UpCodes logo
Table of contentsContents
CALIFORNIA PLUMBING CODE - MATRIX ADOPTION TABLE
APPENDIX I - INSTALLATION STANDARDS
(Matrix Adoption Tables are non-regulatory, intended only as an aid to the code user. See Chapter 1 for state agency authority and building applications.)
Adopting Agency
BSC BSC-CG SFM HCD DSA OSHPD BSCC DPH AGR DWR CEC CA SL SLC
1 2 1-AC AC SS SS/CC 1 1R 2 3 4 5
Adopt Entire Chapter                  
X
X
X
X
X
X
               
Adopt Entire Chapter as amended (amended sections listed below)                                              
Adopt only those sections that are listed below
X
   
X
X
   
X
X
                           
Chapter/Section                                              
IAPMO IS 26-2019                                               
lAPMO IS 31-2014
X
   
X
X
   
X
X
                           
IAPMO IS 33-2019                                              
TCNA Handbook-2018                                              
This state agency does not adopt sections identified with the following symbol:
The Office of the State Fire Marshal's adoption of this chapter or individual sections is applicable to structures regulated by other state agencies pursuant to Section 1.11.0.


"The information contained in this appendix is not part of this American National Standard (ANS) and has not been processed in accordance with ANSI's requirements for an ANS. As such, this appendix may contain material that has not been subjected to public review or a consensus process. In addition, it does not contain requirements necessary for conformance to the standard."

The following IAPMO Installation Standard is included here for the convenience of the users of the California Plumbing Code. It is not considered as a part of the California Plumbing Code unless formally adopted as such. This Installation Standard is an independent, stand-alone document published by the International Association of Plumbing and Mechanical Officials and is printed herein by the expressed written permission of IAPMO.

TRENCHLESS INSERTION OF POLYETHYLENE (PE) PIPE FOR SEWER LATERALS
IAPMO IS 26-2019e2

The provisions contained in this appendix are not mandatory unless specifically adopted by a state agency, or referenced in the adopting ordinance.
This standard shall govern the trenchless installation of polyethylene (PE) pipe for use in sanitary and storm sewers. The installed pipe shall comply with the requirements of the Uniform Plumbing Code (UPCTM) published by the International Association of Plumbing and Mechanical Officials (IAPMO) as to grade and connections to existing pipe and shall also comply with this standard. This standard specifies requirements for the installation of the trenchless insertion of polyethylene (PE) pipe for use in sanitary and storm sewers.
In this Standard,
  1. "shall" is used to express a requirement, i.e., a provision that the user is obliged to satisfy to comply with the Standard;
  2. "should" is used to express a recommendation, but not a requirement;
  3. "may" is used to express an option or something permissible within the scope of the Standard; and
  4. "can" is used to express a possibility or a capability.
Notes accompanying sections of the Standard do not specify requirements or alternative requirements; their purpose is to separate explanatory or informative material from the text. Notes to tables and figures are considered part of the table or figure and can be written as requirements.
This Standard refers to the following publications, and where such reference is made, it shall be to the current edition of those publications, including all amendments published thereto.

ASTM International
ASTM D3261
Standard Specification for Butt Heat Fusion Polyethylene (PE) Plastic Fittings for Polyethylene (PE) Plastic Pipe and Tubing
ASTM F714
Standard Specification for Polyethylene (PE) Plastic Pipe (DR-PR) Based on Outside Diameter
ASTM F894
Standard Specification for Polyethylene (PE) Large Diameter Profile Wall Sewer and Drain Pipe
ASTM F1055
Standard Specification for Electrofusion Type Polyethylene Fittings for Outside Diameter Controlled Polyethylene and Crosslinked Polyethylene (PEX) Pipe and Tubing
ASTM F2620
Standard Practice for Heat Fusion Joining of Polyethylene Pipe and Fittings
The following abbreviations apply in this Standard:
PE Polyethylene
HDPE High Density Polyethylene
Polyethylene (PE) sewer pipe or tubing and fitting joining methods shall be installed in accordance with the manufacturer's installation instructions and comply with ASTM F714, ASTM F894 the applicable nationally recognized standard.
HDPE Extra High Molecular Weight 3408 SDR 17 Pipe Socket-Type PE Fittings for Outside Diameter Controlled.

Note: The HDPE 3408 SDR 17 pipe used in this process was selected because of its ability to retain its circular shape even when bent on a 1.2 m (4 ft) radius during and after installation.
Pipe shall be stored in a way to protect it from mechanical damage (slitting, puncturing, etc.). It shall be stored under cover to keep it clean and avoid long term exposure to sunlight. Exposure to sunlight during normal construction periods is acceptable.
PE joints shall be made in accordance with the manufacturer's installation instructions. PE pipe shall be joined to other pipe materials by an approved listed adapter or transition fittings listed for the specific transition intended.
Butt-fusion joints for PE pipe shall be installed in accordance with ASTM F2620 and shall be made by heating the prepared ends of two pipes, pipe and fitting, or two fittings by holding ends against a heated element. The heated element shall be removed when the required melt or times are obtained, and heated ends shall be placed together with applied force. Do not disturb the joint until cooled to ambient temperature.
Electro-fusion joints shall be heated internally by a conductor at the interface of the joint. Fittings shall comply with ASTM F1055 for the performance requirements of polyethylene electro-fusion fittings. The specified electro-fusion cycle used to form the joint requires consideration of the properties of the materials being joined, the design of the fitting being used, and the environmental conditions. Align and restrain fitting to pipe to prevent movement and apply electric current to the fitting. Turn off the current when the required time has elapsed to heat the joint. Do not disturb the joint until cooled to ambient temperature.
Socket fusion joints shall be installed in accordance with ASTM F2620 and shall be made by simultaneously heating the outside surface of a pipe end and the inside of a fitting socket. Where the required melt is obtained, the pipe and fitting shall be joined by inserting one into the other with applied force. Do not disturb the joint until cooled to ambient temperature.
The trenchless installation of sewers will be as follows:
  1. Preliminary Steps
    1. Inspect the inside of the sewer line using a camera and recording device to ascertain the line condition.
    2. Mark the details revealed by the video inspection including:
      1. The ground surface to show the location of the lateral tie of the city wye.
      2. The line location with an arrow in the street pointing back at the lateral.
      3. The property denoting the lateral location.
      4. The locations of the proposed excavations.
    3. Obtain utility line identification service contact information and all applicable permits.
  2. Excavation
    In addition to the above markings, the local utility companies will mark utilities. Considerations are soil density; clearance from obstacles, utilities, and structures; location of bends, and water service locations. Excavations and shoring shall be in accordance with jurisdictional safety requirements.
  3. Set Up
    Fuse the proper length of polyethylene pipe in accordance with ASTM F2620, or ASTM D3261 and fuse the end to a small length that is attached to the pulling head. A rod pusher cable is pushed through the damaged host pipe and attached to the pulling cable, which is then drawn through the pipe. The clevis end of the cable is attached to the pulling head. The pulling equipment is then set up according to the manufacturer's instructions.
  4. Pulling
    Pull the pulling head through. Once the pull is done, complete the connection to the existing piping.
Each cleanout fitting for cast-iron pipe shall consist of a cast-iron or brass body and an approved plug. Each cleanout for galvanized wrought-iron, galvanized steel, copper, or brass pipe shall consist of a brass plug as specified in Table 1, or a standard weight brass cap, or an approved ABS or PVC plastic plug, or an approved stainless-steel cleanout or plug. Plugs shall have raised square heads or approved countersunk rectangular slots.

TABLE 1
CLEANOUTS

(See Section 4.6.1)
NPS SIZE OF CLEANOUT
(inches)
THREADS PER INCH
1.5 1.5 11.5
2 1.5 11.5
2.5 2.5 8
3 2.5 8
4 & larger 3.5 8
Note: For SI units: 1 inch = 25 mm
Each cleanout fitting and each cleanout plug, or cap shall be of an approved type.
Cleanouts shall be designed to be watertight and gastight.
The piping of the building sewer shall be tested with water. The Authority Having Jurisdiction shall be permitted to require the removal of cleanouts, etc., to ascertain whether the pressure has reached all parts of the system.
The system shall be tested by plugging the end of the building sewer at its points of connection to the public sewer or private sewage disposal system and completely filling the building sewer with water from the lowest to the highest point thereof.
The completed piping shall be internally inspected by camera unless waived by the Administrative Authority.
The following sections of the 2021 Uniform Plumbing Code apply.
105.2 Required Inspections
105.2.2 Other Inspections
105.3 Testing of Systems
301.2 Minimum Standards
309.0 Workmanship
312.0 Protection of Piping, Materials, and Structures
314.0 Trenching, Excavation, and Backfill
701.3 Drainage Fittings
705.5.1.1 Butt Fusion Joints
705.5.1.2 Electro-Fusion Joints
705.5.1.3 Socket-Fusion Joints
723.0 Building Sewer Test
The following standards from Tables 1701.1 and 1701.2 of the 2021 Uniform Plumbing Code apply.
ASTM D2239 Polyethylene (PE) Plastic Pipe (SIDR-PR) Based on Controlled Inside Diameter
ASTM D2683 Socket-Type Polyethylene Fittings for Outside Diameter-Controlled Polyethylene Pipe and Tubing
ASTM D3261 Butt Heat Fusion Polyethylene (PE) Plastic Fittings for Polyethylene (PE) Plastic Pipe and Tubing
ASTM F714 Polyethylene (PE) Plastic Pipe (DR-PR) Based on Outside Diameter
ASTM F894 Polyethylene (PE) Large Diameter Profile Wall Sewer and Drain Pipe
ASTM F1055 Electrofusion Type Polyethylene Fittings for Outside Diameter Controlled Polyethylene and Crosslinked Polyethylene (PEX) Pipe and Tubing
ASTM F2620 Heat Fusion Joining of Polyethylene Pipe and Fittings
ASTM D2657 Heat Fusion Joining of Polyolefin Pipe and Fittings
IAPMO PS 25 Metallic Fittings for Joining Polyethylene Pipe for Water Service and Yard Piping
"The information contained in this appendix is not part of this American National Standard (ANS) and has not been processed in accordance with ANSI's requirements for an ANS. As such, this appendix may contain material that has not been subjected to public review or a consensus process. In addition, it does not contain requirements necessary for conformance to the standard."

The following IAPMO Installation Standard is included here for the convenience of the users of the California Plumbing Code. It is not considered as a part of the California Plumbing Code unless formally adopted as such. This Installation Standard is an independent, stand-alone document published by the International Association of Plumbing and Mechanical Officials and is printed herein by the expressed written permission of IAPMO.
IAPMO IS 31-2014e2

The provisions contained in this appendix are not mandatory unless specifically adopted by a state agency, or referenced in the adopting ordinance.
This Standard specifies requirements for the installation of SDR 9 CTS crosslinked polyethylene (PEX) tubing and fittings, including cold-expansion, crimp, press, and mechanical compression fittings, intended for hot- and cold-water distribution systems within buildings.
This Standards applies to
  1. SDR 9 CTS PEX tubing complying with ASTM F876 and pressure-rated in accordance with PPI TR-3; and
  2. PEX fitting systems complying with
    1. ASTM F877, for mechanical compression fittings and metal or plastic insert fittings with stainless steel press sleeves;
    2. ASTM F1807 or ASTM F2159, for metal or plastic insert fittings with copper crimp rings;
    3. ASTM F1960, for cold expansion fittings with PEX reinforced rings; or
    4. ASTM F2080, for cold expansion fittings with metal compression sleeves.
In this Standard,
  1. "shall" is used to express a requirement, i.e., a provision that the user is obliged to satisfy to comply with the Standard;
  2. "should" is used to express a recommendation, but not a requirement;
  3. "may" is used to express an option or something permissible within the scope of the Standard; and
  4. "can" is used to express a possibility or a capability.
Notes accompanying sections of the Standard do not specify requirements or alternative requirements; their purpose is to separate explanatory or informative material from the text. Notes to tables and figures are considered part of the table or figure and can be written as requirements.
Proposals for amendments to this Standard will be processed in accordance with the standards-writing procedures of IAPMO.
This Standard refers to the following publications, and where such reference is made, it shall be to the current edition of those publications, including all amendments published thereto.
ASTM F876 Standard Specification for Crosslinked Polyethylene (PEX) Tubing
ASTM F877 Standard Specification for Crosslinked Polyethylene (PEX) Hot- and Cold-Water Distribution Systems
ASTM F1807 Standard Specification for Metal Insert Fittings Utilizing a Copper Crimp Ring for SDR9 Cross-linked Polyethylene (PEX) Tubing and SDR9 Polyethylene of Raised Temperature (PE-RT) Tubing
ASTM F1960 Standard Specification for Cold Expansion Fittings with PEX Reinforcing Rings for Use with Cross-linked Polyethylene (PEX) Tubing
ASTM F2080 Standard Specification for Cold-Expansion Fittings With Metal Compression-Sleeves for Cross-Linked Polyethylene (PEX) Pipe
ASTM F2159 Standard Specification for Plastic Insert Fittings Utilizing a Copper Crimp Ring for SDR9 Cross-linked Polyethylene (PEX) Tubing and SDR9 Polyethylene of Raised Temperature (PE-RT) Tubing
ASTM F2657 Standard Test Method for Outdoor Weathering Exposure of Crosslinked Polyethylene (PEX) Tubing
AWWA C904 Cross-Linked Polyethylene (PEX) Pressure Tubing, 1/2 In. (12 mm) Through 3 In. (76 mm) for Water Service
IAPMO/ANSI UPC-1 Uniform Plumbing Code
PPI TR-3 Policies and Procedures for Developing Hydrostatic Design Basis (HDB), Pressure Design Basis (PDB), Strength Design Basis (SDB), and Minimum Required Strength (MRS) Ratings for Thermoplastic Tubing Materials or Tubing
The following abbreviations apply in this Standard:
CTS copper tube size
HDPE high density polyethylene
IC insulation contact
NTS nominal tubing size
PEX crosslinked polyethylene
SDR standard dimension ratio
UV ultraviolet light
PEX tubing can be
  1. pigmented throughout (i.e., with color);
  2. non-pigmented (e.g., translucent or natural); or
  3. coated with a pigmented layer.
PEX tubing is typically available in NTS-1/4 to NTS-3.
Before installation, the installer shall review the tubing markings and verify that
  1. the standard designation(s) of the fittings to which the tube can be joined to is included in the markings;
  2. it bears a certification mark from an accredited certification organization; and
  3. pressure and temperature ratings meet or exceed that of the intended end-use.
Cold-expansion fittings typically
  1. are made of brass, stainless steel, or sulfone;
  2. consist of an insert and a PEX reinforcing ring; and
  3. are available in NTS-3/8 to NTS-3.
Crimp or press insert fittings typically
  1. are made of brass, stainless steel, or sulfone;
  2. consist of an insert and a copper crimp ring or a stainless steel press ring
  3. are available in NTS-3/8 to NTS-2.
Compression (i.e., transition) fittings typically
  1. are made of brass; and
  2. consist of
    1. a nut, a compression ring, and an insert; or
    2. an O-ring brass insert with a compression sleeve
  3. are available in NTS-1/4 to NTS-3.
Only fittings systems marked on the tubing shall be used for installation with that particular tubing.
Tools and tool accessories (e.g., tool heads) used for the installation of PEX tubing systems shall be in accordance with the manufacturer's specifications and written instructions.
PEX tubing passing through drilled or notched metal studs or metal joists, or hollow-shell masonry walls shall be protected from abrasion by elastomeric or plastic sleeves or grommets.
Steel-plate protection shall be installed in accordance with the local plumbing code.
When receiving PEX tubing shipments, the receiver shall inspect and inventory each shipment, ensuring that there has been no loss or damage. In addition:
  1. At the time of unloading, the markings of all tubing, fittings, and accessories shall be verified to ensure that all items have been manufactured in accordance with the applicable product Standard and appropriately certified.
  2. An overall examination of the shipment shall be made. If the shipment is intact, ordinary inspection while unloading shall be sufficient to ensure that the items have arrived in good condition.
  3. If the load has shifted, has broken packaging, or shows evidence of rough treatment, each item shall be carefully inspected for damage.
  4. The total quantities of each shipment (e.g., tubing, gaskets, fittings, and accessories) shall be checked against shipping records.
  5. Any damaged or missing items shall be noted on the delivery slip. The carrier shall be notified immediately and a claim made in accordance with its instructions.
  6. No damaged material shall be disposed of. The carrier shall recommend the procedure to follow.
  7. Shortages and damaged materials are normally not reshipped without request. If replacement material is needed, it shall be reordered from the manufacturer, the distributor, or a manufacturer's representative.
PEX tubing and fittings shall be stored indoors and in its original packaging until the time of installation. Appropriate precautions to protect the tubing from damage, impact, and punctures shall be taken.
Accumulative exposure time to UV radiation during storage and installation shall not exceed the UV exposure limits recommended by the manufacturer or specified in ASTM F876.
Note: ASTM F876 has four categories for UV- resistance, ranging from untested to 6 months of continuous exposure, as listed in the material designation code.
PEX tubing and fittings shall not be exposed to open flames.
PEX tubing shall not be exposed to temperatures exceeding 93°C (200°F).
Chemical compatibility (e.g., with common construction materials) shall be verified with the manufacturer prior to direct contact.
In general, petroleum- or solvent-based chemicals (e.g., paints, greases, pesticides, or sealants) shall not be allowed to come in direct contact with PEX tubing or fittings.
Thermal expansion and contraction forces on suspended horizontal runs of PEX tubing that can experience a 22°C (40°F) or greater change in temperature (operating temperature compared to ambient temperature) shall be controlled by a means of mitigating temperature-induced stresses to other parts of the water distribution system. Means for controlling thermal expansion and contraction include
  1. loops;
  2. offsets;
  3. arms with rigid anchor points; and
  4. supporting the tubing with continuous runs of CTS support channels with
    1. rigid anchor points installed every 20 m (65 ft); and
    2. proper strapping (e.g., 27 kg (60 lb) straps or equivalent) spaced 1 m (3 ft) and rated for the maximum temperature and UV exposure of the PEX tubing application.
Thermal expansion and contraction forces on vertical runs of PEX tubing that pass through more than one floor and can experience a 22°C (40°F) or greater change in temperature (operating temperature compared to ambient temperature) shall be controlled by installing
  1. a riser clamp at the top of every other floor; and
  2. mid-story guides to maintain the alignment of the vertical tubing.
Note: Installing riser clamps isolates expansion and contraction to two-floor intervals allowing the PEX tubing to naturally compensate for the expansion and contraction.
Adequate clearance shall be provided between PEX tubing and the building structure (e.g., using bored holes and sleeves) to allow for free longitudinal movement of the tubing.


Note:
LB = C   x   √(D   x   ΔL)
where
LB = length of flexible arm
C = material constant (12 for PEX)
D = nominal outside diameter of tubing
ΔL = thermal expansion length

FIGURE 1
EXPANSION ARMS
(See Sections 6.4.1 and 7.3)
Expansion arms shall be installed as illustrated in Figure 1.
The minimum length of expansion arms shall be calculated using the following equation:

where
LB = length of flexible arm
C = material constant (12 for PEX)
D = nominal outside diameter of tubing
ΔL = thermal expansion length

Note:

LB shall be calculated as specified in Figure 2 and divided into three sections, as follows:

LB   =   L1 + (2 x L2)

where

L1   =   LB ÷ 5; and

L2   =   L1 x 2.
FIGURE 2
EXPANSION LOOPS
(See Sections 6.4.2 and 7.3)
Expansion loops shall be installed at the mid-point between anchors, as illustrated in Figure 2.
The minimum length of expansion loops shall be calculated using the equation in Section 6.4.1.2; however, the distance LB shall be divided into three sections as illustrated in Figure 2, where

L1 = LB ÷ 5; and

L2 = L1 x 2
Vertical PEX tubing shall
  1. be supported at each floor or as specified by the water-distribution system designer to allow for expansion and contraction; and
  2. have mid-story guides.
Unless otherwise authorized by the authority having jurisdiction, suspended horizontal runs of PEX tubing
  1. NTS-1 and smaller shall be supported every 0.8 m (32 in), unless continuously supported by metallic CTS or V channels that
    1. are supported at intervals not exceeding 1.8 m (6 ft);
    2. have a maximum cantilever, measured from the support to the end of the CTS support channel, of 0.5 m (1.5 ft); and
  2. NTS-11/4 and larger shall be supported every 1.2 m (4 ft), unless continuously supported by metallic CTS or V channels that
    1. are supported at intervals not exceeding 2.4 m (8 ft); and
    2. have a maximum cantilever, measured from the support to the end of the CTS support channel, of 0.5 m (1.5 ft).
Anchors shall be
  1. used to restrict PEX tubing movement;
  2. made of materials that provide rigidity to the support system and utilize pipe clamps designed for plastic tubing capable of restraining the tubing; and
  3. installed in accordance with Figures 1 or 2, as applicable (i.e., anchor distances and size of arms and offsets).
Note: Anchors are typically installed every 20 m (65 ft). See Section 6.
The procedure for making joints shall be as specified by the manufacturer.
PEX tubing systems manufactured in accordance with the applicable standards referenced in Section 2 are deemed manufactured joints and may be installed in concealed spaces without the need for access panels.
Except for double-wall B-vents, which require a 25 mm (1 in) clearance, the clearance between gas appliance vents and PEX tubing shall be at least 150 mm (6 in).
Except when the PEX tubing is protected with fiberglass or closed-cell insulation or the recessed light is IC-rated, the clearance between recessed light fixtures and PEX tubing shall be at least 300 mm (12 in).
When in direct view of the light source, the clearance between fluorescent lighting and PEX tubing shall be at least 1.5 m (5 ft). If the minimum clearance cannot be achieved, the PEX tubing shall be protected with a UV-blocking sleeve.
Hot-work joints (e.g., soldering, brazing, welding, and fusion-welding) shall be
  1. made at least 500 mm (18 in) from PEX tubing in the same water line; and
  2. performed prior to completing the PEX joints.
The free (unsupported) bending radius for PEX tubing, measured at the outside of the bend, shall be not less than six times the actual outside diameter of the tubing, unless otherwise specified by the PEX manufacturer. Supports should be used to facilitate rigid bends and to alleviate stress on PEX joints when bends are needed in close proximity to such joints.
Tighter bends may be used when the PEX tubing is uniformly bent (supported) around a curved bracket or other rigid fixture. In this case, the minimum outside radius of the supported bend shall be as specified by the PEX manufacturer.
Directional fittings (e.g., 90° and 45° elbows) should only be installed where necessary.
Note: The flexible nature of PEX tubing allows for sweeping bends resulting in less fittings and joints.
PEX tubing and fittings may be used in direct burial applications when allowed in the manufacturer's written installation instructions.
Note: AWWA C904 should be consulted for water service applications.
Manufacturer's installation instructions shall be consulted prior to installation of PEX tubing in fire resistive constructions. PEX tubing penetrating a wall or floor-and-ceiling fire-rated assembly shall include a means of passive fire protection in accordance with the local codes.
PEX tubing shall be sized in accordance with IAPMO/ANSI UPC 1.

Note: Potable water piping sizing is addressed in Chapter 6 and Appendix A of IAPMO/ANSI UPC.
The tubing manufacturer's pressure-loss data should be referenced when using Appendix A of IAPMO/ANSI UPC 1. In absence of such data, Figures 3 and 4 shall be used.

FIGURE 3
PRESSURE LOSS OF PEX TUBING AT 16 °C (60°F)
(See Section 10.6.2) 



FIGURE 4
PRESSURE LOSS OF PEXTUBING AT 49 °C (120°F)
(See Section 10.6.2) 


Flow velocities through the water distribution system, used for calculating flush tank and flush valve fixture units depending on the tubing sizes (see Table 1), shall not exceed
  1. 3.0 m/s (10 ft/s) for cold-water distribution systems; and
  2. 2.4 m/s (8 ft/s) for hot-water distribution systems.
Note: The flow velocities in Items (a) and (b) account for the increased velocities through the fittings.

TABLE 1
CALCULATION OF FLUSH TANK AND FLUSH VALVE FIXTURE UNITS
(See Section 10.6.3)
NOMINAL TUBING
SIZE
FLOW VELOCITY: 3.0 m/s (10 ft/s) FLOW VELOCITY: 2.4 m/s (8 ft/s)
FLOW VOLUME,
L/min (gpm)
FLUSH TANK
FIXTURE UNITS
FLUSH VALVE
FIXTURE UNITS
FLOW,
L/min (gpm)
FLUSH TANK
FIXTURE UNITS
FLUSH VALVE
FIXTURE UNITS
1/2 20.8 (5.5) 6 16.7 (4.4) 4
3/4 41.6 (11.0) 15 33.3 (8.8) 11
1 68.9 (18.2) 26 55.3 (14.6) 20
11/4 103.0 (27.2) 46 10 82.5 (21.8) 33 5
11/2 143.5 (37.9) 77 24 114.7 (30.3) 54 13
2 246.1 (65.0) 200 91 196.8 (52.0) 135 52
3 533.0 (140.8) 590 495 426.2 (112.6) 443 310
Hot-water recirculation systems shall
  1. be balanced to maintain adequate system temperatures; and
  2. have flow velocities that do not exceed 0.6 m/s (2 ft/s) (see Table 2); and
  3. use only PEX tubing designated for hot, chlorinated water recirculation systems and rated for the maximum percentage of time during which the system is intended to be operated at elevated temperatures, in accordance with ASTM F876.

TABLE 2
TUBING SIZES, FLOWS, AND FRICTION LOSSES FOR HOT-WATER RECIRCULATION SYSTEMS
(See Section 10.6.4)
NOMINAL TUBING SIZE FLOW VELOCITY
m/s (ft/s)
FLOW VOLUME L/min (gpm) FRICTION LOSSES AT 49°C (120°F)
kPa/m (psi/ft)
1/2 0.6 (2) 4.2 (1.1) 0.4411 (0.0195)
3/4 0.6 (2) 8.3 (2.2) 0.2850 (0.0126)
1 0.6 (2) 13.6 (3.6) 0.2081 (0.0092)
1 1/4 0.6 (2) 20.4 (5.4) 0.1629 (0.0072)
1 1/2 0.6 (2) 28.4 (7.5) 0.1335 (0.0059)
2 0.6 (2) 48.8 (12.9) 0.0950 (0.0042)
Installation of PEX water distribution systems may be tested with air when
  1. expressly allowed in the written instructions of the manufacturers of all plastic pipe and fittings installed at the time the PEX piping system is being tested; and
  2. compressed air or other gas testing is not prohibited by the authority having jurisdiction.
"The information contained in this appendix is not part of this American National Standard (ANS) and has not been processed in accordance with ANSI's requirements for an ANS. As such, this appendix may contain material that has not been subjected to public review or a consensus process. In addition, it does not contain requirements necessary for conformance to the standard."

The following IAPMO Installation Standard is included here for the convenience of the users of the California Plumbing Code. It is not considered as a part of the California Plumbing Code unless formally adopted as such. This Installation Standard is an independent, stand-alone document published by the International Association of Plumbing and Mechanical Officials and is printed herein by the expressed written permission of IAPMO.

IAPMO IS 33-2019e1
The provisions contained in this appendix are not mandatory unless specifically adopted by a state agency, or referenced in the adopting ordinance.
This Standard specifies requirements for the installation of thrust blocking for ductile iron pipe with elastomeric gasketed joints and fittings and PVC piping with solvent cemented or elastomeric gasketed joints intended for cold water building supply and yard piping.
Thrust blocks covered by this standard prevent separation of joints and pipe movement by transferring the resultant thrust force at a bend to the undisturbed soil behind the thrust block. The bearing strength of the soil is expressed in pounds per square foot. Therefore, the area behind the thrust block must engage enough soil area to resist the resultant thrust force at a change in direction.
In this Standard,
  1. "shall" is used to express a requirement, i.e., a provision that the user is obliged to satisfy to comply with the Standard;
  2. "should" is used to express a recommendation, but not a requirement;
  3. "may" is used to express an option or something permissible within the scope of the Standard; and
  4. "can" is used to express a possibility or a capability.
Notes accompanying sections of the Standard do not specify requirements or alternative requirements; their purpose is to separate explanatory or informative material from the text. Notes to tables and figures are considered part of the table or figure and can be written as requirements.
Proposals for amendments to this Standard will be processed in accordance with the standards-writing procedures of IAPMO.
This Standard refers to the following publications, and where such reference is made, it shall be to the current edition of those publications, including all amendments published thereto.
IAPMO/ANSI UPC-1 Uniform Plumbing Code
The following abbreviations apply in this Standard:
PVC polyvinyl chloride
In lines with rubber gasketed joints, thrust blocks shall be installed at all locations including:
  1. Changes in direction, as at tees and bends
  2. Changes in size, as at reducers
  3. Stops, as at dead ends
  4. Valves, where thrusts may be expected.
Note: See examples in Figure 1.


FIGURE 1
LOCATION OF THRUST BLOCKS
(STANDARD AND METRIC COMBINED)
A COMPARISON OF THRUST-BLOCK AREAS
(See Section 4.1)
Piping shall be sized in accordance with the applicable code or jurisdictional requirements.

Note: For example, Appendix A, "Recommended Rules for Sizing the Water Supply System", or Section 610.0, "Size of Potable Water Piping" of IAPMO/ANSI UPC-1 may be use for sizing pipe.
Piping shall be sized in accordance with the applicable code or jurisdictional requirements.

Note: For example, Appendix A, "Recommended Rules for Sizing the Water Supply System", or Section 610.0, "Size of Potable Water Piping" of IAPMO/ANSI UPC-1 may be use for sizing pipe.
Elastomeric gasketed pipe may be deflected in accordance with the manufacturer's recommendations provided that it shall not be permanently staked or blocked to maintain this deflection.
The pipe and fitting system shall be designed for the maximum working pressure in accordance with Table 1.
TABLE 1
MAXIMUM WORKING PRESSURE FOR PIPE AND FITTING SYSTEM DESIGN

(See Section 4.5)
MAXIMUM WORKING PRESSURE kPa (psi) SIZES PIPE FITTINGS
NPS DN
1103 kPa (160 psi) 1/2 to 8 15 to 200 SDR 26 Schedule 40
Schedule 80
1379 kPa (200 psi) 1/2 to 4 15 to 100 SDR 21 Schedule 40
1/2 to 8 15 to 200 Schedule 80
1724 kPa (250 psi) 1/2 to 3 15 to 80 SDR 17 Schedule 40
1/2 to 8 15 to 200 Schedule 80
2172 kPa (315 psi) 1/2 to 1-1/2 15 to 40 SDR 13.5 Schedule 40
1/2 to 4 15 to 100 Schedule 80
1103 kPa (160 psi) 5 to 8 125 to 200 Schedule 40 Schedule 40
1517 kPa (220 psi) 2 to 4 50 to 100 Schedule 40 Schedule 40
Schedule 80
2206 kPa (320 psi) 1/2 to 1-1/2 15 to 40 Schedule 40 Schedule 40
Schedule 80
1103 kPa (160 psi) 5 to 8 125 to 200 Schedule 80 Schedule 40
1517 kPa (220 psi) 2 to 4 50 to 100 Schedule 80 Schedule 40
2206 kPa (320 psi) 1/2 to 1-1/2 15 to 40 Schedule 80 Schedule 40
1724 kPa (250 psi) 5 to 8 125 to 200 Schedule 80 Schedule 80
2206 kPa (320 psi) 1/2 to 4 15 to 100 Schedule 80 Schedule 80
Thrust block sizes shall be based on the maximum line pressure, pipe size and the safe bearing load of the soil.
From Table 2, Thrust at Fittings in pounds at 100 psi of Water Pressure, the thrust for a NPS 4 Dead End Tee at a pressure of 100 psi is 1620 lb.

TABLE 2
THRUST AT FITTINGS IN POUNDS AT 100 psi OF WATER PRESSURE

(See Sections 5.2.1.1, 5.2.1.2, and 5.2.2.2)
PIPE SIZE NPS 90°
BENDS
45°
BENDS
22-1/2°
BENDS
DEAD ENDS AND TEES
1-1/2 415 225 115 295
2 645 350 180 455
2-1/2 935 510 260 660
3 1395 755 385 985
3-1/2 1780 962 495 1260
4 2,295 1245 635 1620
5 3,500 1900 975 2,490
6 4,950 2,710 1385 3,550
8 8,300 4,500 2,290 5,860
10 12,800 6,900 3,540 9,050
12 18,100 9,800 5,000 12,800
The thrust for an NPS 4, Dead End Tee, at a pressure of 150 psi is 2430 lb or 1.5 times the thrust found in Table 2.

The calculation is as follows:
  1. The thrust from Table 2, for an NPS 4, Dead End Tee, at 100 psi, is 1,620 lb.
  2. The actual pressure of the system is 150 psi.
  3. Divide the actual pressure by the table pressure or 150 psi/100 psi is 1.5.
  4. Multiply the thrust from Table 2, for an NPS 4, Dead End Tee, at 100 psi, times the ratio of the actual/table pressure, or 1.5 times 1620 lb for a thrust of 2430 lb.
From Table 3, Thrust at Fittings in Newtons at 689 kPa of Water Pressure, the thrust for a DN 125, 90° Bend, at a pressure of 689 kPa is 15,757 N.

TABLE 3
THRUST AT FITTINGS IN NEWTONS (N) AT 689 kPa OF WATER PRESSURE

(See Sections 5.2.1.3, and 5.2.1.4)
PIPE SIZE DN 90°
BENDS
45°
BENDS
22-1/2°
BENDS
DEAD ENDS AND TEES
40 1847 1000 515 1315
50 2870 1560 800 2025
65 4160 2270 1160 3940
80 6210 3360 1715 4385
90 7925 4280 2205 5610
100 10,215 5540 2815 7210
125 15,575 8455 4340 11,080
150 22,030 12,060 6165 15,800
200 36,935 20,025 10,190 26,080
250 56,960 30,705 15,755 40,275
300 80,545 43,610 22,250 56,960
The thrust for a DN 125, 90° Bend, at a pressure of 861 kPa is 19,469 N or 1.25 times the force in Table 3.

The calculation is as follows
  1. The thrust from Table 3, for a DN 127, 90° Bend at a pressure of 689 kPa, is 15,575 N.
  2. The actual pressure of the system is 861 kPa.
  3. Divide the actual pressure by the table pressure or 861 kPa/689 kPa or 1.25.
  4. Multiply the thrust from Table 2, for a DN 125, 90° Bend, at a pressure of 689 kPa times, the ratio of the actual/table pressure, or 1.25 times 15,757 N for a thrust of 19,469 N.
Note: 1000 N is equal to 1 kN for a thrust of 19.469 kN.
The thrust block bearing area is determined by dividing the thrust by the safe bearing load of the soil.

Note:
See examples in Figure 2


FIGURE 2
THRUST BLOCK BEARING AREA
(See Section 5.2.2)
From Table 4, Safe Bearing Loads of Various Soils the safe bearing load of sand is 2000 lb/ft2.

TABLE 4
SAFE BEARING LOADS OF VARIOUS SOILS

(See Sections 5.2.2.1, and 5.2.2.3 and 5.2.2.4)
  Safe Bearing Load
SOIL lbs/ft2 (psf) kN/m2 (kPa)
Mulch, Peat, etc. 0 0
Soft Clay 1000 48
Sand 2000 96
Sand and Gravel 3000 143
Sand and Gravel Cement with Clay 4000 191
Hard Shale 10,000 478
The thrust block bearing area for an NPS 4, Dead End Tee, at a pressure of 100 psi in sand is 0.81 ft2.

The calculation is as follows
  1. From Table 2, Thrust at Fittings in pounds at 100 psi of Water Pressure, the thrust for a 4 in Dead End Tee at a pressure of 100 psi is 1620 lb.
  2. From Table 4 the safe bearing load of sand is 2000 lb/ft2.
  3. Divide the thrust by the safe bearing load of sand, or 1620 lb/2000 lb/ft2 for a thrust block bearing area of 0.81 ft2.
The thrust block bearing area for an NPS 4, Dead End Tee at a pressure of 150 psi in sand is 1.22 ft2.

The calculation is as follows:
  1. The thrust for an NPS 4, Dead End Tee, at a pressure of 150 psi was found in Example 2 to be 2430 lb.
  2. The soil type is sand and the safe bearing load of sand from Table 4 is 2000 lb/ft2.
  3. The required bearing area of the thrust block is determined by dividing the thrust by the safe bearing load or 2430 lb/2000 lb/ft2 for a thrust block bearing area of 1.22 ft2.
The thrust block bearing area for a DN 125, 90° Bend, at a pressure of 861 kPa in Soft Clay is 2.82 m2

The calculation is as follows:
  1. The thrust for a DN 125, 90° Bend at a pressure of 861 kPa was found in Example 4 to be 19,469 N.
  2. The soil condition is soft clay and the safe bearing load of soft clay from Table 4 is 48 kPa or 48,000 N/m2.
    Note: 1 kPa = 1 kN/m2 = 1000 N/m2
  3. The required block bearing area is determined by dividing the thrust by the safe bearing load or 19,469 N/48,000 N/ m2 for a thrust block bearing area of 0.4 m2.
Properly sized thrust blocks, either permanent or temporary, shall be installed at all required points before testing. When concrete thrust blocks are installed, wait at least 24 hours before pressure testing.
The entire system shall be purged before testing to eliminate all solvent cement vapors and air. The system shall not be pressurized until the joints have cured (set) at least as long as recommended by the manufacturer. If the manufacturers recommendation is not available the cure times in Table 5 shall apply. Systems with solvent cement joints shall be pressure tested filled with water or other fluid. CAUTION: Water Test Only.

TABLE 5
MINIMUM CURE TIME, IN HOURS (h)*
TEST PRESSURE FOR PIPE

(See Section 6.2)
  DN 15 TO 32
(NPS 1/2 TO 1-1/4)
DN 40 TO 80
(NPS 1-1/2 TO 3)
DN 80 TO 200
(NPS 3-1/2 TO 8)
DN 15
(NPS 1/2)
DN 32
(NPS 1-1/2)
DN 40
(NPS 1-1/2)
DN 80
(NPS 1-1/2)
DN 90
(NPS 3-1/2)
DN 200
(NPS 8)
TEMPERATURE RANGE DURING CURE PERIOD UP TO 1240 kPa
(180 PSI)
ABOVE 1240 TO 2549 kPa
(180 TO 370 psi)
UP TO 1240 kPa
(180 PSI)
ABOVE 1240 TO 2549 kPa
(180 TO 370 psi)
UP TO 1240 kPa
(180 PSI)
ABOVE 1240 TO 2549 kPa
(180 TO 370 psi)
60°F - 100°F
(16°C-38°C)
1 h 6 h 2 h 12 h 6 h 24 h
40°F-60°F
(4°C-16°C)
2 h 12 h 4 h 24 h 12 h 48 h
10°F-40°F
(-12°C+4°C)
8 h 48 h 16 h 96 h 48 h 8 days
*If gaps or loose fits are encountered in the system, double these cure times.
A label shall be fastened to the main electrical meter panel stating, "This structure has a nonmetallic water service".
The following sections of the 2021 Uniform Plumbing Code apply to ductile iron and PVC pressure building supply and exterior cold-water piping.

Chapter 3 General Regulations
309.0 Workmanship
312.0 Protection of Piping, Materials, and Structures
313.0 Hangers and Supports
314.0 Trenching, Excavation, and Backfill

Chapter 6 Water Supply and Distribution
604.0 Materials (water piping)
Table 604.1 Materials for Building Supply and Water
Distribution Piping and Fittings
605.4 Ductile Iron Pipe and Joints
605.12 PVC Plastic Pipe and Joints
605.16.2 Plastic Pipe to Other Materials
609.0 Installation, Testing, Unions, and Location

Abbreviations
IAPMO International Association of Plumbing and Mechanical Officials
UPC Uniform Plumbing Code published by IAPMO
AWWA American Water Works Association
CSA Canadian Standards Association

Applicable Standards.
ASME B16.4 Gray Iron Threaded Fittings Classes 125 and 250
ASTM D1785 Poly (Vinyl Chloride) (PVC) Plastic Pipe, Schedules 40, 80, and 120
ASTM D2241 Poly (Vinyl Chloride) (PVC) Pressure-Rated Pipe (SDR Series)
ASTM D2466 Poly (Vinyl Chloride) (PVC) Plastic Pipe Fittings, Schedule 40
ASTM D2467 Poly (Vinyl Chloride) (PVC) Plastic Pipe Fittings, Schedule 80
ASTM F1970 Special Engineered Fittings, Appurtenances or Valves for use in Poly (Vinyl Chloride) (PVC) or Chlorinated Poly (Vinyl Chloride) (CPVC) Systems
AWWA C110 Ductile Iron and Gray-Iron Fittings
AWWA C111 Rubber-Gasket Joints for Ductile-Iron Pressure Pipe and Fittings
AWWA C151 Ductile-Iron Pipe, Centrifugally Cast
AWWA C153 Ductile-Iron Compact Fitting
AWWA C900 Polyvinyl Chloride (PVC) Pressure Pipe and Fabricated Fittings, 4 in. through 12 in. (100 mm through 300 mm)
AWWA C904 Crosslinked Polyethylene (PEX) Pressure Tubing, 1/2 in. through 3 In. (13 mm through 76 mm), for Water Service
AWWA C907 Injection-Molded Polyvinyl Chloride (PVC) Pressure Fittings, 4 In, through 12 in (100 mm through 300 mm) for Water, Wastewater and Reclaimed Water Service
IAPMO/ ANSI UPC-1 Uniform Plumbing Code
The provisions contained in this appendix are not mandatory unless specifically adopted by a state agency, or referenced in the adopting ordinance.

The information contained in this appendix is not part of this American National Standard (ANS) and has not been processed in accordance with ANSI's requirements for an ANS. As such, this appendix may contain material that has not been subjected to public review or a consensus process. In addition, it does not contain requirements necessary for conformance to the standard.
The following Sections B414-18, B417-18, B421C-18, B422C-18, SR614-18, TR418-18, TR420-18, are excerpted in their entirety from the 2018 Handbook for the Installation of Ceramic, Glass, and Stone Tile Installations, with permission from the Tile Council of North America, Inc.
In addition to these, the TCNA Handbook, includes 200+ methods for tile and stone installation based on various installation requirements and application types, as well as product selection guides, field and installation requirements, and guidelines for wet areas. For a complete copy, visit www.TCNAtile.com.

NOTICE OF DISCLAIMER AND LIMITATION OF LIABILITY

This publication is provided as a guide, not a product, and all of the information it contains is provided 'as is' without warranty of any kind, whether express or implied. All implied warranties, including, without limitation, implied warranties of merchantability, fitness for a particular purpose, and non-infringement, are hereby expressly disclaimed.
Publisher has not performed any independent analysis in connection with any of the information contained herein, and expressly disclaims any obligation to obtain and include information other than that presented herein resulting from the handbook committee consensus process. This information does not purport to address safety issues or applicable regulatory requirements associated with its use. It is the responsibility of the user of this information to review any applicable codes and other regulations and any site specific conditions in connection with the use of this information. Publisher expressly makes no representations or warranties regarding use of this information and compliance with any applicable statute, rule or regulation.
The reader is expressly warned to consider and adopt all safety precautions appropriate for the activities herein and to avoid all potential hazards. Such precautions are generally not listed herein and are outside the scope of this document.
Under no circumstances will publisher be liable to any person or business entity for any damages, including without limitation any and all direct, indirect, special, incidental, consequential, or exemplary damages, resulting, in whole or in part, from any use of, reference to, or reliance upon this publication, even if advised of the possibility of such damages. The foregoing limitation of liability is a fundamental element of the use of this information and the information would not be offered by the publisher without such limitation.


Recommended Uses
  • For showers that do not have prefabricated receptors.
  • For areas where wall flatness is critical, such as when tiles with any edge longer than 15" are specified.
Environmental Exposure Classifications
  • Res1, 2, 3, 5; Com1, 2, 3, 5.
  • For Res4 and Com4, see SR614.
  • For installations that may be exposed to staining, specify tile and grout suitable for exposure. Consult product manufacturers; see also "Product Selection Guides."
  • For installations that may be exposed to mild chemical attack, specify epoxy grout and tile suitable for exposure.
    For greater resistance to chemical exposure, also specify an epoxy bonding material. Consult product manufacturers; see also "Product Selection Guides."
Limitations
  • Maximum mortar bed thickness (walls)—1" for metal studs, 11/2" for wood studs.
  • Maximum stud spacing 16" on center.
Membrane Options
  • A waterproof membrane (A 118.10) or vapor retarder membrane (A 108.02-3.8) must be specified for walls to prevent moisture intrusion and protect adjacent building materials. Specifier shall indicate if complete waterproofing of walls is required, including treatment at termination points.
  • If a waterproof membrane is applied over the mortar bed walls, membrane over framing members may not be required.
  • Check with membrane manufacturer for suitability for applicable conditions, as not all membranes are suitable for steam, high-temperature and/or chemical exposure, or exterior use.
  • When glass tile is used, consult glass tile manufacturer for membrane options and recommendations.
Requirements
  • Wood studs—dry and well-braced, minimum depth 31/2".
  • Metal studs—well-braced; 20 gauge (0.033") or heavier; minimum depth 31/2" for residential applications or 35/8" for commercial applications.
  • Mortar bed thickness—3/4" minimum to 1" maximum (metal studs) or 11/2" maximum (wood studs)
  • Membrane behind mortar bed, when used, must lap over shower pan membrane.
  • Slope shower pan membrane 1/4" per foot to weep holes in drain.
  • Turn shower pan membrane up walls a minimum of 3" above shower curb (6" above floor in showers without curbs).
  • Surround drain with pea gravel or other weep protection to prevent mortar from blocking weep holes.
Materials
  • Multiple options exist for membranes, mortars, grouts, and other materials and must be clearly specified to be included. If not specifically indicated, optional materials are not included and mortar/grout choice defaults to minimum performance specification indicated. Consider each system component and intended use to determine minimum requirements and to specify options.
  • Ceramic tile—ANSI A137.1.
  • Glass tile, when used—ANSI A137.2; see also "Glass Tile Selection and Installation Guide," and consult tile manufacturer for environmental exposure classification recommendations. Not all glass tiles are suitable.
  • Cementitious grout—ANSI A118.6 or better or ISO CG1 or better. When glass tile is used, specify grout designated by tile and grout manufacturers.
  • Epoxy grout, when used—ANSI A118.3 or ISO RG.
  • Cementitious bond coat—portland cement paste on a mortar bed that is still workable. For a cured mortar bed, follow recommendations below to select appropriate bonding mortar:
    1. When a waterproof membrane is not used—ANSI A118.1 or better or ISO C1 or better.
    2. When a waterproof membrane is used—ANSI A118.4 or better or ISO C2S1 or better unless ANSI A118.1 or ISO C1 is recommended by membrane manufacturer.
    3. When porcelain tile is used—ANSI A118.4 or better or ISO C2 or better.
    4. When glass tile is used, specify mortar designated by tile and mortar manufacturers. Bond coat color will impact the final appearance of translucent glass tile. Specifier shall confirm bond coat color is acceptable.
  • Epoxy bond coat, when used—ANSI A118.3 or ISO R1 or better.
    1. When glass tile is used, specify epoxy bond coat designated by tile and bond coat manufacturers. Bond coat color will impact the final appearance of translucent glass tile. Specifier shall confirm bond coat color is acceptable.
  • Vapor retarder membrane, when used—ANSI A108.02-3.8.
  • Waterproof membrane, when used—ANSI A118.10.
  • Mortar bed, metal lath, and cleavage membrane—ANSI A108.1A.
  • Flexible mildew-resistant sealant—ASTM C920.
  • Shower pan membrane—local building code.
  • Metal studs—ASTM C645.
Materials for Green/Sustainable Design
  • See "Green Building Standards and Green Product Selection Guide" and consult manufacturers and suppliers for product sustainability and contribution to green building design.
  • Consider specifying tile and installation materials that meet ANSI A138.1, the American National Standard Specifications for Sustainable Ceramic Tiles, Glass Tiles, and Tile Installation Materials.
Preparation by Other Trades
  • Wall framing shall meet the general framing requirements of ANSI A108.11-4.0—4.3.
  • Apply blocking between the studs to support the shower pan membrane.
Movement Joint (architect must specify type of joint and show location and details on drawings)
  • Movement joints—mandatory according to EJ171.
  • When glass tile is used, adhere to more frequent placement recommendations within the ranges listed in EJ171.
Installation Specifications
  • Shower pan membrane—ANSI A108.01-3.6.
  • Tile—ANSI A108.1A, .1B, or .1C. A108.1B required if waterproof membrane or epoxy bond coat to be used.
  • Glass tile—ANSI A108.14,.15, .16, or manufacturer's directions.
  • Cementitious grout—ANSI A108.10.
  • Epoxy mortar/grout—ANSI A108.6.
  • Waterproof membrane—ANSI A108.13.
  • Movement Joints—EJ171 and ASTM C1193.
Notes
  • Test shower pan membrane and drainage fitting for leaks before commencing tilework.
  • Materials adversely affected by moisture in areas immediately adjacent to showers, tubs, and roman tubs should be properly protected.
  • A sloped portland cement mortar fill or approved preformed slope may be used under shower pan membrane when subfloor is not sloped to drain.
  • All horizontal surfaces, for example shower seats, sills, curbs, etc., must slope towards drain or other surface sloped toward drain. Where present, waterproofing also must be sloped.
  • When glass tile is used, see "Glass Tile Selection and Installation Guide," and consult manufacturer for recommendations and requirements.
  • For curbless shower receptor, see B421C and B422C.
For the following standards listed, refer to the 2018 TCNA Handbook for Ceramic, Glass, and Stone Tile Installation.
  1. B441-18 Wood or Metal Studs Backer Board Mortar Bed Walls (One Coat Method) Mortar Bed Floor Ceramic Tile
  2. B415-18 Wood or Metal Studs Cement Backer Board or Fiber-Cement Backer Board Walls Mortar Bed Floor Ceramic Tile, Glass Tile
  3. B420-18 Wood or Metal Studs Coated Glass Mat Water-Resistant Gypsum Backer Board Walls Mortar Bed Floor Ceramic Tile, Glass Tile
  4. B426-18 Wood or Metal Studs Cementitious-Coated Extruded Foam Backer Board Walls Mortar Bed Floor Ceramic Tile, Glass Tile
  5. B431-18 Wood or Metal Studs Fiber-Reinforced Water-Resistant Gypsum Backer Board Walls Mortar Bed Floor Ceramic Tile, Glass Tile
  6. B421-18 Solid Backing Bonded Waterproof Membrane Ceramic Tile, Glass Tile
  7. B422-18 Solid Backing Bonded Waterproof Membrane Integrated Bonding Flange Ceramic Tile, Glass Tile
Note: This detail reflects both concrete and wood substrates. Specify one or the other.

Requirements
  • Waterproof membrane—slope membrane 1/4" per foot to weep holes in drain.
  • Wood framing, when used, should be pressure treated and designed to resist deflection and movement.
Preparation by Other Trades
  • Test tank, membrane, and drainage fittings for leaks before starting tilework.
Materials for Green/Sustainable Design
  • See "Green Building Standards and Green Product Selection Guide" and consult manufacturers and suppliers for product sustainability and contribution to green building design.
  • Consider specifying tile and installation materials that meet ANSI A138.1, the American National Standard Specifications for Sustainable Ceramic Tiles, Glass Tiles, and Tile Installation Materials.
Installation Methods
  • Attach metal lath only above water line.
  • Floor—follow F121.
  • Walls—follow W221.
Installation Specifications
  • Tile—ANSI A108.1 A.
  • Grout—ANSI A108.10.
  • Movement Joints—EJ171 and ASTM C1193.

Recommended Uses
  • For construction of a shower without a curb.
Environmental Exposure Classifications
  • Res1, 2, 3; Com1, 2
  • May be suitable for Com3, Res5, and Com5 as determined by membrane and backing material manufacturers.
  • For Res4 and Com4, see SR613 and SR614.
  • For installations that may be exposed to staining, specify tile and grout suitable for exposure. Consult product manufacturers; see also "Product Selection Guides."
  • For installations that may be exposed to mild chemical attack, specify epoxy grout and tile suitable for exposure. Consult product manufacturers; see also "Product Selection Guides."
Limitations
  • Facilitates construction of a curbless shower without adding floor height at restroom entryway, but does not inherently comply with Americans with Disabilities Act (ADA) Standards for Accessible Design. Follow ADA where ADA compliance is required or desired.
  • Refer to appropriate wall method for applicable limitations based on type of backing used—W201, W202E, W2021, W211, W221, W222, W231/W241, W243, W244C, W244E, W244F, W245, W246, and W247.
Requirements
  • When glass tile is used, consult glass tile manufacturer for tile suitability over non-absorptive surface.
  • Bonded waterproof membrane must be continuous, including at changes in plane. Follow membrane manufacturer's requirements for comers, seaming, and overlap.
  • Waterproof membrane inside shower area must extend to full height of tile assembly. Also, the floor and wall waterproofing must continue outside the immediate shower area one foot beyond the high point of the floor, but not beyond the tiled area. Additional waterproofing of floor and/or walls outside the shower area may be needed to effectively contain and evacuate shower water and splash water and to protect building materials. When additional waterproofing of floor and/or walls outside the shower area is desired or required, the building design professional must specify all areas to be waterproofed and indicate membrane termination points.
  • A secondary drain may be required outside the immediate shower area to facilitate evacuation of shower water and splash water that is not contained in the shower area due to curbless design. When required or desired, building design professional must specify type and location of secondary drain.
  • High point of the floor must be outside the shower area, i.e., beyond shower door or curtain, to facilitate evacuation of shower water and splash water that is not contained in the shower area due to curbless design. Location of the high point of the floor is especially critical when secondary drain is not included outside the shower area.
  • Surround drain with pea gravel or other weep protection to prevent mortar from blocking weep holes.
  • Refer to appropriate wall method for applicable requirements based on type of backing used.
  • Slope mortar bed 1/4" per foot toward drain and follow membrane manufacturer's instructions for connecting membrane to drain.
Materials
  • Multiple options exist for membranes, mortars, grouts, and other materials and must be clearly specified to be included. If not specifically indicated, optional materials are not included and mortar/grout choice defaults to minimum performance specification indicated. Consider each system component and intended use to determine minimum requirements and to specify options.
  • Ceramic tile—ANSI A137.1.
  • Glass tile, when used—ANSI A137.2; see also "Glass Tile Selection and Installation Guide," and consult tile manufacturer for environmental exposure classification recommendations. Not all glass tiles are suitable.
  • Cementitious grout—ANSI A118.6 or better or ISO CG1 or better. When glass tile is used, specify grout designated by tile and grout manufacturers.
  • Epoxy grout, when used—ANSI A118.3 or ISO RG.
  • Cementitious bond coat:
    1. ANSI A118.4 or better or ISO C2S1 or better unless ANSI A118.1 or ISO C1 is recommended by membrane manufacturer.
    2. When glass tile is used, specify mortar designated by tile and mortar manufacturers. Bond coat color will impact the final appearance of translucent glass tile. Specifier shall confirm bond coat color is acceptable.
  • Waterproof membrane—ANSI A118.10 and recommended by manufacturer of membrane for use over backing type in intended application.
  • Flexible mildew-resistant sealant—ASTM C920.
Materials for Green/Sustainable Design
  • See "Green Building Standards and Green Product Selection Guide" and consult manufacturers and suppliers for product sustainability and contribution to green building design.
  • Consider specifying tile and installation materials that meet ANSI A138.1, the American National Standard Specifications for Sustainable Ceramic Tiles, Glass Tiles, and Tile Installation Materials.
Preparation by Other Trades/Backer Board Installers
  • Depressed slab by others. Depressed area must extend beyond shower area to facilitate a finished floor installation that effectively evacuates shower water and splash water, which are often difficult to contain within a curbless shower.
  • Refer to appropriate wall method for applicable preparations by other trades and backer board installers.
  • Maximum allowable variation in the tile substrate—for tiles with all edges shorter than 15", maximum allowable variation is 1/4" in 10' from the required plane, with no more than 1/16" variation in 12" when measured from the high points in the surface. For tiles with at least one edge 15" in length, maximum allowable variation is 1/8" in 10' from the required plane, with no more than 1/16" variation in 24" when measured from the high points in the surface.
  • Center backer board end or edge joints on framing and stagger joints in adjacent rows so four comers do not come together within the same plane. Space panel ends and edges in accordance with manufacturer's recommendations.
Movement Joint (architect must specify type of joint and show location and details on drawings)
  • Movement joints—mandatory according to EJ171.
  • When glass tile is used, adhere to more frequent placement recommendations within the ranges listed in EJ171.
Installation Specifications
  • Waterproof membrane—ANSI A108.13.
  • Tile—ANSI A108.5.
  • Glass tile—manufacturer's directions.
  • Cementitious grout—ANSI A108.10.
  • Epoxy grout—ANSI A108.6.
  • Movement Joints—EJ171 and ASTM C1193.
Notes
  • Test shower pan membrane/waterproof membrane and drainage fitting for leaks before commencing tilework.
  • Materials adversely affected by moisture in areas immediately adjacent to showers, tubs, and roman tubs should be properly protected.
  • All horizontal surfaces, for example shower seats, sills, curbs, etc., must slope towards drain or other surface sloped toward drain. Where present, waterproofing also must be sloped.
  • When glass tile is used, see "Glass Tile Selection and Installation Guide," and consult manufacturer for recommendations and requirements.
  • Follow applicable plumbing and building codes.

Recommended Uses
  • For construction of a shower without a curb.
Environmental Exposure Classifications
  • Res1, 2, 3; Com1, 2
  • May be suitable for Com3, Res5, and Com5 as determined by membrane and backing material manufacturers.
  • For Res4 and Com4, see SR613 and SR614.
  • For installations that may be exposed to staining, specify tile and grout suitable for exposure. Consult product manufacturers; see also "Product Selection Guides."
  • For installations that may be exposed to mild chemical attack, specify epoxy grout and tile suitable for exposure. Consult product manufacturers; see also "Product Selection Guides."
Limitations
  • Facilitates construction of a curbless shower without adding floor height at restroom entryway, but does not inherently comply with Americans with Disabilities Act (ADA) Standards for Accessible Design. Follow ADA where ADA compliance is required or desired.
  • Refer to appropriate wall method for applicable limitations based on type of backing used—W201, W202E, W2021, W211, W221, W222, W231/W241, W243, W244C, W244E, W244F, W245, W246, and W247.
Requirements
  • When glass tile is used, consult glass tile manufacturer for tile suitability over non-absorptive surface.
  • Bonded waterproof membrane must be continuous, including at changes in plane. Follow membrane manufacturer's requirements for comers, seaming, and overlap.
  • Waterproof membrane inside shower area must extend to full height of tile assembly. Also, the floor and wall waterproofing must continue outside the immediate shower area one foot beyond the high point of the floor, but not beyond the tiled area. Additional waterproofing of floor and/or walls outside the shower area may be needed to effectively contain and evacuate shower water and splash water and to protect building materials. When additional waterproofing of floor and/or walls outside the shower area is desired or required, the building design professional must specify all areas to be waterproofed and indicate membrane termination points.
  • A secondary drain may be required outside the immediate shower area to facilitate evacuation of shower water and splash water that is not contained in the shower area due to curbless design. When required or desired, building design professional must specify type and location of secondary drain.
  • High point of the floor must be outside the shower area, i.e., beyond shower door or curtain, to facilitate evacuation of shower water and splash water that is not contained in the shower area due to curbless design. Location of the high point of the floor is especially critical when secondary drain is not included outside the shower area.
  • Refer to appropriate wall method for applicable requirements based on type of backing used.
  • Slope mortar bed 1/4" per foot toward drain and follow membrane and integrated bonding flange manufacturer's instructions for connecting membrane to integrated bonding flange.
Materials
  • Multiple options exist for membranes, mortars, grouts, and other materials and must be clearly specified to be included. If not specifically indicated, optional materials are not included and mortar/grout choice defaults to minimum performance specification indicated. Consider each system component and intended use to determine minimum requirements and to specify options.
  • Ceramic tile—ANSI A137.1.
  • Glass tile, when used—ANSI A137.2; see also "Glass Tile Selection and Installation Guide," and consult tile manufacturer for environmental exposure classification recommendations. Not all glass tiles are suitable.
  • Cementitious grout—ANSI A118.6 or better or ISO CG1 or better. When glass tile is used, specify grout designated by tile and grout manufacturers.
  • Epoxy grout, when used—ANSI A118.3 or ISO RG.
  • Cementitious bond coat:
    1. ANSI A118.4 or better or ISO C2S1 or better unless ANSI A118.1 or ISO C1 is recommended by membrane manufacturer.
    2. When glass tile is used, specify mortar designated by tile and mortar manufacturers. Bond coat color will impact the final appearance of translucent glass tile. Specifier shall confirm bond coat color is acceptable.
  • Waterproof membrane—ANSI A118.10 and recommended by manufacturer of membrane for use over backing type in intended application.
  • Flexible mildew-resistant sealant—ASTM C920.
Materials for Green/Sustainable Design
  • See "Green Building Standards and Green Product Selection Guide" and consult manufacturers and suppliers for product sustainability and contribution to green building design.
  • Consider specifying tile and installation materials that meet ANSI A138.1, the American National Standard Specifications for Sustainable Ceramic Tiles, Glass Tiles, and Tile Installation Materials.
Preparation by Other Trades/Backer Board Installers
  • Depressed slab by others. Depressed area must extend beyond shower area to facilitate a finished floor installation that effectively evacuates shower water and splash water, which are often difficult to contain within a curbless shower.
  • Refer to appropriate wall method for applicable preparations by other trades and backer board installers.
  • Maximum allowable variation in the tile substrate—for tiles with all edges shorter than 15", maximum allowable variation is 1/4 in 10' from the required plane, with no more than 1/16" variation in 12" when measured from the high points in the surface. For tiles with at least one edge 15" in length, maximum allowable variation is 1/8" in 10' from the required plane, with no more than 1/16" variation in 24" when measured from the high points in the surface.
  • Center backer board end or edge joints on framing and stagger joints in adjacent rows so four corners do not come together within the same plane. Space panel ends and edges in accordance with manufacturer's recommendations.
Movement Joint (architect must specify type of joint and show location and details on drawings)
  • Movement joints—mandatory according to EJ171.
  • When glass tile is used, adhere to more frequent placement recommendations within the ranges listed in EJ171.
Installation Specifications
  • Waterproof membrane—ANSI A108.13.
  • Tile—ANSI A108.5.
  • Glass tile—manufacturer's directions.
  • Cementitious grout—ANSI A108.10.
  • Epoxy grout—ANSI A108.6.
  • Movement Joints—EJ171 and ASTM C1193.
Notes
  • Test shower pan membrane/waterproof membrane and drainage fitting for leaks before commencing tilework.
  • Materials adversely affected by moisture in areas immediately adjacent to showers, tubs, and roman tubs should be properly protected.
  • All horizontal surfaces, for example shower seats, sills, curbs, etc., must slope towards drain or other surface sloped toward drain. Where present, waterproofing also must be sloped.
  • When glass tile is used, see "Glass Tile Selection and Installation Guide," and consult manufacturer for recommendations and requirements.
  • Follow applicable plumbing and building codes.



Recommended Uses
  • For steam showers and steam rooms framed with wood or metal studs. Specify mortar bed walls option when wall flatness is critical, such as when tiles with any edge longer than 15" are specified.
Environmental Exposure Classifications
  • Res4.
  • For installations that may be exposed to staining, specify tile and grout suitable for exposure. Consult product manufacturers; see also Notes and "Product Selection Guides."
Limitations
  • Duration of use as a steam shower or steam room as determined by membrane and cement backer board (when used) manufacturers; lower membrane water vapor permeance decreases water vapor transmission.
  • Maximum stud spacing 16" on center.
Requirements
  • Steam rooms are highly specialized applications. Design and installation are critical to avoid damage to adjoining materials from vapor migration. Design criteria must include consideration of necessary insulation and temperature and humidity differential.
  • Use a tile contractor knowledgeable in steam applications and experienced with the materials specified.
  • Bonded waterproof membrane (sheet, liquid, and trowel-on) must be continuous and must adequately limit vapor transmission into adjacent spaces and building materials, according to intended duration of use as a steam shower.
  • Steam showers designed for continuous use applications should specify a low perm waterproof membrane (a waterproof membrane meeting ANSI A118.10 and with a water vapor permeance rating of 0.5 perms or less when tested per ASTM E96 Procedure E, tested at 90% relative humidity). When a waterproof membrane with a water vapor permeance rating greater than 0.5 perms is specified, a vapor retarder behind the wall assembly is required, and vapor retarder must have a water vapor permeance rating of 0.1 perm or less when tested per ASTM E96 Procedure A, tested at 50% relative humidity. Consult waterproof membrane manufacturer for water vapor permeance rating and vapor retarder requirements.
  • Specifier shall indicate how waterproofing and vapor retarding is to be achieved, including details for membrane penetrations such as penetrations for plumbing, lighting fixtures, fasteners, etc. Specifier shall also indicate where and how to waterproof curbs and jambs and where membrane terminates. Area outside steam shower door is a wet area and should be treated accordingly.
  • Check with membrane manufacturer for suitability for applicable conditions, as not all membranes are suitable for steam, high temperature and/or chemical exposure.
  • Some waterproof membrane manufacturers require use of a vapor retarder membrane in addition to the waterproof membrane. Consult membrane manufacturer for requirements. When used, vapor retarder membrane must weather lap itself and lap into the shower pan membrane.
  • If vapor retarder membrane is required, integrated bonding flange cannot be used.
  • Follow waterproof membrane manufacturers' directions for interface between drain and membrane(s).
  • Design professional to specify adequate insulation on walls and ceilings to reduce condensation. Consult insulation manufacturer for application suitability.
  • Seal all membrane penetrations with appropriate sealant according to membrane manufacturer's requirements.
  • Specify slip joints at change in plane, such as where walls and ceiling meet.
  • Slope ceiling minimum 2" per foot to avoid condensate dripping onto occupants; sloping ceiling from center can minimize rundown on walls.
  • When mortar bed walls, studs must provide firm anchorage for metal lath.
  • When mortar bed walls, mortar bed wall thickness—3/4" minimum to 11/2" maximum.
  • When mortar bed walls, cut lath at all slip joints.
  • Slope shower pan membrane minimum 1/4" per foot to weep holes in drain.
  • Turn shower pan membrane up walls a minimum of 3" above shower curb (6" above floor in showers without curbs).
  • Surround drain with pea gravel or other weep protection to prevent mortar from blocking weep holes. (Does not apply if integrated bonding flange is used.)
  • Wood studs, when used—dry and well braced, minimum depth 31/2".
  • Metals studs, when used—well-braced; 20 gauge (0.033") or heavier; minimum depth 31/2" for residential applications or 35/8" for commercial applications.
Preparation by Backer Board Installers
  • Maximum allowable variation in the tile substrate—for tiles with all edges shorter than 15", maximum allowable variation is 1/4" in 10' from the required plane, with no more than 1/16" variation in 12" when measured from the high points in the surface. For tiles with at least one edge 15" in length, maximum allowable variation is 1/4" in 10' from the required plane, with no more than 1/16" variation in 24" when measured from the high points in the surface.
  • Horizontal joints—1/8" spacing filled solid and taped with latex-portland cement mortar and 2" alkali-resistant glass fiber mesh tape.
  • Vertical joints—fill any space and tape with latex-portland cement mortar and 2" alkali-resistant glass fiber mesh tape.
  • Corners—leave space between backer units. Tape joints using skim coat of latex-portland cement mortar, but do not fill.
  • Center backer board end or edge joints on framing and stagger joints in adjacent rows so four corners do not come together within the same plane. Space panel ends and edges in accordance with manufacturer's recommendations.
Materials
  • Multiple options exist for membranes, mortars, grouts, and other materials and must be clearly specified to be included. If not specifically indicated, optional materials are not included and mortar/grout choice defaults to minimum performance specification indicated. Consider each system component and intended use to determine minimum requirements and to specify options.
  • Ceramic tile—ANSI A137.1 and recommended by manufacturer for use in steam showers.
  • Cementitious grout—ANSI A118.6 or better or ISO CG1 or better.
  • Epoxy grout, when used—ANSI A118.3 or ISO RG.
  • Cementitious bond coat:
    1. ANSI A118.15 or better or ISO C2S1 or better, unless ANSI A118.1 or ISO C1 is recommended by membrane manufacturer.
  • Cement backer board, when used—ANSI A118.9 or ASTM C1325 (Type A).
  • Fasteners—noncorrosive and nonoxidizing.
  • Hot dipped fasteners meeting ASTM F2329-05 required in wet areas.
  • 2" alkali-resistant glass fiber mesh tape.
  • Waterproof membrane—ANSI A118.10 and recommended by membrane manufacturer for use in specific application. For continuous use applications, see Requirements for water vapor permeance.
  • Vapor retarder membrane, when used—recommended by manufacturer for use in specific application.
  • Metal studs, when used—ASTM C645.
  • Shower pan membrane—ANSI A118.10, ASTM D4068, or D4551 and meeting applicable building code.
  • Mortar bed and reinforcing—ANSI A108.1A.
  • Flexible mildew-resistant sealant—ASTM C920 and recommended by manufacturer for use in steam showers.
Materials for Green/Sustainable Design
  • See "Green Building Standards and Green Product Selection Guide" and consult manufacturers and suppliers for product sustainability and contribution to green building design.
  • Consider specifying tile and installation materials that meet ANSI A138.1, the American National Standard Specifications for Sustainable Ceramic Tiles, Glass Tiles, and Tile Installation Materials.
Preparation by Other Trades
  • Wall framing shall meet the general framing requirements of ANSI A108.11-4.0-4.3.
Movement Joint (architect must show type of joint and show location and details on drawings)
  • Movement joints—mandatory according to EJ171.
  • Slip joints at changes in plane, such as where walls and ceiling meet.
Installation Specifications
  • Shower pan membrane—ANSI A108.01-3.6.
  • Mortar bed and reinforcing—ANSI A108.1A, .1B, and .1C.
  • Tile—ANSI A108.5.
  • Cementitious grout—A108.10.
  • Epoxy grout—A108.6.
  • Waterproof membrane and slip joint—ANSI A108.13 and membrane manufacturer's slip joint directions.
  • Movement Joints—EJ171 and ASTM C1193.
Notes
  • Use of softened water in steam showers and steam rooms helps reduce grout and tile staining due to iron and/or hard water. Such stains may require harsh chemicals for removal. Select products suitable for water type and maintenance practices that will be used.
  • Standard grouts will need to be periodically maintained over the life of the steam shower.
  • Steam unit design must take into consideration the affect of Moisture Vapor Transmission (MVT) on opposite side of steam unit walls. MVT can cause efflorescence and can affect paints and other adhered finishes.
Recommended Uses
  • For use where old shower pan has failed.
Requirements
  • Remove existing shower receptor, shower pan, and wall tile, as required, to install new shower pan.
  • Replace any damaged wall and floor substrate materials.
  • New shower pan—slope 1/4" per foot to weep holes in drain.
  • New shower pan to turn up wall a minimum of 3" above curb (6" above floor in showers without curbs).
  • New wall membrane/flashing (ANSI A108.02-3.8) placed behind existing wall membrane, out over new shower pan, and fastened to studs.
  • Place continuous bead of sealant on existing wall mortar with new wall mortar brought up tight against it.
Materials for Green/Sustainable Design
  • See "Green Building Standards and Green Product Selection Guide" and consult manufacturers and suppliers for product sustainability and contribution to green building design.
  • Consider specifying tile and installation materials that meet ANSI A138.1, the American National Standard Specifications for Sustainable Ceramic Tiles, Glass Tiles, and Tile Installation Materials.
Notes
  • See B414 for complete specifications.
Recommended Uses
  • For use where old shower pan has failed.
Requirements
  • Remove existing shower receptor, shower pan, and wall tile, as required, to install new shower pan.
  • Replace any damaged wall and floor substrate materials.
  • New shower pan—slope 1/4" per foot to weep holes in drain.
  • New shower pan to turn up wall a minimum of 3" above curb (6" above floor in showers without curbs).
  • New wall membrane/flashing (ANSI A108.02-3.8) placed behind existing wall membrane, out over new shower pan, and fastened to studs.
  • Place continuous bead of sealant on existing wall substrate material with new wall substrate material brought up tight against it.
Materials for Green/Sustainable Design
  • See "Green Building Standards and Green Product Selection Guide" and consult manufacturers and suppliers for product sustainability and contribution to green building design.
  • Consider specifying tile and installation materials that meet ANSI A138.1, the American National Standard Specifications for Sustainable Ceramic Tiles, Glass Tiles, and Tile Installation Materials
Notes
  • See B415, B420, B426, or B431 for complete specifications based on wall backing type.