The definitions contained in this chapter shall apply to the terms used in this Code. Where terms are not defined in this chapter or within another chapter, they shall be defined using their ordinarily accepted meanings within the context in which they are used. Merriam-Webster's Collegiate Dictionary, 11th edition, shall be the source for the ordinarily accepted meaning.
An organization, office, or individual responsible for enforcing the requirements of a code or standard, or for approving equipment, materials, an installation, or a procedure.
A standard that is an extensive compilation of provisions covering broad subject matter or that is suitable for adoption into law independently of other codes and standards.
Equipment or materials to which has been attached a label, symbol, or other identifying mark of an organization that is acceptable to the authority having jurisdiction and concerned with product evaluation, that maintains periodic inspection of production of labeled equipment or materials, and by whose labeling the manufacturer indicates compliance with appropriate standards or performance in a specified manner.
Equipment, materials, or services included in a list published by an organization that is acceptable to the authority having jurisdiction and concerned with evaluation of products or services, that maintains periodic inspection of production of listed equipment or materials or periodic evaluation of services, and whose listing states that either the equipment, material, or service meets appropriate designated standards or has been tested and found suitable for a specified purpose.
Indicates a mandatory requirement.
Indicates a recommendation or that which is advised but not required.
Capable of being reached for operation, renewal, and inspection. [70:100] (SIG-FUN)
Capable of being removed or exposed without damaging the building structure or finish or not permanently closed in by the structure or finish of the building. [70:100] (SIG-FUN)
Capable of being reached quickly for operation, renewal, or inspections without requiring those to whom ready access is requisite to take actions such as to use tools (other than keys), to climb over or under, to remove obstacles, or to resort to portable ladders, and so forth. [70:100] (SIG-FUN)
Spaces or concealed areas of construction that can be entered via openable panels, doors, hatches, or other readily movable construction elements. (SIG-IDS)
An action performed by a person to confirm that a message or signal has been received. (SIG-SSS)
An emergency communications system notification zone, or subdivision thereof, that might be an enclosed or otherwise physically defined space, or that might be distinguished from other spaces because of different acoustical, environmental, or use characteristics, such as reverberation time and ambient sound pressure level. (SIG-NAS)
A multiplexing system in which signaling devices such as transponders are employed to transmit status signals of each initiating device or initiating device circuit within a prescribed time interval so that the lack of receipt of such a signal can be interpreted as a trouble signal. (SIG-SSS)
A fire alarm system component, with an input, output, or combination function, that is discretely identified by a unique address. (SIG-FUN)
Any condition occurring in a communications or transmission channel that interferes with the proper transmission or interpretation, or both, of status change signals at the supervising station. (See also 3.3.272.10, Trouble Signal.) (SIG-SSS)
An indication of the existence of a condition that requires immediate response. (SIG-FUN)
A single- or multiple-station alarm responsive to carbon monoxide (CO). (SIG-HOU)
An alarm box that can only be operated from one or more remote initiating devices or an auxiliary alarm system used to send an alarm to the communications center. (SIG-PRS)
A manually operated box capable of transmitting a fire alarm signal and a separate guard patrol tour supervisory signal. (SIG-IDS)
A manually operated device used to initiate a fire alarm signal. (SIG-IDS)
A publicly accessible alarm box that can also be operated by one or more remote initiating devices or an auxiliary alarm system used to send an alarm to the communications center. (SIG-PRS)
An enclosure, accessible to the public, housing a manually operated transmitter used to send an alarm to the communications center. (SIG-PRS)
A device or system for the purpose of automatically retransmitting alarm information received by the alarm processing equipment. (SIG-PRS)
The service required following the receipt of an alarm signal. (SIG-SSS)
A feature of automatic fire detection and alarm systems to reduce unwanted alarms wherein smoke detectors report alarm conditions for a minimum period of time, or confirm alarm conditions within a given time period after being reset, in order to be accepted as a valid alarm initiation signal. (SIG-PRO)
An attention-getting signal to alert occupants of the pending transmission of a voice message. (SIG-PRO)
Non-emergency activations of the fire alarm or mass notification audible, visual, and textual output circuits. (SIG-ECS)
A unit containing one or more indicator lamps, alphanumeric displays, or other equivalent means in which each indication provides status information about a circuit, condition, or location. (SIG-FUN)
A building or portion thereof containing three or more dwelling units with independent cooking and bathroom facilities. (SIG-HOU) [5000, 2021]
The property owner, or designated representative appointed or selected by the property owner, who performs certain duties. (SIG-FUN)
The root mean square, A-weighted, sound pressure level measured over the period of time that any person is present, or a 24-hour period, whichever time period is the lesser. (SIG-NAS)
A part of a network that acts as a common infrastructure to which the branch parts are connected. (SIG-PRO)
Two or more cells connected together electrically. (SIG-TMS)
The electrical energy available from a fully charged battery expressed in ampere-hours. (SIG-TMS)
A device used to restore and maintain the charge of a secondary battery in which electrical energy is converted to chemical energy. (SIG-TMS)
A constant-voltage charge applied to a battery to maintain it in a fully charged condition. (SIG-TMS)
A condition synonymous with 100 percent state of charge. (See also 3.3.33.2.3, State of Charge.) (SIG-TMS)
The stored or remaining capacity of a battery at a given time expressed as a percentage of its rated capacity. (SIG-TMS)
A continuous, low-rate, constant-current charge given to a cell or battery to keep the unit fully charged. (See also 3.3.33.2.1, Float Charge.) (SIG-TMS)
A controlled discharge of a battery at a specified rate for a given period of time until a final voltage is achieved to determine battery capacity. (SIG-TMS)
An electrochemical cell capable of being discharged and then recharged. (SIG-TMS)
A computer-based electronic device that is intended to display building information and execute system control functions, including fire system information display and control. (SIG-PRO)
A system or portion of a combination system that consists of a control unit, components, and circuits arranged to monitor and annunciate the status of carbon monoxide alarm initiating devices and to initiate the appropriate response to those signals. (SIG-PRO)
A carbon monoxide detection system in which components are used, in whole or in part, in common with a non—carbon monoxide signaling system, and in which components are not used as part of a fire alarm system. (SIG-PRO)
A system of devices that uses a control unit to produce an alarm signal in the household for the purpose of notifying the occupants of the presence of concentrations of carbon monoxide that could pose a life safety risk. (SIG-HOU)
High-frequency energy that can be modulated by voice or signaling impulses. (SIG-SSS)
A means of conveying a number of channels over a single path by modulating each channel on a different carrier frequency and demodulating at the receiving point to restore the signals to their original form. (SIG-SSS)
The upper surface of a space, regardless of height. (SIG-IDS)
Ceilings that have a slope of less than or equal to 1 in 8. (SIG-IDS)
A ceiling that has a slope of more than 1 in 8. (SIG-IDS)
A ceiling in which the ceiling slopes in two directions from the highest point. (SIG-IDS)
A ceiling in which the high point is at one side with the slope extending toward the opposite side. (SIG-IDS)
The height from the continuous floor of a room to the continuous ceiling of a room or space. (SIG-IDS)
Ceilings that have solid structural or solid nonstructural members projecting down from the ceiling surface more than 4 in. (100 mm) and spaced more than 36 in. (910 mm), center to center. (SIG-IDS)
A support for beams or joists that runs at right angles to the beams or joists. If the top of the girder is within 4 in. (100 mm) of the ceiling, the girder is a factor in determining the number of detectors and is to be considered a beam. If the top of the girder is more than 4 in. (100 mm) from the ceiling, the girder is not a factor in detector location. (SIG-IDS)
A ceiling surface uninterrupted by continuous projections, such as solid joists, beams, or ducts, extending more than 4 in. (100 mm) below the ceiling surface. (SIG-IDS)
Ceilings that have solid structural or solid nonstructural members projecting down from the ceiling surface for a distance of more than 4 in. (100 mm) and spaced at intervals of 36 in. (910 mm) or less, center to center. (SIG-IDS)
The basic electrochemical unit, characterized by an anode and a cathode, used to receive, store, and deliver electrical energy. [70:480] (SIG-TMS)
A nonrechargeable electrochemical cell requiring periodic replacement, such as a 9-volt alkaline cell. (SIG-FUN)
A cell in which liquid electrolyte is immobilized, also known as an absorbed glass mat (AGM) cell or a gelled electrolyte cell (gel cell). (SIG-TMS)
A cell in which the liquid electrolyte is immobilized in fiberglass or polymeric fiber separators. (SIG-TMS)
A cell in which the electrolyte is immobilized by addition of a gelling agent. (SIG-TMS)
Multiple cells in a single container, such as a 12-volt unit composed of six 2-volt cells. (SIG-TMS)
A sealed lead-acid cell with a valve that opens to the atmosphere when the internal pressure in the cell exceeds atmospheric pressure by a preselected amount. (SIG-TMS)
See 3.2.5, Listed, for certified equipment.
A path for voice or signal transmission that uses modulation of light or alternating current within a frequency band. (SIG-SSS)
A circuit or path connecting a subsidiary station(s) to a supervising station(s) over which signals are carried. (SIG-SSS)
A band of frequencies of a width sufficient to allow its use for radio communications. (SIG-SSS)
Either a means of providing power or a connection path between locations [see 3.3.205, Path (Pathways)]. (SIG-PRO)
An audible or visual signal that conveys several discrete bits or units of information. (SIG-NAS)
A building or portion of a building that is specifically configured for the primary purpose of providing emergency communications services or public safety answering point (PSAP) services to one or more public safety agencies under the authority or authorities having jurisdiction. [1221, 2019] (SIG-PRS)
Any signaling path of an emergency communications system that carries voice, audio, data, or other signals. (SIG-ECS)
The area in the communications path that is supported by providers of communications services not governed under the scope of NFPA 72 in which signals travel between a protected property and a monitoring station. Depending on the type of transmission that is used, signals can travel on a single defined route or through various routes depending on what is available when the signal is initiated. (SIG-SSS)
A communications channel on which alarm boxes only transmit signals and are incapable of receiving responses. (SIG-PRS)
A situation, environmental state, or equipment state of a fire alarm or signaling system. (SIG-FUN)
A situation, environmental state, or equipment state that warrants some type of signal, notification, communication, response, action, or service. (SIG-FUN)
An abnormal condition that poses an immediate threat to life, property, or mission. (SIG-FUN)
An abnormal condition that poses a potential threat to life, property, or mission, and time is available for investigation. (SIG-FUN)
An abnormal condition in connection with the supervision of other systems, processes, or equipment. (SIG-FUN)
An abnormal condition in a system due to a fault. (SIG-FUN)
Circuits, systems, and components are functioning as designed and no abnormal condition exists. (SIG-FUN)
Attended 24 hours a day and 365 days a year. (SIG-PRO)
Equipment listed as either a control unit or control unit accessory. (SIG-FUN)
A system component that monitors inputs and controls outputs through various types of circuits. (SIG-PRO)
A system capable of sending mass notification messages to individual buildings, zones of buildings, individual outdoor loudspeaker arrays, or zones of outdoor loudspeaker arrays; or a building, multiple buildings, outside areas, or a combination of these. (SIG-ECS)
A component that transmits/receives and processes wireless signals. (SIG-PRO)
The protection of systems from theft or damage of data, or damage to hardware or software, as well as from unauthorized command or control or access to any information of any services the systems provide. (SIG-FUN)
A building or portion of a building in which more than 3 but not more than 12 clients receive care, maintenance, and supervision, by other than their relative(s) or legal guardian(s), for less than 24 hours per day. [101, 2021] (SIG-HOU)
A condition that interferes with the service or reliability for which the part, system, or equipment was intended. (SIG-TMS)
An individual who is registered or licensed to practice their respective design profession as defined by the statutory requirements of the professional registration laws of the jurisdiction in which the project is to be constructed, or other professional with qualifications or credentials acceptable to the jurisdiction in which the project is to be constructed. (SIG-ECS)
A device suitable for connection to a circuit that has a sensor that responds to a physical stimulus such as gas, heat, or smoke. (SIG-IDS)
A detector that draws air and particulate from the protected area into a sampling network that runs to the detector. An aspiration fan in the detector housing draws air from the protected area back to the detector through air sampling ports, piping, or tubing. At the detector, the air is analyzed for fire products. (SIG-IDS)
A device designed to detect the presence of a fire signature and to initiate action. (SIG-IDS)
A device that automatically detects the operation of a fire extinguishing or suppression system by means appropriate to the system employed. (SIG-IDS)
A device that responds to carbon monoxide. (SIG-IDS)
A device that either responds to more than one of the fire phenomena or employs more than one operating principle to sense one of these phenomena. This device has listings for each sensing method employed. (SIG-IDS)
A line-type or spot-type sensing element in which resistance varies as a function of temperature. (SIG-IDS)
A device that detects gases produced by a fire. (SIG-IDS)
A device that responds when its operating element becomes heated to a predetermined level. (SIG-IDS)
A radiant energy—sensing fire detector that detects the radiant energy emitted by a flame. (Refer to A.17.8.2.) (SIG-IDS)
A device that detects the presence of a specified gas concentration. (SIG-IDS)
A fire detector that detects either abnormally high temperature or rate-of-temperature rise, or both. (SIG-IDS)
A device in which detection is continuous along a path. (SIG-IDS)
A device that contains multiple sensors that separately respond to physical stimulus such as heat, smoke, or fire gases, or employs more than one sensor to sense the same stimulus. This sensor is capable of generating only one alarm signal from the sensors employed in the design either independently or in combination. The sensor output signal is mathematically evaluated to determine when an alarm signal is warranted. The evaluation can be performed either at the detector or at the control unit. This detector has a single listing that establishes the primary function of the detector. (SIG-IDS)
A device that contains multiple sensors that separately respond to physical stimulus such as heat, smoke, or fire gases, or employs more than one sensor to sense the same stimulus. A device capable of generating multiple alarm signals from any one of the sensors employed in the design, independently or in combination. The sensor output signals are mathematically evaluated to determine when an alarm signal is warranted. The evaluation can be performed either at the detector or at the control unit. This device has listings for each sensing method employed. (SIG-IDS)
Devices that detect a phenomenon other than heat, smoke, flame, or gases produced by a fire. (SIG-IDS)
A line-type detector comprising small-diameter tubing, usually copper, that is installed on the ceiling or high on the walls throughout the protected area. The tubing is terminated in a detector unit containing diaphragms and associated contacts set to actuate at a predetermined pressure. The system is sealed except for calibrated vents that compensate for normal changes in temperature. (SIG-IDS)
A type of photoelectric light obscuration smoke detector wherein the beam spans the protected area. (SIG-IDS)
A device that detects radiant energy, such as ultraviolet, visible, or infrared, that is emitted as a product of combustion reaction and obeys the laws of optics. (SIG-IDS)
A device that responds when the temperature of the air surrounding the device reaches a predetermined level, regardless of the rate-of-temperature rise. (SIG-IDS)
A device that responds when the temperature rises at a rate exceeding a predetermined value. (SIG-IDS)
A device that detects visible or invisible particles of combustion. (SIG-IDS)
A device in which the detecting element is concentrated at a particular location. (SIG-IDS)
A supervised component of a life safety system that communicates with other components of life safety systems and that collects environmental data or performs specific input or output functions necessary to the operation of the life safety system. (SIG-PRO)
A system component at the protected premises to which initiating devices or groups of devices are connected. The DACT seizes the connected telephone line, dials a preselected number to connect to a DACR, and transmits signals indicating a status change of the initiating device. (SIG-SSS)
A system component composed of two subcomponents: one that receives and decodes radio signals, the other that annunciates the decoded data. These two subcomponents can be coresident at the central station or separated by means of a data transmission channel. (SIG-SSS)
A system component that is connected to or an integral part of a digital alarm communicator transmitter (DACT) that is used to provide an alternate radio transmission channel. (SIG-SSS)
The visible representation of output data, other than printed copy. (SIG-NAS)
A building or a space in a building in which group sleeping accommodations are provided for more than 16 persons who are not members of the same family in one room, or a series of closely associated rooms, under joint occupancy and single management, with or without meals, but without individual cooking facilities. [101, 2021] (SIG-HOU)
A single opening that has no intervening wall space or door trim separating the two doors. (SIG-IDS)
The radio signal from the base station transmitter to the portable public safety subscriber receiver. (SIG-ECS)
One or more rooms arranged for complete, independent housekeeping purposes with space for eating, living, and sleeping; facilities for cooking; and provisions for sanitation. [5000, 2021] (SIG-HOU)
The minimum sound level at which the tone signal is audible in ambient noise. (SIG-NAS)
Mechanical devices, including fusible links, electrically monitored for contact closure to initiate a signal to the FACU. (SIG-TMS)
A particle of solid material that emits radiant energy due either to its temperature or the process of combustion on its surface. (See also 3.3.291, Spark.) (SIG-IDS)
A system for the protection of life by indicating the existence of an emergency situation and communicating information necessary to facilitate an appropriate response and action. (SIG-ECS)
One-way emergency communications systems are intended to broadcast information, in an emergency, to people in one or more specified indoor or outdoor areas. It is intended that emergency messages be conveyed either by audible, visual, or textual means, or any combination thereof. (SIG-ECS)
A distributed recipient mass notification system is a system meant to communicate directly to targeted individuals and groups that might not be in a contiguous area. (SIG-ECS)
Dedicated manual or automatic equipment for originating and distributing voice instructions, as well as alert and evacuation signals pertaining to a fire emergency, to the occupants of a building. (SIG-ECS)
A system used to provide information and instructions to people in a building(s) or other space using intelligible voice communications and including visual signals, text, graphics, tactile, or other communication methods. (SIG-ECS)
Wide-area mass notification systems are generally installed to provide real-time information to outdoor areas and could have the capability to communicate with other notification systems provided for a campus, military base, municipality, or similar single or multiple contiguous areas. (SIG-ECS)
Two-way emergency communications systems are divided into two categories, those systems that are anticipated to be used by building occupants (area of refuge two-way emergency communications systems, elevator landing two-way emergency communications systems, occupant evacuation elevator lobby two-way emergency communications systems, and stairway communications systems) and those systems that are to be used by fire fighters, police, and other emergency services personnel. Two-way emergency communications systems are used to both exchange information and to communicate information such as, but not limited to, instructions, acknowledgement of receipt of messages, condition of local environment, and condition of persons, and to give assurance that help is on the way. (SIG-ECS)
Various emergency communications systems such as fire alarm, mass notification, fire fighter communications, area of refuge communications, elevator communications, or others that can be served through a single control system or through an interconnection of several control systems. (SIG-ECS)
The room(s) or area(s) staffed during any emergency event by assigned emergency management staff. The room or area contains system communications and control equipment serving one or more buildings where responsible authorities receive information from premises sources or systems or from (higher level) regional or national sources or systems and then disseminate appropriate information to individuals, a building, multiple buildings, outside campus areas, or a combination of these in accordance with the emergency response plan established for the premises. The room or area contains the controls and indicators from which the emergency communications systems located in the room or area can be manually controlled as required by the emergency response plan and the emergency management coordinator. (SIG-ECS)
A listed fire alarm or signaling system component that directly interfaces with the system that operates the emergency control function. (SIG-PRO)
Building, fire, and emergency control elements or systems that are initiated by the fire alarm or signaling system and either increase the level of life safety for occupants or control the spread of the harmful effects of fire or other dangerous products. (SIG-PRO)
Person(s) who have been trained in emergency response. (SIG-FUN)
Organizations providing law enforcement, emergency medical, fire, rescue, communications, and related support services. [1221, 2019] (SIG-SSS)
A structure or a portion of a structure that houses emergency response agency equipment or personnel for response to events. [1221, 2019] (SIG-PRS)
A documented set of actions to address the planning for, management of, and response to natural, technological, and man-made disasters and other emergencies. (SIG-ECS)
The end of a pathway where a single addressable device or a control unit is connected. (SIG-PRO)
The withdrawal of occupants from a building. (SIG-PRO)
The virtual cone that extends out from the detector within which the effective sensitivity of the detector is at least 50 percent of its on-axis, listed, or approved sensitivity. (SIG-IDS)
A component of the fire alarm system that receives signals from initiating devices or other fire alarm control units and processes these signals to determine part or all of the required fire alarm system output function(s). (SIG-PRO)
A protected premises fire alarm control unit that is intended to operate specifically identified emergency control function(s). (SIG-PRO)
A protected premises fire alarm control unit specifically listed for releasing service that is part of a fire suppression system and which provides control outputs to release a fire suppression agent based on either automatic or manual input. (SIG-PRO)
A device that produces a fire alarm/evacuation tone upon command. (SIG-PRO)
A system or portion of a combination system that consists of components and circuits arranged to monitor and annunciate the status of fire alarm or supervisory signalinitiating devices and to initiate the appropriate response to those signals. (SIG-FUN)
A fire alarm system in which components are used, in whole or in part, in common with a non-fire signaling system. (SIG-PRO)
A system of devices that uses a fire alarm control unit to produce an alarm signal in the household for the purpose of notifying the occupants of the presence of a fire so that they will evacuate the premises. (SIG-HOU)
A protected premises fire alarm system that includes any of the features identified in 23.3.3.1 and that serves the general fire alarm needs of a building or buildings and provides notification. (SIG-PRO)
A protected premises fire alarm system installed specifically to perform emergency control function(s) where a building fire alarm system is not required. (SIG-PRO)
A protected premises fire alarm system that is part of a fire suppression system and/or that provides control inputs to a fire suppression system related to the fire suppression system's sequence of operations and outputs for other signaling and notification. (SIG-PRO)
The principal attended or unattended room or area where the status of the detection, alarm communications, control systems, and other emergency systems is displayed and from which the system(s) can be manually controlled. (SIG-ECS)
A device connected to a control unit that monitors the fire extinguisher in accordance with the requirements of NFPA 10. (SIG-IDS)
A building staff member or a tenant trained to perform assigned duties in the event of a fire emergency. (SIG-PRO)
A body or stream of gaseous material involved in the combustion process and emitting radiant energy at specific wavelength bands determined by the combustion chemistry of the fuel. (SIG-IDS)
The distance along the optical axis of the detector at which the detector can detect a fire of specified size and fuel within a given time frame. (SIG-IDS)
Minimum and maximum time between events. (SIG-TMS)
Fifty-two times per year, once per calendar week. (SIG-TMS)
Twelve times per year, once per calendar month. (SIG-TMS)
Four times per year with a minimum of 2 months, maximum of 4 months. (SIG-TMS)
Twice per year with a minimum of 4 months, maximum of 8 months. (SIG-TMS)
Once per year with a minimum of 9 months, maximum 15 months. (SIG-TMS)
A device that is used in the transmission of serial data (digital or analog) from the fire alarm control unit to other building system control units, equipment, or networks and/or from other building system control units to the fire alarm control unit. (SIG-PRO)
A device that is manually or automatically initiated to indicate the route being followed and the timing of a guard's tour. (SIG-IDS)
An accommodation combining living, sleeping, sanitary, and storage facilities within a compartment. [101, 2021] (SIG-HOU)
An accommodation with two or more contiguous rooms comprising a compartment, with or without doors between such rooms, that provides living, sleeping, sanitary, and storage facilities. [101, 2021] (SIG-HOU)
A full or partial decrease in the ability to detect or comprehend sounds. (SIG-HOU)
A hearing threshold of greater than 90 dB. (SIG-HOU)
A single- or multiple-station alarm responsive to heat. (SIG-HOU)
A single-station heat alarm employing a mechanical power source. (SIG-HOU)
High power loudspeaker arrays provide capability for voice and tone communications to large outdoor areas. (SIG-ECS)
A ceiling fan that is approximately 6 ft (1.8 m) to 24 ft (7.3 m) in diameter with a rotational speed of approximately 30 to 70 revolutions per minute. [13, 2022] (SIG-PRO)
A building or groups of buildings under the same management in which there are sleeping accommodations for more than 16 persons and primarily used by transients for lodging with or without meals. [101, 2021] (SIG-HOU)
A group of associated telephone lines within which an incoming call is automatically routed to an idle (not busy) telephone line for completion. (SIG-SSS)
Recognizable as suitable for the specific purpose, function, use, environment, application, and so forth, where described in a particular Code requirement. [70: 100] (SIG-PRS)
Performed without unreasonable delay. (SIG-SSS)
An abnormal condition, during either a planned or emergency event, where a system, component, or function is inoperable. (SIG-FUN)
A form of correspondence formatted as a letter or document that can be verified upon request. (SIG-FUN)
A system component that originates transmission of a signal indicating a change-of-state condition. (SIG-IDS)
An initiating device that transmits a signal indicating varying degrees of condition as contrasted with a conventional initiating device, which can only indicate an on—off condition. (SIG-IDS)
A device that responds to abnormal conditions that could affect the proper operation of an automatic sprinkler system, other fire-extinguishing system(s) or fire-suppression system(s). (SIG-IDS)
A device in which the sensing element is designed to be destroyed in the process of operation. (SIG-IDS)
A device in which the sensing element is not ordinarily destroyed in the process of operation, whose restoration can be manual or automatic. (SIG-IDS)
An initiating device in which the change of state signals an off-normal condition that requires action in connection with guard tours or maintenance of related systems. (SIG-IDS)
A circuit to which automatic or manual initiating devices are connected where the signal received does not identify the individual device operated. (SIG-PRO)
The quality or condition of being intelligible. (SIG-NAS)
Capable of being understood; comprehensible; clear. (SIG-NAS)
A circuit component that interfaces initiating devices or control circuits, or both; notification appliances or circuits, or both; system control outputs; and other signaling line circuits to a signaling line circuit. (SIG-PRO)
The fire alarm control interface coordinates signals to and from the fire alarm system and other systems. (SIG-ECS)
The portion of a communications channel that connects not more than one protected premises to a primary or secondary trunk facility. The leg facility includes the portion of the signal transmission circuit from its point of connection with a trunk facility to the point where it is terminated within the protected premises at one or more transponders. (SIG-SSS)
A type of combination system that transmits fire and emergency communications system data to at least one other life safety system. (SIG-PRO)
Any normally occupiable space in a residential occupancy, other than sleeping rooms or rooms that are intended for combination sleeping/living, bathrooms, toilet compartments, kitchens, closets, halls, storage or utility spaces, and similar areas. [101, 2021] (SIG-HOU)
The maximum number of discrete elements of fire alarm systems permitted to be used in a particular configuration. (SIG-SSS)
Equipment used by authorized personnel and emergency responders to activate and operate an in-building mass notification system. (SIG-ECS)
A building or portion thereof that does not qualify as a one- or two-family dwelling, that provides sleeping accommodations for a total of 16 or fewer people on a transient or permanent basis, without personal care services, with or without meals, but without separate cooking facilities for individual occupants. [101, 2021] (SIG-HOU)
The reduction of available voltage at the load below the point at which equipment can function as designed. (SIG-FUN)
Any device that communicates with associated control/receiving equipment or other transceivers by low-power radio signals. (SIG-PRO)
Work, including, but not limited to, repair, replacement, and service, performed to ensure that equipment operates properly. (SIG-TMS)
A physical facilities-based network capable of transmitting real-time signals with formats unchanged that is managed, operated, and maintained by the service provider to ensure service quality and reliability from the subscriber location to the interconnection point with other MFVN peer networks or the supervising station. (SIG-SSS)
Published installation and operating documentation provided for each product or component. The documentation includes directions and necessary information for the intended installation, maintenance, and operation of the product or component. (SIG-TMS)
The mode of operation whereby all fire alarm occupant notification is superseded by emergency mass notification action. (SIG-ECS)
A system component providing an operator interface to receive and view calls from remote call stations and initiate two-way communications between the master control station operator and persons at the call station location. (SIG-ECS)
The closest distance that an occupant's ear can be to an audible appliance. (SIG-NAS)
A single-station alarm capable of being interconnected to one or more additional alarms so that the actuation of one causes the appropriate alarm signal to operate in all interconnected alarms. (SIG-HOU)
A signaling method characterized by simultaneous or sequential transmission, or both, and reception of multiple signals on a signaling line circuit, a transmission channel, or a communications channel, including means for positively identifying each signal. (SIG-SSS)
A net-centric alerting system incorporates web-based management and alert activation application through which all operators and administrators could gain access to the system's capabilities based on the users' permissions and the defined access policy. (SIG-ECS)
The method of communications used in a public emergency alarm reporting system that consists of two or more points that are connected by physical conductors. (SIG-PRS)
The method of communications used in a public emergency alarm reporting system that consists of two or more points that are not connected by physical conductors. (SIG-PRS)
The physical and logical design of a network, and the inherent ability of the design to carry data from one point to another. (SIG-ECS)
A system component or group of components that is installed at the option of the owner, and is not installed due to a building or fire code requirement. (SIG-FUN)
A fire alarm system component such as a bell, horn, loudspeaker, visual notification appliance, or text display that provides audible, tactile, or visual outputs, or any combination thereof. (SIG-NAS)
A notification appliance that alerts by the sense of hearing. (SIG-NAS)
An audible notification appliance that marks building exits and areas of refuge by the sense of hearing for the purpose of evacuation or relocation. (SIG-NAS)
A notification appliance that conveys a stream of audible information. (SIG-NAS)
A notification appliance that alerts by the sense of touch or vibration. (SIG-NAS)
A notification appliance that alerts by the sense of sight. (SIG-NAS)
A notification appliance that conveys a stream of visual information that displays an alphanumeric or pictorial message. (SIG-NAS)
A suggested correction, improvement, or enhancement to the fire alarm or signaling system that is not considered to be an impairment or deficiency. (SIG-TMS)
A room or enclosed space designed for human occupancy. (SIG-FUN)
An area of a facility occupied by people on a regular basis. (SIG-FUN)
The bandwidth of a filter that comprises a frequency range of a factor of 2. (SIG-NAS)
The bandwidth of a filter that comprises a frequency range of a factor of 21/3. (SIG-NAS)
To access a communications network in preparation for connecting a telephone. (SIG-SSS)
Audible or visual signaling only to those persons directly concerned with the implementation and direction of emergency action initiation and procedure in the area protected by the fire alarm system. (SIG-NAS)
Audible or visual signaling to occupants or inhabitants of the area protected by the fire alarm system. (SIG-NAS)
Any property or building or its contents under legal control by the occupant, by contract, or by holding of a title or deed. (SIG-SSS)
A system intended to page one or more persons by such means as voice over loudspeaker, coded audible signals or visual signals, or lamp annunciators. (SIG-PRO)
Any circuit, conductor, optical fiber, radio carrier, or other means connecting two or more locations. (SIG-PRO)
The ability of any conductor, optical fiber, radio carrier, or other means for transmitting system information to remain operational during fire conditions. (SIG-ECS)
An immediately readable, not easily alterable, print, slash, or punch record of all occurrences of status change. (SIG-SSS)
Individuals who conduct a visual examination of a system or portion thereof to verify that it appears to be in operating condition, in proper location, and is free of physical damage or conditions that impair operation. (SIG-TMS)
Individuals who perform those procedures, adjustments, replacement of components, system programming, and maintenance as described in the manufacturer's service instructions that can affect any aspect of the performance of the system. (SIG-TMS)
Individual responsible for the development of fire alarm or signaling system plans and specifications in accordance with this Code. (SIG-FUN)
Individual responsible for the proper installation of fire alarm or signaling systems in accordance with plans, specifications, and manufacturer's requirements. (SIG-FUN)
Individuals who perform procedures used to determine the status of a system as intended by conducting acceptance, reacceptance, or periodic physical checks on systems. (SIG-TMS)
One or more buildings under the same ownership or control on a single property. (SIG-SSS)
An automatic sequence that results in an alarm signal, even when manually delayed for investigation, unless the system is reset. (SIG-PRO)
A source of electrical operating power, including the circuits and terminations connecting it to the dependent system components. (SIG-FUN)
A nonrechargeable battery requiring periodic replacement. (SIG-FUN)
That part of a transmission channel connecting all leg facilities to a supervising or subsidiary station. (SIG-SSS)
The listed central station or listed alarm service local company that is contractually responsible for providing central station services to a subscriber as required by this Code. (SIG-SSS)
A single-owner or single-user protected premises on a continuous plot of ground, including any buildings thereon, that is not separated by a public thoroughfare, transportation right-of-way, property owned or used by others, or body of water not under the same ownership. (SIG-SSS)
An owner- or user-protected premises where two or more protected premises, controlled by the same owner or user, are separated by a public thoroughfare, body of water, transportation right-of-way, or property owned or used by others. (SIG-SSS)
The physical location protected by a fire alarm system. (SIG-PRO)
An electronic amplification system with a mixer, amplifier, and loudspeakers, used to reinforce a given sound and distributing the "sound" to the general public around a building. (SIG-ECS)
A system of alarm-initiating devices, transmitting and receiving equipment, and communications infrastructure — other than a public telephone network — used to communicate with the communications center to provide any combination of manual or auxiliary alarm service. (SIG-PRS)
A protected premises fire alarm system or other emergency system at the protected premises and the system used to connect the protected premises system to a public emergency alarm reporting system for transmitting an alarm to the communications center. (SIG-PRS)
An auxiliary system that employs a locally complete arrangement of parts, initiating devices, relays, power supply, and associated components to automatically activate a master box or auxiliary box over circuits that are electrically isolated from the public emergency alarm reporting system circuits. (SIG-PRS)
A system in which an alarm from an alarm box is received and is retransmitted to an emergency response facility either manually or automatically. (SIG-PRS)
A system in which an alarm from an alarm box is automatically transmitted to an emergency response facility and, if used, is transmitted to supplementary alerting devices. (SIG-PRS)
A fire, emergency medical services, or law enforcement agency. (SIG-ECS)
A system installed to assure the effective operation of radio communication systems used by fire, emergency medical services, or law enforcement agencies. (SIG-ECS)
A radio communication system used by fire, emergency medical services, or law enforcement agencies. (SIG-ECS)
A competent and capable person or company that has met the requirements and training for a given field acceptable to the authority having jurisdiction. (SIG-TMS)
A system component that receives radio signals and resides at a repeater station that is located at a remote receiving location. (SIG-SSS)
A system component that receives data and annunciates that data at the supervising station. (SIG-SSS)
A system in which signals are transmitted from a radio alarm transmitter (RAT) located at a protected premises through a radio channel to two or more radio alarm repeater station receivers (RARSR) and that are annunciated by a radio alarm supervising station receiver (RASSR) located at the supervising station. (SIG-SSS)
A system component at the protected premises to which initiating devices or groups of devices are connected that transmits signals indicating a status change of the initiating devices. (SIG-SSS)
See 3.3.64, Communications, Radio.
The number of electromagnetic wave frequency cycles transmitted by a radio in 1 second. [1221, 2019] (SIG-PRS)
Drawings (as-built) that document the location of all devices, appliances, wiring sequences, wiring methods, and connections of the components of the system as installed. (SIG-FUN)
A document that acknowledges the features of installation, operation (performance), service, and equipment with representation by the property owner, system installer, system supplier, service organization, and the authority having jurisdiction. (SIG-FUN)
The directed movement of occupants from one area to another area within the same building. (SIG-PRO)
Communications between a remote device and a component of a fire alarm or signaling system. (SIG-PRO)
A system component providing a call button used to alert a master control station operator of a person requiring assistance, capabilities providing hands-free two-way communications between the person and operator, and visual indication of both call activation and active two-way communications. (SIG-ECS)
The location of the equipment needed to relay signals between supervising stations, subsidiary stations, and protected premises. (SIG-SSS)
A control function that attempts to return a system or device to its normal, nonalarm state. (SIG-FUN)
An occupancy used for lodging and boarding of four or more residents, not related by blood or marriage to the owners or operators, for the purpose of providing personal care services. [101, 2021] (SIG-HOU)
An occupancy that provides sleeping accommodations for purposes other than health care or detention and correctional. [101, 2021] (SIG-HOU)
Actions performed upon the receipt of a signal. (SIG-FUN)
The response to the receipt of an alarm signal. (SIG-FUN)
The response to the receipt of a pre-alarm signal. (SIG-FUN)
The response to the receipt of a trouble signal. (SIG-FUN)
A numerical value that represents the thermal response sensitivity of the sensing element in a heat detector, sprinkler, or other heat-sensing fire detection device to the fire environment in terms of gas temperature and velocity versus time. (See B.3.3.3.7.) (SIG-IDS)
A process to characterize the likelihood, vulnerability, and magnitude of incidents associated with natural, technological, and manmade disasters and other emergencies that address scenarios of concern, their probability, and their potential consequences. (SIG-ECS)
A person other than the required number of operators on duty at central, supervising, or runner stations (or otherwise in contact with these stations) available for prompt dispatching, when necessary, to the protected premises. (SIG-SSS)
The service provided by a runner at the protected premises, including restoration, resetting, and silencing of all equipment transmitting fire alarm or supervisory or trouble signals to an off-premises location. (SIG-SSS)
That part of a transmission channel connecting two or more, but fewer than all, leg facilities to a primary trunk facility. (SIG-SSS)
The shapes of ceilings can be classified as sloping or smooth. (SIG-IDS)
Documents that provide information pertaining to the system necessary for installation of a fire alarm and/or signaling system. (SIG-FUN)
An indication of a condition communicated by electrical, visible, visual, audible, wireless, or other means. (SIG-FUN)
A signal that results from the manual or automatic detection of an alarm condition. (SIG-FUN)
A signal indicating a concentration of carbon monoxide at or above the alarm threshold that could pose a risk to the life safety of the occupants and that requires immediate action. (SIG-FUN)
A signal indicating a supervisory condition and the need for action in connection with the supervision of guards or system attendants. (SIG-PRO)
A distinctive alarm signal intended to be recognized by the occupants as requiring evacuation of the building. (SIG-PRO)
A signal that results from the manual or automatic detection of a fire alarm condition. (SIG-FUN)
A signal generated when a guard on patrol has actuated a guard's tour reporting station. (SIG-PRO)
A signal that results from the detection of a pre-alarm condition. (SIG-FUN)
A signal that results from the return to normal condition of an initiating device, system element, or system. (SIG-FUN)
A signal that results from the detection of a supervisory condition. (SIG-FUN)
A signal that results from the detection of a trouble condition. (SIG-FUN)
A DACT that obtains dial tone, dials the number(s) of the DACR, obtains verification that the DACR is ready to receive signals, transmits the signals, and receives acknowledgment that the DACR has accepted that signal before disconnecting (going on-hook). (SIG-SSS)
A circuit path between any combination of addressable appliances or devices, circuit interfaces, control units, or transmitters over which multiple system input signals or output signals or both are carried. (SIG-PRO)
A system consisting of one or more of the following: carbon monoxide detection equipment and system, supervising station alarm system, public emergency alarm reporting system, or emergency communications system. (SIG-PRO)
A detector comprising an assembly that incorporates a sensor, control components, and an alarm notification appliance in one unit operated from a power source either located in the unit or obtained at the point of installation. (SIG-HOU)
The area of a dwelling unit where the bedrooms or sleeping rooms are located. (SIG-HOU)
A single or multiple-station alarm responsive to smoke. (SIG-HOU)
The principle of using an air sample drawn from the protected area into a high-humidity chamber combined with a lowering of chamber pressure to create an environment in which the resultant moisture in the air condenses on any smoke particles present, forming a cloud. The cloud density is measured by a photoelectric principle. The density signal is processed and used to convey an alarm condition when it meets preset criteria. (SIG-IDS)
The principle of using a small amount of radioactive material to ionize the air between two differentially charged electrodes to sense the presence of smoke particles. The presence of smoke particles decreases the conductance of the air by reducing ion mobility, which will produce an alarm condition when it meets preset criteria. (SIG-IDS)
The principle of using a light source and a photosensitive sensor onto which the principal portion of the source emissions is focused. When smoke particles enter the light path, some of the light is scattered and some is absorbed, thereby reducing the light reaching the receiving sensor. The light reduction signal is processed and used to convey an alarm condition when it meets preset criteria. (SIG-IDS)
The principle of using a light source and a photosensitive sensor arranged so that the rays from the light source do not normally fall onto the photosensitive sensor. When smoke particles enter the light path, some of the light is scattered by reflection and refraction onto the sensor. The light signal is processed and used to convey an alarm condition when it meets preset criteria. (SIG-IDS)
The principle of using automatic analysis of real-time video images to detect the presence of smoke. (SIG-IDS)
Programs, instruments, procedures, data, and the like that are executed by a central processing unit of a product and that influences the functional performance of that product. For the purpose of this Code, software is one of two types: executive software and site-specific software. (SIG-TMS)
Control and supervisory program that manages the execution of all other programs and directly or indirectly causes the required functions of the product to be performed. Executive software is sometimes referred to as firmware, BIOS, or executive program. (SIG-TMS)
Program that is separate from, but controlled by, the executive software that allows inputs, outputs, and system configuration to be selectively defined to meet the needs of a specific installation. Typically it defines the type and quantity of hardware, customized labels, and the specific operating features of a system. (SIG-TMS)
A horizontally measured dimension used as a criterion in determining the allowable coverage of devices. (SIG-FUN)
A moving particle of solid material that emits radiant energy due to either its temperature or the process of combustion on its surface. [654, 2020] (SIG-IDS)
The number of watts (or the fraction of a watt) of radiant power from a point source radiator, applied as a unit step signal at the wavelength of maximum detector sensitivity, necessary to produce an alarm signal from the detector within the specified response time. (SIG-IDS)
Any individual, group, or organization that might affect, be affected by, or perceive itself to be affected by the risk. (SIG-ECS)
Equipment that receives electrical energy and then provides a means to store that energy in some form for later use in order to supply electrical energy when needed. (SIG-FUN)
The phenomenon where the upward movement of smoke and gases ceases due to the loss of buoyancy. (SIG-IDS)
The recipient of a contractual supervising station signal service(s). In case of multiple, noncontiguous properties having single ownership, the term refers to each protected premises or its local management. (SIG-SSS)
A subsidiary station is a normally unattended location that is remote from the supervising station and is linked by a communications channel(s) to the supervising station. Interconnection of signals on one or more transmission channels from protected premises with a communications channel(s) to the supervising station is performed at this location. (SIG-SSS)
An output circuit that is monitored for integrity and used exclusively to activate control equipment for notification appliance circuits. (SIG-FUN)
A facility that receives signals from alarm systems and at which personnel are in attendance at all times to respond to these signals. (SIG-SSS)
A supervising station that is listed for central station service and that also commonly provides less stringent supervising station services such as remote supervising services. (SIG-SSS)
A supervising station under the same ownership as the protected premises fire alarm system(s) that it supervises (monitors) and to which alarm, supervisory, or trouble signals are received and where personnel are in attendance at all times to supervise operation and investigate signals. (SIG-SSS)
A supervising station to which alarm, supervisory, or trouble signals or any combination of those signals emanating from protected premises fire alarm systems are received and where personnel are in attendance at all times to respond. (SIG-SSS)
A system or group of systems in which the operations of circuits and devices are transmitted automatically to, recorded in, maintained by, and supervised from a listed central station that has competent and experienced servers and operators who, upon receipt of a signal, take such action as required by this Code. Such service is to be controlled and operated by a person, firm, or corporation whose business is the furnishing, maintaining, or monitoring of supervised alarm systems. (SIG-SSS)
An installation of an alarm system that serves contiguous and noncontiguous properties, under one ownership, from a proprietary supervising station located at the protected premises, or at one of multiple noncontiguous protected premises, at which trained, competent personnel are in constant attendance. This includes the protected premises fire alarm system(s); proprietary supervising station; power supplies; signalinitiating devices; initiating device circuits; signal notification appliances; equipment for the automatic, permanent visual recording of signals; and equipment for initiating the operation of emergency building control services. (SIG-SSS)
A protected premises fire alarm system (exclusive of any connected to a public emergency reporting system) in which alarm, supervisory, or trouble signals are transmitted automatically to, recorded in, and supervised from a remote supervising station that has competent and experienced servers and operators who, upon receipt of a signal, take such action as required by this Code. (SIG-SSS)
The use of a system or a group of systems including the protected premises fire alarm system(s) in which the operations of circuits and devices are signaled to, recorded in, and supervised from a listed central station that has competent and experienced operators who, upon receipt of a signal, take such action as required by this Code. Related activities at the protected premises, such as equipment installation, inspection, testing, maintenance, and runner service, are the responsibility of the central station or a listed alarm service local company. Central station service is controlled and operated by a person, firm, or corporation whose business is the furnishing of such contracted services or whose properties are the protected premises. (SIG-SSS)
The use of a system or a group of systems including the protected premises fire alarm system(s) in which the operations of circuits and devices are signaled to, recorded in, and supervised from a supervising station under the same ownership as the protected premises that has competent and experienced operators who, upon receipt of a signal, take such action as required by this Code. Related activities at the protected premises, such as equipment installation, inspection, testing, maintenance, and runner service, are the responsibility of the owner. Proprietary supervising station service is controlled and operated by the entity whose properties are the protected premises. (SIG-SSS)
The use of a system including the protected premises fire alarm system(s) in which the operations of circuits and devices are signaled to, recorded in, and supervised from a supervising station that has competent and experienced operators who, upon receipt of a signal, take such action as required by this Code. Related activities at the protected premises, such as equipment installation, inspection, testing, and maintenance, are the responsibility of the owner. (SIG-SSS)
The service required to monitor performance of guard tours and the operative condition of fixed suppression systems or other systems for the protection of life and property. (SIG-PRO)
As used in this Code, supplementary refers to equipment or operations not required by this Code and designated as such by the authority having jurisdiction. (SIG-FUN)
A protective device for limiting transient voltages by diverting or limiting surge current. (SIG-PRS)
A loop start telephone circuit is an analog telephone circuit that supports loop start signaling as specified in either Telcordia GR-506-CORE, LATA Switching Systems Generic Requirements: Signaling for Analog Interface, or Telcordia GR-909-CORE, Fiber in the Loop Systems Generic Requirements. (SIG-SSS)
An assembly of communications equipment and telephone service providers that utilize managed facilities-based voice networks (MFVN) to provide the general public with the ability to establish communications channels via discrete dialing codes. (SIG-SSS)
An individual trained to operate and/or initiate a mass notification system. (SIG-ECS)
The active subassemblies at the supervising station used for signal receiving, processing, display, or recording of status change signals; a failure of one of these subassemblies causes the loss of a number of alarm signals by that unit. (SIG-SSS)
A means of communications within a building normally dedicated to emergency functions. Commonly referred to as fire fighters' phones, but can also be used for communications with fire fighters and/or fire wardens, including occupants, during an emergency, such as between a fire command center and a designated location, such as a stair, stairwell, or location of emergency equipment. (SIG-ECS)
The ability to conference multiple telephones in a single conversation. This is similar to what was referred to as a party line. (SIG-ECS)
The ability for personnel at the fire command center to receive indication of incoming calls and choose which call to answer. This includes the ability to transfer between incoming calls and conference multiple phone locations. Selective calling can include the ability to initiate calls to emergency phone locations. (SIG-ECS)
A multiplex alarm transmission system functional assembly located at the protected premises. (SIG-SSS)
Any alarm that occurs that is not the result of a potentially hazardous condition. (SIG-FUN)
An unwanted activation of an alarm initiating device caused by a person acting with malice. (SIG-FUN)
An unwanted activation of a signaling system or an alarm initiating device in response to a stimulus or condition that is not the result of a potentially hazardous condition. (SIG-FUN)
An unwanted activation of an alarm initiating device caused by a person acting without malice. (SIG-FUN)
An unwanted activation of an alarm initiating device or system output function where the cause has not been identified. (SIG-FUN)
The radio signal from the portable public safety subscriber transmitter to the base station receiver. (SIG-ECS)
The principle of using automatic analysis of real-time video images to detect the presence of flame. (SIG-IDS)
A scheme for prioritizing mass notification messages. (SIG-ECS)
Telephone company service allowing reduced costs for certain telephone call arrangements. In-WATS or 800-number service calls can be placed from anywhere in the continental United States to the called party at no cost to the calling party. Out-WATS is a service whereby, for a flat-rate charge, dependent on the total duration of all such calls, a subscriber can make an unlimited number of calls within a prescribed area from a particular telephone terminal without the registration of individual call charges. (SIG-SSS)
Signaling intended to provide alerting or information to exterior open spaces, such as campuses, neighborhood streets, a city, a town, or a community. (SIG-NAS)
A decentralized communications network made up of radio nodes organized in a mesh topology that does not rely on a pre-existing infrastructure. (SIG-SSS)
A system or a part of a system that can transmit and receive signals without the aid of interconnection wiring. It can consist of either a wireless control unit or a wireless repeater. (SIG-PRO)
A component used to relay signals among wireless devices, appliances, and control units. (SIG-PRO)
A defined area within the protected premises. A zone can define an area from which a signal can be received, an area to which a signal can be sent, or an area in which a form of control can be executed. (SIG-FUN)
Upcodes Diagrams
A discrete area of a building, or defined area outside a building, in which people are intended to receive common notification. (SIG-PRO)
An area consisting of one or more notification zones where identical signals are activated simultaneously. (SIG-ECS)