CALIFORNIA PLUMBING CODE - MATRIX ADOPTION TABLE
APPENDIX I - INSTALLATION STANDARD FOR PEX TUBING SYSTEMS
FOR HOT- AND COLD-WATER DISTRIBUTION
(Matrix Adoption Tables are non-regulatory, intended only as an aid to the code user. See Chapter 1 for state agency authority and building applications.)
Adopting Agency
BSC
BSC-CG
SFM
HCD
DSA
OSHPD
BSCC
DPH
AGR
DWR
CA
CEC
SL
SLC
1
2
1-AC
AC
SS
SS/C
1
2
3
4
Adopt Entire Chapter
X
X
X
Adopt Entire Chapter as amended (amended sections listed below)
This state agency does not adopt sections identified with the following symbol: †
The Office of the State Fire Marshal's adoption of this chapter or individual sections is applicable to structures regulated by other state agencies pursuant to
Section 1.11.
"The information contained in this appendix is not part of this American National Standard (ANS) and has not been
processed in accordance with ANSI's requirements for an ANS. As such, this appendix may contain material that
has not been subjected to public review or a consensus process. In addition, it does not contain requirements
necessary for conformance to the standard."
The following IAPMO Installation Standard is included here for the convenience of the users of the Uniform
Plumbing Code. It is not considered as a part of the Uniform Plumbing Code unless formally adopted as such.
This Installation Standard is an independent, stand-alone document published by the International Association
of Plumbing and Mechanical Officials and is printed herein by the expressed written permission of IAPMO.
This Standard specifies requirements for the
installation of SDR 9 CTS crosslinked
polyethylene (PEX) tubing and fittings,
including cold-expansion, crimp, press, and
mechanical compression fittings, intended for
hot- and cold-water distribution systems
within buildings.
"shall" is used to express a requirement,
i.e., a provision that the user is obliged to
satisfy to comply with the Standard;
"should" is used to express a
recommendation, but not a requirement;
"may" is used to express an option or
something permissible within the scope of
the Standard; and
"can" is used to express a possibility or a
capability.
Notes accompanying sections of the Standard
do not specify requirements or alternative
requirements; their purpose is to separate
explanatory or informative material from the
text. Notes to tables and figures are considered
part of the table or figures and can be written as
requirements.
This Standard refers to the following
publications, and where such reference is
made, it shall be to the current edition of those
publications, including all amendments
published thereto.
ASTM F876
Standard Specification for Crosslinked Polyethylene (PEX) Tubing
ASTM F877
Standard Specification for Crosslinked Polyethylene (PEX) Hot- and Cold-Water Distribution Systems
ASTM F1807
Standard Specification for Metal Insert Fittings Utilizing a Copper Crimp Ring for SDR9 Cross-linked Polyethylene (PEX) Tubing and SDR9 Polyethylene of Raised Temperature (PE-RT) Tubing
ASTM F1960
Standard Specification for Cold Expansion Fittings with PEX Reinforcing Rings for Use with Cross-linked Polyethylene (PEX) Tubing
ASTM F2080
Standard Specification for Cold-Expansion Fittings With Metal Compression-Sleeves for Cross-Linked Polyethylene (PEX) Pipe
ASTM F2159
Standard Specification for Plastic Insert Fittings Utilizing a Copper Crimp Ring for SDR9 Cross-linked Polyethylene (PEX) Tubing and SDR9 Polyethylene of Raised with
Temperature (PE-RT) Tubing
ASTM F2657
Standard Test Method for Outdoor with
Weathering Exposure of Crosslinked Polyethylene (PEX) Tubing
AWWA C904
Cross-Linked Polyethylene (PEX) Pressure Tubing, 1/2 In. (12 mm) Through 3 In. (76 mm) for Water Service
Tools and tool accessories (e.g., tool heads)
used for the installation of PEX tubing systems
shall be in accordance with the manufacturer's
specifications and written instructions.
PEX tubing passing through drilled or notched
metal studs or metal joists, or hollow-shell
masonry walls shall be protected from abrasion
by elastomeric or plastic sleeves or grommets.
When receiving PEX tubing shipments, the
receiver shall inspect and inventory each
shipment, ensuring that there has been no loss
or damage. In addition:
At the time of unloading, the markings of
all tubing, fittings, and accessories shall
be verified to ensure that all items have
been manufactured in accordance with the
applicable product Standard and
appropriately certified.
An overall examination of the shipment
shall be made. If the shipment is intact,
ordinary inspection while unloading shall
be sufficient to ensure that the items have
arrived in good condition.
If the load has shifted, has broken
packaging, or shows evidence of rough
treatment, each item shall be carefully
inspected for damage.
The total quantities of each shipment
(e.g., tubing, gaskets, fittings, and
accessories) shall be checked against
shipping records.
Any damaged or missing items shall be
noted on the delivery slip. The carrier
shall be notified immediately and a claim
made in accordance with its instructions.
No damaged material shall be disposed
of. The carrier shall recommend the
procedure to follow.
Shortages and damaged materials are
normally not reshipped without request. If
replacement material is needed, it shall be
reordered from the manufacturer, the
distributor, or a manufacturer's
representative.
PEX tubing and fittings shall be stored
indoors and in its original packaging until the
time of installation. Appropriate precautions
to protect the tubing from damage, impact,
and punctures shall be taken.
Accumulative exposure time to UV radiation
during storage and installation shall not
exceed the UV exposure limits recommended
by the manufacturer or specified in ASTM
F876.
Note:ASTM F876 has four categories for
UV-resistance, ranging from untested to 6
months of continuous exposure, as listed in
the material designation code.
In general, petroleum- or solvent-based
chemicals (e.g., paints, greases, pesticides, or
sealants) shall not be allowed to come in
direct contact with PEX tubing or fittings.
Thermal expansion and contraction forces on
suspended horizontal runs of PEX tubing that
can experience a 22°C (40°F) or greater
change in temperature (operating temperature
compared to ambient temperature) shall be
controlled by a means of mitigating
temperature-induced stresses to other parts of
the water distribution system. Means for
controlling thermal expansion and contraction
include
supporting the tubing with continuous
runs of CTS support channels with
rigid anchor points installed every 20 m (65 ft); and
proper strapping (e.g., 27 kg (60 lb)
straps or equivalent) spaced 1 m (3
ft) and rated for the maximum
temperature and UV exposure of the
PEX tubing application.
Thermal expansion and contraction forces on
vertical runs of PEX tubing that pass through
more than one floor and can experience a
22°C (40°F) or greater change in temperature
(operating temperature compared to ambient
temperature) shall be controlled by installing
a riser clamp at the top of every other
floor; and
mid-story guides to maintain the
alignment of the vertical tubing.
Note:Installing riser clamps isolates
expansion and contraction to two-floor
intervals allowing the PEX tubing to naturally
compensate for the expansion and
contraction.
Adequate clearance shall be provided between
PEX tubing and the building structure (e.g.,
using bored holes and sleeves) to allow for
free longitudinal movement of the tubing.
The minimum length of expansion loops shall
be calculated using the equation in
Section 6.4.1.2; however, the distance LB
shall be divided into three sections as
illustrated in Figure 2, where
made of materials that provide rigidity to
the support system and utilize pipe
clamps designed for plastic tubing
capable of restraining the tubing; and
installed in accordance with Figures 1 or
2, as applicable (i.e., anchor distances and
size of arms and offsets).
Note:Anchors are typically installed every
20 m (65 ft). See Section 6.
PEX tubing systems manufactured in
accordance with the applicable standards
referenced in Section 2 are deemed
manufactured joints and may be installed in
concealed spaces without the need for access
panels.
Except for double-wall B-vents, which require
a 25 mm (1 in) clearance, the clearance
between gas appliancevents and PEX tubing
shall be at least 150 mm (6 in).
Except when the PEX tubing is protected with
fiberglass or closed-cell insulation or the
recessed light is IC-rated, the clearance
between recessed light fixtures and PEX
tubing shall be at least 300 mm (12 in).
When in direct view of the light source, the
clearance between fluorescent lighting and
PEX tubing shall be at least 1.5 m (5 ft). If the
minimum clearance cannot be achieved, the
PEX tubing shall be protected with a UV-blocking sleeve.
The free (unsupported) bending radius for
PEX tubing, measured at the outside of the
bend, shall be not less than six times the actual
outside diameter of the tubing, unless
otherwise specified by the PEX manufacturer.
Supportsshould be used to facilitate rigid
bends and to alleviate stress on PEX joints
when bends are needed in close proximity to
such joints.
Tighter bends may be used when the PEX
tubing is uniformly bent (supported) around a
curved bracket or other rigid fixture. In this
case, the minimum outside radius of the
supported bend shall be as specified by the
PEX manufacturer.
Manufacturer's installation instructions shall be
consulted prior to installation of PEX tubing in
fire resistive constructions. PEX tubing
penetrating a wall or floor-and-ceiling fire-rated
assembly shall include a means of passive fire
protection in accordance with the local codes.
The tubing manufacturer's pressure-loss data
should be referenced when using Appendix A
of IAPMO/ANSI UPC 1. In absence of such
data, Figures 3 and 4 shall be used.
FIGURE 3 PRESSURE LOSS OF PEX TUBING AT 16°C (60°F)
(See Section 10.6.2)
FIGURE 4 PRESSURE LOSS OF PEX TUBING AT 49°C (120°F)
(See Section 10.6.2)
Flow velocities through the water distribution
system, used for calculating flush tank and
flush valvefixture units depending on the
tubing sizes (see Table 1), shall not exceed
3.0 m/s (10 ft/s) for cold-water distribution
systems; and
2.4 m/s (8 ft/s) for hot-water distribution
systems.
Note:The flow velocities in Items (a) and (b)
account for the increased velocities through
the fittings.
be balanced to maintain adequate system
temperatures; and
have flow velocities that do not exceed
0.6 m/s (2 ft/s) (see Table 2); and
use only PEX tubing designated for hot,
chlorinated water recirculation systems
and rated for the maximum percentage of
time during which the system is intended
to be operated at elevated temperatures, in
accordance with ASTM F876.
TABLE 2
TUBING SIZES, FLOWS, AND FRICTION LOSSES FOR HOT-WATER RECIRCULATION SYSTEMS
(See Section 10.6.4)
Installation of PEX water distribution systems
may be tested with air when
expressly allowed in the written
instructions of the manufacturers of all
plastic pipe and fittings installed at the time
the PEX piping system is being tested; and
compressed air or other gas testing is not
prohibited by the authority having
jurisdiction.