Heads up: There are no amended sections in this chapter.

This appendix is informative and is not part of the code.

User note:

About this appendix: The design of storm water drainage systems (Chapter 11) requires determination of the design rainfall event for the geographic location of the building. Appendix B provides a list of major cities in the U.S. along with the 1-hour duration, 100-year occurrence rainfall rate.

Rainfall rates, in inches per hour, are based on a storm of 1-hour duration and a 100-year return period. The rainfall rates shown in the appendix are derived from Figure 1106.1.

Alabama:  
Birmingham 3.8
Huntsville 3.6
Mobile 4.6
Montgomery 4.2
Alaska:  
Fairbanks 1.0
Juneau 0.6
Arizona:  
Flagstaff 2.4
Nogales 3.1
Phoenix 2.5
Yuma 1.6
Arkansas:  
Fort Smith 3.6
Little Rock 3.7
Texarkana 3.8
California:  
Barstow 1.4
Crescent City 1.5
Fresno 1.1
Los Angeles 2.1
Needles 1.6
Placerville 1.5
San Fernando 2.3
San Francisco 1.5
Yreka 1.4
Colorado:  
Craig 1.5
Denver 2.4
Durango 1.8
Grand Junction 1.7
Lamar 3.0
Pueblo 2.5
Connecticut:  
Hartford 2.7
New Haven 2.8
Putnam 2.6
Delaware:  
Georgetown 3.0
Wilmington 3.1
District of Columbia:  
Washington 3.2
Florida:  
Jacksonville 4.3
Key West 4.3
Miami 4.7
Pensacola 4.6
Tampa 4.5
Georgia:  
Atlanta 3.7
Dalton 3.4
Macon 3.9
Savannah 4.3
Thomasville 4.3
Hawaii:  
Hilo..... 6.2
Honolulu 3.0
Wailuku 3.0
Idaho:  
Boise 0.9
Lewiston 1.1
Pocatello 1.2
Illinois:  
Cairo 3.3
Chicago 3.0
Peoria 3.3
Rockford 3.2
Springfield 3.3
Indiana:  
Evansville 3.2
Fort Wayne 2.9
Indianapolis 3.1
Iowa:  
Davenport 3.3
Des Moines 3.4
Dubuque 3.3
Sioux City 3.6
Kansas:  
Atwood 3.3
Dodge City 3.3
Topeka 3.7
Wichita 3.7
Kentucky:  
Ashland 3.0
Lexington 3.1
Louisville 3.2
Middlesboro 3.2
Paducah 3.3
Louisiana:  
Alexandria 4.2
Lake Providence 4.0
New Orleans 4.8
Shreveport 3.9
Maine:  
Bangor 2.2
Houlton 2.1
Portland 2.4
Maryland:  
Baltimore 3.2
Hagerstown 2.8
Oakland 2.7
Salisbury 3.1
Massachusetts:  
Boston 2.5
Pittsfield 2.8
Worcester 2.7
Michigan:  
Alpena 2.5
Detroit 2.7
Grand Rapids 2.6
Lansing 2.8
Marquette 2.4
Sault Ste. Marie 2.2
Minnesota:  
Duluth 2.8
Grand Marais 2.3
Minneapolis 3.1
Moorhead 3.2
Worthington 3.5
Mississippi:  
Biloxi 4.7
Columbus 3.9
Corinth 3.6
Natchez 4.4
Vicksburg 4.1
Missouri:  
Columbia 3.2
Kansas City 3.6
Springfield 3.4
St. Louis 3.2
Montana:  
Ekalaka 2.5
Havre 1.6
Helena 1.5
Kalispell 1.2
Missoula 1.3
Nebraska:  
North Platte 3.3
Omaha 3.8
Scottsbluff 3.1
Valentine 3.2
Nevada:  
Elko 1.0
Ely 1.1
Las Vegas 1.4
Reno 1.1
New Hampshire:  
Berlin 2.5
Concord 2.5
Keene 2.4
New Jersey:  
Atlantic City 2.9
Newark. 3.1
Trenton 3.1
New Mexico:  
Albuquerque 2.0
Hobbs 3.0
Raton 2.5
Roswell 2.6
Silver City 1.9
New York:  
Albany 2.5
Binghamton 2.3
Buffalo 2.3
Kingston 2.7
New York 3.0
Rochester 2.2
North Carolina:  
Asheville 4.1
Charlotte 3.7
Greensboro 3.4
Wilmington 4.2
North Dakota:  
Bismarck 2.8
Devils Lake 2.9
Fargo 3.1
Williston 2.6
Ohio:  
Cincinnati 2.9
Cleveland 2.6
Columbus 2.8
Toledo 2.8
Oklahoma:  
Altus 3.7
Boise City 3.3
Durant 3.8
Oklahoma City 3.8
Oregon:  
Baker 0.9
Coos Bay 1.5
Eugene 1.3
Portland 1.2
Pennsylvania:  
Erie 2.6
Harrisburg 2.8
Philadelphia 3.1
Pittsburgh 2.6
Scranton 2.7
Rhode Island:  
Block Island 2.75
Providence 2.6
South Carolina:  
Charleston 4.3
Columbia 4.0
Greenville 4.1
South Dakota:  
Buffalo 2.8
Huron 3.3
Pierre 3.1
Rapid City 2.9
Yankton 3.6
Tennessee:  
Chattanooga 3.5
Knoxville 3.2
Memphis 3.7
Nashville 3.3
Texas:  
Abilene 3.6
Amarillo 3.5
Brownsville 4.5
Dallas 4.0
Del Rio 4.0
El Paso 2.3
Houston 4.6
Lubbock 3.3
Odessa 3.2
Pecos 3.0
San Antonio 4.2
Utah:  
Brigham City 1.2
Roosevelt 1.3
Salt Lake City 1.3
St. George 1.7
Vermont:  
Barre 2.3
Bratteboro 2.7
Burlington 2.1
Rutland 2.5
Virginia:  
Bristol 2.7
Charlottesville 2.8
Lynchburg 3.2
Norfolk 3.4
Richmond 3.3
Washington:  
Omak 1.1
Port Angeles 1.1
Seattle 1.4
Spokane 1.0
Yakima 1.1
West Virginia:  
Charleston 2.8
Morgantown 2.7
Wisconsin:  
Ashland 2.5
Eau Claire 2.9
Green Bay 2.6
La Crosse 3.1
Madison 3.0
Milwaukee 3.0
Wyoming:  
Cheyenne 2.2
Fort Bridger 1.3
Lander 1.5
New Castle 2.5
Sheridan 1.7
Yellowstone Park 1.4