 0.5 Wp and the brace angle is less than 45 degrees from vertical or where the horizontal seismic load exceeds 1.0 Wp and the brace angle is less than 60 degrees from vertical, the braces shall be arranged to resist the net vertical reaction produced by the horizontal load.
Bracing shall be attached directly to the system pipe.
Sway bracing shall be tight.
For individual braces, the slenderness ratio (l/r) shall not exceed 300, where l is the length of the brace and r is the least radius of gyration.
Where threaded pipe is used as part of a sway brace assembly, it shall not be less than Schedule 30.
All parts and fittings of a brace shall lie in a straight line to avoid eccentric loadings on fittings and fasteners.
For longitudinal braces only, the brace shall be permitted to be connected to a tab welded to the pipe in conformance to 7.5.2.
For tension-only braces, two tension-only brace components opposing each other must be installed at each lateral or longitudinal brace location.
The loads determined in 18.5.9 shall not exceed the lesser of the maximum allowable loads provided in Table 18.5.11.8(a) through Table 18.5.11.8(f), and the manufacturer's certified maximum allowable horizontal loads for brace angles of 30 to 44 degrees, 45 to 59 degrees, 60 to 89 degrees, or 90 degrees.
Table 18.5.11.8(a) Maximum Horizontal Loads for Sway Braces with l/r = 100 for Steel Braces with Fy = 36 ksi
Brace Shape and Size (in.) | Area (in.2) | Least Radius of Gyration (r) (in.) |
Maximum Length for l/r= 100 |
Maximum Horizontal Load (lb) | ||||
---|---|---|---|---|---|---|---|---|
Brace Angle | ||||||||
ft | in. | 30° to 44°Angle from Vertical | 45° to 59°Angle from Vertical | 60° to 90°Angle from Vertical | ||||
Pipe Schedule 40 | 1 | 0.494 | 0.421 | 3 | 6 | 3,150 | 4,455 | 5,456 |
11/4 | 0.669 | 0.540 | 4 | 6 | 4,266 | 6,033 | 7,389 | |
11/2 | 0.799 | 0.623 | 5 | 2 | 5,095 | 7,206 | 8,825 | |
2 | 1.07 | 0.787 | 6 | 6 | 6,823 | 9,650 | 11,818 | |
Angles | 11/2 × 11/2 × 1/4 | 0.688 | 0.292 | 2 | 5 | 4,387 | 6,205 | 7,599 |
2 × 2 × 1/4 | 0.938 | 0.391 | 3 | 3 | 5,982 | 8,459 | 10,360 | |
21/2 × 2 × 1/4 | 1.06 | 0.424 | 3 | 6 | 6,760 | 9,560 | 11,708 | |
21/2 × 21/2 × 1/4 | 1.19 | 0.491 | 4 | 1 | 7,589 | 10,732 | 13,144 | |
3 × 21/2 × 1/4 | 1.31 | 0.528 | 4 | 4 | 8,354 | 11,814 | 14,469 | |
3 × 3 × 1/4 | 1.44 | 0.592 | 4 | 11 | 9,183 | 12,987 | 15,905 | |
Rods (all thread) | 3/8 | 0.07 | 0.075 | 0 | 7 | 446 | 631 | 773 |
1/2 | 0.129 | 0.101 | 0 | 10 | 823 | 1,163 | 1,425 | |
5/8 | 0.207 | 0.128 | 1 | 0 | 1,320 | 1,867 | 2,286 | |
3/4 | 0.309 | 0.157 | 1 | 3 | 1,970 | 2,787 | 3,413 | |
7/8 | 0.429 | 0.185 | 1 | 6 | 2,736 | 3,869 | 4,738 | |
Rods (threaded at ends only) | 3/8 | 0.11 | 0.094 | 0 | 9 | 701 | 992 | 1,215 |
1/2 | 0.196 | 0.125 | 1 | 0 | 1,250 | 1,768 | 2,165 | |
5/8 | 0.307 | 0.156 | 1 | 3 | 1,958 | 2,769 | 3,391 | |
3/4 | 0.442 | 0.188 | 1 | 6 | 2,819 | 3,986 | 4,882 | |
7/8 | 0.601 | 0.219 | 1 | 9 | 3,833 | 5,420 | 6,638 | |
Flats | 11/2 × 1/4 | 0.375 | 0.0722 | 0 | 7 | 2,391 | 3,382 | 4,142 |
2 × 1/4 | 0.5 | 0.0722 | 0 | 7 | 3,189 | 4,509 | 5,523 | |
2 × 3/8 | 0.75 | 0.1082 | 0 | 10 | 4,783 | 6,764 | 8,284 |
Table 18.5.11.8(b) Maximum Horizontal Loads for Sway Braces with l/r = 200 for Steel Braces with Fy = 36 ksi
Brace Shape and Size (in.) | Area (in.2) | Least Radius of Gyration (r) (in.) |
Maximum Length for l/r= 200 |
Maximum Horizontal Load (lb) | ||||
---|---|---|---|---|---|---|---|---|
Brace Angle | ||||||||
ft | in. | 30° to 44° Angle from Vertical |
45° to 59° Angle from Vertical |
60° to 90° Angle from Vertical |
||||
Pipe Schedule 40 | 1 | 0.494 | 0.421 | 7 | 0 | 926 | 1310 | 1604 |
11/4 | 0.669 | 0.540 | 9 | 0 | 1254 | 1774 | 2173 | |
11/2 | 0.799 | 0.623 | 10 | 4 | 1498 | 2119 | 2595 | |
2 | 1.07 | 0.787 | 13 | 1 | 2006 | 2837 | 3475 | |
Angles | 11/2 × 11/2 × 1/4 | 0.688 | 0.292 | 4 | 10 | 1290 | 1824 | 2234 |
2 × 2 × 1/4 | 0.938 | 0.391 | 6 | 6 | 1759 | 2487 | 3046 | |
21/2 × 2 × 1/4 | 1.06 | 0.424 | 7 | 0 | 1988 | 2811 | 3442 | |
21/2 × 21/2 × 1/4 | 1.19 | 0.491 | 8 | 2 | 2231 | 3155 | 3865 | |
3 × 21/2 × 1/4 | 1.31 | 0.528 | 8 | 9 | 2456 | 3474 | 4254 | |
3 × 3 × 1/4 | 1.44 | 0.592 | 9 | 10 | 2700 | 3818 | 4677 | |
Rods (all thread) | 3/8 | 0.07 | 0.075 | 1 | 2 | 131 | 186 | 227 |
1/2 | 0.129 | 0.101 | 1 | 8 | 242 | 342 | 419 | |
5/8 | 0.207 | 0.128 | 2 | 1 | 388 | 549 | 672 | |
3/4 | 0.309 | 0.157 | 2 | 7 | 579 | 819 | 1004 | |
7/8 | 0.429 | 0.185 | 3 | 0 | 804 | 1138 | 1393 | |
Rods (threaded at ends only) | 3/8 | 0.11 | 0.094 | 1 | 6 | 206 | 292 | 357 |
1/2 | 0.196 | 0.125 | 2 | 0 | 368 | 520 | 637 | |
5/8 | 0.307 | 0.156 | 2 | 7 | 576 | 814 | 997 | |
3/4 | 0.442 | 0.188 | 3 | 1 | 829 | 1172 | 1435 | |
7/8 | 0.601 | 0.219 | 3 | 7 | 1127 | 1594 | 1952 | |
Flats | 11/2 × 1/4 | 0.375 | 0.0722 | 1 | 2 | 703 | 994 | 1218 |
2 × 1/4 | 0.5 | 0.0722 | 1 | 2 | 938 | 1326 | 1624 | |
2 × 3/8 | 0.75 | 0.1082 | 1 | 9 | 1406 | 1989 | 2436 |
Table 18.5.11.8(c) Maximum Horizontal Loads for Sway Braces with l/r = 300 for Steel Braces with Fy = 36 ksi
Brace Shape and Size (in.) | Area (in.2) | Least Radius of Gyration (r) (in.) |
Maximum Length for l/r = 300 |
Maximum Horizontal Load (lb) | ||||
---|---|---|---|---|---|---|---|---|
Brace Angle | ||||||||
ft | in. | 30° to 44°Angle from Vertical | 45° to 59°Angle from Vertical | 60° to 90°Angle from Vertical | ||||
Pipe Schedule 40 | 1 | 0.494 | 0.421 | 10 | 6 | 412 | 582 | 713 |
11/2 | 0.669 | 0.540 | 13 | 6 | 558 | 788 | 966 | |
11/2 | 0.799 | 0.623 | 15 | 6 | 666 | 942 | 1153 | |
2 | 1.07 | 0.787 | 19 | 8 | 892 | 1261 | 1544 | |
Angles | 11/2 × 11/2 × 1/4 | 0.688 | 0.292 | 7 | 3 | 573 | 811 | 993 |
2 × 2 × 1/4 | 0.938 | 0.391 | 9 | 9 | 782 | 1105 | 1354 | |
21/2 × 2 × 1/4 | 1.06 | 0.424 | 10 | 7 | 883 | 1249 | 1530 | |
21/2 × 21/2 × 1/4 | 1.19 | 0.491 | 12 | 3 | 992 | 1402 | 1718 | |
3 × 21/2 × 1/4 | 1.31 | 0.528 | 13 | 2 | 1092 | 1544 | 1891 | |
3 × 3 × 1/2 | 1.44 | 0.592 | 14 | 9 | 1200 | 1697 | 2078 | |
Rods (all thread) | 3/8 | 0.07 | 0.075 | 1 | 10 | 58 | 82 | 101 |
1/2 | 0.129 | 0.101 | 2 | 6 | 108 | 152 | 186 | |
5/8 | 0.207 | 0.128 | 3 | 2 | 173 | 244 | 299 | |
3/4 | 0.309 | 0.157 | 3 | 11 | 258 | 364 | 446 | |
7/8 | 0.429 | 0.185 | 4 | 7 | 358 | 506 | 619 | |
Rods (threaded at ends only) | 3/8 | 0.11 | 0.094 | 2 | 4 | 92 | 130 | 159 |
1/2 | 0.196 | 0.125 | 3 | 1 | 163 | 231 | 283 | |
5/8 | 0.307 | 0.156 | 3 | 10 | 256 | 362 | 443 | |
3/4 | 0.442 | 0.188 | 4 | 8 | 368 | 521 | 638 | |
7/8 | 0.601 | 0.219 | 5 | 5 | 501 | 708 | 867 | |
Flats | 11/2 × 1/4 | 0.375 | 0.0722 | 1 | 9 | 313 | 442 | 541 |
2 × 1/4 | 0.5 | 0.0722 | 1 | 9 | 417 | 589 | 722 | |
2 × 3/8 | 0.75 | 0.1082 | 2 | 8 | 625 | 884 | 1083 |
Table 18.5.11.8(d) Maximum Horizontal Loads for Sway Braces with l/r = 100 for Steel Braces with Fy = 248 N/mm2
Brace Shape and Size (mm) | Area (mm2) | Least Radius of Gyration (r) (mm) |
Maximum Length for l/r = 100 |
Maximum Horizontal Load (kg) | ||||
---|---|---|---|---|---|---|---|---|
Brace Angle | ||||||||
meters | mm | 30° to 44°Angle from Vertical | 45° to 59°Angle from Vertical | 60° to 90°Angle from Vertical | ||||
Pipe Schedule 40 | 25 | 318.7 | 11 | 1.0 | 150 | 1,429 | 2,021 | 2,475 |
32 | 431.6 | 14 | 1.2 | 150 | 1,935 | 2,737 | 3,352 | |
40 | 515.5 | 16 | 1.5 | 50 | 2,311 | 3,269 | 4,003 | |
50 | 690.3 | 20 | 1.8 | 150 | 3,095 | 4,377 | 5,361 | |
Angles | 40 × 40 × 6 | 443.9 | 7 | 0.6 | 125 | 1,990 | 2,815 | 3,447 |
50 × 50 × 6 | 605.2 | 10 | 1.0 | 75 | 2,713 | 3,837 | 4,699 | |
65 × 50 × 6 | 683.9 | 11 | 1.0 | 150 | 3,066 | 4,336 | 5,311 | |
65 × 65 × 6 | 767.7 | 12 | 1.2 | 25 | 3,442 | 4,868 | 5,962 | |
80 × 65 × 6 | 845.2 | 13 | 1.2 | 100 | 3,789 | 5,359 | 6,563 | |
80 × 80 × 6 | 929.0 | 15 | 1.2 | 275 | 4,165 | 5,891 | 7,214 | |
Rods (all thread) | 10 | 45.2 | 2 | 0.0 | 175 | 202 | 286 | 351 |
15 | 83.2 | 3 | 0.0 | 250 | 373 | 528 | 646 | |
16 | 133.5 | 3 | 0.3 | 0 | 599 | 847 | 1,037 | |
20 | 199.4 | 4 | 0.3 | 75 | 894 | 1,264 | 1,548 | |
22 | 276.8 | 5 | 0.3 | 150 | 1,241 | 1,755 | 2,149 | |
Rods (threaded at ends only) | 10 | 71.0 | 2 | 0.0 | 225 | 318 | 450 | 551 |
15 | 126.5 | 3 | 0.3 | 0 | 567 | 802 | 982 | |
16 | 198.1 | 4 | 0.3 | 75 | 888 | 1,256 | 1,538 | |
20 | 285.2 | 5 | 0.3 | 150 | 1,279 | 1,808 | 2,214 | |
22 | 387.7 | 5 | 0.3 | 225 | 1,739 | 2,458 | 3,011 | |
Flats | 40 × 6 | 241.9 | 2 | 0.0 | 175 | 1,085 | 1,534 | 1,879 |
50 × 6 | 322.6 | 2 | 0.0 | 175 | 1,447 | 2,045 | 2,505 | |
50 × 10 | 483.9 | 3 | 0.0 | 250 | 2,170 | 3,068 | 3,758 |
Table 18.5.11.8(e) Maximum Horizontal Loads for Sway Braces with l/r = 200 for Steel Braces with Fy= 248 N/mm2
Brace Shape and Size (mm) | Area (mm2) | Least Radius of Gyration (r) (mm) |
Maximum Length for l/r = 200 |
Maximum Horizontal Load (kg) | ||||
---|---|---|---|---|---|---|---|---|
Brace Angle | ||||||||
meters | mm | 30° to 44°Angle from Vertical | 45° to 59°Angle from Vertical | 60° to 90°Angle from Vertical | ||||
Pipe Schedule 40 | 25 | 318.7 | 11 | 2.1 | 0 | 420 | 594 | 728 |
32 | 431.6 | 14 | 2.7 | 0 | 569 | 805 | 986 | |
40 | 515.5 | 16 | 3 | 100 | 679 | 961 | 1177 | |
50 | 690.3 | 20 | 4.0 | 25 | 910 | 1287 | 1576 | |
Angles | 40 × 40 × 6 | 443.9 | 7 | 1.2 | 250 | 585 | 827 | 1013 |
50 × 50 × 6 | 605.2 | 10 | 1.8 | 150 | 798 | 1128 | 1382 | |
65 × 50 × 6 | 683.9 | 11 | 2.1 | 0 | 902 | 1275 | 1561 | |
65 × 65 × 6 | 767.7 | 12 | 2.4 | 50 | 1012 | 1431 | 1753 | |
80 × 65 × 6 | 845.2 | 13 | 2.4 | 225 | 1114 | 1576 | 1930 | |
80 × 80 × 6 | 929.0 | 15 | 2.7 | 250 | 1225 | 1732 | 2121 | |
Rods (all thread) | 10 | 45.2 | 2 | 0.3 | 50 | 59 | 84 | 103 |
15 | 83.2 | 3 | 0.3 | 200 | 110 | 155 | 190 | |
16 | 133.5 | 3 | 0.6 | 25 | 176 | 249 | 305 | |
20 | 199.4 | 4 | 0.6 | 175 | 263 | 371 | 455 | |
22 | 276.8 | 5 | 0.9 | 0 | 365 | 516 | 632 | |
Rods (threaded at ends only) | 10 | 71.0 | 2 | 0.3 | 150 | 93 | 132 | 162 |
15 | 126.5 | 3 | 0.6 | 0 | 167 | 236 | 289 | |
16 | 198.1 | 4 | 0.6 | 175 | 261 | 369 | 452 | |
20 | 285.2 | 5 | 0.9 | 25 | 376 | 532 | 651 | |
22 | 387.7 | 5 | 0.9 | 175 | 511 | 723 | 885 | |
Flats | 40 × 6 | 241.9 | 2 | 0.3 | 50 | 319 | 451 | 552 |
50 × 6 | 322.6 | 2 | 0.3 | 50 | 425 | 601 | 737 | |
50 × 10 | 483.9 | 3 | 0.3 | 225 | 638 | 902 | 1105 |
Table 18.5.11.8(f) Maximum Horizontal Loads for Sway Braces with l/r = 300 for Steel Braces with Fy = 248 N/mm2
Brace Shape and Size (mm) | Area (mm2) | Least Radius of Gyration (r) (mm) |
Maximum Length for l/r = 300 |
Maximum Horizontal Load (kg) | ||||
---|---|---|---|---|---|---|---|---|
Brace Angle | ||||||||
meters | mm | 30° to 44°Angle from Vertical | 45° to 59°Angle from Vertical | 60° to 90°Angle from Vertical | ||||
Pipe Schedule 40 | 25 | 318.7 | 10.5 | 3 | 150 | 187 | 264 | 323 |
32 | 431.6 | 13.5 | 4 | 150 | 253 | 357 | 438 | |
40 | 515.5 | 15.6 | 4.6 | 150 | 302 | 427 | 523 | |
50 | 690.3 | 19.7 | 5.8 | 200 | 405 | 572 | 700 | |
Angles | 40 × 40 × 6 | 443.9 | 7.3 | 2.1 | 75 | 260 | 368 | 450 |
50 × 50 × 6 | 605.2 | 9.8 | 2.7 | 225 | 355 | 501 | 614 | |
65 × 50 × 6 | 683.9 | 10.6 | 3 | 175 | 401 | 567 | 694 | |
65 × 65 × 6 | 767.7 | 12.3 | 3.7 | 75 | 450 | 636 | 779 | |
80 × 65 × 6 | 845.2 | 13.2 | 4 | 50 | 495 | 700 | 858 | |
80 × 80 × 6 | 929.0 | 14.8 | 4.3 | 225 | 544 | 770 | 943 | |
Rods (all thread) | 10 | 45.2 | 1.9 | 0.3 | 250 | 26 | 37 | 46 |
15 | 83.2 | 2.5 | 0.6 | 150 | 49 | 69 | 84 | |
16 | 133.5 | 3.2 | 0.9 | 50 | 79 | 111 | 136 | |
20 | 199.4 | 3.9 | 0.9 | 275 | 117 | 165 | 202 | |
22 | 276.8 | 4.6 | 1.2 | 175 | 162 | 230 | 281 | |
Rods (threaded at ends only) | 10 | 71.0 | 2.4 | 0.6 | 100 | 42 | 59 | 72 |
15 | 126.5 | 3.1 | 0.9 | 25 | 74 | 105 | 128 | |
16 | 198.1 | 3.9 | 0.9 | 250 | 116 | 164 | 201 | |
20 | 285.2 | 4.7 | 1.2 | 200 | 167 | 236 | 289 | |
22 | 387.7 | 5.5 | 1.5 | 125 | 227 | 321 | 393 | |
Flats | 40 × 6 | 241.9 | 1.8 | 0.3 | 225 | 142 | 200 | 245 |
50 × 6 | 322.6 | 1.8 | 0.3 | 225 | 189 | 267 | 327 | |
50 × 10 | 483.9 | 2.7 | 0.6 | 200 | 283 | 401 | 491 |
Other pipe schedules and materials not specifically included in Table 18.5.11.8(a) through Table 18.5.11.8(f) shall be permitted to be used if certified by a registered professional engineer to support the loads determined in accordance with the criteria in the tables.
Calculations shall be submitted where required by the authority having jurisdiction.
C-type clamps including beam and large flange clamps, with or without restraining straps, shall not be used to attach braces to the building structure.
Powder-driven fasteners shall not be used to attach braces to the building structure, unless they are specifically listed for service in resisting lateral loads in areas subject to earthquakes.
The designated angle category for the fastener(s) used in the sway brace installation shall be determined in accordance with Figure 18.5.12.1.

FIGURE 18.5.12.1 Designation of Angle Category Based on Angle of Sway Brace and Fastener Orientation.
For individual fasteners, unless alternative allowable loads are determined and certified by a registered professional engineer, the loads determined in 18.5.9 shall not exceed the allowable loads provided in Table 18.5.12.2(a) through Table 18.5.12.2(m) or 18.5.12.7.
Table 18.5.12.2(a) Maximum Load for Wedge Anchors in 3000 psi (207 bar) Lightweight Cracked Concrete on Metal Deck
Wedge Anchors in 3000 psi Sand Lightweight Cracked Concrete on 41/2 in. Flute Width Metal Deck (lb) | ||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
Diameter (in.) | Min. Nom. Embedment (in.) | Min. Slab Thickness (in.) | Max. Flute Center Offset (in.) | A | B | C | D | E | F | G | H | I |
Pr ≤2.0 | Pr ≤1.1 | Pr ≤0.7 | Pr ≤1.2 | Pr ≤1.1 | Pr ≤1.1 | Pr ≤1.4 | Pr ≤0.9 | Pr ≤0.8 | ||||
3/8 | 2.375 | 6.25 | 1 | 123 | 183 | 233 | — | — | — | — | — | — |
1/2 | 3.750 | 6.25 | 1 | 147 | 231 | 310 | — | — | — | — | — | — |
5/8 | 3.875 | 6.25 | 1 | 188 | 292 | 387 | — | — | — | — | — | — |
3/4 | 4.500 | 6.25 | 1 | 255 | 380 | 486 | ||||||
Diameter (in.) | Min. Nom. Embedment (in.) | Min. Slab Thickness (in.) | Max. Flute Center Offset (in.) | A | B | C | D | E | F | G | H | I |
Pr 2.1—3.5 | Pr 1.2—1.8 | Pr 0.8—1.0 | Pr 1.3—1.7 | Pr 1.2—1.8 | Pr 1.2—2.0 | Pr 1.5—1.9 | Pr 1.0—1.3 | Pr 0.9—1.1 | ||||
3/8 | 2.375 | 6.25 | 1 | 79 | 133 | 193 | — | — | — | — | — | — |
1/2 | 3.750 | 6.25 | 1 | 86 | 160 | 247 | — | — | — | — | — | — |
5/8 | 3.875 | 6.25 | 1 | 113 | 204 | 311 | — | — | — | — | — | — |
3/4 | 4.500 | 6.25 | 1 | 165 | 275 | 402 | — | — | — | — | — | — |
Diameter (in.) | Min. Nom. Embedment (in.) | Min. Slab Thickness (in.) | Max. Flute Center Offset (in.) | A | B | C | D | E | F | G | H | I |
Pr 3.6—5.0 | Pr 1.9—2.5 | Pr 1.1—1.3 | Pr 1.8—2.2 | Pr 1.9—2.5 | Pr 2.1—2.9 | Pr 2.0—2.4 | Pr 1.4—1.7 | Pr 1.2—1.4 | ||||
3/8 | 2.375 | 6.25 | 1 | 56 | 104 | 165 | — | — | — | — | — | — |
1/2 | 3.750 | 6.25 | 1 | 60 | 121 | 205 | — | — | — | — | — | — |
5/8 | 3.875 | 6.25 | 1 | 79 | 157 | 260 | — | — | — | — | — | — |
3/4 | 4.500 | 6.25 | 1 | 116 | 216 | 343 | — | — | — | — | — | — |
Diameter (in.) | Min. Nom. Embedment (in.) | Min. Slab Thickness (in.) | Max. Flute Center Offset (in.) | A | B | C | D | E | F | G | H | I |
Pr 5.1—6.5 | Pr 2.6—3.2 | Pr 1.4—1.6 | Pr 2.3—2.7 | Pr 2.6—3.2 | Pr 3.0—3.8 | Pr 2.5—2.9 | Pr 1.8—2.1 | Pr 1.5—1.7 | ||||
3/8 | 2.375 | 6.25 | 1 | 43 | 85 | 144 | — | — | — | — | — | — |
1/2 | 3.750 | 6.25 | 1 | 46 | 94 | 175 | — | — | — | — | — | — |
5/8 | 3.875 | 6.25 | 1 | 60 | 124 | 224 | — | — | — | — | — | — |
3/4 | 4.500 | 6.25 | 1 | 89 | 177 | 299 | — | — | — | — | — | — |
*Pr = Prying factor range. (Refer to A.18.5.12.2 for additional information.)
Table 18.5.12.2(b) Maximum Load for Wedge Anchors in 3000 psi (207 bar) Lightweight Cracked Concrete
Wedge Anchors in 3000 psi Lightweight Cracked Concrete (lb) | ||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
Diameter (in.) | Min. Nom. Embedment (in.) | Min. Slab Thickness (in.) | Min. Edge Distance (in.) | A | B | C | D | E | F | G | H | I |
Pr ≤2.0 | Pr ≤1.1 | Pr ≤0.7 | Pr ≤1.2 | Pr ≤1.1 | Pr ≤1.1 | Pr ≤1.4 | Pr ≤0.9 | Pr ≤0.8 | ||||
3/8 | 2.375 | 5 | 4 | 142 | 216 | 280 | 162 | 216 | 256 | 139 | 208 | 244 |
1/2 | 3.750 | 6 | 6 | 200 | 314 | 419 | 243 | 314 | 362 | 209 | 312 | 365 |
5/8 | 3.875 | 6 | 6 | 259 | 394 | 512 | 297 | 394 | 467 | 255 | 380 | 446 |
3/4 | 4.500 | 7 | 8 | 356 | 552 | 731 | 424 | 552 | 641 | 365 | 544 | 636 |
Diameter (in.) | Min. Nom. Embedment (in.) | Min. Slab Thickness (in.) | Min. Edge Distance (in.) | A | B | C | D | E | F | G | H | I |
Pr 2.1—3.5 | Pr 1.2—1.8 | Pr 0.8—1.0 | Pr 1.3—1.7 | Pr 1.2—1.8 | Pr 1.2—2.0 | Pr 1.5—1.9 | Pr 1.0—1.3 | Pr 0.9—1.1 | ||||
3/8 | 2.375 | 5 | 4 | 89 | 154 | 229 | 133 | 154 | 157 | 117 | 170 | 204 |
1/2 | 3.750 | 6 | 6 | 119 | 218 | 335 | 195 | 218 | 209 | 172 | 250 | 299 |
5/8 | 3.875 | 6 | 6 | 163 | 281 | 418 | 244 | 281 | 286 | 215 | 311 | 373 |
3/4 | 4.500 | 7 | 8 | 214 | 386 | 588 | 343 | 386 | 376 | 303 | 438 | 525 |
Diameter (in.) | Min. Nom. Embedment (in.) | Min. Slab Thickness (in.) | Min. Edge Distance (in.) | A | B | C | D | E | F | G | H | I |
Pr 3.6—5.0 | Pr 1.9—2.5 | Pr 1.1—1.3 | Pr 1.8—2.2 | Pr 1.9—2.5 | Pr 2.1—2.9 | Pr 2.0—2.4 | Pr 1.4—1.7 | Pr 1.2—1.4 | ||||
3/8 | 2.375 | 5 | 4 | 62 | 119 | 194 | 113 | 119 | 108 | 101 | 144 | 175 |
1/2 | 3.750 | 6 | 6 | 83 | 167 | 279 | 163 | 167 | 144 | 147 | 208 | 254 |
5/8 | 3.875 | 6 | 6 | 113 | 218 | 354 | 207 | 218 | 197 | 186 | 263 | 320 |
3/4 | 4.500 | 7 | 8 | 150 | 297 | 492 | 288 | 297 | 259 | 259 | 367 | 447 |
Diameter (in.) | Min. Nom. Embedment (in.) | Min. Slab Thickness (in.) | Min. Edge Distance (in.) | A | B | C | D | E | F | G | H | I |
Pr 5.1—6.5 | Pr 2.6—3.2 | Pr 1.4—1.6 | Pr 2.3—2.7 | Pr 2.6—3.2 | Pr 3.0—3.8 | Pr 2.5—2.9 | Pr 1.8—2.1 | Pr 1.5—1.7 | ||||
3/8 | 2.375 | 5 | 4 | 47 | 97 | 168 | 98 | 97 | 82 | 89 | 125 | 154 |
1/2 | 3.750 | 6 | 6 | 63 | 130 | 239 | 140 | 130 | 109 | 128 | 178 | 220 |
5/8 | 3.875 | 6 | 6 | 87 | 178 | 306 | 179 | 178 | 150 | 163 | 228 | 281 |
3/4 | 4.500 | 7 | 8 | 115 | 234 | 422 | 248 | 234 | 197 | 226 | 315 | 389 |
*Pr = Prying factor range. (Refer to A.18.5.12.2 for additional information.)
Table 18.5.12.2(c) Maximum Load for Wedge Anchors in 3000 psi (207 bar) Normal Weight Cracked Concrete
Wedge Anchors in 3000 psi Normal Weight Cracked Concrete (lb) | ||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
Diameter (in.) | Min. Nom. Embedment (in.) | Min. Slab Thickness (in.) | Min. Edge Distance (in.) | A | B | C | D | E | F | G | H | I |
Pr <2.0 | Pr <1.1 | Pr <0.7 | Pr <1.2 | Pr <1.1 | Pr <1.1 | Pr <1.4 | Pr <0.9 | Pr <0.8 | ||||
3/8 | 2.375 | 5 | 4 | 189 | 274 | 342 | 197 | 274 | 340 | 170 | 251 | 297 |
1/2 | 3.750 | 6 | 6 | 272 | 423 | 563 | 326 | 423 | 490 | 281 | 419 | 490 |
5/8 | 3.875 | 6 | 6 | 407 | 623 | 814 | 472 | 623 | 733 | 406 | 605 | 709 |
3/4 | 4.500 | 7 | 8 | 613 | 940 | 1232 | 715 | 940 | 1104 | 615 | 916 | 1073 |
Diameter (in.) | Min. Nom. Embedment (in.) | Min. Slab Thickness (in.) | Min. Edge Distance (in.) | A | B | C | D | E | F | G | H | I |
Pr 2.1—3.5 | Pr 1.2—1.8 | Pr 0.8—1.0 | Pr 1.3—1.7 | Pr 1.2—1.8 | Pr 1.2—2.0 | Pr 1.5—1.9 | Pr 1.0—1.3 | Pr 0.9—1.1 | ||||
3/8 | 2.375 | 5 | 4 | 125 | 203 | 288 | 167 | 203 | 219 | 147 | 212 | 256 |
1/2 | 3.750 | 6 | 6 | 162 | 295 | 451 | 263 | 295 | 285 | 233 | 337 | 403 |
5/8 | 3.875 | 6 | 6 | 252 | 441 | 662 | 386 | 441 | 442 | 341 | 492 | 590 |
3/4 | 4.500 | 7 | 8 | 378 | 665 | 999 | 583 | 665 | 662 | 515 | 744 | 892 |
Diameter (in.) | Min. Nom. Embedment (in.) | Min. Slab Thickness (in.) | Min. Edge Distance (in.) | A | B | C | D | E | F | G | H | I |
Pr 3.6—5.0 | Pr 1.9—2.5 | Pr 1.1—1.3 | Pr 1.8—2.2 | Pr 1.9—2.5 | Pr 2.1—2.9 | Pr 2.0—2.4 | Pr 1.4—1.7 | Pr 1.2—1.4 | ||||
3/8 | 2.375 | 5 | 4 | 92 | 162 | 249 | 145 | 162 | 159 | 130 | 184 | 225 |
1/2 | 3.750 | 6 | 6 | 113 | 226 | 377 | 220 | 226 | 196 | 199 | 281 | 342 |
5/8 | 3.875 | 6 | 6 | 176 | 341 | 557 | 326 | 341 | 304 | 293 | 415 | 506 |
3/4 | 4.500 | 7 | 8 | 264 | 514 | 841 | 493 | 514 | 456 | 443 | 627 | 763 |
Diameter (in.) | Min. Nom. Embedment (in.) | Min. Slab Thickness (in.) | Min. Edge Distance (in.) | A | B | C | D | E | F | G | H | I |
Pr 5.1—6.5 | Pr 2.6—3.2 | Pr 1.4—1.6 | Pr 2.3—2.7 | Pr 2.6—3.2 | Pr 3.0—3.8 | Pr 2.5—2.9 | Pr 1.8—2.1 | Pr 1.5—1.7 | ||||
3/8 | 2.375 | 5 | 4 | 70 | 134 | 220 | 128 | 134 | 121 | 116 | 162 | 200 |
1/2 | 3.750 | 6 | 6 | 87 | 178 | 323 | 190 | 178 | 149 | 173 | 241 | 298 |
5/8 | 3.875 | 6 | 6 | 135 | 276 | 481 | 283 | 276 | 232 | 258 | 359 | 442 |
3/4 | 4.500 | 7 | 8 | 203 | 413 | 725 | 426 | 413 | 348 | 389 | 541 | 667 |
*Pr = Prying factor range. (Refer to A.18.5.12.2 for additional information.)
Table 18.5.12.2(d) Maximum Load for Wedge Anchors in 4000 psi (276 bar) Normal Weight Cracked Concrete
Wedge Anchors in 4000 psi Normal Weight Cracked Concrete (lb) | ||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
Diameter (in.) | Min. Nom. Embedment (in.) | Min. Slab Thickness (in.) | Min. Edge Distance (in.) | A | B | C | D | E | F | G | H | I |
Pr ≤2.0 | Pr ≤1.1 | Pr ≤0.7 | Pr ≤1.2 | Pr ≤1.1 | Pr ≤1.1 | Pr ≤1.4 | Pr ≤0.9 | Pr ≤0.8 | ||||
3/8 | 2.375 | 5 | 4 | 206 | 293 | 360 | 208 | 293 | 370 | 179 | 264 | 313 |
1/2 | 3.750 | 6 | 6 | 304 | 466 | 610 | 353 | 466 | 548 | 304 | 453 | 531 |
5/8 | 3.875 | 6 | 6 | 469 | 716 | 935 | 542 | 716 | 844 | 467 | 694 | 814 |
3/4 | 4.500 | 7 | 8 | 657 | 997 | 1293 | 750 | 997 | 1182 | 646 | 959 | 1125 |
Diameter (in.) | Min. Nom. Embedment (in.) | Min. Slab Thickness (in.) | Min. Edge Distance (in.) | A | B | C | D | E | F | G | H | I |
Pr 2.1—3.5 | Pr 1.2—1.8 | Pr 0.8—1.0 | Pr 1.3—1.7 | Pr 1.2—1.8 | Pr 1.2—2.0 | Pr 1.5—1.9 | Pr 1.0—1.3 | Pr 0.9—1.1 | ||||
3/8 | 2.375 | 5 | 4 | 138 | 221 | 307 | 178 | 221 | 242 | 157 | 226 | 272 |
1/2 | 3.750 | 6 | 6 | 188 | 330 | 495 | 289 | 330 | 330 | 255 | 368 | 442 |
5/8 | 3.875 | 6 | 6 | 291 | 508 | 761 | 444 | 508 | 511 | 392 | 566 | 678 |
3/4 | 4.500 | 7 | 8 | 414 | 711 | 1057 | 617 | 711 | 725 | 544 | 786 | 942 |
Diameter (in.) | Min. Nom. Embedment (in.) | Min. Slab Thickness (in.) | Min. Edge Distance (in.) | A | B | C | D | E | F | G | H | I |
Pr 3.6—5.0 | Pr 1.9—2.5 | Pr 1.1—1.3 | Pr 1.8—2.2 | Pr 1.9—2.5 | Pr 2.1—2.9 | Pr 2.0—2.4 | Pr 1.4—1.7 | Pr 1.2—1.4 | ||||
3/8 | 2.375 | 5 | 4 | 103 | 177 | 268 | 156 | 177 | 179 | 139 | 197 | 241 |
1/2 | 3.750 | 6 | 6 | 131 | 255 | 417 | 244 | 255 | 227 | 219 | 310 | 378 |
5/8 | 3.875 | 6 | 6 | 203 | 393 | 641 | 375 | 393 | 352 | 337 | 477 | 582 |
3/4 | 4.500 | 7 | 8 | 289 | 553 | 894 | 524 | 553 | 500 | 470 | 665 | 810 |
Diameter (in.) | Min. Nom. Embedment (in.) | Min. Slab Thickness (in.) | Min. Edge Distance (in.) | A | B | C | D | E | F | G | H | I |
Pr 5.1—6.5 | Pr 2.6—3.2 | Pr 1.4—1.6 | Pr 2.3—2.7 | Pr 2.6—3.2 | Pr 3.0—3.8 | Pr 2.5—2.9 | Pr 1.8—2.1 | Pr 1.5—1.7 | ||||
3/8 | 2.375 | 5 | 4 | 80 | 148 | 237 | 139 | 148 | 138 | 125 | 175 | 216 |
1/2 | 3.750 | 6 | 6 | 100 | 205 | 360 | 211 | 205 | 173 | 192 | 268 | 330 |
5/8 | 3.875 | 6 | 6 | 156 | 319 | 554 | 325 | 319 | 268 | 296 | 413 | 509 |
3/4 | 4.500 | 7 | 8 | 222 | 452 | 774 | 455 | 452 | 381 | 414 | 577 | 711 |
*Pr = Prying factor range. (Refer to A.18.5.12.2 for additional information.)
Table 18.5.12.2(e) Maximum Load for Wedge Anchors in 6000 psi (414 bar) Normal Weight Cracked Concrete
Wedge Anchors in 6000 psi Normal Weight Cracked Concrete (lb) | ||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
Diameter (in.) | Min. Nom. Embedment (in.) | Min. Slab Thickness (in.) | Min. Edge Distance (in.) | A | B | C | D | E | F | G | H | I |
Pr ≤2.0 | Pr ≤1.1 | Pr ≤0.7 | Pr ≤1.2 | Pr ≤1.1 | Pr ≤1.1 | Pr ≤1.4 | Pr ≤0.9 | Pr ≤0.8 | ||||
3/8 | 2.375 | 5 | 4 | 225 | 313 | 379 | 219 | 313 | 402 | 189 | 277 | 329 |
1/2 | 3.750 | 6 | 6 | 354 | 529 | 676 | 392 | 529 | 637 | 337 | 500 | 589 |
5/8 | 3.875 | 6 | 6 | 546 | 812 | 1036 | 601 | 812 | 981 | 517 | 766 | 902 |
3/4 | 4.500 | 7 | 8 | 763 | 1127 | 1429 | 829 | 1127 | 1370 | 714 | 1055 | 1243 |
Diameter (in.) | Min. Nom. Embedment (in.) | Min. Slab Thickness (in.) | Min. Edge Distance (in.) | A | B | C | D | E | F | G | H | I |
Pr 2.1—3.5 | Pr 1.2—1.8 | Pr 0.8—1.0 | Pr 1.3—1.7 | Pr 1.2—1.8 | Pr 1.2—2.0 | Pr 1.5—1.9 | Pr 1.0—1.3 | Pr 0.9—1.1 | ||||
3/8 | 2.375 | 5 | 4 | 153 | 240 | 327 | 190 | 240 | 267 | 167 | 240 | 289 |
1/2 | 3.750 | 6 | 6 | 228 | 382 | 559 | 326 | 382 | 400 | 287 | 414 | 498 |
5/8 | 3.875 | 6 | 6 | 353 | 589 | 859 | 500 | 589 | 617 | 441 | 636 | 764 |
3/4 | 4.500 | 7 | 8 | 496 | 822 | 1190 | 693 | 822 | 868 | 611 | 881 | 1058 |
Diameter (in.) | Min. Nom. Embedment (in.) | Min. Slab Thickness (in.) | Min. Edge Distance (in.) | A | B | C | D | E | F | G | H | I |
Pr 3.6—5.0 | Pr 1.9—2.5 | Pr 1.1—1.3 | Pr 1.8—2.2 | Pr 1.9—2.5 | Pr 2.1—2.9 | Pr 2.0—2.4 | Pr 1.4—1.7 | Pr 1.2—1.4 | ||||
3/8 | 2.375 | 5 | 4 | 115 | 194 | 288 | 168 | 194 | 200 | 149 | 211 | 258 |
1/2 | 3.750 | 6 | 6 | 161 | 299 | 477 | 279 | 299 | 278 | 250 | 354 | 431 |
5/8 | 3.875 | 6 | 6 | 249 | 462 | 733 | 429 | 462 | 431 | 384 | 544 | 663 |
3/4 | 4.500 | 7 | 8 | 354 | 647 | 1019 | 596 | 647 | 612 | 534 | 756 | 921 |
Diameter (in.) | Min. Nom. Embedment (in.) | Min. Slab Thickness (in.) | Min. Edge Distance (in.) | A | B | C | D | E | F | G | H | I |
Pr 5.1—6.5 | Pr 2.6—3.2 | Pr 1.4—1.6 | Pr 2.3—2.7 | Pr 2.6—3.2 | Pr 3.0—3.8 | Pr 2.5—2.9 | Pr 1.8—2.1 | Pr 1.5—1.7 | ||||
3/8 | 2.375 | 5 | 4 | 91 | 163 | 257 | 150 | 163 | 157 | 135 | 189 | 233 |
1/2 | 3.750 | 6 | 6 | 123 | 246 | 415 | 243 | 246 | 212 | 221 | 308 | 380 |
5/8 | 3.875 | 6 | 6 | 192 | 380 | 639 | 375 | 380 | 329 | 341 | 475 | 585 |
3/4 | 4.500 | 7 | 8 | 272 | 533 | 891 | 523 | 533 | 467 | 475 | 662 | 815 |
*Pr = Prying factor range. (Refer to A.18.5.12.2 for additional information.)
Table 18.5.12.2(f) Maximum Load for Metal Deck Inserts in 3000 psi (207 bar) Lightweight Cracked Concrete on Metal Deck
Metal Deck Inserts in 3000 psi Sand Lightweight Cracked Concrete on 41/2 in. Flute Width Metal Deck (lb) | ||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
Diameter (in.) | Min. Effect. Embedment (in.) | Min. Slab Thickness (in.) | Max. Flute Center Offset (in.) | A | B | C | D | E | F | G | H | I |
Pr ≤2.0 | Pr ≤1.1 | Pr ≤0.7 | Pr ≤1.2 | Pr ≤1.1 | Pr ≤1.1 | Pr ≤1.4 | Pr ≤0.9 | Pr ≤0.8 | ||||
3/8 | 1.750 | 6.25 | 1 | 135 | 192 | 236 | — | — | — | — | — | — |
1/2 | 1.750 | 6.25 | 1 | 138 | 199 | 247 | — | — | — | — | — | — |
5/8 | 1.750 | 6.25 | 1 | 138 | 199 | 247 | — | — | — | — | — | — |
3/4 | 1.750 | 6.25 | 1 | 164 | 257 | 344 | ||||||
Diameter (in.) | Min. Effect. Embedment (in.) | Min. Slab Thickness (in.) | Max. Flute Center Offset (in.) | A | B | C | D | E | F | G | H | I |
Pr 2.1—3.5 | Pr 1.2—1.8 | Pr 0.8—1.0 | Pr 1.3—1.7 | Pr 1.2—1.8 | Pr 1.2—2.0 | Pr 1.5—1.9 | Pr 1.0—1.3 | Pr 0.9—1.1 | ||||
3/8 | 1.750 | 6.25 | 1 | 90 | 144 | 201 | — | — | — | — | — | — |
1/2 | 1.750 | 6.25 | 1 | 91 | 148 | 209 | — | — | — | — | — | — |
5/8 | 1.750 | 6.25 | 1 | 91 | 148 | 209 | — | — | — | — | — | — |
3/4 | 1.750 | 6.25 | 1 | 97 | 178 | 275 | — | — | — | — | — | — |
Diameter (in.) | Min. Effect. Embedment (in.) | Min. Slab Thickness (in.) | Max. Flute Center Offset (in.) | A | B | C | D | E | F | G | H | I |
Pr 3.6—5.0 | Pr 1.9—2.5 | Pr 1.1—1.3 | Pr 1.8—2.2 | Pr 1.9—2.5 | Pr 2.1—2.9 | Pr 2.0—2.4 | Pr 1.4—1.7 | Pr 1.2—1.4 | ||||
3/8 | 1.750 | 6.25 | 1 | 67 | 115 | 175 | — | — | — | — | — | — |
1/2 | 1.750 | 6.25 | 1 | 67 | 118 | 181 | — | — | — | — | — | — |
5/8 | 1.750 | 6.25 | 1 | 67 | 118 | 181 | — | — | — | — | — | — |
3/4 | 1.750 | 6.25 | 1 | 67 | 136 | 229 | — | — | — | — | — | — |
Diameter (in.) | Min. Effect. Embedment (in.) | Min. Slab Thickness (in.) | Max. Flute Center Offset (in.) | A | B | C | D | E | F | G | H | I |
Pr 5.1—6.5 | Pr 2.6—3.2 | Pr 1.4—1.6 | Pr 2.3—2.7 | Pr 2.6—3.2 | Pr 3.0—3.8 | Pr 2.5—2.9 | Pr 1.8—2.1 | Pr 1.5—1.7 | ||||
3/8 | 1.750 | 6.25 | 1 | 52 | 96 | 155 | — | — | — | — | — | — |
1/2 | 1.750 | 6.25 | 1 | 52 | 98 | 160 | — | — | — | — | — | — |
5/8 | 1.750 | 6.25 | 1 | 52 | 98 | 160 | — | — | — | — | — | — |
3/4 | 1.750 | 6.25 | 1 | 52 | 106 | 196 | — | — | — | — | — | — |
*Pr = Prying factor range. (Refer to A.18.5.12.2 for additional information.)
Table 18.5.12.2(g) Maximum Load for Wood Form Inserts in 3000 psi (207 bar) Lightweight Cracked Concrete
Wood Form Inserts in 3000 psi Lightweight Cracked Concrete (lb) | ||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
Diameter (in.) | Min. Effect. Embedment (in.) | Min. Slab Thickness (in.) | Min. Edge Distance (in.) | A | B | C | D | E | F | G | H | I |
Pr ≤2.0 | Pr ≤1.1 | Pr ≤0.7 | Pr ≤1.2 | Pr ≤1.1 | Pr ≤1.1 | Pr ≤1.4 | Pr ≤0.9 | Pr ≤0.8 | ||||
3/8 | 1.100 | 4 | 6 | 224 | 316 | 387 | 223 | 316 | 401 | 193 | 283 | 336 |
1/2 | 1.690 | 4 | 6 | 252 | 376 | 480 | 278 | 376 | 454 | 239 | 355 | 418 |
5/8 | 1.750 | 4 | 8 | 252 | 376 | 480 | 278 | 376 | 454 | 239 | 355 | 418 |
3/4 | 1.750 | 4 | 8 | 252 | 376 | 480 | 278 | 376 | 454 | 239 | 355 | 418 |
Diameter (in.) | Min. Effect. Embedment (in.) | Min. Slab Thickness (in.) | Min. Edge Distance (in.) | A | B | C | D | E | F | G | H | I |
Pr 2.1—3.5 | Pr 1.2—1.8 | Pr 0.8—1.0 | Pr 1.3—1.7 | Pr 1.2—1.8 | Pr 1.2—2.0 | Pr 1.5—1.9 | Pr 1.0—1.3 | Pr 0.9—1.1 | ||||
3/8 | 1.100 | 4 | 6 | 150 | 239 | 331 | 192 | 239 | 264 | 169 | 243 | 293 |
1/2 | 1.690 | 4 | 6 | 163 | 272 | 398 | 231 | 272 | 286 | 204 | 294 | 354 |
5/8 | 1.750 | 4 | 8 | 163 | 272 | 398 | 231 | 272 | 286 | 204 | 294 | 354 |
3/4 | 1.750 | 4 | 8 | 163 | 272 | 398 | 231 | 272 | 286 | 204 | 294 | 354 |
Diameter (in.) | Min. Effect. Embedment (in.) | Min. Slab Thickness (in.) | Min. Edge Distance (in.) | A | B | C | D | E | F | G | H | I |
Pr 3.6—5.0 | Pr 1.9—2.5 | Pr 1.1—1.3 | Pr 1.8—2.2 | Pr 1.9—2.5 | Pr 2.1—2.9 | Pr 2.0—2.4 | Pr 1.4—1.7 | Pr 1.2—1.4 | ||||
3/8 | 1.100 | 4 | 6 | 113 | 193 | 290 | 169 | 193 | 196 | 150 | 213 | 260 |
1/2 | 1.690 | 4 | 6 | 115 | 213 | 339 | 198 | 213 | 199 | 178 | 251 | 307 |
5/8 | 1.750 | 4 | 8 | 115 | 213 | 339 | 198 | 213 | 199 | 178 | 251 | 307 |
3/4 | 1.750 | 4 | 8 | 115 | 213 | 339 | 198 | 213 | 199 | 178 | 251 | 307 |
Diameter (in.) | Min. Effect. Embedment (in.) | Min. Slab Thickness (in.) | Min. Edge Distance (in.) | A | B | C | D | E | F | G | H | I |
Pr 5.1—6.5 | Pr 2.6—3.2 | Pr 1.4—1.6 | Pr 2.3—2.7 | Pr 2.6—3.2 | Pr 3.0—3.8 | Pr 2.5—2.9 | Pr 1.8—2.1 | Pr 1.5—1.7 | ||||
3/8 | 1.100 | 4 | 6 | 88 | 161 | 257 | 150 | 161 | 152 | 135 | 190 | 234 |
1/2 | 1.690 | 4 | 6 | 88 | 175 | 296 | 173 | 175 | 152 | 157 | 219 | 271 |
5/8 | 1.750 | 4 | 8 | 88 | 175 | 296 | 173 | 175 | 152 | 157 | 219 | 271 |
3/4 | 1.750 | 4 | 8 | 88 | 175 | 296 | 173 | 175 | 152 | 157 | 219 | 271 |
*Pr = Prying factor range. (Refer to A.18.5.12.2 for additional information.)
Table 18.5.12.2(h) Maximum Load for Wood Form Inserts in 3000 psi (207 bar) Normal Weight Cracked Concrete
Wood Form Inserts in 3000 psi Normal Weight Cracked Concrete (lb) | ||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
Diameter (in.) | Min. Effect. Embedment (in.) | Min. Slab Thickness (in.) | Min. Edge Distance (in.) | A | B | C | D | E | F | G | H | I |
Pr ≤2.0 | Pr ≤1.1 | Pr ≤0.7 | Pr ≤1.2 | Pr ≤1.1 | Pr ≤1.1 | Pr ≤1.4 | Pr ≤0.9 | Pr ≤0.8 | ||||
3/8 | 1.100 | 4 | 6 | 248 | 342 | 411 | 237 | 342 | 444 | 205 | 300 | 357 |
1/2 | 1.690 | 4 | 6 | 297 | 443 | 565 | 327 | 443 | 535 | 282 | 418 | 492 |
5/8 | 1.750 | 4 | 8 | 297 | 443 | 565 | 327 | 443 | 535 | 282 | 418 | 492 |
3/4 | 1.750 | 4 | 8 | 297 | 443 | 565 | 327 | 443 | 535 | 282 | 418 | 492 |
Diameter (in.) | Min. Effect. Embedment (in.) | Min. Slab Thickness (in.) | Min. Edge Distance (in.) | A | B | C | D | E | F | G | H | I |
Pr 2.1—3.5 | Pr 1.2—1.8 | Pr 0.8—1.0 | Pr 1.3—1.7 | Pr 1.2—1.8 | Pr 1.2—2.0 | Pr 1.5—1.9 | Pr 1.0—1.3 | Pr 0.9—1.1 | ||||
3/8 | 1.100 | 4 | 6 | 170 | 264 | 357 | 207 | 264 | 298 | 182 | 261 | 315 |
1/2 | 1.690 | 4 | 6 | 192 | 321 | 468 | 272 | 321 | 336 | 240 | 347 | 416 |
5/8 | 1.750 | 4 | 8 | 192 | 321 | 468 | 272 | 321 | 336 | 240 | 347 | 416 |
3/4 | 1.750 | 4 | 8 | 192 | 321 | 468 | 272 | 321 | 336 | 240 | 347 | 416 |
Diameter (in.) | Min. Effect. Embedment (in.) | Min. Slab Thickness (in.) | Min. Edge Distance (in.) | A | B | C | D | E | F | G | H | I |
Pr 3.6—5.0 | Pr 1.9—2.5 | Pr 1.1—1.3 | Pr 1.8—2.2 | Pr 1.9—2.5 | Pr 2.1—2.9 | Pr 2.0—2.4 | Pr 1.4—1.7 | Pr 1.2—1.4 | ||||
3/8 | 1.100 | 4 | 6 | 129 | 215 | 315 | 184 | 215 | 224 | 163 | 231 | 282 |
1/2 | 1.690 | 4 | 6 | 135 | 251 | 399 | 233 | 251 | 235 | 209 | 296 | 361 |
5/8 | 1.750 | 4 | 8 | 135 | 251 | 399 | 233 | 251 | 235 | 209 | 296 | 361 |
3/4 | 1.750 | 4 | 8 | 135 | 251 | 399 | 233 | 251 | 235 | 209 | 296 | 361 |
Diameter (in.) | Min. Effect. Embedment (in.) | Min. Slab Thickness (in.) | Min. Edge Distance (in.) | A | B | C | D | E | F | G | H | I |
Pr 5.1—6.5 | Pr 2.6—3.2 | Pr 1.4—1.6 | Pr 2.3—2.7 | Pr 2.6—3.2 | Pr 3.0—3.8 | Pr 2.5—2.9 | Pr 1.8—2.1 | Pr 1.5—1.7 | ||||
3/8 | 1.100 | 4 | 6 | 104 | 181 | 282 | 165 | 181 | 179 | 148 | 208 | 256 |
1/2 | 1.690 | 4 | 6 | 104 | 207 | 348 | 204 | 207 | 179 | 185 | 258 | 319 |
5/8 | 1.750 | 4 | 8 | 104 | 207 | 348 | 204 | 207 | 179 | 185 | 258 | 319 |
3/4 | 1.750 | 4 | 8 | 104 | 207 | 348 | 204 | 207 | 179 | 185 | 258 | 319 |
*Pr = Prying factor range. (Refer to A.18.5.12.2 for additional information.)
Table 18.5.12.2(i) Maximum Load for Wood Form Inserts in 4000 psi (276 bar) Normal Weight Cracked Concrete
Wood Form Inserts in 4000 psi Normal Weight Cracked Concrete (lb) | ||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
Diameter (in.) | Min. Effect. Embedment (in.) | Min. Slab Thickness (in.) | Min. Edge Distance (in.) | A | B | C | D | E | F | G | H | I |
Pr ≤2.0 | Pr ≤1.1 | Pr ≤0.7 | Pr ≤1.2 | Pr ≤1.1 | Pr ≤1.1 | Pr ≤1.4 | Pr ≤0.9 | Pr ≤0.8 | ||||
3/8 | 1.100 | 4 | 6 | 270 | 364 | 431 | 249 | 364 | 482 | 215 | 313 | 374 |
1/2 | 1.690 | 4 | 6 | 335 | 493 | 623 | 361 | 493 | 602 | 311 | 459 | 541 |
5/8 | 1.750 | 4 | 8 | 344 | 511 | 653 | 378 | 511 | 618 | 326 | 482 | 568 |
3/4 | 1.750 | 4 | 8 | 344 | 511 | 653 | 378 | 511 | 618 | 326 | 482 | 568 |
Diameter (in.) | Min. Effect. Embedment (in.) | Min. Slab Thickness (in.) | Min. Edge Distance (in.) | A | B | C | D | E | F | G | H | I |
Pr 2.1—3.5 | Pr 1.2—1.8 | Pr 0.8—1.0 | Pr 1.3—1.7 | Pr 1.2—1.8 | Pr 1.2—2.0 | Pr 1.5—1.9 | Pr 1.0—1.3 | Pr 0.9—1.1 | ||||
3/8 | 1.100 | 4 | 6 | 188 | 287 | 379 | 220 | 287 | 330 | 193 | 277 | 334 |
1/2 | 1.690 | 4 | 6 | 218 | 361 | 520 | 303 | 361 | 382 | 266 | 384 | 462 |
5/8 | 1.750 | 4 | 8 | 222 | 371 | 541 | 315 | 371 | 389 | 278 | 400 | 481 |
3/4 | 1.750 | 4 | 8 | 222 | 371 | 541 | 315 | 371 | 389 | 278 | 400 | 481 |
Diameter (in.) | Min. Effect. Embedment (in.) | Min. Slab Thickness (in.) | Min. Edge Distance (in.) | A | B | C | D | E | F | G | H | I |
Pr 3.6—5.0 | Pr 1.9—2.5 | Pr 1.1—1.3 | Pr 1.8—2.2 | Pr 1.9—2.5 | Pr 2.1—2.9 | Pr 2.0—2.4 | Pr 1.4—1.7 | Pr 1.2—1.4 | ||||
3/8 | 1.100 | 4 | 6 | 145 | 236 | 338 | 197 | 236 | 251 | 175 | 247 | 302 |
1/2 | 1.690 | 4 | 6 | 157 | 284 | 446 | 261 | 284 | 271 | 233 | 330 | 403 |
5/8 | 1.750 | 4 | 8 | 157 | 290 | 461 | 270 | 290 | 271 | 242 | 342 | 417 |
3/4 | 1.750 | 4 | 8 | 157 | 290 | 461 | 270 | 290 | 271 | 242 | 342 | 417 |
Diameter (in.) | Min. Effect. Embedment (in.) | Min. Slab Thickness (in.) | Min. Edge Distance (in.) | A | B | C | D | E | F | G | H | I |
Pr 5.1—6.5 | Pr 2.6—3.2 | Pr 1.4—1.6 | Pr 2.3—2.7 | Pr 2.6—3.2 | Pr 3.0—3.8 | Pr 2.5—2.9 | Pr 1.8—2.1 | Pr 1.5—1.7 | ||||
3/8 | 1.100 | 4 | 6 | 117 | 201 | 305 | 178 | 201 | 202 | 160 | 224 | 275 |
1/2 | 1.690 | 4 | 6 | 120 | 234 | 390 | 229 | 234 | 207 | 207 | 290 | 357 |
5/8 | 1.750 | 4 | 8 | 120 | 239 | 402 | 236 | 239 | 207 | 214 | 299 | 368 |
3/4 | 1.750 | 4 | 8 | 120 | 239 | 402 | 236 | 239 | 207 | 214 | 299 | 368 |
*Pr = Prying factor range. (Refer to A.18.5.12.2 for additional information.)
Table 18.5.12.2(j) Maximum Load for Wood Form Inserts in 6000 psi (414 bar) Normal Weight Cracked Concrete
Wood Form Inserts in 6000 psi Normal Weight Cracked Concrete (lb) | ||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
Diameter (in.) | Min. Effect. Embedment (in.) | Min. Slab Thickness (in.) | Min. Edge Distance (in.) | A | B | C | D | E | F | G | H | I |
Pr ≤ 2.0 | Pr ≤ 1.1 | Pr ≤ 0.7 | Pr ≤ 1.2 | Pr ≤ 1.1 | Pr ≤ 1.1 | Pr ≤ 1.4 | Pr ≤ 0.9 | Pr ≤ 0.8 | ||||
3/8 | 1.100 | 4 | 6 | 302 | 395 | 458 | 264 | 395 | 537 | 228 | 332 | 397 |
1/2 | 1.690 | 4 | 6 | 385 | 551 | 680 | 394 | 551 | 690 | 339 | 499 | 591 |
5/8 | 1.750 | 4 | 8 | 421 | 627 | 800 | 463 | 627 | 756 | 399 | 591 | 696 |
3/4 | 1.750 | 4 | 8 | 421 | 627 | 800 | 463 | 627 | 756 | 399 | 591 | 696 |
Diameter (in.) | Min. Effect. Embedment (in.) | Min. Slab Thickness (in.) | Min. Edge Distance (in.) | A | B | C | D | E | F | G | H | I |
Pr 2.1—3.5 | Pr 1.2—1.8 | Pr 0.8—1.0 | Pr 1.3—1.7 | Pr 1.2—1.8 | Pr 1.2—2.0 | Pr 1.5—1.9 | Pr 1.0—1.3 | Pr 0.9—1.1 | ||||
3/8 | 1.100 | 4 | 6 | 216 | 319 | 409 | 237 | 319 | 379 | 207 | 297 | 360 |
1/2 | 1.690 | 4 | 6 | 256 | 413 | 578 | 336 | 413 | 449 | 296 | 426 | 512 |
5/8 | 1.750 | 4 | 8 | 272 | 454 | 662 | 386 | 454 | 476 | 340 | 491 | 589 |
3/4 | 1.750 | 4 | 8 | 272 | 454 | 662 | 386 | 454 | 476 | 340 | 491 | 589 |
Diameter (in.) | Min. Effect. Embedment (in.) | Min. Slab Thickness (in.) | Min. Edge Distance (in.) | A | B | C | D | E | F | G | H | I |
Pr 3.6—5.0 | Pr 1.9—2.5 | Pr 1.1—1.3 | Pr 1.8—2.2 | Pr 1.9—2.5 | Pr 2.1—2.9 | Pr 2.0—2.4 | Pr 1.4—1.7 | Pr 1.2—1.4 | ||||
3/8 | 1.100 | 4 | 6 | 169 | 267 | 370 | 215 | 267 | 292 | 190 | 270 | 329 |
1/2 | 1.690 | 4 | 6 | 192 | 330 | 503 | 293 | 330 | 332 | 262 | 371 | 452 |
5/8 | 1.750 | 4 | 8 | 192 | 356 | 565 | 331 | 356 | 332 | 296 | 419 | 511 |
3/4 | 1.750 | 4 | 8 | 192 | 356 | 565 | 331 | 356 | 332 | 296 | 419 | 511 |
Diameter (in.) | Min. Effect. Embedment (in.) | Min. Slab Thickness (in.) | Min. Edge Distance (in.) | A | B | C | D | E | F | G | H | I |
Pr 5.1—6.5 | Pr 2.6—3.2 | Pr 1.4—1.6 | Pr 2.3—2.7 | Pr 2.6—3.2 | Pr 3.0—3.8 | Pr 2.5—2.9 | Pr 1.8—2.1 | Pr 1.5—1.7 | ||||
3/8 | 1.100 | 4 | 6 | 138 | 229 | 337 | 196 | 229 | 238 | 176 | 246 | 303 |
1/2 | 1.690 | 4 | 6 | 147 | 275 | 445 | 260 | 275 | 253 | 235 | 328 | 405 |
5/8 | 1.750 | 4 | 8 | 147 | 293 | 493 | 289 | 293 | 253 | 263 | 366 | 451 |
3/4 | 1.750 | 4 | 8 | 147 | 293 | 493 | 289 | 293 | 253 | 263 | 366 | 451 |
*Pr = Prying factor range. (Refer to A.18.5.12.2 for additional information.)
Table 18.5.12.2(k) Maximum Load for Connections to Steel Using Unfinished Steel Bolts
Connections to Steel (Values Assume Bolt Perpendicular to Mounting Surface) | |||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Diameter of Unfinished Steel Bolt (in.) | |||||||||||||||||
1/4 | 3/8 | ||||||||||||||||
A | B | C | D | E | F | G | H | I | A | B | C | D | E | F | G | H | I |
400 | 500 | 600 | 300 | 500 | 650 | 325 | 458 | 565 | 900 | 1200 | 1400 | 800 | 1200 | 1550 | 735 | 1035 | 1278 |
Diameter of Unfinished Steel Bolt (in.) | |||||||||||||||||
1/2 | 5/8 | ||||||||||||||||
A | B | C | D | E | F | G | H | I | A | B | C | D | E | F | G | H | I |
1600 | 2050 | 2550 | 1450 | 2050 | 2850 | 1300 | 1830 | 2260 | 2500 | 3300 | 3950 | 2250 | 3300 | 4400 | 2045 | 2880 | 3557 |
Table 18.5.12.2(l) Maximum Load for Through-Bolts in Sawn Lumber or Glue-Laminated Timbers
Through-Bolts in Sawn Lumber or Glue-Laminated Timbers (Load Perpendicular to Grain) | ||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Length of Bolt in Timber (in.) | Bolt Diameter (in.) | |||||||||||||||||||||||||||
1/2 | 5/8 | 3/4 | ||||||||||||||||||||||||||
A | B | C | D | E | F | G | H | I | A | B | C | D | E | F | G | H | I | A | B | C | D | E | F | G | H | I | ||
11/2 | 115 | 165 | 200 | 135 | 230 | 395 | 130 | 215 | 310 | 135 | 190 | 235 | 155 | 270 | 460 | 155 | 255 | 380 | 155 | 220 | 270 | 180 | 310 | 530 | 170 | 300 | 450 | |
21/2 | 140 | 200 | 240 | 160 | 280 | 480 | 165 | 275 | 410 | 160 | 225 | 280 | 185 | 320 | 550 | 190 | 320 | 495 | 180 | 255 | 310 | 205 | 360 | 615 | 215 | 365 | 575 | |
31/2 | 175 | 250 | 305 | 200 | 350 | 600 | 200 | 330 | 485 | 200 | 285 | 345 | 230 | 400 | 685 | 235 | 405 | 635 | 220 | 310 | 380 | 255 | 440 | 755 | 260 | 455 | 730 | |
51/2 | — | — | — | — | — | — | — | — | — | 280 | 395 | 485 | 325 | 560 | 960 | 315 | 515 | 735 | 310 | 440 | 535 | 360 | 620 | 1065 | 360 | 610 | 925 |
Note: Wood fastener maximum capacity values are based on the 2001 National Design Specifications (NDS) for wood with a specific gravity of 0.35. Values for other types of wood can be obtained by multiplying the above values by the factors in Table 18.5.12.2(n).
Table 18.5.12.2(m) Maximum Load for Lag Screws and Lag Bolts in Wood
Lag Screws and Lag Bolts in Wood (Load Perpendicular to Grain — Holes Predrilled Using Good Practice) | ||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Length of Bolt in Timber (in.) | Lag Bolt Diameter (in.) | |||||||||||||||||||||||||||
1/2 | 5/8 | 3/4 | ||||||||||||||||||||||||||
A | B | C | D | E | F | G | H | I | A | B | C | D | E | F | G | H | I | A | B | C | D | E | F | G | H | I | ||
31/2 | 165 | 190 | 200 | 170 | 220 | 310 | 80 | 120 | 170 | — | — | — | — | — | — | — | — | — | — | — | — | — | — | — | — | — | — | |
41/2 | 180 | 200 | 200 | 175 | 235 | 350 | 80 | 120 | 170 | 300 | 355 | 380 | 315 | 400 | 550 | 145 | 230 | 325 | — | — | — | — | — | — | — | — | — | |
51/2 | 190 | 200 | 200 | 175 | 245 | 380 | 80 | 120 | 170 | 320 | 370 | 380 | 320 | 420 | 610 | 145 | 230 | 325 | 435 | 525 | 555 | 425 | 550 | 775 | 195 | 320 | 460 | |
61/2 | 195 | 205 | 200 | 175 | 250 | 400 | 80 | 120 | 170 | 340 | 375 | 380 | 325 | 435 | 650 | 145 | 230 | 325 | 465 | 540 | 555 | 430 | 570 | 840 | 195 | 320 | 460 |
Note: Wood fastener maximum capacity values are based on the 2001 National Design Specifications (NDS) for wood with a specific gravity of 0.35. Values for other types of wood can be obtained by multiplying the above values by the factors in Table 18.5.12.2(n).
Table 18.5.12.2(n) Factors for Wood Based on Specific Gravity
Specific Gravity of Wood | Multiplier |
---|---|
0.36 thru 0.49 | 1.17 |
0.50 thru 0.65 | 1.25 |
0.66 thru 0.73 | 1.50 |
The type of fasteners used to secure the bracing assembly to the structure shall be limited to those shown in Table 18.5.12.2(a) through Table 18.5.12.2(m) or to listed devices.
For connections to wood, through-bolts with washers on each end shall be used, unless the requirements of 18.5.12.5 are met.
Where it is not practical to install through-bolts due to the thickness of the wood member in excess of 12 in. (300 mm) or inaccessibility, lag screws shall be permitted and holes shall be pre-drilled 1/8 in. (3 mm) smaller than the maximum root diameter of the lag screw.
Holes for through-bolts and similar listed attachments shall be 1/16 in. (1.6 mm) greater than the diameter of the bolt.
Calculations shall be submitted where required by the authority having jurisdiction.
Post-installed concrete anchors shall be prequalified for seismic applications in accordance with ACI 355.2, Qualification of Post-Installed Mechanical Anchors in Concrete and Commentary, and installed in accordance with the manufacturer's instructions.
Unless the requirements of 18.5.12.7.3 are met, concrete anchors shall be based on concrete strength, anchor type, designated angle category A through I, prying factor (Pr) range, and allowable maximum load.
Sway brace manufacturers shall provide prying factors (Pr) based on geometry of the structure attachment fitting and the designated angle category A through I as shown in Figure 18.5.12.1.
Where the prying factor for the fitting is unknown, the largest prying factor range in Table 18.5.12.2(a) through Table 18.5.12.2(j) for the concrete strength and designated angle category A through I shall be used.
The allowable maximum load shall be permitted to be calculated.
Allowable concrete anchor loads shall be permitted to be determined using approved software that considers the effects of prying for concrete anchors.
Anchors shall be seismically prequalified per 18.5.12.7.1.
Allowable maximum loads shall be based on the anchor capacities given in approved evaluation service reports, where the calculation of ASD allowable shear and tension values are determined in accordance with Chapter 17 of ACI 318, Building Code Requirements for Structural Concrete and Commentary, and include the effects of prying, brace angle, and the over strength factor (Ω = 2.0).
The shear and tension values determined in 18.5.12.7.3(C) using Chapter 17 of ACI 318, Building Code Requirements for Structural Concrete and Commentary, shall be multiplied by 0.43.
Concrete anchors shall be acceptable for use where designed in accordance with the requirements of the building code and certified by a registered professional engineer.
Headed cast-in specialty inserts (concrete inserts) as prescribed in Table 18.5.12.2(a) through Table 18.5.12.2(j) shall be prequalified for seismic applications in accordance with ICC-ES AC446, Acceptance Criteria for Headed Cast-in Specialty Inserts in Concrete, and installed in accordance with the manufacturer's instructions.
A length of pipe shall not be braced to sections of the building that will move differentially.
Restraint is considered a lesser degree of resisting loads than bracing and shall be provided by use of one of the following:
- Listed sway brace assembly
- Wraparound U-hook satisfying the requirements of 18.5.5.11
- No. 12, 440 lb (200 kg) wire installed at least 45 degrees from the vertical plane and anchored on both sides of the pipe
- CPVC hangers listed to provide restraint
- * Hanger not less than 45 degrees from vertical installed within 6 in. (150 mm) of the vertical hanger arranged for restraint against upward movement, provided it is utilized such that l/r does not exceed 400, where the rod extends to the pipe or a surge clip has been installed
- Other approved means
The end sprinkler on a branch line shall be restrained.
The location of the restraint from end of the line shall not be greater than 36 in. (900 mm) for 1 in. (25 mm) pipe, 48 in. (1200 mm) for 11/4 in. (32 mm) pipe, and 60 in. (1.5 m) for 11/2 in. (40 mm) or larger pipe.
Branch lines shall be laterally restrained at intervals not exceeding those specified in Table 18.6.4(a) or Table 18.6.4(b) based on branch line diameter and the value of Cp.
Table 18.6.4(a) Maximum Spacing [ft (m)] of Steel Pipe Restraints
Pipe [in. (mm)] | Seismic Coefficient, Cp | |||
---|---|---|---|---|
Cp ≤ 0.50 | 0.5 < Cp ≤ 0.71 | 0.71 < CP ≤ 1.40 | Cp> 1.40 | |
1/2 (15) | 34 (10.3) | 29 (8.8) | 20 (6.1) | 18 (5.5) |
3/4 (20) | 38 (11.6) | 32 (9.7) | 23 (7.0) | 20 (6.1) |
1 (25) | 43 (13.1) | 36 (11.0) | 26 (7.9) | 22 (6.7) |
11/4 (32) | 46 (14.0) | 39 (11.9) | 27 (8.2) | 24 (7.3) |
11/2 (40) | 49 (14.9) | 41 (12.5) | 29 (8.8) | 25 (7.6) |
2 (50) | 53 (16.1) | 45 (13.7) | 31 (9.4) | 27 (8.2) |
Table 18.6.4(b) Maximum Spacing [ft (m)] of CPVC, Copper, and Red Brass Pipe Restraints
Pipe [in. (mm)] | Seismic Coefficient, Cp | |||
---|---|---|---|---|
Cp ≤ 0.50 | 0.5 < Cp ≤ 0.71 | 0.71 < CP ≤ 1.40 | Cp> 1.40 | |
1/2 (15) | 26 (7.9) | 22 (6.7) | 16 (4.9) | 13 (4.0) |
3/4 (20) | 31 (9.4) | 26 (7.9) | 18 (5.5) | 15 (4.6) |
1 (25) | 34 (10.3) | 28 (8.5) | 20 (6.1) | 17 (5.2) |
11/4 (32) | 37 (11.3) | 31 (9.4) | 22 (6.7) | 19 (5.8) |
11/2 (40) | 40 (12.2) | 34 (10.3) | 24 (7.3) | 20 (6.1) |
2 (50) | 45 (13.7) | 38 (11.6) | 27 (8.2) | 23 (7.0) |
Where the branch lines are supported by rods less than 6 in. (150 mm) long measured between the top of the pipe and the point of attachment to the building structure, the requirements of 18.6.1 through 18.6.4 shall not apply and additional restraint shall not be required for the branch lines.
Drops and armovers shall not require restraint.
Where seismic protection is provided, C-type clamps (including beam and large flange clamps) used to attach hangers to the building structure shall be equipped with a restraining strap unless the provisions of 18.7.1.1 are satisfied.
As an alternative to the installation of a required restraining strap, a device investigated and specifically listed to restrain the clamp to the structure is permitted where the intent of the device is to resist the worst-case expected horizontal load.
The restraining strap shall be listed for use with a C-type clamp or shall be a steel strap of not less than 16 gauge (1.57 mm) thickness and not less than 1 in. (25 mm) wide for pipe diameters 8 in. (200 mm) or less and 14 gauge (1.98 mm) thickness and not less than 11/4 in. (32 mm) wide for pipe diameters greater than 8 in. (200 mm).
The restraining strap shall wrap around the beam flange not less than 1 in. (25 mm).
A lock nut on a C-type clamp shall not be used as a method of restraint.
A lip on a "C" or "Z" purlin shall not be used as a method of restraint.
Where purlins or beams do not provide a secure lip to a restraining strap, the strap shall be through-bolted or secured by a self-tapping screw.
In areas where the horizontal force factor exceeds 0.50 Wp, powder-driven studs shall be permitted to attach hangers to the building structure where they are specifically listed for use in areas subject to earthquakes.
Where seismic protection is provided, concrete anchors used to secure hangers to the building structure shall be in accordance with ACI 355.2, Qualification of Post-Installed Mechanical Anchors in Concrete and Commentary, and installed in accordance with manufacturer's instructions.
In areas where the horizontal force factor exceeds 0.5 Wp, pipe stands over 4 ft (1.2 m) in height shall be certified by a registered professional engineer to be adequate for the seismic forces.
Where seismic protection is provided, concrete anchors used to secure pipe stands to their bases shall be in accordance with ACI 355.2, Qualification of Post-Installed Mechanical Anchors in Concrete and Commentary, and shall be installed in accordance with manufacturer's instructions.