ADOPTS WITH AMENDMENTS:

International Building Code 2018 (IBC 2018)

Heads up: There are no amended sections in this chapter.

Section 601 General

ILLUSTRATION

14B-6-601 The provisions of Section 601 of IBC are adopted by reference with the following modification:

Added Coun. J. 4-10-19, p. 100029.

Amended Coun. J. 2-19-20, p. 14474.

TABLE 601

FIRE-RESISTANCE RATING REQUIREMENTS FOR BUILDING ELEMENTS (HOURS)

BUILDING ELEMENT TYPE I TYPE II TYPE III TYPE IV TYPE V
A B A B A B HT A B
Primary structural framef 3a, b 2a, b 1b 0 1b 0 HT 1b 0
Bearing walls
Exteriore, f
Interior
3
3a
2
2a
1
1
0
0
2
1
2
0
2
1/HT
1
1
0
0
Nonbearing walls and partitions — Exterior See Table 602
Nonbearing walls and partitions — Interiord 0 0 0 0 0 0 Note i 0 0
Floor construction and associated secondary members 2 2 1 0 1g 0 HT 1g 0
Roof construction and associated secondary members 1.5b 1b 1b 0c 1b, c, h 0 HT 1b, c, h 0

For SI: 1 foot = 304.8 mm.

  1. Roof supports: Fire-resistance ratings of primary structural frame and bearing walls are permitted to be reduced by 1 hour where supporting a roof only.
  2. Except in Group F-1, H, M and S-1 occupancies, fire protection of structural members in roof construction shall not be required, including protection of primary structural frame members, roof framing and decking where every part of the roof construction is 20 feet or more above any floor immediately below.
  3. In all occupancies, heavy timber complying with Section 2304.11 shall be allowed where a 1-hour or less fire-resistance rating is required.
  4. Not less than the fire-resistance rating required by other sections of this code.
  5. Not less than the fire-resistance rating based on fire separation distance (see Table 602).
  6. Not less than the fire-resistance rating as referenced in Section 704.10.
  7. In single-family dwellings, the floor construction over basements and unexcavated spaces below the first story above grade plane is not required to have a fire-resistance rating.
  8. In buildings of exclusively Group R-2, R-3, R-4 or R-5 occupancy with no more than four stories above grade plane, the required fire-resistance rating of roof construction and associated secondary members shall be reduced to 30 minutes.
  9. See Section 2304.11.2.
The provisions of this chapter shall control the classification of buildings as to type of construction.

14B-6-602 The provisions of Section 602 of IBC are adopted by reference with the following modifications:

Added Coun. J. 4-10-19, p. 100029.

Amended Coun. J. 2-19-20, p. 14474.

Amended Coun. J. 10-7-20, p. 21791.

TABLE 602

FIRE-RESISTANCE RATING REQUIREMENTS FOR EXTERIOR WALLS BASED ON FIRE SEPARATION DISTANCEa, d, g

FIRE SEPARATION DISTANCE =
X (feet)
TYPE OF
CONSTRUCTION
OCCUPANCY OCCUPANCY OCCUPANCY
GROUP A, B, E, M, I, R, Uh
X < 3b VA, VB
Others
NP
3
NP
2
2h, j
2
3 ≤ X < 5 All 3 2 1
5 ≤ X < 10 IA
Others
3
2
2
1
1
1
10 ≤ X < 30 IA, IB
IIB, VB
Others
2
1
1
1k
0
1k
1c, k
0
1c, k
X ≥ 30 All 0 0 0

For SI: 1 foot = 304.8 mm.

  1. Load-bearing exterior walls shall also comply with the fire-resistance rating requirements of Table 601.
  2. See Section 706.1.1 for party walls.
  3. Open parking garages complying with Section 406 shall not be required to have a fire-resistance rating.
  4. The fire-resistance rating of an exterior wall is determined based upon the fire separation distance of the exterior wall and the story in which the wall is located.
  5. For special requirements for Group H occupancies, see the Chicago Fire Prevention Code.
  6. For special requirements for Group S aircraft hangars, see Section 412.3.1.
  7. Where Table 705.8 permits nonbearing exterior walls with unlimited area of unprotected openings, the required fire-resistance rating for the exterior walls is 0 hours.
  8. A single-story detached private garage, carport or storage building not exceeding 600 square feet (56 m2) in building area, not exceeding 12 feet (3658 mm) in building height and with a roof slope of 2:12 or greater shall be permitted in Type VA or Type VB construction when the fire separation distance is 2 feet (610 mm) or greater and the exterior wall shall not be required to have a fire-resistance rating.
  9. [Reserved]
  10. Any exterior wall with a fire separation distance of less than 3 feet shall have a fire-resistance rating of not less than 2 hours and shall be built of noncombustible materials, materials allowed by Section 603 or fire-retardant treated wood framing complying with Section 2303.2 with a noncombustible exterior wall covering.
  11. The required fire-resistance rating of exterior walls with a fire separation distance of 10 feet or greater shall only be required to be rated for exposure to fire from the inside in accordance with Section 705.5.
Buildings and structures erected or to be erected, altered or extended in height or area shall be classified in one of the five construction types defined in Sections 602.2 through 602.5. The building elements shall have a fire-resistance rating not less than that specified in Table 601 and exterior walls shall have a fire-resistance rating not less than that specified in Table 602. Where required to have a fire-resistance rating by Table 601, building elements shall comply with the applicable provisions of Section 703.2. The protection of openings, ducts and air transfer openings in building elements shall not be required unless required by other provisions of this code.
A building or portion thereof shall not be required to conform to the details of a type of construction higher than that type which meets the minimum requirements based on occupancy even though certain features of such a building actually conform to a higher type of construction.

602.2 Types I and II

ILLUSTRATION
Types I and II construction are those types of construction in which the building elements listed in Table 601 are of noncombustible materials, except as permitted in Section 603 and elsewhere in this code.
Type III construction is that type of construction in which the exterior walls are of noncombustible materials and the interior building elements are of any material permitted by this code.
Type IV construction is that type of construction in which the exterior walls are of noncombustible materials and the interior building elements are of solid wood, laminated wood, heavy timber (HT) or structural composite lumber (SCL) without concealed spaces. The minimum dimensions for permitted materials including solid timber, structural glued-laminated timber, structural composite lumber (SCL), and cross-laminated timber and details of Type IV construction shall comply with the provisions of this section and Section 2304.11. Interior walls and partitions and noncombustible floor and roof assemblies with not less than a 1- hour fire-resistance rating or heavy timber complying with Section 2304.11.2.2 shall be permitted.
Where a fire separation distance of 20 feet (6096 mm) or more is provided, wood columns and arches conforming to heavy timber sizes complying with Section 2304.11 shall be permitted to be used externally.

602.5 Type V

ILLUSTRATION
Type V construction is that type of construction in which the structural elements, exterior walls and interior walls are of any materials permitted by this code.

14B-6-603 The provisions of Section 603 of IBC are adopted by reference with the following modifications:

Added Coun. J. 4-10-19, p. 100029.

Amended Coun. J. 2-19-20, p. 14474.

Combustible materials shall be permitted in buildings of Type I or II construction in the following applications and in accordance with Sections 603.1.1 through 603.1.3:

  1. Fire-retardant-treated wood shall be permitted in:

    1. 1.1. Nonbearing partitions where the required fire-resistance rating is 1 hour or less.
    2. 1.2. [Reserved]
    3. 1.3. Roof construction, including girders, trusses, framing and decking of one-story buildings that do not exceed the height and area limitations for Type IIB construction.
  2. Thermal and acoustical insulation, other than foam plastics, having a flame spread index of not more than 25.

    Exceptions:

    1. Insulation placed between two layers of noncombustible materials without an intervening airspace shall be allowed to have a flame spread index of not more than 100.
    2. Insulation installed between a finished floor and solid decking without intervening airspace shall be allowed to have a flame spread index of not more than 200.
  3. Foam plastics in accordance with Chapter 26.
  4. Roof coverings that have an A, B or C classification.
  5. Interior floor finish and floor covering materials installed in accordance with Section 804.
  6. Millwork such as doors, door frames, window sashes and frames.

    Exception: Combustible millwork shall not be permitted in exterior wall openings that are within 5 feet (1524 mm) horizontally and 3 feet (914 mm) vertically of an opening in an adjacent story.

  7. Interior wall and ceiling finishes installed in accordance with Section 803.
  8. Trim installed in accordance with Section 806.
  9. Where not installed greater than 15 feet (4572 mm) above grade, show windows, nailing or furring strips and wooden bulkheads below show windows, including their frames, aprons and show cases.
  10. Finish flooring installed in accordance with Section 805.
  11. Partitions dividing portions of stores, offices or similar places occupied by one tenant only and that do not establish a corridor serving an occupant load of 30 or more shall be permitted to be constructed of fire-retardant-treated wood, 1-hour fire-resistance-rated construction or of wood panels or similar light construction up to 6 feet (1829 mm) in height.
  12. Stages and platforms constructed in accordance with Sections 410.2 and 410.3, respectively.
  13. Combustible exterior wall coverings, exterior balconies and similar projections and bay or oriel windows in accordance with Chapter 14 and Section 705.2.
  14. Blocking such as for handrails, millwork, cabinets and window and door frames in exterior walls or in interior walls and partitions where the required fire-resistance rating is 1 hour or less.
  15. Light-transmitting plastics as permitted by Chapter 26.
  16. Mastics and caulking materials applied to provide flexible seals between components of exterior wall construction.
  17. Exterior plastic veneer installed in accordance with Section 2605.2.
  18. Nailing or furring strips as permitted by Section 803.15.
  19. Heavy timber as permitted by Note c to Table 601 and Sections 602.4.3 and 705.2.
  20. Aggregates, component materials and admixtures as permitted by Section 703.2.2.
  21. Sprayed fire-resistant materials and intumescent and mastic fire-resistant coatings, determined on the basis of fire resistance tests in accordance with Section 703.2 and installed in accordance with Sections 1705.14 and 1705.15, respectively.
  22. Materials used to protect penetrations in fire-resistance-rated assemblies in accordance with Section 714.
  23. Materials used to protect joints in fire-resistance-rated assemblies in accordance with Section 715.
  24. Materials allowed in the concealed spaces of buildings of Types I and II construction in accordance with Section 718.5.
  25. Materials exposed within plenums complying with the Chicago Mechanical Code and Chicago Electrical Code.
  26. Wall construction of freezers and coolers of less than 1,000 square feet (92.9 m2), in size, lined on both sides with noncombustible materials and the building is protected throughout with an automatic sprinkler system in accordance with Section 903.3.1.1.
  27. Exterior fiber-reinforced polymer as permitted by Section 2613.5.
The use of nonmetallic ducts shall be permitted where installed in accordance with the limitations of the Chicago Mechanical Code.
The use of combustible piping materials shall be permitted where installed in accordance with the limitations of Section 903, the Chicago Mechanical Code and the Chicago Plumbing Code.
The use of electrical wiring methods with combustible insulation, tubing, raceways and related components shall be permitted where installed in accordance with the limitations of the Chicago Electrical Code.

14B-6-604 The following language is adopted as a new Section 604:

Added Coun. J. 4-10-19, p. 100029.

Combustible materials shall be permitted in the exterior walls of buildings of Type III or IV construction where combustible materials in the same application are permitted in the exterior walls of buildings of Type I or II construction by Section 603.1.

14B-6-605 The following language is adopted as a new Section 605:

Added Coun. J. 4-10-19, p. 100029.

In all buildings, basement construction shall comply with the requirements of Sections 605.2 through 605.4.
In buildings of Type III or V construction with three or more stories above grade plane, all basement columns and basement bearing walls shall be of noncombustible material or of heavy timber construction.
In buildings with more than one basement story, the floor construction separating the highest basement from the first story above grade plane and all construction below that level shall be of Type IA construction.
Except in buildings of Group R-5 occupancy, floor construction over basements shall have a fire-resistance rating of not less than 1 hour.