Adopting agency | BSC | BSC-CG | SFM | HCD | DSA | OSHPD | BSCC | DPH | AGR | DWR | CEC | CA | SL | SLC | |||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
1 | 2 | 1/AC | AC | SS | SS/CC | 1 | 1R | 2 | 3 | 4 | 5 | ||||||||||||
Adopt entire chapter | X | X | X | X | X | X | |||||||||||||||||
Adopt entire chapter as amended (amended sections listed below) |
X | X | X | ||||||||||||||||||||
Adopt only those sections that are listed below | X | ||||||||||||||||||||||
Chapter / Section | |||||||||||||||||||||||
302.1 | X | X | X | ||||||||||||||||||||
302.1.3 | X | ||||||||||||||||||||||
303.1 | X | ||||||||||||||||||||||
303.2 | X | ||||||||||||||||||||||
303.7 | X | ||||||||||||||||||||||
303.8 | X | ||||||||||||||||||||||
304.1 | X | ||||||||||||||||||||||
305.1 | X | ||||||||||||||||||||||
305.2 | X | ||||||||||||||||||||||
305.2.1 | X | ||||||||||||||||||||||
306.2 | X | ||||||||||||||||||||||
Table 307.1(1) | X | ||||||||||||||||||||||
Table 307.1(2) | X | ||||||||||||||||||||||
307.1.1 | X | ||||||||||||||||||||||
308.1 | X | ||||||||||||||||||||||
308.3 | X | †| †| ||||||||||||||||||||
308.3.3 | X | ||||||||||||||||||||||
308.4 | X | ||||||||||||||||||||||
308.4.6 | X | ||||||||||||||||||||||
308.4.7 | X | ||||||||||||||||||||||
308.4.8 | X | ||||||||||||||||||||||
308.4.9 | X | ||||||||||||||||||||||
308.5 | X | ||||||||||||||||||||||
308.5.1 | X | ||||||||||||||||||||||
308.5.1.1 | X | ||||||||||||||||||||||
308.5.2 | X | ||||||||||||||||||||||
308.5.3 | X | ||||||||||||||||||||||
308.5.4 | X | ||||||||||||||||||||||
310.1 | X | ||||||||||||||||||||||
310.2 | X | X | |||||||||||||||||||||
310.3 | X | X | |||||||||||||||||||||
310.3.1 | X | ||||||||||||||||||||||
310.3.2 | X | ||||||||||||||||||||||
310.4 | X | X | |||||||||||||||||||||
310.4.1 | X | ||||||||||||||||||||||
310.5 | X | ||||||||||||||||||||||
310.6 | X | ||||||||||||||||||||||
313 | X | ||||||||||||||||||||||
314 | X |
The state agency does not adopt sections identified with the following symbol: â€
The Office of the State Fire Marshal's adoption of this chapter or individual sections is applicable to structures regulated by other state agencies pursuant to Section 1.11.
User note:
About this chapter: Chapter 3 provides the criteria by which buildings and structures are classified into use groups and occupancies. Through the balance of the code, occupancy classification is fundamental in the setting of features of construction; occupant safety requirements, especially building limitations; means of egress; fire protection systems; and interior finishes.
Occupancy classification is the formal designation of the primary purpose of the building, structure or portion thereof. Structures shall be classified into one or more of the occupancy groups listed in this section based on the nature of the hazards and risks to building occupants generally associated with the intended purpose of the building or structure. An area, room or space that is intended to be occupied at different times for different purposes shall comply with all applicable requirements associated with such potential multipurpose. Structures containing multiple occupancy groups shall comply with Section 508. Where a structure is proposed for a purpose that is not specifically listed in this section, such structure shall be classified in the occupancy it most nearly resembles based on the fire safety and relative hazard. Occupied roofs shall be classified in the group that the occupancy most nearly resembles, according to the fire safety and relative hazard, and shall comply with Section 503.1.4.
- Assembly (see Section 303): Groups A-1, A-2, A-3, A-4 and A-5.
- Business (see Section 304): Group B.
- [SFM] Organized Camps (see Section 450): Group C.
- Educational (see Section 305): Group E.
- Factory and Industrial (see Section 306): Groups F-1 and F-2.
- High Hazard (see Section 307): Groups H-1, H-2, H-3, H-4 and H-5.
- Institutional (see Section 308): Groups I-2, I-2.1, I-3 and I-4.
- [SFM] Laboratory (see Section 202): Group B, unless classified as Group L (see Section 453) or Group H (see Section 307).
- [SFM] Laboratory Suites (see Section 453): Group L.
- Mercantile (see Section 309): Group M.
- Residential (see Section 310): Groups R-1, R-2, R-2.1, R-3, R-3.1 and R-4.
- Storage (see Section 311): Groups S-1 and S-2.
- Utility and Miscellaneous (see Section 312): Group U.
- [SFM] Existing buildings housing existing protective social care homes or facilities established prior to 1972 (see California Fire Code Chapter 11 and California Existing Building Code).
Upcodes Diagrams
Occupancy groups contain subordinate uses having similar hazards and risks to building occupants. Uses include, but are not limited to, those functional designations listed within the occupancy group descriptions in Section 302.1. Certain uses require specific limitations and controls in accordance with the provisions of Chapter 4 and elsewhere in this code.
Upcodes Diagrams
Assembly Group A occupancy includes, among others, the use of a building or structure, or a portion thereof, for the gathering of persons for purposes such as civic, social or religious functions; recreation, food or drink consumption or awaiting transportation; motion picture
and television production studio sound stages, approved production
facilities and production locations; or for the showing
of motion pictures when an admission fee is charged and
when such building or structure is open to the public and has
a capacity of 10 or more persons.
A building or tenant space used for assembly purposes with an occupant load of less than 50 persons shall be classified as a Group B occupancy.
The following rooms and spaces shall not be classified as Assembly occupancies:
- A room or space used for assembly purposes with an occupant load of less than 50 persons and accessory to another occupancy shall be classified as a Group B occupancy or as part of that occupancy.
- A room or space used for assembly purposes that is less than 750 square feet (70 m2) in area and accessory to another occupancy shall be classified as a Group B occupancy or as part of that occupancy.
Upcodes Diagrams
A room or space used for assembly purposes that is associated with a Group E occupancy is not considered a separate occupancy.
Upcodes Diagrams
Accessory religious educational rooms and religious auditoriums with occupant loads of less than 100 per room or space are not considered separate occupancies.
Upcodes Diagrams
Group A-1 occupancy includes assembly uses, usually with fixed seating, intended for the production and viewing of the performing arts or motion pictures including, but not limited to:
- Motion picture and television production studio sound stages, approved production facilities and production locations. (with live audiences).
- Motion picture theaters
- Symphony and concert halls
- Television and radio studios admitting an audience
- Theaters
Upcodes Diagrams
Group A-2 occupancy includes assembly uses intended for food and/or drink consumption including, but not limited to:
- Banquet halls
- Casinos (gaming areas)
- Nightclubs
- Restaurants, cafeterias and similar dining facilities (including associated commercial kitchens)
- Taverns and bars
Upcodes Diagrams
Group A-3 occupancy includes assembly uses intended for worship, recreation or amusement and other assembly uses not classified elsewhere in Group A including, but not limited to:
- Amusement arcades
- Art galleries
- Bowling alleys
- Community halls
- Courtrooms
- Dance halls (not including food or drink consumption)
- Exhibition halls
- Funeral parlors
- Greenhouses for the conservation and exhibition of plants that provide public access.
- Gymnasiums (without spectator seating)
- Indoor swimming pools (without spectator seating)
- Indoor tennis courts (without spectator seating)
- Lecture halls
- Libraries
- Museums
- Places of religious worship
- Pool and billiard parlors
- Waiting areas in transportation terminals
Group A-4 occupancy includes assembly uses intended for viewing of indoor sporting events and activities with spectator seating including, but not limited to:
- Arenas
- Skating rinks
- Swimming pools
- Tennis courts
Upcodes Diagrams
Group A-5 occupancy includes assembly uses intended for participation in or viewing outdoor activities including, but not limited to:
- Amusement park structures
- Bleachers
- Grandstands
- Stadiums
Upcodes Diagrams
[SFM] Fixed guideway
transit system buildings shall conform to the requirements
of this code for their occupancy classification in
addition to the provisions set forth in Section 443.
[SFM] For fire and life safety requirements,
see Section 446.
Upcodes Diagrams
Business Group B occupancy includes, among others, the use of a building or structure, or a portion thereof, for office, professional or service-type transactions, including storage of records and accounts. Business occupancies shall include, but not be limited to, the following:
- Airport traffic control towers
- Ambulatory care facilities serving six or fewer patients (see Section 308.3.3, I-2.1 for facilities serving more than five patients)
- Animal hospitals, kennels and pounds
- Banks
- Barber and beauty shops
- Car wash
- Civic administration
- Clinic, outpatient [SFM] (not classified as Group I-2.1)
- Dry cleaning and laundries: pick-up and delivery stations and self-service
- Educational occupancies for students above the 12th grade
- Electronic data processing
- Food processing establishments and commercial kitchens not associated with restaurants, cafeterias and similar dining facilities not more than 2,500 square feet (232 m2) in area.
- Laboratories: testing and research and [SFM] instruction
- Motor vehicle showrooms
- Post offices
- Print shops
- Professional services (architects, attorneys, dentists, physicians, engineers, etc.)
- Radio and television stations
- Telephone exchanges
- Training and skill development not in a school or academic program (this shall include, but not be limited to, tutoring centers, martial arts studios, gymnastics and similar uses regardless of the ages served, and where not classified as a Group A occupancy).
Upcodes Diagrams
Religious educational rooms and religious auditoriums, which are accessory to places of religious worship in accordance with Section 303.1.4 and have occupant loads of less than 100 per room or space, shall be classified as Group A-3 occupancies.
Upcodes Diagrams
This group includes buildings and structures or portions thereof occupied by more than six children 2 years of age and older who receive educational, supervision or personal care services for fewer than 24 hours per day.
Rooms and spaces within places of religious worship providing such day care during religious functions shall be classified as part of the primary occupancy where not licensed for day-care
purposes by the Department of Social Services.
A facility having five or fewer children receiving such day care shall be classified as part of the primary occupancy.
A facility such as the above within a dwelling unit and having five or fewer children receiving such day care shall be classified as a Group R-3 occupancy or shall comply with the California Residential Code.
Upcodes Diagrams
Factory Industrial Group F occupancy includes, among others, the use of a building or structure, or a portion thereof, for assembling, disassembling, fabricating, finishing, manufacturing, packaging, repair or processing operations that are not classified as a Group H hazardous or Group S storage occupancy.
Factory industrial uses that are not classified as Factory Industrial F-2 Low Hazard shall be classified as F-1 Moderate Hazard and shall include, but not be limited to, the following:
- Aircraft (manufacturing, not to include repair)
- Appliances
- Athletic equipment
- Automobiles and other motor vehicles
- Bakeries
- Beverages: over 16-percent alcohol content
- Bicycles
- Boats
- Brooms or brushes
- Business machines
- Cameras and photo equipment
- Canvas or similar fabric
- Carpets and rugs (includes cleaning)
- Clothing
- Construction and agricultural machinery
- Disinfectants
- Dry cleaning and dyeing
- Electric generation plants
- Electronics
- Energy storage systems (ESS) in dedicated use buildings
- Engines (including rebuilding)
-
Food processing establishments and commercial kitchens not associated with restaurants, cafeterias and similar dining facilities more than 2,500 square feet (232 m2) in area.
- Furniture
- Hemp products
- Jute products
- Laundries
- Leather products
- Machinery
- Metals
- Millwork (sash and door)
[SFM] Motion picture and television production studio Sound Stages, Approved Production Facilities and production locations (without live audiences)
- Motion pictures and television filming (without spectators)
- Musical instruments
- Optical goods
- Paper mills or products
- Photographic film
- Plastic products
- Printing or publishing
- Recreational vehicles
- Refuse incineration
- Shoes
- Soaps and detergents
- Textiles
- Tobacco
- Trailers
- Upholstering
- Wood; distillation
- Woodworking (cabinet)
Upcodes Diagrams
Factory industrial uses that involve the fabrication or manufacturing of noncombustible materials that during finishing, packing or processing do not involve a significant fire hazard shall be classified as F-2 occupancies and shall include, but not be limited to, the following:
Upcodes Diagrams
Upcodes Diagrams
High-hazard Group H occupancy includes, among others, the use of a building or structure, or a portion thereof, that involves the manufacturing, processing, generation or storage of materials that constitute a physical or health hazard in quantities in excess of those allowed in control areas complying with Section 414, based on the maximum allowable quantity limits for control areas set forth in Tables 307.1(1) and 307.1(2). Hazardous occupancies are classified in Groups H-1, H-2, H-3, H-4 and H-5 and shall be in accordance with this section, the requirements of Section 415 and the California Fire Code. Hazardous materials stored, or used on top of roofs or canopies, shall be classified as outdoor storage or use and shall comply with the California Fire Code.
MATERIAL | CLASS | GROUP WHEN THE MAXIMUM ALLOWABLE QUANTITY IS EXCEEDED |
STORAGEb | USE-CLOSED SYSTEMSb | USE-OPEN SYSTEMSb | |||||
Solid pounds (cubic feet) |
Liquid gallons (pounds) |
Gas cubic feet at NTP |
Solid pounds (cubic feet) |
Liquid gallons (pounds) |
Gas cubic feet at NTP |
Solid pounds (cubic feet) |
Liquid gallons (pounds) |
|||
Combustible dust | NA | H-2 | See
Note q
|
NA | NA | See
Note q
|
NA | NA | See
Note q
|
NA |
Combustible fiberq | Loose | H-3 | (100) | NA | NA | (100) | NA | NA | (20) | NA |
Baledo | (1,000) | (1,000) | (200) | |||||||
Combustible liquidc, i | II | H-2 or H-3 | NA | 120d, e | NA | NA | 120d | NA | NA | 30d |
IIIA | H-2 or H-3 | 330d, e | 330d | 80d | ||||||
IIIB | NA | 13,200e, f | 13,200f | 3,300f | ||||||
Cryogenic flammable | NA | H-2 | NA | 45d | NA | NA | 45d | NA | NA | 10d |
Cryogenic inert | NA | NA | NA | NA | NL | NA | NA | NL | NA | NA |
Cryogenic oxidizing | NA | H-3 | NA | 45d | NA | NA | 45d | NA | NA | 10d |
Explosives | Division 1.1 | H-1 | 1e, g | (1)e, g | NA | 0.25g | (0.25)g | NA | 0.25g | (0.25)g |
Division 1.2 | H-1 | 1e, g | (1)e, g | 0.25g | (0.25)g | 0.25g | (0.25)g | |||
Division 1.3 | H-1 or H-2 | 10e, g | (10)e, g | 1g | (1)g | 1g | (1)g | |||
Division 1.4 | H-3 | 50e, g | (50)e, g | 50g | (50)g | NA | NA | |||
Division 1.4G | H-3 | 125e, l | NA | NA | NA | NA | NA | |||
Division 1.5 | H-1 | 1e, g | (1)e, g | 0.25g | (0.25)g | 0.25g | (0.25)g | |||
Division 1.6 | H-1 | 1e, g | NA | NA | NA | NA | NA | |||
Flammable gas | Gaseous | H-2 | NA | NA | 1,000d,e | NA | NA | 1,000d,e | NA | NA |
Liquefied | (150)d,e | NA | (150)d,e | NA | ||||||
Flammable liquidc | IA | H-2 or H-3 | NA | 30d, e | NA | NA | 30d | NA | NA | 10d |
IB and IC | 120d, e | 120d | 30d | |||||||
Flammable liquid, combination (IA, IB, IC) | NA | H-2 or H-3 | NA | 120d, e, h | NA | NA | 120d, h | NA | NA | 30d, h |
Flammable solid | NA | H-3 | 125d, e | NA | NA | 125d | NA | NA | 25d | NA |
Inert gas | Gaseous | NA | NA | NA | NL | NA | NA | NL | NA | NA |
Liquefied | NA | NA | NA | NL | NA | NA | NL | NA | NA | |
Organic peroxide | UD | H-1 | 1e, g | (1)e, g | NA | 0.25g | (0.25)g | NA | 0.25g | (0.25)g |
I | H-2 | 5d, e | (5)d, e | 1d | (1)d | 1d | (1)d | |||
II | H-3 | 50d, e | (50)d, e | 50d | (50)d | 10d | (10)d | |||
III | H-3 | 125d, e | (125)d, e | 125d | (125)d | 25d | (25)d | |||
IV | NA | NL | NL | NL | NL | NL | NL | |||
V | NA | NL | NL | NL | NL | NL | NL | |||
Oxidizer | 4 | H-1 | 1g | (1)e, g | NA | 0.25g | (0.25)g | NA | 0.25g | (0.25)g |
3k | H-2 or H-3 | 10d, e | (10)d, e | 2d | (2)d | 2d | (2)d | |||
2 | H-3 | 250d, e | (250)d, e | 250d | (250)d | 50d | (50)d | |||
1 | NA | 4,000e, f | (4,000)e, f | 4,000f | (4,000)f | 1,000f | (1,000)f | |||
Oxidizing gas | Gaseous | H-3 | NA | NA | 1,500d,e | NA | NA | 1,500d,e | NA | NA |
Liquefied | (150)d, e | NA | (150)d,e | NA | ||||||
Pyrophoric | NA | H-2 | 4e, g | (4)e, g | 50e, g | 1g | (1)g | 10e, g | 0 | 0 |
Unstable (reactive) | 4 | H-1 | 1e, g | (1)e, g | 10e, g | 0.25g | (0.25)g | 2e, g | 0.25g | (0.25)g |
3 | H-1 or H-2 | 5d, e | (5)d, e | 50d, e | 1d | (1)d | 10d, e | 1d | (1)d | |
2 | H-3 | 50d, e | (50)d, e | 750d, e | 50d | (50)d | 750d, e | 10d | (10)d | |
1 | NA | NL | NL | NL | NL | NL | NL | NL | NL | |
Water reactive | 3 | H-2 | 5d, e | (5)d, e | NA | 5d | (5)d | NA | 1d | (1)d |
2 | H-3 | 50d, e | (50)d, e | 50d | (50)d | 10d | (10)d | |||
1 | NA | NL | NL | NL | NL | NL | NL |
For SI: 1 cubic foot = 0.028 m3, 1 pound = 0.454 kg, 1 gallon = 3.785 L.
NL = Not Limited; NA = Not Applicable; UD = Unclassified Detonable.
- For use of control areas, see Section 414.2.
- The aggregate quantity in use and storage shall not exceed the quantity listed for storage.
- The quantities of alcoholic beverages in retail and wholesale sales occupancies shall not be limited provided the liquids are packaged in individual containers not exceeding 1.3 gallons. In retail and wholesale sales occupancies, the quantities of medicines, foodstuffs or consumer products, and cosmetics containing not more than 50 percent by volume of water-miscible liquids with the remainder of the solutions not being flammable, shall not be limited, provided that such materials are packaged in individual containers not exceeding 1.3 gallons.
- [SFM] In other than Group L occupancies, maximum allowable quantities shall be increased 100 percent in buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1. Where Note e also applies, the increase for both notes shall be applied accumulatively.
- Maximum allowable quantities shall be increased 100 percent when stored in approved storage cabinets, day boxes, gas cabinets, gas rooms or exhausted enclosures or in listed safety cans in accordance with Section 5003.9.10 of the California Fire Code. Where Note d also applies, the increase for both notes shall be applied accumulatively.
- Quantities shall not be limited in a building equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1.
- Allowed only in buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1.
- Containing not more than the maximum allowable quantity per control area of Class IA, IB or IC flammable liquids.
- The maximum allowable quantity shall not apply to fuel oil storage complying with Section 603.3.2 of the California Fire Code.
- Quantities in parentheses indicate quantity units in parentheses at the head of each column.
- A maximum quantity of 220 pounds of solid or 22 gallons of liquid Class 3 oxidizers is allowed when such materials are necessary for maintenance purposes, operation or sanitation of equipment when the storage containers and the manner of storage are approved.
- Net weight of the pyrotechnic composition of the fireworks. Where the net weight of the pyrotechnic composition of the fireworks is not known, 25 percent of the gross weight of the fireworks, including packaging, shall be used.
- For gallons of liquids, divide the amount in pounds by 10 in accordance with Section 5003.1.2 of the California Fire Code.
- For storage and display quantities in Group M and storage quantities in Group S occupancies complying with Section 414.2.5, see Tables 414.2.5(1) and 414.2.5(2).
- Densely packed baled cotton that complies with the packing requirements of ISO 8115 shall not be included in this material class.
-
The following shall not be included in determining the maximum allowable quantities:
- Liquid or gaseous fuel in fuel tanks on vehicles.
- Liquid or gaseous fuel in fuel tanks on motorized equipment operated in accordance with the California Fire Code.
- Gaseous fuels in piping systems and fixed appliances regulated by the California Mechanical Code.
- Liquid fuels in piping systems and fixed appliances regulated by the California Mechanical Code.
- Alcohol-based hand rubs classified as Class I or II liquids in dispensers that are installed in accordance with Sections 5705.5 and 5705.5.1 of the California Fire Code. The location of the alcohol-based hand rub (ABHR) dispensers shall be provided in the construction documents.
- Where manufactured, generated or used in such a manner that the concentration and conditions create a fire or explosion hazard based on information prepared in accordance with Section 414.1.3.
MATERIAL | STORAGEb | USE-CLOSED SYSTEMSb | USE-OPEN SYSTEMSb | |||||
Solid poundsd, e |
Liquid gallons (pounds)d, e |
Gas cubic feet at NTP (pounds)d |
Solid poundsd |
Liquid gallons (pounds)d |
Gas cubic feet at NTP (pounds)d |
Solid poundsd |
Liquid gallons (pounds)d |
|
Corrosives | 5,000 | 500 | Gaseous 810e
Liquefied (150)
|
5,000 | 500 | Gaseous 810e
Liquefied (150)
|
1,000 | 100 |
Highly Toxic | 10 | (10) | Gaseous 20g
Liquefied (4)g
|
10 | (10) | Gaseous 20g
Liquefied (4)g
|
3 | (3) |
Toxic | 500 | (500) | Gaseous 810e
Liquefied (150)e
|
500 | (500) | Gaseous 810e
Liquefied (150)e
|
125 | (125) |
For SI: 1 cubic foot = 0.028 m3, 1 pound = 0.454 kg, 1 gallon = 3.785 L.
- For use of control areas, see Section 414.2.
- The aggregate quantity in use and storage shall not exceed the quantity listed for storage.
- In retail and wholesale sales occupancies, the quantities of medicines, foodstuffs or consumer products, and cosmetics containing not more than 50 percent by volume of water-miscible liquids and with the remainder of the solutions not being flammable, shall not be limited, provided that such materials are packaged in individual containers not exceeding 1.3 gallons.
- [SFM] In other than Group L occupancies, maximum allowable quantities shall be increased 100 percent in buildings equipped throughout with an approved automatic sprinkler system in accordance with Section 903.3.1.1. Where Note e also applies, the increase for both notes shall be applied accumulatively.
- Maximum allowable quantities shall be increased 100 percent where stored in approved storage cabinets, gas cabinets or exhausted enclosures as specified in the California Fire Code. Where Note d also applies, the increase for both notes shall be applied accumulatively.
- For storage and display quantities in Group M and storage quantities in Group S occupancies complying with Section 414.2.5, see Tables 414.2.5(1) and 414.2.5(2).
- Allowed only where stored in approved exhausted gas cabinets or exhausted enclosures as specified in the California Fire Code.
- Quantities in parentheses indicate quantity units in parentheses at the head of each column.
- For gallons of liquids, divide the amount in pounds by 10 in accordance with Section 5003.1.2 of the California Fire Code.
Upcodes Diagrams
An occupancy that stores, uses or handles hazardous materials as described in one or more of the following items shall not be classified as Group H, but shall be classified as the occupancy that it most nearly resembles.
- Buildings and structures occupied for the application of flammable finishes, provided that such buildings or areas conform to the requirements of Section 416 and the California Fire Code.
- Wholesale and retail sales and storage of flammable and combustible liquids in mercantile occupancies conforming to the California Fire Code.
- Closed piping system containing flammable or combustible liquids or gases utilized for the operation of machinery or equipment.
- Cleaning establishments that utilize combustible liquid solvents having a flash point of 140°F (60°C) or higher in closed systems employing equipment listed by an approved testing agency, provided that this occupancy is separated from all other areas of the building by 1-hour fire barriers constructed in accordance with Section 707 or 1-hour horizontal assemblies constructed in accordance with Section 711, or both.
- Cleaning establishments that utilize a liquid solvent having a flash point at or above 200°F (93°C).
- Liquor stores and distributors without bulk storage.
- Refrigeration systems.
- The storage or utilization of materials for agricultural purposes on the premises.
- Stationary storage battery systems installed in accordance with the California Fire Code.
- Corrosive personal or household products in their original packaging used in retail display.
- Commonly used corrosive building materials.
- Buildings and structures occupied for aerosol product storage shall be classified as Group S-1, provided that such buildings conform to the requirements of the California Fire Code.
- Display and storage of nonflammable solid and nonflammable or noncombustible liquid hazardous materials in quantities not exceeding the maximum allowable quantity per control area in Group M or S occupancies complying with Section 414.2.5.
- The storage of black powder, smokeless propellant and small arms primers in Groups M and R-3 and special industrial explosive devices in Groups B, F, M and S, provided such storage conforms to the quantity limits and requirements prescribed in the California Fire Code.
- Stationary fuel cell power systems installed in accordance with the California Fire Code.
- Capacitor energy storage systems in accordance with the California Fire Code.
- [SFM] Group L occupancies defined in Section 453.
Hazardous materials in any quantity shall conform to the requirements of this code, including Section 414, and the California Fire Code.
Buildings and structures containing materials that pose a detonation hazard shall be classified as Group H-1. Such materials shall include, but not be limited to, the following:
- Detonable pyrophoric materials
- Division 1.1
- Division 1.2
- Division 1.3
- Division 1.4
- Division 1.5
- Division 1.6
- Organic peroxides, unclassified detonable
- Oxidizers, Class 4
- Unstable (reactive) materials, Class 3 detonable and Class 4
The following occupancies containing explosive materials shall be classified as follows:
- Division 1.3 explosive materials that are used and maintained in a form where either confinement or configuration will not elevate the hazard from a mass fire to mass explosion hazard shall be allowed in H-2 occupancies.
- Articles, including articles packaged for shipment, that are not regulated as a Division 1.4 explosive under Bureau of Alcohol, Tobacco, Firearms and Explosives regulations, or unpackaged articles used in process operations that do not propagate a detonation or deflagration between articles shall be allowed in H-3 occupancies.
Buildings and structures containing materials that pose a deflagration hazard or a hazard from accelerated burning shall be classified as Group H-2. Such materials shall include, but not be limited to, the following:
- Class I, II or IIIA flammable or combustible liquids that are used or stored in normally open containers or systems, or in closed containers or systems pressurized at more than 15 pounds per square inch gauge (103.4 kPa).
- Combustible dusts where manufactured, generated or used in such a manner that the concentration and conditions create a fire or explosion hazard based on information prepared in accordance with Section 414.1.3.
- Cryogenic fluids, flammable.
- Flammable gases.
- Organic peroxides, Class I.
- Oxidizers, Class 3, that are used or stored in normally open containers or systems, or in closed containers or systems pressurized at more than 15 pounds per square inch gauge (103 kPa).
- Pyrophoric liquids, solids and gases, nondetonable.
- Unstable (reactive) materials, Class 3, nondetonable.
- Water-reactive materials, Class 3.
Buildings and structures containing materials that readily support combustion or that pose a physical hazard shall be classified as Group H-3. Such materials shall include, but not be limited to, the following:
- Class I, II or IIIA flammable or combustible liquids that are used or stored in normally closed containers or systems pressurized at 15 pounds per square inch gauge (103.4 kPa) or less.
- Combustible fibers, other than densely packed baled cotton, where manufactured, generated or used in such a manner that the concentration and conditions create a fire or explosion hazard based on information prepared in accordance with Section 414.1.3.
- Consumer fireworks, 1.4G (Class C, Common)
- Cryogenic fluids, oxidizing
- Flammable solids
- Organic peroxides, Class II and III
- Oxidizers, Class 2
- Oxidizers, Class 3, that are used or stored in normally closed containers or systems pressurized at 15 pounds per square inch gauge (103 kPa) or less
- Oxidizing gases
- Unstable (reactive) materials, Class 2
- Water-reactive materials, Class 2
Buildings and structures containing materials that are health hazards shall be classified as Group H-4. Such materials shall include, but not be limited to, the following:
- Corrosives
- Highly toxic materials
- Toxic materials
Semiconductor fabrication facilities and comparable research and development areas in which hazardous production materials (HPM) are used and the aggregate quantity of materials is in excess of those listed in Tables 307.1(1) and 307.1(2) shall be classified as Group H-5. Such facilities and areas shall be designed and constructed in accordance with Section 415.11.
Institutional Group I occupancy includes, among others, the use of a building or structure, or a portion thereof, in which care or supervision is provided to persons who are or are not capable of self-preservation without physical assistance or in which persons are detained for penal or correctional purposes or in which the liberty of the occupants is restricted. Institutional occupancies shall be classified as Group I-2, I-2.1, I-3 or I-4.
Restraint shall not be
permitted in any building except in Group I-2 occupancies
constructed for such use in accordance with Section 407.1.1
and Group I-3 occupancies constructed for such use in
accordance with Section 408.1.2.
Where occupancies house both ambulatory and nonambulatory persons, the more restrictive requirements shall apply.
Where occupancies house both ambulatory and nonambulatory persons, the more restrictive requirements shall apply.
Not used. (See Group R-2.1
Section 310.1).
Institutional Group I-2 occupancy shall include buildings and structures used for medical care on a 24-hour basis for more than five persons who are incapable of self-preservation or classified as nonambulatory
or bedridden.
This group shall include, but not be limited to, the following:
- Detoxification facilities
- Hospitals
- Nursing homes
- Psychiatric hospitals
A facility with five or fewer persons receiving medical care shall be classified as Group R-3.1 or shall comply with the California Residential Code provided an automatic sprinkler system is installed in accordance with Section 903.3.1.3 or Section R313 of the California Residential
Code.
A healthcare facility that receives persons
for outpatient medical care that may render the patient
incapable of unassisted self-preservation and where
each tenant space accommodates more than five such
patients.
Institutional Group I-3 occupancy shall include buildings or portions of buildings and structures that are inhabited by one or more persons who are under restraint or security. A Group I-3 facility is occupied by persons who are generally incapable of self-preservation due to security measures not under the occupants' control which includes persons restrained. This group shall include, but not be limited to, the following:
- Correctional centers
- Correctional hospitals
- Correctional nursing facilities
- Correctional mental health facilities
- Correctional treatment centers
- Courthouse holding facility
- Detention centers
- Detention treatment room
- Jails
- Juvenile halls
- Prerelease centers
- Prisons
- Reformatories
- Secure interview rooms
- Temporary holding facility
Buildings of Group I-3 shall be classified as one of the occupancy conditions specified in Sections 308.4.1 through 308.5.8 (see Section 408.1).
This occupancy condition shall include buildings in which free movement is allowed from sleeping areas, and other spaces where access or occupancy is permitted, to the exterior via means of egress without restraint. A Condition 1 facility is permitted to be constructed as Group R.
This occupancy condition shall include buildings in which free movement is allowed from sleeping areas and any other occupied smoke compartment to one or more other smoke compartments. Egress to the exterior is impeded by locked exits.
This occupancy condition shall include buildings in which free movement is allowed within individual smoke compartments, such as within a residential unit comprised of individual sleeping units and group activity spaces, where egress is impeded by remotecontrolled release of means of egress from such a smoke compartment to another smoke compartment.
This occupancy condition shall include buildings in which free movement is restricted from an occupied space. Remote-controlled release is provided to permit movement from sleeping units, activity spaces and other occupied areas within the smoke compartment to other smoke compartments.
This occupancy condition shall include buildings in which free movement is restricted from an occupied space. Staff-controlled manual release is provided to permit movement from sleeping units, activity spaces and other occupied areas within the smoke compartment to other smoke compartments.
This occupancy condition shall
include buildings containing only one temporary holding
facility with six or fewer persons under restraint or security
where the building is protected throughout with a
monitored automatic sprinkler system installed in accordance
with Section 903.3.1.1 and where the temporary
holding facility is protected throughout with an automatic
fire alarm system with notification appliances. A Condition
6 building shall be permitted to be classified as a
Group B occupancy.
This occupancy condition shall
include buildings containing only one temporary holding
facility with nine or less persons under restraint or security
where limited to the first or second story, provided the
building complies with Section 408.1.2.6. A Condition 7
building shall be permitted to be classified as a Group B
occupancy.
This occupancy condition shall
include buildings containing not more than four secure
interview rooms located within the same fire area where
not more than six occupants under restraint are located in
the same fire area. A Condition 8 building shall be is permitted
to be classified as a Group B occupancy, provided
the requirements in Section 408.1.2.7 are met.
This occupancy condition shall
include buildings where the use of the building is for correctional
medical care or correctional mental health care.
Institutional Group I-4 occupancy shall include buildings and structures occupied by more than six clients of any age who receive custodial care for fewer than 24 hours per day by persons other than parents or guardians, relatives by blood, marriage or adoption, and in a place other than the home of the clients cared for. This group shall include, but not be limited to, the following:
- Adult day care
- Child day care
A child day care facility that provides care for more than six but not more than 100 children under 2 years of age, where the rooms in which the children are cared for are located on a level of exit discharge serving such rooms and each of these child care rooms has an exit door directly to the exterior, shall be classified as Group E.
See Section 452.1.4 for daycares located above or below the first story.
Rooms and spaces within places of religious worship providing such care during religious functions shall be licensed by the
California State Department Health Services as required
by Health and Safety Code Division 2 Chapter 3.5.
A facility having six or fewer persons receiving custodial care shall be licensed pursuant to Health and Safety Code Division 2
Chapter 3.5 or 3.6.
A facility such as the above within a dwelling unit and having six or fewer persons receiving custodial care shall be classified as a Group R-3 occupancy, where
occupants are not capable of responding to an emergency
situation without physical assistance from the staff shall
be classified as a Group I-4.
Upcodes Diagrams
Mercantile Group M occupancy includes, among others, the use of a building or structure or a portion thereof for the display and sale of merchandise, and involves stocks of goods, wares or merchandise incidental to such purposes and accessible to the public. Mercantile occupancies shall include, but not be limited to, the following:
- Department stores
- Drug stores
- Markets
- Greenhouses for display and sale of plants that provide public access.
- Motor fuel-dispensing facilities
- Retail or wholesale stores
- Sales rooms
Upcodes Diagrams
The aggregate quantity of nonflammable solid and nonflammable or noncombustible liquid hazardous materials stored or displayed in a single control area of a Group M occupancy shall not exceed the quantities in Table 414.2.5(1).
Upcodes Diagrams
Upcodes Diagrams
Residential Group R includes, among others, the use of a building or structure, or a portion thereof, for sleeping purposes when not classified as an Institutional Group I or when not regulated by the California Residential
Code.
Residential Group R-1 occupancies containing sleeping units where the occupants are primarily transient in nature, including:
- Boarding houses (transient) with more than 10 occupants
- Congregate residences (transient) with more than 10 occupants
- Hotels (transient)
- Motels (transient)
- [HCD 1] Efficiency dwelling units (transient)
Residential Group R-2 occupancies containing sleeping units or more than two dwelling units where the occupants are primarily permanent in nature, including:
- Apartment houses
- Congregate residences (nontransient) with more than 16 occupants
- Boarding houses (nontransient)
- Convents
- Dormitories
- Fraternities and sororities
- Monasteries
- Hotels (nontransient)
- Live/work units
- Motels (nontransient)
- Vacation timeshare properties
- [HCD 1] Efficiency dwelling units (transient)
Upcodes Diagrams
Residential Group R-2.1 occupancies shall include buildings, structures or
parts thereof housing clients, on a 24-hour basis, who
because of age, mental disability or other reasons, live in
a supervised residential environment that provides personal
care services.
This occupancy may contain more than six nonambulatory and/or bedridden clients. (See Section 435 Special Provisions for Licensed 24-Hour Care Facilities in a Group R-2.1, R-3.1 or R-4 Occupancy). This group shall include, but not be limited to, the following:
This occupancy may contain more than six nonambulatory and/or bedridden clients. (See Section 435 Special Provisions for Licensed 24-Hour Care Facilities in a Group R-2.1, R-3.1 or R-4 Occupancy). This group shall include, but not be limited to, the following:
Assisted living facilities such as:
Residential care facilities,
Residential care facilities for the elderly (RCFEs),
Adult residential facilities,
Congregate living health facilities,
Group homes,
Residential care facilities for the chronically ill,
Congregate living health facilities for the terminally ill.
Social rehabilitation facilities such as:
Residential care facilities,
Residential care facilities for the elderly (RCFEs),
Adult residential facilities,
Congregate living health facilities,
Group homes,
Residential care facilities for the chronically ill,
Congregate living health facilities for the terminally ill.
Social rehabilitation facilities such as:
Halfway houses,
Community correctional centers,
Community treatment programs,
Work furlough programs,
Alcoholism or drug abuse recovery or treatment facilities.
Community correctional centers,
Community treatment programs,
Work furlough programs,
Alcoholism or drug abuse recovery or treatment facilities.
Residential Group R-3 occupancies where the occupants are primarily permanent in nature and not classified as Group R-1, R-2, R-2.1, R-2.2, R-3.1, R-4 or I, including:
- Buildings that do not contain more than two dwelling units
-
Congregate residences (nontransient) with 16 or fewer occupants
- Boarding houses (nontransient)
- Convents
- Dormitories
- Fraternities and sororities
- Monasteries
-
Congregate residences (transient) with 10 or fewer occupants
[HCD 1] Efficiency dwelling units - Adult care facilities that provide accommodations for six or fewer clients of any age for less than 24 hours.
- Licensing categories that may use this classification include Adult Day Programs.
- Alcoholism or drug abuse recovery homes (ambulatory only)
- Child care facilities that provide accommodations for six or fewer clients of any age for less than 24 hours.
- Licensing categories that may use this classification include, but are not limited to:
Family Day-Care Homes that provide accommodations for 14 or fewer children, in the provider's own home for less than 24-hours.- Adult care and child care facilities that are within a single family home are permitted to comply with the California Residential Code.
- Lodging houses (transient) with five or fewer guest rooms and 10 or fewer occupants
Upcodes Diagrams
This occupancy group
may include facilities licensed by a governmental agency
for a residentially based 24-hour care facility providing
accommodations for six or fewer clients of any age. Clients
may be classified as ambulatory, nonambulatory or bedridden.
A Group R-3.1 occupancy shall meet the requirements
for construction as defined for Group R-3, except as otherwise
provided for in Section 435 Special Provisions For
Licensed 24-Hour Care Facilities in a Group R-2.1, R-3.1
or R-4 Occupancy. This group may include:
Pursuant to Health and Safety Code Section 13143 with respect to these exempted facilities, no city, county or public district shall adopt or enforce any requirement for the prevention of fire or for the protection of life and property against fire and panic unless the requirement would be applicable to a structure regardless of the special occupancy. Nothing shall restrict the application of state or local housing standards to such facilities if the standards are applicable to residential occupancies and are not based on the use of the structure as a facility for ambulatory children. For the purpose of this exception, ambulatory children do not include relatives of the licensee or the licensee's spouse.
Adult residential facilities
Intermediate care facilities for the developmentally
disabled habilitative
Intermediate care facilities for the developmentally
disabled nursing
Nurseries for the full-time care of children under the age of
six, but not including "infants" as defined in Chapter 2
Residential care facilities for the elderly
Small family homes and residential care facilities for the
chronically ill
Exception:
Group Homes licensed by the Department
of Social Services which provide nonmedical board,
room and care for six or fewer ambulatory children or
children two years of age or younger, and which do not
have any nonambulatory clients shall not be subject to
regulations found in Section 435.
Pursuant to Health and Safety Code Section 13143 with respect to these exempted facilities, no city, county or public district shall adopt or enforce any requirement for the prevention of fire or for the protection of life and property against fire and panic unless the requirement would be applicable to a structure regardless of the special occupancy. Nothing shall restrict the application of state or local housing standards to such facilities if the standards are applicable to residential occupancies and are not based on the use of the structure as a facility for ambulatory children. For the purpose of this exception, ambulatory children do not include relatives of the licensee or the licensee's spouse.
Owner-occupied lodging houses with five or fewer guest rooms and 10 or fewer total occupants shall be permitted to be constructed in accordance with the California Residential Code.
Residential Group R-4 occupancy shall include buildings, structures or portions thereof for more than six ambulatory clients, but not more than 16 persons, excluding staff, who reside on a 24-hour basis in a supervised residential environment and receive custodial care. The persons receiving care are capable of self-preservation.
Group R-4 occupancies shall meet the requirements for construction as defined for Group R-3, except as otherwise provided for in this code. This occupancy classification may include a maximum six nonambulatory or bedridden clients (see Section 435, Special Provisions for Licensed 24-Hour Care Facilities in a Group R-2.1, R-3.1 or R-4). Group R-4 occupancies shall meet the requirements in Section 420. This group shall include, but not be limited to, the following:- Assisted living facilities such as:
- Residential care facilities,
- Residential care facilities for the elderly (RCFE),
- Adult residential facilities,
- Congregate living health facilities,
- Group homes.
- Social rehabilitation facilities such as:
- Halfway houses,
- Community treatment programs,
- Work furlough programs,
- Alcoholism or drug abuse recovery or treatment facilities.
Upcodes Diagrams
Upcodes Diagrams
A room or space used for storage purposes that is accessory to another occupancy shall be classified as part of that occupancy.
Upcodes Diagrams
Storage Group S-1 occupancies are buildings occupied for storage uses that are not classified as Group S-2, including, but not limited to, storage of the following:
- Aerosol products, Levels 2 and 3
- Aircraft hangar (storage and repair)
- Bags: cloth, burlap and paper
- Bamboos and rattan
- Baskets
- Belting: canvas and leather
- Books and paper in rolls or packs
- Boots and shoes
- Buttons, including cloth covered, pearl or bone
- Cardboard and cardboard boxes
- Clothing, woolen wearing apparel
- Cordage
- Dry boat storage (indoor)
- Furniture
- Furs
- Glues, mucilage, pastes and size
- Grains
- Horns and combs, other than celluloid
- Leather
- Linoleum
- Lumber
- Motor vehicle repair garages complying with the maximum allowable quantities of hazardous materials listed in Table 307.1(1) (see Section 406.8)
- Photo engravings
- Resilient flooring
- Self-service storage facility (mini-storage)
- Silks
- Soaps
- Sugar
- Tires, bulk storage of
- Tobacco, cigars, cigarettes and snuff
- Upholstery and mattresses
- Wax candles
Upcodes Diagrams
Storage Group S-2 occupancies include, among others, buildings used for the storage of noncombustible materials such as products on wood pallets or in paper cartons with or without single thickness divisions; or in paper wrappings. Such products are permitted to have a negligible amount of plastic trim, such as knobs, handles or film wrapping. Group S-2 storage uses shall include, but not be limited to, storage of the following:
- Asbestos
- Beverages up to and including 16-percent alcohol in metal, glass or ceramic containers
- Cement in bags
- Chalk and crayons
- Dairy products in nonwaxed coated paper containers
- Dry cell batteries
- Electrical coils
- Electrical motors
- Empty cans
- Food products
- Foods in noncombustible containers
- Fresh fruits and vegetables in nonplastic trays or containers
- Frozen foods
- Glass
- Glass bottles, empty or filled with noncombustible liquids
- Gypsum board
- Inert pigments
- Ivory
- Meats
- Metal cabinets
- Metal desks with plastic tops and trim
- Metal parts
- Metals
- Mirrors
- Oil-filled and other types of distribution transformers
- Parking garages, open or enclosed
- Porcelain and pottery
- Stoves
- Talc and soapstones
- Washers and dryers
Upcodes Diagrams
Upcodes Diagrams
Buildings and structures of an accessory character and miscellaneous structures not classified in any specific occupancy shall be constructed, equipped and maintained to conform to the requirements of this code commensurate with the fire and life hazard incidental to their occupancy. Group U shall include, but not be limited to, the following:
- Agricultural buildings
- Aircraft hangars, accessory to a one- or two-family residence (see Section 412.4)
- Barns
- Carports
- Communication equipment structures with a gross floor area of less than 1,500 square feet (139 m2)
- Fences more than 6 feet (1829 mm) in height
- Grain silos, accessory to a residential occupancy
- Livestock shelters
- Private garages
- Retaining walls
- Sheds
- Stables
- Tanks
- Towers
Group L occupancy includes the use of a building or structure, or a portion thereof, containing one or more laboratory suites as defined
in Section 453.
An organized camp
is a site with programs and facilities established for the primary
purpose of providing an outdoor group living experience
with social, spiritual, educational or recreational objectives,
for five days or more during one or more seasons of the year.