ADOPTS WITH AMENDMENTS:

UMC 2018

Heads up: There are no amended sections in this chapter.
The purpose of this appendix is to provide a comprehensive set of technically sound provisions that encourage sustainable practices and works towards enhancing the design and construction of mechanical systems that result in a positive long-term environmental impact. This appendix is not intended to circumvent the health, safety, and general welfare requirements of this code.
For the purposes of this code, the definitions shall apply to this appendix.

No attempt is made to define ordinary words, which are used in accordance with their established dictionary meanings, except where a word has been used loosely, and it is necessary to define its meaning as used in this appendix to avoid misunderstanding.

The definitions of terms are arranged alphabetically according to the first word of the term.

Cycles of concentration equals the specific conductance of the water in the cooling tower basin divided by the combined flow-weighted average specific conductance of the makeup water(s) to the cooling tower.
Includes pipe, tubing, rods, and wire. Screws and other fasteners are not considered to be ductwork penetrations.
A joint program of the U.S. Environmental Protection Agency and the U.S. Department of Energy. Energy Star is a voluntary program designed to identify and promote energy-efficient products and practices.
Renewable energy generated by deep-earth.
The total heating output of a heat pump during its normal annual usage period for heating in British thermal units (Btu) (kW•h) divided by the total electric energy input during the same period. [ASHRAE 90.1:3.2]
A single-number figure of merit expressing cooling part-load EER efficiency for commercial unitary air-conditioning and heat pump equipment on the basis of weighted operation at various load capacities for the equipment. [ASHRAE 90.1:3.2]
A single-number figure of merit based on part-load EER, COP, or kW/ton expressing part-load efficiency for air-conditioning and heat pump equipment on the basis of weighted operation at various load capacities for the equipment. [ASHRAE 90.1:3.2]
Connections of two duct sections oriented perpendicular to airflow.
The upkeep of property or equipment by the owner of the property in accordance with the requirements of this appendix.

E 201.10 Minimum Efficiency Reporting Value (MERV). Filter minimum efficiency reporting value, in accordance with ASHRAE 52.2.

E 201.11 Multi-Occupant Spaces. Indoor spaces used for presentations and training, including classrooms and conference rooms.

E 201.12 Recirculation System. A system of hot water supply and return piping with shutoff valves, balancing valves, circulating pumps, and a method of controlling the circulating system.

E 201.13 Seam, Longitudinal. Joints oriented in the direction of airflow.

E 201.14 Seasonal Energy Efficiency Ratio (SEER). The total cooling output of an air conditioner during its normal annual usage period for cooling in Btu (kW•h) divided by the total electric energy input during the same period in Btu (kW•h). [ASHRAE 90.1:3.2]

Mechanical systems covered by this appendix shall be installed in accordance with this code, other applicable codes, and the manufacturer's installation and operating instructions.
Where permits are required, the Authority Having Jurisdiction shall have the authority to require contractors, installers, or service technicians to demonstrate competency. Where determined by the Authority Having Jurisdiction, the contractor, installer or service technician shall be licensed to perform such work.
It shall be unlawful for a person to cause, suffer, or permit the disposal of liquid wastes, in a place or manner, except through and by means of an approved drainage system, installed and maintained in accordance with the provisions of the plumbing code.
Equipment and appliances, used to receive or discharge liquid wastes or sewage, shall be connected to the drainage system of the building or premises in accordance with the requirements of the plumbing code and this appendix.
An abandoned system or part thereof covered under the scope of this appendix shall be disconnected from remaining systems, drained, plugged, and capped in an approved manner.
The provisions of this section establish the means of conserving potable and nonpotable water used in and around a building.
A water meter shall be required for buildings connected to a public water system, including municipally supplied reclaimed (recycled) water. In other than single-family houses, multi-family structures not exceeding three stories above grade, and modular houses, a separate meter or submeter shall be installed in the following locations:
  1. The makeup water supply to cooling towers, evaporative condensers, and fluid coolers.
  2. The makeup water supply to one or more boilers collectively exceeding 1 000 000 British thermal units per hour (Btu/h) (293 kW).
  3. The water supply to a water-using process where the consumption exceeds 1000 gallons per day (gal/d) (0.0438 L/s), except for manufacturing processes.
  4. The makeup water supply to an evaporative cooler having an air flow exceeding 30 000 cubic feet per minute (ft3/min) (14.1584 m3/s).
A means of communicating water consumption data from submeters to the water consumer shall be provided.
Meters and submeters shall be accessible.
Once-through cooling using potable water is prohibited.
Cooling towers and evaporative coolers shall be equipped with makeup water and blow down meters, conductivity controllers, and overflow alarms. Cooling towers shall be equipped with efficiency drift eliminators that achieve drift reduction to 0.002 percent of the circulated water volume for counterflow towers and 0.005 percent for cross-flow towers.
Not less than 5 cycles of concentration is required for air-conditioning cooling tower makeup water having a total hardness of less than 11 grains per gallon (gr/gal) (188 mg/L) expressed as calcium carbonate. Not less than 3.5 cycles of concentration is required for air-conditioning cooling tower makeup water having a total hardness equal to or exceeding 11 gr/gal (188 mg/L) expressed as calcium carbonate.

Exception: Air-conditioning cooling tower makeup water having discharge conductivity range not less than 7 gr/gal (120 mg/L) to 9 gr/gal (154 mg/L) of silica measured as silicon dioxide.

Evaporative cooling systems shall use 3.5 gallons (13.2 L) or less of water per ton-hour (kW•h) of cooling where system controls are set to maximum water use. Water use expressed in maximum water use per ton-hour (kW•h) of cooling, shall be marked on the device and included in the product user manual, product information literature, and manufacturer's installation instructions. Water use information shall be readily available at the time of code compliance inspection.
Cooling systems shall be equipped with an overflow alarm to alert building owners, tenants, or maintenance personnel where the water refill valve continues to allow water to flow into the reservoir where the reservoir is full. The alarm shall have a sound pressure level rating of not less than 85 dBa measured at a distance of 10 feet (3048 mm).
Cooling systems shall automatically cease pumping water to the evaporation pads where airflow across evaporation pads ceases.
A water quality management system (either timer or water quality sensor) shall be provided. Where timers are used, the time interval between discharge of reservoir water shall be set to 6 or more hours of cooler operation. Where water quality sensors are used, the discharge of reservoir water shall be set for 800 ppm or more of total dissolved solids (TDS). Continuous discharge or continuous bleed systems shall not be installed.
Discharge water shall be reused where applications exist on site. Where a nonpotable water source system exists on site, evaporative cooler discharge water shall be collected and discharged to the collection system.

Exception: Where the reservoir water affects the quality of the nonpotable water supply making the nonpotable water unusable for its intended purposes.

Where discharge water is not recovered for reuse, the sump overflow line shall not be directly connected to a drain. Where the discharge water is discharged into a sanitary drain, an air gap of not less than 6 inches (152 mm) shall be provided between the termination of the discharge line and the drain opening. The discharge line shall terminate in a location that is visible to the building owner, tenants, or maintenance personnel.
Where approved for use by the water or wastewater utility and the Authority Having Jurisdiction, reclaimed (recycled), or onsite treated nonpotable water shall be permitted to be used for industrial and commercial cooling or air-conditioning.
A drift eliminator shall be utilized in a cooling system, utilizing alternate sources of water, where the aerosolized water is capable of coming in contact with employees or members of the public.
A biocide shall be used to treat the cooling system recirculation water where the recycled water is capable of coming in contact with employees or members of the public.
The provisions of this section shall establish the means of enhancing energy efficiency associated with mechanical systems in a building.
The heating, ventilating, air-conditioning, for single-family houses, multi-family structures not exceeding three stories above grade, and modular houses shall be in accordance with Section E 502.2 through Section E 502.12. The heating, ventilation, and air-conditioning system of other buildings shall be in accordance with Section E 503.0.
This section shall regulate only equipment using single-phase electric power, air conditioners, and heat pumps with rated cooling capacities less than 65 000 British thermal units per hour (Btu/h) (19 kW), warm air furnaces with rated heating capacities less than 225 000 Btu/h (66 kW), boilers less than 300 000 Btu/h (88 kW) input, and heating-only heat pumps with rated heating capacities less than 65 000 Btu/h (19 kW). [ASHRAE 90.2:6.2]
Heating, ventilating, and air-conditioning systems and equipment that do not fall under the requirements of Section E 502.0 shall be in accordance with the applicable requirements of Section E 503.0.
The air distribution system design, including outlet grilles, shall provide a means for balancing the air distribution system unless the design procedure provides a system intended to operate within plus or minus 10 percent of design air quantities. [ASHRAE 90.2:6.3]
Balancing dampers shall be installed in branch ducts, and the axis of the damper shall be installed parallel to the direction of airflow in the main duct.
Ducts shall be sized, installed, and tested in accordance with Section E 502.4.1 through Section E 502.4.4.
Portions of the air distribution system installed in or on buildings for heating and cooling shall be R-8. Where the mean outdoor dew-point temperature in a month exceeds 60°F (16°C), vapor retarders shall be installed on conditioned-air supply ducts. Vapor retarders shall have a water vapor permeance not exceeding 0.5 perm [2.87 E-11 kg/(Pa•s•m2)] where tested in accordance with Procedure A in ASTM E96.

Insulation shall not be required where the ducts are within the conditioned space. [ASHRAE 90.2:6.4]

Joints, seams, and penetrations of duct systems shall be made airtight by means of mastics, gasketing, or other means in accordance with this code. Register penetrations shall be sealed to the wall or floor assemblies. Where HVAC duct penetrates a conditioned space, the duct penetration shall be sealed to the wall or floor assembly to prevent leakage into an un conditioned space.
For systems with a duct or air handler outside of the conditioned space, a duct leakage test shall be performed in accordance with Section E 502.4.3.1.
Ductwork shall be tested to the maximum permitted leakage in 1 cubic foot per minute (ft3/min) per 100 square feet [0.0001 (m3/s)/m2] of duct surface area in accordance with SMACNA HVAC Air Duct Leakage Test Manual. Register penetrations shall be sealed during the test. The test shall be conducted with a pressure differential of 0.1 inch water gauge (0.02 kPa) across the tested system.
Duct systems shall be sized in accordance with ACCA Manual D or other methods approved by the Authority Having Jurisdiction with the velocity in the main duct not to exceed 1000 feet per minute (ft/min) (5.08 m/s) and the velocity in the secondary branch duct not to exceed 600 ft/min (3.048 m/s).
HVAC system piping installed to serve buildings and within buildings shall be thermally insulated in accordance with Table E 502.5. [ASHRAE 90.2:6.5]

TABLE E 502.5 MINIMUM PIPE INSULATION THICKNESS1, 5
[ASHRAE 90.2:TABLE 6.5]

INSULATION CONDUCTIVITY NOMINAL PIPE DIAMETER (inches)
FLUID DESIGN OPERATING TEMPERATURE RANGE (°F) Btu•inch/(h•ft2•°F) MEAN RATING TEMPERATURE(°F) <1 1 TO 11/4 11/2 TO 31/2 4 TO 6 EQUAL TO OR GREATER THAN 8
HEATING SYSTEMS (STEAM, STEAM CONDENSATE, AND HOT WATER)2, 3
201—250 0.27—0.30 150 1.5 1.5 2.0 2.0 2.0
141—200 0.25—0.29 125 1.0 1.0 1.0 1.5 1.5
105—140 0.22—0.28 100 0.5 0.5 1.0 1.0 1.0
COOLING SYSTEMS (CHILLED WATER, BRINE, AND REFRIGERANT)4
40—55 0.22—0.28 100 0.5 0.5 1.0 1.0 1.0
Below 40 0.22—0.28 100 0.5 1.0 1.0 1.0 1.5

For SI Units: °C= (°F—32)/1.8, 1 British thermal unit inch per hour square foot degree Fahrenheit = [0.1 W/(m•K)], 1 inch = 25 mm

Notes:

1 For insulation outside the stated conductivity range, the minimum thickness (T) shall be determined as follows:

T = r{(1 + t/r)K/k — 1}

Where:

T = minimum insulation thickness (inches).

r = actual outside radius of pipe (inches) (mm).

t = insulation thickness listed in this table for applicable fluid temperature and pipe size.

K = conductivity of alternate material at mean rating temperature indicated for the applicable fluid temperature [Btu•in/(h•ft2•°F)] [W/(m•K)].

k = the upper value of the conductivity range listed in this table for the applicable fluid temperature.

2 These thicknesses are based on energy efficiency considerations only. Additional insulation is sometimes required relative to safety issues/surface temperature.

3 Piping insulation is not required between the control valve and coil on run-outs where the control valve is located within 4 feet (1219 mm) of the coil and the pipe size is 1 inch (25 mm) or less.

4 These thicknesses are based on energy efficiency considerations only. Issues such as water vapor permeability or surface condensation sometimes require vapor retarders, additional insulation or both.

5 For piping exposed to outdoor air, increase insulation thickness by 1/2 of an inch (12.7 mm). The outdoor air is defined as any portion of insulation that is exposed to outdoor air. For example, attic spaces and crawlspaces are considered exposed to outdoor air.

The building shall be designed to have the capability to provide the ventilation air specified in Table E 502.6. Mechanical ventilation shall be calculated in accordance with Equation E 502.6. [ASHRAE 90.2:6.6.1]

(Equation E 502.6)

Mechanical Ventilation = [(0.35 — Summer) × Volume] / 60

Where:

Mechanical Ventilation = required mechanical ventilation rate to supplement summer infiltration, cfm (m3/s)
Summer = summer design infiltration rate, ACH
Volume = volume of conditioned space, ft3 (m3)
Combustion air for fossil fuel heating equipment shall comply with this code or with one of the following:
  1. Natural gas and propane heating equipment, NFPA 54
  2. Oil heating equipment, NFPA 31
  3. Solid fuel burning equipment, NFPA 211 [ASHRAE 90.2:6.6.2]

TABLE E 502.6 VENTILATION AIR
[ASHRAE 90.2:TABLE 6.6.1]

CATEGORY MINIMUM REQUIREMENT CONDITIONS
Mechanical ventilation1 50 ft3/min outdoor air Where summer design infiltration rate calculated in accordance with reference standard (a) or (b) is less than 0.35 ACH2.
Kitchen exhaust 100 ft3/min intermittent All conditions
Bath exhaust intermittent All conditions

For SI units: 1 cubic foot per minute = 0.00047 m3/s

Notes:

1 Calculate in accordance with Equation E 502.6.

2 Reference standards:

(a) ACCA Manual J

(b) ASHRAE GRP-158

Electric heating systems shall be installed in accordance with the following requirements. [ASHRAE 90.2:6.7]
Where wall, floor, or ceiling electric-resistance heating units are used, the structure shall be zoned and heaters installed in each zone in accordance with the heat loss of that zone. Where living and sleeping zones are separate, the number of zones shall be not less than two. Where two or more heaters are installed in one room, they shall be controlled by one thermostat. [ASHRAE 90.2:6.7.1]
Where electric central warm air heating is to be installed, an electric heat pump or an off-peak electric heating system with thermal storage shall be used.

Exceptions:

  1. Electric resistance furnaces where the ducts are located inside the conditioned space, and not less than two zones are provided where the living and sleeping zones are separate.
  2. Packaged air-conditioning units with supplemental electric heat. [ASHRAE 90.2:6.7.2]
Bath ceiling units providing a combination of heat, light, or ventilation shall be provided with controls permitting separate operation of the heating function. [ASHRAE 90.2:6.8]
HVAC system equipment and system components shall be furnished with the input(s), the output(s), and the value of the appropriate performance descriptor of HVAC products in accordance with federal law or in accordance with Table E 502.9, as applicable. These shall be based on newly produced equipment or components. Manufacturer's instructions shall be furnished with and attached to the equipment. The manufacturer of electric-resistance heating equipment shall furnish full-load energy input over the range of voltages at which the equipment is intended to operate. [ASHRAE 90.2:6.9]

TABLE E 502.9 MINIMUM REQUIREMENTS FOR NON-FEDERALLY COVERED HVAC EQUIPMENT
[ASHRAE 90.2:TABLE 6.9]

EQUIPMENT TYPE SUBCATEGORY OR RATING CONDITION MINIMUM EFFICIENCY TEST PROCEDURE
Groundwater source heat pump* Cooling Mode 11.0 EER at 70°F Ent. Water ARI 325
11.5 EER at 50°F Ent. Water
Heating Mode 3.4 COP at 70°F Ent. Water
3.0 COP at 50°F Ent. Water
Unitary A/C Water cooled split system 9.3 EER at 85°F Ent. Water ARI 210/240
8.3 IPLV at 75°F Ent. Water
Evaporatively cooled split system 9.3 EER at 95°F Out. Amb.
8.5 IPLV at 80°F Out. Amb.

For SI units: °C = (°F—32)/1.8

* Performance for electrically powered equipment with capacity less than 65 000 Btu/h (19 kW) where rated in accordance with ARI 325.

E 502.10 Controls. Each system or each zone within a system shall be provided with not less than one thermostat capable of being set from 55°F (13°C) to 85°F (29°C) and capable of operating the system's heating and cooling. The thermostat or control system, or both, shall have an adjustable deadband, the range of which includes a setting of 10°F (6°C) between heating and cooling where automatic changeover is provided. Wall-mounted temperature controls shall be mounted on an inside wall. [ASHRAE 90.2:6.10.1]

E 502.10.1 Initial Control Setting. The control shall initially be set for a maximum heating temperature of 70°F (21°C) and a cooling temperature of not less than 78°F (26°C).

E 502.10.2 Ventilation Control. Each mechanical ventilation system (supply, exhaust, or both) shall be equipped with a readily accessible switch or other means for shutoff. Manual or automatic dampers installed for the purpose of isolating outside air intakes and exhausts from the air distribution system shall be designed for tight shutoff. [ASHRAE 90.2:6.10.2]

E 502.10.3 Humidity Control. Where additional energy-consuming equipment is provided for adding moisture to maintain specific selected relative humidities in spaces or zones, a humidistat shall be provided. This device shall be capable of being set to prevent energy from being used to produce relative humidity within the space above 30 percent. [ASHRAE 90.2:6.10.3.1]

E 502.10.3.1 Cooling. Where additional energy-consuming equipment is provided for reducing humidity, it shall be equipped with controls capable of being set to prevent energy from being used to produce a relative humidity within the space below 50 percent during periods of human occupancy and below 60 percent during unoccupied periods. [ASHRAE 90.2:6.10.3.2]

E 502.10.4 Freeze Protection Systems. Freeze protection systems, such as heat tracing of outdoor piping and heat exchangers, including self-regulating heat tracing, shall include automatic controls capable of and configured to shut off the systems where outdoor air temperatures are above 40°F (4°C) or where the conditions of the protected fluid will prevent freezing. Snow- and ice-melting systems shall include automatic controls capable of and configured to shut off the systems where the pavement temperature is above 50°F (10°C) and no precipitation is falling and an automatic or manual control that will allow shutoff where the outdoor temperature is above 40°F (4°C) so that the potential for snow or ice accumulation is negligible. [ASHRAE 90.1:6.4.3.7]

E 502.10.5 Other Controls. Where setback, zoned, humidity and cooling controls and equipment are provided, they shall be designed and installed in accordance with Section E 502.10 through Section E 502.10.3.1. [ASHRAE 90.2:6.10.3.3]

E 502.11 Whole House Fans. Whole house exhaust fans shall have insulated louvers or covers which close where the fan is off. Covers or louvers shall have an insulation value of not less than R-4.2, and shall be installed in accordance with the manufacturer's installation instructions. The attic openings shall be sufficient to accommodate the ventilation capacity of the whole house fan. The operation of the whole house fan shall be considered in determining the adequacy of providing combustion air in accordance with this code.

E 502.12 Dampers. Dampers shall be installed to close off outdoor air inlets and exhaust outlets where the ventilation system is not operating.

The heating, ventilation, and air-conditioning in buildings, other than single-family houses, multi-family structures of not more than three stories above grade, and modular houses, shall be in accordance with Section E 503.0.
Mechanical equipment and systems serving the heating, cooling, ventilating, or refrigeration needs of new buildings shall be in accordance with the requirements of this section as described in Section E 503.2. [ASHRAE 90.1:6.1.1.1]
Mechanical equipment and systems serving the heating, cooling, ventilating, or refrigeration needs of additions to existing buildings shall be in accordance with the requirements of this section as described in Section E 503.2.

Exception: Where HVACR to an addition is provided by existing HVACR systems and equipment, such existing systems and equipment shall not be required to be in accordance with this appendix. A new system or equipment installed shall be in accordance with specific requirements applicable to those systems and equipment. [ASHRAE 90.1:6.1.1.2]

New cooling systems installed to serve previously uncooled spaces shall be in accordance with this section as described in Section E 503.2. [ASHRAE 90.1:6.1.1.3.2]
Alterations to existing cooling systems shall not decrease economizer capability unless the system is in accordance with Section E 503.5 through Section 503.5.4.1. [ASHRAE 90.1:6.1.1.3.3]
New and replacement ductwork shall comply with Section E 503.4.7.1 through Section E 503.4.7.2.1. [ASHRAE 90.1:6.1.1.3.4]
New and replacement piping shall comply with Section E 503.4.7.1.

Exceptions:

  1. For equipment that is being modified or repaired but not replaced, provided that such modifications or repairs will not result in an increase in the annual energy consumption of the equipment using the same energy type.
  2. Where a replacement or alteration of equipment requires extensive revisions to other systems, equipment, or elements of a building, and such replaced or altered equipment is a like-for-like replacement.
  3. For a refrigerant change of existing equipment.
  4. For the relocation of existing equipment.
  5. For ducts and piping where there is insufficient space or access to comply with these requirements. [ASHRAE 90.1:6.11.3.5]
Section E 503.0 shall be achieved in accordance with the requirements of Section E 503.1.1 through Section E 503.1.3.4, Section E 503.6, Section E 503.7, and one of the following:
  1. Section E 503.3 and Section E 503.3.1
  2. Section E 503.4
  3. Section E 503.4 and Section E 503.8 [ASHRAE 90.1:6.2.1]
Projects using the energy cost budget method in accordance with ASHRAE 90.1 shall comply with Section E 503.4, the mandatory provisions of this section, as a portion of that compliance path. [ASHRAE 90.1:6.2.2]
The simplified approach shall be an optional path for compliance where the following conditions are met:
  1. The building is not more than two stories in height.
  2. Gross floor area is less than 25 000 square feet (2322.6 m2).
  3. The HVAC system in the building is in accordance with the requirements listed in Section E 503.3.1. [ASHRAE 90.1:6.3.1]
The HVAC system shall comply with the following criteria:
  1. The system serves a single HVAC zone.
  2. The equipment shall comply with the variable flow requirements of Section E 503.5.6.2.
  3. Cooling (where any) shall be provided by a unitary packaged or split-system air conditioner that is either air-cooled or evaporatively cooled, with efficiency that is in accordance with the requirements shown in Table E 503.7.1(1), Table E 503.7.1(2), or Table E 503.7.1(4) for the applicable equipment category.
  4. The system shall have an air economizer in accordance with Section E 503.5 and Section E 503.4.6.13.
  5. Heating (where any) shall be provided by a unitary packaged or split-system heat pump that is in accordance with the applicable efficiency requirements shown in Table E 503.7.1(2) or Table E 503.7.1(4), a fuel-fired furnace that is in accordance with the applicable efficiency requirements shown in Table E 503.7.1(5), an electric resistance heater, or a baseboard system connected to a boiler that is in accordance with the applicable efficiency requirements shown in Table E 503.7.1(6).
  6. The system shall comply with the exhaust air energy recovery requirements in accordance with Section E 503.5.10.
  7. The system shall be controlled by a manual changeover or dual setpoint thermostat.
  8. Where a heat pump equipped with auxiliary internal electric resistance heaters is installed, controls shall be provided that prevent supplemental heater operation where the heating load is capable of being met by the heat pump alone during both steady-state operation and setback recovery. Supplemental heater operation shall be permitted during outdoor coil defrost cycles. The heat pump shall be controlled in accordance with one of the following:
    1. A digital or electronic thermostat designed for heat pump use that energizes auxiliary heat where the heat pump has insufficient capacity to maintain setpoint or to warm up the space at a sufficient rate.
    2. A multistage space thermostat and an outdoor air thermostat wired to energize auxiliary heat on the last stage of the space thermostat and where outdoor air temperature is less than 40°F (4°C).

    Exceptions: Heat Pumps that comply with the following:

    1. Have a minimum efficiency regulated by NAECA.
    2. In accordance with the requirements shown in Table E 503.7.1(2).
    3. Include all usage of internal electric resistance heating.
  9. The system controls shall not permit reheat or other form of simultaneous heating and cooling for humidity control.
  10. Systems serving spaces other than hotel or motel guest rooms, and other than those requiring continuous operation, which have both a cooling or heating capacity more than 15 000 Btu/h (4.4 kW) and a supply fan motor power more than 0.75 horsepower (hp) (0.56 kW), shall be provided with a time clock that is in accordance with the following:
    1. Can start and stop the system under different schedules for seven different day-types per week.
    2. Is capable of retaining programming and time setting during a loss of power for a period of not less than 10 hours.
    3. Includes an accessible manual override that allows temporary operation of the system for up to 2 hours.
    4. Is capable of and configured with temperature setback down to 55°F (13°C) during off hours.
    5. Is capable of and configured with temperature setup to 90°F (32°C) during off hours.
  11. Except for piping within manufacturer's units, HVAC piping shall be insulated in accordance with Table E 503.7.3(1) and Table E 503.7.3(2). Insulation exposed to weather shall be suitable for outdoor service (e.g., protected by aluminum, sheet metal, painted canvas, or plastic cover). Cellular foam insulation shall be protected as above or painted with a coating that is water retardant and provides shielding from solar radiation.
  12. Ductwork and plenums shall be insulated in accordance with Table E 503.7.2 and shall be sealed in accordance with Section E 503.4.7.2.
  13. Construction documents shall require a ducted system to be air balanced in accordance with industry-accepted procedures.
  14. Outdoor air intake and exhaust systems shall comply with Section E 503.4.6.4 through Section E 503.4.6.5.
  15. Where separate heating and cooling equipment serves the same temperature zone, thermostats shall be interlocked to prevent simultaneous heating and cooling.
  16. Systems with a design supply air capacity more than 10 000 ft3/min (4.7195 m3/s) shall have optimum start controls.
  17. The system shall comply with the demand control ventilation requirements of Section E 503.4.6.9 and the ventilation design requirements of Section E 503.5.6.6.
  18. The system shall comply with the door switch requirements of Section E 503.5.14. [ASHRAE 90.1:6.3.2]
Climate zones identified in this appendix shall be determined in accordance with ASHRAE 90.1. For locations in the United States and its territories, the assigned climate zone and, where required, the assigned climate zone letter shall be in accordance with ASHRAE 169.

Exception: Where recorded historical climatic data are available for a construction site, it is permitted to be used to determine compliance where approved by the Authority Having Jurisdiction. [ASHRAE 90.1:5.1.4.1]

Equipment shown in Table E 503.7.1(1) through Table E 503.7.1(16) shall have a minimum performance at the specified rating conditions where tested in accordance with the specified test procedure. Where multiple rating conditions or performance requirements are provided, the equipment shall satisfy the stated requirements unless otherwise exempted by footnotes in the table. Equipment covered under the Federal Energy Policy Act of 1992 (EPACT) shall have no minimum efficiency requirements for operation at minimum capacity or other than standard rating conditions. Equipment used to provide service water heating functions as part of a combination system shall satisfy the stated requirements for the appropriate space heating or cooling category.

Tables are as follows:

  1. Table E 503.7.1(1), "Electrically Operated Unitary Air Conditioners and Condensing Units-Minimum Efficiency Requirements"
  2. Table E 503.7.1 (2), "Electrically Operated Unitary and Applied Heat Pumps-Minimum Efficiency Requirements"
  3. Table E 503.7.1 (3), "Water-Chilling Packages-Efficiency Requirements" (See Section E 503.4.1 for water-cooled centrifugal water-chilling packages that are designed to operate at nonstandard conditions.)
  4. Table E 503.7.1 (4), "Electrically Operated Packaged Terminal Air Conditioners, Packaged Terminal Heat Pumps, Single-Package Vertical Air Conditioners, Single-Package Vertical Heat Pumps, Room Air Conditioners, and Room Air Conditioner Heat Pumps-Minimum Efficiency Requirements"
  5. Table E 503.7.1 (5), "Warm-Air Furnaces and Combination Warm-Air Furnaces/Air-Conditioning Units, Warm-Air Duct Furnaces, and Unit Heaters-Minimum Efficiency Requirements" Heating, Ventilating, and Air Conditioning
  6. Table E 503.7.1 (6), "Gas- and Oil-Fired Boilers-Minimum Efficiency Requirements"
  7. Table E 503.7.1 (7), "Performance Requirements for Heat-Rejection Equipment"
  8. Table E 503.7.1 (8), "Heat Transfer Equipment"
  9. Table E 503.7.1 (9), "Electrically Operated Variable-Reffigerant-Flow Air Conditioners- Minimum Efficiency Requirements"
  10. Table E 503.7.1 (10), "Electrically Operated Variable- Refrigerant-Flow and Applied Heat Pumps-Minimum Efficiency Requirements
  11. Table E503.7.1(11), "Air Conditioners and Condensing Units Serving Computer Rooms"
  12. Table E 503.7.1 (12), "Commercial Refrigerators and Freezers-Minimum Efficiency Requirements"
  13. Table E 503.7.1 (13), "Commercial Refrigeration-Minimum Efficiency Requirements"
  14. Table E 503.7.1 (14), "Vapor-Compression-Based Indoor Pool Dehumidifiers-Minimum Efficiency Requirements"
  15. Table E 503.7.1 (15), "Electrically Operated DX-DOAS Units, Single-Package and Remote Condenser, without Energy Recovery-Minimum Efficiency Requirements"
  16. Table E 503.7.1 (16), "Electrically Operated DX-DOAS Units, Single-Package and Remote Condenser, with Energy Recovery-Minimum Efficiency Requirements" [ASHRAE 90.1:6.4.1.1]
Equipment not designed for operation in accordance with AHRI 550/590 test conditions of 44°F (7°C) leaving chilled fluid temperature and 2.4 gallons per minute per ton (gpm/ton) (0.00015 L/s/kg) evaporator fluid flow and 85°F (29°C) entering condenser-fluid temperature with 3.0 gpm/ton (0.00018 L/s/kg) condenser-fluid flow shall have maximum full-load kW/ton (FL) and part-load rating requirements adjusted in accordance with Equation E 503.4.1(1) through Equation E 503.4.1(3):

[Equation E 503.4.1(1)]

FLadj = FL/Kadj        

[Equation E 503.4.1(2)]

PLVadj = IPLV/Kadj      

[Equation E 503.4.1(3)]

Kadj = A × B          

Where:

FL = full-load kW/ton value from Table E 503.7.1(3)
FLadj = maximum full-load kW/ton rating, adjusted for nonstandard conditions
1PLV = IPLV value from Table E 503.7.1(3)
IPLVadj = maximum NPLV rating, adjusted for nonstandard conditions
A = 0.00000014592 × (LIFT)4 — 0.0000346496 × (LIFT)3 + 0.00314196 × (LIFT)2 — 0.147199 × (LIFT) + 3.9302
B = 0.0015 × LvgEvap + 0.934
LIFT = LvgCondLvgEvap
LvgCond = Full-load condenser leaving fluid temperature (°F)
LvgEvap = Full-load evaporator leaving temperature (°F)

The FLadj and PLVadj values shall only be applicable for centrifugal chillers in accordance with the following full-load design ranges:

  1. Minimum Evaporator Leaving Temperature: 36°F (2°C)
  2. Maximum Condenser Leaving Temperature: 115°F (46°C)
  3. LIFT is not less than 20°F (—6°C) and not more than 80°F (27°C)

Manufacturers shall calculate the FLadj and PLVadj before determining whether to label the chiller in accordance with Section E 503.4.4. Chillers that are in accordance with ASHRAE 90.1 shall be labeled on chillers in accordance with the scope of ASHRAE 90.1.

Centrifugal chillers designed to operate outside of these ranges shall not be covered under this appendix.

Example: Path A, 600 ton (600 000 kg) centrifugal chiller Table E 503.7.1(3) efficiencies.

F = 0.560 kW/ton
IPLV = 0.500 kW/ton
LvgCond = 91.16°F
LvgEvap = 42°F
LIFT = 91.16°F-42°F = 49.16°F
Kadj = A × B
A = 0.00000014592 × (49.16)4 —0.0000346496 × (49.16)3 + 0.00314196 × (49.16)2 — 0.147199 × (49.16) + 3.9302 = 1.0228
B = 0.0015 × 42 + 0.934 = 0.9970
FLajd = 0.560/(1.0228 × 0.9970) = 0.549 kW/ton
PLVadj = 0.500/(1.0228 × 0.9970) = 0.490 kW/ton [ASHRAE 90.1:6.4.1.2.1]

For SI units: 1 metric ton = 1000 kg, 1000 British thermal units per hour = 0.293 kW, 1 gallon per minute = 0.06 L/s, °C = (°F—32)/1.8

Equipment with an evaporator leaving fluid temperature more than 32°F (0°C) and water-cooled positive displacement chilling packages with a condenser leaving fluid temperature less than 115°F (46°C) shall be in accordance with Table E 503.7.1(3) where tested or certified with water at standard rating conditions, in accordance with the referenced test procedure. [ASHRAE 90.1:6.4.1.2.2]
Equipment not listed in the tables referenced in Section E 503.4 and Section E 503.4.1 shall be permitted to be used. [ASHRAE 90.1:6.4.1.3]
Equipment efficiency information supplied by manufacturers shall be verified in accordance with one of the following:
  1. Equipment covered under EPACT shall be in accordance with U.S. Department of Energy certification requirements.
  2. Where a certification program exists for a covered product, and it includes provisions for verification and challenge of equipment efficiency ratings, then the product shall be listed in the certification program.
  3. Where a certification program exists for a covered product, and it includes provisions for verification and challenge of equipment efficiency ratings, but the product is not listed in the existing certification program, the ratings shall be verified by an independent laboratory test report.
  4. Where no certification program exists for a covered product, the equipment efficiency ratings shall be supported by data furnished by the manufacturer.
  5. Where components such as indoor or outdoor coils from different manufacturers are used, the system designer shall specify component efficiencies whose combined efficiency is in accordance with the minimum equipment efficiency requirements in Section E 503.4 through Section E 503.4.4.1.
  6. Requirements for plate-type liquid-to-liquid heat exchangers are listed in Table E 503.7.1(8). [ASHRAE 90.1:6.4.1.4]
Mechanical equipment that is not covered by the U.S. National Appliance Energy Conservation Act (NAECA) of 1987 shall carry a permanent label installed by the manufacturer stating that the equipment is in accordance with the requirements of ASHRAE 90.1. [ASHRAE 90.1:6.4.1.5.1]
Nonstandard-size packaged terminal air conditioners and heat pumps with existing sleeves having an external wall opening of less than 16 inches (406 mm) high or less than 42 inches (1067 mm) wide and having a cross-sectional area less than 670 square inches (0.432 m2) shall be factory labeled in accordance with the following:

"Manufactured for nonstandard-size applications only: not to be installed in new construction projects." [ASHRAE 90.1:6.4.1.5.2]

Heating and cooling system design loads for the purpose of sizing systems and equipment shall be determined in accordance with ASHRAE/ACCA 183. [ASHRAE 90.1:6.4.2.1]
Pump differential pressure (head) for the purpose of sizing pumps shall be determined in accordance with generally accepted engineering standards and handbooks acceptable to the Authority Having Jurisdiction. The pressure drop through each device and pipe segment in the critical circuit at design conditions shall be calculated. [ASHRAE 90.1:6.4.2.2]
The supply of heating and cooling energy to each zone shall be individually controlled by thermostatic controls responding to temperature within the zone. For the purposes of Section E 503.4.6, a dwelling unit shall be permitted to be considered a single zone.

Exceptions: Independent perimeter systems that are designed to offset only building envelope loads shall be permitted to serve one or more zones also served by an interior system provided:

  1. the perimeter system includes not less than one thermostatic control zone for each building exposure having walls facing only one orientation for 50 contiguous feet (15 240 mm) or more and
  2. the perimeter system heating and cooling supply is controlled by thermostatic controls located within the zones served by the system.

Exterior walls and semiexterior walls are considered to have different orientations where the exposures they face differ by more than 45 degrees (0.79 rad). [ASHRAE 90.1:6.4.3.1.1]

Where used to control both heating and cooling, zone thermostatic controls shall be capable of and configured to provide a temperature range or dead band of not less than 5°F (3°C) within which the supply of heating and cooling energy to the zone is shut off or reduced to a minimum.

Exceptions:

  1. Thermostats that require manual changeover between heating and cooling modes.
  2. Special occupancy or special applications where wide temperature ranges are not acceptable (such as retirement homes, process applications, museums, some areas of hospitals) and are approved by the Authority Having Jurisdiction. [ASHRAE 90.1:6.4.3.1.2]
Where heating and cooling to a zone are controlled by separate zone thermostatic controls located within the zone, means (such as limit switches, mechanical stops, or, for DDC systems, software programming) shall be provided to prevent the heating setpoint from exceeding the cooling setpoint minus any applicable proportional band. [ASHRAE 90.1:6.4.3.2]
HVAC systems shall have the off-hour controls required by Section E 503.4.6.3.1 through Section E 503.4.6.3.4.

Exceptions:

  1. HVAC systems intended to operate continuously.
  2. HVAC systems having a design heating capacity and cooling capacity less than 15 000 Btu/h (4.4 kW) that are equipped with readily accessible manual ON/OFF controls. [ASHRAE 90.1:6.4.3.3]
HVAC systems shall be equipped with not less than one of the following:
  1. Controls that can start and stop the system under different time schedules for seven different day-types per week, are capable of retaining programming and time setting during loss of power for a period of not less than 10 hours, and include an accessible manual override, or equivalent function, that allows temporary operation of the system for up to 2 hours.
  2. An occupant sensor that is capable of shutting the system off where no occupant is sensed for a period of up to 30 minutes.
  3. A manually operated timer capable of being adjusted to operate the system for up to 2 hours.
  4. An interlock to a security system that shuts the system off where the security system is activated.

Exception: Residential occupancies shall be permitted to use controls that can start and stop the system under two different time schedules per week. [ASHRAE 90.1:6.4.3.3.1]

Heating systems shall be equipped with controls capable of and configured to automatically restart and temporarily operate the system as required to maintain zone temperatures above an adjustable heating setpoint of not less than 10°F (6°C) below the occupied heating setpoint. Cooling systems shall be equipped with controls capable of and configured to automatically restart and temporarily operate the mechanical cooling system as required to maintain zone temperatures below an adjustable cooling setpoint of not less than 5°F (3°C) above the occupied cooling setpoint or to prevent high space humidity levels.

Exception: Radiant heating systems capable of and configured with a setback heating setpoint at not less than 4°F (2°C) below the occupied heating setpoint. [ASHRAE 90.1:6.4.3.3.2]

Individual heating and cooling systems with setback controls and DDC shall have optimum start controls. The control algorithm shall, as a minimum, be a function of the difference between space temperature and occupied setpoint, the outdoor temperature, and the amount of time prior to scheduled occupancy. Mass radiant floor slab systems shall incorporate floor temperature into the optimum start algorithm. [ASHRAE 90.1:6.4.3.3.3]
HVAC systems serving zones that are intended to operate or be occupied nonsimultaneously shall be divided into isolation areas. Zones shall be permitted to be grouped into a single isolation area provided it does not exceed 25 000 square feet (2322.6 m2) of conditioned floor area and does not include more than one floor. Each isolation area shall be equipped with isolation devices capable of and configured to automatically shut off the supply of conditioned air and outdoor air to and exhaust air from the area. Each isolation area shall be controlled independently by a device meeting the requirements of Section E 503.4.6.3.1. For central systems and plants, controls and devices shall be provided to allow stable system and equipment operation for any length of time while serving only the smallest isolation area served by the system or plant.

Exceptions: Isolation devices and controls are not required for the following:

  1. Exhaust air and outdoor air connections to isolation zones where the fan system to which they connect is not more than 5000 ft3/min (2.3597 m3/s).
  2. Exhaust airflow from a single isolation zone of less than 10 percent of the design airflow of the exhaust system to which it connects.
  3. Zones intended to operate continuously or intended to be inoperative only when all other zones are inoperative. [ASHRAE 90.1:6.4.3.3.4]
Stair and elevator shaft vents shall be equipped with motorized dampers that are capable of and configured to automatically close during normal building operation and are interlocked to open as required by fire and smoke detection systems. [ASHRAE 90.1:6.4.3.4.1]
Outdoor air intake and exhaust systems shall be equipped with motorized dampers that will automatically shut when the systems or spaces served are not in use. Ventilation outdoor air and exhaust or relief dampers shall be capable of and configured to automatically shut off during preoccupancy building warm-up, cooldown, and setback, except when ventilation reduces energy costs or when ventilation shall be supplied to comply with the code requirements.

Exceptions:

  1. Backdraft gravity (nonmotorized) dampers shall be permitted for exhaust and relief in buildings less than three stories in height and for ventilation air intakes and exhaust and relief dampers in buildings of any height located in Climate Zones 0, 1, 2 and 3. Back-draft dampers for ventilation air intakes shall be protected from direct exposure to wind.
  2. Back-draft gravity (nonmotorized) dampers shall be permitted in systems with a design outdoor air intake or exhaust capacity of 300 ft3/min (0.142 m3/s) or less.
  3. Dampers shall not be required in ventilation or exhaust systems serving unconditioned spaces.
  4. Dampers shall not be required in exhaust systems serving Type 1 kitchen exhaust hoods. [ASHRAE 90.1:6.4.3.4.2]
Where outdoor air supply, and exhaust or relief dampers are required in Section E 503.4.6.4, they shall have a maximum leakage rate in accordance with Table E 503.4.6.4.2 where tested in accordance with AMCA 500D. [ASHRAE 90.1:6.4.3.4.3]

TABLE E 503.4.6.4.2 MAXIMUM DAMPER LEAKAGE (cubic foot per minute per square foot) at 1.0 in. w.g
[ASHRAE 90.1:TABLE 6.4.3.4.3]

VENTILATION AIR INTAKE EXHAUST/RELIEF
CLIMATE ZONE NONMOTORIZED* MOTORIZED NONMOTORIZED* MOTORIZED
0, 1, 2
any height 20 4 20 4
3
any height 20 10 20 10
4, 5b, 5c
less than 3 stories not allowed 10 20 10
3 or more stories not allowed 10 not allowed 10
5a, 6, 7, 8
less than 3 stories not allowed 4 20 4
3 or more stories not allowed 4 not allowed 4

For SI units: 1 cubic foot per minute = 0.00047 m3/s, 1 square foot = 0.0929 m2, 1 inch water gauge = 0.249 kPa

* Dampers smaller than 24 inches (610 mm) in either dimension shall be permitted to have leakage of 40 ft3/min per square foot [0.203 (m3/s)/m2].

Fans with motors more than 0.75 hp (0.56 kW) shall have automatic controls in accordance with Section E 503.4.6.3.1 that are capable of and configured to shut off fans when not required.

Exception: HVAC systems intended to operate continuously. [ASHRAE 90.1:6.4.3.4.4]

Enclosed parking garage ventilation systems shall automatically detect contaminant levels and stage fans or modulate fan airflow rates to 50 percent or less of design capacity, provided acceptable contaminant levels are maintained.

Exceptions:

  1. Garages not more than 30 000 square feet (2787.09 m2) with ventilation systems that do not utilize mechanical cooling or mechanical heating.
  2. Garages that have a garage area to ventilation system motor nameplate hp ratio that exceeds 1500 square feet per horsepower (ft2/hp) (186.8 m2/kW) and do not utilize mechanical cooling or heating.
  3. Where not permitted by the Authority Having Jurisdiction. [ASHRAE 90.1:6.4.3.4.5]
Heat pumps equipped with internal electric resistance heaters shall have controls that prevent supplemental heater operation where the heating load is capable of being met by the heat pump alone during both steady-state operation and setback recovery. Supplemental heater operation shall be permitted during outdoor coil defrost cycles.

Exception: Heat pumps whose minimum efficiency is regulated by U.S. National Appliance Energy Conservation Act (NAECA) and whose ratings are in accordance with the requirements shown in Table E 503.7.1(2) and includes the use of an internal electric resistance heating. [ASHRAE 90.1:6.4.3.5]

Humidity control shall prevent the use of fossil fuel or electricity to produce relative humidity (RH) more than 30 percent in the warmest zone served by the humidification system and to reduce the RH valve to less than 60 percent in the coldest zone served by the dehumidification system. Where a zone is served by a system or systems with both humidification and dehumidification capability, means (such as limit switches, mechanical stops, or, for DDC systems, software programming) shall be provided capable of preventing simultaneous operation of humidification and dehumidification equipment.

Exceptions:

  1. Zones served by desiccant systems used with direct evaporative cooling in series.
  2. Systems serving zones where specific humidity levels are required, such as museums and hospitals, and approved by the Authority Having Jurisdiction or required by accreditation standards and humidity controls are configured to maintain a deadband of not less than 10 percent RH where no active humidification or dehumidification takes place.
  3. Systems serving zones where humidity levels are required to be maintained with precision of not more than ± 5 percent RH to comply with applicable codes or accreditation standards or as approved by the Authority Having Jurisdiction. [ASHRAE 90.1:6.4.3.6]
Freeze protection systems, such as heat tracing of outdoor piping and heat exchangers, including self-regulating heat tracing, shall include automatic controls capable of and configured to shut off the systems when outdoor air temperatures are more than 40°F (4°C) or when the conditions of the protected fluid will prevent freezing. Snow and ice melting systems shall include automatic controls capable of and configured to shut off the systems when the pavement temperature is more than 50°F (10°C) and no precipitation is falling, and an automatic or manual control that will allow shutoff when the outdoor temperature is more than 40°F (4°C) so that the potential for snow or ice accumulation is negligible. [ASHRAE 90.1:6.4.3.7]
Demand control ventilation (DCV) shall be required for spaces that are more than 500 square feet (46.45 m2) and with a design occupancy for ventilation of not less than 25 people per 1000 square feet (92.9 m2) of floor area and served by systems with one or more of the following:
  1. Air-economizer.
  2. Automatic modulating control of outdoor air damper.
  3. Design outdoor airflow more than 3000 ft3/min (1.4158 m3/s).

Exceptions:

  1. Systems with exhaust air energy recovery in accordance with Section E 503.5.10.
  2. Multiple-zone systems without DDC of individual zones communicating with a central control panel.
  3. Systems with a design outdoor airflow less than 750 ft3/min (0.3540 m3/s).
  4. Spaces where more than 75 percent of the space design outdoor airflow is required for makeup air that is exhausted from the space or transfer air that is required for makeup air that is exhausted from other spaces.
  5. Spaces with one of the following occupancy categories in accordance with Chapter 4 or ASHRAE 62.1: correctional cells, daycare sickrooms, science labs, barbers, beauty and nail salons, and bowling alley seating. [ASHRAE 90.1:6.4.3.8]

E 503.4.6.10 Outdoor Heating. Radiant heat systems shall be used to provide heat outdoors. Outdoor radiant heating systems shall be provided with controls that sense the presence of occupants or other device that automatically shuts down the system where no occupants are in the heating area.

E 503.4.6.11 Heated or Cooled Vestibules. Heating for vestibules and for air curtains with integral heating shall include automatic controls capable of and configured to shut off the heating system when outdoor air temperatures are more than 45°F (7.2°C) Vestibule heating and cooling systems shall be controlled by a thermostat in the vestibule capable of and configured to limit heating to a maximum of 60°F (15.5°C) and cooling to a minimum of 85°F (29.4°C).

Exception: Heating or cooling provided by site-recovered energy or by transfer air that would otherwise be exhausted. [ASHRAE 90.1:6.4.3.9]

E 503.4.6.12 Direct Digital Control (DDC) Requirements. Direct digital control shall be required in accordance with Section E 503.4.6.12.1 through Section E 503.4.6.12.3. [ASHRAE 90.1:6.4.3.10]

E 503.4.6.12.1 DDC Applications. DDC shall be provided in the applications and qualifications in accordance with Table E 503.4.6.12.1.

Exception: DDC is not required for systems using the simplified approach to compliance in accordance with Section E 503.3. [ASHRAE 90.1:6.4.3.10.1]

TABLE E 503.4.6.12.1 DDC APPLICATIONS AND QUALIFICATIONS
[ASHRAE 90.1:6.4.3.10.1]

BUILDING STATUS APPLICATION QUALIFICATIONS
New building Air-handling system and all zones served by the system Individual systems supplying more than three zones and with fan system bhp of 10 hp or more
New building Chilled-water plant and all coils and terminal units served by the system Individual plants supplying more than three zones and with design cooling capacity of 300 000 Btu/h or more
New building Hot-water plant and all coils and terminal units served by the system Individual plants supplying more than three zones and with design heating capacity of 300 000 Btu/h or more
Alteration or addition Zone terminal unit such as VAV box Where existing zones served by the same air-handling, chilled-water, or hot-water system have DDC
Alteration or addition Air-handling system or fan coil Where existing air-handling system(s) and fan-coil (s) served by the same chilled- or hot-water plant have DDC
Alteration or addition New air-handling system and all new zones served by the system Individual systems with fan system bhp of 10 hp or more and supplying more than three zones and more than 75 percent of zones are new
Alteration or addition New or upgraded chilled-water plant Where all chillers are new and plant design cooling capacity is 300 000 Btu/h or more
Alteration or addition New or upgraded hot-water plant Where all boilers are new and plant design heating capacity is 300 000 Btu/h or more

For SI units: 1000 British thermal units = 0.293 kW, 1 horsepower = 0.746 kW

E 503.4.6.12.2 DDC Controls. Where DDC is required by Section E 503.4.6.12.1, the DDC system shall be capable of and configured with all of the following, as required, to provide the control logic required in Section E 503.5:

  1. Monitoring zone and system demand for fan pressure, pump pressure, heating, and cooling.
  2. Transferring zone and system demand information from zones to air distribution system controllers and from air distribution systems to heating and cooling plant controllers.
  3. Automatically detecting those zones and systems that are capable of excessively driving the reset logic and generate an alarm or other indication to the system operator.
  4. Readily allowing operator removal of zone(s) from the reset algorithm. [ASHRAE 90.1:6.4.3.10.2]

E 503.4.6.12.3 DDC Display. Where DDC is required in accordance with Section E 503.4.6.12.1 for new buildings, the DDC system shall be capable of trending and graphically displaying input and output points. [ASHRAE 90.1:6.4.3.10.3]

E 503.4.6.13 Economizer Fault Detection Diagnostics (FDD). Air-cooled direct-expansion cooling units listed in Tables E 503.7.1(1) and E 503.7.1(2), where an air economizer is installed in accordance with Section E 503.5, shall include a fault detection and diagnostics (FDD) system complying with the following:

  1. The following temperature sensors shall be permanently installed to monitor system operation:
    1. Outdoor air
    2. Supply air
    3. Return air, where required for economizer control
  2. The system shall have the capability of displaying the value of each sensor.
  3. The FDD system or unit controls shall be capable of and configured to provide system status by indicating the following:
    1. Free cooling available
    2. Economizer enabled
    3. Compressor enabled
    4. Heating enabled
    5. Mixed-air low-limit cycle active
  4. The FDD system or unit controls shall have provisions to manually initiate each operating mode so that the operation of compressors, economizers, fans, and the heating system can be independently tested and verified.
  5. The FDD system shall be capable of and configured to detect the following faults:
    1. Air temperature sensor failure/fault
    2. Not economizing when the unit should be economizing
    3. Economizing when the unit should not be economizing
    4. Damper not modulating
    5. Excess outdoor air
  6. The FDD system shall be capable of and configured to report faults to a fault management application or DDC system accessible by operating or service personnel, or annunciated locally on zone thermostats. [ASHRAE 90.1: 6.4.3.12]
HVAC Ducts shall be constructed in accordance with provisions contained in the SMACNA HVAC Duct Construction Standard. HVAC system construction and insulation shall comply with Section E 503.4.7.1 and Section E 503.4.7.2.
Insulation required by this section shall be installed in accordance with industry-accepted standards. These requirements shall not apply to HVAC equipment. Insulation shall be protected from damage, including that due to sunlight, moisture, equipment maintenance, and wind, but not limited to the following:
  1. Insulation exposed to weather shall be suitable for outdoor service (e.g., protected by aluminum, sheet metal, painted canvas, or plastic cover). Cellular foam insulation shall be protected as above or painted with a coating that is water retardant and provides shielding from solar radiation that is capable of causing degradation of the material.
  2. Insulation covering chilled-water piping, refrigerant suction piping, or cooling ducts located outside the conditioned space shall include a vapor retardant located outside the insulation (unless the insulation is inherently vapor retardant), penetrations and joints of which shall be sealed. [ASHRAE 90.1:6.4.4.1.1]
Supply and return ducts and plenums installed as part of an HVAC air distribution system shall be thermally insulated in accordance with Table E 503.7.2.

Exceptions:

  1. Factory-installed plenums, casings, or ductwork furnished as a part of HVAC equipment tested and rated in accordance with Section E 503.4 through Section E 503.4.4.1.
  2. Ducts or plenums located in heated spaces, semi-heated spaces, or cooled spaces.
  3. For runouts less than 10 feet (3048 mm) in length to air terminals or air outlets, the rated R-value of insulation shall not be required to exceed R-3.5.
  4. Backs of air outlets and outlet plenums exposed to unconditioned or indirectly conditioned spaces with face areas exceeding 5 square feet (0.5 m2) shall not be required to exceed R-2; those not exceeding 5 square feet (0.5 m2) shall not be required to be insulated. [ASHRAE 90.1:6.4.4.1.2]
Piping shall be thermally insulated in accordance with Table E 503.7.3(1) and Table E 503.7.3(2).

Exceptions:

  1. Factory-installed piping within HVAC equipment tested and rated in accordance with Section E 503.4 through Section E 503.4.4.1.
  2. Piping that conveys fluids having a design operating temperature range between 60°F (16°C) and 105°F (41°C), inclusive.
  3. Piping that conveys fluids that have not been heated or cooled through the use of fossil fuels or electricity (such as roof and condensate drains, domestic cold water supply, or natural gas piping).
  4. Where heat gain or heat loss will not increase energy usage (such as liquid refrigerant piping).
  5. For piping 1 inch (25.4 mm) or less, insulation shall not be required for strainers, control valves, and balancing valves. [ASHRAE 90.1:6.4.4.1.3]
Thermally ineffective panel surfaces of sensible heating panels, including U-bends and headers, shall be insulated with not less than R-3.5. Adjacent building envelope insulation shall be applied to this insulation value. [ASHRAE 90.1:6.4.4.1.4]
The bottom surfaces of floor structures incorporating radiant heating shall be insulated not less than R-3.5. Adjacent building envelope insulation shall be applied to this insulated value.

Exception: Heated slab-on-grade floors incorporating radiant heating shall be in accordance with ASHRAE 90.1. [ASHRAE 90.1:6.4.4.1.5]

Transverse joints, longitudinal seams, and duct wall penetrations shall be sealed. Pressure-sensitive tape shall not be used as the primary sealant, unless it has been certified to comply with UL 181A or UL 181B by an independent testing laboratory and the tape is used in accordance with that certification. All other connections shall be considered transverse joints, including but not limited to spin-ins, taps, other branch connections, access door frames and jambs, and duct connections to equipment.

Exceptions:

  1. Rods that penetrate the duct wall that shall be permitted to move in order to function properly (control rod for volume damper) shall not be sealed in a fashion that prevents them from working properly.
  2. Spiral lock seams in a round or flat oval duct.
Ductwork shall be leak-tested in accordance with the SMACNA HVAC Air Duct Leakage Test Manual. Representative sections totaling not less than 20 percent of the total installed duct area shall be tested. Where the tested 20 percent fail to comply with the requirements of this section, then 40 percent of the total installed duct area shall be tested. Where the tested 40 percent fail to comply with the requirements of this section, then 100 percent of the total installed duct area shall be tested. Sections shall be selected by the building owner or designated representative of the building owner. Positive pressure leakage testing shall be permitted for negative pressure ductwork. The permitted duct leakage shall be not more than the following:
Lmax = CLP0.65 (Equation E 503.4.7.2.1)

Where:

Lmax = maximum permitted leakage, (ft3/min)/100 square feet [0.0001 (m3/s)/m2] duct surface area.
CL = Six, duct leakage class, (ft3/min)/l00 square feet [0.0001 (m3/s)/m2] duct surface area at 1 inch water column (0.2 kPa).
P = test pressure, which shall be equal to the design duct pressure class rating, inch water column (kPa).
Cooling systems shall include either an air economizer or fluid economizer in accordance with Section E 503.5.1 through Section E 503.5.4.1.

Exceptions: Economizers shall not be required for the following systems:

  1. Individual fan-cooling units with a supply capacity less than the minimum listed in Table E 503.5(1).
  2. Chilled-water cooling systems without a fan or that use induced airflow, where the total capacity of these systems is less than 1 000 000 Btu/h (293 kW) in Climate Zones 0, 1B, and 2 through 4; less than 1 400 000 Btu/h (410 kW) in Climate Zones 5 through 8; or any size in Climate Zone 1A.
  3. Systems that include nonparticulate air treatment in accordance with ASHRAE 62.1.
  4. In hospitals and ambulatory surgery centers, where more than 75 percent of the air designed to be supplied by the system is to spaces that are required to be humidified more than 35°F (2°C) dew-point temperature to comply with applicable codes or accreditation standards; in all other buildings, where more than 25 percent of the air designed to be supplied by the system is to spaces that are designed to be humidified more than 35°F (2°C) dewpoint temperature to satisfy process needs. This exception shall not apply to computer rooms.
  5. Systems that include a condenser heat recovery system with a minimum capacity in accordance with Section E 503.5.10.1.2.
  6. Systems that serve residential spaces where the system capacity is less than five times the requirement listed in Table E 503.5(1).
  7. Systems that serve spaces whose sensible cooling load at design conditions, excluding transmission and infiltration loads, is less than or equal to transmission and infiltration losses at an outdoor temperature of 60°F (16°C).
  8. Systems expected to operate less than 20 hours per week.
  9. Where the use of outdoor air for cooling will affect supermarket open refrigerated casework systems.
  10. For comfort cooling where the cooling efficiency is not less than the efficiency improvement requirements in accordance with Table E 503.5(2).
  11. Systems primarily serving computer rooms where in accordance with one of the following:
    1. The total design cooling load of all computer rooms in the building is less than 3 000 000 Btu/h (879 kW) and the building in which they are located is not served by a centralized chilled water plant.
    2. The room total design cooling load is less than 600 000 Btu/h (176 kW) and the building in which they are located is served by a centralized chilled water plant.
    3. The local water authority does not permit cooling towers.
    4. Less than 600 000 Btu/h (176 kW) of computer room cooling equipment capacity is being added to an existing building.
  12. Dedicated systems for computer rooms where a minimum of 75 percent of the design load serves one of the following:
    1. Spaces classified as an essential facility.
    2. Spaces having a design of Tier IV in accordance with TIA 942.
    3. Spaces classified as Critical Operations Power Systems (COPS) in accordance with NFPA 70.
    4. Spaces where core clearing and settlement services are performed such that their failure to settle pending financial transactions is capable of systemic risk in accordance with "The Interagency Paper on Sound Practices to Strengthen the Resilience of the US Financial System" (April 7, 2003). [ASHRAE 90.1:6.5.1]

TABLE E 503.5(1) MINIMUM FAN-COOLING UNIT SIZE WHERE AN ECONOMIZER IS REQUIRED
[ASHRAE 90.1:TABLE 6.5.1-1]

CLIMATE ZONES COOLING CAPACITY WHERE AN ECONOMIZER IS REQUIRED
0A, 0B, 1A, 1B No economizer requirement
2A, 2B, 3A, 4A, 5A, 6A, 3B, 3C, 4B, 4C, 5B, 5C, 6B, 7, 8 ≥54 000 Btu/h

For SI units: 1000 British thermal units per hour = 0.293 kW

TABLE E 503.5(2) ELIMINATE REQUIRED ECONOMIZER FOR COMFORT COOLING BY INCREASING COOLING EFFICIENCY
[ASHRAE 90.1:TABLE 6.5.1-2]

CLIMATE ZONES EFFICIENCY IMPROVEMENT*
2A 17%
2B 21%
3A 27%
3B 32%
3C 65%
4A 42%
4B 49%
4C 64%
5A 49%
5B 59%
5C 74%
6A 56%
6B 65%
7 72%
8 77%

* Where a unit is rated with an IPLV, IEER or SEER, to eliminate the required economizer, the minimum cooling efficiency of the HVAC unit shall be increased by the percentage shown. Where the HVAC unit is rated with a full load metric like EER cooling, these shall be increased by the percentage shown.

Air economizer systems shall be capable of and configured to modulate outdoor air and return air dampers to provide up to 100 percent of the design supply air quantity as outdoor air for cooling. [ASHRAE 90.1:6.5.1.1.1]
Economizer controls shall be capable of and configured to sequence the dampers with the mechanical cooling equipment and shall not be controlled by only mixed air temperature.

Exception: The use of mixed air temperature limit control shall be permitted for systems controlled from space temperature (such as single-zone systems). [ASHRAE 90.1:6.5.1.1.2]

Air economizers shall be capable of and configured to automatically reduce outdoor air intake to the design minimum outdoor air quantity where outdoor air intake will no longer reduce cooling energy use. High-limit shutoff control types and associated setpoints for specific climate zones shall be chosen from Table E 503.5.1.2. [ASHRAE 90.1:6.5.1.1.3]
Return air, exhaust or relief, and outdoor air dampers shall comply with Section E 503.4.6.4.2. [ASHRAE 90.1:6.5.1.1.4]
Systems shall provide a means to relieve excess outdoor air during air economizer operation to prevent over-pressurizing the building. The relief air outlet shall be located to avoid recirculation into the building. [ASHRAE 90.1:6.5.1.1.5]
Outdoor air, return air, mixed air, and supply air sensors shall be calibrated within the following accuracies:
  1. Dry-bulb and wet-bulb temperatures shall be accurate to ±2°F (1.1°C) over the range of 40°F (4.4°C) to 80°F (27°C).
  2. Enthalpy and the value of a differential enthalpy sensor shall be accurate to ±3 Btu/lb (7 E+03 J/kg) over the range of 20 Btu/lb (4.6 E+04 J/kg) to 36 Btu/lb (8.4 E+04 J/kg).
  3. Relative humidity shall be accurate to ±5 percent over the range of 20 percent to 80 percent relative humidity. [ASHRAE 90.1:6.5.1.1.6]
Fluid economizer systems shall be capable of providing up to 100 percent of the expected system cooling load at outdoor air temperatures of not more than 50°F (10°C) dry bulb or 45°F (7°C) wet bulb.

Exceptions:

  1. Systems primarily serving computer rooms in which 100 percent of the expected system cooling load at the dry bulb and wet bulb temperatures in accordance with Table E 503.5.2 is met with water-cooled fluid economizers.
  2. Systems primarily serving computer rooms in which 100 percent of the expected system cooling load at the dry bulb temperatures listed in Table E 503.5.2 is met with air-cooled fluid economizers.
  3. Systems where dehumidification requirements are not capable of being met using outdoor air temperatures of 50°F (10°C) dry bulb or 45°F (7°C) wet bulb and where 100 percent of the expected system cooling load at 45°F (7°C) dry bulb or 40°F (4°C) wet bulb is met with water-cooled fluid economizers. [ASHRAE 90.1:6.5.1.2.1]

Units that include an air economizer shall comply with the following:

  1. Unit controls shall have the mechanical cooling capacity control interlocked with the air economizer controls such that the outdoor air damper is at the 100 percent open position when mechanical cooling is on, and the outdoor air damper does not begin to close to prevent coil freezing due to minimum compressor run time until the leaving air temperature is less than 45°F (7°C).
  2. DX units with a rated capacity no less than 65 000 Btu/h (18 kW) that control the capacity of the mechanical cooling directly based on occupied space temperature shall have not less than two stages of mechanical cooling capacity.
  3. Other DX units, including those that control space temperature by modulating the airflow to the space, shall comply with the requirements of Table E 503.5.3. [ASHRAE 90.1:6.5.1.3]

TABLE E 503.5.3 DX COOLING STAGE REQUIREMENTS FOR MODULATING AIRFLOW UNITS
[ASHRAE 90.1:6.5.1.3]

RATING CAPACITY, Btu/h MINIMUM NUMBER OF MECHANICAL COOLING STAGES MINIMUM COMPRESSOR DISPLACEMENT*
≥65 000 and <240 000 3 ≤35% of full load
≥240 000 4 ≤25% full load

For SI units: 1000 British thermal units = 0.293 kW

* For mechanical cooling stage control that does not use variable compressor displacement the percent displacement shall be equivalent to the mechanical cooling capacity reduction evaluated at the full load rating conditions for the compressor.

HVAC system design and economizer controls shall be such that economizer operation does not increase the building heating energy use during normal operation.

Exception: Economizers on variable air valve (VAV) systems that cause zone level heating to increase due to a reduction in supply air temperature. [ASHRAE 90.1:6.5.1.4]

Systems with hydronic cooling and humidification systems designed to maintain inside humidity at a dew-point temperature more than 35°F (2°C) shall use a fluid economizer where an economizer is required in accordance with Section E 503.5 through Section E 503.5.4.1. [ASHRAE 90.1:6.5.1.5]
Zone thermostatic controls shall prevent the following:
  1. Reheating.
  2. Recooling.
  3. Mixing or simultaneously supplying air that has been previously mechanically heated and air that has been previously cooled, either by mechanical cooling or by economizer systems.
  4. Other simultaneous operation of heating and cooling systems to the same zone.

Exceptions:

  1. Zones for which the volume of air that is reheated, recooled, or mixed is less than the larger of the following:
    1. Twenty percent of the zone design peak supply for systems with DDC and 30 percent for other systems.
    2. The outdoor airflow rate required to be in accordance with the ventilation requirements of Chapter 4 or ASHRAE 62.1 for the zone.
    3. A higher rate that is capable of demonstrating, to the satisfaction of the Authority Having Jurisdiction, to reduce overall system annual energy usage by offsetting reheat or recool energy losses through a reduction in outdoor air intake for the system.
    4. The airflow rate required to be in accordance with applicable codes or accreditation standards, such as pressure relationships or minimum air change rates.
  2. Zones with DDC that comply with the following:
    1. The airflow rate in dead band between heating and cooling does not exceed the larger of the following:
      1. Twenty percent of the zone design peak supply rate.
      2. The outdoor airflow rate required to be in accordance with the ventilation requirements of Chapter 4 or ASHRAE 62.1 for the zone.
      3. A higher rate that is capable of demonstrating, to the satisfaction of the Authority Having Jurisdiction, to reduce overall system annual energy usage by offsetting reheat or recool energy losses through a reduction in outdoor air intake.
      4. The airflow rate required in accordance with applicable codes or accreditation standards, such as pressure relationships or minimum air change rates.
    2. The airflow rate that is reheated, recooled, or mixed shall be less than 50 percent of the zone design peak supply rate.
    3. The first stage of heating consists of modulating the zone supply air temperature setpoint up to a maximum setpoint while the airflow is maintained at the dead band flow rate.
    4. The second stage of heating consists of modulating the airflow rate from the dead band flow rate up to the heating maximum flow rate.
  3. Laboratory exhaust systems in accordance with Section E 503.5.11.3.
  4. Zones where not less than 75 percent of the energy for reheating or for providing warm air in mixing systems is provided from a site-recovered (including condenser heat) or site-solar energy source. [ASHRAE 90.1:6.5.2.1]
Where reheating is permitted in accordance with this appendix, zones that have both supply and return or exhaust air openings more than 6 feet (1829 mm) above the floor shall not supply heating air more than 20°F (11°C) above the space temperature setpoint.

Exceptions:

  1. Laboratory exhaust systems in accordance with Section E 503.5.11.3.
  2. During preoccupancy building warm-up and setback. [ASHRAE 90.1:6.5.2.1.1]
The heating of fluids in hydronic systems that have been previously mechanically cooled and the cooling of fluids that have been previously mechanically heated shall be limited in accordance with Section E 503.5.5.2.1 through Section E 503.5.5.2.3. [ASHRAE 90.1:6.5.2.2]
Hydronic systems that use a common return system for both hot water and chilled water shall not be used. [ASHRAE 90.1:6.5.2.2.1]
Systems that use a common distribution system to supply both heated and chilled water are acceptable where in accordance with the following:
  1. The system is designed to allow a dead band between changeover from one mode to the other of not less than 15°F (8°C) outdoor air temperature.
  2. The system is designed to operate and is provided with controls that will allow operation in one mode for not less than 4 hours before changing over to the other mode.
  3. Reset controls are provided that allow heating and cooling supply temperatures at the changeover point to be not more than 30°F (17°C) apart. [ASHRAE 90.1:6.5.2.2.2]
Hydronic heat pumps connected to a common heat pump water loop with central devices for heat rejection (e.g., cooling tower) and heat addition (e.g., boiler) shall have the following:
  1. Controls that are capable of and configured to provide a heat pump water supply temperature dead band of not less than 20°F (11°C) between initiation of heat rejection and heat addition by the central devices (e.g., tower and boiler).
  2. For climate zone 3 through zone 8, where a closed-circuit tower (fluid cooler) is used, either an automatic valve shall be installed to bypass all but a minimal flow of water around the tower (for freeze protection) or low-leakage positive closure dampers shall be provided. Where an open-circuit tower is used directly in the heat pump loop, an automatic valve shall be installed to bypass heat pump water flow around the tower. Where an open-circuit tower is used in conjunction with a separate heat exchanger to isolate the tower from the heat pump loop, then heat loss shall be controlled by shutting down the circulation pump on the cooling tower loop.

Exception: Where a system loop temperature optimization controller is used to determine the most efficient operating temperature based on real-time conditions of demand and capacity, dead bands of less than 20°F (11°C) shall be permitted. [ASHRAE 90.1:6.5.2.2.3]

Where humidity controls are provided, such controls shall prevent reheating, mixing of hot and cold airstreams, or other means of simultaneous heating and cooling of the same airstream.

Exceptions:

  1. The system is capable of and configured to reduce supply air volume to 50 percent or less of the design airflow rate or the minimum outdoor air ventilation rate in accordance with ASHRAE 62.1 or other applicable federal, state, or local code or recognized standard, whichever is larger before simultaneous heating and cooling takes place.
  2. The individual fan cooling unit has a design cooling capacity of not more than 65 000 Btu/h (19 kW) and is capable of and configured to unload to 50 percent capacity before simultaneous heating and cooling takes place.
  3. The individual mechanical cooling unit has a design cooling capacity of not more than 40 000 Btu/h (11.7 kW). An individual mechanical cooling unit is a single system composed of a fan or fans and a cooling coil capable of providing mechanical cooling.
  4. Systems serving spaces where specific humidity levels are required to satisfy process needs, such as vivariums, museums, surgical suites, pharmacies, and buildings with refrigerating systems, such as supermarkets, refrigerated warehouses, and ice arenas, and where the building includes site-recovered energy or site solar energy that provide energy equal to 75 percent or more of the annual energy for reheating or for providing warm air in mixing systems. This exception shall not apply to computer rooms.
  5. Not less than 90 percent of the annual energy for reheating or for providing warm air in mixing systems is provided from site-recovered energy (including condenser heat) or site-solar energy.
  6. Systems where the heat added to the airstream is the result of the use of a desiccant system and 75 percent of the heat added by the desiccant system is removed by a heat exchanger, either before or after the desiccant system with energy recovery. [ASHRAE 90.1:6.5.2.3]
Humidifiers with preheating jackets mounted in the airstream shall be provided with an automatic valve to shut off preheat where humidification is not required. [ASHRAE 90.1:6.5.2.4.1]
Humidification system dispersion tube hot surfaces in the airstreams of ducts or air-handling units shall be insulated with a product with an insulating value of not less than R-0.5.

Exception: Systems where mechanical cooling, including economizer operation, does not occur simultaneously with humidification. [ASHRAE 90.1:6.5.2.4.2]

Preheat coils shall have controls that stop their heat output where mechanical cooling, including economizer operation, is occurring. [ASHRAE 90.1:6.5.2.5]
HVAC air system design and control shall be in accordance with the provisions of Section E 503.5.6.1 through Section E 503.5.6.6.
Each HVAC system having a total fan system motor nameplate horsepower (kW) exceeding 5 hp (3.7 kW) at fan system design conditions shall not exceed the allowable fan system motor nameplate horsepower (kW) (Option 1) or fan system brake horsepower (kW) (Option 2) as shown in Table E 503.5.6.1(1). This shall include supply fans, return or relief fans, exhaust fans, and fan-powered terminal units associated with systems providing heating or cooling capability that operate at fan system design conditions. Single-zone VAV systems shall comply with the constant-volume fan power limitation.

Exceptions:

  1. Hospital, vivarium, and laboratory systems that utilize flow control devices on exhaust, return, or both to maintain space pressure relationships necessary for occupant health and safety, or environmental control shall be permitted to use variable-volume fan power limitation.
  2. Individual exhaust fans with motor nameplate horsepower of 1 hp (0.7 kW) or less. [ASHRAE 90.1:6.5.3.1.1]
For each fan, the selected fan motor shall be not larger than the first available motor size more than the brake horsepower (bhp) (kW). The fan brake horsepower shall be indicated on the design documents to allow for compliance verification by the Authority Having Jurisdiction.

TABLE E 503.5.6.1(1) FAN POWER LIMITATION*
[ASHRAE 90.1:TABLE 6.5.3.1-1]

LIMIT CONSTANT VOLUME VARIABLE VOLUME
Option 1: Fan system motor nameplate (hp) Allowable nameplate motor (hp) hpCFMS • 0.0011 hpCFMS• 0.0015
Option 2: Fan system (bhp) Allowable fan system (bhp) bhpCFMS • 0.00094 + A bhpCFMS• 0.0013 + A

For SI units: 1 horsepower = 0.746 kW, 1 cubic foot per minute = 0.00047 m3/s

* Where:

CFMS = the maximum design supply airflow rate to conditioned spaces served by the system in cubic feet per minute (m3/s)
hp = the maximum combined motor nameplate horsepower (kW)
bhp = the maximum combined fan brake horsepower (kW)
A = sum of (PD × CFMD/4131)
PD = each applicable pressure drop adjustment from Table E 503.5.6.1(2) in inch water column (kPa)
CFMD = the design airflow through each applicable device from Table E 503.5.6.1(2) in cubic feet per minute (m3/s)

Exceptions:

  1. For fans less than 6 bhp (4.5 kW), where the first available motor larger than the bhp (kW) has a nameplate rating within 50 percent of the bhp (kW), the next larger nameplate motor size shall be selected.
  2. For fans 6 bhp (4.5 kW) and larger, where the first available motor larger than the bhp (kW) has a nameplate rating within 30 percent of the bhp (kW), the next larger nameplate motor size shall be selected.
  3. Systems that are in accordance with Section E 503.5.6.1, Option 1.
  4. Fans with motor nameplate horsepower of less than 1 hp (0.7 kW). [ASHRAE 90.1:6.5.3.1.2]
Fans shall have a fan efficiency grade (FEG) of 67 or more, based on manufacturers' certified data in accordance with AMCA 205. The total efficiency of the fan at the design point of operation shall be within 15 percentage points of the maximum total efficiency of the fan.

Exceptions:

  1. Individual fans with a motor nameplate horsepower of 5 hp (3.7 kW) or less that are not part of a group operated as the functional equivalent of a single fan.
  2. Multiple fans in series or parallel (e.g., fan arrays) that have a combined motor nameplate horsepower of 5 hp (3.7 kW) or less and are operated as the functional equivalent of a single fan.
  3. Fans that are part of equipment listed under Section E 503.4.
  4. Fans included in equipment bearing a third party-certified seal for air or energy performance of the equipment package.
  5. Powered wall/roof ventilators (PRV).
  6. Fans outside the scope of AMCA 205.
  7. Fans that are intended to only operate during emergency conditions. [ASHRAE 90.1:6.5.3.1.3]

TABLE E 503.5.6.1(2) FAN POWER LIMITATION PRESSURE DROP ADJUSTMENT
[ASHRAE 90.1:TABLE 6.5.3.1-2]

DEVICE ADJUSTMENT
CREDITS
Return or exhaust systems required by code or accreditation standards to be fully ducted, or systems required to maintain air pressure differentials between adjacent rooms 0.5 in. w.c. (2.15 in w.c. for laboratory and vivarium systems)
Return, exhaust, or both airflow control devices 0.5 in. w.c.
Exhaust filters, scrubbers, or other exhaust treatment The pressure drop of device calculated at fan system design condition
Particulate Filtration Credit: MERV 9 through 12 0.5 in. w.c.
Particulate Filtration Credit: MERV 13 through 15 0.9 in. w.c.
Particulate Filtration Credit: MERV 16 and greater, and electronically enhanced filters Pressure drop calculated at 2× clean filter pressure drop at fan system design condition
Carbon and other gas-phase air cleaners Clean filter pressure drop at fan system design condition
Biosafety cabinet Pressure drop of device at fan system design condition
Energy recovery device, other than coil runaround loop For each airstream [(2.2 × enthalpy recovery ratio) — 0.5] in w.c.
Coil runaround loop 0.6 in. w.c. for each airstream
Evaporative humidifier or cooler in series with another cooling coil Pressure drop of device at fan system design condition
Sound attenuation section (fans serving spaces with design background noise goals below NC35) 0.15 in. w.c.
Exhaust system serving fume hoods 0.35 in. w.c.
Laboratory and vivarium exhaust systems in high-rise buildings 0.25 in. w.c. per 100 feet of vertical duct exceeding 75 ft
DEDUCTIONS
Systems without central cooling device —0.6 in. wc
Systems without central heating device —0.3 in. wc
Systems with central electric resistance heat —0.2 in. wc

For SI units: 1 inch water column = 0.249 kPa, 1 foot = 304.8 mm

Cooling systems listed in Table E 503.5.6.2 shall be designed to vary the indoor fan airflow as a function of load and shall be in accordance with the following:
  1. DX and chilled-water cooling units that control the capacity of the mechanical cooling directly based on space temperature shall have a minimum of two stages of fan control. Low or minimum speed shall not exceed 66 percent of full speed. At low or minimum speed, the fan system shall draw not more than 40 percent of the fan power at fall fan speed. Low or minimum speed shall be used during periods of low cooling load and ventilation-only operation.
  2. Other units, including DX cooling units and chilled water units that control the space temperature by modulating the airflow to the space, shall have modulating fan control. Minimum speed shall not exceed 50 percent of fall speed. At minimum speed, the fan system shall draw not more than 30 percent of the power at fall fan speed. Low or minimum speed shall be used during periods of low cooling load and ventilation-only operation.
  3. Units that include an air-side economizer to comply with Section E 503.5 through Section E 503.5.4.1 shall have not less than of two speeds of fan control during economizer operation.

Exceptions:

  1. Modulating fan control shall not be required for chilled-water and evaporative cooling units with less than l hp (0.7 kW) fan motors where the units are not used to provide ventilation air and the indoor fan cycles with the load.
  2. Where the volume of outdoor air required to comply with the ventilation requirements of Chapter 4 or ASHRAE 62.1 at low speed exceeds the air that would be delivered at the speed defined in Section E 503.5.6.2(1), or Section E 503.5.6.2(2), then the minimum speed shall be selected to provide the required ventilation air. [ASHRAE 90.1:6.5.3.2.1]

TABLE E 503.5.6.2 FAN AIRFLOW CONTROL
[ASHRAE 90.1:TABLE 6.5.3.2.1]

COOLING SYSTEM TYPE FAN MOTOR SIZE, (hp) MECHANICAL COOLING CAPACITY, (Btu/h)
DX cooling Any ≥65 000
Chilled-water and evaporative cooling 1/4 Any

For SI units: 1000 British thermal units per hour = 0.293 kW, 1 horsepower = 0.746 kW, 1 cubic foot per minute = 0.00047 m3/s

Static pressure sensors used to control VAV fans shall be located such that the controller setpoint is not more than l .2 inches water column (0.30 kPa). Where this results in the sensor being located downstream of major duct splits, sensors shall be installed in each major branch to ensure that static pressure is maintained in each.

Exception: Systems that are in accordance with Section E 503.5.6.2.2. [ASHRAE 90.1:6.5.3.2.2]

For multiple-zone VAV systems having a total fan system motor nameplate horsepower exceeding 5 hp (3.7 kW) with DDC of individual zones reporting to the central control panel, static pressure setpoint shall be reset based on the zone requiring the most pressure, such as the setpoint is reset lower until one zone damper is nearly wide open. Controls shall provide the following:
  1. Monitor zone damper positions or other indicator of need for static pressure.
  2. Automatically detect those zones that are capable of excessively driving the reset logic and generate an alarm to the system operator.
  3. Readily allow operator removal of zones from the reset algorithm. [ASHRAE 90.1:6.5.3.2.3]
Multiple-zone VAV systems with DDC individual zone boxes reporting to a central control panel shall include a means to automatically reduce outdoor air intake flow below design rates in response to changes in system ventilation efficiency in accordance with ASHRAE 62.1.

Exceptions:

  1. VAV systems with zonal transfer fans that recirculate air from other zones without directly mixing it with outdoor air, dual-duct dual-fan VAV systems, and VAV systems with fan-powered terminal units.
  2. Systems where total design exhaust airflow is more than 70 percent of total design outdoor air intake flow requirements. [ASHRAE 90.1:6.5.3.3]
Multiple zone HVAC systems shall include controls that automatically reset the supply air temperature in response to representative building loads, or to outdoor air temperature. The controls shall reset the supply air temperature to not less than 25 percent of the difference between the design supply air temperature and the design room air temperature. Controls that adjust the reset based on zone humidity shall be permitted. Zones that are expected to experience relatively constant loads, such as electronic equipment rooms, shall be designed for the fully reset supply temperature.

Exceptions:

  1. Climate zones 0A, 1A, 2A, and 3A.
  2. Systems that prevent reheating, recooling, or mixing of heated and cooled supply air.
  3. Systems where not less than 75 percent of the energy for reheating, on an annual basis, is from site recovered or site solar energy sources. [ASHRAE 90.1:6.5.3.5]
Motors for fans that are 1/12 hp (62.1 W) or more and less than 1 hp (0.7 kW) shall be electronically-commutated motors or shall have a motor efficiency of not less than 70 percent where rated in accordance with DOE 10 CFR 431. These motors shall also have the means to adjust motor speed for either balancing or remote control. Belt-driven fans shall be permitted to use sheave adjustments for airflow balancing in lieu of a varying motor speed.

Exceptions:

  1. Motors in the airstream within fan coils and terminal units that operate when providing heating to the space served.
  2. Motors installed in space conditioning equipment certified in accordance with Section E 503.4 through Section E 503.4.4.1.
  3. Motors shown in Table E 503.5.6.5(1) or Table E 503.5.6.5(2). [ASHRAE 90.1:6.5.3.6]

TABLE E 503.5.6.5(1) MINIMUM AVERAGE FULL-LOAD EFFICIENCY FOR POLYPHASE SMALL ELECTRIC MOTORS*
[ASHRAE 90.1:TABLE 10.8-3]

FULL-LOAD EFFICIENCY, %
NUMBER OF POLES OPEN MOTORS
2 4 6
SYNCHRONOUS SPEED (RPM) 3600 1800 1200
MOTOR HORSEPOWER EFFICIENCY,%
0.25 65.6 69.5 67.5
0.33 69.5 73.4 71.4
0.50 73.4 78.2 75.3
0.75 76.8 81.1 81.7
1 77.0 83.5 82.5
1.5 84.0 86.5 83.8
2 85.5 86.5 N/A
3 85.5 86.9 N/A

* Average full-load efficiencies shall be established in accordance with 10 CFR 431.

TABLE E 503.5.6.5(2) MINIMUM AVERAGE FULL-LOAD EFFICIENCY FOR CAPACITOR-START CAPACITOR-RUN AND CAPACITOR-START INDUCTION-RUN SMALL ELECTRIC MOTORS*
[ASHRAE 90.1:TABLE 10.8-4]

FULL-LOAD EFFICIENCY, %
NUMBER OF POLES OPEN MOTORS
2 4 6
SYNCHRONOUS SPEED (RPM) 3600 1800 1200
MOTOR HORSEPOWER EFFICIENCY,%
0.25 66.6 68.5 62.2
0.33 70.5 72.4 66.6
0.50 72.4 76.2 76.2
0.75 76.2 81.8 80.2
1 80.4 82.6 81.1
1.5 81.5 83.8 N/A
2 82.9 84.5 N/A
3 84.1 N/A N/A

* Average full-load efficiencies shall be established in accordance with 10 CFR 431.

The required minimum outdoor air rate is the larger of the minimum outdoor air rate or the minimum exhaust air rate required by ASHRAE 62.1, ASHRAE 170, or applicable codes or accreditation standards. Outdoor air ventilation systems shall comply with one of the following:
  1. Design minimum system outdoor air provided shall not exceed 135 percent of the required minimum outdoor air rate.
  2. Dampers, ductwork, and controls shall be provided that allow the system to supply no more than the required minimum outdoor air rate with a single setpoint adjustment.
  3. The system includes exhaust air energy recovery complying with Section E 503.5.10. [ASHRAE 90.1:6.5.3.7]
Boiler systems with design input of 1 000 000 Btu/h (293 kW) or more shall comply with the turndown ratio in accordance with Table E 503.5.7.

The system turndown requirement shall use multiple single-input boilers, one or more modulating boilers, or a combination of single-input and modulating boilers.

Boilers shall comply with the minimum efficiency requirements in Table E 503.7.1(6). [ASHRAE 90.1:6.5.4.1]

TABLE E 503.5.7 BOILER TURNDOWN
[ASHRAE 90.1:TABLE 6.5.4.1]

BOILER SYSTEM DESIGN INPUT, Btu/h MINIMUM TURNDOWN RATIO
≥1 000 000 and ≤5 000 000 3 to 1
>5 000 000 and ≤10 000 000 4 to 1
>10 000 000 5 to 1

For SI unts: 1000 British thermal units per hour = 0.293 kW

Chilled- and hot-water distribution systems that include three or more control valves designed to modulate or step open and close as a function of load shall be designed for variable fluid flow and shall be capable of and configured to reduce pump flow rates to not more than the larger of 25 percent of the design flow rate or the minimum flow required by the heating/cooling equipment manufacturer for the proper operation of equipment. Individual or parallel pumps serving variable-flow heating-water or chilled-water systems, where the nameplate horsepower of the motor or combined parallel motors is not less than the power shown in Table E 503.5.7.1, shall have controls or devices that will result in pump motor demand of not more than 30 percent of design wattage at 50 percent of design water flow. The controls or devices shall be controlled as a function of desired flow or to maintain a minimum required differential pressure. Differential pressure shall be measured at or near the most remote heat exchanger or the heat exchanger requiring the greatest differential pressure. The differential pressure setpoint shall not exceed 110 percent of that required to achieve design flow through the heat exchanger. Where differential pressure control is used to comply with this section, and DDC systems are used, the setpoint shall be reset downward based on valve positions until one valve is nearly wide open.

Exceptions:

  1. Differential pressure set-point reset is not required where valve position is used to comply with Section E 503.5.7.3.
  2. Variable-pump flow control is not required on heating-water pumps where more than 50 percent of annual heat is generated by an electric boiler.
  3. Variable flow is not required for primary pumps in a primary/secondary system.
  4. Variable flow is not required for a coil pump provided for freeze protection.
  5. Variable flow is not required for heat recovery coil runaround loops. [ASHRAE 90.1:6.5.4.2]

TABLE E 503.5.7.1 PUMP FLOW CONTROL REQUIREMENTS
[ASHRAE 90.1:TABLE 6.5.4.2]

CHILLED WATER PUMPS IN THESE CLIMATE ZONES HEATING WATER PUMPS IN THESE CLIMATE ZONES MOTOR NAMEPLATE HORSEPOWER
0A, 0B, 1A, 1B, 2B NR ≥2 hp
2A, 3B NR ≥3 hp
3A, 3C, 4A, 4B 7, 8 ≥5 hp
4C, 5A, 5B, 5C, 6A, 6B 3C, 5A, 5C, 6A, 6B ≥7.5 hp
4A, 4C, 5B ≥ 10 hp
7, 8 4B ≥15 hp
2A, 2B, 3A, 3B ≥25 hp
1B ≥100 hp
0A, 0B, 1A ≥200 hp

For SI units: 1 horsepower = 0.746 kW

Where a chilled-water plant includes more than one chiller, provisions shall be made so that the fluid flow through the chiller is automatically shut off where the chiller is shut down. Chillers piped in series for the purpose of increased temperature differential, shall be considered as one chiller. Where constant-speed chilled-water or condenser water pumps are used to serve multiple chillers, the number of pumps shall be not less than the number of chillers and staged on and off with the chillers. [ASHRAE 90.1:6.5.4.3.1]
Where a boiler plant includes more than one boiler, provisions shall be made so that the flow through the boiler is automatically shut off where the boiler is shut down. Where constant-speed hot-water pumps are used to serve multiple boilers, the number of pumps shall be not less than the number of boilers and staged on and off with the boilers. [ASHRAE 90.1:6.5.4.3.2]
Chilled- and hotwater systems with a design capacity exceeding 300 000 Btu/h (88 kW) supplying chilled or heated water (or both) to comfort conditioning systems shall include controls that automatically reset supply water temperatures by representative building loads (including return water temperature) or by outdoor air temperature. Where DDC is used to control valves, the set point shall be reset based on valve positions until one valve is nearly wide open or setpoint limits of the system equipment or application have been reached.

Exceptions:

  1. Where chilled-water supply is already cold, such as chilled water supplied from a district cooling or thermal energy storage system, such that blending would be required to achieve the reset chilled-water supply temperature.
  2. Where a specific temperature is required for a process.
  3. Water temperature reset is not required where valve position is used to comply with Section E 503.5.7. [ASHRAE 90.1:6.5.4.4]
Hydronic heat pumps and water-cooled unitary air-conditioners shall have a two-position automatic valve interlocked to shut off water flow when the compressor is off.

Exception: Units employing water economizers. [ASHRAE 90.1:6.5.4.5.1]

Hydronic heat pumps and water-cooled unitary air-conditioners having a total pump system power exceeding 5 hp (3.7 kW) shall have controls, devices, or both (such as variable speed control) that will result in pump motor demand of not more than 30 percent of design wattage at 50 percent of design water flow. [ASHRAE 90.1:6.5.4.5.2]
Chilled-water and condenser-water piping shall be designed such that the design flow rate in a pipe segment does not exceed the values listed in Table E 503.5.7.5 for the appropriate total annual hours of operation. Pipe size selections for systems that operate under variable flow conditions, such as modulating two-way control valves at coils, and that contain variable-speed pump motors shall be permitted to be made from the "Variable Flow/Variable Speed" columns. All others shall be made from the "Other" columns.

Exceptions:

  1. Design flow rates exceeding the values in Table E 503.5.7.5 shall be permitted in specific sections of pipe where the pipe is not in the critical circuit at design conditions and is not predicted to be in the critical circuit during 30 percent or more of operating hours.
  2. Piping systems that have not more than the total pressure drop than the same system constructed with standard weight steel pipe with piping and fittings sized in accordance with Table E 503.5.7.5. [ASHRAE 90.1:6.5.4.6]

TABLE E 503.5.7.5 PIPING SYSTEM DESIGN MAXIMUM FLOW RATE (gallons per minute)
[ASHRAE 90.1:TABLE 6.5.4.6]

OPERATING HOURS/YEAR ≤2000 HOURS/YEAR >2000 AND ≤ 4400 HOURS/YEAR >4400 HOURS/YEAR
NOMINAL PIPE SIZE, (inches) OTHER VARIABLE FLOW/ VARIABLE SPEED OTHER VARIABLE FLOW/ VARIABLE SPEED OTHER VARIABLE FLOW/ VARIABLE SPEED
21/2 120 180 85 130 68 110
3 180 270 140 210 110 170
4 350 530 260 400 210 320
5 410 620 310 470 250 370
6 740 1100 570 860 440 680
8 1200 1800 900 1400 700 1100
10 1800 2700 1300 2000 1000 1600
12 2500 3800 1900 2900 1500 2300
Maximum velocity for pipes over 14-24 inches in size 8.5 ft/s 13.0 ft/s 6.5 ft/s 9.5 ft/s 5.0 ft/s 7.5 ft/s

For SI units: l gallon per minute = 0.06 L/s, 1 foot per second = 0.3048 m/s, 1 inch = 25.4 mm

Section E 503.5.8 through Section E 503.5.9 apply to heat rejection equipment used in comfort cooling systems such as air-cooled condensers, dry coolers, open-circuit cooling towers, closed-circuit cooling towers, and evaporative condensers.

Exception: Heat rejection devices whose energy usage is included in the equipment efficiency ratings listed in Table E 503.7.1(1) through Table E 503.7.1(4). [ASHRAE 90.1:6.5.5.1]

The fan system on a heat-rejection device powered by an individual motor or an array of motors with a connected power, including the motor service factor, totaling 5 hp (3.7 kW) or more shall have controls and/or devices (such as variable-speed control) that shall result in fan motor demand of no more than 30 percent of design wattage at 50 percent of the design airflow and that shall automatically change the fan speed to control the leaving fluid temperature or condensing temperature or pressure of the heat rejection device.

Exceptions:

  1. Condenser fans serving multiple refrigerant circuits or fluid cooling circuits.
  2. Condenser fans serving flooded condensers. [ASHRAE 90.1:6.5.5.2.1]
Multicell heat rejection equipment with variable-speed fan drives shall:
  1. Operate the maximum number of fans allowed that comply with the manufacturer's requirements for all system components.
  2. Control all fans to the same fan speed required for the instantaneous cooling duty, as opposed to staged (on/off) operation. Minimum fan speed shall comply with the minimum allowable speed of the fan drive system per the manufacturer's recommendations. [ASHRAE 90.1:6.5.5.2.2]
Centrifugal fan open-circuit cooling towers with a combined rated capacity of 1100 gallons per minute (gpm) (69.39 L/s) or greater at 95°F (35°C) condenser water return, 85°F (29°C) condenser water supply, and 75°F (24°C) outdoor air wet-bulb temperature shall comply with the energy efficiency requirement for axial fan open-circuit cooling towers in accordance with Table E 503.7.1(7).

Exception: Centrifugal open-circuit cooling towers that are ducted (inlet or discharge) or require external sound attenuation. [ASHRAE 90.1:6.5.5.3]

Open-circuit cooling towers used on water-cooled chiller systems that are configured with multiple- or variable-speed condenser water pumps shall be designed so that all open-circuit cooling tower cells can be run in parallel with the larger of the following:
  1. The flow that is produced by the smallest pump at its minimum expected flow rate.
  2. Fifty percent of the design flow for the cell. [ASHRAE 90.1:6.5.5.4]

E 503.5.10 Exhaust Air Energy Recovery. Each fan system shall have an energy recovery system where the design supply fan airflow rate exceeds the value listed in Table E 503.5.10(1) and Table E 503.5.10(2), based on the climate zone and percentage of outdoor air at design airflow conditions. Table E 503.5.10(1) shall be used for all ventilation systems that operate less than 8000 hours per year and Table E 503.5.10(2) shall be used for all ventilation systems that operate 8000 or more hours per year.

Energy recovery systems required by this section shall result in an enthalpy recovery ratio of not less than 50 percent. A fifty percent enthalpy recovery ratio shall mean a change in the enthalpy of the outdoor air supply equal to 50 percent of the difference between the outdoor air and entering exhaust air enthalpies at design conditions. Provision shall be provided to bypass or control the energy recovery system to permit air economizer operation in accordance with Section E 503.5.1.

Exceptions:

  1. Laboratory systems that are in accordance with Section E 503.5.11.3.
  2. Systems serving spaces that are not cooled and that are heated to less than 60°F (16°C).
  3. Where more than 60 percent of the outdoor air heating energy is provided from site-recovered energy or site-solar energy.
  4. Heating energy recovery in Climate Zones 0, 1, and 2.
  5. Cooling energy recovery in climate zones 3C, 4C, 5B, 5C, 6B, 7, and 8.
  6. Where the sum of the airflow rates exhausted and relieved within 20 feet (6096 mm) of each other is less than 75 percent of the design outdoor airflow rate, excluding exhaust air that is;
    1. used for another energy recovery system,
    2. not allowed by ASHRAE 170 for use in energy recovery systems with leakage potential, or
    3. of Class 4 as defined in ASHRAE 62.1.
  7. Systems requiring dehumidification that employ energy recovery in series with the cooling coil.
  8. Systems expected to operate less than 20 hours per week at the outdoor air percentage in accordance with Table E 503.5.10(1). [ASHRAE 90.1:6.5.6.1]

E 503.5.10.1 Heat Recovery for Service Water Heating. Heat recovery shall comply with Section E 503.5.10.1.1 and Section E 503.5.10.1.2.

E 503.5.10.1.1 Condenser Heat Recovery Systems. Condenser heat recovery systems shall be installed for the heating or preheating of service hot water where the following conditions exist:

  1. The facility operates 24 hours a day.
  2. The total installed heat rejection capacity of the water-cooled system is more than 6 000 000 Btu/h (1757 kW) of heat rejection.
  3. The design service water heating load is more than 1 000 000 Btu/h (293 kW). [ASHRAE 90.1:6.5.6.2.1]

E 503.5.10.1.2 Capacity. The required heat recovery system shall have the capacity to provide the smaller of:

TABLE E 503.5.10(1) EXHAUST AIR ENERGY RECOVERY REQUIREMENTS FOR VENTILATION SYSTEMS OPERATING LESS THAN 8000 HOURS PER YEAR*
[ASHRAE 90.1:TABLE 6.5.6.1-1]

CLIMATE ZONE PERCENT OUTDOOR AIR AT FULL DESIGN AIRFLOW RATE
≥10% and <20% ≥20% and <30% ≥30% and <40% ≥40% and <50% ≥50% and <60% ≥60% and <70% ≥70% and <80% ≥80%
DESIGN SUPPLY FAN AIRFLOW RATE (cubic feet per minute)
3B, 3C, 4B, 4C, 5B NR NR NR NR NR NR NR NR
0B, 1B, 2B, 5C NR NR NR NR ≥26 000 ≥12 000 ≥5000 ≥4000
6B ≥28 000 ≥26 500 ≥11 000 ≥5500 ≥4500 ≥3500 ≥2500 ≥1500
0A, 1A, 2A, 3A, 4A, 5A, 6A ≥26 000 ≥16 000 ≥5500 ≥4500 ≥3500 ≥2000 ≥1000 ≥120
7, 8 ≥4500 ≥4000 ≥2500 ≥1000 ≥140 ≥120 ≥100 ≥80

For SI units: 1 cubic foot per minute = 0.00047 m3/s

* NR = Not Required

TABLE E 503.5.10(2) EXHAUST AIR ENERGY RECOVERY REQUIREMENTS FOR VENTILATION SYSTEMS OPERATING NOT LESS THAN 8000 HOURS PER YEAR*
[ASHRAE 90.1:TABLE 6.5.6.1-2]

CLIMATE ZONE PERCENT OUTDOOR AIR AT FULL DESIGN AIRFLOW RATE
≥10% and <20% ≥20% and <30% ≥30% and <40% ≥40% and <50% ≥50% and <60% ≥60% and <70% ≥70% and <80% ≥80%
DESIGN SUPPLY FAN AIRFLOW RATE (cubic feet per minute)
3C NR NR NR NR NR NR NR NR
0B, 1B, 2B, 3B, 4C, 5C NR ≥19 500 ≥9000 ≥5000 ≥4000 ≥3000 ≥1500 ≥120
0A, 1A, 2A, 3A, 4B, 5B ≥2500 ≥2000 ≥1000 ≥500 ≥140 ≥120 ≥100 ≥80
4A, 5A, 6A, 6B, 7, 8 ≥200 ≥130 ≥100 ≥80 ≥70 ≥60 ≥50 ≥40

For SI units: 1 cubic foot per minute = 0.00047 m3/s

* NR = Not Required

  1. Sixty percent of the peak heat rejection load at design conditions.
  2. Preheat of the peak service hot water draw to 85°F (29°C).

Exceptions:

  1. Facilities that employ condenser heat recovery for space heating with a heat recovery design of more than 30 percent of the peak water-cooled condenser load at design conditions.
  2. Facilities that provide 60 percent of their service water heating from site-solar, site-recovered energy, or from other sources. [ASHRAE 90.1:6.5.6.2.2]

E 503.5.11 Exhaust Systems. Exhaust systems shall comply with Section E 503.5.11.1 through Section E 503.5.11.3.

E 503.5.11.1 Kitchen Exhaust Systems. Replacement air introduced directly into the hood cavity of kitchen exhaust hoods shall not exceed 10 percent of the hood exhaust airflow rate. [ASHRAE 90.1:6.5.7.2.1]

E 503.5.11.1.1 Conditioned Supply Air. Conditioned supply air delivered to a space with a kitchen hood shall not exceed the greater of the following:

  1. The supply flow required to be in accordance with the space heating or cooling load.
  2. The hood exhaust flow minus the available transfer air from adjacent spaces. Available transfer air is that portion of outdoor ventilation air not required to satisfy other exhaust needs, such as restrooms, and not required to maintain pressurization of adjacent spaces. [ASHRAE 90.1:6.5.7.1.2]

E 503.5.11.2 Exhaust Flow Rate. Where a kitchen or dining facility has a total kitchen hood exhaust airflow rate exceeding 5000 ft3/min (2.3597 m3/s), each hood shall have an exhaust rate in accordance with Table E 503.5.11.2. Where a single hood, or hood section, is installed over appliances with different duty ratings, the maximum allowable flow rate for the hood or hood section shall not exceed the values in Table E 503.5.11.2 for the highest appliance duty rating under the hood or hood section. Refer to ASHRAE 154 for definitions of hood type, appliance duty, and net exhaust flow rate.

TABLE E 503.5.11.2 MAXIMUM NET EXHAUST FLOW RATE, CFM PER LINEAR FOOT OF HOOD LENGTH
[ASHRAE 90.1:TABLE 6.5.72.2]

TYPE OF HOOD LIGHT DUTY EQUIPMENT MEDIUM DUTY EQUIPMENT HEAVY DUTY EQUIPMENT EXTRA HEAVY DUTY EQUIPMENT
Wall-mounted canopy 140 210 280 385
Single island 280 350 420 490
Double island (per side) 175 210 280 385
Eyebrow 175 175 Not allowed Not allowed
Backshelf/ Pass-over 210 210 280 Not allowed

For SI units: 1 foot = 304.8 mm, 1 cubic foot per minute = 0.00047 m3/s

Exception: Seventy-five percent or more of the total replacement air is transfer air that would otherwise be exhausted. [ASHRAE 90.1:6.5.7.2.2]

E 503.5.11.2.1 Kitchen or Dining Facility. Where a kitchen or dining facility has a total kitchen hood exhaust airflow rate more than 5000 ft3/min (2.3597 m3/s), then one of the following shall be provided:

  1. Fifty percent or more of all replacement air is transfer air that would otherwise be exhausted.
  2. Demand ventilation systems on 75 percent or more of the exhaust air. Such systems shall be capable of and configured to provide 50 percent or more reduction in exhaust and replacement air system airflow rates, including controls necessary to modulate airflow in response to appliance operation and to maintain full capture and containment of smoke, effluent, and combustion products during cooking and idle.
  3. Listed energy recovery devices that result in a sensible energy recovery ratio of 40 percent or more on 50 percent or more of the total exhaust airflow. A 40 percent sensible energy recovery ratio shall mean a change in the dry-bulb temperature of the outdoor air supply equal to 40 percent of the difference between the outdoor air and entering exhaust air dry-bulb temperatures at design conditions. [ASHRAE 90.1:6.5.7.2.3]

E 503.5.11.2.2 Performance Testing. An approved field test method shall be used to evaluate design air flow rates and demonstrate proper capture and containment performance of installed commercial kitchen exhaust systems. Where demand ventilation systems are utilized to be in accordance with Section E 503.5.11.2.1, additional performance testing shall be provided to demonstrate proper capture and containment at minimum airflow. [ASHRAE 90.1:6.5.7.2.4]

E 503.5.11.3 Laboratory Exhaust Systems. Buildings with laboratory exhaust systems having a total exhaust rate of more than 5000 ft3/min (2.3597 m3/s) shall include not less than one of the following features:

  1. VAV laboratory exhaust and room supply systems capable of and configured to reduce exhaust and makeup airflow rates, incorporate a heat recovery system to precondition makeup air from laboratory exhaust, or both and shall be in accordance with the following:

    (Equation E 503.5.11.3)

    A+B•(E/M)≥ 50%   

    Where:

    A = Percentage that the exhaust and makeup airflow rates are capable of being reduced from design conditions.
    B = Sensible energy recovery ratio.
    E = Exhaust airflow rate through the heat recovery device at design conditions.
    M = Makeup airflow rate of the system at design conditions.
  2. VAV laboratory exhaust and room supply systems that are required to have minimum circulation rates to be in accordance with the codes or accreditation standards shall be capable of and configured to reduce zone exhaust and makeup airflow rates to the regulated minimum circulation values, or the minimum required to maintain pressurization relationship requirements. Systems serving nonregulated zones shall be capable of and configured to reduce exhaust and makeup airflow rates to 50 percent of the zone design values, or the minimum required to maintain pressurization relationship requirements.
  3. Direct makeup (auxiliary) air supply of 75 percent or more of the exhaust airflow rate, heated not more than 2°F (1°C) below room setpoint, cooled to not less than 3°F (2°C) above room setpoint, no humidification added, and no simultaneous heating and cooling are used for dehumidification control. [ASHRAE 90.1:6.5.7.3]

E 503.5.12 Radiant Heating Systems. Radiant heating shall be used when heating is required for unenclosed spaces.

Exception: Loading docks equipped with air curtains. [ASHRAE 90.1:6.5.8.1]

E 503.5.12.1 Heating Enclosed Spaces. Radiant heating systems that are used as primary or supplemental enclosed space heating shall be in accordance with this appendix, including, but not limited to, the following:

  1. Radiant hydronic ceiling or floor panels (used for heating or cooling).
  2. Combination or hybrid systems incorporating radiant heating (or cooling) panels.
  3. Radiant heating (or cooling) panels used in conjunction with other systems such as VAV or thermal storage systems. [ASHRAE 90.1:6.5.8.2]

E 503.5.13 Hot Gas Bypass Limitation. Cooling systems shall not use hot gas bypass or other evaporator pressure control systems unless the system is designed with multiple steps of unloading or continuous capacity modulation. The capacity of the hot gas bypass shall be limited as indicated in Table E 503.5.13 for VAV units and single-zone VAV units. Hot-gas bypass shall not be used on constant-volume units. [ASHRAE 90.1:6.5.9]

TABLE E 503.5.13 HOT GAS BYPASS LIMITATION
[ASHRAE 90.1:TABLE 6.5.9]

RATED CAPACITY MAXIMUM HOT GAS BYPASS (percent of total capacity)
≤240 000 Btu/h 15%
>240 000 Btu/h 10%

For SI units: 1000 British thermal units per hour = 0.293 kW

E 503.5.14 Door Switches. Conditioned spaces with doors, including doors with more than one-half glass, opening to the outdoors shall be provided with controls that when any such door is open, the following shall occur:

  1. Disable mechanical heating or reset the heating setpoint to 55°F (13°C) or lower within five minutes of the door opening.
  2. Disable mechanical cooling or reset the cooling setpoint to 90°F (32°C) or more within five minutes of the door opening. Mechanical cooling shall be permitted to remain enabled where outdoor air temperature is less than the space temperature.

Exceptions:

  1. Building entries with automatic closing devices.
  2. Any space without a thermostat.
  3. Alterations to existing buildings.
  4. Loading docks. [ASHRAE 90.1:6.5.10]
The Authority Having Jurisdiction shall require submittal of compliance documentation and supplemental information in accordance with Section E 503.6.1 through Section E 503.6.3.
Compliance documents shall show the pertinent data and features of the building, equipment, and systems in sufficient detail to permit a determination of compliance by the building official and to indicate compliance with the requirements of this appendix. [ASHRAE 90.1:4.2.2.1]
Supplemental information necessary to verify compliance with this appendix, such as calculations, worksheets, compliance forms, vendor literature, or other data, shall be made available where required by the Authority Having Jurisdiction. [ASHRAE 90.1:4.2.2.2]
Operating and maintenance information shall be provided to the building owner. This information shall include, but not be limited to, the information specified in Section E 503.6.3.1, Section E 503.6.3.2, and Section E 503.6.5.2. [ASHRAE 90.1:4.2.2.3]
Construction documents shall require that an operating manual and maintenance manual be provided to the building owner. The manuals shall include, at a minimum, the following:
  1. Submittal data stating equipment rating and selected options for each piece of equipment requiring maintenance.
  2. Operation manuals and maintenance manuals for each piece of equipment requiring maintenance. Required routine maintenance actions shall be clearly identified.
  3. Names and addresses of not less than one qualified service agency.
  4. A complete narrative of how each system is intended to operate.

The Authority Having Jurisdiction shall only check to ensure that the construction documents required are provided to the owner, and shall not expect copies of any of the materials. [ASHRAE 90.1:8.7.2]

Construction documents shall require for all lighting equipment and lighting controls that an operating and maintenance manual be provided to the building owner or the designated representative of the building owner within 90 days after the date of system acceptance. These manuals shall include, at a minimum, the following:
  1. Submittal data indicating all selected options for each piece of lighting equipment, including but not limited to lamps, ballasts, drivers, and lighting controls.
  2. Operation and maintenance manuals for each piece of lighting equipment and lighting controls with routine maintenance clearly identified including, as a minimum, a recommended relamping or cleaning program and a schedule for inspecting and recalibrating all lighting controls.
  3. A complete narrative of how each lighting control system is intended to operate including recommended settings. [ASHRAE 90.1:9.7.2.2]
Materials and equipment shall be labeled in a manner that will allow for determination of their compliance with the applicable provisions of this appendix. [ASHRAE 90.1:4.2.3]
Section E 503.6.5.1 through Section E 503.6.5.4.1 are mandatory provisions and are necessary to comply with this appendix. [ASHRAE 90.1:6.7.2]
Construction documents shall require that, within 90 days after the date of system acceptance, record drawings of the actual installation be provided to the building owner or the designated representative of the building owner. Record drawings shall include, as a minimum, the location and performance data on each piece of equipment, general configuration of duct and pipe distribution system including sizes, and the terminal air or water design flow rates. [ASHRAE 90.1:6.7.2.1]
Construction documents shall require that an operating manual and a maintenance manual be provided to the building owner or the designated representative of the building owner within 90 days after the date of system acceptance. These manuals shall be in accordance with industry-accepted standards and shall include, at a minimum, the following:
  1. Submittal data stating equipment size and selected options for each piece of equipment requiring maintenance.
  2. Operation manuals and maintenance manuals for each piece of equipment and system requiring maintenance, except equipment not furnished as part of the project. Required routine maintenance actions shall be clearly identified.
  3. Names and addresses of not less than one service agency.
  4. HVAC controls system maintenance and calibration information, including wiring diagrams, schematics, and control sequence descriptions. Desired or field-determined setpoints shall be permanently recorded on control drawings at control devices or, for digital control systems, in programming comments.
  5. A complete narrative of how each system is intended to operate, including suggested set-points. [ASHRAE 90.1:6.7.2.2]
Construction documents shall require that HVAC systems be balanced in accordance with generally accepted engineering standards. Construction documents shall require that a written balance report be provided to the building owner or the designated representative of the building owner for HVAC systems serving zones with a total conditioned area exceeding 5000 square feet (464.52 m2). [ASHRAE 90.1:6.7.2.3.1]
Air systems shall be balanced in a manner to first minimize throttling losses. Then, for fans with fan system power greater than 1 hp (0.7 kW), fan speed shall be adjusted to meet design flow conditions. [ASHRAE 90.1:6.7.2.3.2]
Hydronic systems shall be proportionately balanced in a manner to first minimize throttling losses; then the pump impeller shall be trimmed or pump speed shall be adjusted to meet design flow conditions.

Exceptions: Impellers need not be trimmed nor pump speed adjusted.

  1. For pumps with pump motors of 10 hp (7.5 kW) or less.
  2. Where throttling results is not greater than 5 percent of the nameplate horsepower draw, or 3 hp (2.2 kW), whichever is greater, above that required where the impeller was trimmed. [ASHRAE 90.1:6.7.2.3.3]
HVAC control systems shall be tested to ensure that control elements are calibrated, adjusted, and in proper working condition. For projects larger than 50 000 square feet (4645.15 m2) conditioned area, except warehouses and semiheated spaces, detailed instructions for commissioning HVAC systems shall be provided by the designer in plans and specifications. [ASHRAE 90.1:6.7.2.4]
Commissioning shall be performed for HVAC systems in accordance with Level 1, Basic Commissioning of the SMACNA HVAC Systems Commissioning Manual. (See Section E 801.0 for additional information on HVAC system commissioning)
The minimum efficiency requirements for equipment shall comply with Section E 503.7.1; duct insulation shall comply with Section E 503.7.2, and pipe insulation shall comply with Section E 503.7.3.
The minimum efficiency requirements for equipment shall comply with Table E 503.7.1(1) through Table E 503.7.1(16).

TABLE E 503.7.1(1) ELECTRICALLY OPERATED UNITARY AIR CONDITIONERS AND CONDENSING UNITS MINIMUM EFFICIENCY REQUIREMENTS
[ASHRAE 90.1:TABLE 6.8.1-1]

EQUIPMENT TYPE SIZE CATEGORY HEATING SECTION TYPE SUBCATEGORY OR RATING CONDITION MINIMUM EFFICIENCY TEST PROCEDURE1
Air conditioners, air cooled <65 000 Btu/h2 All Split system, three phase 13.0 SEER AHRI 210/240
Single package, three phase 14 SEER
Through the wall, air cooled ≤30 000 Btu/h2 All Split system, three phase 12.0 SEER AHRI 210/240
Single package, three phase 12.0 SEER
Small duct, high velocity, air cooled <65 000 Btu/h2 All Split system, three phase 11.0 SEER AHRI 210/240
Air conditioners, air cooled ≥65 000 Btu/h and <135 000 Btu/h Electric resistance (or none) Split system and single package 11.2 EER 12.9 IEER AHRI 340/360
All other 11.0 EER 12.7 IEER
≥135 000 Btu/h and <240 000 Btu/h Electric resistance (or none) 11.0 EER 12.4 IEER
All other 10.8 EER 12.2 IEER
≥240 000 Btu/h and <760 000 Btu/h Electric resistance (or none) 10.0 EER 11.6 IEER
All other 9.8 EER 11.4 IEER
≥760 000 Btu/h Electric resistance (or none) 9.7 EER 11.2 IEER
All other 9.5 EER 11.0 IEER
Air conditioners, water cooled <65 000 Btu/h All Split system and single package 12.1 EER 12.3 IEER AHRI 210/240
≥65 000 Btu/h and <135 000 Btu/h Electric resistance (or none) 12.1 EER 13.9 IEER AHRI 340/360
All other 11.9 EER 13.7 IEER
≥135 000 Btu/h and <240 000 Btu/h Electric resistance (or none) 12.5 EER 13.9 IEER
All other 12.3 EER 13.7 IEER
≥240 000 Btu/h and <760 000 Btu/h Electric resistance (or none) 12.4 EER 13.6 IEER
All other 12.2 EER 13.4 IEER
≥760 000 Btu/h Electric resistance (or none) 12.2 EER 13.5 IEER
All other 12.0 EER 13.3 IEER
Air conditioners, evaporatively cooled <65 000 Btu/h2 All Split system and single package 12.1 EER 12.3 IEER AHRI 210/240
≥65 000 Btu/h and <135 000 Btu/h Electric resistance (or none) 12.1 EER 12.3 IEER AHRI 340/360
All other 11.9 EER 12.1 IEER
≥135 000 Btu/h and <240 000 Btu/h Electric resistance (or none) 12.0 EER 12.2 IERR
All other 11.8 EER 12.0 IEER
≥240 000 Btu/h and <760 000 Btu/h Electric resistance (or none) 11.9 EER 12.1 IEER
All other 11.7 EER 11.9 IEER
≥760 000 Btu/h Electric resistance (or none) 11.7 EER 11.9 IEER
All other 11.5 EER 11.7 IEER
Condensing units, air cooled ≥135 000 Btu/h 10.5 EER 11.8 IEER AHRI 365
Condensing units, water cooled ≥135 000 Btu/h 13.5 EER 14.0 IEER AHRI 365
Condensing units, evaporatively cooled ≥135 000 Btu/h 13.5 EER 14.0 IEER AHRI 365

For SI units: 1000 British thermal units per hour = 0.293 kW

Notes:

1 ASHRAE 90.1 contains a complete specification of the referenced test procedure, including the referenced year version of the test procedure.

2 Single-phase, air-cooled air conditioners less than 65 000 Btu/h (19 kW) are regulated by the U.S. Department of Energy Code of Federal Regulations 10 CFR 430. SEER values for single-phase products are set by the U.S. Department of Energy.

TABLE E 503.7.1(2) ELECTRICALLY OPERATED UNITARY AND APPLIED HEAT PUMPS MINIMUM EFFICIENCY REQUIREMENTS
[ASHRAE 90.1:TABLE 6.8.1-2]

EQUIPMENT TYPE SIZE CATEGORY HEATING SECTION TYPE SUBCATEGORY OR RATING CONDITION MINIMUM EFFICIENCY TEST PROCEDURE1
Air cooled (cooling mode) <65 000 Btu/h2 All Split system, three phase 14 SEER AHRI 210/240
Single package, three phase 14 SEER
Through the wall, air cooled (cooling mode) ≤30 000 Btu/h2 All Split system, three phase 12.0 SEER AHRI 210/240
Single package, three phase 12.0 SEER
Small duct, high velocity, air cooled <65 000 Btu/h2 All Split System, three phase 11.0 SEER AHRI 210/240
Air cooled (cooling mode) ≥65 000 Btu/h and <135 000 Btu/h Electric resistance (or none) Split system and single package 11.0 EER 12.2 IEER AHRI 340/360
All other 10.8 EER 12.0 IEER
≥135 000 Btu/h and <240 000 Btu/h Electric resistance (or none) 10.6 EER 11.6 IEER
All other 10.4 EER 11.4 IEER
≥240 000 Btu/h Electric resistance (or none) 9.5 EER 10.6 IEER
All other 9.3 EER 10.4 IEER
Water to air, water loop (cooling mode) <17 000 Btu/h All 86°F entering water 12.2 EER ISO 13256-1
≥17 000 Btu/h and <65 000 Btu/h 13.0 EER
≥65 000 Btu/h and <135 000 Btu/h 13.0 EER
Water to air, groundwater (cooling mode) <135 000 Btu/h All 59°F entering water 18.0 EER ISO 13256-1
Brine to air, ground loop (cooling mode) <135 000 Btu/h All 77°F entering water 14.1 EER ISO 13256-1
Water to water, water loop (cooling mode) <135 000 Btu/h All 86°F entering water 10.6 EER ISO 13256-2
Water to water, groundwater (cooling mode) <135 000 Btu/h All 59°F entering water 16.3 EER ISO 13256-2
Brine to water, ground loop (cooling mode) <135 000 Btu/h All 77°F entering water 12.1 EER ISO 13256-2
Air cooled (heating mode) <65 000 Btu/h2 (cooling capacity) Split system, three phase 8.2 HSPF AHRI 210/240
Single package, three phase 8.0 HSPF
Through the wall, air cooled (heating mode) ≤30 000 Btu/h2 (cooling capacity) Split system, three phase 7.4 HSPF AHRI 210/240
Single package, three phase 7.4 HSPF
Small duct high velocity, air cooled (heating mode) <65 000 Btu/h2 Split system, three phase 6.8 HSPF AHRI 210/240
Air cooled (heating mode) ≥65 000 Btu/hc and <135 000 Btu/h (cooling capacity) 47°F db/43°F wb outdoor air 3.3 COPH AHRI 340/360
17°F db/15°F wb outdoor air 2.25 COPH
≥135 000 Btu/hc (cooling capacity) 47°F db/43°F wb outdoor air 3.2 COPH
17°F db/15°F wb outdoor air 2.05 COPH
Water to air, water loop (heating mode) <135 000 Btu/h (cooling capacity) 68°F entering water 4.3 COPH ISO 13256—1
Water to air, groundwater (heating mode) <135 000 Btu/h (cooling capacity) 50°F entering water 3.7 COPH ISO 13256—1
Brine to air, ground loop (heating mode) <135 000 Btu/h (cooling capacity) 32°F entering fluid 3.2 COPH ISO 13256—1
Water to water, water loop (heating mode) <135 000 Btu/h (cooling capacity) 68°F entering water 3.7 COPH ISO 13256—2
Water to water, groundwater (heating mode) <135 000 Btu/h (cooling capacity) 50°F entering water 3.1 COPH ISO 13256—2
Brine to water, ground loop (heating mode) <135 000 Btu/h (cooling capacity) 32°F entering fluid 2.5 COPH ISO 13256—2

For SI units: 1000 British thermal units per hour = 0.293 kW, °C = (°F—32)/1.8

Notes:

1 ASHRAE 90.1 contains a complete specification of the referenced test procedure, including the referenced year version of the test procedure.

2 Single-phase, air-cooled heat pumps less than 65 000 Btu/h (19 kW) are regulated by the U.S. Department of Energy Code of Federal Regulations 10 CFR 430. SEER and HSPF values for single-phase products are set by the U.S. Department of Energy.

TABLE E 503.7.1(3) WATER-CHILLING PACKAGES — MINIMUM EFFICIENCY REQUIREMENTS1, 2, 5
[ASHRAE 90.1:TABLE 6.8.1-3]

EQUIPMENT TYPE SIZE CATEGORY UNITS PATH A PATH B TEST PROCEDURE3
Air-cooled chillers <150 tons EER (Btu/Wh) ≥10.100 FL ≥9.700 FL AHRI 550/590
≥13.700 IPLV.IP ≥15.800 IPLV.IP
≥150 tons ≥10.100 FL ≥9.700 FL
≥14.000 IPLV.IP ≥16.100 IPLV.IP
Air-cooled without condenser, electrically operated All capacities EER (Btu/Wh) Air-cooled chillers without condenser must be rated with matching condensers and comply with air-cooled chiller efficiency requirements AHRI 550/590
Water-cooled, electrically operated positive displacement <75 tons kW/ton ≤0.750 FL ≤0.780 FL AHRI 550/590
≤0.600 IPLV.IP ≤0.500 IPLV.IP
≥75 tons and <150 tons ≤0.720 FL ≤0.750 FL
≤0.560 IPLV.IP ≤0.490 IPLV.IP
≥150 tons and <300 tons ≤0.660 FL ≤0.680 FL
≤0.540 IPLV.IP ≤0.440 IPLV.IP
≥300 tons and <600 tons ≤0.610 FL ≤0.625 FL
≤0.520 IPLV.IP ≤0.410 IPLV.IP
≥600 tons ≤0.560 FL ≤0.585 FL
≤0.500 IPLV.IP ≤0.380 IPLV.IP
Water cooled, electrically operated centrifugal <150 tons kW/ton ≤0.610 FL ≤0.695 FL AHRI 550/590
≤0.550 IPLV.IP ≤0.440 IPLV.IP
≥150 tons and <300 tons ≤0.610 FL ≤0.635 FL
≤0.550 IPLV.IP ≤0.400 IPLV.IP
≥300 tons and <400 tons ≤0.560 FL ≤0.595 FL
≤0.520 IPLV.IP ≤0.390 IPLV.IP
≥400 tons and <600 tons ≤0.560 FL ≤0.585 FL
≤0.500 IPLV.IP ≤0.380 IPLV.IP
≥600 tons ≤0.560 FL ≤0.585 FL
≤0.500 IPLV.IP ≤0.380 IPLV.IP
Air-cooled absorption, single effect All capacities COP (WAV) ≥0.600 FL NA4 AHRI 560
Water-cooled absorption, single effect All capacities COP (WAV) ≥0.700 FL NA4 AHRI 560
Absorption double effect, indirect fired All capacities COP (W/W) ≥ 1.000 FL NA4 AHRI 560
≥1.050 IPLV.IP
Absorption double effect, direct fired All capacities COP (W/W) ≥1.000 FL NA4 AHRI 560
≥1.000 IPLV

For SI units: 1 metric ton = 1000 kg, 1000 British thermal units per hour = 0.293 kW

Notes:

1 The requirements for centrifugal chillers shall be adjusted for nonstandard rating conditions per Section E 503.4.1 and are only applicable for the range of conditions listed there. The requirements for air-cooled, water-cooled positive displacement and absorption chillers are at standard rating conditions defined in the reference test procedure.

2 Both the full-load and IPLV.IP requirements must be met or exceeded to comply with this appendix. When there is a Path B, compliance can be with either Path A or Path B for any application.

3 ASHRAE 90.1 contains a complete specification of the referenced test procedure, including the referenced year version of the test procedure.

4 NA means the requirements are not applicable for Path B, and only Path A can be used for compliance.

5 FL is the full-load performance requirements, and IPLV.IP is for the part-load performance requirements.

TABLE E 503.7.1(4) ELECTRICALLY OPERATED PACKAGED TERMINAL AIR CONDITIONERS, PACKAGED TERMINAL HEAT PUMPS, SINGLE-PACKAGE VERTICAL AIR CONDITIONERS, SINGLE-PACKAGE VERTICAL HEAT PUMPS, ROOM AIR CONDITIONERS, AND ROOM AIR CONDITIONER HEAT PUMPS — MINIMUM EFFICIENCY REQUIREMENTS
[ASHRAE 90.1:TABLE 6.8.1-4]

EQUIPMENT TYPE SIZE CATEGORY (INPUT) SUBCATEGORY OR RATING CONDITION MINIMUM EFFICIENCY TEST PROCEDURE1
PTAC (cooling mode) standard size All capacities 95°F db outdoor air 13.8 — (0.300 × Cap/1000)3 (before 1/1/2015) AHRI 310/ 380
14.0 — (0.300 × Cap/1000)3 (as of 1/1/2015)
PTAC (cooling mode) nonstandard size1 All capacities 95°F db outdoor air 10.9 — (0.213 × Cap/1000)3 EER AHRI 310/ 380
PTHP (cooling mode) standard size All capacities 95°F db outdoor air 14.0 — (0.300 × Cap/1000)3 AHRI 310/380
PTHP (cooling mode) nonstandard size2 All capacities 95°F db outdoor air 10.8 — (0.213 × Cap/1000)3 EER AHRI 310/380
PTHP (heating mode) standard size All capacities 3.7 — (0.052 × Cap/1000)3 COPH AHRI 310/380
PTHP (heating mode) nonstandard size2 All capacities 2.9 — (0.026 × Cap/1000)3 COPH AHRI 310/ 380
SPVAC (cooling mode) <65,000 Btu/h 95°F db/75°F wb outdoor air 10.0 EER AHRI 390
≥65 000 Btu/h and <135 000 Btu/h 10.0 EER
≥135 000 Btu/h and <240 000 Btu/h 10.0 EER
SPVHP (cooling mode) <65 000 Btu/h 95°F db/75°F wb outdoor air 10.0 EER AHRI 390
≥65 000 Btu/h and <135 000 Btu/h 10.0 EER
≥135 000 Btu/h and <240 000 Btu/h 10.0 EER
SPVHP (heating mode) <65 000 Btu/h 47°F db/43°F wb outdoor air 3.0 COPH AHRI 390
≥65 000 Btu/h and <135 000 Btu/h 3.0 COPH
≥135 000 Btu/h and <240 000 Btu/h 3.0 COPH
Room air conditioners with louvered sides <6000 Btu/h 9.7 SEER AH AM RAC-1
≥6000 Btu/h and <8000 Btu/h 9.7 SEER
≥8000 Btu/h and <14 000 Btu/h 9.8 EER
≥14 000 Btu/h and <20 000 Btu/h 9.7 SEER
≥20 000 Btu/h 8.5 EER
SPVAC (cooling mode), nonweatherized space constrained ≤30 000 Btu/h 95°F db/75°F wb outdoor air 9.2 EER AHRI 390
>30 000 Btu/h and ≤36 000 Btu/h 9.0 EER
SPVHP (cooling mode), nonweatherized space constrained ≤30 000 Btu/h 95°F db/75°F wb outdoor air 9.2 EER AHRI 390
>30 000 Btu/h and ≤36 000 Btu/h 9.0 EER
SPVHP (heating mode), nonweatherized space constrained ≤30 000 Btu/h 47°F db/43°F wb outdoor air 3.0 COPH AHRI 390
>30 000 Btu/h and ≤36 000 Btu/h 3.0 COPH
Room air conditioners without louvered sides <8000 Btu/h 9.0 EER AHAM RAC-1
≥8000 Btu/h and <20 000 Btu/h 8.5 EER
≥20 000 Btu/h 8.5 EER
Room air conditioner heat pumps with louvered sides <20 000 Btu/h 9.0 EER AHAM RAC-1
≥20 000 Btu/h 8.5 EER
Room air conditioner heat pumps without louvered sides <14 000 Btu/h 8.5 EER AHAM RAC-1
≥14 000 Btu/h 8.0 EER
Room air conditioner, casement only All capacities 8.7 EER AHAM RAC-1
Room air conditioner, casement slider All capacities 9.5 EER AHAM RAC-1

For SI units: 1000 British thermal units per hour = 0.293 kW, °C = (°F—32)/1.8

Notes:

1 ASHRAE 90.1 contains a complete specification of the referenced test procedure, including the referenced year version of the test procedure.

2 Nonstandard size units must be factory labeled as follows: "MANUFACTURED FOR NONSTANDARD SIZE APPLICATIONS ONLY; NOT TO BE INSTALLED IN NEW STANDARD PROJECTS." Nonstandard size efficiencies apply only to units being installed in existing sleeves having an external wall opening of less than 16 inch (406 mm) high or less than 42 inch (1067 mm) wide and having a cross-sectional area less than 670 square inches (0.432 m2).

3 "Cap" means the rated cooling capacity of the product in Btu/h (kW). If the unit's capacity is less than 7000 Btu/h (2.05 kW), use 7000 Btu/h (2.05 kW) in the calculation. Where the unit's capacity is more than 15 000 Btu/h (4.4 kW), use 15 000 Btu/h (4.4 kW) in the calculation.

TABLE E 503.7.1(5)
WARM-AIR FURNACES AND COMBINATION WARM-AIR FURNACES/AIR-CONDITIONING UNITS, WARM-AIR DUCT FURNACES, AND UNIT HEATERS — MINIMUM EFFICIENCY REQUIREMENTS
[ASHRAE 90.1:TABLE 6.8.1-5]

EQUIPMENT TYPE SIZE CATEGORY (INPUT) SUBCATEGORY OR RATING CONDITION MINIMUM EFFICIENCY TEST PROCEDURE1
Warm-air furnace, gas fired <225 000 Btu/h Maximum capacity3 78% AFUE or 80% Et2, 4 DOE 10 CFR Part 430 or Section 2.39, Thermal Efficiency, CSA Z21.47
≥225 000 Btu/h 80% Et4 Section 2.39, Thermal Efficiency, CSA Z21.47
Warm-air furnace, oil fired <225 000 Btu/h Maximum capacity3 78% AFUE or 80% Et2, 4 DOE 10 CFR Part 430 or Section 42, Combustion, UL 727
≥225 000 Btu/h 81% Et4 Section 42, Combustion, UL 727
Warm-air duct furnaces, gas fired All capacities Maximum capacity3 80% EC5 Section 2.10, Efficiency, CSA Z83.8
Warm-air unit heaters, gas fired All capacities Maximum capacity3 80% EC5, 6 Section 2.10, Efficiency, CSA Z83.8
Warm-air unit heaters, oil fired All capacities Maximum capacity3 80% EC5, 6 Section 40, Combustion, UL 731

For SI units: 1000 British thermal units per hour = 0.293 kW

Notes:

1 ASHRAE 90.1 contains a complete specification of the referenced test procedure, including the referenced year version of the test procedure.

2 Combination units not covered by the U.S. Department of Energy Code of Federal Regulations 10 CFR 430 [three-phase power or cooling capacity greater than or equal to 65 000 Btu/h (19 kW)] may comply with either rating.

3 Compliance of multiple firing rate units shall be at the maximum firing rate.

4 Et = thermal efficiency. Units must also include an interrupted or intermittent ignition device (IID), have jacket losses not exceeding 0.75 percent of the input rating, and have either power venting or a flue damper. A vent damper is an acceptable alternative to a flue damper for those furnaces where combustion air is drawn from the conditioned space.

5 Ec = combustion efficiency (100 percent less flue losses). See test procedure for detailed discussion.

6 As of August 8, 2008, according to the Energy Policy Act of 2005, units must also include an interrupted or intermittent ignition device (IID) and have either power venting or an automatic flue damper.

TABLE E 503.7.1(6) GAS- AND OIL-FIRED BOILERS — MINIMUM EFFICIENCY REQUIREMENTS2, 3
[ASHRAE 90.1:TABLE 6.8.1-6]

EQUIPMENT TYPE1 SUBCATEGORY OR RATING CONDITION SIZE CATEGORY (INPUT) MINIMUM EFFICIENCY EFFICIENCY AS OF 3/2/2020 TEST PROCEDURE
Boilers, hot water Gas fired <300 000 Btu/h6, 7 82% AFUE 82% AFUE 10 CFR Part 430
≥300 000 Btu/h and ≤2 500 000 Btu/h4 80% Et 80% Et 10 CFR Part 431
>2 500 000 Btu/h1 82% Ec 82% Ec
Oil fired5 <300 000 Btu/h7 84% AFUE 84% AFUE 10 CFR Part 430
≥300 000 Btu/h and ≤2 500 000 Btu/h4 82% Et 82% Et 10 CFR Part 431
>2 500 000 Btu/h1 84% Ec 84% Ec
Boilers, steam Gas fired <300 000 Btu/h7 80% AFUE 80% AFUE 10 CFR Part 430
Gas fired— all, except natural draft ≥300 000 Btu/h and ≤2 500 000 Btu/h4 79% Et 79% Et 10 CFR Part 430
>2 500 000 Btu/h1 79% Et 79% Et
Gas fired— natural draft ≥300 000 Btu/h and ≤2 500 000 Btu/h4 77% Et 79% Et
>2 500 000 Btu/h1 77% Et 79% Et
Oil fired5 <300 000 Btu/h 82% AFUE 82% AFUE 10 CFR Part 430
≥300 000 Btu/h and ≤2 500 000 Btu/h4 81% Et 81% Et 10 CFR Part 431
>2 500 000 Btu/h1 81% Et 81% Et

For SI units: 1000 British thermal units per hour = 0.293 kW

Notes:

1 These requirements apply to boilers with rated input of 8 000 000 Btu/h (2343 kW) or less that are not packaged boilers and to all packaged boilers. Minimum efficiency requirements for boilers cover all capacities of packaged boilers.

2 Ec = combustion efficiency (100 percent less flue losses). See reference document for detailed information.

3 Et = thermal efficiency. See reference document for detailed information.

4 Maximum capacity—minimum and maximum ratings as provided for and allowed by the unit's controls.

5 Includes oil-fired (residual).

6 Boilers shall not be equipped with a constant burning pilot light.

7 A boiler not equipped with a tankless domestic water-heating coil shall be equipped with an automatic means for adjusting the temperature of the water such that an incremental change in inferred heat load produces a corresponding incremental change in the temperature of the water supplied.

TABLE E 503.7.1(7) PERFORMANCE REQUIREMENTS FOR HEAT REJECTION EQUIPMENT MINIMUM EFFICIENCY REQUIREMENTS
[ASHRAE 90.1:TABLE 6.8.1-7]

EQUIPMENT TYPE TOTAL SYSTEM HEAT- REJECTION CAPACITY AT RATED CONDITIONS SUBCATEGORY OR RATING CONDITION8 PERFORMANCE REQUIRED1, 2, 3, 6, 7 TEST PROCEDURE4, 5
Propeller or axial fan open-circuit cooling towers All 95°F entering water 85°F leaving water 75°F entering wb ≥40.2 gpm/hp CTI ATC-105 and CTI STD-201 RS
Centrifugal fan open-circuit cooling towers All 95°F entering water 85°F leaving water 75°F entering wb ≥20.0 gpm/hp CTI ATC-105 and CTI STD-201 RS
Propeller or axial fan closed- circuit cooling towers All 102°F entering water 90°F leaving water 75°F entering wb ≥16.1 gpm/hp CTI ATC-105S and CTI STD-201 RS
Centrifugal closed- circuit cooling towers All 102°F entering water 90°F leaving water 75°F entering wb ≥7.0 gpm/hp CTI ATC-105S and CTI STD-201 RS
Propeller or axial fan evaporative condensers All R-507A test fluid 165°F entering gas temperature 105°F condensing temperature 75°F entering wb ≥157 000 Btu/hhp CTI ATC-106
Propeller or axial fan evaporative condensers All Ammonia test fluid 140°F entering gas temperature 96.3°F condensing temperature 75°F entering wb ≥134 000 Btu/h hp CTI ATC-106
Centrifugal fan evaporative condensers All R-507A test fluid 165°F entering gas temperature 105°F condensing temperature 75°F entering wb ≥135 000 Btu/h hp CTI ATC-106
Centrifugal fan evaporative condensers All Ammonia test fluid 140°F entering gas temperature 96.3°F condensing temperature 75°F entering wb ≥110 000 Btu/h hp CTI ATC-106
Air cooled condensers All 125°F condensing temperature 190°F entering gas temperature 15°F subcooling 95°F entering db ≥176 000 Btu/h hp AHRI 460

For SI units: °C = (°F—32)/1.8, 1 gallon per minute per horsepower = 0.085 [(L/s)/kW], 1000 British thermal units per hour = 0.293 kW, 1 horsepower = 0.746 kW

Notes:

1 For purposes of this table, open-circuit cooling tower performance is defined as the water flow rating of the tower at the thermal rating condition listed in Table E 503.7.1(7) divided by the fan motor nameplate power.

2 For purposes of this table, closed-circuit cooling tower performance is defined as the process water flow rating of the tower at the thermal rating condition listed in Table E 503.7.1(7) divided by the sum of the fan motor nameplate power and the integral spray pump motor nameplate power.

3 For purposes of this table, air-cooled condenser performance is defined as the heat rejected from the refrigerant divided by the fan motor nameplate power.

4 ASHRAE 90.1 contains a complete specification of the referenced test procedure, including the referenced year version of the test procedure.

5 The efficiencies and test procedures for both open- and closed-circuit cooling towers are not applicable to hybrid cooling towers that contain a combination of separate wet and dry heat exchange sections. The certification requirements do not apply to field-erected cooling towers.

6 All cooling towers shall comply with the minimum efficiency listed in the table for that specific type of tower with the capacity effect of any project-specific accessories and/or options included in the capacity of the cooling tower.

7 For purposes of this table, evaporative condenser performance is defined as the heat rejected at the specified rating condition in the table, divided by the sum of the fan motor nameplate power and the integral spray pump nameplate power.

8 Requirements for evaporative condensers are listed with ammonia (R-717) and R-507A as test fluids in the table. Evaporative condensers intended for use with halocarbon refrigerants other than R-507A must meet the minimum efficiency requirements listed above with R-507A as the test fluid.

TABLE E 503.7.1(8) HEAT TRANSFER EQUIPMENT — MINIMUM EFFICIENCY REQUIREMENTS
[ASHRAE 90.1:TABLE 6.8.1-8]

EQUIPMENT TYPE SUBCATEGORY MINIMUM EFFICIENCY1 TEST PROCEDURE2
Liquid-to-liquid heat exchangers Plate type NR AHRI 400

Notes:

1 NR = No Requirement

2 ASHRAE 90.1 contains a complete specification of the referenced test procedure, including the referenced year version of the test procedure.

TABLE E 503.7.1(9) ELECTRICALLY OPERATED VARIABLE-REFRIGERANT-FLOW AIR CONDITIONERS — MINIMUM EFFICIENCY REQUIREMENTS
[ASHRAE 90.1:TABLE 6.8.1-9]

EQUIPMENT TYPE SIZE CATEGORY HEATING SECTION TYPE SUBCATEGORY OR RATING CONDITION MINIMUM EFFICIENCY TEST PROCEDURE
VRF air conditioners, air cooled <65 000 Btu/h All VRF multisplit system 13.0 SEER AHRI 1230
≥65 000 Btu/h and <135 000 Btu/h Electric resistance (or none) VRF multisplit system 11.2 EER
13.1 IEER
(before 1/1/2017)
15.5 IEER
(as of 1/1/2017)
≥135 000 Btu/h and <240 000 Btu/h Electric resistance (or none) VRF multisplit system 11.0 EER
12.9 IEER
(before 1/1/2017)
14.9 IEER
(as of 1/1/2017)
≥240 000 Btu/h Electric resistance (or none) VRF multisplit system 10.0 EER
11.6 IEER
(before 1/1/2017)
13.9 IEER
(as of 1/1/2017)

For SI units: 1000 British thermal units per hour = 0.293 kW

TABLE E 503.7.1(10) ELECTRICALLY OPERATED VARIABLE-REFRIGERANT-FLOW AND APPLIED HEAT PUMPS — MINIMUM EFFICIENCY REQUIREMENTS
[ASHRAE 90.1:TABLE 6.8.1-10]

EQUIPMENT TYPE SIZE CATEGORY HEATING SECTION TYPE SUBCATEGORY OR RATING CONDITION MINIMUM EFFICIENCY TEST PROCEDURE
VRF air cooled (cooling mode) <65 000 Btu/h All VRF multisplit system 13.0 SEER AHRI 1230
≥65 000 Btu/h and <135 000 Btu/h Electric resistance (or none) 11.0 EER
12.9 IEER
(before 1/1/2017)
14.6 IEER
(as of 1/1/2017)
VRF multisplit system with heat recovery 10.8 EER
12.7 IEER
(before 1/1/2017)
14.4 IEER
(as of 1/1/2017)
≥135 000 Btu/h and <240 000 Btu/h VRF multisplit system 10.6 EER
12.3 IEER
(before 1/1/2017)
13.9 IEER
(as of 1/1/2017)
VRF multisplit system with heat recovery 10.4 EER
12.1 IEER
(before 1/1/2017)
13.7 IEER
(as of 1/1/2017)
≥240 000 Btu/h VRF multisplit system 9.5 EER
11.0 IEER
(before 1/1/2017)
12.7 IEER
(as of 1/1/2017)
VRF multisplit system with heat recovery 9.3 EER
10.8 IEER
(before 1/1/2017)
12.5 IEER
(as of 1/1/2017)
VRF water source (cooling mode) <65 000 Btu/h All VRF multisplit systems 86°F entering water 12.0 EER
16.0 IEER
(as of 1/1/2018)
AHRI 1230
VRF multisplit systems with heat recovery 86°F entering water 11.8 EER
15.8 IEER
(as of 1/1/2018)
≥65 000 Btu/h and <135 000 Btu/h VRF multisplit system 86°F entering water 12.0 EER
16.0 IEER
(as of 1/1/2018)
VRF multisplit system with heat recovery 86°F entering water 11.8 EER
15.8 IEER
(as of 1/1/2018)
≥135 000 Btu/h and <240 000 Btu/h VRF multisplit system 86°F entering water 10.0 EER
14.0 IEER
(as of 1/1/2018)
VRF multisplit system with heat recovery 86°F entering water 9.8 EER
13.8 IEER
(as of 1/1/2018)
≥240 000 Btu/h VRF multisplit system 86°F entering water 10.0 EER
(before 1/1/2018)
12.0 IEER
(as of 1/1/2018)
VRF multisplit system with heat recovery 86°F entering water 9.8 EER
(before 1/1/2018)
11.8 IEER
(as of 1/1/2018)
VRF groundwater source (cooling mode) <135 000 Btu/h All VRF multisplit system with heat recovery 59°F entering water 16.2 EER AHRI 1230
VRF multisplit system with heat recovery 59°F entering water 16.0 EER
≥135 000 Btu/h VRF multisplit system with heat recovery 59°F entering water 13.8 EER
VRF multisplit system with heat recovery 59°F entering water 13.6 EER
VRF ground source (cooling mode) <135 000 Btu/h All VRF multisplit system 77°F entering water 13.4 EER AHRI 1230
VRF multisplit system with heat recovery 77°F entering water 13.2 EER
≥135 000 Btu/h VRF multisplit system 77°F entering water 11.0 EER
VRF multisplit system with heat recovery 77°F entering water 10.8 EER
VRF Air cooled (heating mode) <65 000 Btu/h (cooling capacity) VRF Multi—split system 7.7 HSPF AHRI 1230
≥65 000 Btu/h and <135 000 Btu/h VRF Multi—split system 47°F db/43°F wb outdoor air 3.3 COPH
17°F db/15°F wb outdoor air 2.25 COPH
≥135 000 Btu/h (cooling capacity) VRF Multi—split system 47°F db/43°F wb outdoor air 3.2 COPH
17°F db/15°F wb outdoor air 2.05 COPH
VRF Water source (heating mode) <65 000 Btu/h (cooling capacity) VRF multisplit system 68°F entering water 4.2 COPH
(before 1/1/2018)
4.3 COPH
(as of 1/1/2018)
AHRI 1230
≥65 000 Btu/h and <135 000 Btu/h (cooling capacity) VRF multisplit system 68°F entering water 4.2 COPH
(before 1/1/2018)
4.3 COPH
(as of 1/1/2018)
≥135 000 Btu/h and <240 000 Btu/h (cooling capacity) VRF multisplit system 68°F entering water 3.9 COPH
(before 1/1/2018)
4.0 COPH
(as of 1/1/2018)
≥240 000 Btu/h (cooling capacity) VRF multisplit system 68°F entering water 3.9 COPH
VRF Groundwater source (heating mode) <135 000 Btu/h (cooling capacity) VRF Multi—split system 50°F entering water 3.6 COPH AHRI 1230
≥135 000 Btu/h (cooling capacity) VRF Multi—split system 50°F entering water 3.3 COPH
VRF Ground source (heating mode) <135 000 Btu/h (cooling capacity) VRF Multi—split system 32°F entering water 3.1 COPH AHRI 1230
≥135 000 Btu/h (cooling capacity) VRF Multi—split system 32°F entering water 2.8 COPH

For SI units: 1000 British thermal units per hour = 0.293 kW, °C=(°F—32)/1.8

TABLE E 503.7.1(11) AIR CONDITIONERS AND CONDENSING UNITS SERVING COMPUTER ROOMS MINIMUM EFFICIENCY REQUIREMENTS
[ASHRAE 90.1:TABLE 6.8.1-11]

EQUIPMENT TYPE NET SENSIBLE COOLING CAPACITY STANDARD MODEL MINIMUM NET SENSIBLE COPc TEST PROCEDURE
RETURN AIR DRY-BULB TEMPERATURE/ DEW-POINT TEMPERATURE
CLASS 1 CLASS 2 CLASS 3
75°F/52°F 85°F/52°F 95°F/52°F
Air cooled <65 000 Btu/h Downflow unit 2.30 AHRI 1360
Upflow unit—ducted 2.10
Upflow unit—nonducted 2.09
Horizontal-flow unit 2.45
≥65 000 Btu/h and <240 000 Btu/h Downflow unit 2.20
Upflow unit—ducted 2.05
Upflow unit—nonducted 1.99
Horizontal-flow unit 2.35
≥240 000 Btu/h Downflow unit 2.00
Upflow unit—ducted 1.85
Upflow unit—nonducted 1.79
Horizontal-flow unit 2.15
Water cooled <65 000 Btu/h Downflow unit 2.50 AHRI 1360
Upflow unit—ducted 2.30
Upflow unit—nonducted 2.25
Horizontal-flow unit 2.70
≥65 000 Btu/h and <240 000 Btu/h Downflow unit 2.40
Upflow unit—ducted 2.20
Upflow unit—nonducted 2.15
Horizontal-flow unit 2.60
≥240 000 Btu/h Downflow unit 2.25
Upflow unit—ducted 2.10
Upflow unit—nonducted 2.05
Horizontal-flow unit 2.45
Water cooled with fluid economizer <65 000 Btu/h Downflow unit 2.45 AHRI 1360
Upflow unit—ducted 2.25
Upflow unit—nonducted 2.20
Horizontal-flow unit 2.60
≥65 000 Btu/h and <240 000 Btu/h Downflow unit 2.35
Upflow unit—ducted 2.15
Upflow unit—nonducted 2.10
Horizontal-flow unit 2.55
≥240 000 Btu/h Downflow unit 2.20
Upflow unit—ducted 2.05
Upflow unit—nonducted 2.00
Horizontal-flow unit 2.40
Glycol cooled <65 000 Btu/h Downflow unit 2.30 AHRI 1360
Upflow unit—ducted 2.10
Upflow unit—nonducted 2.00
Horizontal-flow unit 2.40
≥65 000 Btu/h and <240 000 Btu/h Downflow unit 2.05
Upflow unit—ducted 1.85
Upflow unit—nonducted 1.85
Horizontal-flow unit 2.15
≥240 000 Btu/h Downflow unit 1.95
Upflow unit—ducted 1.80
Upflow unit—nonducted 1.75
Horizontal-flow unit 2.10
Glycol cooled with fluid economizer <65 000 Btu/h Downflow unit 2.25 AHRI 1360
Upflow unit—ducted 2.10
Upflow unit—nonducted 2.00
Horizontal-flow unit 2.35
≥65 000 Btu/h and <240 000 Btu/h Downflow unit 1.95
Upflow unit—ducted 1.80
Upflow unit—nonducted 1.75
Horizontal-flow unit 2.10
≥240 000 Btu/h Downflow unit 1.90
Upflow unit—ducted 1.80
Upflow unit—nonducted 1.70
Horizontal-flow unit 2.10

For SI units: 1000 British thermal units per hour = 0.293 kW, °C=(°F—32)/1.8

TABLE E 503.7.1(12) COMMERCIAL REFRIGERATOR AND FREEZERS — MINIMUM EFFICIENCY REQUIREMENTS
[ASHRAE 90.1:TABLE 6.8.1-12]

EQUIPMENT TYPE APPLICATION ENERGY USE LIMITS, KWH/DAY* TEST PROCEDURE
Refrigerator with solid doors Holding temperature 0.10 × V + 2.04 AHRI 1200
Refrigerator with transparent doors Holding temperature 0.12 × V +3.34 AHRI 1200
Freezers with solid doors Holding temperature 0.40 × V + 1.38 AHRI 1200
Freezers with transparent doors Holding temperature 0.75 × V + 4.10 AHRI 1200
Refrigerators/freezers with solid doors Holding temperature the greater of 0.12 × V + 3.34 or 0.70 AHRI 1200
Commercial refrigerators Pulldown 0.126 × V + 3.51 AHRI 1200

For SI units: 1000 British thermal units per hour per day = 0.293 kW/day

* V = the chiller or frozen compartment volume (ft3) as defined in Association of Home Appliance Manufacturers.

TABLE E 503.7.1(13) COMMERCIAL REFRIGERATION — MINIMUM EFFICIENCY REQUIREMENTS
[ASHRAE 90.1:TABLE 6.8.1-13]

EQUIPMENT TYPE ENERGY USE LIMITS2, 3 KWH/DAY TEST PROCEDURE
EQUIPMENT CLASS1 FAMILY CODE OPERATING MODE RATING TEMPERATURE
VOP.RC.M Vertical open Remote condensing Medium temperature 0.82 × TDA + 4.07 AHRI 1200
SVO.RC.M Semivertical open Remote condensing Medium temperature 0.83 × TDA + 3.18 AHRI 1200
HZO.RC.M Horizontal open Remote condensing Medium temperature 0.35 × TDA + 2.88 AHRI 1200
VOP.RC.L Vertical open Remote condensing Low temperature 2.27 × TDA + 6.85 AHRI 1200
HZO.RC.L Horizontal open Remote condensing Low temperature 0.57 × TDA + 6.88 AHRI 1200
VCT.RC.M Vertical transparent door Remote condensing Medium temperature 0.22 × TDA + 1.95 AHRI 1200
VCT.RC.L Vertical transparent door Remote condensing Low temperature 0.56 × TDA + 2.61 AHRI 1200
SOC.RC.M Service over counter Remote condensing Medium temperature 0.51 × TDA + 0.11 AHRI 1200
VOP.SC.M Vertical open Self contained Medium temperature 1.74 × TDA + 4.71 AHRI 1200
SVO.SC.M Semivertical open Self contained Medium temperature 1.73 × TDA + 4.59 AHRI 1200
HZO.SC.M Horizontal open Self contained Medium temperature 0.77 × TDA + 5.55 AHRI 1200
HZO.SC.L Horizontal open Self contained Low temperature 1.92 × TDA + 7.08 AHRI 1200
VCT.SC.I Vertical transparent door Self contained Ice cream 0.67 × TDA + 3.29 AHRI 1200
VCS.SC.I Vertical solid door Self contained Ice cream 0.38 × V+ 0.88 AHRI 1200
HCT. SC.I Horizontal transparent door Self contained Ice cream 0.56 × TDA + 0.43 AHRI 1200
SVO.RC.L Semivertical open Remote condensing Low temperature 2.27 × TDA + 6.85 AHRI 1200
VOP.RC.I Vertical open Remote condensing Ice cream 2.89 × TDA + 8.7 AHRI 1200
SVO.RC.I Semivertical open Remote condensing Ice cream 2.89 × TDA + 8.7 AHRI 1200
HZO.RC.I Horizontal open Remote condensing Ice cream 0.72 × TDA + 8.74 AHRI 1200
VCT.RC.I Vertical transparent door Remote condensing Ice cream 0.66 × TDA + 3.05 AHRI 1200
HCT.RC.M Horizontal transparent door Remote condensing Medium temperature 0.16 × TDA + 0.13 AHRI 1200
HCT.RC.L Horizontal transparent door Remote condensing Low temperature 0.34 × TDA + 0.26 AHRI 1200
HCT.RC.I Horizontal transparent door Remote condensing Ice cream 0.4 × TDA + 0.31 AHRI 1200
VCS.RC.M Vertical solid door Remote condensing Medium temperature 0.11 × V + 0.26 AHRI 1200
VCS.RC.L Vertical solid door Remote condensing Low temperature 0.23 × V + 0.54 AHRI 1200
VCS.RC.I Vertical solid door Remote condensing Ice cream 0.27 × V + 0.63 AHRI 1200
HCS.RC.M Horizontal solid door Remote condensing Medium temperature 0.11 × V + 0.26 AHRI 1200
HCS.RC.L Horizontal solid door Remote condensing Low temperature 0.23 × V + 0.54 AHRI 1200
HCS.RC.I Horizontal solid door Remote condensing Ice cream 0.27 × V + 0.63 AHRI 1200
HCS.RC.I Horizontal solid door Remote condensing Ice cream 0.27 × V+ 0.63 AHRI 1200
SOC.RC.L Service over counter Remote condensing Low temperature 1.08 × TDA + 0.22 AHRI 1200
SOC.RC.I Service over counter Remote condensing Ice cream 1.26 × TDA + 0.26 AHRI 1200
VOP.SC.L Vertical open Self contained Low temperature 4.37 × TDA + 11.82 AHRI 1200
VOP.SC.I Vertical open Self contained Ice cream 5.55 × TDA + 15.02 AHRI 1200
SVO.SC.L Semivertical open Self contained Low temperature 4.34 × TDA + 11.51 AHRI 1200
SVO.SC.I Semivertical open Self contained Ice cream 5.52 × TDA + 14.63 AHRI 1200
HZO.SC.I Horizontal open Self contained Ice cream 2.44 × TDA + 9.0 AHRI 1200
SOC.SC.I Service over counter Self contained Ice cream 1.76 × TDA + 0.36 AHRI 1200
HCS.SC.I Horizontal solid door Self contained Ice cream 0.38 × V+ 0.88 AHRI 1200

For SI units: 1000 British thermal units per hour per day = 0.293 kW/day, °C = (°F—32)/l .8

Notes:

1 Equipment class designations consist of a combination [in sequential order separated by periods (AAA).(BB).(C)] of the following:

(a) (AAA)—An equipment family code (VOP = vertical open, SVO = semivertical open, HZO = horizontal open, VCT = vertical transparent doors, VCS = vertical solid doors, HCT = horizontal transparent doors, HCS = horizontal solid doors, and SOC = service over counter).

(b) (BB)—An operating mode code (RC = remote condensing and SC = self contained).

(c) (C)—A rating temperature code (M = medium temperature [38°F], L = low temperature [0°F], or I = ice cream temperature [15°F]). For example, "VOP.RC.M" refers to the "vertical open, remote condensing, medium temperature" equipment class.

2 V is the volume of the case (ft) as measured in accordance with AHRI 1200.

3 TDA is the total display area of the case (ft) as measured in accordance with AHRI 1200.

TABLE E 503.7.1(14) VAPOR COMPRESSION BASED INDOOR POOL DEHUMIDIFIERS — MINIMUM EFFICIENCY REQUIREMENTS
[ASHRAE 90.1:TABLE 6.8.1-14]

EQUIPMENT TYPE SUBCATEGORY OR RATING CONDITION MINIMUM EFFICIENCY TEST PROCEDURE
Single package indoor* (with or without economizer) Rating Conditions: A, B, or C 3.5 MRE AHRI 910
Single package indoor water-cooled (with or without economizer) 3.5 MRE
Single package indoor air-cooled (with or without economizer) 3.5 MRE
Split system indoor air-cooled (with or without economizer) 3.5 MRE

* Units without air-cooled condenser

TABLE E 503.7.1(15) ELECTRICALLY OPERATED DX-DOAS UNITS, SINGLE-PACKAGE AND REMOTE CONDENSER, WITHOUT ENERGY RECOVERY — MINIMUM EFFICIENCY REQUIREMENTS
[ASHRAE 90.1:TABLE 6.8.1-15]

EQUIPMENT TYPE SUBCATEGORY OR CONDITION MINIMUM EFFICIENCY TEST PROCEDURE
Air cooled (dehumidification mode) 4.0 ISMRE AHRI 920
Air source heat pumps (dehumidification mode) 4.0 ISMRE AHRI 920
Water cooled (dehumidification mode) Cooling tower condenser water 4.9 ISMRE AHRI 920
Chilled Water 6.0 ISMRE
Air source heat pump (heating mode) 2.7 ISCOP AHRI 920
Water source heat pump (dehumidification mode) Ground source, closed loop 4.8 ISMRE AHRI 920
Ground-water source 5.0 ISMRE
Water source 4.0 ISMRE
Water source heat pump (heating mode) Ground source, closed loop 2.0 ISCOP AHRI 920
Ground-water source 3.2 ISCOP
Water source 3.5 ISCOP

TABLE E 503.7.1(16) ELECTRICALLY OPERATED DX-DOAS UNITS, SINGLE PACKAGE AND REMOTE CONDENSER, WITH ENERGY RECOVERY — MINIMUM EFFICIENCY REQUIREMENTS
[ASHRAE 90.1:TABLE 6.8.1-16]

EQUIPMENT TYPE SUBCATEGORY OR RATING CONDITION MINIMUM EFFICIENCY TEST PROCEDURE
Air cooled (dehumidification mode) 5.2 ISMRE AHRI 920
Air source heat pumps (dehumidification mode) 5.2 ISMRE AHRI 920
Water cooled (dehumidification mode) Cooling tower condenser water 5.3 ISMRE AHRI 920
Chilled Water 6.6 ISMRE
Air source heat pump (heating mode) 3.3 ISCOP AHRI 920
Water source heat pump (dehumidification mode) Ground source, closed loop 5.2 ISMRE AHRI 920
Ground—water source 5.8 ISMRE
Water source 4.8 ISMRE
Water source heat pump (heating mode) Ground source, closed loop 3.8 ISCOP AHRI 920
Ground—water source 4.0 ISCOP
Water source 4.8 ISCOP
Duct insulation shall comply with Table E 503.7.2.

TABLE E 503.7.2 MINIMUM DUCT INSULATION R-VALUE1
[ASHRAE 90.1:TABLE 6.8.2]

CLIMATE ZONE DUCT LOCATION
EXTERIOR2 UNCONDITIONED SPACE AND BURIED DUCTS INDIRECTLY CONDITIONED SPACE3, 4
SUPPLY AND RETURN DUCTS FOR HEATING AND COOLING
0 to 4 R-8 R-6 R-1.9
5 to 8 R-12 R-6 R-1.9
SUPPLY AND RETURN DUCTS FOR HEATING ONLY
0 to 1 none none none
2 to 4 R-6 R-6 R-1.9
5 to 8 R-12 R-6 R-1.9
SUPPLY AND RETURN DUCTS FOR COOLING ONLY
0 to 6 R-8 R-6 R-1.9
7 to 8 R-1.9 R-1.9 R-1.9

Notes:

1. Insulation R-values, measured in [°F•h•ft2/(Btu•in)] [(m•K)/W], are for the insulation as installed and do not include film resistance. The required minimum thicknesses do not consider water vapor transmission and possible surface condensation. Where portions of the building envelope are used as a plenum enclosure, building envelope insulation shall be as required by the most restrictive condition of Section E 503.4.7.1 or ASHRAE 90.1, depending on whether the plenum is located in the roof, wall, or floor. Insulation resistance measured on a horizontal plane in accordance with ASTM C518 at a mean temperature of 75°F (24°C) at the installed thickness.

2 Includes attics above insulated ceilings, parking garages and crawl spaces.

3 Includes return air plenums, with or without exposed roofs above.

4. Return ducts in this duct location do not require insulation.

Pipe insulation shall comply with Table E 503.7.3(1) through Table E 503.7.3(2).

TABLE E 503.7.3(1) MINIMUM PIPE INSULATION THICKNESS FOR HEATING AND HOT WATER SYSTEMS1, 2, 3, 4, 5
(STEAM, STEAM CONDENSATE, HOT WATER HEATING, AND DOMESTIC WATER SYSTEMS)
[ASHRAE 90.1:TABLE 6.8.3-1]

FLUID OPERATING TEMPERATURE RANGE (F°) AND USAGE INSULATION CONDUCTIVITY NOMINAL PIPE SIZE OR TUBE SIZE (inches)
CONDUCTIVITY Btu•inch/(h•ft2•°F) MEAN RATING TEMPERATURE °F <1 1 to <11/2 11/2 to <4 4 to <8 ≥8
INSULATION THICKNESS (inches)
>350 0.32 — 0.34 250 4.5 5.0 5.0 5.0 5.0
251 — 350 0.29 — 0.32 200 3.0 4.0 4.5 4.5 4.5
201 — 250 0.27 — 0.30 150 2.5 2.5 2.5 3.0 3.0
141 — 200 0.25 — 0.29 125 1.5 1.5 2.0 2.0 2.0
105 — 140 0.22 — 0.28 100 1.0 1.0 1.5 1.5 1.5

For SI units: °C=(°F—32)/l .8, 1 inch = 25 mm, 1 British thermal unit inch per hour square foot degree Fahrenheit =[0.1 W/(m•K)]

Notes:

1 For insulation outside the stated conductivity range, the minimum thickness (T) shall be determined as follows:

T = r{(1 + t/r)K/k — 1}

Where:

T = minimum insulation thickness (inches).
r = actual outside radius of pipe (inches).
t = insulation thickness listed in this table for applicable fluid temperature and pipe size.
K = conductivity of alternate material at mean rating temperature indicated for the applicable fluid temperature [Btu•in/(h•ft2•°F)][(W/(m•K)].
k = the upper value of the conductivity range listed in this table for the applicable fluid temperature.

2 These thicknesses shall be based on energy efficiency considerations only. Additional insulation shall be permitted to required relative to safety issues/surface temperature.

3 Piping 11/2 inches (40 mm) or less and located in partitions within conditioned spaces, reduction of insulation thickness by 1 inch (25.4 mm) shall be permitted before thickness adjustment required in footnote 1, but not a thickness less than 1 inch (25.4 mm).

4 For direct-buried heating and hot water system piping, reduction of insulation thickness by 11/2 inch (40 mm) shall be permitted before thickness adjustment required in footnote 1, but not a thickness less than 1 inch (25.4 mm).

5 Table E 503.7.3(1) is based on steel pipe. Non-metallic pipes, less than schedule 80 thickness shall use the table values. For other non-metallic pipes having a thermal resistance more than that of steel pipe, reduced insulation thicknesses shall be permitted where documentation is provided showing that the pipe with the proposed insulation has less heat transfer per foot (mm) than a steel pipe of the same size with the insulation thickness shown in Table E 503.7.3(1).

TABLE E 503.7.3(2) MINIMUM PIPE INSULATION THICKNESS FOR COOLING SYSTEMS (CHILLED WATER, BRINE, AND REFRIGERANT)1, 2, 3, 4
[ASHRAE 90.1:TABLE 6.8.3-2]

INSULATION CONDUCTIVITY NOMINAL PIPE SIZE OR TUBE SIZE (inches)
FLUID OPERATING TEMPERATURE RANGE (°F) AND USAGE CONDUCTIVITY Btu•inch/(h•f2•°F) MEAN RATING TEMPERATURE °F <1 1 to <11/2 11/2 to <4 4 to <8 >8
INSULATION THICKNESS(lnches)
40°F — 60°F 021 — 0.27 75 0.5 0.5 1.0 1.0 1.0
<40°F 0.20 — 0.26 50 0.5 1.0 1.0 1.0 1.5

For SI units: °C=(°F—32)/l .8, 1 inch = 25 mm, 1 British thermal unit inch per hour square foot degree Fahrenheit =[0.1 W/(m•K)]

Notes:

1 For insulation outside the stated conductivity range, the minimum thickness (T) shall be determined as follows:

T = r{(1 + t/r)K/k — 1}

Where:

T = minimum insulation thickness (inches).
r = actual outside radius of pipe (inches).
t = insulation thickness listed in this table for applicable fluid temperature and pipe size.
K = conductivity of alternate material at mean rating temperature indicated for the applicable fluid temperature [Btu•in/(h•ft2•°F)][(W/(m•K)].
k = the upper value of the conductivity range listed in this table for the applicable fluid temperature.

2 These thicknesses shall be based on energy efficiency considerations only. Issues such as water, vapor permeability, or surface condensation require vapor retarders or additional insulation.

3 Insulation shall not be required for direct-buried cooling system piping.

4 Table E 503.7.3(2) is based on steel pipe. Non-metallic pipes less than schedule 80 thickness shall use the table values. For other non-metallic pipes having thermal resistance more than that of steel pipe, reduced insulation thicknesses shall be permitted where documentation is provided showing that the pipe with the proposed insulation has less heat transfer per foot (mm) than a steel pipe of the same size with the insulation thickness shown in Table E 503.7.3(2).

HVAC systems serving heating, cooling, or ventilation needs of a computer room shall be in accordance with Section E 503.1, Section E 503.4, Section E 503.8.1 or Section E 503.8.2, Section E 503.8.3, Section E 502.7 through Section E 502.7.2, and Section E 503.7. [ASHRAE 90.1:6.6.1]
The computer room PUE1 shall be not more than the values listed in Table E 503.8.1. Hourly simulation of the proposed design, for purposes of calculating PUE1, shall be in accordance with ASHRAE 90.1.

Exception: The compliance path shall not be permitted for a proposed computer room design utilizing a combined heat and power system. [ASHRAE 90.1:6.6.1.1]

TABLE E 503.8.1 POWER USAGE EFFECTIVENESS (PUE) MAXIMUM
[ASHRAE 90.1:TABLE 6.6.1]

CLIMATE ZONE PUE*
0A 1.64
0B 1.62
1A 1.61
2A 1.49
3A 1.41
4A 1.36
5A 1.36
6A 1.34
1B 1.53
2B 1.45
3B 1.42
4B 1.38
5B 1.33
6B 1.33
3C 1.39
4C 1.38
5C 1.36
7 1.32
8 1.30

* PUE0 and PUE1 shall not include energy for battery charging.

The computer room PUE0 shall be not more than the values listed in Table E 503.8.1. The PUE0 shall be the highest value determined at outdoor cooling design temperatures, and shall be limited to systems utilizing electricity for an energy source. The PUE0 shall be calculated for the following conditions:
  1. One hundred percent design IT equipment energy.
  2. Fifty percent design IT equipment energy. [ASHRAE 90.1:6.6.1.2]
Documentation on the following components shall be provided, including a breakdown of energy consumption or demand:
  1. IT equipment
  2. Power distribution losses external to the IT equipment
  3. HVAC systems
  4. Lighting [ASHRAE 90.1:6.6.1.3]
Solar energy systems shall be installed in accordance with the Uniform Solar Energy and Hydronics Code (USEHC).
Geothermal systems that use the earth or body of water as a heat source or sink for heating or cooling shall be in accordance with Section E 505.1.1 through Section E 509.2.
Geothermal systems shall be designed by a registered design professional. The geothermal system design, installation, and testing shall be in accordance with CSA C448.
Water source heat pumps used in conjunction with geothermal heat exchangers shall be listed and labeled for use in such systems and shall be designed for the minimum and maximum design water temperature.
Ground source heat pump ground-loop piping and tubing material for water-based systems shall comply with the standards cited in this appendix.
Piping shall be rated for the operating temperature and pressure of the ground source heat pump-loop system. Fittings shall be rated for the temperature and pressure applications and recommended by the manufacturer for installation with the piping material installed. Where used underground, materials shall be approved for burial.
The installation of used pipe, fittings, valves, and other materials shall not be permitted.
Ground source heat pump ground-loop pipe and tubing shall comply with the standards listed in Table E 505.5.

TABLE E 505.5 PLASTIC GROUND SOURCE LOOP PIPING

MATERIAL STANDARD
Chlorinated polyvinyl chloride (CPVC) ASTM D2846; ASTM F441; ASTM F442
Cross-linked polyethylene (PEX) ASTM F876; ASTM F877; CSA B137.5; NSF 358-3
Polyethylene/aluminum/poly-ethylene (PE-AL-PE) pressure pipe ASTM F1282; CSA B137.9
High Density Polyethylene (HDPE) ASTM D2737; ASTM D3035; ASTM F714; AWWAC901; CSA B137.1; CSA C448; NSF 358-1
Polypropylene (PP) ASTM F2389; CSA B137.11; NSF 358-2
Polyvinyl chloride (PVC) ASTM D1785; ASTM D2241
Polyethylene Raised Temperature (PE-RT) ASTM F2623; ASTM F2769
Fittings for ground source heat pump systems shall be approved for installation with the piping materials to be installed, and shall comply with the standards listed in Table E 505.6.

TABLE E 505.6 GROUND SOURCE LOOP PIPE FITTINGS

MATERIAL STANDARD
Chlorinated polyvinyl chloride (CPVC) ASTM D2846; ASTM F437; ASTM F438; ASTM F439; ASTM F1970; CSA B137.6
Cross-linked polyethylene (PEX) ASTM F877; ASTM F1807; ASTM F1960; ASTMF2080; ASTM F2159; ASTM F2434; CSAB137.5; NSF 358-3
Polyethylene/aluminum/poly- ethylene (PE-AL-PE) ASTM F1282; ASTM F2434; CSAB137.9
High Density Polyethylene (HDPE) ASTM D2683; ASTM D3261; ASTM F1055; CSA B137.1; CSA C448; NSF 358-1
Polypropylene (PP) ASTM F2389; CSA B137.11, NSF 358-2
Polyvinyl chloride (PVC) ASTM D2464; ASTM D2466; ASTM D2467; ASTM F1970; CSA B 137.2; CSA B137.3
Polyethylene Raised Temperature (PE-RT) ASTM D3261; ASTM F1807; ASTM F2159; ASTM F2769; CSA B137.1
Joints and connections shall be of an approved type. Joints and connections shall be tight for the pressure of the ground source-loop system. Joints and fittings used underground shall be approved for buried applications.
Joints between various piping materials shall be made with approved transition fittings.
Pipe shall be cut square, reamed, and free of burrs and obstructions. Pipe ends shall have full-bore openings and shall not be undercut. CPVC, PE, and PVC pipe shall be chamfered.
Where required by Section E 506.5 through Section E 506.12.2, the preparation and installation of mechanical and thermoplastic-welded joints shall be in accordance with Section E 506.4 and Section E 506.5.
Mechanical joints shall be installed in accordance with the manufacturer's installation instructions.
Joint surfaces for thermoplastic welded joints shall be cleaned by an approved procedure. Joints shall be welded in accordance with the manufacturer's installation instructions.
Joints between CPVC plastic piping and fittings shall comply with Section E 506.7.1 and Section E 506.7.2.
Threads shall comply with ASME B1.20.1. Schedule 80 or heavier plastic pipe shall be threaded with dies specifically designed for plastic pipe. Thread lubricant, pipe-joint compound or tape shall be applied on the male threads only and shall be approved for application on the piping material.
Solvent cement joints for CPVC pipe and fittings shall be clean from dirt and moisture. Solvent cements in accordance with ASTM F493, requiring the use of a primer, shall be orange in color. The primer shall be colored and be in accordance with ASTM F656. Listed solvent cement in accordance with ASTM F493 that does not require the use of primers, yellow or red in color shall be permitted for pipe and fittings manufactured in accordance with ASTM D2846, 1/2 of an inch (15 mm) through 2 inches (50 mm) in diameter.
Compression or plastic to metal transition joints between cross-linked polyethylene plastic tubing and fittings shall comply with Section E 506.8.1 and Section E 506.8.2. Mechanical joints shall comply with Section E 506.5.