ADOPTS WITH AMENDMENTS:

International Existing Building Code 2018 (IEBC 2018)

Heads up: There are no amended sections in this chapter.
Editor's Note—Because of the extensive changes to this chapter made by the ordinance adopted February 19, 2020, the chapter, as amended, is reprinted in its entirety.

14R-8-801 The provisions of Section 801 of IEBC are adopted by reference with the following modifications:

Added Coun. J. 4-10-19, p. 100029.

Amended Coun. J. 2-19-20, p. 14474.

Amended Coun. J. 10-7-20, p. 21791.

Level 2 alterations as described in Section 603 shall comply with the requirements of this chapter.

Exception: Buildings in which the reconfiguration is exclusively the result of compliance with the accessibility requirements of Section 305.7 shall be allowed to comply with Chapter 7.

In addition to the requirements of this chapter, all work shall comply with the requirements of Chapter 7.

New construction elements, components, systems, and spaces shall comply with the requirements of the Chicago Building Code.

Exceptions:

  1. Where windows are added to an existing space, the room or space is not required to comply with the natural light and ventilation requirements of the Chicago Building Code to a greater extent than before the alteration.
  2. Newly installed electrical equipment shall comply with Section 807.
  3. The length of dead-end corridors in newly constructed or reconfigured spaces shall only be required to comply with Section 805.6.
  4. The minimum ceiling height of newly created habitable and occupiable spaces and corridors shall be 7 feet (2134 mm) except where a lower ceiling height is allowed by the Chicago Building Code.
  5. Where provided in below-grade transportation stations, existing and new escalators shall be allowed to have a clear width of less than 32 inches (815 mm).
  6. New structural members and connections shall be allowed to comply with alternative design criteria in accordance with Section 302.

14R-8-802 The provisions of Section 802 of IEBC are adopted by reference with the following modifications:

Added Coun. J. 4-10-19, p. 100029.

Amended Coun. J. 2-19-20, p. 14474.

The requirements of this section are limited to work areas in which Level 2 alterations are being performed and shall apply beyond the work area where specified.
Existing vertical openings shall comply with the provisions of Sections 802.2.1, 802.2.2 and 802.2.3.

Existing interior vertical openings connecting two or more stories shall be enclosed with assemblies having a fire-resistance rating of not less than 1 hour with opening protectives.

Exceptions:

  1. Where unenclosed vertical openings are allowed by the Chicago Building Code.
  2. Interior vertical openings other than stairways may be blocked at each floor and ceiling within the work area by installation of not less than 2 inches (51 mm) nominal solid wood or equivalent construction.
  3. The enclosure shall not be required where:

    1. 3.1. [Reserved]
    2. 3.2. All of the following conditions are met:

      1. 3.2.1. The connected stories are protected throughout by an automatic sprinkler system.
      2. 3.2.2. The lowest or next-to-the-lowest story is a level of exit discharge.
      3. 3.2.3. The entire area is open and unobstructed in a manner such that it is reasonable to assume that a fire in any part of the interconnected spaces will be readily obvious to all of the occupants.
      4. 3.2.4. Exit capacity is sufficient to provide egress simultaneously for all occupants of all connected stories by considering all areas to be a single floor area for the determination of required exit capacity.
      5. 3.2.5. Each story considered separately, has not less than one-half of its individual required exit capacity provided by an exit or exits leading directly out of that story without having to traverse another connected story or be exposed to the smoke or fire spreading from another connected story.
  4. [Reserved]
  5. In Group B occupancies, a minimum 30-minute enclosure shall be provided to protect all vertical openings not exceeding three stories. This enclosure shall not be required in the following locations:

    1. 5.1. Buildings not exceeding 3,000 square feet (279 m2) per story.
    2. 5.2. Buildings protected throughout by an automatic sprinkler system.
  6. [Reserved]
  7. In Group F occupancies, the enclosure shall not be required in the following locations:

    1. 7.1. Vertical openings not exceeding three stories.
    2. 7.2. Special-purpose occupancies where necessary for manufacturing operations and direct access is provided to not fewer than one protected stairway.
  8. In Group H occupancies, the enclosure shall not be required for vertical openings not exceeding three stories where necessary for manufacturing operations and every floor level has direct access to not fewer than two remote enclosed stairways or other approved exits.
  9. In Group M occupancies, a minimum 30-minute enclosure shall be provided to protect all vertical openings not exceeding three stories. This enclosure shall not be required in the following locations:

    1. 9.1. Openings connecting only two stories.
    2. 9.2. Occupancies protected throughout by an automatic sprinkler system.
  10. [Reserved]
  11. In Group R-2 occupancies, a minimum 30-minute enclosure shall be provided to protect all vertical openings not exceeding four stories. This enclosure shall not be required in the following locations:

    1. 11.1. Vertical openings not exceeding two stories with not more than four dwelling units per story.
    2. 11.2. Buildings protected throughout by an automatic sprinkler system.
  12. Buildings of Group R-3, R-4, or R-5 occupancy.
  13. Group S occupancies where connecting not more than two stories or where connecting not more than three stories and the structure is equipped throughout with an automatic sprinkler system.

Where the work area on any story exceeds 50 percent of the floor area, the enclosure requirements of Section 802.2 shall apply to vertical openings other than stairways throughout the story.

Exception: Vertical openings located in tenant spaces that are entirely outside the work area.

Where the work area on any story exceeds 50 percent of the floor area, stairways that are part of the means of egress serving the work area shall, at a minimum, be enclosed with smoke-tight construction on the highest work area story and all stories below.

Exception: Where unenclosed stairways are allowed by the Chicago Building Code.

In Group I-2 occupancies where the work area is on a story used for sleeping rooms for more than 30 patients, the story shall be divided into not less than two compartments by smoke barrier walls in accordance with Section 407.5 of the Chicago Building Code as required for new construction.

The interior finish of walls and ceilings in exits and corridors in any work area shall comply with the requirements of the Chicago Building Code.

Exception: Existing interior finish materials that do not comply with the interior finish requirements of the Chicago Building Code shall be allowed to be treated with a fire-retardant coating in accordance with the manufacturer's instructions to achieve the required rating.

Where the work area on any story exceeds 50 percent of the floor area, Section 802.4 shall apply to the interior finish in exits and corridors serving the work area throughout the story.

Exception: Interior finish within tenant spaces that are entirely outside the work area.

The requirements of Sections 802.5.1 and 802.5.2 shall apply in all work areas.

Every portion of a floor, such as a balcony or a loading dock, that is more than 30 inches (762 mm) above the floor or grade below and is not provided with guards, or those in which the existing guards are judged to be in danger of collapsing, shall be provided with guards.

Exception: At locations where guards are not required by the Chicago Building Code.

Where there are no guards or where existing guards must be replaced, the new guards shall be designed and installed in accordance with the Chicago Building Code.

Where approved by the building official, buildings where an automatic sprinkler system installed in accordance with Section 903.3.1.1 or 903.3.1.2 of the Chicago Building Code has been added, and the building is now sprinklered throughout, the required fire-resistance ratings of building elements and materials shall be allowed to meet the requirements of the Chicago Building Code. The building is required to meet the other applicable requirements of the Chicago Building Code.

Plans, investigation and evaluation reports, and other data shall be submitted indicating which building elements and materials the applicant is requesting the building official to review and approve for determination of applying the fire-resistance ratings provided by the Chicago Building Code. Any special construction features, including fire-resistance-rated assemblies and smoke-resistive assemblies, conditions of occupancy, means-of-egress conditions, fire code deficiencies, approved modifications or approved alternative materials, design and methods of construction, and equipment applying to the building that impact required fire-resistance ratings shall be identified in the evaluation reports submitted.

Where an automatic sprinkler system is installed throughout a story, the required fire-resistance rating for any corridor located on the story shall be allowed to be reduced in accordance with the Chicago Building Code. In order to be considered for a corridor rating reduction, the automatic sprinkler system shall provide coverage for the stairway landings serving the floor and the intermediate landings immediately below.

14R-8-803 The provisions of Section 803 of IEBC are adopted by reference with the following modifications:

Added Coun. J. 4-10-19, p. 100029.

Amended Coun. J. 2-19-20, p. 14474.

The requirements of this section shall be limited to work areas in which Level 2 alterations are being performed, and where specified they shall apply throughout the story on which the work areas are located or otherwise beyond the work area.

Automatic sprinkler systems shall be provided in accordance with the requirements of Sections 803.2.1 through 803.2.4. Installation requirements shall be in accordance with the Chicago Building Code.
In high-rise buildings, work areas that have exits or corridors shared by more than one tenant or that have exits or corridors serving an occupant load greater than 30 shall be provided with automatic sprinkler protection in the entire work area where the work area is located on a story that has a sufficient sprinkler water supply system from an existing standpipe or a sprinkler riser serving that story.

Where the work area on any story exceeds 50 percent of the floor area, Section 803.2.1 shall apply to the entire story on which the work area is located.

Exception: Occupied tenant spaces that are entirely outside the work area.

In buildings with occupancies in Groups A, B, E, F-1, H, I, M, R-1, R-2, R-4, S-1 and S-2, work areas that have exits or corridors shared by more than one tenant or that have exits or corridors serving an occupant load greater than 30 shall be provided with automatic sprinkler protection where both of the following conditions occur:

  1. The work area is required to be provided with automatic sprinkler protection in accordance with the Chicago Building Code as applicable to new construction.
  2. The work area exceeds 50 percent of the floor area of the story.

Exceptions:

  1. If the existing building does not have sufficient municipal water supply for design of an automatic sprinkler system available to the work area without installation of a new fire pump or new water service, work areas shall be protected by an automatic smoke detection system throughout all occupiable spaces, other than sleeping units or individual dwelling units, that activates the occupant notification system in accordance with Sections 907.4, 907.5 and 907.6 of the Chicago Building Code.
  2. Group R-2 occupancies not containing congregate living facilities with no more than four stories above grade plane and no more than 20 dwelling units where each dwelling unit is equipped with hardwired smoke alarms in accordance with Section 907.2.10.2 of the Chicago Building Code.
In work areas containing mixed uses, one or more of which requires automatic sprinkler protection in accordance with Section 803.2.2, such protection shall not be required throughout the work area provided that the uses requiring such protection are separated from those not requiring protection by fire-resistance-rated construction having a minimum rating as provided in Section 508 of the Chicago Building Code.
Work located in a windowless story, as determined in accordance with the Chicago Building Code, shall be sprinklered where the work area is required to be sprinklered under the provisions of the Chicago Building Code for newly constructed buildings and the building has a sufficient municipal water supply without installation of a new fire pump or new water service.
Automatic sprinkler systems required by this section shall be supervised as required by the Chicago Building Code.

Where the work area includes exits or corridors shared by more than one tenant and the finished floor is located more than 50 feet (15 240 mm) above or below grade plane, a standpipe system shall be provided. Standpipe systems shall be installed in accordance with the Chicago Building Code.

Exceptions:

  1. A pump shall not be required provided that the standpipes are capable of accepting delivery by fire department apparatus of not less than 250 gallons per minute (gpm) at 65 pounds per square inch (psi) (946 L/m at 448KPa) to the highest story in buildings equipped throughout with an automatic sprinkler system or not less than 500 gpm at 65 psi (1892 L/m at 448KPa) to the highest story in all other buildings. Where the standpipe terminates below the highest story, the standpipe shall be designed to meet (gpm/psi) (L/m/KPa) requirements of this exception for possible future extension of the standpipe.
  2. The interconnection of multiple standpipe risers shall not be required.

A fire alarm and detection system shall be installed in accordance with Sections 803.4.1 and 803.4.3. Where automatic sprinkler protection is provided in accordance with Section 803.2 and is connected to the building fire alarm system, automatic heat detection shall not be required.

An automatic fire detection system shall be installed in accordance with the provisions of this code and NFPA 72. The automatic fire detectors shall be smoke detectors, except that an alternative type of detector shall be installed in spaces such as boiler rooms, where products of combustion are present during normal operation in sufficient quantity to actuate a smoke detector.

A fire alarm system shall be installed in occupancies where required by Section 506.4 of the Chicago Minimum Requirements for Existing Buildings.

Individual sleeping units and individual dwelling units in any work area in Group R and I-1 occupancies shall be provided with smoke alarms in accordance with the Chicago Minimum Requirements for Existing Buildings.

Exception: Interconnection of smoke alarms outside of the work area shall not be required.

14R-8-804 The provisions of Section 804 of IEBC are adopted by reference with the following modification:

Added Coun. J. 4-10-19, p. 100029.

Amended Coun. J. 2-19-20, p. 14474.

Any work area shall be equipped with carbon monoxide alarms in accordance with Section 504.9 of the Chicago Minimum Requirements for Existing Buildings.

Exceptions:

  1. Work involving the exterior surfaces of buildings, such as the replacement of roofing or siding, the addition or replacement of windows or doors, or the addition of porches or decks.
  2. Installation, alteration or repair of plumbing or mechanical systems, other than fuel-burning appliances.

14R-8-805 The provisions of Section 805 of IEBC are adopted by reference with the following modifications:

Added Coun. J. 4-10-19, p. 100029.

Amended Coun. J. 2-19-20, p. 14474

Amended Coun. J. 10-7-20, p. 21791.

The requirements of this section shall be limited to work areas that include exits or corridors shared by more than one tenant and where specified they shall apply throughout the story on which the work areas are located or otherwise beyond the work area.

The means of egress shall comply with the requirements of this section.

Exception: Means of egress complying with the requirements in effect at the time the means of egress was constructed or altered shall be considered to be compliant means of egress if, in the opinion of the building official, they do not constitute a distinct hazard to life.

The number of exits shall be in accordance with Sections 805.3.1 through 805.3.3.
Every story utilized for human occupancy on which there is a work area that includes exits or corridors shared by more than one tenant within the work area shall be provided with the minimum number of exits based on the occupancy and the occupant load in accordance with the Chicago Building Code. In addition, the exits shall comply with Sections 805.3.1.1 and 805.3.1.2.

A single exit or access to a single exit shall be permitted from spaces, any story or any occupiable rooftop in accordance with Section 1006.3 of the Chicago Building Code.

For other than Group I, where more than one exit is required, an existing or newly constructed fire escape complying with Section 307 may be approved by the building official as providing one of the required means of egress where conditions do not allow the construction of more adequate means of egress facilities.
The fire escape shall be designed to support a live load of 100 pounds per square foot (4788 Pa) and shall be constructed of steel or other approved noncombustible materials. Fire escapes constructed of wood not less than nominal 2 inches (51 mm) thick are permitted on buildings of Type V construction. Walkways and railings located over or supported by combustible roofs in buildings of Types III and IV construction are permitted to be of wood not less than nominal 2 inches (51 mm) thick.
Stairways shall be not less than 22 inches (559 mm) wide with risers not more than, and treads not less than, 8 inches (203 mm). Landings at the foot of stairways shall be not less than 40 inches (1016 mm) wide by 36 inches (914 mm) long and located not more than 8 inches (203 mm) below the door.

Mezzanines in the work area and with an occupant load of more than 50 or in which the travel distance to an exit exceeds 75 feet (22 860 mm) shall have access to not fewer than two independent means of egress.

Exception: Two independent means of egress are not required where the travel distance to an exit does not exceed 100 feet (30 480 mm) and the building is protected throughout with an automatic sprinkler system.

Buildings of Group A with an occupant load of 300 or more shall be provided with a main entrance capable of serving as the main exit with an egress capacity of not less than one-half of the total occupant load. The remaining exits shall be capable of providing one-half of the total required exit capacity.

Exception: Where a main exit is not well defined or where multiple main exits are provided, exits shall be allowed to be distributed around the perimeter of the building provided that the total width of egress is not less than 100 percent of the required width.

Egress doorways in any work area shall comply with Sections 805.4.1 through 805.4.5.
Work areas shall be provided with two egress doorways in accordance with the requirements of Sections 805.4.1.1 and 805.4.1.2.

In any work area, all rooms and spaces having an occupant load greater than 50 or in which the common path of egress travel exceeds 75 feet (22 860 mm) shall have not fewer than two egress doorways.

Exceptions:

  1. Storage rooms having a maximum occupant load of 10.
  2. Single-exit conditions in accordance with Section 805.3.1.1.
In buildings of Group I-2 occupancy, any patient sleeping room or suite of patient rooms greater than 1,000 square feet (93 m2) within the work area shall have not fewer than two egress doorways.
In the work area and in the egress path from any work area to the exit discharge, all egress doors serving an occupant load greater than 50 shall swing in the direction of exit travel.
Exception: In Group B occupancies, existing egress doors and replacement egress doors of the same size and configuration installed in the same location shall be allowed to swing opposite the direction of egress travel when opening onto a corridor and serving an occupant load of 100 or less.

Where the work area exceeds 50 percent of the floor area of the story, door swing shall comply with Section 805.4.2 throughout the story.

Exception: Means of egress within or serving only a tenant space that is entirely outside the work area.

In any work area, all doors opening onto an exit passageway or an exit stairway shall be self-closing or automatic-closing by listed closing devices.

Exceptions:

  1. Where exit enclosure is not required by the Chicago Building Code.
  2. Means of egress within or serving only a tenant space that is entirely outside the work area.
Where the work area exceeds 50 percent of the floor area of a story, doors shall comply with Section 805.4.3 throughout the exit stairway from that story to, and including, the level of exit discharge.
In any work area, and in the egress path from any work area to the exit discharge, in buildings or portions thereof of Group A assembly occupancies with an occupant load greater than 100, all required egress doors equipped with latching devices shall be equipped with panic hardware meeting the requirements of the Chicago Building Code or other approved panic hardware.

Where the work area exceeds 50 percent of the floor area of a story, panic hardware shall comply with Section 805.4.4 throughout that story.

Exception: Means of egress within a tenant space that is entirely outside the work area.

Power-operated sliding doors or power-operated locks for swinging doors shall be operable by a manual release mechanism at the door. Emergency power shall be provided for the doors and locks in accordance with Section 2702 of the Chicago Building Code.

Exceptions:

  1. Emergency power is not required in facilities with 10 or fewer locks complying with the exception to Section 408.4.1 of the Chicago Building Code.
  2. Emergency power is not required where remote mechanical operating releases are provided.

Openings in corridor walls in any work area shall comply with Sections 805.5.1 through 805.5.4.

Exception: Openings in corridors where such corridors are not required to be rated in accordance with the Chicago Building Code or where the openings are provided with opening protectives in accordance with the Chicago Building Code.

Corridor doors in the work area shall not be constructed of hollow core wood and shall not contain louvers. Dwelling unit or sleeping unit corridor doors in work areas in buildings of Groups R and I-1 shall be not less than 13/8-inch (35 mm) solid core wood or approved equivalent and shall not have any glass panels, Dwelling unit or sleeping unit corridor doors in work areas in buildings of Groups R and I-1 shall be equipped with door closers. Replacement doors shall be 13/4-inch (44 mm) solid bonded wood core or approved equivalent.

Exceptions:

  1. Corridor doors within a dwelling unit, sleeping unit or single tenant space.
  2. Existing doors meeting the requirements of Resource A for a rating of 15 minutes or more shall be accepted as meeting the provisions of this requirement.
  3. [Reserved]
  4. [Reserved]
  5. Door assemblies having a fire protection rating of not less than 20 minutes.
  6. Existing doors to electrical rooms and utility rooms not exceeding 50 square feet (4.6m2) in floor area may remain.

In all buildings of Group I-1, I-2, and R occupancies, all transoms in corridor walls in work areas shall be either glazed with 1/4-inch (6.4 mm) wired glass set in metal frames or other glazing assemblies having a fire protection rating as required for the door and permanently secured in the closed position or sealed with materials consistent with the corridor construction.

Exception: Corridor walls within a dwelling unit, sleeping unit or single-tenant space.

In any work area, any other sash, grille, or opening in a corridor and any window in a corridor not opening to the outside air shall be sealed with materials consistent with the corridor construction.

Where the work area exceeds 50 percent of the floor area of a story, Section 805.5.3 shall be applicable to all corridor windows, grills, sashes, and other openings throughout the story.

Exception: Means of egress within or serving only a tenant space that is entirely outside the work area.

Where the work area on any story exceeds 50 percent of the floor area, the requirements of Sections 805.5.1 through 805.5.3 shall apply throughout the story.

Dead-end corridors in any work area shall not exceed the length specified in Table 805.6.

Exception: Where dead-end corridors of greater length are allowed by the Chicago Building Code.
TABLE 805.6
MAXIMUM LENGTH OF DEAD-END CORRIDORS (feet)
OCCUPANCY CLASSIFICATION EXISTING OR EXTENDED CORRIDOR NEWLY CREATED CORRIDOR OR CHANGE OF OCCUPANCY
NS S NS S
Group A-1, A-3, A-4 or A-5 75 75 35 50
Group A-2 50 75 35 50
Group B, F, M, S or U 75 115 35 50
Group E-1 20 20 20 20
Group E-2 or I-4 20 50 35 50
Group H 20 40 0 20
Group I-1 0 50 0 50
Group I-2 0 20 0 20
Group I-3  50 50 35 50
Group R  50 50 35 50
For SI: 1 foot = 304.8 mm.
Means-of-egress lighting shall be in accordance with this section, as applicable.
Means of egress in all work areas shall be provided with artificial lighting in accordance with the requirements of the Chicago Building Code and Chicago Electrical Code.

Where the work area on any story exceeds 50 percent of the floor area, means of egress throughout the story shall comply with Section 805.7.1.

Exception: Means of egress within or serving only a tenant space that is entirely outside the work area.

Exit signs shall be in accordance with this section, as applicable.
Means of egress in all work areas shall be provided with exit signs in accordance with the requirements of the Chicago Building Code.

Where the work area on any story exceeds 50 percent of the floor area, means of egress throughout the story shall comply with Section 805.8.1.

Exception: Means of egress within a tenant space that is entirely outside the work area.

The requirements of Sections 805.9.1 and 805.9.2 shall apply to handrails from the highest work area story to, and including, the level of exit discharge.
Every stairway that is part of the required means of egress for any work area and that has three or more risers and is not provided with at least one handrail, or in which the existing handrails are judged to be in danger of collapsing, shall be provided with handrails for the full length of the stairway on not fewer than one side. Stairways with a required egress width of more than 66 inches (1676 mm) shall have handrails on both sides.

805.9.2 Design

ILLUSTRATION
New handrails required in accordance with Section 805.9.1 shall be designed and installed in accordance with the provisions of the Chicago Building Code.
Where alterations affect the configuration of an area utilized as a refuge area, the capacity of the refuge area shall not be reduced below that required in Sections 805.10.1 and 805.10.2.
The required capacity of refuge areas shall be in accordance with Sections 805.10.1.1 through 805.10.1.3.
In Group I-2 occupancies, the required capacity of the refuge areas for smoke compartments in accordance with Section 407.5.1 of the Chicago Building Code shall be maintained.
In Group I-3 occupancies, the required capacity of the refuge areas for smoke compartments in accordance with Section 408.6.2 of the Chicago Building Code shall be maintained.
In ambulatory care facilities required to be separated by Section 422.2 of the Chicago Building Code, the required capacity of the refuge areas for smoke compartments in accordance with Section 422.3.2 of the Chicago Building Code shall be maintained.
The required capacity of the refuge area for horizontal exits in accordance with Section 1026.4 of the Chicago Building Code shall be maintained.

805.11 Guards

ILLUSTRATION
The requirements of Sections 805.11.1 and 805.11.2 shall apply to guards from the highest work area story to, and including, the level of exit discharge but shall be confined to the egress path of any work area.
Every open portion of a stairway, landing, or balcony that is more than 30 inches (762 mm) above the floor or grade below and is not provided with guards, or those portions in which existing guards are judged to be in danger of collapsing, shall be provided with guards.
New guards required in accordance with Section 805.11.1 shall be designed and installed in accordance with the Chicago Building Code.
Existing stairways and extensions of existing stairways shall not be required to comply with the requirements of Section 1011 of the Chicago Building Code where the existing space and construction does not allow a reduction in pitch or slope. Existing stairways shall be allowed to be rebuilt without complying with the requirements of Section 1011 of the Chicago Building Code where the existing space and construction does not allow a reduction in pitch or slope.

14R-8-806 The provisions of Section 806 of IEBC are adopted by reference with the following modifications:

Added Coun. J. 4-10-19, p. 100029.

Structural elements and systems within buildings undergoing Level 2 alterations shall comply with this section.

Any existing gravity load-carrying structural element for which an alteration causes an increase in design dead, live or snow load, including snow drift effects, of more than 5 percent shall be replaced or altered as needed to carry the gravity loads required by the Chicago Building Code for new structures. Any existing gravity load-carrying structural element whose gravity load-carrying capacity is decreased as part of the alteration shall be shown to have the capacity to resist the applicable design dead, live and snow loads, including snow drift effects, required by the Chicago Building Code for new structures.

Exceptions:

  1. Buildings of Group R-5 occupancy where the altered building complies with the conventional light-frame construction methods of the Chicago Building Code.
  2. Buildings in which the increased dead load is attributable to the addition of a second layer of roof covering weighing 3 pounds per square foot (0.1437 kN/m2) or less over an existing single layer of roof covering.

Except as allowed by Section 806.4, where the alteration increases design lateral loads, or where the alteration results in prohibited structural irregularity as defined in ASCE 7, or where the alteration decreases the capacity of any existing lateral load-carrying structural element, the structure of the altered building or structure shall meet the requirements of Sections 1609 and 1613 of the Chicago Building Code. Reduced seismic forces shall be allowed.

Exception: Any existing lateral load-carrying structural element whose demand-capacity ratio with the alteration considered is not more than 10 percent greater than its demand-capacity ratio with the alteration ignored shall be allowed to remain unaltered. For purposes of calculating demand-capacity ratios, the demand shall consider applicable load combinations with design lateral loads or forces in accordance with Sections 1609 and 1613 of the Chicago Building Code. Reduced seismic forces shall be allowed. For purposes of this exception, comparisons of demand-capacity ratios and calculation of design lateral loads, forces and capacities shall account for the cumulative effects of additions and alterations since original construction.

Structural alterations that are intended exclusively to improve the lateral force-resisting system and are not required by other sections of this code shall not be required to meet the requirements of Section 1609 or Section 1613 of the Chicago Building Code, provided that the following conditions are met:

  1. The capacity of existing structural systems to resist forces is not reduced.
  2. New structural elements are detailed and connected to existing or new structural elements as required by the Chicago Building Code for new construction.
  3. New or relocated nonstructural elements are detailed and connected to existing or new structural elements as required by the Chicago Building Code for new construction.
  4. The alterations do not create a structural irregularity as defined in ASCE 7 or make an existing structural irregularity more severe.

14R-8-807 The provisions of Section 807 of IEBC are adopted by reference with the following modifications:

Added Coun. J. 4-10-19, p. 100029.

Newly installed electrical equipment and wiring relating to work done in any work area shall comply with all applicable requirements of the Chicago Electrical Code except as provided for in Section 807.3.
Existing wiring in all work areas in Group A-1, A-5, H and I occupancies shall be upgraded to meet the materials and methods requirements of Chapter 7.
In Group R-2, R-3, R-4 and R-5 occupancies, work areas located within a dwelling unit shall comply with Article 570 of the Chicago Electrical Code, regardless of the height of the building.
Enclosed areas, other than closets, kitchens, basements, garages, hallways, laundry areas, utility areas, storage areas and bathrooms shall have not fewer than two duplex receptacle outlets or one duplex receptacle outlet and one ceiling or wall-type lighting outlet.
Kitchen areas shall have not fewer than two duplex receptacle outlets.
Laundry areas shall have not fewer than one duplex receptacle outlet located near the laundry equipment and installed on an independent circuit.
Newly installed receptacle outlets shall be provided with ground fault circuit interruption as required by Chicago Electrical Code.
Not fewer than one lighting outlet shall be provided in every bathroom, hallway, stairway, attached garage, and detached garage with electric power, and to illuminate outdoor entrances and exits.
Not fewer than one lighting outlet shall be provided in utility rooms and basements where such spaces are used for storage or contain equipment requiring service.
Clearance for electrical service equipment shall be provided in accordance with the Chicago Electrical Code.

14R-8-808 The provisions of Section 808 of IEBC are adopted by reference without modification.

Added Coun. J. 4-10-19, p. 100029.

Reconfigured spaces intended for occupancy and spaces converted to habitable or occupiable space in any work area shall be provided with natural or mechanical ventilation in accordance with the Chicago Mechanical Code.

Exception: Existing mechanical ventilation systems shall comply with the requirements of Section 808.2.

In mechanically ventilated spaces, existing mechanical ventilation systems that are altered, reconfigured, or extended shall provide not less than 5 cubic feet per minute (cfm) (0.0024 m3/s) per person of outdoor air and not less than 15 cfm (0.0071 m3/s) of ventilation air per person; or not less than the amount of ventilation air determined by the Indoor Air Quality Procedure of ASHRAE 62.1.
Newly introduced devices, equipment, or operations that produce airborne particulate matter, odors, fumes, vapor, combustion products, gaseous contaminants, pathogenic and allergenic organisms, and microbial contaminants in such quantities as to affect adversely or impair health or cause discomfort to occupants shall be provided with local exhaust.

14R-8-809 The provisions of Section 809 of IEBC are adopted by reference with the following modification:

Added Coun. J. 4-10-19, p. 100029.

Where the occupant load of a story is increased by more than 20 percent, plumbing fixtures for the story shall be provided in quantities specified in the Chicago Plumbing Code based on the increased occupant load.

14R-8-810 The provisions of Section 810 of IEBC are adopted by reference with the following modification:

Added Coun. J. 4-10-19, p. 100029.

Level 2 alterations to existing buildings or structures are permitted without requiring the entire building or structure to comply with the energy requirements of the Chicago Energy Conservation Code. The alterations shall conform to the energy requirements of the Chicago Energy Conservation Code.