The Office of the State Fire Marshal's adoption of this chapter or individual sections is applicable to structures regulated by other state agencies pursuant to Section 1.11.0.
This chapter shall govern the materials,
design, and installation of storm water drainage systems.
Roofs, paved areas, yards, courts,
courtyards, vent shafts, light wells, or similar areas having
rainwater, shall be drained into a separate storm sewer system,
or into a combined sewer system where a separate storm
sewer system is not available, or to some other place of disposal
satisfactory to the Authority Having Jurisdiction. In the
case of one- and two-family dwellings, storm water shall be
permitted to be discharged on flat areas, such as streets or
lawns, so long as the storm water shall flow away from the
building and away from adjoining property, and shall not create a nuisance.
Upcodes Diagrams
Storm water shall not be drained into sewers
intended for sanitary drainage.
Pipe, tube, and fittings conveying rainwater shall be of such materials and design as to perform their intended function to the satisfaction of the Authority Having Jurisdiction. Conductors within a vent or shaft shall be of cast-iron, galvanized steel, wrought iron, copper, copper alloy, lead, Schedule 40 ABS DWV, Schedule 40 PVC DWV, stainless steel 304 or 316L [stainless steel 304 pipe and fittings shall not be installed underground and shall be kept not less than 6 inches (152 mm) aboveground], or other approved materials, and changes in direction shall be in accordance with the requirements of Section 706.0. ABS and PVC DWV piping installations shall be installed in accordance with applicable standards referenced in Table 1701.1 and the firestop protection requirements in the California Building Code. Except for individual single-family dwelling units, materials exposed within ducts or plenums shall have a flame-spread index of not more than 25 and a smoke-developed index of not more than 50, where tested in accordance with ASTM E84 or UL 723. These tests shall comply with all requirements of the standards to include the sample size, both for width and length. Plastic pipe shall not be tested filled with water.
[HCD 1 & HCD 2] ABS or PVC installations are limited to not more than two stories of areas of residential accommodation.
[OSHPD 1, 2, 3, 4 & 5] ABS and PVC installations are not allowed.
[HCD 1 & HCD 2] ABS or PVC installations are limited to not more than two stories of areas of residential accommodation.
[OSHPD 1, 2, 3, 4 & 5] ABS and PVC installations are not allowed.
Joints and connections
in copper and copper alloy pipe and tube shall
be installed in accordance with Section 705.3.
Conductors installed aboveground
in buildings shall comply with the applicable
standards referenced in Table 701.2 for aboveground
drain, waste, and vent pipe. Conductors installed aboveground
level shall be of seamless copper water tube, Type K, L, or M; Schedule 40 copper pipe or Schedule 40 copper
alloy pipe; Type DWV copper drainage tube; service
weight cast-iron soil pipe or hubless cast-iron soil pipe;
standard weight galvanized steel pipe; stainless steel 304
or 316L [stainless steel 304 pipe and fittings shall not be
installed underground and shall be kept not less than 6
inches (152 mm) aboveground], or Schedule 40 ABS or
Schedule 40 PVC plastic pipe.
[HCD 1] ABS or PVC installations are limited to not more than two stories of areas of residential accommodation.
[OSHPD 1, 2, 3, 4 & 5] ABS and PVC installations are not allowed.
Underground building storm drains shall comply with the
applicable standards referenced in Table 701.2 for underground drain, waste, and vent pipe.
Building storm
sewers shall comply with the applicable standards referenced
in Table 701.2 for building sewer pipe.
Subsoil drains shall be open
jointed, perforated, or both and constructed of materials
in conformance with Table 1101.4.6.
MATERIAL | REFERENCED STANDARD(S) |
---|---|
PE | ASTM F667 |
PVC | ASTM D2729 |
Vitrified Clay (Extra strength) | ASTM C4, ASTM C700 |
Expansion joints or
sleeves shall be provided where warranted by temperature
variations or physical conditions.
Subsoil drains shall be provided
around the perimeter of buildings having basements, cellars,
crawl spaces, or floors below grade. Such subsoil drains shall
be permitted to be positioned inside or outside of the footing,
shall be of perforated or open-jointed approved drain tile or
pipe, not less than 3 inches (80 mm) in diameter, and shall be
laid in gravel, slag, crushed rock, approved 3/4 of an inch (19.1 mm) crushed, recycled glass aggregate, or other approved porous material with not less than 4 inches (102 mm) surrounding the pipe. Filter media shall be provided for exterior subsoil piping.
Exception: [HCD 1 & HCD 2] Subsoil drains are mandatory only when required by the Authority Having Jurisdiction due to geological conditions.
Subsoil drains shall be piped to a
storm drain, to an approved water course, to the front
street curb or gutter, to an alley, or the discharge from the
subsoil drains shall be conveyed to the alley by a concrete
gutter. Where a continuously flowing spring or
groundwater is encountered, subsoil drains shall be piped
to a storm drain or an approved water course.
Where it is not possible to convey the
drainage by gravity, subsoil drains shall discharge to an
accessible sump provided with an approved automatic
electric pump. The sump shall be not less than 15 inches
(381 mm) in diameter, 18 inches (457 mm) in depth, and
provided with a fitted cover. The sump pump shall have
an adequate capacity to discharge water coming into the
sump as it accumulates to the required discharge point,
and the capacity of the pump shall be not less than 15
gallons per minute (gpm) (0.95 L/s). The discharge piping
from the sump pump shall be not less than 11/2 inches
(40 mm) in diameter and have a union or other approved
quick-disconnect assembly to make the pump accessible
for servicing.
For separate dwellings not
serving continuously flowing springs or groundwater, the
sump discharge pipe shall be permitted to discharge onto
a concrete splash block with a minimum length of 24
inches (610 mm). This pipe shall be within 4 inches (102
mm) of the splash block and positioned to direct the flow
parallel to the recessed line of the splash block.
Subsoil drains subject to
backflow where discharging into a storm drain shall be
provided with a backwater valve in the drain line so
located as to be accessible for inspection and maintenance.
Nothing in Section 1101.6 shall
prevent drains that serve either subsoil drains or
areaways of a detached building from discharging to a
properly graded open area, provided that:
- They do not serve continuously flowing springs or groundwater.
- The point of discharge is not less than 10 feet (3048 mm) from a property line.
- It is impracticable to discharge such drains to a storm drain, to an approved water course, to the front street curb or gutter, or to an alley.
Building subdrains located
below the public sewer level shall discharge into a sump or
receiving tank, the contents of which shall be automatically
lifted and discharged into the drainage system as required for building sumps.
Open subsurface space adjacent
to a building, serving as an entrance to the basement or cellar
of a building, shall be provided with a drain or drains. The
areaway drains shall be not less than 2 inches (50 mm) in
diameter for area ways at a maximum of 100 square feet (9.29 m2) in area, and shall be discharged in the manner provided
for subsoil drains not serving continuously flowing springs
or groundwater (see Section 1101.6.1). Areaways exceeding
100 square feet (9.29 m2) shall not drain into subsoil drains.
The drains for areaways exceeding 100 square feet (9.29 m2) shall be sized in accordance with Table 1103.2.
For SI units: 1 inch = 25 mm, 1 gallon per minute = 0.06 L/s, 1/8 inch per foot = 10.4 mm/h, 1 inch per hour = 25.4 mm/h, 1 square foot = 0.0929 m2
Notes:
SIZE OF PIPE | FLOW (1/8 inch per foot slope) |
MAXIMUM ALLOWABLE HORIZONTAL PROJECTED ROOF AREAS AT VARIOUS RAINFALL RATES (square feet) | |||||
inches | gpm | 1 (in/h) | 2 (in/h) | 3 (in/h) | 4 (in/h) | 5 (in/h) | 6 (in/h) |
3 | 34 | 3288 | 1644 | 1096 | 822 | 657 | 548 |
4 | 78 | 7520 | 3760 | 2506 | 1880 | 1504 | 1253 |
5 | 139 | 13360 | 6680 | 4453 | 3340 | 2672 | 2227 |
6 | 222 | 21400 | 10700 | 7133 | 5350 | 4280 | 3566 |
8 | 478 | 46000 | 23000 | 15330 | 11500 | 9200 | 7670 |
10 | 860 | 82800 | 41400 | 27600 | 20700 | 16580 | 13800 |
12 | 1384 | 133200 | 66600 | 44400 | 33300 | 26650 | 22200 |
15 | 2473 | 238000 | 119000 | 79333 | 59500 | 47600 | 39650 |
SIZE OF PIPE | FLOW (1/4 inch per foot slope) |
MAXIMUM ALLOWABLE HORIZONTAL PROJECTED ROOF AREAS AT VARIOUS RAINFALL RATES (square feet) | |||||
inches | gpm | 1 (in/h) | 2 (in/h) | 3 (in/h) | 4 (in/h) | 5 (in/h) | 6 (in/h) |
3 | 48 | 4640 | 2320 | 1546 | 1160 | 928 | 773 |
4 | 110 | 10600 | 5300 | 3533 | 2650 | 2120 | 1766 |
5 | 196 | 18880 | 9440 | 6293 | 4720 | 3776 | 3146 |
6 | 314 | 30200 | 15100 | 10066 | 7550 | 6040 | 5033 |
8 | 677 | 65200 | 32600 | 21733 | 16300 | 13040 | 10866 |
10 | 1214 | 116800 | 58400 | 38950 | 29200 | 23350 | 19450 |
12 | 1953 | 188000 | 94000 | 62600 | 47000 | 37600 | 31350 |
15 | 3491 | 336000 | 168000 | 112000 | 84000 | 67250 | 56000 |
SIZE OF PIPE | FLOW (1/2 inch per foot slope) |
MAXIMUM ALLOWABLE HORIZONTAL PROJECTED ROOF AREAS AT VARIOUS RAINFALL RATES (square feet) | |||||
inches | gpm | 1 (in/h) | 2 (in/h) | 3 (in/h) | 4 (in/h) | 5 (in/h) | 6 (in/h) |
3 | 68 | 6576 | 3288 | 2192 | 1644 | 1310 | 1096 |
4 | 156 | 15040 | 7520 | 5010 | 3760 | 3010 | 2500 |
5 | 278 | 26720 | 13360 | 8900 | 6680 | 5320 | 4450 |
6 | 445 | 42800 | 21400 | 14267 | 10700 | 8580 | 7140 |
8 | 956 | 92000 | 46000 | 30650 | 23000 | 18400 | 15320 |
10 | 1721 | 165600 | 82800 | 55200 | 41400 | 33150 | 27600 |
12 | 2768 | 266400 | 133200 | 88800 | 66600 | 53200 | 44400 |
15 | 4946 | 476000 | 238000 | 158700 | 119000 | 95200 | 79300 |
Notes:
Window areaways at a
maximum of 10 square feet (0.93 m2) in area shall be permitted
to discharge to the subsoil drains through a 2 inch (50
mm) diameter pipe. However, window areaways exceeding
l0 square feet (0.93 m2) in area shall be handled in the manner
provided for entrance areaways (see Section 1101.8).
Where the occupant creates surface
water drainage, the sumps, gratings, or floor drains shall be
piped to a storm drain or an approved water course.
Roof drainage shall comply with
Section 1101.12.1 and Section 1101.12.2.
Roof areas of a
building shall be drained by roof drains or gutters. The
location and sizing of drains and gutters shall be coordinated
with the structural design and pitch of the roof.
Unless otherwise required by the Authority Having Jurisdiction,
roof drains, gutters, vertical conductors or leaders,
and horizontal storm drains for primary drainage
shall be sized based on a storm of 60 minutes duration
and 100 year return period. Refer to Table D 101.1 (in
Appendix D) for 100 years, 60-minute storms at various
locations.
Secondary (emergency) roof drainage shall be provided by one of the methods specified in Section 1101.12.2.1 or Section 1101.12.2.2.
Secondary
roof drainage shall be provided by an open-sided
roof or scuppers where the roof perimeter
construction extends above the roof in such a manner
that water will be entrapped. An open-sided roof
or scuppers shall be sized to prevent the depth of
ponding water from exceeding that for which the
roof was designed as determined by Section
1101.12.1. Scupper openings shall be not less than 4
inches (102 mm) high and have a width equal to the
circumference of the roof drain required for the area
served, sized in accordance with Table 1103.1.
Secondary
roof drains shall be provided. The secondary roof
drains shall be located not less than 2 inches (51
mm) above the roof surface. The maximum height
of the roof drains shall be a height to prevent the
depth of ponding water from exceeding that for
which the roof was designed as determined by Section 1101.12.1. The secondary roof drains shall connect
to a piping system in accordance with Section
1101.12.2.2.1 or Section 1101.12.2.2.2.
The secondary roof drainage system shall be a
separate system of piping, independent of the
primary roof drainage system. The discharge
shall be above grade, in a location observable
by the building occupants or maintenance personnel.
Secondary roof drain systems shall be
sized in accordance with Section 1101.12.1
based on the rainfall rate for which the primary
system is sized.
The secondary
roof drains shall connect to the vertical
piping of the primary storm drainage conductor
downstream of the last horizontal offset located
below the roof. The primary storm drainage system
shall connect to the building storm water
that connects to an underground public storm
sewer. The combined secondary and primary
roof drain systems shall be sized in accordance
with Section 1103.0 based on double the rainfall
rate for the local area.
Cleanouts for building storm drains shall comply with the requirements of Section 719.0 of this code.
Rain leaders and conductors connected to a building storm
sewer shall have a cleanout installed at the base of the
outside leader or outside conductor before it connects to
the horizontal drain.
Rainwater sumps serving
"public use" occupancy buildings shall be provided with dual
pumps arranged to function alternately in the case of overload
or mechanical failure. Pumps rated 600 V or less shall
comply with UL 778 and shall be installed in accordance with
the manufacturer's installation instructions.
Leaders
and storm drains, where connected to a combined sewer, shall
be trapped. Floor and area drains connected to a storm drain
shall be trapped.
Exception: Traps shall not be required where roof drains, rain leaders, and other inlets are at locations permitted under Section 906.0, Vent Termination.
No trap shall be
required for leaders or conductors that are connected to
a sewer carrying storm water exclusively.
Traps, where installed for individual
conductors, shall be the same size as the horizontal
drain to which they are connected.
Individual storm-water traps shall be installed
on the stormwater drain branch serving each storm-water
inlet, or a single trap shall be installed in the main storm
drain just before its connection with the combined building
sewer. Such traps shall be provided with an accessible
cleanout on the outlet side of the trap.
Leaders or conductors shall not be used as soil, waste, or vent pipes nor shall soil, waste, or vent pipes be used as leaders or conductors.
The sanitary and storm drainage system of a
building shall be entirely separate, except where a combined
sewer is used, in which case the building storm
drain shall be connected in the same horizontal plane
through a single wye fitting to the combined building
sewer not less than 10 feet (3048 mm) downstream from
a soil stack.
Roof drains shall be constructed of
aluminum, cast-iron, copper alloy of not more than 15 percent
zinc, leaded nickel bronze, stainless steel, ABS, PVC,
polypropylene, polyethylene, or nylon and shall comply with
ASME A112.3.1 or ASME A112.6.4.
Roof drains shall have domed strainers.
Exception: Roof drain strainers for use on sun decks, parking
decks, and similar areas that are normally serviced and
maintained, shall be permitted to be of the flat surface type. Such roof drain strainers shall be level with the deck.
The connection between
the roof and roof drains that pass through the roof and into
the interior of the building shall be made watertight by the
use of proper flashing material.
Where lead flashing material
is used, it shall be not less than 4 pounds per square
foot (lb/ft2) (19 kg/m2).
Where copper flashing
material is used, it shall be not less than 12 ounces per
square foot (oz/ft2) (3.7 kg/m2).
Vertical conductors
and leaders shall be sized by the maximum projected
roof area and Table 1103.1.
For SI units: 1 inch = 25 mm, 1 gallon per minute = 0.06 L/s, 1 inch per hour = 25.4 mm/h, 1 square foot = 0.0929 m2
Notes:
SIZE OF DRAIN, LEADER, OR PIPE | FLOW | MAXIMUM ALLOWABLE HORIZONTAL PROJECTED ROOF AREAS AT VARIOUS RAINFALL RATES (square feet) |
|||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|
inches | gpm1 | 1 (in/h) | 2 (in/h) | 3 (in/h) | 4 (in/h) | 5 (in/h) | 6 (in/h) | 7 (in/h) | 8 (in/h) | 9 (in/h) | 10 (in/h) | 11 (in/h) | 12 (in/h) |
2 | 30 | 2880 | 1440 | 960 | 720 | 575 | 480 | 410 | 360 | 320 | 290 | 260 | 240 |
3 | 92 | 8800 | 4400 | 2930 | 2200 | 1760 | 1470 | 1260 | 1100 | 980 | 880 | 800 | 730 |
4 | 192 | 18400 | 9200 | 6130 | 4600 | 3680 | 3070 | 2630 | 2300 | 2045 | 1840 | 1675 | 1530 |
5 | 360 | 34600 | 17300 | 11530 | 8650 | 6920 | 5765 | 4945 | 4325 | 3845 | 3460 | 3145 | 2880 |
6 | 563 | 54000 | 27000 | 17995 | 13500 | 10800 | 9000 | 7715 | 6750 | 6000 | 5400 | 4910 | 4500 |
8 | 1208 | 116000 | 58000 | 38660 | 29000 | 23200 | 19315 | 16570 | 14500 | 12890 | 11600 | 10545 | 9600 |
Notes:
The size of building storm drains, or building storm sewers or their horizontal branches shall be based on the maximum projected roof or paved area to be handled and Table 1103.2.
The size of semi-circular gutters shall be based on the maximum projected roof area and Table 1103.3.
For SI units: 1 inch = 25 mm, 1/16 inch per foot = 5.2 mm/m, 1 inch per hour = 25.4 mm/h, 1 square foot = 0.0929 m2
DIAMETER OF GUTTER (1/16 inch per foot slope) |
MAXIMUM RAINFALL RATES BASED ON ROOF AREA (square feet) |
||||
inches | 2 (in/h) | 3 (in/h) | 4 (in/h) | 5 (in/h) | 6 (in/h) |
3 | 340 | 226 | 170 | 136 | 113 |
4 | 720 | 480 | 360 | 288 | 240 |
5 | 1250 | 834 | 625 | 500 | 416 |
6 | 1920 | 1280 | 960 | 768 | 640 |
7 | 2760 | 1840 | 1380 | 1100 | 918 |
8 | 3980 | 2655 | 1990 | 1590 | 1325 |
10 | 7200 | 4800 | 3600 | 2880 | 2400 |
DIAMETER OF GUTTER (1/8 inch per foot slope) |
MAXIMUM RAINFALL RATES BASED ON ROOF AREA (square feet) |
||||
inches | 2 (in/h) | 3 (in/h) | 4 (in/h) | 5 (in/h) | 6 (in/h) |
3 | 480 | 320 | 240 | 192 | 160 |
4 | 1020 | 681 | 510 | 408 | 340 |
5 | 1760 | 1172 | 880 | 704 | 587 |
6 | 2720 | 1815 | 1360 | 1085 | 905 |
7 | 3900 | 2600 | 1950 | 1560 | 1300 |
8 | 5600 | 3740 | 2800 | 2240 | 1870 |
10 | 10200 | 6800 | 5100 | 4080 | 3400 |
DIAMETER OF GUTTER (1/4 inch per foot slope) |
MAXIMUM RAINFALL RATES BASED ON ROOF AREA (square feet) |
||||
inches | 2 (in/h) | 3 (in/h) | 4 (in/h) | 5 (in/h) | 6 (in/h) |
3 | 680 | 454 | 340 | 272 | 226 |
4 | 1440 | 960 | 720 | 576 | 480 |
5 | 2500 | 1668 | 1250 | 1000 | 834 |
6 | 3840 | 2560 | 1920 | 1536 | 1280 |
7 | 5520 | 3680 | 2760 | 2205 | 1840 |
8 | 7960 | 5310 | 3980 | 3180 | 2655 |
10 | 14400 | 9600 | 7200 | 5750 | 4800 |
DIAMETER OF GUTTER (1/2 inch per foot slope) |
MAXIMUM RAINFALL RATES BASED ON ROOF AREA (square feet) |
||||
inches | 2 (in/h) | 3 (in/h) | 4 (in/h) | 5 (in/h) | 6 (in/h) |
3 | 960 | 640 | 480 | 384 | 320 |
4 | 2040 | 1360 | 1020 | 816 | 680 |
5 | 3540 | 2360 | 1770 | 1415 | 1180 |
6 | 5540 | 3695 | 2770 | 2220 | 1850 |
7 | 7800 | 5200 | 3900 | 3120 | 2600 |
8 | 11200 | 7460 | 5600 | 4480 | 3730 |
10 | 20000 | 13330 | 10000 | 8000 | 6660 |
Where vertical
walls project above a roof to permit storm water to drain
into the roof area below, the adjacent roof area shall be permitted to be computed from Table 1103.1 as follows:
- For one wall - add 50 percent of the wall area to the roof area figures.
- For two adjacent walls of equal height - add 35 percent of the total wall areas.
- For two adjacent walls of unequal height - add 35 percent of the total common height and add 50 percent of the remaining height of the highest wall.
- Two opposite walls of same height - add no additional area.
- Two opposite walls of differing heights - add 50 percent of the wall area above the top of the lower wall.
- Walls on three sides - add 50 percent of the area of the inner wall below the top of the lowest wall, plus an allowance for the area of the wall above the top of the lowest wall, in accordance with Section 1103.4(3) and Section 1103.4(5) above.
- Walls on four sides - no allowance for wall areas below the top of the lowest wall - add for areas above the top of the lowest wall in accordance with Section 1103.4(1), Section 1103.4(3), Section 1103.4(5), and Section 1103.4(6) above.
Where there is a continuous or semi-continuous
discharge into the building storm drain or building
storm sewer, as from a pump, ejector, air-conditioning plant,
or similar device, 1 gpm (0.06 L/s) of such discharge shall be computed as being equivalent to 24 square feet (2.2 m2) of roof area, based upon a rate of rainfall of 4 inches per hour (in/h) (102 mm/h).
Instead of sizing the storm drainage
system in accordance with Section 1103.0, the roof drainage
shall be permitted to be sized by controlled flow and storage
of the storm water on the roof, provided the following conditions are met:
For SI units: 1 inch = 25.4 mm
For SI units : 1 inch = 25.4 mm
- The water from a 25-year frequency storm shall not be stored on the roof exceeding 24 hours.
- During the storm, the water depth on the roof shall not exceed the depths specified in Table 1105.1(1).
- Not less than two drains shall be installed in roof areas of 10000 square feet (929 m2) or less, and not less than one additional drain shall be installed for each 10000 square feet (929 m2) of roof area exceeding 10000 square feet (929 m2).
- Each roof drain shall have a pre-calibrated, fixed (nonadjustable), and proportional weir (notched) in a standing water collar inside the strainer. No mechanical devices or valves shall be permitted.
- Pipe sizing shall be based on the pre-calibrated rate of flow (gpm) (L/s) of the pre-calibrated weir for the maximum allowable water depth, and Table 1103.1 and Table 1103.2.
- The height of stones or other granular material above the waterproofed surface shall not be considered in water depth measurement, and the roof surface in the vicinity of the drain shall not be recessed to create a reservoir.
- Roof design, where controlled-flow roof drainage is used, shall be such that the design roof live load is not less than 30 lb/ft2 (146 kg/m2) to provide a safety factor exceeding the 15 lb/ft2 (73 kg/m2) represented by the depth of water stored on the roof in accordance with Table 1105.1(1).
- Scuppers shall be provided in parapet walls. The distance of scupper bottoms above the roof level at the drains shall not exceed the maximum distances specified in Table 1105.1(2).
- Scupper openings shall be not less than 4 inches (102 mm) high and have a width equal to the circumference of the roof drain required for the area served, sized in accordance with Table 1103.1.
- Flashings shall extend above the top of the scuppers.
- At a wall or parapet, 45 degree (0.79 rad) cants shall be installed.
- Separate storm and sanitary drainage systems shall be provided within the building.
- Calculations for the roof drainage system shall be submitted along with the plans to the Authority Having Jurisdiction for approval.
ROOF RISE* (inches) | MAXIMUM WATER DEPTH AT DRAIN (inches) |
---|---|
Flat | 3 |
2 | 4 |
4 | 5 |
6 | 6 |
* Vertical measurement from the roof surface at the drain to the highest point of the roof surface served by the drain, ignoring a local depression immediately adjacent to the drain.
ROOF RISE* (inches) | ABOVE ROOF LEVEL AT DRAIN (inches) |
---|---|
Flat | 3 |
2 | 4 |
4 | 5 |
6 | 6 |
Drains on setback roofs shall be
permitted to be connected to the controlled-flow drainage systems provided:
- The setback is designed for storing water, or
- The square footage of the setback drainage area is converted as outlined in Section 1105.0 to gpm, and the storm-water pipe sizes in the controlled-flow system are based on the sum of the loads.
- The branch from each of the roof drains that are not provided with controlled flow shall be sized in accordance with Table 1103.1.
The design and sizing of a storm drainage
system shall be permitted to be determined by accepted engineering
practices. The system shall be designed by a registered
design professional and approved in accordance with
Section 301.5.
The design of a siphonic roof drainage system shall comply with ASPE 45.
Siphonic roof drains shall comply with ASME A112.6.9.
New building storm drainage
systems and parts of existing systems that have been altered, extended, or repaired shall be tested in accordance with Section 1107.2.1 or Section 1107.2.2 to disclose leaks and
defects.
Except for outside leaders and perforated or open-jointed
drain tile, the piping of storm drain systems shall be tested
upon completion of the rough piping installation by water or
air, except that plastic pipe shall not be tested with air, and
proved tight. The Authority Having Jurisdiction shall be permitted
to require the removal of cleanout plugs to ascertain
whether the pressure has reached parts of the system. One of
the following test methods shall be used in accordance with
Section 1107.2.1 through Section 1107.2.3.
After piping has been installed,
the water test shall be applied to the drainage system,
either to the entire system or sections. Where the test is
applied to the entire system, all openings in the piping
shall be tightly closed except for the highest opening, and
the system shall be filled with water to the point of overflow.
Where the system is tested in sections, each opening
shall be tightly plugged except for the highest
opening of the section under test, and each section shall
be filled with water, but no section shall be tested with
less than a 10 foot (3048 mm) head of water. In testing
successive sections, not less than the upper 10 feet (3048
mm) of the next preceding section shall be tested so that
no joint of pipe in the building except the uppermost 10
feet (3048 mm) of a roof drainage system, which shall
be filled with water to the flood level of the uppermost
roof drain, shall have been submitted to a test of less than 10 foot (3048 mm) head of water. The water shall be kept
in the system or the portion of the test for not less than 15
minutes before inspection starts; the system shall then be
tight.
The air test shall be made by attaching an air compressor testing apparatus to a suitable
opening after closing other inlets and outlets to the system,
forcing air into the system until there is a uniform
gauge pressure of 5 pounds-force per square inch (psi)
(34 kPa) or sufficient pressure to balance a column of
mercury 10 inches (34 kPa) in height. This pressure shall
be held without the introduction of additional air for not
less than 15 minutes.
Where circumstances exist that
make air and water tests described in Section 1107.2.1
and Section 1107.2.2 impractical, see Section 105.3.